PSBEN 3012C/LCD PSBEN 13,8V/3A/17Ah/EN/LCD Buffer, switched mode power supply unit.

PSBEN 3012C/LCD PSBEN 13,8V/3A/17Ah/EN/LCD Buffer, switched mode power supply unit.
PSBEN 3012C/LCD
v.1.0
PSBEN 13,8V/3A/17Ah/EN/LCD
Buffer, switched mode power supply unit.
EN
Edition: 2nd (14th Sep 2012)
Supersedes the: 1st (25th April 2012) edition
www.pulsar.pl
PSBEN3012C/LCD
CONTENTS
1. FUNCTIONAL REQUIREMENTS OF THE PSU COMPLIANT WITH PN-EN 50131-6. ...........4
2. TECHNICAL DESCRIPTION. .............................................................................................................5
2.1. GENERAL DESCRIPTION. .......................................................................................................................................................5
2.2. BLOCK DIAGRAM..................................................................................................................................................................5
2.3 DESCRIPTION OF PSU’S COMPONENTS AND CONNECTORS.....................................................................................................6
3. OPERATING STATUS INDICATION.................................................................................................7
3.1. CONTROL PANEL. .................................................................................................................................................................7
3.2. MAIN SCREEN OF THE LCD DISPLAY. ...................................................................................................................................8
3.3 INFORMATION DISPLAYED ON THE PANEL..............................................................................................................................9
3.3.1. Overview menu. ............................................................................................................................................................9
3.3.2 Screen – parameters of the PSU....................................................................................................................................9
3.3.3 Screen – history of the PSU’s parameters...................................................................................................................10
3.3.4 Screen – failure history. ..............................................................................................................................................10
3.4 PSU SETTINGS.....................................................................................................................................................................11
3.4.1 Password of access......................................................................................................................................................11
Entering the password. .........................................................................................................................................................................12
Password change. .................................................................................................................................................................................13
Skipping the access password...............................................................................................................................................................13
Erasing passwords. ...............................................................................................................................................................................13
Keypad password..................................................................................................................................................................................13
3.4.2 PSU. ............................................................................................................................................................................14
Setting the battery presence. .................................................................................................................................................................14
Setting the battery test. .........................................................................................................................................................................15
Setting the battery protection................................................................................................................................................................15
Setting the EPS output lag. ...................................................................................................................................................................16
Setting the communication address. .....................................................................................................................................................17
3.4.3 Desktop........................................................................................................................................................................17
Setting the language of messages. ........................................................................................................................................................18
Setting the date. ....................................................................................................................................................................................18
Setting the time.....................................................................................................................................................................................19
Setting the highlighting. .......................................................................................................................................................................19
Setting the contrast. ..............................................................................................................................................................................20
3.5 ACOUSTIC INDICATION. .......................................................................................................................................................21
3.6 TECHNICAL OUTPUTS. .........................................................................................................................................................21
3.7 INPUT OF COLLECTIVE FAILURE: EXT IN. ...........................................................................................................................22
4. BATTERY-ASSISTED OPERATION. ...............................................................................................23
4.1. RUNNING THE PSU FROM THE BATTERY.............................................................................................................................23
4.2. DEEP DISCHARGE BATTERY PROTECTION UVP...................................................................................................................23
4.3 DYNAMIC BATTERY TEST. ...................................................................................................................................................23
4.4. STANDBY TIME. ..................................................................................................................................................................23
4.6 OPERATION WITHOUT A BATTERY. ......................................................................................................................................24
5. REMOTE MONITORING (OPTION: WI-FI, ETHERNET, RS485, USB). ..................................25
5.1 COMMUNICATION IN WI-FI WIRELESS NETWORK................................................................................................................25
5.2 COMMUNICATION IN ETHERNET NETWORK......................................................................................................................25
5.3 COMMUNICATION IN RS485 NETWORK. ..............................................................................................................................25
5.4 USB-TTL COMMUNICATION. ..............................................................................................................................................26
5.5 ”POWER SECURITY” PROGRAM. ..........................................................................................................................................26
6. TECHNICAL SPECIFICATIONS. .....................................................................................................27
TABLE 10. ELECTRICAL SPECIFICATIONS...................................................................................................................................27
TABLE 11. MECHANICAL SPECIFICATIONS.................................................................................................................................28
TABLE 12. OPERATION SAFETY. ................................................................................................................................................28
TABLE 13. OPERATING SPECIFICATIONS....................................................................................................................................28
TABLE 14. PSU’S FACTORY SETTINGS.......................................................................................................................................28
7. INSTALLATION...................................................................................................................................29
2
www.pulsar.pl
PSBEN3012C/LCD
7.1 REQUIREMENTS...................................................................................................................................................................29
7.2 INSTALLATION PROCEDURE.................................................................................................................................................29
8. OPERATION AND USE.......................................................................................................................30
8.1. OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT. ..................................................................................................30
8.2 OVERLOAD OF THE PSU. .....................................................................................................................................................30
8.3 SHORT CIRCUIT AT THE PSU OUTPUT. .................................................................................................................................30
8.4 BATTERY REPLACEMENT.....................................................................................................................................................30
8.5. MAINTENANCE. ..................................................................................................................................................................30
9. PSU FAILURE CODES. .......................................................................................................................30
3
www.pulsar.pl
PSBEN3012C/LCD
Features:
• PN-EN50131-6 compliance, grades 1÷3 and II
environmental class
• mains supply of 230VAC
• uninterrupted voltage of 13,8VDC
• fitting battery: 17Ah/12V
• high efficiency 70%
• PSU current efficiency:
• 1,4A – for grades 1 , 2 *
• 0,56A – for grades 3 **
• 3A – for general use ***
(see: chapter 2.1)
• low level of voltage ripple
• microprocessor-based automation system
• intelligent management of PSU power’s output stage
• serial port for communication with a computer via ”Power
Security” program
• remote monitoring (option: WiFi, Ethernet, RS485, USB)
• load current control
• output voltage control
• output fuse status control
• dynamic battery test
• battery circuit continuity control
• battery voltages control
• battery fuse status control
• battery charge and maintenance control
• deep discharge battery protection (UVP)
• battery overcharge protection
• battery output protection against short circuit and reverse
polarity connection
• jumper selectable battery charging current
0,2A/0,6A/1A/1,5A
• remote test of the PSU (additional module required)
• START button for battery activation
• STOP button for disconnecting during battery-assisted
operation
• optical indication – LCD panel
• electrical parameters reading, e.g.: voltage,
current
• failure indication
• PSU settings adjusted from the panel’s level
• 3 levels of access, password-protected
• PSU’s operation history
• failure history
• real-time clock, battery-backed
• optical indication of PSU overload OVL
• acoustic indication of failure
• adjustable times indicating AC power failure
• technical inputs/outputs with galvanic isolation
• collective failure input EXT IN
• EPS technical output indicating AC power loss
• PSU technical output indicating PSU failure
• APS technical output indicating battery failure
• internal memory of PSU operating status
• protections:
• SCP short circuit protection
• OLP overload protection
• OHP overheat protection
• OVP over voltage protection
• surge protection
• against tampering: unwanted opening of the
enclosure or detachment from the mounting surface
• convectional cooling
1. Functional requirements of the PSU compliant with PN-EN 50131-6.
Functional requirements
EPS network absence
Battery low voltage
Protection against full battery discharge
Battery fault
No battery charge
Output low voltage
Output high voltage
PSU fault
Surge protection
Short circuit protection
Overload protection
Output fuse activation
Battery fuse fault
EPS technical output
APS technical output
PSU technical output
Collective failure input
PSU remote test
Tamper resistance – enclosure opening
Tamper resistance – detachment from the
mounting surface
Requirements of
PN-EN 50131-6
Grade 1
Grade 2
Grade 3
YES
YES
YES
YES
YES
YES
YES
YES
-
4
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
PSBEN3012C/
LCD
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
www.pulsar.pl
PSBEN3012C/LCD
2. Technical description.
2.1. General description.
The buffer power supply has been designed in accordance with the requirements of the PN-EN 50131-6
standard, grade 1÷3 and II environmental class. It is intended for an uninterrupted supply to alarm system devices
requiring stabilized voltage of 12V/DC (+/-15%).
Depending on a required protection level of the alarm system in the installation place, the PSU efficiency
and the battery charging current ought to be measured as follows:
* Grade 1, 2 - standby time 12h
Output voltage 1,4A + 1,5A battery charge
** Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1).
Output voltage 0,56A + 1,5A battery charge
- standby time 60h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1).
Output voltage 0,28A + 1,5A battery charge
*** General use – if the PSU is not mounted within an installation which is PN-EN-50131 compliant, the
acceptable current efficiency amounts to:
1. Output voltage 3A + 0,2A battery charge
2. Output voltage 2,6A + 0,6A battery charge
3. Output voltage 2,2A + 1A battery charge
4. Output voltage 1,7A + 1,5A battery charge
Total current of the receivers + battery: 3,2A max.
In case of power decay, a battery back-up is activated immediately. The PSU is housed in a metal
enclosure (colour: RAL 9005 - black) which can accommodate a 17Ah/12V battery. It features a micro switch that
indicates unwanted door opening (faceplate) and detaching from the mounting surface.
2.2. Block diagram.
The PSU has been manufactured based on a high-duty system of DC/DC converter. It features a
microprocessor-based operation control, responsible for full diagnostics of the PSU and battery parameters.
Fig. 1. Block diagram of the PSU.
5
www.pulsar.pl
PSBEN3012C/LCD
2.3 Description of PSU’s components and connectors.
Table 1. Elements of the PSU pcb (see Fig. 2).
Element no.
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
Description
PANEL – optical indication connector
PBAT
– jumper; idle in this model
– jumpers J1, J2; idle in this model
TAC
CAUTION. In this model, jumpers are operated from the LCD desktop’s level (see: chapter 3.4.2).
IBAT
– battery charging current selection
J1=
J1=
J1=
J1=
, J2=
, J2=
, J2=
, J2=
, J3=
J3=
J3=
J3=
IBAT =0,2 A
IBAT =0,6 A
IBAT =1,0 A
IBAT =1,5 A
Caption:
jumper on,
START – button (launching the PSU from a battery)
STOP – button (disconnection of the PSU during battery-assisted operation)
– pin; activation of acoustic indication
- indication on
- indication off
Caption:
jumper on,
jumper off
VADJ
– potentiometer, DC voltage adjustment
BUZZER – acoustic indicator
FBAT
– fuse in the battery circuit
Connectors:
~AC~ – AC power input
+BAT – DC power battery output
+AUX – DC power output (+AUX= +U, -AUX=GND)
EPS FLT – technical output of AC network absence indication
open
= AC power failure
close
= AC power - O.K.
PSU FLT – technical output of PSU failure
open
= failure
close
= PSU working correctly - O.K.
APS FLT – technical output of battery failure
open
= battery failure
close
= battery O.K.
EXT IN – output of collective failure
VEXT pin – polarisation of EXT IN circuit
Communication connector
LEDs – optical indication:
AC
– presence of the AC power
AUX
– DC output voltage
OVL
– PSU overload
PSU
– PSU failure
APS
– battery failure
EXT
– EXT IN output’s status
LB
– battery charge
OVP
– optical indication for activating the over voltage system
Fig. 2. The view of the PSU’s pcb.
6
jumper off
www.pulsar.pl
PSBEN3012C/LCD
Table 2. PSU elements (see fig. 3).
Element no.
Description
[1]
Insolation transformer
[2]
PSU board (tab.1, fig.2)
[3]
TAMPER; micro-switch (contacts) of tamper resistance (NC)
[4]
FMAIN fuse in the supply circuit (230 V AC)
[5]
[6]
[7]
L-N 230V/AC power connector,
PE connector
Battery connectors: positive: +BAT = red, negative: - BAT = black
Grip of tamper resistance
Fig.3. The view of the PSU.
3. Operating status indication.
3.1. Control panel.
The PSU is equipped with a panel with buttons and an LCD display which enables reading all available
parameters of the device. The buttons are for selecting and approving a certain parameter that is to be displayed.
Fig. 4. The control panel.
7
www.pulsar.pl
PSBEN3012C/LCD
Table 3. A description of buttons and LEDs of the LCD panel.
- move the cursor on the display
- selection approval
- leaving the editing mode without changing the values
- entering the overview menu mode
- red LED indicating the presence of AC voltage
- green LED indicating power at the AUX output of the PSU
- red LED indicating the PSU failure
The resolution for voltage measurement amounts to 0.1V, for current measurement: 0.1A. Displayed
voltage and current rate is only approximate. For higher accuracy, a multimeter shall be used.
3.2. Main screen of the LCD display.
The main screen of the LCD display shows basic electrical parameters and informs about the current PSU
state.
Fig. 5. The main screen.
Table 4. Description of the symbols on the main screen.
Screen field
Description
Information about the current AC power status.
- AC power present
- no AC power
Information about the present voltage at the AUX output and the current consumption. In
case of a failure tripped by incorrect output voltage or exceeding the load current, an
appropriate parameter twinkles on the display.
Information about the battery charging level. In case of a failure, the battery symbol
twinkles.
A field symbolising the PSU.
In case of a PSU failure, a twinkling symbol with an exclamation mark appears.
Fuse symbol.
Twinkling symbol informs about activation of the fuse.
Clock
8
www.pulsar.pl
PSBEN3012C/LCD
3.3 Information displayed on the panel.
3.3.1. Overview menu.
After pressing the ‘ESC’ button, an overview menu appears at the bottom of the display. It enables
choosing one of three available PSU screens:
- parameters of the PSU
- history of the PSU’s parameters
- history of events
In order to choose a proper screen, select a dedicated field by pressing the arrow buttons: ‘<’ or ‘>’. Then,
approve by pressing the SET button.
Fig. 6. Overview menu.
3.3.2 Screen – parameters of the PSU.
The screen displays electrical parameters and the technical outputs’ status during operation. Highlighting of
an element informs about an active state and reflects the status of LEDs on the pcb of the PSU. (see table 1, [12]).
Fig. 7. Screen – parameters of the PSU.
Table 5. Description of the symbols on the screen – parameters of the PSU.
Screen field
Description
- Indicates presence of AC power (highlighted = AC power present)
- Indicates battery charging process (highlighted = charging in process)
- Indicates the PSU’s overload (highlighted = PSU overloaded)
- Indicates the PSU’s failure (highlighted = failure of the PSU)
- Indicates the battery failure (highlighted = failure of the battery)
- Indicates the EXT IN input status (highlighted = EXT IN input is active)
Current electrical parameters of the PSU:
Uaku – battery voltage
Uaux – output voltage
Iaux – output current
9
www.pulsar.pl
PSBEN3012C/LCD
PSU technical outputs’ status:
EPS – AC network presence indication
open = AC power failure
close = AC power - O.K.
PSU – PSU failure indication
open = failure
close = PSU working correctly - O.K.
APS – battery failure indication
open = battery failure
close = battery O.K.
3.3.3 Screen – history of the PSU’s parameters.
During normal operation the PSU records the electrical parameters delivered to the AUX output and saves
them in its non-volatile memory. The saving occurs every 5 minutes and the internal memory can store up to about
6100 values. The memory works in a circular cycle. When the memory becomes fulfilled, the oldest entries get
replaced with the newest ones.
The screen of the parameters history enables reading of the stored parameters and scanning the values on
a chart. The screen features a time axis, located horizontally in the bottom part of the chart, and the axis of a
selected parameter – located vertically in the left part. The cursor can be moved into various time points via ‘<’ and
‘>’ buttons. For each time point, the corresponding value in can be read.
Fig. 8. Screen of the history of PSU’s parameters.
From the given chart entries, the values of the following parameters can be read:
- Uaux
- output voltage (approximate value within 5 minute period)
- Uaux max
- maximum output voltage
- Uaux min
- minimum output voltage
- Iaux
- output current (approximate value within 5 minute period)
- Iaux max
- maximum output current
- Iaux min
- minimum output current
For optimal reading and analysis of the values shown on the chart, the time range of the chart screen can
be adjusted in the bottom axis. Here are the available ranges:
<8h>
<24h>
<2days>
<week> (weekly)
In order to change the displayed parameter, highlight its name by pressing the ‘SET’ button. Then, with the
‘<’ and ‘>’ buttons choose the requested measurement. Pressing the ‘SET” button again will highlight the time
range of the chart, which can be changed with the ‘<’ and ‘>’ buttons. Another pressing of the ‘SET’ button will
enable moving the cursor (vertical dotted line on the chart) along the time line with the ’<’ and ‘>’ buttons. The
values of currently chosen parameter and the register time pointed by the cursor will also be highlightened,
3.3.4 Screen – failure history.
If any incorrect electrical parameters appear during the operation, the PSU will begin indicating the failure
by cyclical switching on and off the LCD display illumination, illuminating the failure LED on the panel and activating
the acoustic indication (provided, it has not been switched off).
The screen of the PSU failure history enables overviewing the events recorded by the internal diagnostic
system. The memo can store over 2000 events carrying information about the fault type, time of occurrence and
values of the voltages or load current. Additionally, on the basis of the stored parameters, the diagnostic system
assigns the fault code characteristic for a particular event.
The operation history can be previewed by pressing ’<’ or ‘>’. It can be done in two modes: short (date,
time, code, fault description) or full - with additional information about values of voltages and current, and status of
inputs and outputs. Switching between the modes is to be done by the ‘SET’ button.
10
www.pulsar.pl
PSBEN3012C/LCD
Fig. 9. Failure history screen.
In chapter 9, there have been listed codes of all possible failures that may occur during the PSU operation.
Each code is accompanied by appropriate optical indication on the panel, acoustic indication and activation of a
dedicated technical output.
3.4 PSU settings.
From the desktop’s level, the configuration of the PSU settings is possible. To enter the adjustment mode,
press the ‘SET’ button from the main screen’s level.
Fig .10. Window of the PSU settings.
3.4.1 Password of access.
The PSU operates 3 levels of access to configuration which limit the possibility of changing the PSU’s
settings from the level of the LCD desktop. They are protected with separate passwords.
Keypad password
User password
Installer password
– locks the access to buttons of the LCD desktop, only an idle screen is visible.
In this mode, pressing any button causes a password demand.
– allows access to the desktop’s settings
– full access to the PSU’s settings
The option with the keypad password appears on the screen only after entering the correct user or installer
password.
Table 6. Ranges of access.
Access range
PASSWORD
Buttons
KEYPAD
USER
INSTALLER
•
•
•
Preset passwords:
keypad password
user password
installer password
‘Desktop’
Settings
•
•
– ____ (none)
– 1111
– 1234
11
‘PSU’
Settings
•
www.pulsar.pl
PSBEN3012C/LCD
Entering the password.
- set menu with ‘>’ or ‘<’ Password (enter/change)
- press the ‘SET’ button,
another window with available levels of passwords will
appear
- with ‘>’ or ‘<’ choose the right level of the password
- confirm your choice with the ‘SET’ button
- with ‘>’ or ‘<’ enter the first digit
- confirm your choice with the ‘SET’ button
- with ‘>’ or ‘<’ enter the second digit
- confirm your choice with the ‘SET’ button
- with ‘>’ or ‘<’ enter the third digit
- confirm your choice with the ‘SET’ button
- with ‘>’ or ‘<’ enter the fourth digit
- confirm your choice with the ‘SET’ button
12
www.pulsar.pl
PSBEN3012C/LCD
If the typed password is incorrect, the following message will appear:
Fig. 11. The message after entering a wrong keypad password.
If none of the buttons is pressed within the next 30 seconds, the PSU settings will be locked
automatically.
Password change.
After entering the correct password, it is a possibility to change it. Choose the password that will be altered
and enter the new one.
Skipping the access password.
If the password of access to the PSU’s settings is not required, it can be skipped by typing ‘0000’ as a new
password.
Keypad password ”0000” unlocks the access to the keypad.
User password ”0000” unlocks the access from the user’s level.
Installer password ”0000” unlocks the access from the installer’s level.
Erasing passwords.
If by any chance, the passwords have been lost, there is a procedure that will allow reassigning the
passwords.
Please, do as follows:
a) unplug the PSU from the AC network and the battery for at least 10 seconds
b) press the STOP button on the pcb of the PSU
c) plug in the PSU to the AC power and the battery while having the button pressed for another 10
seconds
d) the PSU will display the message: ”Access unlocked”
e) confirm by pressing the ‘SET’ button
f) go to menu ”Settings -> Password” and change the passwords into new ones
If none of the buttons is pressed within the next 30 seconds, the PSU settings will be locked
automatically.
Keypad password.
If the keypad has been locked due to the access password, the activation of the keypad access will occur
after minimum 30 seconds of not pressing any buttons on the desktop. After this time, pressing any button on the
desktop will display a window witch a password demand. The password is to be entered using ‘<’ or ‘>’ as it has
been explained above.
Fig. 12. Keypad password demand.
13
www.pulsar.pl
PSBEN3012C/LCD
3.4.2 PSU.
The facility is only available after entering the correct installer’s password.
Selecting the “PSU” entry in the setting menu enables entering another menu from which the full PSU’s
settings configuration is possible. After entering the right settings, they are stored in non-volatile memo which
protects the PSU against data loss in case of a failure of mains power decay.
Fig. 13. ‘PSU’ screen
Table 7. Description of the ‘PSU’ screen.
Entry
Battery present
Battery test
Battery protection
EPS output lag
Communication
address
Transmission
Description
YES – battery connected to the PSU
NO – battery not connected to the PSU
(see chapter 4.6)
YES – battery test on
NO – battery test off
(see chapter 4.3)
YES – battery protection function (disconnection) on
NO – battery protection function (disconnection) off
(see chapter 4.2)
Adjustable time lag of AC power failure indication:
5s/2min 20s/17min/2h20min
1÷ 247 PSU address required during the communication with the computer
Defines the speed and protocol of communication
9.6k 8N2
9.6k 8E1
9.6k 8O1
19.2k 8N2
19.2k 8E1 (factory settings)
19.2k 8O1
Setting the battery presence.
- with ‘>’ or ‘<’ choose the Battery presence menu
- press the ”SET” button, you will see the prompt at the end of the line
14
www.pulsar.pl
PSBEN3012C/LCD
- with ‘>’ or ‘<’ set ‘YES’ or ‘NO’
YES – if the battery is connected to the PSU
NO – if the battery is not connected to the PSU
- confirm your choice with the ‘SET’ button
Setting the battery test.
- with ‘>’ or ‘<’ choose the Battery test menu
- press the ”SET” button, you will see the prompt at the end of the line
- with ‘>’ or ‘<’ set ‘YES’ or ‘NO’
YES – battery test on
NO – battery test off
- confirm your choice with the ‘SET’ button
Setting the battery protection.
- with ‘>’ or ‘<’ choose the Battery protection menu
15
www.pulsar.pl
PSBEN3012C/LCD
- press the ”SET” button, you will see the prompt at the end of the line
- with ‘>’ or ‘<’ set ‘YES’ or ‘NO’
YES – battery protection function (disconnection) on
NO – battery protection function (disconnection) off
- confirm your choice with the ‘SET’ button
Setting the EPS output lag.
- with ‘>’ or ‘<’ choose the EPS output lag menu
- press the ”SET” button, you will see the prompt at the end of the line below
- with ‘>’ or ‘<’ choose the time lag
- 5s
- 2min 20s
- 17min
- 2h 20min
- confirm your choice with the ‘SET’ button
16
www.pulsar.pl
PSBEN3012C/LCD
Setting the communication address.
- with ‘>’ or ‘<’ choose the Communication address menu
- press the ”SET” button, you will see the prompt at the end of the line
- change the setting with ‘>’ or ‘<’
1÷ 247 – PSU’s address during communication with the computer
- confirm your choice with the ‘SET’ button
3.4.3 Desktop.
The facility is only available after entering the correct user’s or installer’s password.
.
The ‘Desktop’ menu enables setting the current date, time, brightness, contrast and the language of
messages. Setting the correct date and time is important for keeping chronology of events stored in the memo.
Setting the brightness and contrast guarantees the quality of the displayed messages.
Fig. 14. 'Desktop' screen.
17
www.pulsar.pl
PSBEN3012C/LCD
Setting the language of messages.
- with ‘>’ or ‘<’ choose the Language menu
- press the ”SET” button, you will see the prompt at the end of the line
- with ‘>’ or ‘<’ choose the language of messages
- confirm your choice with the ‘SET’ button
Setting the date.
- with ‘>’ or ‘<’ choose the Date menu
- press the ‘SET’ button,
the prompt will appear at the year digits
- with ‘>’ or ‘<’ set the year
- press the ‘SET’ button,
the prompt will move to the month section
18
www.pulsar.pl
PSBEN3012C/LCD
- with ‘>’ or ‘<’ set the current month
- press the ‘SET’ button,
the prompt will move to the day section
- with ‘>’ or ‘<’ set the current day
- approve the settings with the ‘SET’ button
Setting the time.
- with ‘>’ or ‘<’ choose the Time menu
- press the ‘SET’ button,
the prompt will appear at the digits of hours
- with ‘>’ or ‘<’ set the hour
- press the ‘SET’ button,
the prompt will move to the minute section
- with ‘>’ or ‘<’ set the minutes
- press the ‘SET’ button,
the prompt will move to the second section
- with ‘>’ or ‘<’ set the seconds
- approve the settings with the ‘SET’ button
Setting the highlighting.
Intensity of the LCD highlighting (brightness) can be adjusted within the range of 0 to 100% with a 10%
step. The display features a function of constant or temporary highlighting. In the mode of time highlighting the
screen blanking is on after 60 seconds counting from the last pressing of the button on the panel. To set the
intensity with the screen blanking, the following procedure is to be followed:
19
www.pulsar.pl
PSBEN3012C/LCD
- with ‘>’ or ‘<’ choose the Highlight. menu (abbr. Highlighting)
- press the ‘SET’ button, the prompt will appear next to the constant< option
- with ‘>’ or ‘<’ change the setting into 60 s
- press the ‘SET’ button, the prompt will move to the end of the line
- with ‘>’ or ‘<’ set the demanded screen brightness
- approve your choice with the ‘SET’ button
Setting the contrast.
- with ‘>’ or ‘<’ choose the Contrast menu
- press the ‘SET’ button, the prompt will appear at the end of the line
20
www.pulsar.pl
PSBEN3012C/LCD
- with ‘>’ or ‘<’ set the contrast
- approve your choice with the ‘SET’ button
3.5 Acoustic indication.
Emergency situations are acoustically indicated. The frequency and the number of signals depend on an
event type (see chapter 9). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]).
Table 8. Acoustic indication.
No.
1
2
3
4
5
6
7
Description
1 signal per 10s, battery-assisted
operation
1 signal per 10s, mains operation
2 signals per 10s, battery-assisted
operation
Fast signals, battery-assisted operation
Continuous indication
1 signal
2 signals
Event
No 230V AC supply
Battery fault, undercharged battery
Low level of battery charge
The PSU will be disconnected due to the battery discharge
PSU failure [see chapter 9]
Breaking the battery test
Activation of the battery test
3.6 Technical outputs.
The PSU feature indication outputs, with galvanic isolation, which change state if any of the following event
occur:
•
EPS FLT – output indicating AC power loss.
The output indicates AC power loss. Under normal status – with the 230V AC supply, the output is
close. In case of a power failure the PSU will switch the output into the open state after a period of time
determined by the ‘EPS output lag’ facility (see 3.4.2, table 7).
•
APS FLT - output indicating battery failure.
The output indicates a failure in the battery circuit. Under normal status (during correct operation) the
output is close. In case of a failure the PSU will switch the output into the open state. Any failures can be
triggered by the following events:
- a faulty or undercharged battery
- battery voltage below 11,5V during battery-assisted operation
- battery fuse fault
- no continuity in the battery circuit
•
PSU FLT - output indicating PSU failure.
The output indicates the PSU failure. Under normal status (during correct operation) the output is close.
In case of a failure the PSU will switch the output into the open state. Any failures can be triggered by the
following events:
- low output voltage Uaux<11,8V
- high output voltage Uaux>14,7V
- high battery voltage Uaku>14V (during battery test)
- failure of the battery charging circuit
- polymer fuse PTC activation
- exceeding the PSU nominal current
- failure in the battery charging circuit
- activation of the over voltage protection OVP
The technical outputs have been implemented with galvanic isolation between the PSU’s systems and the
attached devices.
21
www.pulsar.pl
PSBEN3012C/LCD
Fig. 15. Electrical diagram of the technical outputs.
•
TAMPER - output that indicates tampering with the PSU enclosure: output with volt-free (potentialfree) contacts indicating the door status and PSU detachment from the mounting surface. NC contacts: the
PSU is locked and fixed to the dedicated surface.
3.7 Input of collective failure: EXT IN.
The EXT IN (external input) technical input indicating a collective failure is intended for additional, external
devices that generate the failure signal. If voltage appears at the EXT IN input, it will cause generating a PSU
failure, storing the information about the event in the internal memo and sending the signal about the failure to the
PSU FLT output.
The EXT IN technical input has been implemented with galvanic isolation between the PSU’s systems and the
devices attached.
Fig. 16. Electrical diagram of the EXT IN input.
The electrical diagram below shows the way of connecting external devices to the EXT IN input. Outputs
such as: OC (open collector), relay type or tamper may be used as a source of the signal.
Fig. 17. Examples of connections.
In the option with tamper switches, the VEXT jumper must be on. It polarises the EXT IN input circuit
therefore is required in such configuration.
The EXT IN input has been adjusted to cooperate with fuse modules that generate a failure signal in case
of a fuse fault in any of output sections (e.g. AWZ535, AWZ536). To guarantee a correct cooperation between the
module and the EXT IN input, the VEXT jumper must be on and the connections are to be made accordingly to the
diagram below.
Fig. 18. Example of a connection with the fuse module AWZ535 or AWZ536.
22
www.pulsar.pl
PSBEN3012C/LCD
4. Battery-assisted operation.
4.1. Running the PSU from the battery.
The PSU has been equipped with two buttons on the pcb board which enable running or disconnecting the
PSU during battery-assisted operation.
• Running the PSU from the battery: press the START button on the main board and hold for 1s.
• Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s.
4.2. Deep discharge battery protection UVP.
The PSU is equipped with the disconnection system and the discharged battery indication. If the voltage at
the battery terminals drops below 10V±0.2V during battery-assisted operation, the battery will be disconnected
after appr.15s.
Switching off/on the function of the battery protection:
Press the ‘SET’ button from the level of the LCD desktop and then choose:
”PSU -> Battery protection: YES/NO” (see chapter 3.4.2, table 7).
Caution.
Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its
capability of storing energy, lowers its capacity and shortens its durability.
4.3 Dynamic battery test.
The PSU runs a battery test every 10 minutes. It is done by a momentary switching into a battery-assisted
operation. A failure is indicated when voltage drops below 12V. The battery test facility can be switched off.
Deactivating/activating the test:
- enter the PSU settings from the level of the LCD desktop by pressing the ‘SET’ button. Then choose:
”PSU -> Battery protection: YES/NO” (see chapter 3.4.2, table 7) or
- from the pcb level: during mains-powered PSU operation press the STOP button on the main board and
hold it for 3 seconds.
The device will confirm the activation/deactivation of the test (see tab.8 [6, 7]) and show an appropriate
message on the display: ”TEST ON/ TEST OFF”.
Deactivating/activating the test is stored in the memory even after unplugging the device from
mains. The battery failure indication at the APS FLT output is automatically switched off. The
battery protection system against deep discharged remains on, though.
4.4. Standby time.
The standby time during batter-assisted operation depends on: battery capacity, battery charge level and
load current. In order to keep the standby time, the current drawn from the PSU during battery-assisted operation
should be limited. Characteristics for a 17Ah/12V SLA:
Grade 1, 2 - standby time 12h
Output current 1,4A + 1,5A battery charge
Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1).
Output current 0,56A + 1,5A battery charge
- standby time 60h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1).
Output current 0,28A + 1,5A battery charge
23
www.pulsar.pl
PSBEN3012C/LCD
4.5. Battery charging time.
The PSU has a battery circuit charged with direct current. The current selection is done via IBAT jumpers.
The table below shows how long it takes to charge a (fully discharged) battery up to min. 80% of its nominal
capacity.
Table 9. Battery charging time.
17Ah battery charging time
up to capacity of 0,8*C
10h12m
15h18m
25h30m
-
Charging
current [A]
1,5
1
0,6
0,2
Configuration of
IBAT jumper
J1=
J1=
J1=
J1=
, J2=
, J2=
, J2=
, J2=
, J3=
J3=
J3=
J3=
4.6 Operation without a battery.
In case of an expected PSU operation without an attached battery, make a necessary configuration setting
from the level of the LCD desktop (see chapter 3.4.2, table 7).
”Settings -> PSU -> Battery present: YES/NO”
In this mode the automation system allows adjustments of PSU’s output voltage without indicating a failure
connected with working of the battery.
CAUTION. During operation without battery assistance the PSU does not perform any parameter
control that monitors its proper operation. Therefore, this mode ought to be chosen thoughtfully.
24
www.pulsar.pl
PSBEN3012C/LCD
5. Remote monitoring (option: Wi-Fi, Ethernet, RS485, USB).
The PSU has been adjusted to operate in a system that requires a remote control of the parameters in a
monitoring centre. Transmitting data concerning PSU status is possible due to an additional, external
communication module that is responsible for communication in Wi-Fi, Ethernet or RS485 standard. A USB-TTL
interface enables connection between the PSU and a computer.
5.1 Communication in WI-FI wireless network.
WI-FI wireless communication can be implemented on the basis of the additional WI-FI ”INTWF” interface
which works within the frequency range of 2,4GHz accordingly to the IEEE 802.11b standard. The interface shall
be mounted in a selected location, inside the enclosure so that the aerial protrudes outwards.
A great advantage of wireless communication is lack of additional cords and fast development or
modification of the network’s structure.
Fig. 19. WI-FI communication with the use of the WI-FI ”INTW” interface.
5.2 Communication in ETHERNET network.
Communication in the Ethernet network is possible due to the additional Ethernet ”INTE” interface compliant
with the IEEE802.3 standard, featuring a built-in connection socket RJ45. This interface features full galvanic
isolation and protection against surges.
Fig. 20. Ethernet communication with the use of the Ethernet ”INTE” interface.
5.3 Communication in RS485 network.
Another kind of network communication is the RS485 that uses a two-wire transmission line. To implement
this kind of data exchange, the PSU needs to be equipped with the additional RS485-TTL ”INTR” interface which
converts data from the PSU into the RS485 standard and the USB-RS485 ”INTUR” one that converts data from the
RS485 network into a USB. These interfaces feature full galvanic isolation and protection against surges.
25
www.pulsar.pl
PSBEN3012C/LCD
Fig. 21. RS485 communication with the use of the interfaces: ”INTR” and ”INTUR”.
5.4 USB-TTL communication.
If the PSU does not cooperate with any of previously mentioned network and the access to the parameters’
adjustment and memo readings are necessary, the USB-TTL ”INTU” needs to be used. This interface allows direct
connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM
port.
Fig. 22. USB-TTL communication with the use of the USB-TTL ”INTU” interface.
5.5 ”Power security” program.
”Power security” is a computer program that has been created for displaying and analysing the information
sent from the PSU installation spots. Here is its front panel:
Fig. 23. Front panel of “Power security” program.
26
www.pulsar.pl
PSBEN3012C/LCD
The main panel of the program has been formulated in such a way that it is possible to divide it into smaller
areas, depending on the number of power supplies.
The program enables both a visualisation and an analysis of the received data. Exceeding of the acceptable
parameters is indicated by highlighting in red the appropriate area or by twinkling of the indicator. Particular tabs
contain a chart with an overview of the PSU parameters and failure memo along with the information about status
and the electrical specifications of the technical outputs.
The ”Power Security” program is available on our website: www.pulsar.pl
Its detailed description can be found in the manual of the program.
6. Technical specifications.
Electrical specifications (tab.10).
Mechanical specifications (tab.11).
Operation safety (tab.12).
Operating specifications (tab.13).
Factory settings (tab. 14).
Table 10. Electrical specifications.
PSU type
Mains supply
Current consumption
Power frequency
PSU’s power
Efficiency
Output voltage
Output current
Output voltage setting, escalation and keeping
time
Output voltage adjustment range
Ripple voltage
Current consumption by the PSU systems
during batter-assisted operation
Battery charging current
Low battery voltage indication
Over voltage protection OVP
Short circuit protection SCP
Overload protection OLP
Battery circuit protection SCP and reverse
polarity connection
Deep discharge battery protection UVP
Technical outputs:
- EPS FLT; output indicating AC power failure
- APS FLT; output indicating battery failure
- PSU FLT; output indicating PSU failure
- TAMPER output indicating enclosure opening
and detachment from the mounting surface
A, protection grade 1÷3, II environmental class
230V/AC (-15%/+10%)
0,39 A
50Hz
44 W
70%
11,0V÷13,8 V DC – buffer operation
10,0V÷13,8 V DC – battery-assisted operation
- for grades 1, 2:
Io = 1,4A + 1,5A battery charge
- for grade 3:
Io = 0,56A + 1,5A battery charge - (connection with
ARC required, compliant with 9.2 – PN-EN 50131-1)
Io = 0,28A + 1,5A battery charge
- for general use:
Io = 3A + 0,2A battery charge
Io = 2,6A + 0,6A battery charge
Io = 2,2A + 1A battery charge
Io = 1,7A + 1,5A battery charge
5ms / 40ms / 18ms
12 V÷ 14,5 V
30 mV p-p max.
I = 26mA
I = 17 mA – highlighting of the LCD desktop is off
0,2A / 0,6A/1A/1,5A –IBAT jumper selectable
Ubat < 11,5V, during battery-assisted operation
U>15,5V, disconnection of the output voltage, automatic return
(AUX+ disconnection)
200% ÷ 250% of the PSU power - current limiting and/or fuse
fault in the battery circuit (fuse-element replacement required)
Program - equipment
F5 A- current limiting, FBAT fuse (failure requires fuse-element
replacement)
U<10,0 V (± 2%) – disconnection (-BAT) of the battery,
adjustment from the LCD desktop’s level
- type – electronic, max 50mA/30V DC, galvanic isolation
1500VRMS
- time lag, approx. 5s/140s/17m/2h 20m (+/-5%)
- type – electronic, max 50mA/30V DC, galvanic isolation
1500VRMS
- type – electronic, max 50mA/30V DC, galvanic isolation
1500VRMS
- microswitches x2, NC contacts (enclosure closed and fixed to
the mounting surface), 0,[email protected] DC (max.)
27
www.pulsar.pl
PSBEN3012C/LCD
Voltage ’on’ – 10÷30V DC
Voltage ’off’ – 0÷2V DC
Level of galvanic isolation: 1500VRMS
- LEDs on the PSU’s pcb,
- LCD panel
• electrical parameters reading
• failure indication
• PSU settings adjusted from the panel’s level
• 3 levels of access, password-protected
• PSU operation history – 6144 values
• failure history - 2048 events
• real-time clock, battery-backed
- piezoelectric indicator ~75dB /0,3m, switched via jumper
EXT IN technical input
Optical indication:
Acoustic indication:
3V, lithium, CR2032
F 5,A / 250V
T 0,63A / 250V
LCD display’s battery
FBAT fuse
FMAIN fuse
Table 11. Mechanical specifications.
Enclosure dimensions
Fixing
Fitting battery
Net/gross weight
Enclosure
Closing
Connectors
Notes
300 x 300 x 98 (305 x 305 x 90+8) (WxHxD) [mm] (+/- 2)
272 x 247 x Φ 6 x4 (WxH)
17Ah/12V (SLA) max.
4,4/4,8 kg
Steel plate DC01 1mm, colour RAL 9005 (black)
Cheese head screw x2 (at the front), lock assembly possible
Supply: Φ0,63÷2,50 (AWG 22-10)
Outputs : Ф0,51÷2 (AWG 24-12)
Battery outputs BAT: 6,3F-2,5, 30cm,
TAMPER output: wires, 25cm
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Table 12. Operation safety.
Protection class PN-EN 60950-1:2007
Protection grade PN-EN 60529: 2002 (U)
Electrical strength of insulation:
- between input (network) circuit and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
Insulation resistance:
- between input circuit and output or protection circuit
I (first)
IP20
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
100 MΩ, 500V/DC
Table 13. Operating specifications.
Operating temperature
Storage temperature
Relative humidity
Vibrations during operation
Impulse waves during operation
Direct insolation
Vibrations and impulse waves during transport
-10ºC...+40ºC
-20ºC...+60ºC
20%...90%, without condensation
unacceptable
unacceptable
unacceptable
PN-83/T-42106
Table 14. PSU’s factory settings.
Indication time of EPS network loss
Battery charging current
Battery presence
Battery test
Deep discharge battery protection UVP
Communication address
Transmission
Highlighting
Passwords:
- keypad’s
- user’s
- installer’s
5s
1,5A
YES (battery present)
YES (activated)
YES (battery protected)
1
19.2k 8E1
Constant – 50%
(n/a)
1111
1234
28
www.pulsar.pl
PSBEN3012C/LCD
7. Installation.
7.1 Requirements.
The buffer PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable
and required for a given country) for 230V/AC interference and low-voltage installations. The unit should be
mounted in confined spaces, in accordance with the II environmental class, with normal relative humidity (RH=90%
maximum, without condensation) and temperature from -10°C to +40°C. The PSU shall work in a vertical p osition
that guarantees sufficient convectional air-flow through ventilating holes of the enclosure.
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an
appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user shall be
informed about the method of unplugging (most frequently through separating and assigning an appropriate fuse in
the fuse-box). The electrical system shall follow valid standards and regulations.
7.2 Installation procedure.
CAUTION!
Before installation, cut off the voltage in the 230V power-supply circuit.
To switch off power use an external switch in which the distance between the contacts of all poles in the
disconnection state is not less than 3mm.
1. Mount the PSU in a selected location. It is crucial to bolt the tamper grip to the mounting surface. The grip
is located in the central part of the enclosure (see fig. 3 [7]) and guarantees indication in case of any
attempts of detaching the device from the mounting surface. Proper installation is one of the requirements
of the PN-EN 50131-6 standard.
Fig. 24. Fixing a tamper grip.
2.Connect the power cables (~230Vac) to L-N terminals of the PSU. Connect the ground wire to the terminal
marked by the earth symbol: PE. Use a three-core cable (with a yellow and green PE protection wire) to make the
connection. Lead the cables to the appropriate terminals through the insulating bushing.
The shock protection circuit shall be performed with a particular care, i.e. the yellow and green wire coat
of the power cable shall stick to one side of the terminal - marked with the PE symbol on the PSU
enclosure. Operation of the PSU without the properly made and fully operational shock protection circuit
is UNACCEPTABLE! It can cause a device failure or an electric shock.
3. Connect the receivers’ cables to the +AUX, -AUX connectors of the terminal block on the PSU board.
4. If necessary, connect the device’s leads to the technical inputs and outputs:
- EPS FLT; technical output of AC power loss indication (alarm panel, controller, indicator, etc.)
- PSU FLT; technical output of the PSU failure.
- APS FLT; technical output of the battery failure.
- TAMPER; output indicating enclosure opening or detaching from the assembly surface.
- EXT IN; collective failure output
5. With the IBAT jumper determine the maximum battery charging current, in accordance with the battery
parameters.
6. From the level of the LCD panel decide whether the function of discharged battery disconnection U<10 V (+/-5%)
is to be on or off (see chapter 3.4.2).
29
www.pulsar.pl
PSBEN3012C/LCD
7. Switch on the ~230V AC supply (red AC diode and green AUX diode should be lit).
8. Check the output voltage (the PSU voltage without load and without a battery should amount to 13,7 V ÷ 13,9 V,
with a battery or during battery charging process: 11,0 V÷13,8 V). If the value of the voltage requires adjustment, it
should be set by the VADJ potentiometer, monitoring the voltage at the AUX output of the PSU.
9. Connect the batteries in accordance with the markings: +BAT red to 'plus', -BAT black to 'minus’. The LB diode
should be on during battery charging process.
10. With the STOP button, activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU
failure indication at the APS FLT output, but it does not affect the protection system against complete battery
discharge.
11. Check the current consumption of the receivers allowing of the battery charging current no to exceed the total
current efficiency of the PSU.
12. Once the tests and operation control have been completed, the enclosure can be locked.
8. Operation and use.
8.1. Over voltage protection OVP at the PSU output.
In case of voltage exceeding 15.5V±0.5V at the regulator’s output, the system cuts off the power at the
outputs to protect the battery and the receivers from damage. The outputs will be battery-powered. The protection
system is indicated by illuminating of the OVP red LED on the pcb board, PSU FLT output status change opening
state, acoustie and appropriate message on the PSU front panel.
8.2 Overload of the PSU.
The PSU has been equipped with a LED OVL (overload) indicator light on the pcb. It informs about the
output overload status. If the nominal current of the PSU is exceeded, the indicator light will be lit and the
microprocessor will proceed to a specially implemented procedure. If the overload threatens the PSU’s power
grade, the control system will decide about a disconnection of the AUX output. Restart will occur after 1 minute.
8.3 Short circuit at the PSU output.
In the case of a short circuit at the AUX, BAT output (load 200% ÷ 250% of the PSU power) or a reverse
polarity connection, the FBAT fuse in the battery circuit becomes permanently damaged and the restoration of the
voltage at the BAT output requires replacement of the fuse.
8.4 Battery replacement.
The battery replacement of the LCD panel should be done when the PSU is supplied from mains or a battery. This
will prevent the time settings from erasing
CAUTION!
The removed batteries ought to be stored in a dedicated place. The poles should not be
reversed. The use of the batteries of a different kind is forbidden. Tampering with the battery
may lead to its explosion.
8.5. Maintenance.
Any and all maintenance operations may be performed following the disconnection of the PSU from the
power supply network. The PSU does not require performing any specific maintenance measures. However, in
the case of significant dust level, clean its interior with compressed air. In the case of a fuse replacement, use a
replacement of the same parameters.
30
www.pulsar.pl
PSBEN3012C/LCD
9. PSU FAILURE CODES.
Failure
code
EXT
LED indication
F01
F02
Acoustic
indication
OVL
AC
PSU
APS
-
-
-
-
-
1 beep
per 10s
-
-
twinkles
-
ON
ON
Technical
outputs
activation
EPS FLT
PSU FLT
Fault description
Battery-assisted
operation
PTC polyswitch
activation at the
AUX output
APS FLT
F03
-
F04
-
F05
-
-
F06
-
-
F07
-
-
-
ON
ON
ON
ON
ON
ON
-
twinkles
ON
ON
-
ON
-
ON
1 beep
per 10s
1 flash
-
ON
2 flashes
-
ON
Blown fuse of the
battery FBAT
PSU FLT
APS FLT
PSU FLT
PSU FLT
-
Faulty battery*
Too high output voltage
Too high battery
voltage*
PSU FLT
Battery charging circuit
failure
F08
-
-
ON
3 flashes
-
ON
F09
-
-
ON
4 flashes
-
ON
PSU FLT
F10
-
-
-
-
ON
2 signals
per 10s
APS FLT
F11
-
-
-
-
ON
Fast
audible
signals
F12
ON
-
-
-
-
-
-
-
ON
-
-
-
-
F50
F51
F60
F61-64
F65
ON
ON
APS FLT
ON
PSU FLT
ON
PSU FLT
-
ON
PSU FLT
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
31
Too low output voltage
Too low battery voltage
PSU disconnection
caused by battery
discharge
Activation of the EXT IN
collective failure input
Internal damage of the
PSU
Error in setting memo
No communication
Desktop fault
-
Causes
- No AC mains
supply
- Faulty main fuse
FMAIN
- Overloaded AUX
output
- Short circuit in the
battery circuit
- Short circuit in the
AUX output circuit
- Overloaded AUX
output
- Overloaded AUX
output
- Drained battery
- Undercharged
battery
- Unplugged battery
- Output voltage
>14.7V
- Battery voltage
> 14V
- Too low output
voltage of the PSU,
set <13V
- Fault in the battery
charging circuit
- Output voltage
<11.8V (during buffer
operation)
- Battery voltage
drops below 11.5V
(during batteryassisted operation)
- Battery voltage
drops below 10V
(during batteryassisted operation)
Broken cord between
the PSU and the
display
Password unblocking
procedure
www.pulsar.pl
PSBEN3012C/LCD
WEEE MARKING
According to the EU WEE Directive – It is required not to dispose of electric or electronic waste as
unsorted municipal waste and to collect such WEEE separately.
CAUTION! The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but
recycled according to the applicable law.
GENERAL WARRANTY CONDITIONS
1. Pulsar K. Bogusz Sp.j. (the manufacturer) grants a five-year warranty for the equipment, starting from the initial product date
of purchase placed on the receipt.
2. If a purchase proof is missing, a five -year warranty period is counted from the device’s production date.
3. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the
manufacturer’s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects, unless such
defects have been reported within the warranty period (item 1 and 2).
4. The equipment subject to warranty is to be brought to the place where it was purchased, or directly to the main office of the
manufacturer.
5. The warranty applies to complete equipment, accompanied by a properly filled warranty claim with a description of the defect.
6. Should the claim be accepted, the manufacturer is obliged to provide warranty repairs, at the earliest convenience, however not
later that within 14 days from the delivery to the service centre of the manufacturer.
7. The repair period mentioned in item 6 may be prolonged, if there are no technical possibilities to carry out the repairs, or if the
equipment has been conditionally accepted, due to the breaking warranty terms by the claimant.
8. All the services rendered by force of the warranty are carried out at the service centre of the manufacturer, exclusively.
9. The warranty does not cover the defects of the equipment, resulting from:
- reasons beyond the manufacturer's control,
- mechanical damage,
- improper storage and transport,
- use that violates the operation manual or equipment’s intended use
- fortuitous events, including lightning discharges, power failures, fire, flood, high temperatures and chemical agents,
- improper installation and configuration (in defiance with the manual),
10. The warranty is void in any of the following circumstances:
- construction changes
- repairs carried out by any unauthorized service center
- damage or removal of warranty labels
- modifications of the serial number
11. The liability of the manufacturer towards the buyer is limited to the value of the equipment, determined according to the
wholesale prices suggested by the manufacturer on the day of purchase.
12. The manufacturer takes no responsibility for the defects that result from:
- the damaging, malfunctioning or inability to operate the equipment
- defects that result from using the equipment outside its stated specifications and operating parameters failing to abide by the
recommendations and requirements contained in the manual, or the use of the equipment.
Pulsar K.Bogusz Sp.j.
Siedlec 150,
32-744 Łapczyca, Polska
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail: [email protected], [email protected]
http:// www.pulsar.pl, www.zasilacze.pl
32