ACTUATORa

ACTUATORa
ACTUATOR
Thermo-actuator
ACTUATOR
General
ACTUATOR – thermo-actuator with on/off functionality
Quick facts
► Available in two versions – normally closed (NC) and
normally open (NO)
► Position indicator shows when the actuator is
open or closed
► First Open-funcion facilitates pressure test at delivery
► Valve adapter (ADAPT Valve) is included at delivery
► ACTUATOR Adapter – alternative valve adapters for easy
fitting to leading suppliers are available as accessories
1
WISE
Description
• Thermo-actuator, on/off in NC/NO versions with pinconnection cable ends.
• NC – Normally Closed. Deenergized closed, commonly
used on cooling valves.
• NO – Normally Open. Deenergized open, commonly
used on heating valves.
• Older ADAPT and CONTROL controllers only support
NC valve functionality.
Ordering key
Valve actuator
ACTUATOR
a
aa
ACTUATOR Adapter
a
aaa
Version
Type: NC, NO
Accessories
Valve adapter
Version
Electrical data
Supply voltage
24 V AC/DC, ±10%, 0-60 Hz
Temperature
Operating temperature, room air: 0-60 °C
Operating temperature,
energy carrier: 10-100 °C
Cable
Fixed two-wire cable, L= 1.0 m,
Ø 0.75 mm2
Power rating, start-up
6 VA for a maximum of 2 min.
For valve type:
32 = Tour & Andersson
39 = Oventrop
50 = Honeywell, Reich, MNG, Bönisch (H), Cazzaniga
54 = MMA
59 = Danfoss RAV/L
72 = Danfoss RAV
78 = Danfoss RA
80 = Siemens and others
Power rating, operation 1,8 VA
Protection class
IP 54
Actuator power
100 N ±5%
Stroke
4 mm
Weight
0,1 Kg
Connection
As standard, the VA-80 adapter is
included, fits an M30 × 1.5 mm
threaded socket.
”First open”-funCtion
• At delivery, the actuator is set to the ”first open” function.
This means that the actuator is open when it is installed,
making it easier to pressure test and vent the water system.
• The function will be automatically disabled after the
actuator has been energized for approx. 6 minutes.
A clicking noise will be heard after which the actuator will change over to the NC mode and the normal
regulation function will begin.
Figure 1. ACTUATOR valve position indicator. The actuator’s cylinder shaped position indicator clearly shows the current operating
setting from all angles. The actuator is in closed position when the
indicator is at its lowest position, i.e. the same height as the enclosure. The actuator is in open position when the indicator is in the
raised position above the enclosure, i.e. the blue marking is visible.
2
Swegon reserves the right to alter specifications.
20130813
www.swegon.com