3340
3300
PDS 3300
SERIES
Multiloop
Controller
• 3340: 4 loops of PID
Heat, Cool or Heat/Cool
Control
• 3380: 8 loops of PID
Heat or Cool Control
• Auto-Tuning PID
Control
• Up to 11 total outputs,
4 or 8 for control,
others for alarm
• Thermocouple, RTD or
Analog inputs
FEATURES
Space and Time Savings:
The 3340/3380 can control up to a
maximum of 8 channels in a compact 1/4 DIN package. The 1/4
DIN controller reduces panel size
and panel cutouts. By increasing
zone density, the 3340/3380 can
now make PID temperature control
for 3 to 8 zones affordable in a
multi-loop form factor, aiding
designers of control equipment to
save labor costs, installation costs,
electric panel size, and operation
cost.
• Modular Outputs,
Relay, SSR drive, Triac
or analog
• Heater Breakdown
Option with CT Inputs
• RS-232, RS-422,
RS-485 Communications Option with
MODBUS Protocol
In comparison to other multi-loop
packages, the 3340/3380 has a
straight forward user interface that
does not require a PLC programmer or other support hardware to
operate. The display, pushbuttons,
outputs and software are integrated
in this single multi-loop package.
Although all inputs are scanned at
least once per second, the display
of the 3340/3380 will display the
temperatures of each channel on
an adjustable scan rate so the
operator can view all channels
without touching any pushbuttons.
Flexible Outputs:
The control outputs are available
as Relay, Triac, SSR drive, or
Analog. The Relay and SSR drive
control outputs are plug-in modPH: 1-888-996-9258 • Fax: 615-793-3563
www.chromalox.com
ules that can be exchanged individually in the field. These modules simplify application changes
and field service.
A total of 11 outputs are available:
In the 3340 four loop controller,
these can be used as:
• 8 control (4 Heat, 4 Cool) plus 3
alarms
• 4 control, with up to 7 alarm
outputs
In the 3380 eight loop unit, 8 outputs and up to 3 alarms
Alarms:
Alarm 1 is standard with all controllers. It is
mapped to all the
control loops and
can be used as
an Absolute High
and Low Process
Alarm, or as a
high, low, high
and low, or band
Deviation alarm
or as a loop
break alarm. All
Alarm set points can be individual
for each loop or can be grouped.
Two additional alarms give the
user the flexibility of having a low,
high and high-high alarm arrangement.
Heater Break Alarm:
Alarm 2 can be ordered as a
Heater Break Alarm. For loads
with multiple heaters this feature
alarms when individual heaters
fail. This provides maintenance of
a process before the problem
becomes critical.
© 2002 Chromalox®, Inc.
3340/3380 Multiloop Controller
With this feature the 3340/3380 is equipped with Current
Transformer (CT) inputs. External CTs send a signal to the
3340/3380 which is converted to the load current. Two
ranges are available 0-30 Amps and 0-100 Amps. Eight
single phase loads can be monitored by the 3380 and four
single or three phase loads can be monitored by the 3340.
Digital Communications:
Multi-Memory Area:
Temperature set point, PID constants, alarm set point,
ramp to set point rate, channel used/unused for each
loop can be stored in a “memory area”. The eight memory area allows for quick changes to alternate processes
or products. The memory area can be selected via the
front faceplate or digital inputs.
With the Digital Communications option the 3340/3380
can communicate with a remote PLC or Computer via an
RS-232 interface or an RS-422/485 interface, if multiple
3340/3380s are connected. The 3340/3380s communicate using MODBUS Protocol.
Digital Inputs:
An optional ChromaSoft/SpecView software program
communicates with multiple Chromalox controllers from
a single computer. This flexible Windows based package
allows an operator
to view, change,
data log any controller parameter.
protection prevents dust and
splashed liquids from rain and accidental splashing of the front overlay.
Optional digital inputs are available to select Stop and
Run or one of the eight “Memory Areas”.
Splashproof Option: The IP65
Channel (CH)
Display [Green]
• Displays channel Number.
• Displays Character “A”
showing batch setting.
Process Value (PV)
Display [Green]
Displays PV or various
parameter symbols.
Memory area (AREA)
Display [Orange]
Displays memory area
number.
Set Value (SV)
Display [Orange]
Displays SV or various
parameter set values.
Indication Lamps:
Autotuning (AT)
lamp (Green)
Flashes with the autotuning
activated in the display
channel.
Channel Key
• Used when the channel
number is changed.
• Used to display the character
“A” showing batch setting.
• Used for start/stop of scan
display.
2
UP Key
Increase values.
DOWN Key
Decrease values.
Set Key
Used for parameter
selection and set
value registration.
Shift & R/S Key
• Shift digits when settings
are changed.
• Selects the RUN/STOP.
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563
3340/3380 Multiloop Controller
SPECIFICATIONS
Control Modes:
Control Adjustments:
Control Set Point
Set Point Limits
Dead band
Proportional Band (P)
Cool Proportional Band
Integral (I)
Derivative (D)
Anti reset windup
Heat Cycle Time
Cool Cycle Time
H/C Overlap Deadzone
Ramp Rate
PV bias
Alarm Adjustments
Alarm Type
Alarm Inhibit/Hold
Ranges
Alarm Differential
Loop Break Alarm
Heater Break Alarm
Sensor Inputs
Input Update Rate
Input Break Action
Input Filter
Influence of external Resistance
Influence of lead wire Resistance
PID with Autotuning
PID Heat/Cool with Autotuning (3340 only)
Air or water cooling selectable
PI, PD, P or On/Off Selectable
Input Span
Within Span High and Low
2 degrees or .2% factory setting (default)
Adjustable up to full span
Input Span (PB=0 selects On/Off control)
1-1000% of the Heat Proportional Band
1 to 3600sec (0= Off)
1 to 3600 sec (0=Off)
1 to 100% of Proportional Band (0 turns off Integral)
1-100 sec (no setting for current output)
1-100 sec (no setting for current output)
-Span to +Span (within –1999 to +1999)
Minus setting Overlap
0 to span/minute (0=off)
-span to +span (within –1999 to 9999)
High Process
Low Process
Deviation Low, High, High-Low, Band
Loop Break Alarm
Heater Break Alarm
FAIL – Automatic alarm on controller failure
Available on all except Deviation Band, Set value, FAIL
Inhibit on: Power Up, From STOP to RUN, Set point Changes
Memory area changes
Process Alarm: Input span
Deviation Alarm: -span to +span
2 degrees (temperature input), 0.2%(Voltage input)default
Adjustable to span
Off, 0.1 to 200.0 minutes, dead band: 0 to span,
LBA output is allocated to Alarm 1
(Requires external current transformers (CT)
Input Range 0-30A or 0-100A
Display Range
0.0 to 100.0A
Accuracy ±5% of input value or ±2A
HBA is allocated to Alarm 2
Thermocouple, RTD or Voltage
0.5sec (3340), 1 sec (3380)
Upscale: Thermocouple and RTD
Downscale: Voltage input
1-100 sec. Time constant 0=off
First order digital filter
0.2 V/Ω(Thermocouple)
10Ω maximum
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563
3
3340/3380 Multiloop Controller
Thermocouple
Type
Max Range ˚F
Max Range ˚C
Accuracy
J
0 to 2192
-199.9 to 999.9
0-1200
-199.9 to 999.9
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy under –100C not guaranteed
K
0 to 2502
-199.9 to999.9
0 to 1372
-199.9 to 800.0
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy under –100C not guaranteed
E
0 to 1820
0 to 1000
±0.3% of reading + 1 digit or ±2˚C(4˚F)
T
-199.9 to 752.0
-199.9 to 400.0
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy under –100C not guaranteed
R
0 to 3216
0 to1769
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy 0 to 399C not guaranteed
S
0 to 3216
0 to1769
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy 0 to 399C not guaranteed
B
0 to 3308
0 to 1820
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy 0 to 399C not guaranteed
N
0 to 2372
0.0 to 999.9
0 to 1300
0.0 to 800.0
±0.3% of reading + 1 digit or ±2˚C(4˚F)
PLII
0 to 1390
0 to 2534
±0.3% of reading + 1 digit or ±2˚C(4˚F)
W5Re/W26Re
0 to 4000
0 to 2320
±0.3% of reading + 1 digit or ±2˚C(4˚F)
U
-199.9 to 999.9
-199.9 TO 600.0
±0.3% of reading + 1 digit or ±2˚C(4˚F)
Accuracy under –100C not guaranteed
L
0 to 1600
0 to 800
±0.3% of reading + 1 digit or ±2˚C(4˚F)
All thermocouple ranges can be limited within their Max Ranges.
RTD non-isolated
Type
Max Range ˚F
Max Range ˚C
Accuracy
100Ω PLT IEC
-199.9 to 999.9
-199.9 to 649.0
±0.3% of reading + 1 digit or ±0.8˚C(1.6˚F)
100Ω PLT JIS
-199.9 to 999.9
-199.9 to 649.0
±0.3% of reading + 1 digit or ±0.8˚C(1.6˚F)
RTD ranges can be limited within their Max Range.
Voltage non-isolated
Type
Adjustable Range
0-10, 0-5, 1-5 Vdc
-1999 to 9999 (0.0 to 100.0 default)
Decimal Point in 1/10, 1/100, 1/1000
4
Accuracy
±0.3% of reading + 1 digit
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563
3340/3380 Multiloop Controller
Control Outputs (up to 8)
Relay
SSR drive(Voltage Pulse)
Triac
Current
Alarm Outputs
Relay
Electrical Life
Contact Input (Optional)
Number of input
Rating
Function
Communications (Optional)
Hardware
Protocol
Baud Rate
Bit configuration
Environment
Supply Voltage:
Power Consumption
Memory Backup
Ambient temperature
Ambient Humidity
Weight
Operating environment
Standard Compliance:
NO Form A contact, 3A (resistive) at 250VAC,
300,000 cycles or more at rated load
12Vdc, 20ma max
0.5A @ 40C or less
0 to 20ma into 0 to 600Ω
4 to 20ma into 0 to 600Ω
3 Relays, NO Form A contact, 1A (resistive) at 250VAC
Out 5-8 on 3340 can be used as alarms, 3A at 250VAC via Alarm 3 settings
300,000 cycles or more at rated load
5 inputs
Non-voltage contact input
Open: 500kΩ or more, Close: 10Ω or less
Run (close) Stop(open)
Memory area selection, 3 inputs binary (0-7)
Data Set
RS232C 3 wire single drop
RS-422 4 wire multi-drop, up to 31 units
RS-485 2 wire multi-drop, up to 31 units
Modbus
2400,4800,9600,19200 bps
Start bit: 1
Data Bits: 8
Parity bit: None, Odd, Even
IP65 Protection (Optional)
100 to 240VAC (±10%)
24VAC/VDC (±10%)
Up to 20VA
Non-Volatile memory
0˚ to 50˚C (32˚ to 122˚F)
45 to 85% non-condensing
1.2 lb. (560g)
Free from corrosive and flammable gas and dust,
Free from exposure to direct sunlight
CE Mark, UL Recognized, CSA Certified
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563
5
3340/3380 Multiloop Controller
ORDERING INFORMATION
Model
3340 Four Loop Autotuning PID Controller
Code
1
3
4
Input
Thermocouple J, K, R, S, B, E, PLII, N, T, U, L
Analog Vdc 0-5, 0-10, 1-5 Vdc
RTD, 100 ohm Plt
Code
R
V
T
7
8
Control Output 1-4, Heat or Cool
Relay 3 amp, 250 Vac
SSR drive, 12 Vdc at 20 ma
Triac, 0.5 A
0-20 ma up to 600ohms
4-20 ma up to 600ohms
Code
0
R
V
T
7
8
Output 5-8, Alarm or Cooling Control
No outputs
Relay 3 amp, 250 Vac
SSR drive, 12 Vdc
Triac, 0.5 A
0-20 ma up to 600ohms
4-20 ma up to 600ohms
Code
3
4
Instrument Power
24 Vac/Vdc
100-240 Vac
Code
1
Alarm 1
Relay, 1A, 250 Vac
Code
0
1
2
3
4
5
Alarm 2
No alarm
Relay, 1A, 250 Vac
Heater Break Alarm, 0-30A Single Phase Input*
Heater Break Alarm, 0-100A Single Phase Input*
Heater Break Alarm, 0-30A Three Phase Input*
Heater Break Alarm, 0-100A Three Phase Input*
Code
0
1
Alarm 3
No alarm
Relay, 1A, 250 Vac
Code
0
1
Contact In
None
5 Digital Inputs
Code
0
6
8
Digital Communications
None
RS-485/RS-422 Modbus
RS 232 - Modbus
Code
0
1
33401
V
R
4
1
00
0
6
NOTE: Each alarm output is common to all channels.
*Heater break is not available when the control output is 0-20mA or 4-20 mA.
6
Splashproof Cover
Not Included
IP65
1 Typical Model Number
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563
3340/3380 Multiloop Controller
ORDERING INFORMATION
Model
3380 Eight Loop Autotuning PID Tempeature Controller
Code Input
1
Thermocouple J, K, R, S, B, E, PLII, N, T, U, L
3
Analog Vdc 0-5, 0-10, 1-5 Vdc
4
RTD, 100 ohm Plt
Code
R
V
T
7
8
Control Output 1-4
Relay 3 amp, 250 Vac
SSR drive, 12 Vdc at 20 ma
Triac, 0.5 A
0-20 ma up to 600ohms
4-20 ma up to 600ohms
Code
R
V
T
7
8
Control Output 5-8
Relay 3 amp, 250 Vac
SSR drive, 12 Vdc at 20 ma
Triac, 0.5 A
0-20 ma up to 600ohms
4-20 ma up to 600ohms
Code
3
4
Instrument Power
24 Vac/Vdc
100-240 Vac
Code
1
Alarm 1
Relay, 1A, 250 Vac
Code
0
1
2
3
Alarm 2
No alarm
Relay, 1A, 250 Vac
Heater Break Alarm, 0-30A Single Phase Input*
Heater Break Alarm, 0-100A Single Phase Input*
Code
0
1
Alarm 3
No alarm
Relay, 1A, 250 Vac
Code
0
1
Contact In
None
5 Digital Inputs*
Code
0
6
8
Digital Communications
None
RS-485/RS-422 Modbus*
RS 232 - Modbus*
Code
0
1
Splashproof Cover
Not Included
IP65
33801
V
8
4
1
30
0
6
1 Typical Model Number
NOTE: Each alarm output is common to all channels.
* Heater Break alarm and communication/contact input cannot be specified on the same hardware.
* Heater Break is not available when the control output is 0-20 mA or 4-20 mA.
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563
7
3340/3380 Multiloop Controller
Stocked Items
3340
Part Number
3340-1R04100000
3340-4R04100000
3340-1V04100000
PCN
317884
317892
317905
Description
4 channel, with 4 Relay, TC
4 channel, with 4 Relay, RTD
4 channel, with SSR Drive, TC
PCN
317770
317788
317809
317817
317825
317833
317841
317850
317868
317876
Description
8 channel, with 8 Relay, TC
8 channel, with 8 Relay, RTD
8 channel, with 8 Triac, TC
8 channel, with 8 Triac, RTD
8 channel, with 8 SSR drive, TC
8 channel, with 8 SSR drive, RTD
8 channel, with 8 SSR drive, TC, 2 additional alarms
8 channel, with 8 SSR drive, RTD, 2 additional alarms
8 channel, with 8 SSR drive, TC, RS485
8 channel, with 8 SSR drive, RTD, RS485
PCN
339135
339143
339151
339160
314448
Description
Current Transformer, 0-30.0Aac for Heater Break Option
Current Transformer, 0-100.0Aac for Heater Break Option
Control Relay module for outputs 1-8
SSR drive module for outputs 1-8
Snubber
3380
Part Number
3380-1RR4100000
3380-4RR4100000
3380-1TT4100000
3380-4TT4100000
3380-1VV4100000
3380-4VV4100000
3380-1VV4111000
3380-4VV4111000
3380-1VV4100060
3380-4VV4100060
Accessories
Part Number
700462222
700462223
700562224
700462225
0149-01305
3.6 (91.8)
Dimensions
Units: Inches (mm)
Mounting bracket
Up to 4 mounting brackets can be used.
3.78
(96)
3.94
(100)
8
4.36 (110.8)
3.6
92
3.6 (91.8)
3.78
(96)
PDS 3300
May 2002
Chromalox® • 1382 Heil Quaker Boulevard • LaVergne, Tennessee 37086 • PH: 1-888-996-9258 • FX: 615-793-3563