White Rodgers 3L09-9 0.3/12/24/120/240V 4-3/10 in. HVAC Fan Control Installation instructions
Add to my manuals
1 Pages
advertisement
WHITE-RODGERS
3L09
Limit Controls
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
This series of limit controls has a normally closed SPST switch that opens on temperature rise to limit the maximum allowable temperature in forced air heating systems. A small bimetal sensing element is located in the air stream for quick response. These controls have a fixed temperature setting and fixed differential.
PRECAUTIONS
THIS CONTROL MUST BE INSTALLED BY A QUALI-
FIED INSTALLER.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to re-calibrate this control will void the White-
Rodgers warranty.
!
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt, low or line voltage, have it inspected by a qualified heating and air conditioning contractor or a licensed electrician.
!
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manufacturers’ recommended installation/service instructions to insure proper operation.
SPECIFICATIONS
Temperature Setting:
Fixed setting stamped on control
ELECTRICAL RATING:
Resistive: 15 amps @ 120 VAC
13 amps @ 240 VAC
9.3 amps @ 277 VAC
Inductive: 5.8 FLA, 34.8 LRA @ 120 VAC
2.9 FLA, 13.0 LRA @ 240 VAC
Pilot Duty: 278 VA
This control must be mounted in the air stream of the appliance. Follow the original equipment manufacturers’ recommendations for proper location and wiring.
INSTALLATION
Wiring
All wiring must conform to local and national electrical codes and ordinances.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
Printed in U.S.A.
PART NO. 37-6133A
9949
advertisement