G83
Shenzhen Growatt New Energy Technology CO ,Ltd
Type Verification Test Report
Type Approval and manufacturer/supplier declaration of compliance with the requirements
of Engineering Recommendation G83/2.
SSEG Type reference number
SSEG Type
System Supplier name
Address
Tel.
+86 755 2951 5888
E:mail
[email protected]
Growatt 6000UE
Photovoltaic inverter
Shenzhen Growatt New Energy Technology CO ,Ltd
1st East & 3rd Floor, Jiayu Industrial Zone,
Xibianling,Shangwu Village, Shiyan, Baoan District,
Shenzhen,P.R.China
+86 755 2747 2131
Fax
Web site
www.ginverter.com
Connection Option
kW single phase, single, split or three phase system
kW three phase
Maximum rated
capacity, use separate
kW three phase
sheet if more than one
kW three phase
connection option.
kW two phases in three phase system
kW two phases split phase system
SSEG manufacturer/supplier declaration.
I certify on behalf of the company named above as a manufacturer/supplier of Small Scale
Embedded Generators, that all products manufactured/supplied by the company with the
above SSEG Type reference number will be manufactured and tested to ensure that they
perform as stated in this Type Verification Test Report, prior to shipment to site and that no
site modifications are required to ensure that the product meets all the requirements of
G83/2.
Signed
On behalf of
Shenzhen Growatt New Energy
N/A
4
5
6
N/A
N/A
Technology CO ,Ltd
Note that testing can be done by the manufacturer of an individual company, by an external
test house, or by the supplier of the complete system, or any combination of them as
appropriate.
Where parts of the testing are carried out by persons or organisations other than the
supplier then the supplier shall keep copies of all test records and results supplied to them
to verify that the testing has been carried out by people with sufficient technical competency
to carry out the tests.
The family product model is made by the following products:
Growatt 4000UE
Growatt 5000UE
Growatt 6000UE
The model Growatt 6000UE is as the representative test models in this report.
Shenzhen Growatt New Energy Technology CO ,Ltd
Power Quality. Harmonics. The requirement is specified in
PASS
section 5.4.1, test procedure in Annex A or B 1.4.1
kW
SSEG rating per phase (rpp)
NV=MV*3.68/rpp
6
Harmonic
At 45-55% of rated output
100% of rated output
Average harmonic current results – Phase 1
Measured
Value (MV)
in Amps
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
0.067
0.016
0.026
0.072
0.008
0.033
0.004
0.032
0.009
0.093
0.007
0.016
0.005
0.009
0.009
0.022
0.005
0.015
0.004
0.008
0.019
0.020
0.031
0.010
0.005
0.009
0.030
0.008
0.026
0.004
0.003
0.003
0.004
0.005
0.004
0.002
0.002
0.002
0.003
Normalised
Value
(NV) in Amps
0.067
0.016
0.026
0.072
0.008
0.033
0.004
0.032
0.009
0.093
0.007
0.016
0.005
0.009
0.009
0.022
0.005
0.015
0.004
0.008
0.019
0.020
0.031
0.010
0.005
0.009
0.030
0.008
0.026
0.004
0.003
0.003
0.004
0.005
0.004
0.002
0.002
0.002
0.003
Measured
Value (MV)
in Amps
0.082
0.023
0.035
0.084
0.012
0.057
0.006
0.037
0.012
0.100
0.008
0.022
0.010
0.012
0.012
0.024
0.008
0.022
0.006
0.011
0.041
0.025
0.066
0.012
0.007
0.017
0.065
0.013
0.054
0.007
0.005
0.004
0.007
0.006
0.008
0.003
0.003
0.003
0.004
Normalise
d Value
(NV) in
Amps
0.082
0.023
0.035
0.084
0.012
0.057
0.006
0.037
0.012
0.100
0.008
0.022
0.010
0.012
0.012
0.024
Limit in BS
EN 610003-2 in
Amps
1.080
2.300
0.430
1.140
0.300
0.770
0.230
0.400
0.184
0.330
0.153
0.210
0.131
0.150
0.115
0.132
0.008
0.022
0.006
0.011
0.041
0.025
0.066
0.012
0.007
0.017
0.065
0.013
0.054
0.007
0.005
0.004
0.007
0.006
0.008
0.003
0.003
0.003
0.004
0.102
0.118
0.092
0.107
0.084
0.098
0.077
0.090
0.071
0.083
0.066
0.078
0.061
0.073
0.058
0.068
0.054
0.064
0.051
0.061
0.048
0.058
0.046
Higher limit
for odd
harmonics 21
and above
0.160
0.147
0.135
0.124
0.117
0.109
0.102
0.096
0.091
0.087
Shenzhen Growatt New Energy Technology CO ,Ltd
Average harmonic current results – Phase 2
Measured
Value (MV)
in Amps
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
0.020
0.035
0.038
0.079
0.016
0.035
0.011
0.009
0.015
0.093
0.007
0.025
0.008
0.009
0.006
0.027
0.004
0.016
0.003
0.006
0.022
0.013
0.028
0.016
0.006
0.010
0.035
0.009
0.022
0.009
0.003
0.003
0.005
0.006
0.004
0.006
0.003
0.004
0.003
Normalised
Value
(NV) in Amps
0.020
0.035
0.038
0.079
0.016
0.035
0.011
0.009
0.015
0.093
0.007
0.025
0.008
0.009
0.006
0.027
0.004
0.016
0.003
0.006
0.022
0.013
0.028
0.016
0.006
0.010
0.035
0.009
0.022
0.009
0.003
0.003
0.005
0.006
0.004
0.006
0.003
0.004
0.003
Measured
Value (MV)
in Amps
0.032
0.041
0.042
0.084
0.020
0.057
0.012
0.013
0.017
0.098
0.009
0.030
0.010
0.015
0.010
0.029
0.006
0.021
0.005
0.011
0.046
0.019
0.060
0.018
0.009
0.019
0.076
0.013
0.047
0.011
0.006
0.005
0.009
0.009
0.008
0.008
0.005
0.006
0.005
Normalised
Value
(NV) in
Amps
0.032
0.041
0.042
0.084
0.020
0.057
0.012
0.013
0.017
0.098
0.009
0.030
0.010
0.015
0.010
0.029
0.006
0.021
0.005
0.011
0.046
0.019
0.060
0.018
0.009
0.019
0.076
0.013
0.047
0.011
0.006
0.005
0.009
0.009
0.008
0.008
0.005
0.006
0.005
Limit in BS
EN 610003-2 in
Amps
1.080
2.300
0.430
1.140
0.300
0.770
0.230
0.400
0.184
0.330
0.153
0.210
0.131
0.150
0.115
0.132
0.102
0.118
0.092
0.107
0.084
0.098
0.077
0.090
0.071
0.083
0.066
0.078
0.061
0.073
0.058
0.068
0.054
0.064
0.051
0.061
0.048
0.058
0.046
Higher limit
for odd
harmonics 21
and above
0.160
0.147
0.135
0.124
0.117
0.109
0.102
0.096
0.091
0.087
Shenzhen Growatt New Energy Technology CO ,Ltd
Average harmonic current results – Phase 3
Measured
Value (MV)
in Amps
Normalised
Value
(NV) in Amps
Measured
Value (MV)
in Amps
Normalised
Limit in BS Higher limit
Value
EN 61000- for odd
(NV) in
3-2 in
harmonics 21
Amps
Amps
and above
2
0.051
0.051
0.060
0.060
1.080
3
0.031
0.031
0.036
0.036
2.300
4
0.036
0.036
0.039
0.039
0.430
5
0.073
0.073
0.079
0.079
1.140
6
0.009
0.009
0.012
0.012
0.300
7
0.025
0.025
0.053
0.053
0.770
8
0.008
0.008
0.010
0.010
0.230
9
0.018
0.018
0.024
0.024
0.400
10
0.008
0.008
0.011
0.011
0.184
11
0.089
0.089
0.097
0.097
0.330
12
0.008
0.008
0.011
0.011
0.153
13
0.011
0.011
0.014
0.014
0.210
14
0.007
0.007
0.009
0.009
0.131
15
0.015
0.015
0.018
0.018
0.150
16
0.007
0.007
0.009
0.009
0.115
17
0.021
0.021
0.024
0.024
0.132
18
0.005
0.008
0.008
0.005
0.102
19
0.009
0.009
0.013
0.013
0.118
20
0.004
0.004
0.006
0.006
0.092
0.006
0.006
0.008
0.008
21
0.107 0.160
22
0.018
0.018
0.036
0.036
0.084
0.011
0.011
0.015
0.015
23
0.098 0.147
24
0.024
0.024
0.050
0.050
0.077
0.010
0.010
0.012
0.012
25
0.090 0.135
26
0.003
0.003
0.006
0.006
0.071
0.007
0.007
0.011
0.011
27
0.083 0.124
28
0.026
0.026
0.056
0.056
0.066
0.007
0.007
0.012
0.012
29
0.078 0.117
30
0.019
0.019
0.042
0.042
0.061
0.007
0.007
0.009
0.009
31
0.073 0.109
32
0.002
0.002
0.004
0.004
0.058
0.004
0.004
0.006
0.006
33
0.068 0.102
34
0.003
0.003
0.007
0.007
0.054
0.005
0.005
0.006
0.006
35
0.064 0.096
36
0.004
0.004
0.007
0.007
0.051
0.004
0.004
0.005
0.005
37
0.061 0.091
38
0.004
0.004
0.005
0.005
0.048
0.004
0.004
0.005
0.005
39
0.058 0.087
0.003
0.003
0.005
0.005
40
0.046
Note the higher limits for odd harmonics 21 and above are only allowable under certain
conditions, if these higher limits are utilised please state the exemption used as detailed in
part 6.2.3.4 of BS EN 61000-3-2 in the box below.
Shenzhen Growatt New Energy Technology CO ,Ltd
Power Quality.
Voltage fluctuations and Flicker. The
requirement is specified in section 5.4.2, test procedure in
Annex A or B 1.4.3
Growatt 6000UE
Starting
Stopping
Running
dmax
dmax dc
dc
Pst
d(t)
d(t)
Measured
-0.55
Values
Normalised
-0.55
to standard
impedance
and 6kW for
multiple units
Limits
set 4%
under BS EN
61000-3-2
1.46
0
1.46
0
3.3%
3.3
%
PASS
Plt 2 hours
1.41
0.50
1.41
0.50
0
0.636
0.278
0
0.636
0.278
4%
3.3
%
1.0
0.65
3.3
%
500ms
500ms
Test start date
2013.7.13
3:41:27 PM
Test end date
2013.7.13
4:51:50 PM
Test location
Shenzhen Growatt New Energy Technology CO ,Ltd
Research &
Development Laboratory
Power quality. DC injection. The requirement is specified in section
5.5, test procedure in Annex A or B 1.4.4
Growatt 6000UE
Test power 10%
55%
100%
level
Recorded
21.3mA -15.3mA
10.1mA
value
as % of 0.237%
0.170%
0.112%
rated AC
current
Limit
0.25%
0.25%
0.25%
PASS
Power Quality. Power factor. The requirement is specified in section PASS
5.6, test procedure in Annex A or B 1.4.2
Growatt 6000UE
216.2V
230V
253V
Measured at three voltage levels and at
full output. Voltage to be maintained
within ±1.5% of the stated level during
Measured
0.998
0.999
0.998
the test.
value
Limit
>0.95
>0.95
>0.95
Shenzhen Growatt New Energy Technology CO ,Ltd
Protection. Frequency tests The requirement is specified in section
5.3.1, test procedure in Annex A or B 1.3.3
Growatt 6000 3ph UE
Function
Setting
Trip test
“No trip tests”
Frequency Time
Frequency Time
Frequency
delay
delay
/time
U/F stage 1 47.5Hz
20s
47.51Hz
20.05s 47.7Hz
25s
U/F stage 2 47Hz
0.5s
47.01Hz
0.548s 47.2Hz
19.98s
46.8Hz
0.48s
O/F stage 1 51.5Hz
90s
51.50Hz
90.04s 51.3Hz
95s
O/F stage 2 52Hz
0.5s
52.00Hz
0.548s 51.8Hz
89.98s
52.2Hz
0.48s
Protection. Voltage tests The requirement is specified in
test procedure in Annex A or B 1.3.2
Growatt 6000UE
Function
Setting
Trip test
Voltage
Time
Voltage
Time
delay
delay
U/V stage 1 200.1V
2.5s
200.45V
2.582s
section 5.3.1,
PASS
Confirm no trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
PASS
“No trip tests”
Voltage
Confirm no trip
/time
204.1V
No Trip
3.5s
U/V stage 2 184V
0.5s
184.5V
0.584s 188V
No Trip
2.48s
180V
No Trip
0.48s
O/V stage 1 262.2V
1.0s
262.38V
1.062s 258.2V
No Trip
2.0s
O/V stage 2 273.7V
0.5s
273.9V
0.574s 269.7V
No Trip
0.98s
277.7V
No Trip
0.48s
Note for Voltage tests the Voltage required to trip is the setting ±3.45V. The time delay can
be measured at a larger deviation than the minimum required to operate the protection. The
No trip tests need to be carried out at the setting ±4V and for the relevant times as shown in
the table above to ensure that the protection will not trip in error.
Shenzhen Growatt New Energy Technology CO ,Ltd
Protection. Loss of Mains test. The requirement is specified in PASS
section 5.3.2, test procedure in Annex A or B 1.3.4
Growatt 6000 UE
To be carried out at three output power levels with a tolerance of plus or minus 5% in Test
Power levels.
Test Power
10%
55%
100%
10%
55%
100%
Balancing load
on islanded
network
95%
SSEG
output
Trip time. Limit is 0.32
0.5 seconds
of 95%
SSEG
output
0.21
of 95% of 105% of
SSEG
SSEG
output
output
0.16
0.17
105% of 105%
SSEG
SSEG
output
output
0.31
of
0.25
For Multi phase SSEGs confirm that the device shuts down correctly after the removal of a
single fuse as well as operation of all phases.
Test Power
10%
55%
100%
10%
55%
100%
Balancing load
95% of
95% of
95% of
105% of
105% of 105% of
on islanded
SSEG
SSEG
SSEG
SSEG
SSEG
SSEG
network
output
output
output
output
output
output
Trip time. Ph1
0.21
0.36
0.31
0.25
0.16
0.20
fuse removed
Test Power
10%
55%
100%
10%
55%
100%
Balancing load
95% of
95% of
95% of
105% of
105% of 105% of
on islanded
SSEG
SSEG
SSEG
SSEG
SSEG
SSEG
network
output
output
output
output
output
output
Trip time. Ph2
0.22
0.36
0.30
0.26
0.19
0.22
fuse removed
Test Power
10%
55%
100%
10%
55%
100%
Balancing load
95% of
95% of
95% of
105% of
105% of 105% of
on islanded
SSEG
SSEG
SSEG
SSEG
SSEG
SSEG
network
output
output
output
output
output
output
Trip time. Ph3
0.20
0.37
0.33
0.25
0.16
0.18
fuse removed
Note for technologies which have a substantial shut down time this can be added to the 0.5
seconds in establishing that the trip occurred in less than 0.5s. Maximum shut down time
could therefore be up to 1.0 seconds for these technologies.
Protection. Frequency change, Stability test The requirement is
in section 5.3.3, test procedure in Annex A or B 1.3.6
Growatt 6000 3ph UE
Start
Change
End
Frequency
Frequency
Positive Vector Shift
49.5Hz
+9 degrees
Negative Vector Shift
50.5Hz
- 9 degrees
Positive Frequency drift
49.5Hz
+0.19Hz/sec
51.5Hz
Negative Frequency drift
50.5Hz
-0.19Hz/sec
47.5Hz
specified PASS
Confirm no trip
No Trip
No Trip
No Trip
No Trip
Shenzhen Growatt New Energy Technology CO ,Ltd
Protection. Re-connection timer. The requirement is specified in
PASS
section 5.3.4, test procedure in Annex A or B 1.3.5
Growatt 6000UE
Test should prove that the reconnection sequence starts after a minimum delay of 20
seconds for restoration of voltage and frequency to within the stage 1 settings of table 1.
Time delay Measured delay
Checks on no reconnection when voltage or frequency
setting
is brought to just outside stage 1 limits of table 1.
At 266.2V At 196.1V At 47.4Hz At 51.6Hz
20S
36.21/36.22
36.11/36.21
Confirmation that the SSEG does No
not re-connect.
Connect
No
Connect
No
Connect
No Connect
Fault level contribution. The requirement is specified in section 5.7,
test procedure in Annex A or B 1.4.6
Growatt 6000UE
For a directly coupled SSEG
Parameter
PASS
For a Inverter SSEG
Symbol
Peak Short Circuit current
ip
--
Time
after fault
20ms
Initial Value of aperiodic
current
Initial symmetrical shortcircuit current*
Decaying
(aperiodic)
component of short circuit
current*
Reactance/Resistance
Ratio of source*
A
--
100ms
30Vr.m.s
0
Ik
--
250ms
30Vr.m.s
0
iDC
--
500ms
30Vr.m.s
0
X
--
Time to
trip
0.11
In seconds
/R
Value
Volts
Amps
30Vr.m.s
0.4A
Self-Monitoring solid state switching The requirement is specified in Yes/or NA
section 5.3.1, No specified test requirements.
Growatt 6000UE
It has been verified that in the event of the solid state switching device failing Yes
to disconnect the SSEG, the voltage on the output side of the switching
device is reduced to a value below 50 volts within 0.5 seconds.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement