Omega FPUDV1000 Series Owner Manual
Add to my manuals20 Pages
Omega FPUDV1000 Series variable speed positive displacement injector pumps are designed to inject chemicals into piping systems and are capable of injecting against a high system pressure up to 150 PSI (10.4 bar). In addition to the front mounted mechanical flow rate adjustment, the pump is equipped with an external input control circuitry which allows the pumps output to be externally controlled by either a 4-20mA input signal, a 0-10V DC input signal or a pulsed input signal.
advertisement
User’s Guide
FPUDV1000 Series
Shop online at
Omega.com
e-mail: [email protected]
For latest product manuals:
Omegamanual.info
VARIABLE SPEED
POSITIVE DISPLACEMENT INJECTOR PUMP
OPERATING MANUAL
OMEGAnet Online Service
Omega.com
Internet e-mail
Servicing North America:
U.S.A.:
ISO 9001 Certified
One Omega Drive, P.O. Box 4047
Stamford, CT 06907-0047
TEL: (203) 359-1660
E-mail: [email protected]
FAX: (203) 359-7700
Canada: 976 Bergar
Laval (Quebec) H7L5A1, Canada
TEL: (514) 856-6928
E-mail: [email protected]
FAX: (514) 856-6886
For immediate technical or application assistance:
U.S.A. And Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
Customer Service: 1-800-622-2378 / 1-800-622-BEST
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
Mexico: En Espanol: (001) 203-359-7803
FAX: (001) 203-359-7807
Service Europe: e-mail: [email protected]
Benelux:
Czech Republic:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
TEL: +31 (0)20 3472121 FAX: +31 (0)20 6434643
Toll Free in Benelux: 0800 0993344
E-mail: [email protected]
Frystatska 184, 733 01 Karvina, Czech Republic
Tel: +420 (0)59 6311899
Toll Free: 0800-1-66342
FAX: +420 (0)59 6311114
e-mail: [email protected]
France: 11, rue Jacques Cartier, 78280 Guyancourt, France
TEL: +33 (0)1 61 37 2900 FAX: +33 (0)1 30 57 5427
Toll Free in France: 0800 466 342
E-mail: [email protected]
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 (0)7056 9398-0 FAX: +49 (0)7056 9398-29
Toll Free in Germany: 0800 639 7678
E-mail: [email protected]
United Kingdom: One Omega Drive, River Bend Technology Centre
ISO 9002 Certified Northbank, Irlam, Manchester
M44 5BD United Kingdom
TEL: +44 (0)161 777 6611
Toll Free in United Kingdom: 0800-488-488
E-mail: [email protected]
FAX: +44 (0)161 777 6622
It is the policy of OMEGA Engineering, Inc. To comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is belived to be correct, but OMEGA accepts no liability for any erroes it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for usein, and should not be used for, human applications.
2
3
4
SECTION
1
4.1
4.2
4.2.1
4.2.2
4.3
5
5.1
5.2
5.3
5.4
5.5
5.6
6
6.1
6.2
6.3
TABLE OF CONTENTS
HEADING
Introduction
Specifications
Features
How to install the pump
Mounting location
Electrical connections
Input Voltage connections
External Input Signal connections
How to install the tubing and fittings
How to operate the pump
8
9
How to adjust the output -Cam type Mechanism Adjustments 9
Description of the electronic adjustment controls 10
Mode 1 - Manually adjusting the output
Mode 2 - 4-20 mA input
11
11
Mode 3 - 0-10VDC input
Mode 4 - Pulse (frequency Hz) Input
How to maintain the FPUDV1000
Routine inspection and cleaning
500 hour service warning timer
How to clean the FPUDV1000
Replacement parts drawing
Replacement parts list 17
15
15
16
13
14
15
15
6
6
6
4
4
3
3
PAGE
2
Page 2
1.0
Introduction
Congratulations on purchasing the positive displacement metering pump. The pump is designed to inject chemicals into piping systems and is capable of injecting against a high system pressure up to 150 PSI (10.4 bar). In addition to the front mounted mechanical flow rate adjustment, the pump is equipped with an external input control circuitry which allows the pumps output to be externally controlled by either a 4-20mA input signal, a 0-10V DC input signal or a pulsed input signal.
Page 3
2.0
Specifications
Maximum Working Pressure 150 psig / 10.4 bar* o o Maximum Fluid Temperature 130 F / 54 C
Output Accuracy o
+/- 10% of maximum (water @ 70 F, 0 psig, and 5’ suction lift) o o
Ambient Temperature Range 14 to 110 F / -10 to 43 C
Duty Cycle
Maximum Viscosity
Continuous
1,000 Centipoise
Maximum Suction Lift
Power Requirements up to 10 ft. water
115V60Hz 40 Watts
Signal Inputs
Dimensions
Weight
220V50Hz 40 Watts
230V60Hz 40 Watts
4-20 mA , 0-10 VDC
TTL, CMOS pulses
Hall Effect sensors, Open-collector transistors,
Dry Contact switches (must withstand 12 VDC @ 2 mA )
6-1/4” high x 10” wide x 9-1/4” deep
(159 MM x 254 MM x 235 MM )
14 lb. / 6.35 Kg
3.0
Features
! Double-ball ceramic check valves.
! PVDF (Kynar) valve assemblies.
! High grade Aflas and Viton O-rings.
! Large outlet flowrate up to 360 GPD / 1363 Liters per day.
! High outlet pressure capability of 150 PSIG / 10.4 Bar.*
! Easy access, front mounted mechanical feed rate adjustment.
! Ball bearing supported motor drive shaft.
! Permanently lubricated ball bearing motor.
! Digital electronic feed rate control.
! 400:1 adjustment turn down ratio.
! Pump output verification system.
! Pump service inspection warning timer.
! Corrosion resistant Valox housing.
! Easy servicing.
! Includes suction tube foot valve & strainer, suction tube weight, suction tubing, discharge tubing and injection fitting with internal back-flow check valve and mounting hardware.
* Most models
Page 4
10 1
2
IN.
(267 MM ) 10 IN . (254 MM )
VARIABLE SPEED PUMP
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
STANDBY
FIELD DIGIT MODE
PRIME
RESET SERVICE
PROGRAM
DISPLAY
1 - MANUAL
INPUT MODES
2 - 4-20mA 3 - 0-10VDC 4 - PULSE (Hz)
6 1
4 IN.
(159 MM )
J-Box
Pumphead
Adjustment knob
Slide Clamps*
Control Cover
Motor Housing
Rear Cover
FIG. 3.0 PARTS LOCATOR DRAWING
* Slide both top & bottom clamps to the left only far enough to open the control cover.
4.0
How To Install the Pump
CAUTION: PROPER EYE AND SKIN PROTECTION MUST BE WORN WHEN
INSTALLING AND SERVICING THE FPUDV1000
Note: All diagrams are strictly for guideline purposes only. Always consult an expert before installing the pump into specialized systems.
The pump should be serviced by qualified persons only.
4.1
Mounting Location
Choose an area located near the chemical supply tank, chemical injection point and electrical supply. Although the pump is designed to withstand outdoor conditions, a cool, dry, well ventilated location is recommended. Install the pump where it can be easily serviced.
! Mount the pump to a secure surface or wall using the enclosed hardware. Wall mount to a solid surface only. Mounting to drywall with anchors is not recommended.
! Keep the outlet (discharge) tubing as short as possible. Longer tubing increases the back pressure at the pump tube.
! Do not mount the pump directly over your chemical container. Chemical fumes may damage the unit. Mount the pump off to the side or at a lower level than the chemical container.
! Mounting the pump lower than the chemical container will gravity feed the chemical into the pump. This “flooded suction” installation can reduce the time required to prime the pump.
Install a shut-off valve, pinch clamp or other means to halt the gravity feed to the pump during servicing.
! Your solution tank should be sturdy. Keep the tank covered to reduce fumes.
Page 5
Floor Mount
Drill .156 Dia. (5/32)
For Self-Tap Screw
#10 X 1” Phillips Steel
4 Places
3-1/2”
7-5/8”
2
Wall Mount
Drill .156 Dia. (5/32)
For Self-Tap Screw
#10 X 1” Phillips Steel
2 Places
8-3/16”
7-3/8”
Note: For wall-mounting, recommend drill & thread into
solid wood only.
FIG. 4.1 - INJECTOR MOUNTING
3 4 5 6 8
77
VARIABLE SPEED PUMP
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
STANDBY
FIELD DIGIT MODE
PRIME
RESET SERVICE
PROGRAM
DISPLAY
1 - MANUAL
INPUT MODES
2 - 4-20mA 3 - 0-10VDC 4 - PULSE (Hz)
1
Poo l
1. Strainer
2. Circulation Pump
3. Filter
4. Heater
5. Check Valve
6. Flowmeter
9
10
7. Injector
8. Solution Tank
9. Injection Fitting (FPU1000-IF)
10. Return Line
Discharge
Tube
FIG. 4.2 - SWIMMING POOL INSTALLATION
VARIABLE SPEED PUMP
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
STANDBY
FIELD DIGIT MODE
PRIME
RESET SERVICE
PROGRAM
DISPLAY
1 - MANUAL
INPUT MODES
2 - 4-20mA 3 - 0-10VDC 4 - PULSE (Hz)
¼" & ½" NPT Injector
FIG. 4.3 - TYPICAL INSTALLATION
Page 6
4.2
Electrical Connections
4.2.1 Input Power Connections -
Be certain to connect the pump to the proper supply voltage. Using the incorrect voltage will damage the pump and may result in injury. The voltage requirement is printed on the pump serial label.
WARNING-RISK OF ELECTRICAL SHOCK
Jumper pins on the circuit board are factory preset for the correct voltage. See Fig. 4.4, page 7 for details.
The pump is supplied with a ground wire conductor and a grounding type attachment plug
(power cord). To reduce the risk of electric shock, be certain that the power cord is connected only to a properly grounded, grounding type receptacle.
Note: When in doubt regarding your electrical installation, contact a licensed electrician.
4.2.2 External Input Signal Connections -
The pump will accept any one of three different types of external input signals; 4-20 mA, 0-10
VDC, or frequency. Two types of frequency inputs, AC sine waves (magnetic coils type outputs) and Digital Square waves (Hall Effect signals, contact closures), are acceptable. A jumper plug located on the circuit board is factory pre-set for AC sine wave signals, the jumper must be re-positioned when digital square wave signals are being used. (See Fig. 4.4, page 7,
“Hz input jumper settings”)
All wiring connections are to be made inside of the junction box located on the side of the pump. A liquid-tite connector is supplied and should be used for the external signal cable. The signal input wires are color coded to the type of signal being used.
INPUT SIGNAL TYPE
4-20 mA
0-10 V DC
AC sine wave, Digital square wave
POSITIVE
WIRE COLOR
BLUE
ORANGE
WHITE
NEGATIVE
WIRE COLOR
BLACK
BLACK
BLACK
FIG. 4.3 WIRING CHART - INPUT SIGNAL WIRE COLORS
Page 7
SIGNAL INPUT MODES / FUNCTIONS & WIRING COLOR CODES
INPUT MODE / FUNCTION WIRES REQUIRED
MANUAL
4-20 mA
0-10 VDC
FREQUENCY
ALARM RELAY
FLOW VERIFICATION SENSOR
(Digital square waves)
MOTOR ON SIGNAL
NO CONNECTIONS
BLUE (+) & BLACK (-)
ORANGE (+) & BLACK (-)
WHITE (+) & BLACK (-)
PURPLE & PURPLE
RED (+ 20VDC) & BLACK (-) & YELLOW (signal)
BROWN (+) & BLACK (-)
EXTERNAL INPUT CABLE
ACCEPTABLE CABLE JACKET RANGE:
.118 - .255 INCH
.( 3,0 - 6,5 MM)
RED (+20VDC)
BLACK (Ground)
BLUE (4-20 mA input)
ORANGE (0-10 VDC input)
WHITE (frequency input)
YELLOW (verification sensor input)
BROWN (motor-on contact output)
PURPLE X2 (alarm relay contacts)
JUNCTION BOX
LIQUID-TIGHT
CONNECTOR
ALARM OUTPUT
(CONTACT CLOSURE) connect 2-conductor plug to either normally open (NO) (factory default) or normally closed (NC) side of receptacle.
1 AMP MAX @ 125VAC (24VDC)
DC
MOTOR
Hz INPUT JUMPER SETTINGS
Located under connector
AC sine waves
Jumper Not Installed
(open - factory default)
Digital square waves
Jumper Installed
INPUT SIGNAL CONNECTOR
7 wire bundle
AC LINE VOLTAGE SETTINGS
1 AMP
250VAC
TS
230 VAC
One Jumper Installed on center position
(ends open)
115 VAC
Two Jumpers Installed on end positions
(no open pins)
THERMAL SWITCH
.187 push tab connectors
2 conductors
PROTECTOR FUSE
1 Amp, 250 Volt AC
(Littlefuse #239001 or Equivalent)
MOTOR
RED (+)
MOTOR
BLACK (-)
AC LINE
NEUTRAL
AC LINE
HOT
RED (+)
BLACK (-)
Ground (green)
Hot
Common
Earth Ground (green)
AC
Input
Power
FIG. 4.4 WIRING DIAGRAM - CIRCUIT BOARD
Page 8
4.3
How To Install the Tubing and Fittings
CAUTION: PROPER EYE AND SKIN PROTECTION MUST BE WORN WHEN
INSTALLING AND SERVICING THE FPUDV1000
4.3.1 Inlet Tubing - Locate the inlet fitting of the pump head, see fig 4.9. Remove the tube nut.
Push the clear PVC suction tubing onto the compression barb of the fitting. Use the tube nut to secure the tube. Hand tighten only.
4.3.2 Footvalve/Strainer -Trim the inlet end of the suction tubing so that the strainer will rest approximately one inche from the bottom of the solution tank. This will prevent sediment from clogging the strainer. Slip the ceramic weight over the end of the suction tube. Press the footvalve/strainer into the end of the tube. Secure the ceramic weight to the strainer. Drop the strainer into the solution tank.
4.3.3 Outlet Tubing - Locate the outlet fitting of the pump head, see fig 4.9. Remove the tube nut.
Push the opaque outlet (discharge) tubing onto the compression barb of the fitting. Use the tube nut to secure the tube. Hand tighten only.
Trim the other end of the outlet tube leaving only enough slack to connect it to the
Injection/Check valve Fitting (see below). Increasing the length of the outlet tube increases the back pressure at the pump head, particularly when pumping viscous fluids.
Discharge Tube
(Rigid P.E.)
Tube Nut
Outlet Adapter
Pump Head
Suction Tubing
Ceramic
Weight
Footvalve Adapter
O-Ring
Ceramic Ball
O-Ring
VARIABLE SPEED PUMP
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
STANDBY
FIELD
DIGIT MODE
1 - MANUAL
PRIME
RESET SERVICE
PROGRAM
DISPLAY
INPUT MODES
2 - 4-20mA 3 - 0-10VDC 4 - PULSE (Hz)
FootValve
Sub-Assembly
Footvalve Body
Footvalve Strainer
Inlet Adapter
Tube Nut
Suction Tubing
(clear PVC)
FootValve
FIG. 4.9
FIG. 4.10 FOOTVALVE ASSY.
Page 9
4.3.4 Injection/Check Valve Fitting Installation - The Injection/Check valve fitting is designed to install directly into either 1/4” or 1/2” female pipe threads. This fitting will require periodic cleaning, especially when injecting fluids that calcify such as sodium hypochlorite. These lime deposits and other build ups can clog the fitting increasing the back pressure and interfering with the check valve operation. See section 6.0.
Install the Injection/Check valve directly into the piping system. Do not use a pipe stud with a tee for insertion of the injection valve. The solution must inject directly into the flow stream.
Use Teflon thread sealing tape on the pipe threads. Push the opaque outlet (discharge) tubing onto the compression barb of the Injection/Check valve fitting. Use the tube nut to secure the tube. Hand tighten only.
TEE INSTALLATION
EXPLODED VIEW
FIG. 4.11
INJECTION/CHECK VALVE
TEE INSTALLATION AND EXPLODED VIEW
5.0
How To Operate The Pump
5.1
How to adjust the output- Cam-Type Mechanism Adjustment (fig. 5.1)
- The flow rate can be adjusted within a range of 5% -100% of maximum output (20:1 turndown ration) by means of a mechanical, cam type mechanism. The mechanism adjusts the pump’s stroke length to an infinite number of settings within the flow range. Because the pump’s output is reduced by increasing the pressure of the system being injected into, the amount of suction lift, and the viscosity of the fluid being injected, the pump must be over-sized to allow for these factors. Sizing the pump to allow adjustment within the midrange is preferred to maintain accuracy. Consult the factory for individual pump model output curve data.
To adjust the pump’s output:
1. With the pump running, loosen the lock screw.
2. Turn the adjustment knob to the desired setting.
3. Re-tighten the lock screw.
Adjustment Knob
(Cam Type Mechanism)
Lock screw
FIG. 5.1
Page 10
5.2
Description of Electronic Adjustment Controls -
Open the control panel door by sliding the upper and lower slide clamps to the left. FIG. 5.2
! RUN/STANDBY Button -
4 Press to start and stop the pump. The ARROW next to the word RUN will light when in the run mode. The ARROW next to the word STAND-BY will blink when in the stand-by mode.
4 Press to clear ALARM.
4 When pressed with the FIELD Button, initiates a 99 second prime cycle which temporarily overrides the mode setting and runs the pump motor at 100% speed. The ARROW next to the word PRIME will blink.
4 When pressed with the DIGIT button, resets the 500 hour service warning timer to zero.
4 When pressed with the MODE button, initiates the programming mode. The ARROW next to the word PROGRAM will blink.
! FIELD Button -
4 In the programming mode, selects the digit to be changed.
! DIGIT Button -
4 In the programming mode, increases the selected digit.
4 When pressed with the MODE Button, toggles the display from % motor speed to input signal value.
! MODE Button -
4 Used to select one of four operating modes.
Mode 1 - Manual Adjustment (external input disabled)
Mode 2 - 4-20mA input
Mode 3 - 0-10VDC input
Mode 4 - Frequency (Hz) input
VARIABLE SPEED PUMP
MODE
% SPEED mA
1
VDC 1000
SERVICE ALARM
Hz
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
STANDBY
FIELD DIGIT MODE
PRIME
RESET SERVICE
PROGRAM
1 - MANUAL
DISPLAY
INPUT MODES
2 - 4-20mA 3 - 0-10VDC 4 - PULSE (Hz)
FIG. 5.1
SLIDE CLAMP
Slide both top & bottom clamps to the left only far enough
(as shown) to open the control cover
FIG. 5.2
Adjustment Knob
(Cam Type Mechanism)
VARIABLE SPEED PUMP
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN
STANDBY
FIELD DIGIT MODE
PRIME
RESET SERVICE
PROGRAM
1 - MANUAL
DISPLAY
INPUT MODES
2 - 4-20mA 3 - 0-10VDC 4 - PULSE (Hz)
Electronic Control Panel
Page 11
5.3
5.4
OPERATING MODE 1 - Output adjusted manually -
In this mode, the pump’s motor speed is adjusted manually using the front panel touch pad. The motor speed can be adjusted from 0-100%. To adjust the speed:
4
Set the pump for mode 1. Press the MODE button until MODE 1 is shown on the
LCD display. The %SPEED icon will light. The large 3-DIGIT LCD will indicate the currently programmed percentage of speed.
4
Enter the programming mode. At the same time, press the RUN/STANDBY button and the MODE button. A blinking ARROW will point to the word PROGRAM indicating the program mode has been activated.
4
Press the FIELD button to select the digit to program. The digit will blink when
4
4 selected.
4
Press the DIGIT button to change the selected digit.
Repeat until all digits are programmed.
To exit the programming mode, press the RUN/STANDBY button and the MODE button at the same time. The arrow next to the word PROGRAM will disappear.
[ NOTE: If while in the program mode no buttons are pressed within 20 seconds, the circuitry will automatically return to the run mode, without saving changes.
[
OPERATING MODE 2 - Output adjusted by 4-20 mA input signal -
In this mode, the pump’s motor speed is adjusted automatically based on the value of the
4-20 mA input signal. Any motor speed can be assigned to either the minimum or maximum milliamp input values. However, the programmed minimum mA value must
be less than the programmed maximum mA value. The ALARM and SERVICE icons will blink if the programming is in error. To assign the minimum and maximum motor speed and the minimum and maximum mA input signal values:
4
Set the pump for mode 2. Press the MODE button until MODE 2 is shown on the
LCD display. The %SPEED or mA icon will light depending on the current display setting. The large 3-DIGIT LCD will indicate the current motor speed or the current mA input value.
4
Enter the programming mode. At the same time, press the RUN/STANDBY and
4
4
MODE buttons. A blinking ARROW will point to the word PROGRAM indicating the program mode is activated. A blinking ARROW will point to the word MINIMUM indicating the minimum value is ready to be programmed. The % SPEED icon will blink indicating the percentage of speed is ready to be programmed.
Enter the motor speed at the minimum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the mA icon will blink indicating the minimum mA value is ready to be programmed. The currently programmed minimum value is shown on the 3-DIGIT LCD.
4
Enter the minimum mA input signal value. Note: this value must be less than the maximum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The Ma icon will stop blinking and the % SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-DIGIT LCD.
Enter the motor speed at the maximum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
4
Press the mode button. The % SPEED icon will stop blinking and the mA icon will blink indicating the maximum mA value is ready to be programmed. The currently programmed maximum value is shown on the 3-DIGIT LCD.
4
Enter the maximum mA input signal value. Note: this value must be greater than the minimum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected..
4
Press the DIGIT button to change the selected digit.
4
Repeat until all digits are programmed.
RUN MODE 1
MODE
% SPEED 100
MODE
% SPEED
1
000
MODE mA
2
1
04.0
MODE
% SPEED 000
MODE mA 04.0
2
2
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 1 constant speed % setting
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
RUN MODE 2
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 2
% speed at the minimum input
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 2 minimum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
Page 12
4 Press the mode button. The Ma icon will stop blinking and the %
SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-
DIGIT LCD.
4 Enter the motor speed at the maximum mA input signal value.
Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The % SPEED icon will stop blinking and the
mA icon will blink indicating the maximum mA value is ready to be programmed. The currently programmed maximum value is shown on the 3-DIGIT LCD.
4 Enter the maximum mA input signal value. Note: this value must be greater than the minimum mA input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected..
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. Programming is complete.
4 To exit the programming mode, press the RUN/STANDBY button and the MODE button at the same time. The PROGRAM arrow will disappear.
Example 1
MODE 2 PROGRAMMING EXAMPLES
Example 2
4 mA = 0% OUTPUT
20 mA = 100% OUTPUT
4 mA = 100% OUTPUT
20 mA = 0% OUTPUT
100 100
PROGRAM MODE 2
% speed at the maximum input
MODE
% SPEED 100
MODE mA 20.0
2
2
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 2 maximum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
75 75
50 50
25 25
0
4 6 8 10 12 14 16 18 20
Milliamp input (mA)
Example 3
4 mA = 0% OUTPUT
20 mA = 75% OUTPUT
100
0
4 6 8 10 12 14 16 18 20
Milliamp input (mA)
Example 4
4 mA = 20% OUTPUT
20 mA = 50% OUTPUT
100
75 75
50
25
0
4 6 8 10 12 14 16 18 20
Milliamp input (mA)
50
25
0
4 6 8 10 12 14 16 18 20
Milliamp input (mA)
Page 13
5.5
OPERATING MODE 3 - Output adjusted by 0-10VDC input signal -
In this mode, the pump’s motor speed is adjusted automatically based on the value of the 0-10VDC input signal. Any motor speed can be assigned to either the minimum or maximum DC input signal values. However, the programmed minimum VDC value must be less than the programmed
maximum VDC value. The ALARM and SERVICE icons will blink if the programming is in error. To assign the minimum and maximum motor speed and the minimum and maximum VDC input signal values:
4 Set the pump for mode 3. Press the MODE button until MODE 3 is shown on the LCD display. The % SPEED or VDC icon will light depending on the current display setting. The large 3-DIGIT LCD will indicate the current motor speed or the VDC input value.
4 Enter the programming mode. At the same time, press the
RUN/STANDBY and MODE buttons. A blinking ARROW will point to the word PROGRAM indicating the program mode is activated. A blinking
ARROW will point to the word MINIMUM indicating the minimum value is ready to be programmed. The % SPEED icon will blink indicating the percentage of speed is ready to be programmed.
4 Enter the motor speed at the minimum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The % SPEED icon will stop blinking and the VDC icon will blink indicating the minimum VDC value is ready to be programmed. The currently programmed minimum value is shown on the 3-
DIGIT LCD.
4 Enter the minimum VDC input signal value. Note: this value must be less than the maximum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The VDC icon will stop blinking and the % SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-DIGIT LCD.
4 Enter the motor speed at the maximum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The % SPEED icon will stop blinking and the VDC icon will blink indicating the maximum VDC value is ready to be programmed. The currently programmed maximum value is shown on the 3-
DIGIT LCD.
4 Enter the maximum VDC input signal value. Note: this value must be greater than the minimum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. Programming is complete.
4 To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The PROGRAM arrow will disappear.
RUN MODE 3
MODE 3
VDC 00.0
MODE
% SPEED 000
MODE 3
VDC 00.0
MODE
% SPEED 100
3
3
MODE 3
VDC 10.0
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 3
% speed at the minimum input
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 3 minimum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 3
% speed at the maximum input
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 3 maximum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
5.6
Page 14
OPERATING MODE 4 - Output adjusted by frequency (Hz) input signal -
In this mode, the pump’s motor speed is adjusted automatically based on the frequency (Hz) of the input signal. Any motor speed can be assigned to either the minimum or maximum Hz input signals. However, the programmed minimum Hz value must be less than the programmed maximum Hz
value. The ALARM and SERVICE icons will blink if the programming is in error. To assign the minimum and maximum motor speed and the minimum and maximum Hz input signal values:
4 Set the pump for mode 4. Press the MODE button until MODE 4 is shown on the LCD display. The % SPEED or Hz icon will light depending on the current display setting. The large 3-DIGIT LCD will indicate the current motor speed or the Hz input value.
4 Enter the programming mode. At the same time, press the
RUN/STANDBY and MODE buttons. A blinking ARROW will point to the word PROGRAM indicating the program mode is activated. A blinking
ARROW will point to the word MINIMUM indicating the minimum value is ready to be programmed. The % SPEED icon will blink indicating the percentage of speed is ready to be programmed.
4 Enter the motor speed at the minimum Hz input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The % SPEED icon will stop blinking and the Hz icon will blink indicating the minimum Hz value is ready to be programmed. The currently programmed minimum value is shown on the 3-
DIGIT LCD.
4 Enter the minimum Hz input signal value. Note: this value must be less than the maximum Hz input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The Hz icon will stop blinking and the % SPEED icon will blink. The ARROW next to the word MAXIMUM will blink indicating the maximum value is ready to be programmed. The currently programmed maximum motor speed value is shown on the 3-DIGIT LCD.
4 Enter the motor speed at the maximum VDC input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The % SPEED icon will stop blinking and the Hz icon will blink indicating the maximum Hz value is ready to be programmed. The currently programmed maximum value is shown on the 3-
DIGIT LCD.
4 Enter the maximum Hz input signal value. Note: this value must be greater than the minimum Hz input signal value. Press the FIELD button to select the digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. Programming is complete.
4 To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The PROGRAM arrow will disappear.
RUN MODE 4
MODE
000
MODE
% SPEED 000
MODE
000
MODE
% SPEED 82.5
MODE
4
628
4
4
Hz
4
Hz
4
Hz
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 4
% speed at the minimum input
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 4 minimum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 4
% speed at the maximum input
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
PROGRAM MODE 4 minimum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
Page 15
Example 1
0 Hz = 0% OUTPUT
1000 Hz = 100% OUTPUT
100
MODE 4 PROGRAMMING EXAMPLES
Example 2
0 Hz = 100% OUTPUT
1000 Hz = 0% OUTPUT
100
Example 3
0 Hz = 10% OUTPUT
275 Hz = 75% OUTPUT
100
75 75 75
50 50 50
25 25 25
0
0 200 400 600 800 1000
Frequency input (Hz)
0
0 200 400 600 800 1000
Frequency input (Hz)
0
0 200 400 600 800 1000
Frequency input (Hz)
6.0
How to Maintain the Pump
CAUTION: PROPER EYE AND SKIN PROTECTION MUST BE WORN WHEN
INSTALLING AND SERVICING THE FPUDV1000
6.1
Routine Inspection and Maintenance
The pump requires very little maintenance. However, the pump and all accessories should be checked regularly. This is especially important when pumping chemicals. Inspect all components for signs of leaking, swelling, cracking, discoloration or corrosion. Replace worn or damaged components immediately.
Cracking, crazing, discoloration and the like during the first week of operation are signs of severe chemical attack. If this occurs, immediately remove the chemical from the pump.
Determine which parts are being attacked and replace them with parts that have been manufactured using more suitable materials. The manufacturer does not assume responsibility for damage to the pump that has been caused by chemical attack.
6.2
500 Hour Service Warning Timer
The pump is equipped with a service warning timer. After 500 hours of accumulated running time, the SERVICE icon will light. This is a reminder that the pump should be inspected for service. Your actual service period will depend on many factors such as the chemical used, back pressure, temperature, viscosity, and motor RPM.
Simultaneously press the RUN/STANDBY and DIGIT buttons to reset the service timer to zero.
Note: Pressing the FIELD and DIGIT buttons will display the currently accumulated time value.
6.3
How to Clean the Pump
The pump will require occasional cleaning, especially the Injection fitting, the Footvalve/Strainer, and the pump head valves. The frequency will depend on the type and severity of service.
] Inspect and replace the pumphead valves as required.
] When changing the diaphragm, the pump head chamber and pump head cover should be wiped free of any dirt and debris.
] Periodically clean the injection/check valve assembly, especially when injecting fluids that calcify such as sodium hypochlorite. These lime deposits and other build ups can clog the fitting, increase the back pressure and interfere with the check valve operation. See section 4.3.4. Fig.
4.11.
] Periodically clean the suction strainer. Fig.4.10
] Periodically inspect the air vents located under the motor housing and in the back on the rear housing cover. Clean if necessary.
R epl c e a raw ng
P age 1 6
D
F
EL
A
D
N
S
T
Y
B
D
G
T
M
E
O
D
IM
E
R
P
E.
T G
R
E
E
S
WIN
M
ER
M
AN
U
L 2
P
UT m
IN
-0
O
D
E
=-1
M
C
D
U
(H
Page 17
MADE
IN
USA
WARRANTY/DISCLAIMER
FOR WARRANTY RETURNS, please have FOR NON WARRANTY REPAIRS OR
The following information available CALIBRATION, consult OMEGA for
1. P.O. Number under which the product current repair/calbration charges. Have
was PURCHASED. Information before contacting OMEGA.
2. Model and serial number of the product 1. P.O. Number to cover the COAST of
under warranty, and the repair/ calibration.
3. Repair Instructions and/or specific 2. Model and serial number of product,
Problems relative to the Product. and
3. Repair instructions and/or specific
Problems relative to the product
Where Do I Find Everything I Need For
Process Measurement and Control?
OMEGA... Of Course!
Shop on line at www.Omega.com
TEMPERATURE
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrations & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE / STRAIN FORCE
Transducers & Strain Gauges
Load Cells & Pressure Gauge
Displacement Transducers
Instrumentation & Accessories
FLOW / LEVEL
Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine / Paddlewheel Systems
Totalizers & Batch Controllers
pH / CONDUCTIVITY
pH Electrodes,Testers& Accessories
Benchtop / Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrations & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
HEATERS
Heating Cable
Cartridge & Strip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment pH, Conductivity & Dissolved Oxygen Instruments
M-4197/0505
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Key Features
- High grade Aflas and Viton O-rings.
- Large outlet flowrate up to 360 GPD / 1363 Liters per day.
- High outlet pressure capability of 150 PSIG / 10.4 Bar.
- Easy access, front mounted mechanical feed rate adjustment.
- Ball bearing supported motor drive shaft.
- Permanently lubricated ball bearing motor.
- Digital electronic feed rate control.
- 400:1 adjustment turn down ratio.
- Pump output verification system.
- Pump service inspection warning timer.