Shenzhen Growatt New Energy Technology CO ,Ltd Type Verification Test Report Type Approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G83/2. SSEG Type reference number SSEG Type System Supplier name Address Tel. +86 755 2951 5888 E:mail [email protected] Growatt 6000UE Photovoltaic inverter Shenzhen Growatt New Energy Technology CO ,Ltd 1st East & 3rd Floor, Jiayu Industrial Zone, Xibianling,Shangwu Village, Shiyan, Baoan District, Shenzhen,P.R.China +86 755 2747 2131 Fax Web site www.ginverter.com Connection Option kW single phase, single, split or three phase system kW three phase Maximum rated capacity, use separate kW three phase sheet if more than one kW three phase connection option. kW two phases in three phase system kW two phases split phase system SSEG manufacturer/supplier declaration. I certify on behalf of the company named above as a manufacturer/supplier of Small Scale Embedded Generators, that all products manufactured/supplied by the company with the above SSEG Type reference number will be manufactured and tested to ensure that they perform as stated in this Type Verification Test Report, prior to shipment to site and that no site modifications are required to ensure that the product meets all the requirements of G83/2. Signed On behalf of Shenzhen Growatt New Energy N/A 4 5 6 N/A N/A Technology CO ,Ltd Note that testing can be done by the manufacturer of an individual company, by an external test house, or by the supplier of the complete system, or any combination of them as appropriate. Where parts of the testing are carried out by persons or organisations other than the supplier then the supplier shall keep copies of all test records and results supplied to them to verify that the testing has been carried out by people with sufficient technical competency to carry out the tests. The family product model is made by the following products: Growatt 4000UE Growatt 5000UE Growatt 6000UE The model Growatt 6000UE is as the representative test models in this report. Shenzhen Growatt New Energy Technology CO ,Ltd Power Quality. Harmonics. The requirement is specified in PASS section 5.4.1, test procedure in Annex A or B 1.4.1 kW SSEG rating per phase (rpp) NV=MV*3.68/rpp 6 Harmonic At 45-55% of rated output 100% of rated output Average harmonic current results – Phase 1 Measured Value (MV) in Amps 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 0.067 0.016 0.026 0.072 0.008 0.033 0.004 0.032 0.009 0.093 0.007 0.016 0.005 0.009 0.009 0.022 0.005 0.015 0.004 0.008 0.019 0.020 0.031 0.010 0.005 0.009 0.030 0.008 0.026 0.004 0.003 0.003 0.004 0.005 0.004 0.002 0.002 0.002 0.003 Normalised Value (NV) in Amps 0.067 0.016 0.026 0.072 0.008 0.033 0.004 0.032 0.009 0.093 0.007 0.016 0.005 0.009 0.009 0.022 0.005 0.015 0.004 0.008 0.019 0.020 0.031 0.010 0.005 0.009 0.030 0.008 0.026 0.004 0.003 0.003 0.004 0.005 0.004 0.002 0.002 0.002 0.003 Measured Value (MV) in Amps 0.082 0.023 0.035 0.084 0.012 0.057 0.006 0.037 0.012 0.100 0.008 0.022 0.010 0.012 0.012 0.024 0.008 0.022 0.006 0.011 0.041 0.025 0.066 0.012 0.007 0.017 0.065 0.013 0.054 0.007 0.005 0.004 0.007 0.006 0.008 0.003 0.003 0.003 0.004 Normalise d Value (NV) in Amps 0.082 0.023 0.035 0.084 0.012 0.057 0.006 0.037 0.012 0.100 0.008 0.022 0.010 0.012 0.012 0.024 Limit in BS EN 610003-2 in Amps 1.080 2.300 0.430 1.140 0.300 0.770 0.230 0.400 0.184 0.330 0.153 0.210 0.131 0.150 0.115 0.132 0.008 0.022 0.006 0.011 0.041 0.025 0.066 0.012 0.007 0.017 0.065 0.013 0.054 0.007 0.005 0.004 0.007 0.006 0.008 0.003 0.003 0.003 0.004 0.102 0.118 0.092 0.107 0.084 0.098 0.077 0.090 0.071 0.083 0.066 0.078 0.061 0.073 0.058 0.068 0.054 0.064 0.051 0.061 0.048 0.058 0.046 Higher limit for odd harmonics 21 and above 0.160 0.147 0.135 0.124 0.117 0.109 0.102 0.096 0.091 0.087 Shenzhen Growatt New Energy Technology CO ,Ltd Average harmonic current results – Phase 2 Measured Value (MV) in Amps 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 0.020 0.035 0.038 0.079 0.016 0.035 0.011 0.009 0.015 0.093 0.007 0.025 0.008 0.009 0.006 0.027 0.004 0.016 0.003 0.006 0.022 0.013 0.028 0.016 0.006 0.010 0.035 0.009 0.022 0.009 0.003 0.003 0.005 0.006 0.004 0.006 0.003 0.004 0.003 Normalised Value (NV) in Amps 0.020 0.035 0.038 0.079 0.016 0.035 0.011 0.009 0.015 0.093 0.007 0.025 0.008 0.009 0.006 0.027 0.004 0.016 0.003 0.006 0.022 0.013 0.028 0.016 0.006 0.010 0.035 0.009 0.022 0.009 0.003 0.003 0.005 0.006 0.004 0.006 0.003 0.004 0.003 Measured Value (MV) in Amps 0.032 0.041 0.042 0.084 0.020 0.057 0.012 0.013 0.017 0.098 0.009 0.030 0.010 0.015 0.010 0.029 0.006 0.021 0.005 0.011 0.046 0.019 0.060 0.018 0.009 0.019 0.076 0.013 0.047 0.011 0.006 0.005 0.009 0.009 0.008 0.008 0.005 0.006 0.005 Normalised Value (NV) in Amps 0.032 0.041 0.042 0.084 0.020 0.057 0.012 0.013 0.017 0.098 0.009 0.030 0.010 0.015 0.010 0.029 0.006 0.021 0.005 0.011 0.046 0.019 0.060 0.018 0.009 0.019 0.076 0.013 0.047 0.011 0.006 0.005 0.009 0.009 0.008 0.008 0.005 0.006 0.005 Limit in BS EN 610003-2 in Amps 1.080 2.300 0.430 1.140 0.300 0.770 0.230 0.400 0.184 0.330 0.153 0.210 0.131 0.150 0.115 0.132 0.102 0.118 0.092 0.107 0.084 0.098 0.077 0.090 0.071 0.083 0.066 0.078 0.061 0.073 0.058 0.068 0.054 0.064 0.051 0.061 0.048 0.058 0.046 Higher limit for odd harmonics 21 and above 0.160 0.147 0.135 0.124 0.117 0.109 0.102 0.096 0.091 0.087 Shenzhen Growatt New Energy Technology CO ,Ltd Average harmonic current results – Phase 3 Measured Value (MV) in Amps Normalised Value (NV) in Amps Measured Value (MV) in Amps Normalised Limit in BS Higher limit Value EN 61000- for odd (NV) in 3-2 in harmonics 21 Amps Amps and above 2 0.051 0.051 0.060 0.060 1.080 3 0.031 0.031 0.036 0.036 2.300 4 0.036 0.036 0.039 0.039 0.430 5 0.073 0.073 0.079 0.079 1.140 6 0.009 0.009 0.012 0.012 0.300 7 0.025 0.025 0.053 0.053 0.770 8 0.008 0.008 0.010 0.010 0.230 9 0.018 0.018 0.024 0.024 0.400 10 0.008 0.008 0.011 0.011 0.184 11 0.089 0.089 0.097 0.097 0.330 12 0.008 0.008 0.011 0.011 0.153 13 0.011 0.011 0.014 0.014 0.210 14 0.007 0.007 0.009 0.009 0.131 15 0.015 0.015 0.018 0.018 0.150 16 0.007 0.007 0.009 0.009 0.115 17 0.021 0.021 0.024 0.024 0.132 18 0.005 0.008 0.008 0.005 0.102 19 0.009 0.009 0.013 0.013 0.118 20 0.004 0.004 0.006 0.006 0.092 0.006 0.006 0.008 0.008 21 0.107 0.160 22 0.018 0.018 0.036 0.036 0.084 0.011 0.011 0.015 0.015 23 0.098 0.147 24 0.024 0.024 0.050 0.050 0.077 0.010 0.010 0.012 0.012 25 0.090 0.135 26 0.003 0.003 0.006 0.006 0.071 0.007 0.007 0.011 0.011 27 0.083 0.124 28 0.026 0.026 0.056 0.056 0.066 0.007 0.007 0.012 0.012 29 0.078 0.117 30 0.019 0.019 0.042 0.042 0.061 0.007 0.007 0.009 0.009 31 0.073 0.109 32 0.002 0.002 0.004 0.004 0.058 0.004 0.004 0.006 0.006 33 0.068 0.102 34 0.003 0.003 0.007 0.007 0.054 0.005 0.005 0.006 0.006 35 0.064 0.096 36 0.004 0.004 0.007 0.007 0.051 0.004 0.004 0.005 0.005 37 0.061 0.091 38 0.004 0.004 0.005 0.005 0.048 0.004 0.004 0.005 0.005 39 0.058 0.087 0.003 0.003 0.005 0.005 40 0.046 Note the higher limits for odd harmonics 21 and above are only allowable under certain conditions, if these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box below. Shenzhen Growatt New Energy Technology CO ,Ltd Power Quality. Voltage fluctuations and Flicker. The requirement is specified in section 5.4.2, test procedure in Annex A or B 1.4.3 Growatt 6000UE Starting Stopping Running dmax dmax dc dc Pst d(t) d(t) Measured -0.55 Values Normalised -0.55 to standard impedance and 6kW for multiple units Limits set 4% under BS EN 61000-3-2 1.46 0 1.46 0 3.3% 3.3 % PASS Plt 2 hours 1.41 0.50 1.41 0.50 0 0.636 0.278 0 0.636 0.278 4% 3.3 % 1.0 0.65 3.3 % 500ms 500ms Test start date 2013.7.13 3:41:27 PM Test end date 2013.7.13 4:51:50 PM Test location Shenzhen Growatt New Energy Technology CO ,Ltd Research & Development Laboratory Power quality. DC injection. The requirement is specified in section 5.5, test procedure in Annex A or B 1.4.4 Growatt 6000UE Test power 10% 55% 100% level Recorded 21.3mA -15.3mA 10.1mA value as % of 0.237% 0.170% 0.112% rated AC current Limit 0.25% 0.25% 0.25% PASS Power Quality. Power factor. The requirement is specified in section PASS 5.6, test procedure in Annex A or B 1.4.2 Growatt 6000UE 216.2V 230V 253V Measured at three voltage levels and at full output. Voltage to be maintained within ±1.5% of the stated level during Measured 0.998 0.999 0.998 the test. value Limit >0.95 >0.95 >0.95 Shenzhen Growatt New Energy Technology CO ,Ltd Protection. Frequency tests The requirement is specified in section 5.3.1, test procedure in Annex A or B 1.3.3 Growatt 6000 3ph UE Function Setting Trip test “No trip tests” Frequency Time Frequency Time Frequency delay delay /time U/F stage 1 47.5Hz 20s 47.51Hz 20.05s 47.7Hz 25s U/F stage 2 47Hz 0.5s 47.01Hz 0.548s 47.2Hz 19.98s 46.8Hz 0.48s O/F stage 1 51.5Hz 90s 51.50Hz 90.04s 51.3Hz 95s O/F stage 2 52Hz 0.5s 52.00Hz 0.548s 51.8Hz 89.98s 52.2Hz 0.48s Protection. Voltage tests The requirement is specified in test procedure in Annex A or B 1.3.2 Growatt 6000UE Function Setting Trip test Voltage Time Voltage Time delay delay U/V stage 1 200.1V 2.5s 200.45V 2.582s section 5.3.1, PASS Confirm no trip No Trip No Trip No Trip No Trip No Trip No Trip PASS “No trip tests” Voltage Confirm no trip /time 204.1V No Trip 3.5s U/V stage 2 184V 0.5s 184.5V 0.584s 188V No Trip 2.48s 180V No Trip 0.48s O/V stage 1 262.2V 1.0s 262.38V 1.062s 258.2V No Trip 2.0s O/V stage 2 273.7V 0.5s 273.9V 0.574s 269.7V No Trip 0.98s 277.7V No Trip 0.48s Note for Voltage tests the Voltage required to trip is the setting ±3.45V. The time delay can be measured at a larger deviation than the minimum required to operate the protection. The No trip tests need to be carried out at the setting ±4V and for the relevant times as shown in the table above to ensure that the protection will not trip in error. Shenzhen Growatt New Energy Technology CO ,Ltd Protection. Loss of Mains test. The requirement is specified in PASS section 5.3.2, test procedure in Annex A or B 1.3.4 Growatt 6000 UE To be carried out at three output power levels with a tolerance of plus or minus 5% in Test Power levels. Test Power 10% 55% 100% 10% 55% 100% Balancing load on islanded network 95% SSEG output Trip time. Limit is 0.32 0.5 seconds of 95% SSEG output 0.21 of 95% of 105% of SSEG SSEG output output 0.16 0.17 105% of 105% SSEG SSEG output output 0.31 of 0.25 For Multi phase SSEGs confirm that the device shuts down correctly after the removal of a single fuse as well as operation of all phases. Test Power 10% 55% 100% 10% 55% 100% Balancing load 95% of 95% of 95% of 105% of 105% of 105% of on islanded SSEG SSEG SSEG SSEG SSEG SSEG network output output output output output output Trip time. Ph1 0.21 0.36 0.31 0.25 0.16 0.20 fuse removed Test Power 10% 55% 100% 10% 55% 100% Balancing load 95% of 95% of 95% of 105% of 105% of 105% of on islanded SSEG SSEG SSEG SSEG SSEG SSEG network output output output output output output Trip time. Ph2 0.22 0.36 0.30 0.26 0.19 0.22 fuse removed Test Power 10% 55% 100% 10% 55% 100% Balancing load 95% of 95% of 95% of 105% of 105% of 105% of on islanded SSEG SSEG SSEG SSEG SSEG SSEG network output output output output output output Trip time. Ph3 0.20 0.37 0.33 0.25 0.16 0.18 fuse removed Note for technologies which have a substantial shut down time this can be added to the 0.5 seconds in establishing that the trip occurred in less than 0.5s. Maximum shut down time could therefore be up to 1.0 seconds for these technologies. Protection. Frequency change, Stability test The requirement is in section 5.3.3, test procedure in Annex A or B 1.3.6 Growatt 6000 3ph UE Start Change End Frequency Frequency Positive Vector Shift 49.5Hz +9 degrees Negative Vector Shift 50.5Hz - 9 degrees Positive Frequency drift 49.5Hz +0.19Hz/sec 51.5Hz Negative Frequency drift 50.5Hz -0.19Hz/sec 47.5Hz specified PASS Confirm no trip No Trip No Trip No Trip No Trip Shenzhen Growatt New Energy Technology CO ,Ltd Protection. Re-connection timer. The requirement is specified in PASS section 5.3.4, test procedure in Annex A or B 1.3.5 Growatt 6000UE Test should prove that the reconnection sequence starts after a minimum delay of 20 seconds for restoration of voltage and frequency to within the stage 1 settings of table 1. Time delay Measured delay Checks on no reconnection when voltage or frequency setting is brought to just outside stage 1 limits of table 1. At 266.2V At 196.1V At 47.4Hz At 51.6Hz 20S 36.21/36.22 36.11/36.21 Confirmation that the SSEG does No not re-connect. Connect No Connect No Connect No Connect Fault level contribution. The requirement is specified in section 5.7, test procedure in Annex A or B 1.4.6 Growatt 6000UE For a directly coupled SSEG Parameter PASS For a Inverter SSEG Symbol Peak Short Circuit current ip -- Time after fault 20ms Initial Value of aperiodic current Initial symmetrical shortcircuit current* Decaying (aperiodic) component of short circuit current* Reactance/Resistance Ratio of source* A -- 100ms 30Vr.m.s 0 Ik -- 250ms 30Vr.m.s 0 iDC -- 500ms 30Vr.m.s 0 X -- Time to trip 0.11 In seconds /R Value Volts Amps 30Vr.m.s 0.4A Self-Monitoring solid state switching The requirement is specified in Yes/or NA section 5.3.1, No specified test requirements. Growatt 6000UE It has been verified that in the event of the solid state switching device failing Yes to disconnect the SSEG, the voltage on the output side of the switching device is reduced to a value below 50 volts within 0.5 seconds.
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement