GIVARE
GB.GIVARE.050101
Instructions for Installation
Room sensor, for wall mounting, IP20, Part No. 018926
Outdoor/room sensor, watertight, IP43, Part No. 018954,
GOLD
1. General
The sensor kit consists of a sensor, junction box for transition from modular connector to screw terminal block and
an 8 metre long cable with modular connector at both
ends.
2. Field of Application
The room sensor is intended for use as a replacement for
the extract air sensor situated inside the GOLD air handling unit. The room sensor can be used in systems that
supply air to several rooms/zones and if the temperature in
one of the rooms is to be given priority. It can also be used
if the temperature drops in the extract air duct upstream
of the measuring point inside the air handling unit.
The outdoor/room sensor is intended for use as a replacement for the outdoor air sensor situated inside the GOLD
air handling unit.
The outdoor/room sensor can be used if it is necessary to
measure the outdoor temperature while the air handling
unit is shut down or if the damper in the outdoor air duct
is closed. The sensor can also be used as a room sensor in
applications that require a higher enclosure class.
3. Mounting
3.1 Room sensor
Carefully remove the upper, smaller cover. Then unscrew
the screw to remove the lower, larger cover. Secure the
sensor to an interior wall by means of two screws. The air
slots that allow air to pass through the sensor must be vertical. Locate the sensor at a representative measurement
point, about 1.5 meters above the floor. Avoid locating
the sensor near sources of disturbance such as radiators,
direct sunlight and the like.
3.2 Outdoor/room sensor
Secure the sensor on an external wall by means of two
screws. Note that the sensor shall be mounted with the
cable gland facing down. Locate the sensor at a representative measurement point, about 1.5 meters above the
floor. Avoid sources of disturbance such as direct sunlight,
exhaust air discharge and the like. If the sensor is used as a
room sensor, it should be located and mounted as described under item 3.1 above.
Specifications are subject to alteration without notice.
4. Technical Details
4.1 Room sensor
Dimensions (WxHxD)
Enclosure class
Measuring range
80x80x16 mm
IP 20
-50 °C – +70 °C
4.2 Outdoor/room sensor
Dimensions (WxHxD)
Enclosure class
Measuring range
52x55x27 mm
IP 43
-50 °C – +70 °C
4.3 Junction box
Dimensions (WxHxD)
Measuring range
52x58x21 mm
IP 20
www.swegon.se
1
GB.GIVARE.050101
5. Electrical Connections
To be carried out by a qualified electrician in accordance
with local regulations. The temperature sensor is digital
and, depending on the nature of the installation, may be
sensitive to external interference.
The cable to the sensor must not be arranged to run parallel with power cables. If the sensor cable crosses power
cables, it should do so at a right angle to them. If there
is risk of interference, a shielded sensor 
cable shouldbe
 
used.
The cable
shield should
to earth(GND)

 
 be connected





in
the junction
box
and not
connected in the sensor.
Connect the cable with modular connector to the control
  

unit of the GOLD air handling unit. See the Instructions
   
for Operation and Maintenance Instructions, Section 10.5,

Electrical Wiring Diagram.



Junction box for transition from Modular cable to screw
terminal block connection
Sensor
Modular cable for connection to the control unit
of the GOLD air handling unit (8 metres long).
DATA/Green
Max. length 22 m.
Min permissible cable cross section. 0,5 mm²
DATA
GND
GND/Red
2
www.swegon.se
Specifications are subject to alteration without notice.