Mini8 Controller

Mini8 Controller
Controller
Mini8®
SERIES
• 16 control loops
• 32 analogue inputs
• Modular & compact
• SP programming
• Maths and logic
• Remote HMI
• Modbus RTU
• DeviceNet® network
• Profibus DP network
• Modbus TCP
• EtherNet/IP
• OEM Security
Multi-loop Control
and Data Acquisition
Specification Sheet
The Mini8® Controller offers high performance control usually only
found in Eurotherm® panel mount PID controllers. It is also a very
competitive and compact data acquisition device. Its modular design
enables its I/O and feature set to be selected to cater for a wide range
of applications from simple to complex.
The Mini8 controller is an ideal partner to a programmable logic
controller. Able to multi-drop on either Serial, Fieldbus or Ethernet
communications. It offers a cost effective alternative to performing
analogue measurement or loop control in a PLC. Implementing these
functions in the Mini8 controller reduces the hardware cost of the PLC,
relieving it of the burden of performing analogue functions, often
allowing a lower specification processor to be used.
The feature set is comparable with the Eurotherm 3000 series panel
controllers including its high performance PID control and SP
programming functions together with a range of features such as
Maths, Logic and Timing blocks.
When used in a data acquisition installation the controller’s high density
analogue I/O can be combined with Eurotherm’s 6000 series paperless
graphic recorder.
imagine process excellence
Setpoint programming
Specification
The Mini8 controller can run up to 8 programmer function blocks,
to follow a user defined series of ramp and dwell segments. Each
programmer is capable of running a program of up to 16
segments with 8 event outputs. The event outputs can be used
internally within the configuration soft wiring or to external digital
or relay outputs. (Note that this depends on the type and number
of the hardware outputs fitted).
General
Environmental performance
Power supply voltage:
Supply ripple:
Power consumption:
Operation temperature:
Storage temperature:
Operating humidity:
Max. applied voltage
any terminal:
Recipes
Using a PC tool, recipes can be created that can be used to
change the operating parameters of the Mini8 controller simply by
selecting a new recipe via the HMI. This is very useful where
multiple products are processed using the same controller but
require different parameters to be set.
17.8V dc min to 28.8V dc max.
2Vp-p max.
15W max.
0 to 55°C
–10 to 70°C
5% to 95% RH non-condensing
42Vpk.
The Mini8 controller must be mounted in a protective enclosure.
Electromagnetic compatibility (EMC)
EMC:
EN61326 for Industrial Environments
This controller conforms with the essential protection requirements of the
EMC Directive 2004/108/EC, by the application of EMC standard EN61326.
This instrument satisfies the general requirements of the industrial
environment defined in EN 61326.
Heater failure detection
The Mini8 controller with a CT3 input card fitted, has the capability
of detecting failures in heater loads connected to its time
proportioned outputs. By measuring the current flowing through
the heaters via 3 current transformer inputs the Mini8 controller
can, for up to 8 loops, detect Partial Load failure, Over Current, as
well as SSR short or open circuit. Individual load current
parameters indicate the measurement for each heater. The current
monitor block utilises a cyclic algorithm to measure the current
flowing through one heater per measurement interval.
Electrical safety
Safety:
Meets EN61010, installation category II,
pollution degree 2
INSTALLATION CATEGORY II
This controller complies with the European Low Voltage Directive 73/23/EEC,
by the application of the safety standard EN 61010.
POLLUTION DEGREE 2
Normally, only non-conductive pollution occurs. Occasionally, however, a
temporary conductivity caused by condensation shall be expected.
Toolkit blocks
A range of toolkit functions, including Maths, Logic and Timing
blocks can be used to create custom solutions and small machine
controllers.
Physical
Dimensions:
Weight:
Mounting:
iTools Graphical Wiring Editor (GWE)
The GWE is an extremely easy way to create applications. It allows
users to select the function blocks they wish to use in their
application then connect them together using ‘Soft Wiring’. The
GWE gives the user a pictorial view of exactly what he has
configured and can also be used to monitor runtime conditions.
W124 x H108 x D115mm
1Kg typical
DIN rail to EN50022 35 x 7.5 or
35 x 15 horizontally
Approvals
CE, cUL listed (file E57766)
Communications
Network communications support
Modbus RTU:
RS485, 2 x RJ45, user select switch for 3-wire
or 5-wire
Baud rates: 4800, 9600, 19200
DeviceNet:
CAN, 5-pin standard "open connector" with
screw terminals
Baud rates: 125k, 250k, 500k
Profibus DP:
RS485 via standard 9 pin D connector or
2 RJ45 connectors
Baud rates: Up to 12M set by the Master
Ethernet:
Standard Ethernet RJ45 connector
Baud rate: 10baseT
EtherNet/IP:
Standard Ethernet RJ45 connector
Baud rates: 10baseT
100baseT
Modbus /DeviceNet /Profibus /Ethernet/EtherNet/IP are mutually exclusive
options; refer to the Mini8 controller Order Code.
Configuration communications support
Modbus RTU:
3-wire RS232, through RJ11 configuration port
Baud rates: 4800, 9600, 19200
All versions of Mini8 controller support one configuration port.
The configuration port can be used simultaneously with the network link.
OEM Security
An OEM or reseller can protect their intellectual property by
preventing unauthorised cloning of the configuration.
Eurotherm Part No. HA028480 Issue 9 March 12
2
Mini8 controller Specification Sheet
CT3 3-channel current-transformer input Card
The CT3 supports 3 independent channels designed for heater current
monitoring. A scan block allows periodic test of nominated outputs to detect
load (failure) changes.
Fixed I/O resources
The PSU card supports 2 independent and isolated relay contacts.
Relay output types:
Contact current:
Terminal voltage:
Contact material:
Snubbers:
Contact isolation:
On/Off (C/O contacts, "On" closing the
N/O pair)
<1A (resistive loads)
<42V pk.
Gold
Snubber networks are NOT fitted
42V pkmax.
Channel types:
Factory set accuracy:
Current input range:
Transformer ratio:
Input load burden:
Isolation:
The PSU card supports 2 independent and isolated logic inputs
Input types:
Input logic 0 (off):
Input logic 1 (on):
Input current:
Detectable pulse width:
Isolation to system:
Load failure detection
Requires CT3 module.
Logic (24V dc)
–28.8V to +5V dc
+10.8V to +28.8V dc
2.5mA (approx.) at 10.8V; 10mA max at
28.8V supply
110ms min.
42V pkmax.
Max number of loads:
Max loads per CT:
Alarms:
Commissioning:
Measurement interval:
Input/Output cards
Temperature coefficient:
Cold junction range:
CJ rejection:
CJ accuracy:
Linearisation types:
Total accuracy:
Channel PV filter:
Sensor Break:
Input resistance:
Input leakage current:
Common mode rejection:
Series mode rejection:
Isolation channel-channel:
Isolation to system:
Input types:
Input logic 0 (off):
Input logic 1 (on):
Input current:
TC, mV Input Range: –77mV to +77mV
20 bit (∑Δ converter), 1.6μV with 1.6s
filter time
< ±50ppm (0.005%) of reading/ °C
–10°C to +70°C
> 30:1
± 1°C
C, J, K, L, R, B, N, T, S, LINEAR mV, custom
± 1°C ± 0.1% of reading (using internal CJC)
0.0 seconds (off) to 999.9 seconds, 1st order
low-pass
AC detector: Off, Low or High resistance trip
levels
>100M
<100nA (1nA typical)
>120dB, 47 - 63Hz
>60dB, 47 - 63Hz
42V pkmax.
42V pkmax.
Detectable pulse width:
Isolation channel-channel:
Isolation to system:
Channel types:
Input range:
Calibration error:
Resolution:
Measurement noise:
Linearity error:
Temp coefficient:
Lead resistance:
The supply line is protected to limit total card current to 200mA.
Bulb current:
Isolation channel-channel:
Isolation to system:
The 8 channels are isolated from the system (but not from each other). To
maintain isolation it is essential to use an independent and isolated PSU.
Terminal supply protection:
Isolation (channel-channel):
Isolation to system:
Logic (24V dc)
-28.8V to +5V dc
+10.8V to +28.8V dc
2.5mA (approx.) at 10.8V; 10mA max at
28.8V supply
110ms min.
42V pkmax.
42V pkmax.
RT4 resistance thermometer input card
The RT4 supports 4 independently programmable and electrically isolated
resistance input channels. Each channel may connected as 2 wire, 3 wire or 4
wire.
DO8 8-channel digital output card
The DO8 supports 8 independently programmable channels, the output
switches requiring external power supply. Each channel is current and
temperature protected, foldback limiting occurring at about 100mA.
Channel types:
Channel supply (Vcs):
Logic 1 voltage output:
Logic 0 voltage output:
Logic 1 current output:
Min. pulse time:
Channel power limiting:
16 Time Proportioned Outputs
6 loads per CT input
1 in 8 Partial load failure, Over current,
SSR short circuit, SSR open circuit
Automatic or manual
1 sec - 60 sec
DI8 8-channel logic input card
The DI8 supports 8 independent input channels.
TC8 8-channel and TC4 4-channel TC input card
The TC8 supports 8 independently programmable and electrically isolated
channels, catering for all standard and custom thermocouple types. The TC4
supports 4 channels to the same specification.
Channel types:
Resolution:
A (current)
Better than ±2% of range
0mA to 50mA rms, 50/60Hz nominal
10/0.05 to 1000/0.05
1W
None (provided by CT)
On/Off, Time Proportioned
15V dc to 30V dc
> (Vcs - 3V) (not in power limiting)
< 1.2V dc no-load, 0.9V typical
100mA max. (not in power limiting)
20ms
Current limiting capable of driving shortcircuit load
Card supply is protected by 200mA selfhealing fuse
N/A (Channels share common connections)
42V pkmax.
Resistance/PT100
0 to 600 ohms, –200°C to +850°C for PT100
±0.1ohms ±0.1% of reading, 22 to 500 ohms
±0.3°C ±0.1% of reading, -200°C to +850°C
0.008 ohms, 0.2°C
0.016 ohms, 0.04°C peak to peak, 1.6s
channel filter
0.06 ohms, 0.15°C peak to peak, no filter
±0.02 ohms, ±0.05°C
±0.002% of ohms reading per °C ambient
change relative to normal ambient 25°C
22 ohms max in each leg. Total resistance
including leads is restricted to the 600 ohm
maximum limit. 3 wire connection assumed
matched leads.
300μA
42V pkmax
42V pkmax
AO8 8-channel and AO4 4-channel 4-20mA output card
The AO8 supports 8 independently programmable and electrically isolated
mA output channels for 4-20mA current-loop applications. The AO4 supports
4 channels to the same specification. The AO4 and AO8 modules may only
be fitted in slot 4.
Channel types:
Output range:
Setting accuracy:
Resolution:
Isolation channel-channel:
Isolation to system:
mA (current) Output
0-20mA, 360Ω load max.
±0.5% of reading
1 part in 10000 (1uA typical)
42V pkmax.
42V pkmax.
RL8 8-channel relay output card
The RL8 supports 8 independently programmable channels. This module
may only be fitted in slot 2 or 3, giving a maximum of 16 relays in a Mini8
controller.
The Mini8 controller chassis must be earthed (grounded) using the
protective earth stud.
Channel types:
Maximum contact voltage:
Maximum contact current:
Contact snubber:
Minimum contact wetting:
Min. pulse time:
Isolation (channel-channel):
Isolation to system:
On/Off, Time Proportioned
264V ac
2 amps ac
Fitted on module
5V dc, 10mA
220ms
264V 230V nominal
264V 230V nominal
Eurotherm Part No. HA028480 Issue 9 March 12
3
Mini8 controller Specification Sheet
Process alarms
Number of alarms:
Alarm types:
Software features
Toolkit blocks
User wires:
User values:
2 input maths:
Orderable options of 30, 60, 120 or 250
32 real values
24 blocks Add, subtract, multiply, divide, absolute
difference, maximum, minimum, hot
swap, sample and hold, power, square root,
Log, Ln, exponential, switch
2 input logic:
24 blocks AND, OR, XOR, latch, equal, not equal,
greater than, less than, greater than or
equal to, less than or equal to
8 input logic:
4 blocks AND, OR, XOR
8 input multiple operator:
4 blocks Maximum, Minimum, Average. Input/Outputs
to allow cascading of blocks
8 input multiplexer: 4 blocks 8 sets of 8 values selected by input
parameter
BCD input:
2 blocks 2 decades (8 inputs giving 0 to 99)
Input monitor:
2 blocks Max, min, time above threshold
16 point linearisation:
2 blocks 16-point linearisation fit
Polynomial fit:
2 blocks Characterisation by poly fit table
Switchover:
1 block Smooth transition between two input values
Timer blocks:
8 blocks OnPulse, OnDelay, OneShot, MinOn Time
Counter blocks:
2 blocks Up or down, Directional flag
Totaliser blocks:
2 blocks Alarm at Threshold value
Real time clock:
1 block Day & time, 2 time based alarms
Transducer scaling: 2 blocks Transducer Auto-tare, calibration &
comparison cal
PID control loop blocks
Number of Loops:
Control modes:
Control outputs:
Cooling algorithms:
Tuning:
Auto manual control:
Setpoint rate limit:
Output rate limit:
Other features:
Alarm modes:
32 analogue, 32 digital, 32 Sensor break
Absolute high, absolute low, deviation high,
deviation low, deviation band, sensor break,
logic high, logic low, rising edge, falling
edge, edge
Latching or non-latching, blocking, time
delay
Setpoint programmer
The Setpoint Programmer is a software orderable option.
Number of programs:
Number of segments:
Number of event outputs:
Digital inputs:
Power failure action:
Servo start:
8
128
8 per program (64 total)
Run, Hold, Reset, Run/Hold, Run/Reset,
Program Advance, Skip, Segment, Sync
Ramp, Reset, Continue
PV, SP
Recipes
Recipes are a software orderable option.
Number of recipes:
Tags:
8
24 tags in total
0, 4, 8 or 16 Loops (order options)
On/Off, single PID, Dual channel OP
Analogue 4-20mA, Time proportioned logic
Linear, water, fan, or oil
3 sets PID, One-shot auto-tune
Bumpless transfer or forced manual output
available
Ramp in units per sec, per min or per hour
Ramp in % change per second
Feedforward, Input track, Sensor break OP,
Loop break alarm, remote SP, 2 internal loop
setpoints
Mechanical Details
Allow min 25mm
above and below
each unit
Allow min 25mm
for terminals and
cables
Mounting Information
The Mini8 controller is intended to be
horizontally mounted on symmetrical DIN Rail
to EN50022-35 or 35 x 35 x 15
108mm
124mm
Eurotherm Part No. HA028480 Issue 9 March 12
115mm
4
Mini8 controller Specification Sheet
Communications Interface LEDs
Legend
Colour
Function
Action
RN
Green
Run mode
CC
Green
Configuration activity
FC
Green
Field Comms activity
On – Running
Blinking – Standby/Config
Off – Not Running
On – N/A
Blinking – Config Traffic
Off – N/A
On – Connected
Blinking – Ready Non-enhanced DeviceNet®
Off – Offline
Off – No traffic or offline
Blinking – Comms Traffic Modbus, Profibus, and Ethernet
NET
Bi-Col
Network Status
(enhanced
DeviceNet only)
Off – Offline
Blinking Green – Online but no connections
On Green – Online with connections
Blinking Red – Connection timed out
On Red – Total connection failure
Blinking Red/Green – Comms fault
Off – Not online
Flashing Green – Online but no connection
Steady Green – Online and operating correctly
Flashing Red – Connection timeout
Steady Red – Duplication of IP address
Flashing Green and red – Initialisation
Off – Power not supplied to network
On Green – DeviceNet interface operational
On Red – Power not supplied to controller or Checksum failure
Blinking Red/Off – Recoverable fault. Comms. error between
network and DeviceNet interface
Blinking Red/Green – Power-up tests, failure to enter cyclic states
or invalid baud rate
Off – Not online
Flashing Green – Online but no connection
Steady Green – Online and operating correctly
Flashing Red – Connection timeout
Steady Red – Duplication of IP address
Flashing Green and Red – Initialisation
Network Satus
(EtherNet/IP only)
MOD
Bi-Col
Module Status
(enhanced
DeviceNet only)
Module Status
(EtherNet/IP only)
RL8
AO8/A04
Relay Output
(slots 2 and/or 3 only)
Ananlogue Output
(slot 4 only)
Contact voltage/current –
264V ac/2A RMS max.
Output current – 0 to 20mA
360 ohm max. load.
ISOLATION (264V ac Basic
• Channel to Channel: 264V ac Basic
• Channel to system: Reinforced
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
Note.
AO4 supports Channels
1 to 4 only.
Note.
Protective earth conductor MUST be
used if RL8 module is fitted.
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
RLY1 A
RLY1 B
RLY2 A
RLY2 B
RLY3 A
RLY3 B
RLY4 A
RLY4 B
RLY5 A
RLY5 B
RLY6 A
RLY6 B
RLY7 A
RLY7 B
RLY8 A
RLY8 B
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
OP1+
OP1–
OP2+
OP2–
OP3+
OP3–
OP4+
OP4–
OP5+
OP5–
OP6+
OP6–
OP7+
OP7–
OP8+
OP8–
LEDs
Legend
P
Colour
Green
Function
Indicates Power status
A
Red
Indicates Relay A state
B
Red
Indicates Relay B state
Action
On – Power On
Off – Power Off
On – Energised
Off – De-Energised
On – Energised
Off – De-Energised
Power Supply
Legend
Supply
24V
24V
0V
GND
24V dc
24V dc
0V
Ground
This terminal can accept wire
sizes 0.2 - 2.5mm (24 – 12 awg).
Linked
POWER SUPPLY SPECIFICATON
Power supply voltage: 17.8V dc min to 28.8V dc max.
Power comsumption: 15W max.
Standard I/O Connections
Legend
D1
D2
C
A1
A2
A3
B1
B2
B3
Function
Digital Input 1
Digital Input 2
Digital Input Common
Relay A n/open
Relay A n/closed
Relay A Common
Relay B n/open
Relay B n/closed
Relay B Common
Note.
Digital Inputs: ON requires greater than 10.8V with
2mA drive, 30V max.
Relay Contacts: 1 Amp max, 42V dc max.
COMMUNICATIONS
Communications
connection terminals
are version dependant.
TC8/TC4
RT4
DI8
CT3
DO8
Thermocouple Input
2, 3, 4 Wire RTD Input
Logic Input
Transformer Input
Logic Output
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
ISOLATION
• Channel to Channel: 42V pk.
• Channel to system: 42V pk.
ISOLATION
• Channel to Channel: N/A
• Channel to system: N/A
ISOLATION
• Channel to Channel: N/A
• Channel to system: 42V peak with
independant supply
Note.
Input specification as for
Standard I/O above.
Note.
Isolation provided by current
transformers.
Note.
TC4 supports Channels 1 to 4
only.
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
TC1+
TC1–
TC2+
TC2–
TC3+
TC3–
TC4+
TC4–
TC5+
TC5–
TC6+
TC6–
TC7+
TC7–
TC8+
TC8–
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
CH1 I+
CH1 S+
CH1 S–
CH1 I–
CH2 I+
CH2 S+
CH2 S–
CH2 I–
CH3 I+
CH3 S+
CH3 S–
CH3 I–
CH4 I+
CH4 S+
CH4 S–
CH4 I–
Eurotherm Part No. HA028480 Issue 9 March 12
Wire
Connections
2 3 4
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
D1+
D1–
D2+
D2–
D3+
D3–
D4+
D4–
D5+
D5–
D6+
D6–
D7+
D7–
D8+
D8–
5
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
In1 A
In1 B
No connection
In2 A
In2 B
No connection
In3 A
In3 B
Notes.
Requires 24V dc supply.
* Linked internally.
*
Legend
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Function
Supply in +
Supply in +
OP1+
OP2+
OP3+
OP4+
Supply & OP
Supply & OP –
Supply in +
Supply in +
OP5+
OP6+
OP7+
OP8+
Supply & OP
Supply & OP –
*
Mini8 controller Specification Sheet
Order codes
15
1
2
16
17
3
Basic Product
MINI8
1
2
4
6
7
8
Communications
Non isolated Modbus
Slave
ISOLMBUS Isolated Modbus RTU
Slave
DEVICENET DeviceNet Slave
PBUSRJ45
Profibus Slave RJ45
PBUS9PIN
Profibus Slave 9 Pin
D type
ENETMBUS Ethernet Modbus
TCP/IP Slave
DNETM12
DeviceNet M12
Connector Slave
ENETIP
EtherNet/IP
IO Acquisition only
4 Control loops
8 Control loops
16 Control loops
Programs
0PRG
1PRG
XPRG
5
MODBUS
Mini8 Controller
Control Loops
ACQ
4LP
8LP
16LP
4
No programs
1 profile – 50 programs
Multi-profiles – 50 programs
(Note 1)
5
10
11
12
13
10 Applications
13 Manual Language
STD
EC8
ENG
FRA
GER
SPA
ITA
FC8
Temperature Units
C
F
9
No configuration
8 Loop extrusion controller
(Note 5)
Requires 8LP or 250 wires
and modules placed in the
following slots
Slot 1 = TC8
Slot 2 = CT3 or XXX
Slot 3 = DO8
Slot 4 = DO8
8 Loop furnace controller
Requires 8LP or 250 wires
and modules placed in the
following slots
Slot 1 = TC8
Slot 4 = AO8
14
English
French
German
Spanish
Italian
14 Configuration Software
ENG
English
NONE No CD
ITOOLS iTools CD & Mini8
Controller documentation
15 Warranty
XXXXX Standard
WL005 Extended
Centigrade
Fahrenheit
11 Wires
16 Calibration Certificates
3
PSU
VL
6-9
24V dc
30
60
120
250
IO Slots 1, 2, 3, 4
XXX
TC4
TC8
RT4
AO4
AO8
DO8
CT3
RL8
DI8
No module fitted
4 Ch TC input
8 Ch TC input
4 Ch RTD input
4 Ch 4-20mA O/P
(Note 2)
8 Ch 4-20mA O/P
(Note 2)
8 Ch logic O/P
3 Ch CT input
(Note 4)
8 Ch relay O/P
(Note 3)
8 Ch logic input
30 User Wires
60 User Wires
120 User Wires
250 User Wires
17 Special
12 Recipes
NONE
RCP
No recipes
8 Recipes
If 4 Loops ordered 4 programmers are supplied; 8 or 16 loops ordered 8 programmers are supplied.
AO4/AO8 in slot 4 only.
RL8 in slots 2/3 only.
Only 1 CT3 per Mini8.
EC8 is a preconfigured version of Mini8 offering 8 control loops with Heat/Cool logic outputs.
CERT2 is 5 point calibration.
Profibus motherboard fitted.
Eurotherm:
AUSTRALIA Melbourne
T (+61 0) 8562 9800
E [email protected]
AUSTRIA Vienna
T (+43 1) 7987601
E [email protected]
BELGIUM & LUXEMBOURG Moha
T (+32) 85 274080
E [email protected]
BRAZIL Campinas-SP
T (+5519) 3707 5333
E [email protected]
CHINA
T (+86 21) 61451188
E [email protected]
XXXXX Standard
EU0725 OEM Security
Accessories
Notes
1.
2.
3.
4.
5.
6.
7.
XXXXX None
CERT1 Certificate of Conformity
CERT2 Factory input calibration
per input (Note 6)
International sales and service
HA031260
SUBMINI8/SHUNT/249R.1
RES250
RES500
CTR100000/000
CTR200000/000
CTR400000/000
CTR500000/000
iTools/None/3000CK
SUB21/IV10
www.eurotherm.com
ITALY Como
T (+39 031) 975111
E [email protected]
KOREA Seoul
T (+82 2) 2090 0900
E [email protected]
NETHERLANDS Alphen a/d Rijn
T (+31 172) 411752
E [email protected]
POLAND Katowice
T (+48 32) 78395000
E [email protected]
SPAIN Madrid
T (+34 91) 6616001
E [email protected]
Beijing Office
T (+86 10) 5909 5700
E [email protected]
FRANCE Lyon
T (+33 478) 664500
E [email protected]
GERMANY Limburg
T (+49 6431) 2980
E [email protected]
INDIA Mumbai
T (+91 22) 67579800
E [email protected]
IRELAND Dublin
T (+353 1) 4691800
E [email protected]
Engeering/CD manual
2.49R Precision resistor
250R resistor for 0-5V dc OP
500R resistor for 0-10V dc OP
10A Current transformer
25A Current transformer
50A Current transformer
100A Current transformer
Configuration clip
0-10V input adaptor
SWEDEN Malmo
T (+46 40) 384500
E [email protected]
SWITZERLAND Wollerau
T (+41 44) 7871040
E [email protected]
UNITED KINGDOM Worthing
T (+44 1903) 268500
E [email protected]
U.S.A. Ashburn VA
T (+1 703) 724 7300
E [email protected]
ED68
Contact details correct at time of print.
© Copyright Eurotherm Limited 2012
Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower nanodac, piccolo, Foxboro and Wonderware are
trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be
stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior
written permission of Eurotherm limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be
changed without notice. The information in this document is given in good faith, but is intended for guidance only.
Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
Eurotherm Part No. HA028480 Issue 9 March 12
6
Mini8 controller Specification Sheet
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement