Goodman GKS9 Gas-fired warm air furnace Installation Instructions
Below you will find brief information for GKS9. The GKS9 is a gas-fired warm air furnace designed for residential heating applications. It can also be used for non-industrial commercial applications like schools, offices, retail stores, and more. GKS9 is a dual-certified appliance, meaning it can be vented as a single pipe (non-direct vent) or dual pipe (direct vent), providing flexibility in installations. It features a hot surface igniter for efficient ignition and a condensate drain trap that helps manage condensation during operation.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
GKS9
G
AS
-F
IRED
W
ARM
A
IR
F
URNACE
I
NSTALLATION
I
NSTRUCTIONS
This furnace is shipped from the factory as a Dedicated Upflow.
A Blocked Drain Kit (part #0270K00012) is available and MUST BE USED if the furnace is installed Horizontal Left or Horizontal Right.
Installer: Affix all manuals adjacent to the unit.
(Type FSP CATEGORY IV Direct or Non Direct Vent Air Furnace)
These furnaces comply with requirements embodied in the American National Standard
/ National Standard of Canada ANSI
Z21.47·CSA-2.3 Gas Fired Central Furnaces.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.
IO-300N
2/2013
Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
©
2006-2008, 2010-2013 Goodman Manufacturing Company, L.P.
Table of Contents
I. Component Identification ............................................................................................................................................... 5
II. Safety considerations .................................................................................................................................................... 6
E
LECTROSTATIC
D
ISCHARGE
(ESD) P
RECAUTIONS
.................................................................................................................... 6
III. Product Application ...................................................................................................................................................... 6
IV. Location Requirements & Considerations .................................................................................................................. 7
G
ENERAL
......................................................................................................................................................................... 7
C
LEARANCES AND
A
CCESSIBILITY
.......................................................................................................................................... 8
F
URNACE
S
USPENSION
....................................................................................................................................................... 8
E
XISTING
F
URNACE
R
EMOVAL
............................................................................................................................................... 9
T
HERMOSTAT
L
OCATION
........................................................................................................................................................ 9
V. Combustion & Ventilation Air Requirements ............................................................................................................... 9
VI. Installation Positions ................................................................................................................................................... 11
VII. Horizontal Applications & Considerations ................................................................................................................ 11
G
ENERAL
....................................................................................................................................................................... 11
D
RAIN
T
RAP AND
L
INES
.................................................................................................................................................... 12
L
EVELING
....................................................................................................................................................................... 12
A
LTERNATE
V
ENT
/F
LUE
C
ONNECTION
.................................................................................................................................. 12
A
LTERNATE
E
LECTRICAL AND
G
AS
L
INE
C
ONNECTIONS
............................................................................................................ 12
D
RAIN
P
AN
..................................................................................................................................................................... 12
F
REEZE
P
ROTECTION
........................................................................................................................................................ 12
F
URNACE
S
USPENSION
..................................................................................................................................................... 12
VIII. Propane Gas /High Altitude Installations ............................................................................................................... 13
IX. Vent/Flue Pipe & Combustion Air Pipe ..................................................................................................................... 13
G
ENERAL
....................................................................................................................................................................... 13
D
UAL
C
ERTIFICATION
: N
ON
-D
IRECT
/D
IRECT
V
ENT
.................................................................................................................. 13
M
ATERIALS AND
J
OINING
M
ETHODS
..................................................................................................................................... 13
P
ROPER
V
ENT
/F
LUE AND
C
OMBUSTION
A
IR
P
IPING
P
RACTICES
............................................................................................... 14
T
ERMINATION
L
OCATIONS
................................................................................................................................................... 14
C
ANADIAN
V
ENTING
R
EQUIREMENTS
..................................................................................................................................... 14
S
TANDARD
F
URNACE
C
ONNECTIONS
.................................................................................................................................... 14
A
LTERNATE
F
URNACE
C
ONNECTIONS
.................................................................................................................................... 15
N
ON
-D
IRECT
V
ENT
(S
INGLE
P
IPE
) P
IPING
........................................................................................................................... 16
D
IRECT
V
ENT
(D
UAL
P
IPE
) P
IPING
..................................................................................................................................... 17
V
ENT
/I
NTAKE
T
ERMINATIONS
F
OR
I
NSTALLATION OF
M
ULTIPLE
D
IRECT
V
ENT
F
URNACES
................................................................ 18
C
ONCENTRIC
V
ENT
T
ERMINATION
........................................................................................................................................ 18
S
IDE
W
ALL
V
ENT
K
IT
...................................................................................................................................................... 18
X. Condensate Drain Lines & Drain Trap ........................................................................................................................ 18
G
ENERAL
....................................................................................................................................................................... 18
U
PRIGHT
I
NSTALLATIONS
.................................................................................................................................................... 19
H
ORIZONTAL
I
NSTALLATIONS
................................................................................................................................................ 22
XI. Electrical Connections ................................................................................................................................................ 23
W
IRING
H
ARNESS
............................................................................................................................................................ 23
115 V
OLT
L
INE
C
ONNECTIONS
........................................................................................................................................... 23
24 V
OLT
T
HERMOSTAT
W
IRING
........................................................................................................................................... 24
24 V
OLT
H
UMIDIFIER
........................................................................................................................................................ 24
XII. Gas Supply and Piping .............................................................................................................................................. 24
G
ENERAL
....................................................................................................................................................................... 24
G
AS
P
IPING
C
ONNECTIONS
................................................................................................................................................ 25
P
ROPANE
G
AS
T
ANKS AND
P
IPING
...................................................................................................................................... 26
XIII. Circulating Air & Filters ............................................................................................................................................ 27
D
UCTWORK
- A
IR
F
LOW
................................................................................................................................................... 27
C
HECKING
D
UCT
S
TATIC
................................................................................................................................................... 27
B
OTTOM
R
ETURN
A
IR
O
PENING
[U
PFLOW
M
ODELS
] .............................................................................................................. 28
F
ILTERS
- R
EAD
T
HIS
S
ECTION
B
EFORE
I
NSTALLING
T
HE
R
ETURN
A
IR
D
UCTWORK
..................................................................... 28
U
PRIGHT
I
NSTALLATIONS
.................................................................................................................................................... 28
H
ORIZONTAL
I
NSTALLATIONS
................................................................................................................................................ 29
XIV. Startup Procedure & Adjustment ............................................................................................................................. 29
H
EAT
A
NTICIPATOR
S
ETTING
............................................................................................................................................... 29
2
Table of Contents
D
RAIN
T
RAP
P
RIMING
....................................................................................................................................................... 29
F
URNACE OPERATION
........................................................................................................................................................ 29
G
AS
S
UPPLY
P
RESSURE
M
EASUREMENT
............................................................................................................................... 29
G
AS
M
ANIFOLD
P
RESSURE
M
EASUREMENT AND
A
DJUSTMENT
................................................................................................... 30
G
AS
I
NPUT
R
ATE
M
EASUREMENT
(N
ATURAL
G
AS
O
NLY
) ............................................................................................................ 31
T
EMPERATURE
R
ISE
.......................................................................................................................................................... 31
C
IRCULATOR
B
LOWER
S
PEEDS
........................................................................................................................................... 31
XV. Normal Sequence of Operation ................................................................................................................................ 32
P
OWER
U
P
..................................................................................................................................................................... 32
H
EATING
M
ODE
................................................................................................................................................................ 32
C
OOLING
M
ODE
.............................................................................................................................................................. 32
F
AN
O
NLY
M
ODE
............................................................................................................................................................. 32
XVI. Operational Checks .................................................................................................................................................. 32
B
URNER
F
LAME
............................................................................................................................................................... 32
XVII. Safety Circuit Description ....................................................................................................................................... 33
G
ENERAL
....................................................................................................................................................................... 33
I
NTEGRATED
C
ONTROL
M
ODULE
.......................................................................................................................................... 33
P
RIMARY
L
IMIT
................................................................................................................................................................ 33
A
UXILIARY
L
IMIT
.............................................................................................................................................................. 33
R
OLLOUT
L
IMIT
............................................................................................................................................................... 33
P
RESSURE
S
WITCHES
...................................................................................................................................................... 33
F
LAME
S
ENSOR
............................................................................................................................................................... 33
XVIII. Troubleshooting ...................................................................................................................................................... 33
E
LECTROSTATIC
D
ISCHARGE
(ESD) P
RECAUTIONS
.................................................................................................................. 33
D
IAGNOSTIC
C
HART
.......................................................................................................................................................... 33
R
ESETTING
F
ROM
L
OCKOUT
............................................................................................................................................... 33
XIX. Maintenance ............................................................................................................................................................. 34
A
NNUAL INSPECTION
......................................................................................................................................................... 34
F
ILTERS
......................................................................................................................................................................... 34
B
URNERS
....................................................................................................................................................................... 34
I
NDUCED
D
RAFT AND
C
IRCULATOR
B
LOWERS
........................................................................................................................ 34
C
ONDENSATE
T
RAP AND
D
RAIN
S
YSTEM
(Q
UALIFIED
S
ERVICER
O
NLY
) ....................................................................................... 34
F
LAME
S
ENSOR
(Q
UALIFIED
S
ERVICER
O
NLY
) ....................................................................................................................... 34
I
GNITER
(Q
UALIFIED
S
ERVICER
O
NLY
) ................................................................................................................................. 34
F
LUE
P
ASSAGES
(Q
UALIFIED
S
ERVICER
O
NLY
) ...................................................................................................................... 35
XX. Before Leaving an Installation ................................................................................................................................. 35
XXI. Repair & Replacement Parts ................................................................................................................................... 35
T
ROUBLESHOOTING
C
HART
................................................................................................................................................ 36
B
LOWER
P
ERFORMANCE
D
ATA
............................................................................................................................................ 38
GKS9 Wiring Diagram ...................................................................................................................................................... 39
S
PECIAL
I
NSTRUCTIONS FOR
P
RODUCTS IN THE
S
TATE OF
M
ASSACHUSETTS
................................................................................. 40
WARNING
G
OODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR
PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE
PROCEDURES
. I
F YOU INSTALL OR PERFORM SERVICE ON THIS UNIT
,
YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR
PROPERTY DAMAGE WHICH MAY RESULT
. M
ANY JURISDICTIONS
REQUIRE A LICENSE TO INSTALL OR SERVICE HEATING AND AIR
CONDITIONING EQUIPMENT
.
3
WARNING
I
F THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED
EXACTLY
,
A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY
DAMAGE
,
PERSONAL INJURY OR LOSS OF LIFE
.
- D
O NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
- WHAT TO DO IF YOU SMELL GAS:
* D
O NOT TRY TO LIGHT ANY APPLIANCE
.
* D
O NOT TOUCH ANY ELECTRICAL SWITCH
;
DO NOT USE
ANY PHONE IN YOUR BUILDING
.
* I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A
NEIGHBORS PHONE
. F
OLLOW THE GAS SUPPLIERS
INSTRUCTIONS
.
* I
F YOU CANNOT REACH YOUR GAS SUPPLIER
,
CALL THE
FIRE DEPARTMENT
.
- I
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER
,
SERVICE AGENCY OR THE GAS SUPPLIER
WARNING
S
HOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT
OFF
,
TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE
FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY
.
CARBON MONOXIDE POISONING HAZARD
Special Warning for Installation of Furnace or Air Handling Units in
Enclosed Areas such as Garages, Utility Rooms or Parking Areas
T
O
T
HE
I
NSTALLER
Before installing this unit, please read this manual thoroughly to familiarize yourself with specific items which must be adhered to, including but not limited to: unit maximum external static pressure, gas pressures, BTU input rating, proper electrical connections, circulating air temperature rise, minimum or maximum CFM, and motor speed connections.
T
RANSPORTATION
D
AMAGE
All units are securely packed in shipping containers tested according to International Safe Transit Association specifications. The carton must be checked upon arrival for external damage. If damage is found, a request for inspection by carrier’s agent must be made in writing immediately.
The furnace must be carefully inspected on arrival for damage and bolts or screws which may have come loose in transit. In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon as possible - preferably within five days.
4. File the claim with the following support documents within a nine month statute of limitations.
•
Original or certified copy of the Bill of Lading, or indemnity bond.
•
Original paid freight bill or indemnity in lieu thereof.
•
Original or certified copy of the invoice, showing trade and other discounts or reductions.
•
Copy of the inspection report issued by carrier ’s representative at the time damage is reported to carrier.
The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
Keep this literature in a safe place for future reference.
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
4
25
2
1
27
29
26
17
18
24
I. COMPONENT IDENTIFICATION
3
4
6
5
6
7
8
9
10
11
12
13
14
15
17
18
16
19
28
20
1 Gas Valve
2 Gas Line Entrance (Alternate)
3 Combustion Air Intake Connection / “Coupling”
4 Hot Surface Igniter
5 Burners
6 Rollout Limit
7 Flame Sensor
8 Flue Pipe Connection / “Coupling”
9 Flue Pipe (Internal)
10 Primary Limit
11 Pressure Switch
12 Gas Line Entrance
13 Rubber Elbow
14 Flue Pipe Connection (Alternate)
15 Induced Draft Blower
23
22
Upflow/Horizontal
21
16 Electrical Connection Inlets (Alternate)
17 Coil Front Cover Drain Port
18 Drain Line Penetrations
19 Blower Door Interlock Switch
20 24-Volt Thermostat Connections
21 Integrated Control Module
(with fuse and diagnostic LED)
22 Transformer (40 VA)
23 Circulator Blower
24 Auxiliary Limit
25 Gas Manifold
26 Junction Box
27 Coil Front Cover
28 Drain Trap
29 Electrical Connection Inlets
5
II. SAFETY CONSIDERATIONS
Please adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace.
Adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace. To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and application of this product.
This furnace is manufactured for use with natural gas. It may be field converted to operate on L.P. gas by using the appropriate L.P.
conversion kit listed in the PROPANE GAS/HIGH ALTITUDE INSTAL-
LATIONS section of this manual
Install this furnace only in a location and position as specified in
LOCATION REQUIREMENTS & CONSIDERATIONS section and IN-
STALLATION POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the furnace as specified in COMBUSTION & VENTILATION AIR REQUIREMENTS
section of this manual.
Combustion products must be discharged to the outdoors. Connect this furnace to an approved vent system only, as specified in
VENT/FLUE PIPE & COMBUSTION AIR PIPE section of this manual.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s intended temperature-rise range with a duct system which has external static pressure within the allowable range, as specified on the furnace rating plate and OPERATIONAL CHECKS section of these instructions.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed as specified in the LOCATION REQUIREMENTS AND CON-
SIDERATIONS section of this manual.
This furnace may be used as a construction site heater only if certain conditions are met. These conditions are listed in the PROD-
UCT APPLICATION section of this manual.
E
D
O NOT UTILIZE THE HEATING UNIT WITHOUT REASONABLE ROUTINE
INSPECTION
,
MAINTENANCE AND SUPERVISION
. I
F THE UNIT IS IN A
BUILDING THAT IS OR WILL BE VACANT
,
CARE SHOULD BE TAKEN TO
ROUTINELY INSPECT
,
MAINTAIN AND MONITOR THE UNIT
. I
N THE
EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING
TEMPERATURES AND WILL BE VACANT
,
DRAIN ALL WATER
-
BEARING
PIPES
,
PROPERLY WINTERIZE THE BUILDING
,
AND TURN OFF ALL
WATER SOURCES
. I
N THE EVENT THAT THE BUILDING IS EXPOSED TO
FREEZING TEMPERATURES AND IS VACANT
,
ANY HYDRONIC COIL
UNITS SHOULD ALSO BE DRAINED AND AN ALTERNATIVE HEAT
SOURCES UTILIZED
.
LECTROSTATIC
D
ISCHARGE
WARNING
(ESD) P
RECAUTIONS
NOTE: Discharge static electricity accumulated in the body before touching the unit. An electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and non-installed (ungrounded) furnaces.
1.
Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
WARNING
2.
Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’s hand during grounding will be discharged.
3.
Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.).
If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4.
Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
INSTALLATION
,
ADJUSTMENT
,
ALTERATION
,
SERVICE OR
MAINTENANCE
,
REFER TO THIS MANUAL
. F
OR ADDITIONAL
ASSISTANCE OR INFORMATION
,
CONSULT A QUALIFIED INSTALLER
,
SERVICE
T
O
DEATH
BE
AGENCY
AVOID
DUE
LOCATED
TO
COMPONENTS
TO
OR
FROM
THE
DAMAGE
PROTECT
GAS SUPPLIER
.
T
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS
WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE
KNOWN TO THE
S
TATE OF
C
ALIFORNIA TO CAUSE CANCER
,
BIRTH
DEFECTS OR OTHER REPRODUCTIVE HARM
.
HIGH VOLTAGE!
PROPERTY
ELECTRICAL
THE
WATER
.
,
WARNING
PERSONAL
SHOCK
,
THE
ELECTRICAL
INJURY
FURNACE
OR
MUST
III. PRODUCT APPLICATION
6
This furnace is primarily designed for residential home-heating applications. It is NOT designed or certified for use in mobile homes, trailers or recreational vehicles. This unit is NOT designed or certified for outdoor applications. The furnace must be installed indoors (i.e., attic space, crawl space, or garage area provided the garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial commercial applications:
Schools, Office buildings, Churches, Retail stores
Nursing homes, Hotels/motels, Common or office areas
In such applications , the furnace must be installed with the following stipulations:
• It must be installed per the installation instructions provided and per local and national codes.
• It must be installed indoors in a building constructed on site.
• It must be part of a ducted system and not used in a free air delivery application.
• It must not be used as a “make-up” air unit.
•
•
Dual certification means that the combustion air inlet pipe is optional and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace in which combustion air is taken from the installation area or from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace in which all combustion air supplied directly to the furnace burners through a special air intake system outlined in these instructions.
This furnace may be used as a construction site heater ONLY if the following conditions are met:
• The vent system is permanently installed per these installation instructions.
• A room thermostat is used to control the furnace. Fixed jumpers that provide continuous heating CANNOT be used.
•
•
It must be installed with two-pipe systems for combustion air, especially if VOC’s or other contaminants are present in the conditioned space.
All other warranty exclusions and restrictions apply This furnace is an ETL dual-certified appliance and is appropriate for use with natural or propane gas (NOTE: If using propane, a propane conversion kit is required).
•
Return air ducts are provided and sealed to the furnace.
A return air temperature range between 60ºF (16ºC) and
80ºF (27ºC) is maintained.
Air filters are installed in the system and maintained during construction, replaced as appropriate during construction, and upon completion of construction are replaced.
•
•
•
•
The input rate and temperature rise are set per the furnace rating plate.
100% outside air is provided for combustion air requirements during construction. Temporary ducting can be used.
NOTE: Do not connect the temporary duct directly to the furnace. The duct must be sized according to the instructions under Section V, Combustion and Ventilation
Air Requirements, Section 5.3.3.
The furnace heat exchanger, components, duct system, air filters and evaporator coils are thoroughly cleaned following final construction clean up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) are verified according to these installation instructions.
NOTE: The Commonwealth of Massachusetts requires that the following additional requirements must also be met:
•
•
•
P
FIRE
Gas furnaces must be installed by a licensed plumber or gas fitter.
A T-handle gas cock must be used.
If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring.
To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and application of this product.
OSSIBLE PROPERTY DAMAGE
,
WARNING
PERSONAL INJURY OR DEATH
,
EXPLOSION
,
SMOKE
,
SOOT
,
CONDENSATION
,
ELECTRICAL
SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER
DUE
INSTALLATION
,
REPAIR
,
OPERATION
,
OR MAINTENANCE OF THIS
PRODUCT
.
TO
T
O PREVENT
IV. LOCATION REQUIREMENTS & CONSIDERATIONS
G
ENERAL
PERSONAL INJURY
TO FIRE
,
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME
,
TRAILER OR RECREATIONAL VEHICLE
.
1 Batterymarch Park
Quincy, MA 02269
WARNING
,
PROPERTY
WARNING
DAMAGE
American National Standards Institute
1430 Broadway
New York, NY 10018
National Fire Protection Association
OR DEATH DUE
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installation and operation instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas Code
ANSI Z223.1, and/or CAN/CSA B149.1-05 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code ANSI Z223.1 can be obtained from any of the following:
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
A copy of the CAN/CSA B149.1-05 Installation Codes can also be obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of America.
T
O PREVENT POSSIBLE EQUIPMENT DAMAGE
,
PROPERTY DAMAGE
,
PERSONAL INJURY OR DEATH
,
THE FOLLOWING BULLET POINTS MUST
BE OBSERVED WHEN INSTALLING THE UNIT
.
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in Section V, Combus-
tion and Ventilation Air Requirements.
• Centrally locate the furnace with respect to the proposed or existing air distribution system.
• Ensure the temperature of the return air entering the furnace is between 55°F and 100°F when the furnace is heating.
• Provide provisions for venting combustion products outdoors through a proper venting system. Special consideration should be given to vent/flue pipe routing and combustion air intake pipe when applicable. Refer to Section IX, Vent/Flue Pipe and Combustion Air Pipe -
Termination Locations for appropriate termination
locations and to determine if the piping system from furnace to termination can be accomplished within the guidelines given. NOTE: The length of flue and/or combustion air piping can be a limiting factor in the location of the furnace.
7
•
•
•
•
•
•
•
•
Locate the furnace so condensate flows downwards to the drain. Do not locate the furnace or its condensate drainage system in any area subject to below freezing temperatures without proper freeze protection. Refer to
Section X, Condensate Drain Lines and Trap for further
details.
Ensure adequate combustion air is available for the furnace. Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon monoxide. Refer to Section V,
Combustion and Ventilation Air Requirements.
Set the furnace on a level floor to enable proper condensate drainage. If the floor becomes wet or damp at times, place the furnace above the floor on a concrete base sized approximately 1-1/2" larger than the base of the furnace. Refer to the Section VII, Horizontal
Applications and Considerations for leveling of horizontal
furnaces.
Ensure upflow or horizontal furnaces are not installed directly on carpeting, or any other combustible material.
The only combustible material allowed is wood.
Exposure to contaminated combustion air will result in safety and performance-related problems. Do not install the furnace where the combustion air is exposed to the following substances: chlorinated waxes or cleaners chlorine-based swimming pool chemicals water softening chemicals deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions (such as perchloroethylene) printing inks paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials
Seal off a non-direct vent furnace if it is installed near an area frequently contaminated by any of the above substances. This protects the non-direct vent furnace from airborne contaminants. To ensure that the enclosed non-direct vent furnace has an adequate supply of combustion air, vent from a nearby uncontaminated room or from outdoors. Refer to the Section V,
Combustion and Ventilation Air Requirements for details.
If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cooling unit. Premature heat exchanger failure will result if the cooling unit is placed ahead of the furnace.
For vertical (upflow or downflow) applications, the minimum cooling coil width shall not be less than furnace width minus 1”. Additionally, a coil installed above an upflow furnace or under a counterflow furnace may be the same width as the furnace or may be one size larger than the furnace. Example: a “C” width coil may be installed
with a “B” width furnace.
For upflow applications, the front of the coil and furnace must face the same direction.
If the furnace is installed in a residential garage, position the furnace so that the burners and ignition source are located not less than 18 inches (457 mm) above the floor.
Protect the furnace from physical damage by vehicles.
8
• If the furnace is installed horizontally, the furnace access doors must be vertical so that the burners fire horizontally into the heat exchanger. Do not install the unit with the access doors on the “up/top” or “down/bottom” side of the furnace.
C
LEARANCES AND
A
CCESSIBILITY
Installations must adhere to the clearances to combustible materials to which this furnace has been design certified. The minimum clearance information for this furnace is provided on the unit’s clearance label. These clearances must be permanently maintained. Clearances must also accommodate an installation’s gas, electrical, and drain trap and drain line connections. If the alternate vent/flue connections are used additional clearance must be provided to accommodate these connections. Refer to Section IX,
Vent Flue Pipe and Combustion Air Pipe for details. NOTE: In
addition to the required clearances to combustible materials, a minimum of 24 inches service clearance must be available in front of the unit.
TOP
SIDE
3/8" DIAMETER
THREADED ROD
(6 PLACES)
BOTTOM
Upflow Horizontal
A furnace installed in a confined space (i.e., a closet or utility room) must have two ventilation openings with a total minimum free area of 0.25 square inches per 1,000 BTU/hr of furnace input rating.
Refer to the Specification Sheet applicable to your model* for minimum clearances to combustible surfaces. One of the ventilation openings must be within 12 inches of the top; the other opening must be within 12 inches of the bottom of the confined space. In a typical construction, the clearance between the door and door frame is usually adequate to satisfy this ventilation requirement.
F
URNACE
S
USPENSION
If suspending the furnace from rafters or joists, use 3/8" threaded rod and 2”x2”x1/8” angle iron as shown below. The length of rod will depend on the application and the clearances necessary.
PROVIDE 8" MINMUM CLEARANCE BETWEEN
CENTER ROD AND FURNACE CABINET
TO ALLOW FOR CIRCULATOR BLOWER REMOVAL
ASSURE FURNACE IS LEVEL FROM
END TO END AND HAS A SLIGHT
FORWARD TILT WITH THE FRONT
OF THE FURNACE 0"-3/4"
BELOW THE BACK OF THE FURNACE
HOLD DOWN
NUTS
SUPPORT
NUTS
2"
X
2"
X
1/8" ANGLE IRON
(3 PLACES)
SIDE
POSITION AS CLOSE AS POSSIBLE
TO BLOWER DECK TO ALLOW FOR
CIRCULATOR BLOWER REMVOAL
Suspended Furnace
TILT OUTWARD TO ALLOW FOR
DOOR AND CIRCULATOR BLOWER
REMOVAL
E
XISTING
F
URNACE
R
EMOVAL
NOTE: When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the American
National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47·CSA-2.3 Section 1.23.1.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation: a. Seal any unused openings in the venting system; b. Inspect the venting system for proper size and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the CSA
B149.1-05 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition; c. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers; d. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously; e. Test for draft hood equipped spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle; f.
After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use; g. If improper venting is observed during any of the above tests, the common venting system must be corrected.
Corrections must be in accordance with the latest edition of the
National Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05 Installation Codes.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National
Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05 Installation
Codes.
T
HERMOSTAT
L
OCATION
The thermostat should be placed approximately five feet from the floor on a vibration-free, inside wall in an area having good air circulation. Do not install the thermostat where it may be influenced by any of the following:
•
Drafts, or dead spots behind doors, in corners, or under cabinets.
•
Hot or cold air from registers.
•
Radiant heat from the sun.
•
Light fixtures or other appliances.
•
Radiant heat from a fireplace.
•
Concealed hot or cold water pipes, or chimneys.
•
Unconditioned areas behind the thermostat, such as an outside wall.
DRAFTS OR DEAD SPOTS
-BEHIND DOORS
-IN CORNERS
-UNDER CABINETS
HOT
COLD
Thermostat Influences
Consult the instructions packaged with the thermostat for mounting instructions and further precautions.
V. COMBUSTION & VENTILATION AIR REQUIREMENTS
WARNING
T
O AVOID PROPERTY DAMAGE
,
PERSONAL INJURY OR DEATH
,
SUFFICIENT FRESH AIR FOR PROPER COMBUSTION AND VENTILATION
OF FLUE GASES MUST BE SUPPLIED
. M
OST HOMES REQUIRE OUTSIDE
AIR BE SUPPLIED INTO THE FURNACE AREA
.
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped in reducing heating/cooling costs but have created a problem supplying combustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances for air.
House depressurization can cause back drafting or improper combustion of gas-fired appliances, thereby exposing building occupants to gas combustion products that could include carbon monoxide.
1. Headaches-Nausea-Dizziness, Flu-Like Symptoms.
2. Excessive humidity-heavily frosted windows or a moist
“clammy” feeling in the home.
3. Smoke from a fireplace will not draw up the chimney.
4. Flue gases that will not draw up the appliance vent pipe.
If this furnace is to be installed in the same space with other gas appliances, such as a water heater, ensure there is an adequate supply of combustion and ventilation air for the other appliances.
Refer to the latest edition of the National Fuel Gas Code ANSI Z223.1
(Section 5.3), or CSA B149.1-05 Installation Codes (Sections 7.2,
7.3, or 7.4), or applicable provisions of the local building codes for determining the combustion air requirements for the appliances.
Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
The following information on air for combustion and ventilation is reproduced from the National Fuel Gas Code ANSI Z223.1 Section 5.3.
5.3.1 General:
(a) The provisions of 5.3 apply to gas utilization equipment installed in buildings and which require air for combustion, ventilation and dilution of flue gases from within the building. They do not apply to (1) direct vent equipment which is constructed and installed so that all air for combustion is obtained from the outside atmosphere and all flue gases are discharged to the outside atmosphere, or (2) enclosed furnaces which incorporate an integral total enclosure and use only outside air for combustion and dilution of flue gases.
9
(b) Equipment shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas, proper venting and the maintenance of ambient temperature at safe limits under normal conditions of use. Equipment shall be located so as not to interfere with proper circulation of air. When normal infiltration does not provide the necessary air, outside air shall be introduced.
(c) In addition to air needed for combustion, process air shall be provided as required for: cooling of equipment or material, controlling dew point, heating, drying, oxidation or dilution, safety exhaust, odor control, and air for compressors.
(d) In addition to air needed for combustion, air shall be supplied for ventilation, including all air required for comfort and proper working conditions for personnel.
(e) While all forms of building construction cannot be covered in detail, air for combustion, ventilation and dilution of flue gases for gas utilization equipment vented by natural draft normally may be obtained by application of one of the methods covered in 5.3.3 and
5.3.4.
(f) Air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air requirements.
5.3.2 Equipment Located in Unconfined Spaces:
In unconfined spaces (see definition below) in buildings, infiltration may be adequate to provide air for combustion ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in 5.3.3b or 5.3.4.
Space, Unconfined.
For purposes of this Code, a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, are considered a part of the unconfined space.
5.3.3 Equipment Located in Confined Spaces:
(a) All Air from Inside the Building: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 BTU per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
NOTE: Each opening must have a free area of not less than one square inch per 1000 BTU of the total input rating of all equipment in the enclosure, but not less than 100 square inches.
Chimney or Gas Vent
Furnace
Water
Heater
Equipment Located in Confined Spaces; All Air from Inside
Building. See 5.3.3-a.
(b) All Air from Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
1. When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.
Alternate air inlet
Chimney or Gas Vent
Furnace
Water
Heater
Ventilation louvers
(each end of attic)
NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment in the enclosure.
Outlet Air
Inlet Air
Opening
Opening
Ventilation louvers for unheated crawl space
Equipment Located in Confined Spaces; All Air from Outdoors—
Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated
Attic. See 5.3.3-b
2. When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per
4,000 BTU per hour of total input rating of all equipment in the enclosure.
10
Chimney or Gas Vent
Furnace
Water
Heater
Ventilation louvers
(each end of attic)
NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment in the enclosure.
Outlet Air
Inlet air duct
[ends 1 ft (300 mm) above floor]
Equipment Located in Confined Spaces; All Air from Outdoors
Through Ventilated Attic. See 5.3.3-b.
3. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per
2,000 BTU per hour of total input rating of all equipment in the enclosure.
Chimney or Gas Vent
5.3.4 Specially Engineered Installations:
The requirements of 5.3.3 shall not necessarily govern when special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combustion, ventilation, and dilution of flue gases.
5.3.5 Louvers and Grilles:
In calculating free area in 5.3.3, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than 1/4 inch mesh. If the area through a design of louver or grille is known, it should be used in calculating the size of opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will have 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
5.3.6 Special Conditions Created by Mechanical Exhausting or Fireplaces:
Operation of exhaust fans, ventilation systems, clothes dryers, or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment. Air from
Inside Building. See 5.3.3-a.
NOTE: The air duct openings must have a free area of not less than one square inch per
2000 BTU of the total input rating of all equipment in the enclosure*.
Furnace
Water
Heater
Outlet air duct
Inlet air duct
*If the appliance room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour of the total input rating of all appliances in the enclosure.
Equipment Located in Confined Spaces; All Air from Outdoors.
See 5.3.3-b.
4. When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall not be less than 3 inches.
VI. INSTALLATION POSITIONS
NOTE: This furnace is shipped from the factory as a Dedicated
Upflow. A “Blocked Drain Kit” (0270K00012) is available and MUST
BE USED if the furnace is installed Horizontal Left or Horizontal
Right.
This furnace may be installed in an upright position or horizontal on either the left or right side panel. Do not install this furnace on its back. For upright upflow furnaces, return air ductwork may be attached to the side panel(s) and/or basepan. For horizontal upflow furnaces, return air ductwork must be attached to the basepan.
NOTE: Ductwork must never be attached to the back of the furnace.
Contact your distributor for proper airflow requirements and number of required ductwork connections. Refer to “Recommended
Installation Positions” figure for appropriate installation positions, ductwork connections, and resulting airflow arrangements.
VII. HORIZONTAL APPLICATIONS & CONSIDERATIONS
NOTE: The single opening must have a free area of not less than one square inch per 3000 BTU of the total input rating of all equipment in the enclosure, but not less than the sum of the areas of all vent connectors in the confined space.
Chimney or Gas Vent
NOTE: This furnace is shipped from the factory as a Dedicated
Upflow. A “Blocked Drain Kit” is available and MUST BE USED if the furnace is installed Horizontal Left or Horizontal Right. Check the
Serial/ Rating Plate on the furnace for the Kit P/N.
Furnace
Water
Heater
Opening
Alternate
Opening
Location
G
ENERAL
Horizontal applications, in particular, may dictate many of the installation’s specifics such as airflow direction, ductwork connections, flue and combustion air pipe connections, etc. The basic application of this furnace as a horizontal furnace differs only slightly from an upright installation. When installing a furnace horizontally, additional consideration must be given to the following:
Equipment Located in Confined Spaces; All Air from Outdoors -
Single Air Opening. See 5.3.3-b.
5. When directly communicating with the outdoors, the single opening shall have a minimum free area of 1 square inch per 3,000
BTU per hour of total input rating of all equipment in the enclosure.
11
ALTERNATE VENT/FLUE
LOCATION
FURNACE MUST BE LEVEL
FROM END TO END
FURNACE MUST BE LEVEL
OR SLIGHTLY TILTED FORWARD
WITH THE DOORS 0" - 3/4"
BELOW THE BACK PANEL
4 3/4" MINIMUM
DRAIN TRAP
CLEARANCE
GAS LINE WITH
DRIP LEG (3" MINIMUM)
DRAIN PAN
DRAIN LINE WITH 1/4" PER FOOT
DOWNWARD SLOPE
FURNACE MUST BE SUPPORTED
AT BOTH ENDS AND MIDDLE
36" MINIMUM SERVICE
CLEARANCE REQUIRED
Horizontal Furnace
D
RAIN
T
RAP AND
L
INES
In horizontal applications the condensate drain trap is secured to the furnace side panel, suspending it below the furnace. A minimum clearance of 4 3/4 inches below the furnace must be provided for the drain trap. Additionally, the appropriate downward piping slope must be maintained from the drain trap to the drain location. Refer to Section X, Condensate Drain Trap and Lines for further details. If the drain trap and drain line will be exposed to temperatures near or below freezing, adequate measures must be taken to prevent condensate from freezing.
L
EVELING
Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower. For proper flue pipe drainage, the furnace must be level lengthwise from end to end. The furnace should also be level from back to front or have a slight tilt with the access doors downhill (approximately 3/4 inches) from the back panel. The slight tilt allows the heat exchanger condensate, generated in the recuperator coil, to flow forward to the recuperator coil front cover.
A
LTERNATE
V
ENT
/F
LUE
C
ONNECTION
In horizontal installations provisions for alternate flue piping are available for upflow furnaces with left discharge. This configuration allows the flue piping to be run vertically through the furnace.
Refer to the “Recommended Installation Positions” figure for further detail. The standard piping connections may also be used in these positions. Refer to Section IX, Vent/Flue Pipe and Combustion Air Pipe for details concerning the conversion to the alternate vent/flue connections.
When using the horizontal alternate vent configuration, you must use the RF000142 vent drain kit. See following illustration.
Recommended Installation Positions
NOTE: Alternate “vertical” piping connections can not be used when an upflow furnace is installed with supply air discharging to the right. In either case, use the standard flue and combustion air piping connections.
A
LTERNATE
E
LECTRICAL AND
G
AS
L
INE
C
ONNECTIONS
This furnace has provisions allowing for electrical and gas line connections through either side panel. In horizontal applications the connections can be made either through the “top” or “bottom” of the furnace.
D
RAIN
P
AN
A drain pan must be provided if the furnace is installed above a conditioned area. The drain pan must cover the entire area under the furnace (and air conditioning coil if applicable).
F
REEZE
P
ROTECTION
Refer to Section VII, Horizontal Applications and Conditions - Drain
Trap and Lines.
F
URNACE
S
USPENSION
If the furnace is installed in a crawl space it must be suspended from the floor joist or supported by a concrete pad. Never install the furnace on the ground or allow it to be exposed to water. Refer to
Section IV, Location Requirements and Considerations - Furnace
Suspension for further details.
12
VIII. PROPANE GAS /HIGH ALTITUDE INSTALLATIONS
Altitude Gas
Natural
Kit
None
WARNING
P
OSSIBLE PROPERTY DAMAGE
,
PERSONAL INJURY OR DEATH MAY
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED
. T
HE
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
FURNACE OPERATION
. A
LL CONVERSIONS MUST BE PERFORMED BY
A QUALIFIED INSTALLER OR SERVICE AGENCY
.
This furnace is shipped from the factory configured for natural gas at standard altitude. Propane gas installations require an orifice change to compensate for the energy content difference between natural and propane gas.
For furnaces being converted to LP gas, it is strongly recommended that a LPLP03 kit also be installed. The use of this kit will prevent the furnace from firing when the LP gas supply pressure is too low to support proper combustion.
High altitude installations may require both a pressure switch and an orifice change. These changes are necessary to compensate for the natural reduction in the density of both the gas fuel and the combustion air at higher altitude.
For installations above 7000 feet, please refer to your distributor for required kit(s).
Or ifice
M anifold
Pr e s s ur e
Pre s s ur e
Sw itch
#43 3.5" w .c.
A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensation takes place.
Because of the relatively low flue gas temperature and water condensation requirements, PVC pipe is used as venting material.
This furnace must not be connected to Type B, BW, or L vent or vent connector, and must not be vented into any portion of a factory built or masonry chimney except when used as a pathway for PVC as described later in this section. Never common vent this appliance with another appliance or use a vent which is used by a solid fuel appliance. Do not use commercially available “no hub connectors” other than those shipped with this product.
It is the responsibility of the installer to follow the manufacturers’ recommendations and to verify that all vent/flue piping and connectors are compatible with furnace flue products. Additionally, it is the responsibility of the installer to ensure that all piping and connections possess adequate structural integrity and support to prevent flue pipe separation, shifting, or sagging during furnace operation.
D
UAL
C
ERTIFICATION
: N
ON
-D
IRECT
/D
IRECT
V
ENT
This furnace is dual certified and may be installed as a non-direct vent (single pipe) or direct vent (dual pipe) appliance. A non-direct
vent installation requires only a vent/flue pipe, while a direct vent
installation requires both a vent/flue pipe and a combustion air intake pipe. Refer to the appropriate section for details concerning piping size, length, number of elbows, furnace connections, and terminations.
M
ATERIALS AND
J
OINING
M
ETHODS
0-7000 None
Propane
LPT-00*
1
LPT-03*
2
#55 10.0" w .c.
WARNING
1
Supports White-Rodgers 1-stage valve only
2
Supports both Honeyw ell and White-Rodgers 1-stage valves
NOTE: In Canada, gas fur nace s ar e ce rtifie d to 4500 fe e t.
Contact the distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified installer, or service agency.
G
ENERAL
IX. VENT/FLUE PIPE & COMBUSTION AIR PIPE
WARNING
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY
INJURY OR DEATH
. C
AREFULLY READ AND FOLLOW ALL
INSTRUCTIONS GIVEN IN THIS SECTION
.
WARNING
U
PON COMPLETION OF THE FURNACE INSTALLATION
,
CAREFULLY
INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF
THE FURNACE TO ASSURE IT IS PROPERLY SEALED
. L
EAKS IN THE
FLUE SYSTEM CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH
DUE TO EXPOSURE TO FLUE PRODUCTS
,
INCLUDING CARBON
MONOXIDE
.
T
O AVOID BODILY INJURY, FIRE OR EXPLOSION, SOLVENT CEMENTS MUST BE
KEPT AWAY FROM ALL IGNITION SOURCES (I.E., SPARKS, OPEN FLAMES, AND
EXCESSIVE HEAT) AS THEY ARE COMBUSTIBLE LIQUIDS.
A
VOID BREATHING
CEMENT VAPORS OR CONTACT WITH SKIN AND/OR EYES.
Two-three-inch nominal diameter PVC Schedule 40 pipe meeting
ASTM D1785, PVC primer meeting ASTM F656, and PVC solvent cement meeting ASTM D2564 specifications must be used. Fittings must be DWV type fittings meeting ASTM D2665 and ASTM
D3311. Carefully follow the manufacturer’s instructions for cutting, cleaning, and solvent cementing of PVC.
The use of Schedule 40 PVC or ABS cellular core (Foam Core) plastic pipe is also acceptable as a flue/vent and intake pipe material. PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used. Fittings must be DWV type fittings meeting ASTM D2665 and ASTM D3311. Carefully follow the manufactures instructions for cutting, cleaning and solvent cementing of PVC.
In addition to PVC and ABS pipe and fittings, Innoflue ® by
Centrotherm Eco Systems and PolyPro
®
by M&G Duravent are also approved vent and combustion air materials for installations in the
U.S.A. and Canada. Manufacturers Installation instructions for these products must be followed. These products have specific instructions for installing, joining and terminating. Do not mix materials or components of one manufacturer with materials or components of another manufacturer.
For Canadian installations; all PVC pipe, fittings and joining materials must be UL S636 listed.
13
As an alternative to PVC pipe, primer, solvent cement, and fittings,
ABS materials which are in compliance with the following specifications may be used. Two-three-inch ABS Schedule 40 pipe must meet ASTM D1527 and, if used in Canada, must be CSA listed.
Solvent cement for ABS to ABS joints must meet ASTM D2235 and, if used in Canada, must be CSA listed. The solvent cement for the
PVC to ABS transition joint must meet ASTM D3138. Fittings must be DWV type fittings meeting ASTM D2661 and ASTM D3311 and, if used in Canada, must be CSA listed. Carefully follow the pipe manufacturers’ instructions for cutting, cleaning, and solvent cementing PVC and/or ABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long radius (Long sweep 1/4 bend DWV) types conforming to ASTM
D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/
16” minimum from the plane of one opening to the centerline of the other opening for 2” diameter pipe, and 4 9/16” minimum for 3” pipe.
•
•
•
•
The vent termination of a direct vent application must terminate at least 12 inches from any opening through which flue gases may enter a building (door, window, or gravity air inlet).
The vent termination of vent pipe run vertically through a roof must terminate at least 12 inches above the roof line
(or the anticipated snow level) and be at least 12 inches from any vertical wall (including any anticipated snow build up).
A vent termination shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.
The combustion air intake termination of a direct vent application should not terminate in an area which is frequently dusty or dirty.
P
ROPER
V
ENT
/F
LUE AND
C
OMBUSTION
A
IR
P
IPING
P
RACTICES
Adhere to these instructions to ensure safe and proper furnace performance. The length, diameter, and number of elbows of the vent/flue pipe and combustion air pipe (when applicable) affects the performance of the furnace and must be carefully sized. All piping must be installed in accordance with local codes and these instructions.
Piping must be adequately secured and supported to prohibit sagging, joint separation, and/or detachment from the furnace. Horizontal runs of vent/flue piping must be supported every three to five feet and must maintain a 1/4 inch per foot downward slope, back towards the furnace, to properly return condensate to the furnace’s drain system. Allowances should be made for minor expansion and contraction due to temperature variations. For this reason, particular care must be taken to secure piping when a long run is followed by a short offset of less than 40 inches.
Precautions should be taken to prevent condensate from freezing inside the vent/flue pipe and/or at the vent/flue pipe termination. It is our recommendation that all vent/flue piping exposed to temperatures below 35°F for extended periods of time should be insulated with 1/2” thick closed cell foam. Also all vent/flue piping exposed outdoors in excess of the terminations shown in this manual (or in unheated areas) should be insulated with 1/2” thick closed cell foam. Inspect piping for leaks prior to installing insulation.
T
ERMINATION
L
OCATIONS
ENT
/F
Non-Direct Vent
&
Direct Vent
Vent/Flue Terminations
3' min.
<10'
Non-Direct Vent
Vent/Flue Termination
12"
Grade or Highest
Anticipated
Snow Level
Forced Air
Inlet
12" min.
12" min.
Direct Vent
Vent/Flue Termination
IPE
No Terminations
Above Walkway
Vent Termination Clearances
NOTE: In Canada, the Canadian Fuel Gas Code takes precedence over the preceding termination restrictions.
C
S
V
ANADIAN
TANDARD
LUE
V
F
P
ENTING
R
URNACE
EQUIREMENTS
C
ONNECTIONS
4' min.
12" min.
4' min.
Non-Direct Vent
Vent/Flue Termination
NOTES: Refer to Section IV, Location Requirements and
Considerations for combustion air contaminant restrictions.
The following bullets and diagram describe the restrictions concerning the appropriate location of vent/flue pipe and combustion air intake pipe (when applicable) terminations. Refer to Non-Di-
rect Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping
located in this section for specific details on termination construction.
• All terminations (flue and/or intake) must be located at least 12 inches above ground level or the anticipated snow level.
• Vent terminations (non-direct and direct vent) must terminate at least 3 feet above any forced air inlet located within 10 feet.
NOTE: This provision does not apply to the combustion air intake termination of a direct vent application.
• The vent termination of a non-direct vent application must terminate at least 4 feet below, 4 feet horizontally from, or
1 foot above any door, window, or gravity air inlet into any building.
14
In Canada, venting must conform to the requirements of the current CAN/CSA-B149.1-05 Installation Code. Use only CSA-listed,
ULC-S636 compliant two-three-inch diameter PVC or ABS pipe, solvent cement, and fittings throughout. The certified piping should be clearly marked with the ULC Std “S636” on the pipe and fittings.
Carefully follow the pipe manufacturers’ instructions for cutting, cleaning, and solvent cementing PVC and/or ABS.
The vent can be run through an existing unused chimney provided the space between the vent pipe and the chimney is insulated and closed with a weather-tight, corrosion-resistant flashing.
It is the responsibility of the installer to ensure that the piping connections to the furnace are secure, airtight, and adequately supported.
As shipped, attachment “couplings” for vent/flue and combustion air intake pipe connections are provided on the furnace’s top cover
(upflow). To use the standard connections, field supplied vent/flue pipe and combustion air intake pipe (when applicable) should be secured directly to the furnace at these locations.
Vent/flue pipe can be secured to the vent/flue coupling using the rubber coupling and worm gear hose clamps provided with this furnace (see “Standard Connections” figure). The rubber coupling
allows separation of the vent/flue pipe from the furnace during servicing. Combustion Air and Vent piping should be routed in a manner to avoid contact with refrigerant lines, metering devices, condensate drain lines, etc. If necessary, clearances may be increased by utilizing two 45 deg. Long-Sweep Elbows and creating an “S” joint to provide additional space at connection locations. This joint can be rotated on the fitting to establish maximum clearance between refrigerant lines, metering devices, and condensate drain lines, etc. This joint is the equivalent of one 90 deg. elbow when considering elbow count.
A
LTERNATE
F
URNACE
C
ONNECTIONS
If the standard locations are undesirable for a specific installation, alternate side panel locations are available for vent/flue pipe connections. These locations may be of particular benefit to upright upflow installations requiring additional access to an A coil or to horizontal installations desiring vent/flue piping run vertically from the side of the cabinet.
NOTE: Standard and alternate locations can be combined (i.e., an installation may use the standard combustion air intake location but use the alternate vent/flue location), if needed.
WARNING
V
E
N
T
E
DGES OF SHEET METAL HOLES MAY BE SHARP
. U
SE GLOVES AS A
PRECAUTION WHEN REMOVING HOLE PLUGS
.
45 DEGREE
LONG-SWEEP
ELBOWS
Increased Clearance Configuration
NOTE: Do not use other commercially available “no hub connectors” due to possible material conflicts. The vent/flue pipe can also be secured using a PVC or ABS elbow or coupling using the appropriate glue (see Section IX, Materials and Joining Methods.
A
LTERNATE
V
ENT
/F
LUE
L
OCATION
The alternate vent/flue location is the large hole directly in line with the induced draft blower outlet. To use the alternate vent/flue location refer to the following steps, the “Vent/Flue Pipe Cuts” figure, and the “Alternate Vent/Flue Location” figure.
1. Remove and save the four screws securing the vent/flue coupling to the furnace top panel.
2. Loosen the worm gear hose clamps on the rubber elbow and detach it from both the induced draft blower and the vent/flue pipe.
3. Remove the vent/flue pipe from the furnace.
4. Cut the vent/flue pipe 3.75 inches from the flanged end of the pipe. See Vent/Flue Pipe Cuts figure. The section of pipe attached to the coupling will reach through the side panel to the induced draft blower. Discard remaining pipe and elbows.
NOTE: For non-direct vent installations, a minimum of one 90° elbow should be installed on the combustion air intake coupling to guard against inadvertent blockage.
C
OMBUSTION
A
IR
P
IPE
D
IRECT
V
ENT
I
NSTALLATIONS
On upflow units secure the combustion air intake pipe directly to the air intake coupling. NOTE: Because of probable material conflicts, do not use other commercially available “no hub connectors”.
N
ON
-D
IRECT
V
ENT
I
NSTALLATIONS
A minimum of one 90° elbow should be installed on the combustion air intake “coupling” to guard against inadvertent blockage.
CO MBUS TION
AIR PIP E
(DIREC T VENT ON LY)
VE NT/F LUE
PIPE
90 PVC
ELB OW
(NON-DIRECT VENT)
O R
RUBBER
COUPLING
WITH WORM
GEAR CLAM PS
(NON-DIRECT VENT)
FLANGE
CUT HERE
Vent/Flue Pipe Cuts
3.75"
5. Remove plastic plug from alternate vent/flue location.
Relocate and install plug in standard vent/flue location (top cover).
6. Insert cut section of vent/flue pipe and coupling into alternate vent/flue location. Using a rubber coupling and worm gear hose clamps from the drain kit bag, attach the vent/flue pipe and coupling to the induced draft blower. Secure the coupling to the cabinet using the screws removed in step 1 or with field-supplied 3/8” #8 self drilling screws.
U PF LO W
STANDARD CONNECTIONS
15
WARNING
T
HE RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD
. W
HEN
THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE
CABINET
,
EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT
FIELD
-
SUPPLIED VENT
/
FLUE PIPING
,
AS DAMAGE CAN RESULT IN
LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO
FLUE GASES
,
INCLUDING CARBON MONOXIDE
.
7. For upright installations, externally mount the rubber elbow to the vent/flue coupling using a worm gear hose clamp.
Secure field supplied vent/flue piping to the rubber elbow using a worm gear hose clamp. NOTE: Use of the alternate vent/flue location for upright installations, requires the drain trap be installed on the same side of the unit as the flue pipe.
8. For horizontal installations, externally secure the fieldsupplied vent/flue pipe directly to the vent/flue coupling using a PVC or ABS coupling or elbow.
3
REMOVE
PIPE
1
REMOVE
4 SCREWS
UPFLOW
6
SECURE TO
ID BLOWER WITH
RUBBER COUPLING
AND HOSE
CLAMPS
5
REMOVE
AND RELOCATE
2
DETACH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
6
SECURE TO
CABINET WITH
SCREWS
Air - Standard Furnace Connections or Alternate Furnace Con-
nections for specific details. Refer to the following Non-Direct
Vent (Single Pipe) Piping - Vent/Flue Pipe Terminations for spe-
cific details on termination construction.
Although non-direct vent installations do not require a combustion air intake pipe, a minimum of one 90° elbow should be attached to the furnace’s combustion air intake if: an upright installation uses the standard intake location. This elbow will guard against inadvertent blockage of the air intake.
V
ENT
/F
LUE
P
IPE
L
ENGTHS AND
D
IAMETERS
Refer to the following table for applicable length, elbows, and pipe diameter for construction of the vent/flue pipe system of a non-direct vent installation. In addition to the vent/flue pipe, a single 90° elbow should be secured to the combustion air intake to prevent inadvertent blockage. The tee used in the vent/flue termination must be included when determining the number of elbows in the piping system.
Direct Vent (2 - Pipe) and Non-Direct Vent (1 - Pipe)
6
Maximum Allowable Length of Vent/Flue Pipe
& Combustion Air Pipe(ft)
(1) (2)
Unit Input
(Btu)
Pipe
Size
(4)
(in.)
0 1
Number of Elbows
(3) (5)
2 3 4 5 6 7
45,000
70,000
90,000
90,000
115,000
115,000
2 or
2 1/2
2 or
2 1/2
2 or
2 1/2
3
2 or
2 1/2
3
201 196 191 186 181 176 171 166
140 135 130 125 120 115 110 105
20
15
15
10
10
5
112 105 98 91
Not Applicable
122 115 108 101 94
Not Applicable
84
87
77
80
70
73
63
UPFLOW/HORIZONTAL
Alternate Vent/Flue Location
N
ON
-D
IRECT
V
ENT
(S
INGLE
P
IPE
) P
IPING
Non-direct vent installations require only a vent/flue pipe. The
vent pipe can be run horizontally with an exit through the side of the building or run vertically with an exit through the roof of the building. The vent can also be run through an existing unused chimney; however, it must extend a minimum of 12 inches above the top of the chimney. The space between the vent pipe and the chimney must be closed with a weather-tight, corrosion-resistant flashing. For details concerning connection of the vent/flue pipe to the furnace, refer to Section IX, Vent/Flue Pipe and Combustion
1) Maximum allowable limits listed on individual lengths for inlet and flue and NOT a combination.
2) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee.
3) Tee used in the vent/flue termination must be included when determining the number of elbows in the piping system.
4) 2 1/2” or 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows should be considered equivalent to one 90 deg. elbow.
6) One 90° elbow should be secured to the combustion air intake connection.
V
ENT
/F
LUE
P
IPE
T
ERMINATIONS
NOTE: If either a 90 degree or 45 degree elbow is used for termination, it must be pointed downward.
The vent/flue pipe may terminate vertically, as through a roof, or horizontally, as through an outside wall.
Vertical vent/flue pipe terminations should be as shown in the following figure. Refer to Section IX, Vent/Flue Pipe and Com-
bustion Air Pipe - Termination Locations for details concerning
location restrictions. The penetration of the vent through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent.
Horizontal vent/flue pipe terminations should be as shown in the following figure. Refer to Section IX, Vent/Flue Pipe and Combus-
tion Air Pipe - Termination Locations for details concerning loca-
tion restrictions. A 2 3/8” diameter wall penetration is required for
16
2” diameter pipe. A 3” diameter hole is required for a 2 1/2” pipe and a 3 1/2” diameter hole is required for 3” diameter pipe. To secure the pipe passing through the wall and prohibit damage to piping connections, a coupling should be installed on either side of the wall and solvent cemented to a length of pipe connecting the two couplings. The length of pipe should be the wall thickness plus the depth of the socket fittings to be installed on the inside and outside of the wall. The wall penetration should be sealed with silicone caulking material.
In a basement installation, the vent/flue pipe can be run between joist spaces. If the vent pipe must go below a joist and then up into the last joist space to penetrate the header, two 45° elbows should be used to reach the header rather than two 90° elbows.
NOTE: Terminate both pipes in the same pressure zone (same side of roof, no major obstacles between pipes, etc.).
TEE (OPTIONAL)
COMBUSTION AIR INTAKE
(OPTIONAL)
*Not required for single pipe installation
RO
OF
LIN
E
INTAKE
SCREEN
OPTIONAL
12” MIN TO ROOF OR HIGHEST
ANTICIPATED SNOW LEVEL
12” MIN
HEIGHT DIFFERENCE
BETWEEN
INTAKE AND VENT
96
” M
AX
. -
3”
M
IN
.
D
IRECT
V
ENT
(D
UAL
P
IPE
) P
IPING
Direct vent installations require both a combustion air intake and a
vent/flue pipe. The pipes may be run horizontally and exit through the side of the building or run vertically and exit through the roof of the building. The pipes may be run through an existing unused chimney; however, they must extend a minimum of 12 inches above the top of the chimney. The space between the pipes and the chimney must be closed with a weather tight, corrosion resistant flashing. Both the combustion air intake and a vent/flue pipe terminations must be in the same atmospheric pressure zone.
Refer to Section IX, Vent/Flue and Combustion Air Pipe - Termina-
tion Locations or Concentric Vent Termination for specific details
on termination construction. For details concerning connection of pipes to the furnace, refer to the Section IX, Vent/Flue Pipe and
Combustion Pipe - Standard Furnace Connections or Alternate
Furnace Connections.
V
ENT
/F
LUE AND
C
OMBUSTION
A
IR
P
IPE
L
ENGTHS AND
D
IAMETERS
Refer to the following table for applicable length, elbows, and pipe diameter for construction of the vent/flue and combustion air intake pipe systems of a direct vent (dual pipe) installation. The number of elbows tabulated represents the number of elbows and/or tees in each (Vent/Flue & Combustion Air Intake) pipe. Elbows and/or tees used in the terminations must be included when determining the number of elbows in the piping systems.
If the combustion air intake pipe is to be installed above a finished ceiling or other area where dripping of condensate will be objectionable, insulation of the combustion air pipe may be required.
Use 1/2” thick closed cell foam insulation such as Armaflex or
Insultube where required.
STRAIGHT
ELBOWS
_____________________________________
V
ENT
/F
LUE AND
C
OMBUSTION
A
IR
P
IPE
T
ERMINATIONS
The vent/flue and combustion air pipes may terminate vertically, as through a roof, or horizontally, as through an outside wall.
Vertical pipe terminations should be as shown in the following figure. Refer to Section IX, Vent/Flue Pipe and Combustion Pipe -
Termination Locations for details concerning location restrictions.
The penetrations through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent
12" MIN.
VENT/FLUE TEE (OPTIONAL) or
90° ELBOW TURNED
DOWN
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
Horizontal terminations should be as shown in the following figure. Refer to Section IX, Vent/Flue Pipe and Combustion Pipe -
Termination Location for location restrictions. A 2 3/8” diameter
wall penetration is required for 2” diameter pipe. A 3” diameter hole is required for a 2 1/2” pipe and a 3 1/2” diameter hole is required for 3” diameter pipe. To secure the pipe passing through the wall and prohibit damage to piping connections, a coupling should be installed on either side of the wall and solvent cemented to a pipe connecting the two couplings. The pipe length should be the wall thickness plus the depth of the socket fittings to be installed on the inside and outside of the wall. The wall penetration should be sealed with silicone caulking material.
Horizontal Termination (Single Pipe)
Above Highest Anticipated Snow Level
17
10”- 24”
6” MAX
3” - 24”
4” MIN
12” MIN SEPARATION
3” MIN
90º OR 45°
ELBOW
SCREEN
(OPTIONAL)
OPTIONAL
INTAKE
SCREENS
12" MIN. TO GRADE OR
HIGHEST ANTICIPATED
SNOW LEVEL
12” MIN TO GRADE OR HIGHEST
ANTICIPATED SNOW LEVEL
Standard Horizontal Terminations (Dual Pipe)
Vent & Combustion Air Intake Measurements for Standard Horizontal Terminations (Dual Pipe)
Center to center = 10” min / 24” max.
Vertical separation: 0” - 24”
Vent termination from wall = 8” min / 12” max.
Combustion air intake from wall = 6” max.
Vent and intake clearance to ground or anticipated snow level = 12” min.
____________________________________
90°
ELBOWS
Termination of Multiple Direct Vent Furnaces
C
ONCENTRIC
V
ENT
T
ERMINATION
Refer to the directions provided with the Concentric Vent Kit (DCVK) for installation specifications.
S
IDE
W
ALL
V
ENT
K
IT
This kit is to be used with 2” or 3” direct vent systems. The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located side-by-side or with one pipe above the other. This kit is NOT intended for use with single pipe
(indirect vent) installations.
Refer to the directions furnished with the Side Wall Vent Kit (p/n
0170K00000S) for installation specifications.
AIR
INTAKE
SCREEN
(OPTIONAL)
3”-24” BETWEEN PIPES
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
Combustion Air Intake may also be snorkeled to obtain 12” min ground clearance.
Alternate Vent Termination Above Anticipated Snow Level
(Dual Pipe)
V
ENT
/I
NTAKE
T
ERMINATIONS
F
OR
I
NSTALLATION OF
M
ULTIPLE
D
IRECT
V
ENT
F
URNACES
If more than one direct vent furnace is to be installed vertically through a common roof top, maintain the same minimum clearances between the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake terminations of a single unit.
If more than one direct vent furnace is to be installed horizontally through a common side wall, maintain the clearances as in the following figure. Always terminate all exhaust vent outlets at the same elevation and always terminate all air intakes at the same elevation.
G
ENERAL
X. CONDENSATE DRAIN LINES & DRAIN TRAP
A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensation takes place.
The condensate which is generated must be piped to an appropriate drain location.
In upright installations, the furnace’s drain hoses may exit either the right or left side of the furnace. NOTE: If the alternate vent/flue outlet is utilized in an upright installation, the drain trap and drain connections must be located on the same side as the alternate vent/flue outlet.
In horizontal installations, the drain hoses will exit through the bottom (down side) of the unit with the drain trap suspended beneath the furnace. The field-supplied drain system must be in accordance with all local codes and the instructions in the following sections.
Follow the bullets listed below when installing the drain system.
Refer to the following sections for specific details concerning furnace drain trap installation and drain hose hook ups.
• The drain trap supplied with the furnace must be used.
•
•
•
The drain line between furnace and drain location must maintain a 1/4 inch per foot downward slope toward the drain.
Do not trap the drain line in any other location than at the drain trap supplied with the furnace.
If the drain line is routed through an area which may see temperatures near or below freezing, precautions must be taken to prevent condensate from freezing within the drain line.
18
• If an air conditioning coil is installed with the furnace, a common drain may be used. An open tee must be installed in the drain line, near the cooling coil, to relieve positive air pressure from the coil’s plenum.
This is necessary to prohibit any interference with the function of the furnace’s drain trap.
U
PRIGHT
I
NSTALLATIONS
In an upright installation drain hoses are connected to drain ports on the rubber elbow and the recuperator coil front cover. The drain lines are then routed through the right or left side panel and into the drain trap secured to the outside of the cabinet.
NOTE: Refer to Section X, Condensate Drain Lines and Drain Trap
- Alternate Vent/Flue Hose Connections for upright installations
using an alternate vent/flue outlet.
S
TANDARD
R
IGHT OR
L
EFT
S
IDE
D
RAIN
H
OSE
C
ONNECTIONS
Upright installations using the standard vent/flue outlet require drain hoses to be connected as follows. The following quantity of hoses, tubes, and hose clamps are provided with the unit.
HOSE A
QTY: 1
HOSE B
QTY: 1
DRAIN TRAP
QTY: 1
TUBE 1
QTY: 1
GREEN
HOSE CLAMPS
QTY: 3
RED
HOSE CLAMP
QTY: 1
SILVER
HOSE CLAMP
QTY: 1
Hose and Tube Identification
TUBE 2
QTY: 2
1. Remove the rubber plug/cap from the front cover drain port
(right or left side, depending on the intended drain trap mounting).
2. Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear side panel grommet hole.
FRONT COVER
DRAIN PORT
RED HOSE
CLAMP
HOSE
A GREEN
HOSE
CLAMPS
(3 PLACES)
RIGHT SIDE
PANEL
RUBBER
ELBOW
RUBBER ELBOW
DRAIN PORT
SILVER HOSE CLAMP
TUBE 1
HOSE
B
SIDE PANEL
GROMMET
HOLES
TUBE(S) 2
DRAIN
TRAP
LEFT
SIDE PANEL
FRONT COVER
DRAIN PORT
RED HOSE
CLAMP
HOSE A
SIDE PANEL
DRAIN
HOLES
TUBE(S) 2
DRAIN
TRAP
HOSE B
RUBBER
ELBOW
RUBBER
ELBOW
DRAIN PORT
SILVER HOSE
CLAMP
TUBE 1
GREEN HOSE
CLAMPS
(3 PLACES)
Upright “Standard” Connections - Left Side
19
NOTE: For left side drainage, grommets will have to be relocated to left side panel.
3. Cut and remove 1/4 inch from the end of the drain port on the rubber elbow.
4. Insert Tube 1 into rubber elbow drain port and secure with silver hose clamp. Angle tube outward toward front of furnace.
5. Right side drains
Cut 17 3/4 inches from the long end (end opposite the bend) of Hose B. Save the part with the bend and discard the 17 3/4 inch piece that was cut. Secure the remaining hose to Tube 1 with a green hose clamp. Route the other end of Hose B to front right side panel grommet hole.
Left side drains
Cut “X” inches from the long end of Hose B and discard.
Refer to table for appropriate length to cut. Secure remaining hose to Tube 1 with a green hose clamp. Route other end of Hose B to front left side panel grommet hole.
Cabinet Width
(inches)
Models
(kBTU_Tons)
"X" Length to Cut From Long
End of Hose B
17 1/2
21
24 1/2
045_30
070_30
070_40
090_40
090_50
115_50
7 inches
3 1/2 inches
None
6. Insert short end of each Tube 2 through side panel grommet holes. Secure tubes to Hose A and Hose B with green hose clamps. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.
For details concerning mounting of the drain trap, refer to Section
X, Condensate Drain Lines and Drain Trap - Upright Drain Trap
Mounting.
A
LTERNATE
V
ENT
/F
LUE
D
RAIN
H
OSE
C
ONNECTIONS
Upright installations using the alternate vent/flue outlet will require
“right-side only” drain hoses to be connected as follows. Refer to
Section IX, Vent/Flue Pipe and Combustion Air Pipe for details on
alternate vent/flue pipe connection.
Upright “Alternate” Connections - Right Side Only
20
1. Remove the rubber plug/cap from the front cover right-side drain port. Save for use in step 3.
2. Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear right side panel grommet hole.
3. Remove grommet from front right-side panel drain hole.
Seal hole in grommet with large end of plug. Reinstall grommet and plug into side panel drain hole.
4. Cut 1/4 inch from the end of the drain port on the externally mounted rubber elbow. Discard cut portion.
5. Insert Tube 1 into rubber elbow drain port and secure with a silver hose clamp. Angle tube outward toward front of furnace.
6. Cut 17 7/8 inches from the long end of Hose B and discard.
7. Secure remaining end of Hose B to exposed end of Tube 1 with a green hose clamp. Route hose toward right side panel grommet holes.
8. Insert short end of one Tube 2 through rear right side panel grommet drain hole. Secure tube to Hose A with a green hose clamp.
9. Insert short end of remaining Tube 2 into Hose B from rubber elbow and secure with green hose clamp. Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or binding.
For details concerning mounting of the drain trap, refer to the following section.
U
PRIGHT
D
RAIN
T
RAP
M
OUNTING
(L
EFT OR
R
IGHT
S
IDE
P
ANEL
)
1. Insert drain tubes into drain trap and position the drain trap against the side panel. NOTE: Drain tubes must reach the bottom of the drain trap.
2. Secure drain trap to side panel at the mounting holes
(dimples or crosshairs) located below the grommet drain holes.
FRONT COVER
DRAIN PORT
HOSE A
RED HOSE
CLAMP
HOSE B
SIDE PANEL
GROMMET
HOLES
FRONT
COVER
PRESSURE
TAP
RUBBER
ELBOW
TUBES 2
DRAIN TRAP
GREEN
HOSE
CLAMP
(3 PLACES)
TUBE 1
RIGHT
SIDE
PANEL
RUBBER ELBOW
DRAIN PORT
SILVER HOSE
CLAMP
Horizontal Connections - Right Side Down
INDUCED
DRAFT BLOWER
DRAIN PORT
HOSE B
FRONT
COVER
PRESSURE
TAP
HOSE A
GREEN HOSE
CLAMPS
(3 PLACES)
TUBE(S) 2 LEFT SIDE
PANEL
FRONT COVER
DRAIN PORT
RED HOSE CLAMP
SIDE PANEL
GROMMET
HOLES
DRAIN TRAP
Horizontal Connections - Left Side Down
21
3. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
H
ORIZONTAL
I
NSTALLATIONS
NOTE: This furnace is shipped from the factory as a Dedicated
Upflow. A “Blocked Drain Kit” is available and MUST BE USED if the furnace is installed Horizontal Left or Horizontal Right. Check the
Serial/ Rating Plate on the furnace for the Kit P/N.
R
IGHT
S
IDE
D
OWN
L
EFT
S
IDE
D
OWN
WARNING
A
BLOCKED DRAIN KIT IS REQUIRED FOR HORIZONTAL
INSTALLATIONS WITH THE RIGHT SIDE OR LEFT SIDE DOWN
. T
HE KIT
PROTECTS AGAINST A BLOCKED CONDENSATE DRAIN
. F
AILURE TO
PROPERLY INSTALL THE KIT COULD LEAD TO BODILY INJURY OR
DEATH DUE TO CARBON MONOXIDE EXPOSURE
.
WARNING
A
BLOCKED DRAIN KIT IS REQUIRED FOR HORIZONTAL
INSTALLATIONS WITH THE RIGHT SIDE OR LEFT SIDE DOWN
. T
HE KIT
PROTECTS AGAINST A BLOCKED CONDENSATE DRAIN
. F
AILURE TO
PROPERLY INSTALL THE KIT COULD LEAD TO BODILY INJURY OR
DEATH DUE TO CARBON MONOXIDE EXPOSURE
.
NOTE: This furnace is shipped from the factory as a Dedicated
Upflow. A “Blocked Drain Kit” is available and MUST BE USED if the furnace is installed Horizontal Left or Horizontal Right. Check the
Serial/ Rating Plate on the furnace for the Kit P/N.
Horizontal installations with the left side panel down will require drain hoses to be connected to the left side front cover drain port and the side drain port on the rubber elbow.
NOTE: This furnace is shipped from the factory as a Dedicated
Upflow. A “Blocked Drain Kit” is available and MUST BE USED if the furnace is installed Horizontal Left or Horizontal Right. Check the
Serial/ Rating Plate on the furnace for the Kit P/N.
Horizontal installations with the right side down require that the drain hoses be connected to the right side front cover drain port and the rubber elbow drain port.
Make connections as follows:
1. Remove the rubber plug/cap from the coil front cover drain port.
2. Secure Hose A to front cover drain tap with a red hose clamp.
Route hose to rear right (down) side panel grommet holes.
3. Cut 1/4 inch from the end of the drain port on the rubber elbow and discard.
4. Insert Tube 1 into rubber elbow drain port and secure with a silver hose clamp. Angle tube outward toward front of furnace.
5. Cut 17 3/4 inches from the long end (end opposite the bend) of Hose B. Save the part with the bend and discard the
17 3/4 inch piece that was cut.
6. Secure remaining end of Hose B to exposed end of Tube 1 with a green hose clamp. Route hose to front right down side panel grommet holes.
7. Cut 5 1/2 inches straight length from the long end (end with taper) of each Tube 2. Save the 5 1/2” long pieces and discard the pieces with the bends.
8. Insert approximately one inch of each Tube 2 through the right down side panel grommet holes. Secure tubes to
Hose A and Hose B using green hose clamps. Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound.
9. A “Blocked Drain Kit” MUST be installed for right side down installations. The kit includes a front cover pressure switch that must be used to protect against a blocked drain condition. Install the front cover pressure switch per the instructions included with the “Blocked Drain Kit”. Failure to install the “Blocked Drain Kit” will void the warranty and could lead to bodily injury or death.
For details concerning mounting of the drain trap, refer to Section
X, Condensate Drain Lines and Drain Trap - Horizontal Drain Trap
Mounting (Left or Right Side Panel).
1.
2.
3.
4.
Secure the short end of Hose B to rubber elbow side drain port using a green hose clamp. NOTE: For left side drainage,
5.
Cut 5 1/2 inches straight length from the long end (end with
6.
Remove the rubber plug/cap from the coil front cover left
(down) side drain port.
Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear left (down) side panel grommet holes. NOTE: For left side drainage, grommets must be relocated to left side panel.
Remove the rubber cap from the side drain port on the rubber elbow.
route hose to far left (down) side panel grommet holes.
NOTE: Horizontal left side connections (when using new side port drain elbow) does not require connecting a hose to the induced draft blower housing.
taper) of each Tube 2. Save the 5 1/2” long pieces and discard the pieces with the bends.
Insert approximately one inch of each Tube 2 through left side panel grommet hole. Secure tubes to Hose A and
Hose B with a green hose clamps. NOTE: Tube must reach bottom of trap. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.
7.
A “Blocked Drain Kit” MUST be installed for left side down installations. The kit includes a front cover pressure switch that must be used to protect against a blocked drain condition. Install the front cover pressure switch per the instructions included with the “Blocked Drain Kit”. Failure to install the “Blocked Drain Kit” will void the warranty and could lead to bodily injury or death.
For details concerning mounting of the drain trap, refer to Section
X, Condensate Drain Lines and Drain Trap - Horizontal Drain Trap
Mounting (Left or Right Side Panel).
H
ORIZONTAL
D
RAIN
T
RAP
M
OUNTING
(L
EFT OR
R
IGHT
S
IDE
P
ANEL
)
NOTE: This furnace is shipped from the factory as a Dedicated
Upflow. A “Blocked Drain Kit” is available and MUST BE USED if the furnace is installed Horizontal Left or Horizontal Right. Check the
Serial/ Rating Plate on the furnace for the Kit P/N.
1.
Position the drain trap against side panel with drain tubes inserted into trap. Note that the trap may be orientated with the outlet facing either the furnace’s top cover or base pan.
22
2. Secure drain trap to side panel at the dimples or crosshairs located on either side of the grommet drain holes.
3. Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding.
4. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
XI. ELECTRICAL CONNECTIONS
WARNING
HIGH VOLTAGE!
T
O AVOID THE RISK OF ELECTRICAL SHOCK
,
WIRING TO
THE UNIT MUST BE POLARIZED AND GROUNDED
.
Connect hot, neutral, and ground wires as shown in the wiring diagram located on the unit’s blower door. For direct vent applications, the cabinet opening to the junction box must be sealed air tight using either a UL approved bushing such as Heyco Liquid
Tight or by applying a UL approved non-reactive sealant to bushing.
Line polarity must be observed when making field connections.
Line voltage connections can be made through either the right or left side panel. The furnace is shipped configured for a left side electrical connection with the junction box located inside the burner compartment. To make electrical connections through the opposite side of the furnace, the junction box must be relocated to the other side of the burner compartment prior to making electrical connections. To relocate the junction box, follow the steps shown below.
NOTE: Wire routing must not to interfere with circulator blower operation, filter removal, or routine maintenance.
WARNING
WARNING
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK
,
DISCONNECT ELECTRICAL POWER
BEFORE SERVICING OR CHANGING ANY ELECTRICAL
WIRING
.
E
DGES OF SHEET METAL HOLES MAY BE SHARP
. U
SE GLOVES AS A
PRECAUTION WHEN REMOVING HOLE PLUGS
.
CAUTION
1. Remove the burner compartment door.
2. Remove and save the two screws securing the junction box to the side panel.
3. Relocate junction box and associated plugs and grommets to opposite side panel. Secure with screws removed in step 2.
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS
. W
IRING ERRORS CAN CAUSE IMPROPER AND
DANGEROUS OPERATION
. V
ERIFY PROPER OPERATION AFTER
SERVICING
.
W
IRING
H
ARNESS
The wiring harness is an integral part of this furnace. Field alteration to comply with electrical codes should not be required. Wires are color-coded for identification purposes. Refer to the wiring diagram for wire routings. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C. Any replacement wiring must be copper conductor.
115 V
OLT
L
INE
C
ONNECTIONS
Before proceeding with electrical connections, ensure that the supply voltage, frequency, and phase correspond to that specified on the unit rating plate. Power supply to the furnace must be N.E.C.
Class 1, and must comply with all applicable codes. The furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of The National Electric Code,
ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1.
Use a separate fused branch electrical circuit containing properly sized wire, and fuse or circuit breaker. The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating plate. An electrical disconnect must be provided at the furnace location.
NOTE: Line polarity must be observed when making field connections.
WARNING
STANDARD
JUNCTION BOX
LOCATION
Junction Box Relocation
WARNING
ALTERNATE
JUNCTION BOX
LOCATION
HIGH VOLTAGE!
T
O AVOID THE RISK OF INJURY
,
ELECTRICAL SHOCK OR
DEATH
,
THE FURNACE MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN
THEIR ABSENCE
,
WITH THE LATEST EDITION OF THE
N
ATIONAL
E
LECTRIC
C
ODE
.
To ensure proper unit grounding, the ground wire should run from the furnace ground screw located inside the furnace junction box all the way back to the electrical panel. NOTE: Do not use gas piping as an electrical ground. To confirm proper unit grounding, turn off the electrical power and perform the following check.
1. Measure resistance between the neutral (white) connection and one of the burners.
I
N UPRIGHT UPFLOW INSTALLATIONS
,
THE DRAIN TRAP MUST BE
MOUNTED ON THE OPPOSITE SIDE OF THE UNIT FROM THE JUNCTION
BOX
. T
HIS WILL REDUCE THE RISK OF WATER REACHING THE
JUNCTION BOX IN THE EVENT OF A BLOCKED DRAIN CONDITION
.
23
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which interrupts unit voltage when the blower door is opened for servicing. Do not defeat this switch.
24 V
OLT
T
HERMOSTAT
W
IRING
NOTE: Wire routing must not interfere with circulator blower operation, filter removal, or routine maintenance.
Low voltage connections can be made through either the right or left side panel. Thermostat wiring entrance holes are located adjacent to the junction box locations in the blower compartment. Wire routing must not to interfere with circulator blower operation, filter removal, or routine maintenance. Refer to the following figure for thermostat connections to the integrated control module terminal strip.
Y Y
W W
W Y W Y
R
R
G
G R
R
G
C
C C
HEATING
ROOM
THERMOSTAT
FURNACE
HEATING AND
COOLING ROOM
THERMOSTAT
FURNACE
REMOTE
CONDENSING
UNIT
Thermostat Diagram
This furnace is equipped with a 40 VA transformer to facilitate use with most cooling equipment. Consult the wiring diagram, located on the blower compartment door, for further details of 115 Volt and
24 Volt wiring.
24 V
OLT
H
UMIDIFIER
The yellow wire connected to the I.D. Blower pressure switch is powered anytime the pressure switch is closed and provides 24
VAC humidifier control. Remove the yellow wire and connect a field supplied jumper wire with a “piggyback” terminal to the pressure switch terminal. Reconnect the yellow wire to the “piggyback” terminal on the jumper wire and then connect the 24 VAC line of the humidifier to the stripped end of the jumper wire. Using a wire nut or a field-supplied quick connect terminal can make this connection. The wiring must conform to all local and national codes. Connect the COM side of the humidifier to the B/C terminal on the furnace control board (or to the COM side of the 24 VAC transformer). DO NOT CONNECT 115V HUMIDIFIER TO THESE TERMI-
NALS.
Inlet gas supply pressures must be maintained within the ranges specified below. The supply pressure must be constant and available with all other household gas fired appliances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring.
Inlet Gas Supply Pressure
Natural Gas Minimum: 4.5" W.C. Maximum: 10.0" W.C.
Propane Gas Minimum: 11.0" W.C. Maximum: 13.0" W.C.
H
IGH
A
LTITUDE
D
ERATE
When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied. This is required due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range.
High altitude kits are purchased according to the installation altitude and usage of either natural or propane gas. Contact your distributor for a tabular listing of appropriate altitude ranges and corresponding manufacturer’s high altitude (Natural, Propane Gas, and/or Pressure Switch) kits.
Do not derate the furnace by adjusting the manifold pressure to a lower pressure than specified on the furnace rating plate. The combination of the lower air density and a lower manifold pressure will prohibit the burner orifice from drawing the proper amount of air into the burner. This may cause incomplete combustion, flashback, and possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude. If the gas is artificially derated, the appropriate orifice size must be determined based upon the BTU/ft 3 content of the derated gas and the altitude.
Refer to the National Fuel Gas Code, ANSI Z223.1, and information provided by the gas supplier to determine the proper orifice size.
A different pressure switch may be required at high altitude regardless of the BTU/ft 3 content of the fuel used. Contact your distributor for a tabular listing of appropriate altitude ranges and corresponding manufacturer’s pressure switch kits.
P
ROPANE
G
AS
C
ONVERSION
WARNING
XII. GAS SUPPLY AND PIPING
G
ENERAL
The furnace rating plate includes the approved furnace gas input rating and gas types. The furnace must be equipped to operate on the type of gas applied. This includes any conversion kits required for alternate fuels and/or high altitude.
CAUTION
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE
,
THE
GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE
. O
NLY MINOR ADJUSTMENTS SHOULD BE MADE BY
ADJUSTING THE GAS VALVE PRESSURE REGULATOR
.
P
OSSIBLE PROPERTY DAMAGE
,
PERSONAL INJURY OR DEATH MAY
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED
. T
HE
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
FURNACE OPERATION
. A
LL CONVERSIONS MUST BE PERFORMED BY
A QUALIFIED INSTALLER OR SERVICE AGENCY
.
This unit is configured for natural gas. The appropriate manufacturer’s propane gas conversion kit, must be applied for propane gas installations. Refer to the Section VIII, Propane Gas
/ High Altitude Installations section for details.
G
AS
V
ALVE
This unit is equipped with a 24 volt gas valve controlled during furnace operation by the integrated control module. As shipped, the valve is configured for natural gas. The valve is field convertible for use with propane gas by replacing the regulator spring with a propane gas spring from an appropriate manufacturer’s propane gas conversion kit. Taps for measuring the gas supply pressure and manifold pressure are provided on the valve.
24
The gas valve has a manual ON/OFF control located on the valve itself. This control may be set only to the “ON” or “OFF” position.
Refer to the lighting instructions label or Section XIV, Startup Pro-
cedure & Adjustment for use of this control during start up and shut
down periods.
G
AS
P
IPING
C
ONNECTIONS
G
ENERAL
CAUTION
T
O AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT
DAMAGE DUE TO UNDERFIRING OR EQUIPMENT
,
USE THE PROPER
SIZE OF NATURAL
/
PROPANE GAS PIPING NEEDED WHEN RUNNING
PIPE FROM THE METER
/
TANK TO THE FURNACE
.
When sizing a trunk line, be sure to include all appliances which will operate simultaneously when sizing a trunk line.
The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas
Code, ANSI Z223.1.
Length of
Pipe in Feet
10
20
30
40
50
60
70
In Cubic Feet of Gas Per Hour (CFH)
1/2"
132
92
73
63
56
50
46
Natural Gas Capacity of Pipe
3/4"
278
190
152
130
115
105
96
Nominal Black Pipe Size
1"
520
350
285
245
215
195
180
1 1/4"
1050
730
590
500
440
400
370
80
90
43
40
90
84
170
160
350
320
100 38 79 150 305
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)
1 1/2"
1600
1100
980
760
670
610
560
530
490
460
CFH =
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from 1/2" pipe to a larger pipe size.
The following stipulations apply when connecting gas piping. Refer to Gas Piping Connections figure for typical gas line connections to the furnace.
•
Use black iron or steel pipe and fittings for building piping.
Where possible, use new pipe that is properly chamfered, reamed, and free of burrs and chips. If old pipe is used, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound.
•
Use pipe joint compound on male threads ONLY. Always use pipe joint compound (pipe dope) that is APPROVED
FOR ALL GASSES. DO NOT apply compound to the first two threads.
•
Use ground joint unions.
•
Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
•
Install a 1/8" NPT pipe plug fitting, accessible for test gage connection, immediately upstream of the gas supply connection to the furnace.
•
Always use a back-up wrench when making the connection to the gas valve to keep it from turning. The orientation of the gas valve on the manifold must be maintained as shipped from the factory. Maximum torque for the gas valve connection is 375 in-lbs; excessive over-tightening may damage the gas valve.
•
Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.
•
Tighten all joints securely.
•
Connect the furnace to the building piping by one of the following methods:
–
Rigid metallic pipe and fittings.
–
Semi-rigid metallic tubing and metallic fittings.
Aluminum alloy tubing must not be used in exterior locations. In order to seal the grommet cabinet penetration, rigid pipe must be used to reach the outside of the cabinet. A semi-rigid connector to the gas piping may be used from there.
•
Use listed gas appliance connectors in accordance with their instructions. Connectors must be fully in the same room as the furnace.
•
Protect connectors and semirigid tubing against physical and thermal damage when installed. Ensure aluminumalloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.
GAS VALVE BURNERS
MANIFOLD
ALTERNATE
UNION
LOCATION
MANUAL
SHUT OFF VALVE
(UPSTREAM FROM
PIPE UNION)
GAS LINE
PIPE
UNION
GROMMET IN
GAS LINE
HOLE
HEIGHT REQUIRED
BY LOCAL CODE
GROMMET
IN STANDARD
GAS LINE HOLE
DRIP LEG
25
MANUAL SHUT-OFF VALVE
(UPSTREAM FROM GROUND
JOINT PIPE UNION)
WARNING
GROUND
JOINT
PIPE
UNION
ALTERNATE
UNION
LOCATION
GAS VALVE
BURNERS
DRIP LEG
GROMMET IN STANDARD
GAS LINE HOLE
DRAIN TRAP
T
O AVOID THE POSSIBILITY OF EXPLOSION OR FIRE
,
NEVER USE A
MATCH OR OPEN FLAME TO TEST FOR LEAKS
.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods.
NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).
Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressures equal to or less than 1/2 psig
(3.48 kPa).
P
ROPANE
G
AS
T
ANKS AND
P
IPING
MANIFOLD
ALTERNATE GAS
LINE LOCATION
GROMMET IN ALTERNATE
GAS LINE HOLE
HORIZONTAL [UPFLOW MODEL]
WARNING
Gas Piping Connections
WARNING
E
DGES OF SHEET METAL HOLES MAY BE SHARP
. U
SE GLOVES AS A
PRECAUTION WHEN REMOVING HOLE PLUGS
.
D
IRECT
/S
TANDARD
I
NLET
P
IPING
When gas piping enters directly to the gas valve through the stan-
dard inlet hole, the installer must supply straight pipe with a ground
joint union to reach the exterior of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
I
NDIRECT
/A
LTERNATE
I
NLET
P
IPING
When gas piping enters indirectly to the gas valve through the
alternate gas inlet hole the following 1/2 inch pipe fittings (starting
from the gas valve) to reach the outside of the cabinet must be supplied:
•
1 - 90 degree street elbow.
•
1 - 2-1/2 inch pipe nipple.
•
1 - 90 degree elbow.
•
1 - Straight pipe
The straight pipe must be long enough to reach the outside of the cabinet so as to seal the grommet cabinet penetration and to install the ground joint union outside of the cabinet. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
G
AS
P
IPING
C
HECKS
Before placing unit in operation, leak test the unit and gas connections.
I
F THE GAS FURNACE IS INSTALLED IN A BASEMENT
,
AN EXCAVATED
AREA OR A CONFINED SPACE
,
IT IS STRONGLY RECOMMENDED TO
CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING
WARNING DEVICE IN CASE OF A GAS LEAK
.
• S
INCE PROPANE GAS IS HEAVIER THAN AIR
,
ANY LEAKING AS CAN
SETTLE IN ANY LOW AREAS OR CONFINED SPACES
.
• P
ROPANE GAS ODORANT MAY FADE
,
MAKING THE GAS
U
NDETECTABLE EXCEPT FOR WITH A WARNING DEVICE
.
A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in propane gas. Do not rely on your sense of smell. Contact a local propane gas supplier about installing a gas detecting warning system. If the presence of gas is suspected, follow the instructions on Page
4 of this manual.
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 11 inch w.c. at the furnace manifold with all gas appliances in operation.
Maintaining proper gas pressure depends on three main factors:
1.
Vaporization rate, depending on temperature of the liquid, and “wetted surface” area of the container or containers.
2.
Proper pressure regulation. (Two-stage regulation is recommended for both cost and efficiency).
3.
Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size will depend on length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most standard commercial compounds, special pipe dope must be used.
Shellac-based compounds resistant to the actions of liquefied petroleum gases such as Gasolac
®
, Stalactic
®
, Clyde’s
®
or John
Crane
®
are satisfactory.
Refer to the following illustration for typical propane gas installations.
26
First Stage
Regulator
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
Propane Gas Installation (Typ.)
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or Nominal Pipe Size
Tubing
Length,
Feet
10
3/8"
Tubing Size, O.D. Type L
1/2" 5/8" 3/4" 7/8"
Schedule 40
1/2" 3/4"
20
30
40
730
500
400
370
1,700
1,100
920
850
3,200
2,200
2,000
1,700
5,300
3,700
2,900
2,700
8,300
5,800
4,700
4,100
3,200
2,200
1,800
1,600
7,500
4,200
4,000
3,700
50
60
80
100
125
150
175
200
330
300
260
220
200
190
170
160
770
700
610
540
490
430
400
380
1,500
1,300
1,200
1,000
900
830
780
730
2,400
2,200
1,900
1,700
1,400
1,300
1,200
1,100
To convert to capacities at 5 psig settings - multiply by 0.879
3,700
3,300
2,900
2,600
2,300
2,100
1,900
1,800
To convert to capacities at 15 psig settings - multiply by 1.130
1,500
1,300
1,200
1,000
900
830
770
720
3,400
3,100
2,600
2,300
2,100
1,900
1,700
1,500
Propane Gas Piping Chart I
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or Nominal Pipe Size
Tubing
Length,
Feet
10
3/8"
Tubing Size, O.D. Type L
1/2" 5/8" 3/4" 7/8" 1-1/8" 1/2" 3/4"
Schedule 40
1" 1-1/4" 1-1/2"
20
30
40
50
60
80
100
125
39
26
21
19
18
16
13
11
10
92
62
50
41
37
35
29
26
24
199
131
107
90
79
72
62
55
48
329
216
181
145
131
121
104
90
81
501
346
277
233
198
187
155
138
122
935
630
500
427
376
340
289
255
224
275
189
152
129
114
103
89
78
69
567 1,071 2,205 3,307
393
315
732
590
1,496
1,212
2,299
1,858
267
237
217
185
162
146
504 1,039 1,559
448
409
346
307
275
913
834
724
630
567
1,417
1,275
1,066
976
866
150
200
250
9
8
8
21
19
17
43
39
36
72
66
60
109
100
93
*Data in accordance with NFPA pamphlet NO. 54
202
187
172
63
54
48
132
112
100
252
209
185
511
439
390
787
665
590
Propane Gas Piping Chart II
XIII. CIRCULATING AIR & FILTERS
D
UCTWORK
- A
IR
F
LOW
Duct systems and register sizes must be properly designed for the
CFM and external static pressure rating of the furnace. Design the ductwork in accordance with the recommended methods of “Air
Conditioning Contractors of America” Manual D.
Install the duct system in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No.
90A and 90B.
A closed return duct system must be used, with the return duct connected to the furnace. NOTE: Ductwork must never be attached to the back of the furnace. Flexible joints may be used for supply and return connections to reduce noise transmission. To prevent the blower from interfering with combustion air or draft when a central return is used, a connecting duct must be installed between the unit and the utility room wall. Never use a room, closet, or alcove as a return air chamber.
NOTE: Two side openings or a side opening and bottom opening are required for airflow delivery of 1800 CFM and greater.
C
HECKING
D
UCT
S
TATIC
Refer to your furnace rating plate for the maximum ESP (external duct static) rating.
Total external static refers to everything external to the furnace cabinet. Cooling coils, filters, ducts, grilles, registers must all be considered when reading your total external static pressure. The supply duct pressure must be read between the furnace and the cooling coil. This reading is usually taken by removing the “A” shaped block off plate from the end on the coil; drilling a test hole in it and reinstalling the block off plate. Take a duct static reading at the test hole. Tape up the test hole after your test is complete. The negative pressure must be read between the filter and the furnace blower.
Too much external static pressure will result in insufficient air that can cause excessive temperature rise. This can cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as follows;
1.
With clean filters in the furnace, use a draft gauge (inclined manometer) to measure the static pressure of the return duct at the inlet of the furnace. (Negative Pressure)
2.
Measure the static pressure of the supply duct. (Positive Pressure)
3.
The difference between the two numbers is .4” w.c.
Example: static reading from return duct = -.1" w.c.
static reading from supply duct = .3" w.c.
total external static pressure on this system = .4" w.c.
NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. If an air conditioner coil or
Electronic Air Cleaner is used in conjunction with the furnace, the readings must also include theses components, as shown in the following drawing.
4.
Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum listed on the furnace rating plate, check for closed dampers, registers, undersized and/or oversized poorly laid out duct work.
Checking Static Pressure
(80% Furnace Shown, 90% Similar)
27
B
OTTOM
R
ETURN
A
IR
O
PENING
[U
PFLOW
M
ODELS
]
The bottom return air opening on upflow models utilizes a “lance and cut” method to remove sheet metal from the duct opening in the base pan. To remove, simply press out the lanced sections by hand to expose the metal strips retaining the sheet metal over the duct opening. Using tin snips, cut the metal strips and remove the sheet metal to free the duct flanges. Using the scribe line along the duct flange as a guide, unfold the duct flanges around the perimeter of the opening using a pair of seamer pliers or seamer tongs. NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.
On upflow units, guide dimples locate the side return cutout locations. Use a straight edge to scribe lines connecting the dimples. Cut out the opening on these lines. NOTE: An undersized opening will cause reduced airflow.
Refer to Minimum Filter Area tables to determine filter area requirements.
0453_XA
600
188*
COOLING AIRFLOW REQUIREMENT (CFM)
800
192
1000
240
1200 1400
288 ---
1600
---
2000
---
E
DGES OF SHEET METAL HOLES MAY BE SHARP
. U
SE GLOVES AS A
PRECAUTION WHEN REMOVING SHEET METAL FROM DUCT OPENING
.
CUT USING TIN SNIPS
WARNING
0703_XA
0704_XA
0904_XA
0905_XA
115_XA
---
---
---
---
---
282*
---
---
---
---
282*
260*
376*
---
---
282*
260*
376*
376*
470*
336
336
376*
376*
470*
---
384
384
384
470*
---
---
---
480
480
PRESS OUT BY HAND
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
COOLING AIRFLOW REQUIREMENT (CFM)
600
376*
800
384
1000 1200 1400 1600 2000
480 576 -------
CUT FOUR CORNERS
AFTER REMOVING SHEET
METAL
0453_XA
0703_XA --564* 564* 564* 672 -----
SCRIBE LINES OUTLINING
DUCT FLANGES
Duct Flange Cut Outs
When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element.
With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is recommended that a removable access panel be provided in the outlet air duct. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream. The access panel must be made to prevent air leaks when the furnace is in operation.
When the furnace is heating, the temperature of the return air entering the furnace must be between 55°F and 100°F.
0704_XA
0904_XA
0905_XA
1155_XA
---
---
---
---
---
---
---
---
564* 564* 672
752* 752* 752*
---
---
752* 752*
768
768
768
940* 940* 940*
---
---
800
800
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter area (sq. in)
[Based on 300 ft/min filter face velocity]
U
PRIGHT
I
NSTALLATIONS
Depending on the installation and/or customer preference, differing filter arrangements can be applied. Filters can be installed in the central return register or a side panel external filter rack kit
(upflows). As an alternative a media air filter or electronic air cleaner can be used as the requested filter.
The following figure shows possible filter locations.
F
ILTERS
- R
EAD
T
HIS
S
ECTION
B
EFORE
I
NSTALLING
T
HE
R
ETURN
A
IR
D
UCTWORK
Filters must be used with this furnace. Discuss filter maintenance with the building owner. Filters do not ship with this furnace, but must be provided by the installer. Filters must comply with UL900 or CAN/ULCS111 standards. If the furnace is installed without filters, the warranty will be voided.
28
CENTRAL
RETURN
GRILLE
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
AIR FLOW
Possible Upright Upflow
Filter Locations
H
ORIZONTAL
I
NSTALLATIONS
Filters must be installed in either the central return register or in the return air duct work.
NOTE: This furnace is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
5. Move the furnace gas valve manual control to the OFF position.
6. Wait five minutes then smell for gas. Be sure to check near the floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow the instructions on page 4 of this manual. If you do not smell gas after five minutes, move the furnace gas valve manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room temperature.
12. After the burners are lit, set the thermostat to desired temperature.
F
URNACE
S
HUTDOWN
1. Set the thermostat to the lowest setting.
The integrated control will close the gas valve and extinguish flame. Following a 15 second delay, the induced draft blower will be de-energized. After a 150-second delay period (fixed), the circulator blower will be de-energized.
2. Remove the burner compartment door and move the furnace gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.
XIV. STARTUP PROCEDURE & ADJUSTMENT
Furnace must have a 115 VAC power supply properly connected and grounded. Proper polarity must be maintained for correct operation. In addition to the following start-up and adjustment items, refer to further information in Section XVI, Operational Checks.
H
EAT
A
NTICIPATOR
S
ETTING
The heat anticipator in the room thermostat must be correctly adjusted to obtain the proper number of cycles per hour and to prevent “overshooting” of the setting. Set the heat anticipator setting to
0.7 amps. Follow the thermostat manufacturer’s instructions on how to adjust the heat anticipator setting.
D
RAIN
T
RAP
P
RIMING
The drain trap must be primed prior to furnace startup. To prime, fill the drain trap with water. This ensures proper furnace drainage upon startup and prohibits the possibility of flue gases escaping through the drain system.
F
URNACE OPERATION
Purge gas lines of air prior to startup. Be sure not purge lines into an enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved method. Verify that all required kits (propane gas, high altitude, etc.) have been appropriately installed.
F
URNACE
S
TARTUP
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
G
AS
S
UPPLY
P
RESSURE
M
EASUREMENT
CAUTION
T
O
PREVENT
UNRELIABLE
OPERATION
OR
EQUIPMENT
DAMAGE
,
THE
INLET
GAS
SUPPLY
PRESSURE
MUST
BE
AS
SPECIFIED
ON
THE
UNIT
RATING
PLATE
WITH
ALL
OTHER
HOUSEHOLD
GAS
FIRED
APPLIANCES
OPERATING
.
WARNING
HIGH VOLTAGE !
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
. M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be measured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg. The supply pressure must be measured with the unit OFF. To measure inlet pressure, use the following procedure.
29
OUTLET
Gas Valve
On/Off
Selector
Switch
Inlet Pressure
Tap
INLET
Pressure Regulator
Adjustment
(Under Cap Screw)
Inlet
Pressure
Tap
Outlet Pressure
Tap
White-Rodgers Model 36G22
Pressure Regulator
(under cap screw)
Outlet
Pressure
Tap
Gas Valve On/Off
Selector Switch
Honeywell Model VR8215 (Single-Stage)
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2. Turn OFF all electrical power to the system.
3. Inlet pressure tap connections: a. Honeywell VR8215 Valve:
Remove the inlet pressure boss plug. Install an 1/8” NPT hose barb fitting into the outlet pressure tap.
b. White-Rodgers 36G22 valve:
Back inlet pressure test screw (inlet pressure boss) out one turn (counterclockwise, not more than one turn).
4. Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or inlet pressure boss (White-
Rodgers valve).
5. Turn ON the gas supply.
6. Turn On power and close thermostat “R” and “W” contacts to provide a call for heat.
7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS
IMMEDIATELY!
8. Measure the gas supply pressure with burners firing. Adjust supply pressure using the Inlet Gas Supply Pressure table shown below. If supply pressure reading differs from the table, make necessary adjustments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.
Natural Gas
Propane Gas
Inlet Gas Supply Pressure
Minimum: 4.5" W.C. Maximum: 10.0" W.C.
Minimum: 11.0" W.C. Maximum: 13.0" W.C.
9.
Turn OFF all electrical power and gas supply to the system.
10. Remove the manometer hose from the hose barb fitting or inlet pressure boss.
11. Replace inlet pressure tap: a.
Honeywell VR8215 valve:
Remove the 1/8” NPT hose barb fitting from the inlet pressure tap. Replace the inlet pressure boss plug and seal with a high quality thread sealer.
b.
White-Rodgers 36G22 valve:
Turn inlet pressure test screw in to seal pressure port
(clockwise, 7 in-lb minimum).
12. Retest for leaks. If bubbles form, shut down gas and repair leaks immediately.
13. Turn ON electrical power and gas supply to the system.
14. Turn valve switch ON.
G
AS
M
ANIFOLD
P
RESSURE
M
EASUREMENT AND
A
DJUSTMENT
CAUTION
T
O
PREVENT
UNRELIABLE
OPERATION
OR
EQUIPMENT
DAMAGE
,
THE
GAS
MANIFOLD
PRESSURE
MUST
BE
AS
SPECIFIED
ON
THE
UNIT
RATING
PLATE
. O
NLY
MINOR
ADJUSTMENTS
SHOULD
BE
MADE
BY
ADJUSTING
THE
GAS
VALVE
PRESSURE
REGULATOR
.
WARNING
HIGH VOLTAGE !
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
. M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
This valve is shipped from the factory with the regulator preset (see control label).
Consult the appliance rating plate to ensure burner manifold pressure is as specified. If another outlet pressure is required, follow these steps.
1.
Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2.
Turn OFF all electrical power to the system.
3.
Outlet pressure tap connections: a.
Honeywell VR8215 valve:
Remove the outlet pressure boss plug. Install an 1/8”
NPT hose barb fitting into the outlet pressure tap.
b.
White-Rodgers 36G22 valve:
Back outlet pressure test screw (outlet pressure boss) out one turn (counterclockwise, not more than one turn).
4.
Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or outlet pressure boss (White-
Rodgers valve).
5.
Turn ON the gas supply.
6.
Turn ON power and close thermostat “R” and “W” contacts to provide a call for heat.
30
7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS
IMMEDIATELY!
8. Measure the gas manifold pressure with burners firing.
Adjust manifold pressure using the Manifold Gas Pressure table shown below.
Manifold Gas Pressure
Natural Gas
Propane Gas
3.5" w.c.
10.0" w.c.
9. Remove regulator cover screw from the outlet pressure regulator and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.
10. Turn OFF all electrical power and gas supply to the system.
11. Remove the manometer hose from the hose barb fitting or outlet pressure boss.
12. Replace outlet pressure tap: a. Honeywell VR8215 valve:
Remove the 1/8” NPT hose barb fitting from the outlet pressure tap. Replace the outlet pressure boss plug and seal with a high quality thread sealer.
b. White-Rodgers 36G22 valve: Turn outlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum).
13. Turn ON electrical power and gas supply to the system.
14. Close thermostat contacts to provide a call for heat.
15. Retest for leaks. If bubbles form, SHUT OFF GAS AND
REPAIR ALL LEAKS IMMEDIATELY!
G
AS
I
NPUT
R
ATE
M
EASUREMENT
(N
ATURAL
G
AS
O
NLY
)
The gas input rate to the furnace must never be greater than that specified on the unit rating plate. To measure natural gas input using the gas meter, use the following procedure.
1. Turn OFF the gas supply to all other gas-burning appliances except the furnace.
2. While the furnace is operating, time and record one complete revolution of the smallest gas meter dial.
3. Calculate the number of seconds per cubic foot (sec/ft 3 ) of gas being delivered to the furnace. If the dial is a one cubic foot dial, divide the number of seconds recorded in step 2 by one. If the dial is a two cubic foot dial, divide the number of seconds recorded in step 2 by two.
4. Calculate the furnace input in BTUs per hour (BTU/hr). Input equals the installation’s gas heating value multiplied by a conversion factor (hours to seconds), divided by the number of seconds per cubic foot. The measured input must not be greater than the input indicated on the unit rating plate.
EXAMPLE:
Installation’s gas heating (HTG) value: 1,000 BTU/ft
3
(Obtained from gas supplier)
Installation’s seconds per cubic foot: 34 sec/ ft 3
Conversion Factor (hours to seconds): 3600 sec/hr
Input = (Htg. value x 3600) ÷ seconds per cubic foot
Input = (1,000 BTU/ft 3 x 3600 sec/hr) ÷ 34 sec/ ft 3
Input = 106,000 BTU/hr
Minor changes to the input rate may be accomplished through manifold pressure adjustments at the gas valve. Refer to Section
XIV, Startup Procedure and Adjustment - Gas Manifold Pressure
Measurement and Adjustment for details. NOTE: The final mani-
fold pressure cannot vary by more than ± 0.3” w.c. from the specified setting. Consult your local gas supplier if additional input rate adjustment is required.
5. Turn ON gas to and relight all other appliances turned off in step 1. Be certain that all appliances are functioning properly and that all pilot burners are operating.
T
EMPERATURE
R
ISE
Temperature rise must be within the range specified on the unit rating plate. An incorrect temperature rise may result in condensing in or overheating of the heat exchanger. An airflow and temperature rise table is provided in the Specification Sheet applicable to your model. Determine and adjust temperature rise as follows:
1. Operate furnace with burners firing for approximately ten minutes. Ensure all registers are open and all duct dampers are in their final (fully or partially open) position.
2. Place thermometers in the return and supply ducts as close to the furnace as possible. Thermometers must not be influenced by radiant heat by being able to “see” the heat exchanger.
Temperature Rise Measurement
3. Subtract the return air temperature from the supply air temperature to determine the air temperature rise. Allow adequate time for thermometer readings to stabilize.
4. Adjust temperature rise by adjusting the circulator blower speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise. Refer to Section XIV, Startup Procedure and Adjustment -Circulator
Blower Speeds for speed changing details.
C
IRCULATOR
B
LOWER
S
PEEDS
SUPPLY
AIR
RETURN
AIR
WARNING
T
O PREVENT PREMATURE FAILURE OF HEAT EXCHANGER
,
PROPERTY
DAMAGE
,
PERSONAL INJURY OR DEATH
,
DO NOT ADJUST THE LIMIT
CONTROL
(
FACTORY
-
SET
).
31
This furnace is equipped with a multi-speed circulator blower. This blower provides ease in adjusting blower speeds. The Specification Sheet applicable to your model provides an airflow table, showing the relationship between airflow (CFM) and external static pressure (E.S.P.), for the proper selection of heating and cooling speeds.
The cooling blower speed is shipped set on HIGH, and the heating blower speed is set as indicated in the Specification Sheet applicable to your model. These blower speeds should be adjusted by the installer to match the installation requirements so as to provide the correct heating temperature rise and correct cooling CFM.
To adjust the circulator blower speed, proceed as follows:
1. Turn OFF power to the furnace.
2. Select the heating and cooling blower speeds that match the installation requirements from the airflow table in the
Specification Sheet.
3. Relocate desired motor leads to the circulator blower heat and cool speed terminals on the integrated control module.
(Terminals are identified as HEAT and COOL (hot)). If heating and cooling blower speeds are the same, a jumper wire must be used between the heat and cool terminals.
4. Connect all unused blower motor leads to the “PARK” terminals on the integrated control module. Any leads not connected to the “PARK” terminals must be taped.
5. Turn ON power to furnace.
6. Verify proper temperature rise as outlined in Section XIV,
Startup Procedure and Adjustment - Temperature Rise.
Circulator Blower Speeds
Low
Medium Low
Red
Orange
Medium Blue
High Black
Common/Neutral White
•
Furnace runs, integrated control module monitors safety circuits continuously.
•
R and W thermostat contacts open, completing the call for heat.
•
Gas valve closes, extinguishing flame.
•
Induced draft blower is de-energized following a fifteen second post purge.
•
Circulator blower is de-energized following the heat off delay period (fixed 150 seconds).
•
Furnace awaits next call from thermostat.
C
OOLING
M
ODE
The normal operational sequence in cooling mode is as follows:
•
R and Y thermostat contacts close, initiating a call for cool.
•
Integrated control module performs safety circuit checks.
•
Outdoor fan and compressor are energized.
•
Circulator blower is energized on cool speed following a fixed five second on delay.
•
Furnace circulator blower and outdoor cooling unit run, integrated control module monitors safety circuits continuously.
•
R and Y thermostat contacts open, completing the call for cool.
•
Outdoor fan and compressor are de-energized.
•
Circulator blower is de-energized following a fixed forty five second cool off delay period.
•
Furnace awaits next call from thermostat.
XV. NORMAL SEQUENCE OF OPERATION
P
OWER
U
P
The normal power up sequence is as follows:
•
115 VAC power applied to furnace.
•
Integrated control module performs internal checks.
•
Integrated control module LED will light.
•
Integrated control module monitors safety circuits continuously.
•
Furnace awaits call from thermostat.
H
EATING
M
ODE
The normal operational sequence in heating mode is as follows:
•
R and W thermostat contacts close, initiating a call for heat.
•
Integrated control module performs safety circuit checks.
•
Induced draft blower is energized for 15 second prepurge period causing pressure switch contacts to close.
•
Igniter warm up begins after 15 second prepurge expires.
•
Gas valve opens at end of igniter warm up period, delivering gas to burners and establishing flame.
•
Integrated control module monitors flame presence. Gas valve will remain open only if flame is sensed.
•
Circulator blower is energized on heat speed following a fixed thirty second blower on delay.
F
AN
O
NLY
M
ODE
The normal operational sequence in fan only mode is as follows:
•
R and G thermostat contacts close, initiating a call for fan.
•
Integrated control module performs safety circuit checks.
•
Circulator blower is energized on heat speed.
•
Circulator blower runs, integrated control module monitors safety circuits continuously.
•
R and G thermostat contacts open, completing the call for fan.
•
Circulator blower is de-energized.
•
Furnace awaits next call from thermostat.
XVI. OPERATIONAL CHECKS
B
URNER
F
LAME
The burner flames should be inspected with the burner compartment door installed. A sight glass is provided for inspection purposes. Flames should stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). Flames should extend directly outward from the burners without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.
32
F
LAME
S
ENSOR
The flame sensor is a probe mounted to the burner/manifold assembly which uses the principle of flame rectification to determine the presence or absence of flame.
Check the
Burner Flames for:
1. Stable, soft and blue.
2. Not curling, floating
or lifting off.
XVIII. TROUBLESHOOTING
E
LECTROSTATIC
D
ISCHARGE
(ESD) P
RECAUTIONS
Burner Flame
XVII. SAFETY CIRCUIT DESCRIPTION
G
ENERAL
A number of safety circuits are employed to ensure safe and proper furnace operation. These circuits serve to control any potential safety hazards and serve as inputs in the monitoring and diagnosis of abnormal function. These circuits are continuously monitored during furnace operation by the integrated control module.
I
NTEGRATED
C
ONTROL
M
ODULE
The integrated control module is an electronic device which, if a potential safety concern is detected, the module will take the necessary precautions and provide diagnostic information through an
LED.
P
RIMARY
L
IMIT
The primary limit control is located on the partition panel and monitors heat exchanger compartment temperatures. It is a normallyclosed (electrically), automatic reset, temperature-activated sensor. The limit guards against the overheating as a result of insufficient conditioned air passing over the heat exchanger.
A
UXILIARY
L
IMIT
The auxiliary limit control(s) are located on or near the circulator blower and monitors heat exchanger compartment temperatures.
They are a normally-closed (electrically), manual-reset, temperature activated sensors. These limits guard against overheating as a result of insufficient conditioned air passing over the heat exchanger.
R
OLLOUT
L
IMIT
The rollout limit controls are mounted on the burner/manifold assembly and monitor the burner flame. They are normally-closed
(electrically), manual-reset, temperature-activated sensors. These limits guard against burner flames not being properly drawn into the heat exchanger.
P
RESSURE
S
WITCHES
The pressure switches are normally-open (closed during operation), single-pole single-throw, negative air pressure-activated switches. They monitor the airflow (combustion air and flue products) through the heat exchanger via pressure taps located on the induced draft blower and the coil front cover. These switches guard against insufficient airflow (combustion air and flue products) through the heat exchanger and/or blocked condensate drain conditions.
NOTE: Discharge body’s static electricity before touching unit. An electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.).
If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
D
IAGNOSTIC
C
HART
WARNING
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK
,
DISCONNECT ELECTRICAL POWER
BEFORE
P
ERFORMAING ANY SERVICE OR MAINTENANCE
.
Refer to the Troubleshooting Chart at the end of this manual for assistance in determining the source of unit operational problems.
The red diagnostic LED blinks to assist in troubleshooting the unit.
The number of blinks refers to a specific fault code.
R
ESETTING
F
ROM
L
OCKOUT
Furnace lockout results when a furnace is unable to achieve ignition after three attempts during a single call for heat. It is characterized by a non-functioning furnace and a one flash diagnostic LED code. If the furnace is in “lockout”, it will (or can be) reset in any of the following ways.
1. Automatic reset. The integrated control module will automatically reset itself and attempt to resume normal operations following a one hour lockout period.
33
2. Manual power interruption. Interrupt 115 volt power to the furnace for 1 - 20 seconds.
3. Manual thermostat cycle. Lower the thermostat so that there is no longer a call for heat then reset to previous setting.
Interrupt thermostat signal to the furnace for 1 - 20 seconds.
NOTE: If the condition which originally caused the lockout still exists, the control will return to lockout. Refer to Section XVIII,
Troubleshooting - Diagnostic Chart for aid in determining the cause.
XIX. MAINTENANCE
A
NNUAL INSPECTION
The furnace should be inspected by a qualified installer, or service agency at least once per year. This check should be performed at the beginning of the heating season. This will ensure that all furnace components are in proper working order and that the heating system functions appropriately. Pay particular attention to the following items. Repair or service as necessary.
•
Flue pipe system. Check for blockage and/or leakage. Check the outside termination and the connections at and internal to the furnace.
•
Heat exchanger. Check for corrosion and/or buildup within the heat exchanger passageways.
•
Burners. Check for proper ignition, burner flame, and flame sense.
•
Drainage system. Check for blockage and/or leakage.
Check hose connections at and internal to furnace.
•
Wiring. Check electrical connections for tightness and/or corrosion. Check wires for damage.
•
Filters.
F
ILTERS
WARNING
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK
,
DISCONNECT ELECTRICAL POWER
BEFORE PERFORMING ANY MAINTENANCE
. I
F YOU MUST
HANDLE THE IGNITER
,
HANDLE WITH CARE
. T
OUCHING
THE IGNITER ELEMENT WITH BARE FINGERS
,
ROUGH
HANDLING OR VIBRATION COULD DAMAGE THE IGNITER
RESULTING IN PREMATURE FAILURE
. O
NLY A QUALIFIED
SERVICER SHOULD EVER HANDLE THE IGNITER
.
CAUTION
T
O ENSURE PROPER UNIT PERFORMANCE
,
ADHERE TO THE FILTER
SIZES GIVEN IN THE RECOMMENDED
M
INIMUM
F
ILTER
S
IZE
T
ABLE OR
S
PECIFICATION
S
HEET APPLICABLE TO YOUR MODEL
*
M
AINTENANCE
Improper filter maintenance is the most common cause of inadequate heating or cooling performance. Filters should be cleaned
(permanent) or replaced (disposable) every two months or as required. When replacing a filter, it must be replaced with a filter of the same type and size.
F
ILTER
R
EMOVAL
Depending on the installation, differing filter arrangements can be applied. Filters can be installed in either the central return register or a side panel external filter rack (upflow only). A media air filter or electronic air cleaner can be used as an alternate filter. Follow the filter sizes given in the Recommended Minimum Filter size table to ensure proper unit performance.
To remove filters from an external filter rack in an upright upflow installation, follow the directions provided with external filter rack kit. For further details, see your distributor.
H
ORIZONTAL
U
NIT
F
ILTER
R
EMOVAL
Filters in horizontal installations are located in the central return register or the ductwork near the furnace.
To remove:
1.
Turn OFF electrical power to furnace.
2.
Remove filter(s) from the central return register or ductwork.
3.
Replace filter(s) by reversing the procedure for removal.
4.
Turn ON electrical power to furnace.
M
EDIA
A
IR
F
ILTER OR
E
LECTRONIC
A
IR
C
LEANER
R
EMOVAL
Follow the manufacturer’s directions for service.
B
URNERS
Visually inspect the burner flames periodically during the heating season. Turn on the furnace at the thermostat and allow several minutes for flames to stabilize, since any dislodged dust will alter the flames normal appearance. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). They should extend directly outward from the burners without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.
I
NDUCED
D
RAFT AND
C
IRCULATOR
B
LOWERS
The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No further lubrication is required. Check motor windings for accumulation of dust which may cause overheating. Clean as necessary.
C
ONDENSATE
T
RAP AND
D
RAIN
S
YSTEM
(Q
UALIFIED
S
ERVICER
O
NLY
)
Annually inspect the drain tubes, drain trap, and field-supplied drain line for proper condensate drainage. Check drain system for hose connection tightness, blockage, and leaks. Clean or repair as necessary.
F
LAME
S
ENSOR
(Q
UALIFIED
S
ERVICER
O
NLY
)
Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame sense signal. If the flame sense signal drops too low the furnace will not sense flame and will lock out. The flame sensor should be carefully cleaned by a qualified servicer using emery cloth or steel wool. Following cleaning, the flame sense signal should be 1 to 6 microamps.
I
GNITER
(Q
UALIFIED
S
ERVICER
O
NLY
)
If the igniter and the surrounding air are at about 70°F and the igniter wires are not connected to any other electrical components, the resistance of the igniter should not exceed 200 ohms. If it does, the igniter should be replaced.
34
F
LUE
P
ASSAGES
(Q
UALIFIED
S
ERVICER
O
NLY
)
The heat exchanger flue passageways should be inspected at the beginning of each heating season. If necessary, clean the passageways as outlined below.
1. Turn OFF the electrical power and gas supply to the furnace.
2. Disconnect the gas line and remove the burner/ manifold assembly by removing the screws securing the assembly to the partition panel.
3. Disconnect the flue pipe system from the induced draft blower.
4. Remove the induced draft blower and the drain and pressure tap hoses from the recuperator coil front cover.
5. Remove the recuperator coil front cover to expose the coil tubes and turbulators.
6. Remove the recuperator coil turbulators individually by slowly pulling each turbulator forward firmly.
7. Clean the recuperator coil tubes using a long handle wire brush, such as a gun cleaning brush.
8. Clean the primary heat exchanger tubes using a wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the cable. Slowly rotate the cable with the drill and insert it into one of the heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Repeat for each tube.
9. Clean residue from furnace using a vacuum cleaner.
10. Replace the parts removed in the previous steps in reverse order.
11. Turn on electrical power and gas to furnace. Check for leaks and proper unit operation.
12. Severe heat exchanger fouling is an indication of an operational problem. Perform the checks listed in Section
XIV, Startup Procedure and Adjustments to reduce the
chances of repeated fouling.
XXI. REPAIR & REPLACEMENT PARTS
•
When ordering any of the listed functional parts, be sure to provide the furnace model, manufacturing, and serial numbers with the order.
•
Although only functional parts are shown in the parts list, all sheet metal parts, doors, etc. may be ordered by description.
•
Parts are available from your distributor.
Functional Parts List-
Gas Valve
Gas Manifold
Natural Gas Orifice
Propane Gas Orifice
Igniter
Flame Sensor
Rollout Limit Switch
Primary Limit Switch
Auxiliary Limit Switch
Pressure Switch
Induced Draft Blower
Door Switch
Blower Motor
Blower Wheel
Blower Mounting Bracket
Blower Cutoff
Blower Housing
Capacitor
Heat Exchanger
Recuperator Coil
Coil Front Cover
Integrated Control Module
Transformer
XX. BEFORE LEAVING AN INSTALLATION
•
Cycle the furnace with the thermostat at least three times.
Verify cooling and fan only operation.
•
Review the Owner’s Manual with the homeowner and discuss proper furnace operation and maintenance.
•
Leave literature packet near furnace.
35
T
ROUBLESHOOTING
C
HART
Symptoms of Abnormal
Operation
• Furnace fails to operate.
• Integrated control module diagnostic LED provides
no signal.
• LED is Steady On.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing ONE (1) flash.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing TWO (2) flashes.
• Induced draft blower runs continuously with no further furnace operation.
• Integrated control module diagnostic LED is flashing THREE (3) flashes.
LED Code 2
2
NONE • No 115 volt power to furnace, or no 24 volt power to integrated control module.
• Blown fuse or circuit breaker.
• Manual disconnect switch
OFF, door switch open, or
24 volt wires improperly connected or loose.
• Blown fuse or circuit breaker.
ON
• Integrated control module has an internal fault.
• Normal Operation
• Integrated control module has an internal fault.
• Normal Operation
Corrective Action
Cautions and Notes
• Assure 115 and 24 volt power to furnace integrated control module.
• Turn power OFF prior to repair.
• Check integrated control module fuse (3A).
Replace if necessary.
• Replace integrated control module fuse with 3A automotive fuse.
• Check for possible shorts in 115 and 24 volt circuits.
Repair as necessary.
• Read precautions in “Electrostatic
Discharge” section
• Replace bad integrated of manual.
control module.
• None
• Normal Operation
CONTINUOUS
ON
1
1 FLASH
2
2 FLASHES
• Pressure switch circuit is closed.
• Induced draft blower is not operating.
3
3 FLASHES
• Furnace lockout due to an excessive number of ignition
“retries” (3 total) 1 .
• Failure to establish flame.
Cause may be no gas to burners, front cover pressure switch stuck open, bad igniter or igniter alignment, improper orifices, or coated/oxidized or improperly connected flame sensor.
• Loss of flame after establishment. Cause may be interrupted gas supply, lazy burner flames (improper gas pressure or restriction in flue and/or combustion air piping), front cover pressure switch opening, or improper induced draft blower performance.
• Locate and correct gas interruption.
• Check front cover pressure switch operation (hose, wiring, contact operation).
Correct if necessary.
• Replace or realign igniter.
• Check flame sense signal. Sand sensor if coated and/or oxidized.
• Check flue piping for blockage, proper length, elbows, and termination.
• Verify proper induced draft blower performance.
• Turn power
OFF prior to repair.
• Igniter is fragile, handle with care.
• Sand flame sensor with emery cloth.
• See “Vent/Flue
Pipe” section for piping details.
• Induced draft blower pressure switch contacts sticking.
• Shorts in pressure switch circuit.
• Pressure switch circuit not closed.
• Induced draft blower
is operating.
• Pressure switch hose blocked, pinched or connected improperly.
• Blocked flue and/or inlet air pipe, blocked drain system, or weak induced draft blower.
• Incorrect pressure switch setpoint or malfunctioning switch contacts.
• Loose or improperly connected wiring.
• Replace induced draft blower pressure switch.
• Repair short.
• Turn power OFF prior to repair.
• Replace pressure switch with proper replacement part.
• Inspect pressure switch hose. Repair, if necessary,
• Inspect flue and/or inlet air piping for blockage, proper length, elbows, and termination. Check drain system. Correct as necessary.
• Correct pressure switch setpoint or contact motion.
• Tighten or correct wiring connection.
• Turn power
OFF prior to repair.
• Replace pressure switch with proper replacement part.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
36
T
ROUBLESHOOTING
C
HART
Symptoms of Abnormal
Operation
Associated
LED Code 2
• Circulator blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing FOUR (4) flashes.
4
4 FLASHES
Fault Description(s)
• Primary or auxiliary limit circuit is open.
Possible Causes
• Faulty primary or auxiliary limit switch.
• Insufficient conditioned air over the heat exchanger.
Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.
• Loose or improperly connected wiring.
Corrective Action Cautions and Notes
• Check primary/auxiliary limit. Replace if necessary.
• Check filters and ductwork for blockage.
Clean filters or remove obstruction.
• Check circulator blower speed and performance. Correct speed or replace blower if necessary.
• Tighten or correct wiring connection.
• Turn power OFF prior to repair.
• Replace primary/ auxiliary limit with proper replacement part.
• Replace blower with correct replacement part.
• Correct short at flame sensor or in flame sensor wiring.
• Turn power OFF prior to repair.
• Induced draft blower and circulation blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing FIVE (5) flashes.
5
5 FLASHES
• Flame sensed with no call for heat.
• Short to ground in flame sense circuit.
• Circulator blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing SIX (6) flashes.
6
6 FLASHES
• Rollout limit circuit is open.
• Flame rollout.
• Misaligned burners, blocked flue and/or air inlet pipe, or failed induced draft blower.
• Loose or improperly connected wiring.
• Faulty rollout limit.
• Check burners for proper alignment.
• Check flue and air inlet piping for blockage, proper length, elbows, and termination.
Correct as necessary.
• Check rollout limit.
Replace if necessary.
• Check induced draft blower for proper performance. Replace, if necessary.
• Tighten or correct wiring connection.
• Normal furnace operation.
• Integrated control module diagnostic LED is flashing SEVEN (7) flashes.
7
7 FLASHES
• Flame sense microamp signal is low.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing continuously.
C
CONTINUOUS/
RAPID FLASH
• Polarity of 115 or 24 volt power is reversed.
• Flame sensor is coated/ oxidized.
• Flame sensor incorrectly positioned in burner flame.
• Lazy burner flame due to improper gas pressure or combustion air.
• Polarity of 115 volt AC power to furnace or integrated control module is reversed.
• Orange and gray wires to transformer are reversed.
• Poor unit ground.
• Sand flame sensor if coated/oxidized.
• Inspect for proper sensor alignment.
• Check inlet air piping for blockage, proper length, elbows, and termination.
• Compare current gas pressure to rating plate info. Adjust as needed.
• Review wiring diagram to correct polarity.
• Reverse orange and gray wires going to transformer.
• Verify proper ground.
Correct if necessary.
• Turn power OFF prior to repair.
• See “Vent/Flue
Pipe” section for piping details.
• Replace rollout limit with correct replacement part.
• Replace induced draft blower with correct replacement part.
• Turn power OFF prior to repair.
• Sand flame sensor with emery clot.
• See “Vent/Flue
Pipe” section for piping details.
• See rating plate for proper gas pressure.
• Turn power OFF prior to repair.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
37
BLOWER PERFORMANCE
(CFM & Temperature Rise vs. External Static Pressure)
EXTERNAL STATIC PRESSURE (Inches Water Column)
Model
(
Heating Speed
)
As Shipped
Motor
Speed
Tons AC at 0.5"
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
GKS90453BX*
(LOW)
HIGH 3.0
MED 2.5
MED-LO 2.0
1352 --1318 --1260 --1202 --1128 --1044 955 853
1214 --1172 --1123 --1064 --1012 --938 859 741
997 --994 --960 35 923 36 884 38 817 741 611
GKS90703BX*
(MED-HI)
GKS90704CX*
(LOW)
GKS90904CX*
(MED-LO)
GKS90905DX*
(MED-LO)
GKS91155DX*
(MED-HI)
LOW
HIGH
MED
MED-LO
LOW
HIGH
1.5
4.0
MED 3.5
1.5
3.0
2.5
2.0
MED-LO
LOW
3.0
2.5
HIGH 4.0
MED 3.5
MED-LO
LOW
HIGH
3.0
2.5
5.0
MED 4.0
MED-LO 3.5
LOW
HIGH
3.0
5.0
MED 4.0
MED-LO 3.5
LOW 3.0
757 44 753 44 734 45 704 47 674 49 620 524 438
1449 36 1409 37 1326 39 1273 41 1201 43 1194 1136 1018
1192 43 1172 44 1141 45 1094 47 1046 49 973 904 793
981 53 962 54 943 55 917 56 888 58 830 764 665
750 --730 --714 --692 --657 --620 570 502
2069 --1965 --1871 --1756 --1661 --1549 1415 1275
1752 --1724 --1667 --1603 --1488 35 1402 1290 1082
1437 36 1437 36 1417 36 1369 38 1320 39 1256 1140 984
1184 44 1177 44 1161 44 1132 46 1095 47 1047 928 837
1970 --1874 35 1757 38 1667 40 1566 42 1431 1334 1182
1713 39 1650 40 1572 42 1510 44 1418 47 1313 1211 1079
1439 46 1412 47 1370 48 1327 50 1260 53 1166 1078 956
1183 56 1155 57 1122 59 1108 60 1062 62 1011 931 816
2147 --2114 --2057 --2030 --1978 --1889 1784 1713
1675 40 1686 --1640 40 1623 41 1557 43 1501 1455 1360
1489 45 1470 45 1436 46 1409 47 1361 49 1318 1243 1130
1307 51 1265 52 1234 54 1203 55 1168 57 1096 1053 991
2134 40 2103 40 2029 42 1941 44 1906 44 1818 1733 1625
1678 51 1643 52 1643 52 1577 54 1527 56 1489 1423 1339
1453 58 1440 59 1426 59 1363 62 1349 63 1314 1253 1205
1259 67 1239 68 1220 70 1181 --1159 --1118 1082 1015
1.
CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart assumes both filters are installed.
2.
All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.
3.
For most jobs, about 400 CFM per ton when cooling is desirable.
4.
INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
5.
The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only.
6 The dashed (---) areas indicate a temperature rise not recommended for this model.
7.
The above chart is for U.S. furnaces installed at 0-4000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.
38
24 VAC
HUMIDIFIER
24V THERMOSTAT
CONNECTIONS
C G R W Y
FUSE
BL
OR
(MED)
(MED LOW )
RD (LOW )
RD
3
6
9
2
5
8
1
4
7
12 11 10
GKS9 WIRING DIAGRAM
BLOWER
COMPARTMENT
DOOR SWITCH
(OPEN WHEN
DOOR OPEN)
HUMIDIFIER
C
G
Y
W
TO
MICRO
TR (6)
GND (8)
MVC (9)
N
O
MV(12)
GND
C
OPTIONAL FRONT
PRESSURE
COVER
SWITCH
PS (10)
PSO (4)
HLI (7)
C
HLO (1)
INTEGRATED
CONTROL MODULE
C2
M1
ID BLOWER
PRESSURE
SWITCH
NO
GAS
VALVE
R
RO2 (11)
RO1 (5)
DIAGNOSTIC
LED
115 VAC HOT AND PARK TERMINALS
COOL-H HEAT-H
LINE-H
2
1
B K
WH
BK
MANUAL RESET
AUXILIARY LIMIT
IN UPFLOW
BLOW ER DECK
TH (3)
24 VAC
40 VA
TRANSFORMER
XFMR-H
FS
IGN
115 VAC
FLAME SENSOR
HOT SURFACE
IGNITER
IND
ID
BLWR
CO
OL
HE
AT
-H
CIRCULATOR
BLWR
LINE-H
DOOR
SWITCH
JUNCTION BOX
DISCONNECT
N
O
C
24 VAC
HUMIDIFIER
2 CIRCUIT
CONNE CTOR
HOT
SURFACE
IG NITER
C2
MI
G AS VALVE
NO C
3
4
5
1
2
6
C
0 STEADY ON = NORMAL OPERATION
OFF
1 FLASH
=
=
CONTROL FAILURE
2 FLASHES = PRESSURE SW ITCH STUCK CLOSED
3
4
5
6
FLASHES
FLASHES
FLASHES
FLASHES
=
=
PRESSURE
= OPEN HIGH
CONTINUOUS/RAPID
SW ITCH
LIMIT
FLASHES =
STUCK
= FLAME SENSE WITHOUT
OPEN
GAS VALVE
REVERSED 115 VAC POLARITY
BL
JUNCTION
BOX
TO 115VAC/ 1 Ø
L
/60
OVERCURRENT
GND
HZ
N
POW ER SUPPLY
PROTECTION
DEVICE
W ITH
BK
FLA ME
SENSOR
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
HI VOLTAGE (115V)
HI VOLTAGE FIELD
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
EQUIPMENT GND
FIELD GND
FIELD SPLICE
SWITCH (TEMP.)
IGNITER
SW ITCH (PRESS.)
OVERCURRENT
PROT.
DEVICE
COLOR CODES:
YL YELLOW
OR ORANGE
PU PURPLE
GN GREEN
BK BLACK
PK PINK
BR BROW N
W H W HITE
BL BLUE
GY GRAY
RD RED
0140F00236 REV.
D
NOTES:
1.
2.
SET HEAT ANTICIPATOR
MANUFACTURER'S
ON ROOM
SPECIFIED
THERMOSTAT
REPLACEMENT
AT 0.7
AMPS.
PARTS MUST BE USED WHEN SERVICING.
3.
IF ANY
HAVING
OF THE
A
ORIGINAL
TEMPERATURE
WIRE AS
RATING
SUPPLIED
OF AT
WITH
LEAST 105
THE
°C.
FURNACE MUST BE REPLACED, IT
USE COPPER CONDUCTORS ONLY.
MUST BE REPLACED WITH WIRING MATERIAL
4.
IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE SAME, DISCARD JUMPER BEFORE CONNECTING BLOWER LEADS.
UNUSED
BLOWER LEADS MUST BE PLACED ON "PARK" TERMINALS OF INTEGRATED CONTROL OR TAPED.
5.
UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C.
AND LOCAL CODES.
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
39
S
PECIAL
I
NSTRUCTIONS FOR
P
RODUCTS
I
NSTALLED
IN THE
S
TATE OF
M
ASSACHUSETTS
COMBUSTION
AIR INTAKE.
DISTANCE BETWEEN
COMBUSTION AIR
INTAKE AND GRADE
VENT/FLUE
TEE
DISTANCE BETWEEN
VENT AND GRADE
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.
3.
SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4.
INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
EXEMPTIONS
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1.
The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
2.
Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1.
Detailed instructions for the installation of the venting system design or the venting system components; and
2.
A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1.
The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2.
The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
40
advertisement
Key Features
- Dual-certified venting (non-direct/direct vent)
- Hot surface igniter
- Condensate drain trap
- Integrated control module
- Residential and commercial applications
- Construction site heater (conditional)
- Variable blower speeds
- Safety features (rollout limit, pressure switches, flame sensor)
Frequently Answers and Questions
How do I determine the correct venting system for my GKS9 furnace?
What is the role of the condensate drain trap in the GKS9 furnace?
Can the GKS9 furnace be used as a construction site heater?
What are the safety features included in the GKS9 furnace?
How do I adjust the blower speeds on the GKS9 furnace?
Related manuals
advertisement
Table of contents
- 5 I. Component Identification
- 6 II. Safety considerations
- 6 III. Product Application
- 7 IV. Location Requirements & Considerations
- 9 V. Combustion & Ventilation Air Requirements
- 11 VI. Installation Positions
- 11 VII. Horizontal Applications & Considerations
- 13 VIII. Propane Gas /High Altitude Installations
- 13 IX. Vent/Flue Pipe & Combustion Air Pipe
- 18 X. Condensate Drain Lines & Drain Trap
- 23 XI. Electrical Connections
- 24 XII. Gas Supply and Piping
- 27 XIII. Circulating Air & Filters
- 29 XIV. Startup Procedure & Adjustment
- 32 XV. Normal Sequence of Operation
- 32 XVI. Operational Checks
- 33 XVII. Safety Circuit Description
- 33 XVIII. Troubleshooting
- 34 XIX. Maintenance
- 35 XX. Before Leaving an Installation
- 35 XXI. Repair & Replacement Parts
- 39 GKS9 Wiring Diagram