M-SYSTEM M2 PHS Signal Conditioner Instruction Manual

M-SYSTEM M2 PHS Signal Conditioner Instruction Manual

Below you will find brief information for Signal Conditioner M2PHS. This device is designed to provide a conditioned signal that can be used in various applications. It includes a signal conditioner, a base socket, and an input resistor for current input. The device is designed to be used in Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations. It also meets CE/UL requirements. To ensure the device functions properly, it requires a warm-up time of 10 minutes after power is supplied. The device has various features, such as calibration and adjustment procedures, which allow you to make it compatible with different applications. The device also has a peak hold feature that allows you to capture the maximum value of an input signal.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Signal Conditioner M2PHS Instruction Manual | Manualzz
M2PHS
INSTRUCTION MANUAL
PEAK HOLD
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor)...... (1)
Input resistor is provided only with current input type.
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ NONINCENDIVE APPROVAL OPTION
•This equipment is suitable for use in Class I, Div. 2, Groups
A, B, C and D or Non-Hazardous Locations only.
•WARNING!Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
•WARNING!– Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
•WARNING!– Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazardous.
•The equipment was evaluated for use in the ambient temperature and relative humidity as mentioned in ‘ENVIRONMENT’ section.
•The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■ CONFORMITY WITH EC DIRECTIVES OR UL
•This equipment is suitable for use in a Pollution Degree
2 environment and in Installation Category II, with the
maximum operating voltage of 300V.
Basic insulation is maintained between signal input and
output. Prior to installation, check that the insulation
class of this unit satisfies the system requirements.
•Altitude up to 2000 meters
•The equipment must be mounted inside a panel.
•The equipment must be installed such that appropriate
clearance and creepage distances are maintained to conform to CE/UL requirements. Failure to observe these requirements may invalidate the CE/UL conformance.
MODEL
M2PHS
■ ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
•Be sure that the ventilation slits are not covered with cables, etc.
■ WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
•The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
•With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to endure it without breakdown, however, it may shorten appropriate life duration.
COMPONENT IDENTIFICATION
Body
Fixing Screw
Input Resistor
Model
ZERO
Zero Adj.
Base Socket
SPAN
Span Adj.
Connection
Diagram
Specifications
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V (90 – 264V for UL),
47 – 66 Hz, approx. 3 – 5VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■ DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■ GENERAL PRECAUTIONS
•Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
EM-5086 Rev.4
P. / 2
M2PHS
TERMINAL CONNECTIONS
ADJUSTMENT PROCEDURE
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
When an input resistor is provided with the module, attach
it together with input wiring to the input screw terminals.
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibration.
For matching the signal to a receiving instrument or in case
of regular calibration, close across the terminal 5 – 8 and
adjust the output as explained in the following.
+
INPUT
–
R
*
HOLD CONTROL
Close : Track
Open : Hold
1
9 +
4
12 –
5
13 U(+)
8
14 V(–)
OUTPUT
POWER
*Input shunt resistor attached for current input.
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
13 – 14 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
When the output does not track the input signal, check
that the terminals 5 – 8 are closed or not.
4) Output: Check that the load resistance meets the described specifications.
■ HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUSTMENT PROCEDURE” explained earlier.
EXTERNAL DIMENSIONS unit: mm (inch)
■ TERMINAL ASSIGNMENTS
INPUT RESISTOR
(model: REM2)
8–M3
SCREW
21.5 (.85) 10 (.39)
84 (3.31)
114 (4.49)
4 1
5
12
14 13
9
15 (.59)
[4 (.16)]
23 (.91)
4 1
5
72 (2.83)
8
59 (2.32)
70.5 (2.78)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
8
12
14 13
4 (.16)
DIN RAIL
35mm wide
19 (.75)
6 (.23)
9
Input shunt resistor attached
for current input.
• When mounting, no extra space is needed between units.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
EM-5086 Rev.4
P. / 2

advertisement

Key Features

  • Signal Conditioning
  • Peak Hold Feature
  • CE/UL Conformance
  • Input Resistor for Current Input
  • Calibration and Adjustment
  • Non-Hazardous Locations
  • DIN Rail Mounting
  • Wall Mounting
  • Warm-up Time

Frequently Answers and Questions

What is the purpose of the input resistor?
The input resistor is provided only with current input type and attached together with input wiring to the input screw terminals.
What are the environmental requirements for the M2PHS?
The device is suitable for use in an environment with a temperature between -5 to +55°C (23 to 131°F) and relative humidity within 30 to 90% RH. It should be installed indoors and protected from heavy dust, metal particles, continuous vibration, and physical impact.
How do I calibrate the M2PHS?
Turn the power supply on and warm up for more than 10 minutes. Apply 0% input and adjust output to 0%. Apply 100% input and adjust output to 100%. Check ZERO adjustment again with 0% input. When ZERO value is changed, repeat the above procedure. Regular calibration procedure is explained in the manual. Warm up the unit, apply 0%, 25%, 50%, 75% and 100% input signal, check that the output signal remains within accuracy described in data sheet. When output is out of tolerance, recalibrate the unit.
What are the power input ratings for the M2PHS?
The device has different power input ratings depending on the model: for 100 – 240V AC rating: 85 – 264V (90 – 264V for UL), 47 – 66 Hz, approx. 3 – 5VA; for 24V DC rating: 24V ±10%, approx. 3W; for 11 – 27V DC rating: 11 – 27V, approx. 3W; for 110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W.
How do I install the M2PHS on a DIN rail?
Set the base socket so that its DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down DIN rail adaptor utilizing a minus screwdriver and pull.

Related manuals