ITYS
1 - 1 0 k V A
安装及操作手册
CN
Installations- und bedienungsanleitung
DE
Manual de instalación y uso
ES
Manuel d’installation et d’utilisation
FR
Installation and operating manual
GB
Manuale di installazione e uso
IT
Installatie– en bedieningshandleiding
NL
Dokumentacja Techniczno-Ruchowa
PL
Manual de instalação e funcionamento
PT
Manual de instalare şi utilizare
RO
Руководство по установке и эксплуатации
RU
Navodila za priključitev in uporabo
SI
Kurulum ve kullanım kılavuzu
TR
WARRANTY CERTIFICATE AND CONDITIONS
This SOCOMEC appliance is guaranteed against manufacturing and material defects for a period of 12 months from the date of purchase (local warranty conditions are applicable in addition to the general conditions). This warranty certificate should NOT be e-mailed, but kept by the customer along with proof of purchase, for use in the event of a claim being made for repairs or replacement under warranty.
The warranty period commences on the date the new product was purchased by the end user at an authorised showroom (reference details are shown on the receipt).
Return-to-base warranty is provided: components and labour for repairs supplied free of charge, any products to be replaced must be returned to SOCOMEC or authorised service centres, at the customer’s own risk and expense.
The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall be limited to the cover of the parts used to repair the fault.
To claim service under the warranty please observe the following:
• The product must be returned in the original packing. Any damage caused during shipping in packaging other than the original will not be covered by the warranty;
• The product must be accompanied by proof of purchase such as an invoice or receipt indicating the date of purchase and product ID information (model, serial numer). The sender must also attach the reference number issued to authorise the return of the product, together with a detailed description of the defect. If any of this information is missing the warranty will be invalid.
The authorisation number is issued by service centres over the telephone on receiving information on the malfunction in question;
• If it is not possible to provide proof of purchase the serial number and date of manufacture will be used to calculate the probable expiry date of the warranty; this could result in a reduction of the original warranty period.
The warranty on the product does not cover damage caused by carelessness (improper use: wrong input power, explosions, excessive humidity, temperature, poor ventilation, etc.), tampering or any unauthorised repair work.
During the warranty period, SOCOMEC reserves the right to decide whether the product should be repaired, or whether to replace defective parts with new parts, or used parts that are equivalent to new parts in terms of functionality and performance.
In the case of batteries, warranty is valid only if the battery has been recharged regularly in accordance with the manufacturer’s instructions. On purchasing the product it is advisable to check that the next recharge date indicated on the packaging has not expired.
Battery
• Batteries are treated as consumable parts and warranty only covers manufacturing defects.
• Batteries must be stored in compliance with Supplier recommendations.
• Warranty is valid only if the battery has been recharged regularly in accordance with the manufacturer’s instructions. On purchasing the product it is advisable to check that the next recharge date indicated on the packaging has not expired.
Optionals
A 12-month return-to-base warranty is provided on optionals.
Software products
Software products are guaranteed for 90 days. The software is guaranteed to work as indicated in the manual accompanying the product. Hardware media or accessories (e.g. diskettes, cables, etc.) used with appliances are guaranteed free of material or manufacturing defects under normal conditions of use for a period of 12 months from the date of purchase.
SOCOMEC will not be responsible for damages (including loss of income, interruption of business activity, loss of information or other financial losses, of any nature) arising from the use of the product.
These conditions are subject to Italian law. Disputes shall come under the jurisdiction of Court of Vicenza.
SOCOMEC retains the full and exclusive ownership rights over this document. Only a personal right to utilize the document for the application indicated by SOCOMEC is granted to the recipient of such document. All reproduction, modification, dissemination of this document whether in part or whole and by any manner are expressly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC reserves the right to make any changes to data without prior notice.
2
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
TABLE OF CONTENTS
1. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 DESCRIPTION OF THE SYMBOLS USED ON LABELS ATTACHED TO THE UNIT . . . . . . . . 5
2. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. REAR VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. CONNECTION OF BATTERY EXTENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 SAFETY WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 CONNECTION OF BATTERY EXTENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.1 MIMIC PANEL FOR ITYS 1-3 KVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7. OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.1 OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.2 BATTERY RECHARGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.3 SWITCHING THE ITYS ON AND OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.4 SETTING MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8. VISUAL AND AUDIBLE WARNING SIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 ALARM INDICATION (ITYS 1-3 KVA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9. COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1 USB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.2 WEB/SNMP CARD (OPTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.3 RS232 INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11. TECHNICAL SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
12. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12.1 ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
13 REAR VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
14. CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15. CONNECTION OF BATTERY EXTENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
15.1 SAFETY WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
15.2 CONNECTION OF BATTERY EXTENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
16. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
17. OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
17.1 SWITCHING THE ITYS ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
17.2 SWITCHING THE ITYS OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
17.3 OPERATING MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
17.4 MENU TREE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
17.5 OPERATION WITH MANUAL BY-PASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
17.6 OPERATION FROM MANUAL BY-PASS TO NORMAL OPERATION . . . . . . . . . . . . . . . . . 32
18. VISUAL AND AUDIBLE WARNING SIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
19. COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
19.1 USB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
19.2 WEB/SNMP CARD (OPTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
19.3 RS232 INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
19.4 DRY CONTACT INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
20. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
21. TECHNICAL SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
3
1. SAFETY STANDARDS
1.1. IMPORTANT
This manual should be kept in a safe place near the UPS, so it can be consulted by the operator at any time for information that may be needed regarding correct use of the unit. Read the manual carefully before connecting the unit to the a.c. mains supply and the downstream appliances. Before the UPS is put into commission the user should be completely familiar with its operation, the position of all the controls and the technical and functional characteristics of the unit, so as to ensure there will be no risk to people or the appliance itself.
• Before being started, the unit must be equipotentially bonded, in accordance with current safety regulations. The earth wire of the
UPS must then be connected to an efficient earth system.
• If there is no earth connection, the appliances connected to the UPS will not be equipotentially bonded. In this situation, the manufacturer declines all liability for any damage or accidents that could result from failure to observe the requirements.
• Should a power outage occur (UPS in stand-alone mode), do not disconnect the power cord from the mains, as this will break the earth connection to bonded appliances.
• All subsequent maintenance operations must only be performed by authorised service engineers. The UPS generates high internal voltages that could be hazardous for a maintenance operative not in possession of the appropriate skills and training for this type of work.
• If a hazardous situation should arise at any time when the UPS is in use, isolate the unit from the power supply (by operating a switch at the upstream PDU if possible) and switch the appliance off completely by running the shutdown procedure.
• The UPS houses a source of electrical energy, i.e. its batteries. The output of the UPS may be powered even when the appliance is not connected to the a.c. mains supply.
• Never force, break or attempt to open the batteries. These batteries are sealed, maintenance-free components containing substances that are harmful to health and a source of environmental pollution. If liquid can be seen leaking from the battery, or a white powdery residue is noticeable, do not switch the UPS on.
• Avoid exposing the UPS to contact with water or any liquids generally. Do not insert foreign objects into the cabinet.
• Danger of explosion if the batteries are replaced with others of the wrong type.
• Replaced batteries must be disposed of at authorised waste disposal centres.
It is very dangerous to touch any part of the batteries as there is no insulation between the batteries and the mains power source.
CAUTION!
A battery can present a risk of electrical shock and high short circuit current.
• If the appliance is to be disposed of it should only be entrusted to a specialist waste disposal company. These companies will dismantle and dispose of the various components in accordance with statutory regulations in the country of purchase.
• Use the UPS in accordance with the technical specifications indicated in this manual.
• To meet Emergency Switch Device (ESD) operating requirements, a specific input with remote ESD/EPO function is available.
• In the event that the equipment has no automatic backfeed protection contactor device, ensure that:
- the user/installer attaches warning labels to all mains isolating switches located remotely from the area where the UPS is situated,
in order to inform service personnel that the circuit is connected to a UPS.
- an external isolating device is installed
• The product you have selected, given the specified conditions of use, capacity and performance limits, is designed exclusively for commercial and industrial operation. Using the product in critical applications could require compliance with statutory regulations and standards, specific local bylaws, or adaptation to SOCOMEC recommendations. For this type of use it is always advisable to contact SOCOMEC beforehand for confirmation regarding the capacity of products to meet required levels of safety, performance and reliability. Critical applications include, in particular, life support systems, medical applications, commercial transport, nuclear facilities or any other systems where failure of the product might on occasion cause serious damage to people or property.
4
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
1. SAFETY STANDARDS
WARNING!
This is a product for commercial and industrial applications in an industrial environment – installation restrictions or additional measures may be needed to prevent interference.
CAUTION IF DAMAGED
NON-SPILLABLE BATTERIES
Torn, crushed or damaged packaging which exposes the contents should be set aside in an isolated area and inspected by a qualified person. If the package cannot be shipped the contents must be promptly collected, segregated, and either the sender or recipient contacted.
All packaging material must be recycled in compliance with the laws in force in the country where the system is installed.
1.1.1. Only for ITYS 1-3 kVA
• Since the UPS power cord functions as an isolating device, ensure ready access to the mains power socket where the UPS is connected, and/or the rear panel of the UPS, so the unit can be easily unplugged.
• The UPS generates a leakage current of approximately 3 mA. To guarantee the maximum leakage current of 3.5 mA, ensure the leakage current generated by the load is no greater than 0.5 mA. Should the leakage current from the load exceed this limit, instruct a skilled engineer to install an industrial type connection (to IEC 309 standard) between the UPS and the a.c. mains supply, sized to handle a current compatible with the rating of the appliance.
1.1.2. Only for ITYS 6-10 kVA
If the UPS does not have an automatic protection device against current back feed, the operator/installer must:
- add warning labels to all the mains power disconnecting switches installed at a distance from the UPS area; this serves to remind technicians of the fact that the circuit is connected to a UPS.
- install an external isolating device as shown in figure.
ISOLATE THE UPS BEFORE
OPERATING ON THIS CIRCUIT
External distribution panel
Q
T
L
N
L
N
UPS
B
Legend
B Coil
Q Magneto-thermal input main switch
T 90 A AC1 remote contactor 2-pole; 230 V coil
THE UNIT
Comply with all precautions and warnings on labels and plates on the inside and outside of the equipment.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
GROUND TERMINAL
READ THE USER MANUAL BEFORE USING THE UNIT
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
5
2. INSTALLATION
2.1. ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION
Consult the following check list when installing the UPS:
• ITYS units are designed for use in enclosed environments.
• Position the UPS on a flat, stable surface in a properly ventilated room, well away from heat sources and avoiding direct exposure to sunlight.
• Ambient temperature should be kept between 0 to 45 °C, and relative humidity below 90% (without condensation); the optimum temperature to maximise battery lifetime is 15 to 20 °C.
• Check that the UPS will not be installed in a dusty environment.
• Ensure clearance of at least 20 cm on all sides of the unit to ensure adequate ventilation and provide access to the rear panel.
• Take care not to stand the UPS or any other heavy objects on cables.
• Check that the operating voltage and frequency settings are correct for the mains power supply at the installation site. Details for the UPS will be found on the data plate attached to the rear panel.
• When carrying out the RS232 serial connection, use only the cables and accessories supplied or specified by the manufacturer.
• When the UPS is first used, it is advisable to leave the battery on charge for a minimum of 8 hours.
• Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be completely dry before being installed. Please allow at least two hours for the UPS system to become acclimatised to the environment.
• Do not install the UPS system near water or in damp environments.
• Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
• Ensure there is a reliable earth connection.
• Ensure external battery sources are earthed.
PRECAUTIONS IN THE EVENT OF DAMAGE
DO NOT TURN THE BATTERIES OVER
Torn, crushed or damaged packaging which exposes the contents should be kept separate in a secure area, and inspected by qualified staff. Packing which cannot be shipped must be set aside immediately and kept secure, and the sender or recipient contacted.
2.1.1. Only for 1-3 k
• Connect the UPS system to an earthed shockproof outlet only, which is easily accessible and close to the UPS system.
• Do not block ventilation openings on the UPS casing. Ensure the air vents on the front, side and rear of the UPS are not blocked.
Allow at least 25cm of space on each side.
2.1.2. Only for 6-10 k
• This is permanently connected equipment and must be installed by qualified maintenance personnel.
• The overload capacity would be de rated automatically in Line mode while the circumstance temperature is larger than 35 degree.
• Do not block ventilation openings on the UPS casing. Ensure at least 50 cm of space at the front and back of the UPS.
6
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
ITYS
1 - 3 k V A
3. ELECTRICAL REQUIREMENTS
The fixed power distribution unit must include protection and isolation for the utility supply and the back-up supply. In the event that a residual current device is installed on the UPS input line (optional), this must be located upstream of the power distribution unit.
Electrical requirements
UPS Thermal-magnetic switch on input
1 kVA 10 C
2 kVA
3 kVA
16 C
20 C
Input leakage current
< 3.5 mA
< 3.5 mA
< 3.5 mA
Cable section according to IEC according to IEC according to IEC
8
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
4. REAR VIEW
Connection to the mains power supply and to the load(s) must be made using cables of suitable cross section, in accordance with current standards.
If not already provided, install a PDU panel allowing isolation of the mains supply upstream of the UPS. The panel must be equipped with an automatic switch rated high enough to handle the current draw on full load, and with a residual current device.
USB serial port
RS232 serial connector
Fan
EPO (Emergency Power Off)
Slot for optional communication cards
Battery extension socket
Output sockets
OUT 230 V~
3 x IEC 320
Input protection
Mains input socket
230 V~
Use the power cable provided (IEC 320)
ITYS 1 k
USB serial port
RS232 serial connector
Fan
EPO (Emergency Power Off)
Slot for optional communication cards
Battery extension socket
Output sockets
OUT 230 V~
6 x IEC 320
Input protection
Mains input socket
230 V~
Use the power cable provided (IEC 320)
ITYS 2 k
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
9
4. REAR VIEW
USB serial port
RS232 serial connector
Fan
Input protection
Mains input socket
230 V~
Use the power cable provided (IEC 320)
ITYS 3 k
EPO (Emergency Power Off)
Slot for optional communication cards
Battery extension socket
Output socket (full power)
230 V~
4 x IEC 320
OUT 230 V~
3 x 2,5 mm 2
Output socket
10
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
5. CONNECTION OF BATTERY EXTENSION
• Before connecting the battery extension, check that it is fully compatible with the model of UPS in use.
• The use of battery extensions not supplied by the manufacturer is inadvisable.
WARNING!
There is a risk of explosion if battery modules are replaced with others of incorrect type.
• Depleted batteries are considered as toxic waste. When battery replacement becomes necessary, release all depleted batteries only to certified and licensed waste disposal companies. In accordance with local bylaws, it is absolutely forbidden to dispose of batteries together with other industrial waste or household refuse.
WARNING!
It is extremely dangerous to touch any part of the battery storage unit.
5.2. CONNECTION OF BATTERY EXTENSION
When connecting the UPS to the battery extension, use only the cable provided with the equipment.
Any wiring error that results in the polarity of the battery being inverted can cause permanent damage to the equipment.
• Connect the External Battery cable on the rear of the UPS.
5.2-1
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
11
6. MIMIC PANEL
The mimic panel on the front of the UPS provides all essential information on the operating status of the appliance.
6.1. MIMIC PANEL FOR ITYS 1-3 kVA
Select
There is Load
Enter OFF
Load Level
(5 steps)
Battery status
ON/Alarm Silence
General Alarm
Overload
Input main present
Output
Value
Battery bad/fault
Setting details
12
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
7. OPERATING MODES
Normal mode Battery mode
Icon will fl ash every second
Standby mode
Confi g mode Eco Mode Converter Mode
Connect the UPS to the mains voltage for approximately 8 hours to recharge the internal batteries.
The UPS can be used even with the batteries not fully charged, though if a power cut occurs backup duration will be shorter.
7.3. SWITCHING THE ITYS ON AND OFF
7.3.1. Switching on with mains present
7.3.1-1
Standby mode
7.3.1-2
Normal mode
1 sec
Power up all loads, one at a time.
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
13
7. OPERATING MODES
7.3.2. Switching on with no mains power
7.3.2-1 7.3.2-2
Normal mode
1 sec
Power up all loads, one at a time.
7.3.3. Switching off with mains present
7.3.3-1
Normal mode
7.3.3-2 Standby mode 7.3.3-3
• UPS is off but battery remains on charge
• Shut down all loads, one at a time.
• Switch off mains power to shut down completely.
1 sec
7.3.4-1
Normal mode
7.3.4-2
1 sec
14
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
7. OPERATING MODES
7.4-1
Standby mode
7.4-2
Function Description
OPV Output voltage selection
OPF
MODE
Output frequency selection
Work mode select
STY Auto bypass enable disable
1 sec
Settings
[208] = 208 V
[220] = 220 V
[230] = 230 V
[240] = 240 V
[050] = 50 Hz
[060] = 60 Hz
[UPS] = Normal
[ECO] = ECO mode
[CVF] = Converter mode
[000] = disable
[001] = enable
Default settings
[230]
[050]
[UPS]
[000]
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
15
8. VISUAL AND AUDIBLE WARNING SIGNALS
8.1. ALARM INDICATION (ITYS 1-3 kVA)
Battery replace or battery disconnect Overload alarm
Low battery mode
Icon will fl ash every second
Icon will fl ash every second
Fault mode (over temperature)
The following table shows the description of the LCD display string:
Warning
Site fail
Fan fail
Battery over voltage (over charged)
Battery low
Charge fail
DC-DC temperature high
Inverter temperature high
Ambient temperature high
Line voltage high (OVCD action)
Battery open
Overload 29
EPO active 30
25
26
27
11
12
13
21
24
Code
09
10
Fault
Bus fault
Inverter fault
Overload fault
Over temperature fault
Inverter short
Bus short
08
14
28
Code
05
06
07
16
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
9. COMMUNICATION
Communication software and accessories are available for monitoring the status of the UPS, with the end in view of optimizing normal operation and ensuring that shutdown at the end of backup time is managed correctly. Applications allow recording of all power outages and any depletion of battery power so as to enable the activation of an automatic procedure for closing programs in ordered sequence and shutting down the system.
ITYS no-break systems are equipped with RS232 serial communication interface, and slots for NetVision cards.
The UPS can communicate with the server direct by way of the USB interface, if available on the computer operating system, without the need to install any additional software. Once connected, recognition of the UPS occurs in the same way as for any other peripheral, and the operating parameters can be managed by way of the OS service menu. Use the connecting cable provided.
9.2. WEB/SNMP CARD (OPTION)
With this card installed, the UPS can be connected directly to a LAN (RJ45 ethernet) and controlled remotely from a WEB browser using TCP/IP protocol. Reference should be made to the relevant literature for a full description of functionality.
Communication with the server can take place directly via the RS232 interface.
In addition to local or networked shutdown it is possible to perform full monitoring of the electrical parameters regarding battery status and the automatic programming of the UPS start-up and shutdown procedures.
For a complete description of the software features, refer to the UniVision and UniVision Pro documentation.
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
17
10. TROUBLESHOOTING
WARNING!
If problems persist or recur frequently after following the procedures indicated in this section contact the
SOCOMEC After Sales Service, providing a full description of the problem.
Problem
The UPS works in battery mode even if mains power is available
Back-up time shorter than expected
The UPS stalls/goes into overload alarm
Possible cause
Poor connection to the input mains
The mains voltage is out of range
Input protection triggered (blown fuse or automatic switch)
Batteries not fully charged
Batteries not working properly
Overload on the load line
Solution
Check the connection of the cable to the
UPS and to the mains outlet
No solution because mode of operation is correct
Replace the input fuse with another of the same type or reset the automatic switch
Leave the batteries to charge for 8 hours consecutively
Have the batteries replaced by authorised personnel
Check that the load applied is not greater than the maximum permitted or reduce the load power requirement
18
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
10. TROUBLESHOOTING
If the UPS system does not operate correctly use the table below to try and resolve the problem.
Problem
No indication, no warning tone even though system is connected to mains power supply
Possible cause
No input voltage
Remedy
Check building wiring socket outlet and input cable.
Displays battery modes, and alarm Mains power supply has failed, or input sounds every 4 seconds power and/or frequency are outside tolerance limits
Switching to battery mode automatically.
Check input power source.
Backup time shorter than nominal value Batteries not fully charged / batteries defect
Fan failure Fan abnormal
Charge the batteries for at least 5 - 8 hours and then check capacity. If the problem still persists, consult your dealer.
Check if the fan is running
Battery over voltage
Battery low
Battery is over charged
Battery voltage is low
Switch to battery mode automatically, and after the battery voltage is normal and the mains is normal, the UPS should switch to line mode automatically again.
When alarm sounds every second battery is almost empty.
Charge failure
DC-DC temperature high
Inverter temperature high
Ambient temperature high
Line voltage high (OVCD action)
The charge is broken Notify dealer.
Internal UPS temperature too high Check UPS ventilation of the UPS, check the ambient temperature.
Inside temperature of the UPS is too high Check the ventilation, check ambient temperature.
The ambient temperature is too high Check room ventilation.
Battery open
Overload
Site failure
EPO active
Bus fault
Inverter fault
Over temperature fault
Inverter short
Bus short
Input power voltage is too high
Battery pack is not connected correctly Do the battery test to confi rm.
Check the battery bank is connected to the UPS.
Check the battery breaker is turned on.
Overload
Switch to battery mode automatically, after the mains is normal the UPS should switch to line mode automatically again.
Check the loads and remove some noncritical loads.
Check whether some loads have failed.
Phase and neutral conductor at input of
UPS system are reversed
Rotate mains power socket by 180° or connect UPS system.
EPO function is enabled
UPS internal fault
UPS internal fault
Over temperature
Turn off the EPO switch.
Notify dealer
Notify dealer
Output short circuit
Check UPS ventilation, check ambient temperature and ventilation.
Remove all the loads. Turn off the UPS.
Check whether the output of UPS and loads have short circuited. Make sure the short circuit is removed, and the UPS has no internal faults before turning on again.
UPS internal fault Notify dealer
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
19
11. TECHNICAL SPECIFICATION
Models
Nominal Power
Input/Output phases
Electrical Specifications - Input
Mains voltage (Vin)
Input frequency
VA/W
Vin
Hz
Input power factor
THDI
Electrical Specifications - Output
Output Voltage V
1
1000/800
1/1
1 (LB) 2 2 (LB)
2000/1600
1/1
110 to 300 V Derating to 50 % @ 110 V input
45 to 55/54 - 66
≥ 0.99
< 5 % with full load
3 3 (LB)
3000/2400
1/1
Frequency
Overload – Normal
Mode (@ 25°C)
1 m
30 s
10 s
1 s
Hz
%
Crest Factor
Voltage distortion %
Electrical Specificationsn - Battery
Type
Voltage
208/220/230/240 V ± 2 %
Output power must derating to 90 % when the output voltage rate be set with 208 V
45-55/54 to 66 Hz (50/60 Hz ± 0.2 Hz in Battery Mode or Converter Mode)
105 to 110
110 to 125
125 to 150
> 150
3:1
< 5 % Non Linear Load; < 3 % Linear Load
BUT
Charger
Enviroment
Operating temperature
Relative humidity
Max. altitude
Acoustic noise
Standards
Safety
EMC
Product Certification
Protection Level
°C
% m dBA
> 5 min
-
36
Sealed lead acid maintenance free-expected life 3/5 years
96 96
-
8 A
Mechanical Characteristics with standard batteries
Dimensions (W x D x H) mm 145 x 400 x 220
Weight kg 13 7
> 9 min
-
0 to 40
1
20 to 90 No Condensing
< 1000 m without derating up to 50 dB at front 1 m
EN 62040-1, EN 60950-1
EN 62040-2
CE
IP20
192 x 460 x 347
31
-
8 A
13
> 5 min
-
-
8 A
192 x 460 x 347
31 13
1. 15-25 °C for a longer battery life.
20
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
ITYS
6 - 1 0 k V A
12. SAFETY STANDARDS
12.1. ELECTRICAL REQUIREMENTS
The installation and the system must comply with pertinent national statutory regulations.
The fixed power distribution unit must include protection and isolation for the utility supply and the back-up supply. In the event that a residual current device is installed on the UPS input line (optional), this must be located upstream of the power distribution unit.
Electrical requirements
UPS
6 kVA
10 kVA
Thermal-magnetic switch on input
40 C
63 C
Input leakage current
0.1 A type A
0.1 A type A
Cable section
6 mm 2
10 mm 2
WARNING!
Use type A two-pole selective (S) RCDs. Any leakage currents at the loads will be added to that of the UPS, so that current peaks can occur during transients (loss and restoration of mains supply), although these will be of very short duration. Where loads generate high leakage current, ensure the rating of the RCD is suitably matched.
Always conduct a preliminary test for current leakage to earth. When connecting the UPS to the mains and the load, it is strongly recommended that protective devices are installed. The protective devices must use approved components that meet safety standards.
Always refer to local wiring regulations for correct cable sizes and protective device ratings depending on installation environment.
22
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
13. REAR VIEW
Fan
USB serial port
RS232 serial connector
EPO (Emergency Power Off)
Dry contact
Slot for optional communication cards
Parallel port
Input protection
(magneto-thermal)
Input and output terminal board
Manual bypass
Fuse Holder
ITYS 6 k
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
23
Input protection
(magneto-thermal)
Input and output terminal board
Fan
13. REAR VIEW
USB serial port
RS232 serial connector
EPO (Emergency Power Off)
Dry contact
Slot for optional communication cards
Parallel port
Manual bypass
Fuse Holder
ITYS 10 k
24
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
14. CONNECTIONS
The installation and the system must comply with national plant regulations. If a differential switch is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel.
CAUTION!
Use selective type differentials. Any current dispersed by the loads will be summed to that of the UPS. The differential protection must be regulated in cases of loads with high current dispersion.
Mains
UPS
ø UPS ø
(mm²) (mm²)
≥ 6 6 kVA ≥ 6
≥ 10 10 kVA ≥ 10
Output
14-1 14-2
NA N L + N L
14-3
N L + N L
6 to 10 kVA
14-4
OUTPUT
BATTERY
14-5
N L + N L
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
25
15. CONNECTION OF BATTERY EXTENSION
15.1. SAFETY WARNINGS
• Before connecting the battery extension, check that it is fully compatible with the model of UPS in use.
• The use of battery extensions not supplied by the manufacturer is inadvisable.
WARNING!
There is a risk of explosion if battery modules are replaced with others of incorrect type.
• Depleted batteries are considered as toxic waste. When battery replacement becomes necessary, release all depleted batteries only to certified and licensed waste disposal companies. In accordance with local bylaws, it is absolutely forbidden to dispose of batteries together with other industrial waste or household refuse.
WARNING!
It is extremely dangerous to touch any part of the battery storage unit.
15.2. CONNECTION OF BATTERY EXTENSION
When connecting the UPS to the battery extension, use only the cable provided with the equipment.
Any wiring error that results in the polarity of the battery being inverted can cause permanent damage to the equipment.
• Connect the battery cabinet to ground.
• Connect the External Battery cable on the rear of the UPS.
• Connect the cables to the battery cabinet terminals, respecting polarity very carefully.
15.2-1
Breaker
Terminal
Block cover
26
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
16. MIMIC PANEL
Battery
Bypass mode
Normal mode Fault
1. Press for 1 second
ON/OFF
Up/Exit 1 Down
Enter
Battery status
Input
Bypass Output Load
Output load
Alarm icon
Inverter
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
27
17. OPERATING MODES
17.1. SWITCHING THE ITYS ON
17.1-1 17.1-2
5 sec
17.1-4
17.1-3
17.2. SWITCHING THE ITYS OFF
17.2-1 17.2-2
5 sec
17.2-4
Wait for the complete shutdown.
17.2-5
17.2-3
28
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
17. OPERATING MODES
17.3. OPERATING MODE
17.3-1
Line mode
17.3-2
Battery mode
17.3-3
UPS OFF
17.3-4
HE mode
17.3-5
Converter Mode
17.3-6
Manual Bypass
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
29
17. OPERATING MODES
17.4. MENU TREE
FIRST LEVEL
UPS STATUS
EVENT LOG
MEASUREMENTS
COMMANDS
IDENTIFICATION
SERVICE
SECOND LEVEL THIRD LEVEL
BUZZER MUTE
SINGLE UPS BATTERY TEST
CLEAR EPO STATUS
RESET FAULT STATE
CLEAR EVENT LOG
RESTORE FACTORY SETTINGS
Buzzer Mute: no
Status: battery test
Schedule battery test: no
Status EPO active
Clear: no
Status: Fault active
Reset fault: no
Total events: 50
Clear event log: no
Reset: no
USER PASSWORD
AUDIO ALARM
RATED OUTPUT VOLTAGE
OUTPUT FREQUENCY
POWER STRATEGY
DC START
SITE WIRING ALARM enabled/disabled enabled/disabled
208/220/230/240 V autosensing 50/60 Hz normal/high effi ciency/ converter enabled/disabled enabled/disabled
AMBIENT TEMPERATURE WARNING enabled/disabled
AUTOMATIC BATTERY TESTS PERIOD 0 to 31days
AUTO RESTART enabled/disabled
AUTOMATIC OVERLOAD RESTART
AUTO BYPASS
SHORT CIRCUIT CLEARANCE
BYPASS VOLTAGE LOW LIMIT
BYPASS VOLTAGE HIGH LIMIT enabled/disabled enabled/disabled enabled/disabled
110 to 215 V
245 to 276 V
BYPASS FREQUENCY LOW LIMIT
BYPASS FREQUENCY HIGH LIMIT
HE VOLTAGE LOW LIMIT
HE VOLTAGE HIGH LIMIT
HE FREQUENCY LOW LIMIT
HE FREQUENCY HIGH LIMIT
BATTERY QUANTITY
SET RUNNING TIME
LCD CONTRAST
1 to 10 %
1 to 10 %
1 to 10 %
1 to 10 %
1 to 10 %
1 to 10 %
19/20/21
Day:hour:minute:second
0000:0000:00~9999:23:59:59
-5 to +5
30
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
17. OPERATING MODES
17.5. OPERATION WITH MANUAL BY-PASS
If the maintenance bypass is activated using the appropriate procedure, the load is powered directly from the maintenance bypass, while the UPS is separated from the power supply.
WARNING!
In this mode continuity is not guaranteed in the event of a mains power failure.
This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions can be performed by service personnel without having to disconnect the power supply to the load.
17.5-1 17.5-2 17.5-3
17.5-4 17.5-5
17.5-6
17.5-7
Wait for the complete shutdown.
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
31
17. OPERATING MODES
17.6. OPERATION FROM MANUAL BY-PASS TO NORMAL OPERATION
17.6-1 17.6-2 17.6-3
17.6-4 17.6-5 17.6-6
17.6-7
5 sec
17.6-8
32
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
18. VISUAL AND AUDIBLE WARNING SIGNALS
I
H
A B C D
E
F
G
Key Description
Load on bypass, in Eco-mode or Maintenance bypass closed
A
Automatic bypass alarm
Battery OK
B
Battery alarm
C Output voltage present
D
Load present
Overload
E Output load indicator
Activation code alarm
F
General alarm
Inverter on
G
Inverter general alarm
Input rectifi er active, input mains OK
H
Input rectifi er general alarm/Input mains alarm
Remaining battery capacity
I
Battery recharging
Condition
Steady
Flashing
Steady
Flashing
Steady
Steady
Flashing
Steps of 10%
Steady
Flashing
Steady
Flashing
Steady
Flashing
Steps of 25%
Sequence
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
33
19. COMMUNICATION
Communication software and accessories are available for monitoring the status of the UPS, with the end in view of optimizing normal operation and ensuring that shutdown at the end of backup time is managed correctly. Applications allow recording of all power outages and any depletion of battery power so as to enable the activation of an automatic procedure for closing programs in ordered sequence and shutting down the system.
ITYS no-break systems are equipped with RS232 serial communication interface, and slots for NetVision cards.
19.1. USB INTERFACE
The UPS can communicate with the server direct by way of the USB interface, if available on the computer operating system, without the need to install any additional software. Once connected, recognition of the UPS occurs in the same way as for any other peripheral, and the operating parameters can be managed by way of the OS service menu. Use the connecting cable provided.
19.2. WEB/SNMP CARD (OPTION)
With this card installed, the UPS can be connected directly to a LAN (RJ45 ethernet) and controlled remotely from a WEB browser using TCP/IP protocol. Reference should be made to the relevant literature for a full description of functionality.
19.3. RS232 INTERFACE
Communication with the server can take place directly via the RS232 interface.
In addition to local or networked shutdown it is possible to perform full monitoring of the electrical parameters regarding battery status and the automatic programming of the UPS start-up and shutdown procedures.
For a complete description of the software features, refer to the UniVision and UniVision Pro documentation.
19.4. DRY CONTACT INTERFACE
This series UPS has an independent dry contact interface. Please contact your local distributor for details. The following is the pin assignment and description of the DB-9 connector.
19.4-1
UPS Fail
Summary Alarm
GND
Remote
Shutdown
Common
Bypass
Battery Low
UPS ON
Line Loss
6
7
4
5
8
9
Pin Description
1
2
3
UPS Fail
Summary Alarm
GND
Remote Shutdown
Common
Bypass
Battery Low
UPS ON
Line Loss
I/O
Output
Output
Input
Input
Input
Output
Output
Output
Output
34
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
20. TROUBLESHOOTING
Please have the following information at hand before calling the After-Sales Service Department:
• Model number, serial number
• Date on which the problem occurred
• LCD display status, Buzzer alarm status
• Utility power condition, load type and capacity, ambient temperature, ventilation conditions
• The information (battery capacity, quantity) of external battery pack if the UPS is an S model
• Other information for a complete description of the problem
IMPORTANT!
If problems persist or recur frequently after following the instructions in this chapter call the technical service centre providing a full description of the problem.
WARNING
Problem Displayed
Read EEPROM Error
Epo Active
On Maintain Bypass
IP softstart failed
Site Wiring Fault
Battery Disconnect
Battery low
Output Overload
Fan Failure
Charger failure
Battery Over Voltage
Over Charge
Model Pin Error
Ambient Over Temperature
Heatsink Over Temperature
Ambient NTC abnormal
Para Bat Differ
Para Line Differ
IP Fuse Open
Possible cause
UPS internal fault
EPO connector is open
Maintain bypass switch is open
Remedy
Consult dealer.
Check the EPO connector status
Check the maintain bypass switch status
UPS internal fault
Phase and neutral conductor at input of
UPS system are reversed
Consult dealer
Reverse mains power wiring.
Battery pack is not connected correctly Do the battery test to confi rm.
Check the battery bank is connected to the UPS
Check the battery breaker is turned on.
Battery voltage is low
Overload
When alarm sounds every second battery is almost empty.
Check the loads and remove some noncritical loads.
Fan abnormal
Check if some loads have failed.
Check if the fan is running normally.
The charge fails Consult dealer.
Battery voltage is higher than normal value Check if the battery quantity is right.
Battery is over charged The UPS will turn off the charger until the battery voltage is normal
Internal UPS fault
The ambient temperature is too high
Inside temperature of UPS is too high
Consult dealer.
Check the environment ventilation.
Check the ventilation of UPS and the ambient temperature.
Consult dealer.
UPS internal fault
The battery packs of some UPSs are disconnected
Check if all the battery pack is connected.
The mains input of some UPSs is disconnected Check the building wiring and input cable.
Check if the input breaker is closed.
Input fuse break
Ensure the UPSs are connected to same input source.
Check the input fuse status
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
35
20. TROUBLESHOOTING
FAULT
Problem Displayed
Inv Overload Fault
Byp Overload Fault
Output Short Circuit
Heatsink Over Temperature Fault
Bus Over Voltage
Bus Under Voltage
Bus Unbalance
Bus short
Bus Softstart Fail
Inv Over Voltage
Inv Under Voltage
Inv Softstart Fail
Negative Power Fault
Possible cause
Overload
Overload
Output short circuit
Remedy
Check the loads and remove some noncritical loads.
Check if some loads have failed.
Check the loads and remove some noncritical loads.
Check if some loads are failed.
Remove all the loads. Turn off the UPS.
Check if UPS output and loads have short circuited
Ensure short circuit is removed before turning on again.
Internal UPS temperature of UPS high
Internal UPS fault
Internal UPS fault
Internal UPS fault
Internal UPS fault
Internal UPS fault
Internal UPS fault
Check UPS ventilation of UPS and ambient temperature.
Consult dealer.
Consult dealer.
Consult dealer.
Consult dealer.
Consult dealer.
Consult dealer.
Internal UPS fault
Internal UPS fault
Consult dealer.
Consult dealer.
The load is pure inductive and capacitive Remove some non-critical loads.
Bypass supplies the load fi rst, ensure there is no overload, then turn on UPS.
Fan blocked or disconnected over time Check the fan status
Output voltage has returned to input Consult dealer
Fan lock fault
Backfeed
OTHER CASES
Problem Displayed Possible cause
No indication, no warning tone even though system is connected to mains power supply
No input voltage
Remedy
Check the building wiring and input cable.
BYPASS LED lights up even though the power supply is available
Inverter not switched on
BATTERY LED lights up, and alarm sounds every 4 seconds
Input voltage and/or frequency are out of tolerance
Check if the input breaker is closed.
Press On-Switch “I” to turn on UPS.
Check input power source.
Check the building wiring and input cable.
Check if the input breaker is closed.
Emergency supply period shorter than nominal value
Batteries not fully charged / battery defect Charge the batteries for at least 12 hours and then check capacity.
36
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
21. TECHNICAL SPECIFICATION
Models
6 6 (LB) 10 10 (LB)
Nominal Power
Input/Output phases
Electrical Specifications - Input
Mains voltage (Vin)
Input frequency
VA/W
Vin
Hz
Input power factor
THDI
Electrical Specifications - Output
Output Voltage V
6000/5400
1/1
220/230/240 V; 1 Ph (L/N) + PE, 3-wire
50/60
≥ 0.99
< 5 % with full load
10000/9000
1/1
Frequency
Overload –
Normal Mode
(@ 25°C)
Overload –
Battery Mode
(@25°C)
Crest Factor
Voltage distortion
10 m
1 m
10 s
100 ms
2 m
30 s
100 ms
Hz kW kW
Electrical Specificationsn - Battery
Type
Voltage
BUT
Charger
Enviroment
Operating temperature
Relative humidity
Max. altitude
Acoustic noise
Standards
°C
% m dBA
208/220/230/240 V ±1 %; 1 Ph (L/N) + PE, 3-Wire
Output power must derating to 90 % when the output voltage rate be set with 208 V, and 80 % for 200 V
> 5 min
-
Safety
EMC
Product Certification
Protection Level
Mechanical Characteristics with standard batteries
Dimensions (W x D x H)
Weight mm kg 73
50/60 ± 0.05 %
105 to 125
125 to 150
> 150
> 170
105 to 125
125 to 150
> 150
3:1
< 5 % Non Linear Load; < 2 % Linear Load
Sealed lead acid maintenance free-expected life 3/5 years
240 V
-
4 A
> 4 min
-
50 dB at front 1 m
0 to 40 °C
1
0 to 95 % No Condensing
< 1000 m without derating
EN 62040-1, EN 60950-1
25,5
EN 62040-2 C3
CE
IP20
428 x 970 x 720
84
55 dB at front 1 m
-
4 A
29,5
1. 15-25 °C for a longer battery life.
ITYS 1-10 kVA - Ref.: IOMITYTWXX05-GB 00
37
Socomec worldwide
IN WESTERN EUROPE
BELGIUM
B - 1190 Bruxelles
Tel. +32 (0)2 340 02 34 [email protected]
FRANCE
F - 94132 Fontenay-sous-Bois Cedex
Tel. +33 (0)1 45 14 63 90 [email protected]
GERMANY
D - 68309 Mannheim
Tel. +49 (0) 621 71 68 40 [email protected]
ITALY
20098 San Giuliano Milanese (MI)
Tel. +39 02 98 242 942 [email protected]
PORTUGAL
2640-486 Mafra
Tel. +351 261 812 599 [email protected]
SPAIN
E - 08329 Teià (Barcelona)
Tel. +34 935 407 575 [email protected]
THE NETHERLANDS
NL - 3991 CD Houten
Tel. +31 (0)30 760 0911 [email protected]
UNITED KINGDOM
Cirencester - GL7 5XL
Tel. +44 (0)1285 863300 [email protected]
OTHER COUNTRIES
Tel. +34 935 407 575 [email protected]
IN EASTERN EUROPE,
MIDDLE EAST, AFRICA
UNITED ARAB EMIRATES
371355 Dubai airport free zone
Dubai (United Arab Emirates)
Tel.: +971 (0) 4 29 98 441 [email protected]
POLAND
01-625 Warszawa
Tel. +48 22 825 73 60 [email protected]
ROMANIA
023383 Bucharest
Tel. +40 21 319 36 88 ( 89, 81, 82) [email protected]
RUSSIA
125167 - Moscow
Tel. +7 495 775 19 85 [email protected]
SLOVENIA
SI - 1000 Ljubljana
Tel. +386 1 5807 860 [email protected]
TURKEY
34357 Istanbul
Tel. +90 (0) 216 540 71 20 [email protected]
OTHER COUNTRIES
Tel. +39 0444 598 611 [email protected]
IN ASIA PACIFIC IN AMERICA
AUSTRALIA
Macquarie Park NSW 2113
Tel. +61 2 9325 3900 [email protected]
CHINA
Chaoyang, Beijing 100016 P.R., China
Tel. +86 10 59756108 [email protected]
INDIA
Guindy, Chennai – 600 032
Tel. +91 44 3921 5400 [email protected]
MALAYSIA
47301 Petaling Jaya.- Selangor, Malaysia
Tel. +603 7804 0850 [email protected]
SINGAPORE
Singapore 408723
Tel. +65 6506 7600 [email protected]
THAILAND
Chatujak Bangkok 10900
Tel. +66 2 941-1644-7 [email protected]
VIETNAM
Ho Chi Minh City
Tel. +84 8 3559 1220 [email protected]
ASIA PACIFIC HEAD OFFICE
Tel. +65 6506 7600 [email protected]
LATIN AMERICAN COUNTRIES
Tel. +34 935 407 575 [email protected]
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 951 300 €
R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse
F-67235 Benfeld Cedex - FRANCE
VALID FOR FRANCE VALID FOR ITALY
SALES, MARKETING AND
SERVICE MANAGEMENT
SOCOMEC Paris
95, rue Pierre Grange
F-94132 Fontenay-sous-Bois Cedex
FRANCE
Tel. +33 (0)1 45 14 63 90
Fax +33 (0)1 48 77 31 12 [email protected]
YOUR DISTRIBUTOR
*IOMITYTWXX05-GB 00*
IOMITYTWXX05-GB 00 05.2013
ISO 9001
FM 28237
ISO14001
EMS 553476
www.socomec.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
advertisement
Table of contents
- 4 1. SAFETY STANDARDS
- 4 1.1 IMPORTANT
- 5 1.2 DESCRIPTION OF THE SYMBOLS USED ON LABELS ATTACHED TO THE UNIT
- 6 2. INSTALLATION
- 6 2.1ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION
- 8 3. ELECTRICAL REQUIREMENTS
- 8 3.1 ELECTRICAL REQUIREMENTS
- 9 4. REAR VIEW
- 11 5. CONNECTION OF BATTERY EXTENSION
- 11 5.1 SAFETY WARNINGS
- 11 5.2 CONNECTION OF BATTERY EXTENSION
- 12 6. MIMIC PANEL
- 12 6.1 MIMIC PANEL FOR ITYS 1-3 KVA
- 13 7. OPERATING MODES
- 13 7.1 OPERATING MODES
- 13 7.2 BATTERY RECHARGING
- 13 7.3 SWITCHING THE ITYS ON AND OFF
- 15 7.4 SETTING MENU
- 16 8. VISUAL AND AUDIBLE WARNING SIGNALS
- 16 8.1 ALARM INDICATION (ITYS 1-3 KVA)
- 17 9. COMMUNICATION
- 17 9.1 USB INTERFACE
- 17 9.2 WEB/SNMP CARD (OPTION)
- 17 9.3 RS232 INTERFACE
- 18 10. TROUBLESHOOTING
- 20 11. TECHNICAL SPECIFICATION
- 22 12. SAFETY STANDARDS
- 22 12.1 ELECTRICAL REQUIREMENTS
- 23 13 REAR VIEW
- 25 14. CONNECTIONS
- 26 15. CONNECTION OF BATTERY EXTENSION
- 26 15.1 SAFETY WARNINGS
- 26 15.2 CONNECTION OF BATTERY EXTENSION
- 27 16. MIMIC PANEL
- 28 17. OPERATING MODES
- 28 17.1 SWITCHING THE ITYS ON
- 28 17.2 SWITCHING THE ITYS OFF
- 29 17.3 OPERATING MODE
- 30 17.4 MENU TREE
- 31 17.5 OPERATION WITH MANUAL BY-PASS
- 32 17.6 OPERATION FROM MANUAL BY-PASS TO NORMAL OPERATION
- 33 18. VISUAL AND AUDIBLE WARNING SIGNALS
- 34 19. COMMUNICATION
- 34 19.1 USB INTERFACE
- 34 19.2 WEB/SNMP CARD (OPTION)
- 34 19.3 RS232 INTERFACE
- 34 19.4 DRY CONTACT INTERFACE
- 35 20. TROUBLESHOOTING
- 37 21. TECHNICAL SPECIFICATION