SVA
INSTRUCTION MANUAL
SIGNAL TRANSMITTER
BEFORE USE ....
INSTALLATION
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
Detach the yellow clamps
located at the top and bottom of the unit for separating the body from the
base socket.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) (1)
Input resistor is provided only with current input type.
SVA
MODEL
(isolated; max. 200mA output)
Clamp
(top & bottom)
DIN Rail
35mm wide
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic maintenance procedures.
■ DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
Spring Loaded
DIN Rail Adaptor
of base socket on the DIN
rail and push in the lower. Shape and size of the base socket are
When removing the slightly different with various socket types.
socket, push down the DIN
rail adaptor utilizing a screwdriver (–) and pull.
COMPONENT IDENTIFICATION
■ WALL MOUNTING
Refer to the drawings in the following page.
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
Body
Base Socket
Connection
Diagram Label
TERMINAL CONNECTIONS
Front Cover
Input Resistor
Connect the unit as in the diagram below or refer to the
connection diagram label on top of the unit.
When an input resistor is provided with the module, attach
it together with input wiring to the input screw terminals.
Specification
Label
+
■ HOW TO OPEN THE FRONT COVER:
Position your finger on the hook at the top of front cover and
pull.
INPUT
R
–
*
3
1 +
4
2 –
OUTPUT
7 U(+)
POWER
8 V(–)
*Input shunt resistor attached for current input.
CHECKING
The shape of base socket may be different
for some models.
■ FRONT PANEL CONFIGURATIONS
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
–␣ 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the described specifications.
Zero Adj.
Span Adj.
Front Cover (open)
P. 1 / 2
EM-1309
SVA
• Be sure that the ventilation slits are not covered with
cables, etc.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■ HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure
1) – 3).
POINTS OF CAUTION
■ GENERAL
•Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the "ADJUSTMENT PROCEDURE" explained earlier.
■ ENVIRONMENT
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +50°C (23
to 122°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
mm (inch)
■ TERMINAL ASSIGNMENTS
■ DIMENSIONS
INPUT RESISTOR
(model: REM)
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
107 (4.21)
127 (5)
5
4
3
7
8
1
2
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
50 (1.97)
6
40 (1.57)
[3.3 (.13)]
6
5
4
3
7
8
1
2
80 (3.15)
80 (3.15)
35.4 (1.39)
DIN RAIL
35mm wide
12 (.47)
DRAWINGS
50 (1.97)
Input shunt resistor attached
for current input.
•When mounting, no extra space is needed between units.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 2 / 2
EM-1309
">