GW (Discontinued)

GW (Discontinued)
Installation Guide
Air Quality
TM
G Series
Carbon Monoxide Transmitter
and Fan Controller
Product Overview
The G Series carbon monoxide detectors measure CO levels and signal control systems to provide an inlet of fresh
air optimal for the space at a given time. G Series devices are equipped with a relay contact that closes when
the CO level is below 25 ppm and opens when the CO level is above 25 ppm (when used with a normally closed
contactor). Removal of the sensor, interruption of power, or cut wires cause the relay circuit to open and start the
fan. Minimum relay cycle time is 3 minutes to prevent fan short-cycling.
NOTICE
Audible Alarm: An 85 dB alarm sounds if the CO level rises above 100 ppm for 30 minutes.
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
Product Identification
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
G
Enclosure
Output
Auxiliary Alarm Output
D = Duct mount
W = Wall mount
V = Field-selectable,
0-5/0-10VDC
M =4-20mA
R = Relay only
US or EU
S
A = Auxiliary Contact
X = None
= Standard
Specifications
Input Power
15-30VDC/24VAC, [email protected]
Sensor Type
Digitally profiled metal oxide semiconductor (MOS)
Sensor Life
Detection Range
5-10 years typical, replaceable
0 to 200 ppm
Analog Output
3-wire sourcing, 4-20mA or user selectable 0-5V/0-10V (specify mA
or V)
Output Scaling
User-selectable 100 ppm F.S. or 200 ppm F.S.
Response Time
2 min 30 sec sample interval cycle
Relay Output
Relay Setpoint
High Limit Setpoint
High Limit Alarm
High Limit Contact (-AS Models)
LED Indicators
N.O. Form A (SPST) [email protected]/VDC; (Use with N.C. contactor)
25 ppm
100 ppm for 30 minutes
Audible, 85 dB, resets below 100 ppm (solid-state contact for -AS
version)
250VAC/DC, 120mA max. Ron 35 Ω
Solid Green = Normal; Solid Red = Call for ventilation;
Flashing Green = Sensor life has expired; Flashing Red = High-limit
alarm
Operating Temperature Range
Operating Humidity Range
Coverage
Housing
Z202025-0R
Page 1 of 3
-20° to 50°C (-4° to 122°F)
0 to 90% RH non-condensing
5000-7500 sq ft typical (465-697 sq m)
White powder coat over steel
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Air Quality
G Series
TM
Dimensions
0.9" dia.
(22 mm)
2.5"
(63 mm)
2.4"
(55 mm)
4.5”
(114 mm)
4"
(102 mm)
5.0"
(127 mm)
2.25"
(57 mm)
Installation
1. Lock out all power supplies prior to installation.
2. Select a location for the sensor in a secure area where it will be accessible only to qualified service personnel. Install the G Series
sensor centrally in the parking structure, near the main traffic paths, but away from outside air vents and excessive drafts.
Mount the unit securely to a wall or column at a height of about 5 ft. (1.52 m) from the floor.
3. Connect wiring as shown below. If using a voltage output model, use the output jumper to select 0-5 V or 0-10 V.
CONTACTOR
POWER
-
SENSOR
+
V in
COMM
OUT
-
FAN
POWER
ALARM
N.O.
N.C.
CONTACTOR
+
0-10V/0-5V
or
4-20mA
DDC
SYSTEM
SENSOR DETAIL
10V
Common
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
N.O. Relay
N.O. Relay
5V
OUTPUT
100
200
PPM
4. Apply power to the unit. A green LED on the circuit board indicates proper operation of the power supply.
Coverage is not dependent on the sensor. Coverage is a function of the building structure and air flow patterns. Wide open areas where the air is well mixed may
require multiple sensors.
Z202025-0R
Page 2 of 3
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Air Quality
G Series
Service
TM
For any service or installation, consult qualified service personnel. To ensure continued reliable operation, replace the sensor
module every five years with a Veris Industries CO sensor replacement module (Veris part number AA09).
Replacement instructions:
1. Disconnect power from the unit.
2. Carefully remove the old sensor module.
3. Install the new module firmly into the socket.
4. Reconnect power to the unit.
5. The replacement sensor requires 96 hours to stabilize after initial power application.
The sensor module is factory calibrated. No field calibration is required or possible. Verify proper operation by observing the LED
indicators.
Troubleshooting
Problem
Solution
4-20 mA output does not function • Verify that the unit is a 4-20 model.
• Verify that the unit is wired for sourcing output.
Z202025-0R
Page 3 of 3
Output is half or twice what is
expected
• Verify span jumper is set to desired scale.
• For voltage units, verify jumper is set to desired
voltage output scale.
Output is inaccurate or unstable
• Allow 96 hours for sensor to burn in and stabilize.
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.