RGS-TBS Series T-Bar 12V MR16 LED Unit TYPICAL SPECIFICATIONS

RGS-TBS Series T-Bar 12V MR16 LED Unit TYPICAL SPECIFICATIONS
Type:
Project/Location:
Contractor:
RGS-TBS Series
Prepared by:
Date:
T-Bar 12V MR16 LED Unit
Model:
Fully recessed units for T-Bar mounting in suspended ceilings.
TYPICAL SPECIFICATIONS
The RGS-TBS Series battery units are designed for T-Bar ceiling grid installation.
Supply and install a complete emergency lighting system as described herein
and shown on the drawings.
The Lumacell® Smart Diagnostic Micro controller board shall supply the
rated load for a minimum of a 30 minutes to 87.5% of the rated battery
voltage. The unit shall be rated 120V or 347V, 60 Hz and be CSA listed. The
V.
unit shall have an output of
The charger shall be fully computer tested and its charge voltage factory
set to ± 1% tolerance. Chargers with field-adjusted potentiometers are not
acceptable. A pulse-type charger shall be employed to promote long battery
life and reduce the potential for grid corrosion. The charger shall provide a
continuous high charge to recharge the battery, when the battery is at full
capacity, the charger will shut-off. Periodically the charger shall provide a
pulse of energy to keep the battery topped off. The charger shall be current
limited, temperature compensated, short-circuit proof and reverse polarity
protected. The unit shall be furnished with an electronic lockout circuit, which
will connect the battery when the AC circuit is activated, and an electronic
brownout circuit, which will activate the emergency lights when utility power
dips below 75% of nominal voltage.
A low voltage battery protection circuit shall be provided and will disconnect
the battery from the fused output circuit at the end of discharge. The unit
shall self-test for 1 minute every 30 days, 10 minutes on the 6th month
and 30 minutes every 12 months. The unit shall be capable of full recharge
in compliance with CSA specifications. The unit shall be furnished with
sealed dust tight relay, a test switch and seven diagnostic LED indicator
lights to continuously monitor the status of the unit: Battery Failure, Battery
Disconnected, Charger Failure, Lamp Failure, Service Alarm, AC “ON”,
Charger High Rate. The unit shall be T-bar mounted and come complete
with tool-less emergency lighting heads requiring no tools to adjust or aim.
.
The unit shall be Lumacell® model:
This slim-line, unobtrusive unit is ideally suited for any commercial location
where there is limited wall space and where the greater directional flexibility
of ceiling-mounted heads is needed to provide greater light distribution.
FEATURES
• Rugged steel cabinet with corrosion-resistant undercoating
• Battery and charger are concealed above the ceiling level
in the unit cabinet
• Removable panel provides easy access to battery and circuitry
• Test switch and LED indicators are mounted on the visible bottom panel
• Units mount quickly and easily in standard 2’ x 2’ or 2’ x 4’ grids
without any additional hardware
• Solid-state pulse-type charger – current-limited, temperaturecompensated, short-circuit proof and reverse-polarity protected
• Unit comes standard with electronic lockout and brownout circuits
• Sealed dust-proof transfer relay, test switch and LED indicator lights
• Long-life, maintenance-free Lead Acid battery
• Standard 120/347VAC input voltage
• NEXUS® compatible (for more information on NEXUS®, please consult
your sales representative)
• CSA C22.2 No. 141 certified
• Available with a selection of 4W, 5W or 6W LED lamps
• Vandal resistance clear polycarbonate lens
• Optional tamper-proof screws available
REPLACEMENT LAMPS
ORDERING CODE
LAMP TYPE
VOLTAGE/WATTAGE
580.0093-L
MR16, LED
12V-4W
580.0104-L
MR16, LED
12V-5W
580.0106-L
MR16, LED
12V-6W
DIMENSIONS
Dimensions are approximate and subject to change.
71/4” [18.3 cm]
101/2” [23.6 cm]
31/4” [8.2 cm]
233/4” [60.3 cm]
45/8” [11.8 cm]
Type:
Project/Location:
Contractor:
RGS-TBS Series
Prepared by:
Date:
T-Bar 12V MR16 LED Unit
Model:
POWER CONSUMPTION AND UNIT RATING
MODEL
WATTAGE CAPACITY
AC SPECS
RG12S36TBS
120/347VAC
RG12S72TBS
30MIN
1H00
1H30
2H00
0.09/0.03A
36
21
15
12
4H00
–
0.15/0.06A
72
42
30
24
12
ORDERING INFORMATION
SERIES
RG12S= 12V
CAPACITY HOUSING # OF HEADS
36W= 36W
72W= 72W
TBS= T-bar
cabinet
2= two heads
3= three heads
HEAD STYLE
LAMP WATTAGE
LD7= 12V-4W, MR16 LED
LD9= 12V-5W, MR16 LED
LD10= 12V-6W, MR16 LED
COLOUR
AC VOLTAGE
Blank= factory white Blank= 120/347
VAC input
OPTIONS
AT= Auto-test, audible
ATN= Auto-test, non-audible
NEX= NEXUS® wired system interface*
NEXRF= NEXUS® wireless system interface*
CT= Cabtire
TL= Twist Lock Plug (120V only)
LD= Lamp Disconnect
LTS= Light Activated Test Switch
RR2= Remote Test Reciever
(remote test transmitter needed)**
TD= Time Delay (programmable)
TMBB= AC/DC Terminal Block
TMBD= DC Terminal Block
TMBK= AC Terminal Block
TP= Tamper Proof Screws
(tamper proof bit needed)***
* Not all options available with NEXUS® System.
Please consult your sales representative.
**HH2= remote test transmitter (sold separately)
***990.0119-L= tamper proof bit (sold separately
EXAMPLE: RG12S36WTBS2LD7
All information and specification contained in this catalogue sheet are
subject to change due to engineer design, errors and omissions.
Illustrations and diagrams within this catalogue sheet may vary from actual products.
© 2014 Thomas & Betts Limited. All rights reserved.
Printed in Canada.