Murphy Display & Diagnostic Module
with MODBUS RTU Communications
MDB-02106B
Effective 11-02
Catalog Section 78
®†
MDDM-MOD Series
Shutdown
(LED) Red
Alarm (LED)
Amber
(00-02-0516)
■ Specifically Designed For SAE J1939 Controller
Scroll Up
Area Network (CAN) Equipment Applications
■ Displays Over 30 Standard SAE J1939 Parameters
Broadcast by Major Engine and Transmission
Manufacturers’ ECM’s
■ Displays Active Faults and ECM Stored Fault
Codes For Diagnosing Equipment Malfunctions
■ Converts Critical SAE J1939 CAN Data Into
Standard MODBUS®† RTU Information
Scroll Down
Description
Engine Parameters
Specifications
The Murphy Display and Diagnostic Module or
MDDM is the keystone in a line of components
manufactured by FWMurphy as part of its J1939
MurphyLinkTM System. The J1939 MurphyLinkTM
System has been developed to meet the needs for
instrumentation and control on electronically
controlled engines communicating using the
SAE J1939 Controller Area Network (CAN).
The MDDM-MOD is an additional model of the
MDDM series. The MDDM-MOD can translate
SAE J1939 to MODBUS † RTU registers for
remote monitoring via satellite, land lines and cell
phones or other controller and computer systems.
This powerful unit is an easy to use multifunction
tool that enables the operator to view many different engine parameters and engine service codes.
The MDDM-MOD includes a two-line by eight
character backlit LCD display. The top line displays
data labels (e.g. OilPress). The bottom line displays
appropriate units (e.g. 80 psi for oil pressure).
The UP and DOWN push buttons located on the
front of the MDDM-MOD, are used for scrolling
through the parameters and viewing the menu list.
Two LEDs (amber & red) are used to annunciate
active fault messages received by the MDDM-MOD.
MODBUS † devices can be connected to the
MDDM-MOD by an RS485 twisted pair cable up
to 1,000 meters. The MDDM-MOD can be powered by 12 or 24* volt systems, is back lit using
LEDs, and is environmentally sealed.
The following are typical engine parameters displayed and made available via
MODBUS † by the MDDM-MOD in
English and Metric units (when applicable):
Bezel: Stainless Steel (Black Optional).
Membrane Switch: Polyester.
Case/Clamp: Nickel Plated Steel,
Aluminum Killed, QQ-S-698.
Maximum Panel Thickness:
0.30 inch. (8 mm).
Mounting Hole:
2.062 inch (52 mm) in diameter.
Dial: White on Black.
Reversed Polarity:
Withstands reversed battery terminal
polarity indefinitely within operating
temperatures.
CAN BUS: SAE J1939 Compliant.
Communications: One (1) RS485 serial
port, MODBUS † RTU slave, baud
rate 9600 or 19200, N, 8, 1 or 2, half
duplex.
Operating Voltage: 8 VDC Minimum to
32 VDC Maximum.
Operating Temperature:
-4 to 158°F (-20 to 70°C).
Storage Temperature:
-40 to 185°F (-40 to 85°C).
Shipping Weights (all models): 1 lb. (45 g.).
Shipping Dimensions (all models):
5-1/2 x 5-1/2 x 5-1/2 in. (140 x 140 x
140 mm).
®
®
®
Engine Hours
● Engine RPM
● System Voltage
● % Engine Load at the current RPM
● Coolant Temperature
● Oil Pressure
● Fuel Economy
● Throttle Position
● Manifold Air Temperature
● Current Fuel Consumption
● Active Service Codes
● Stored Service Codes from the engine
● Set the Units for display
● View Engine Configuration
Parameters (n/a MODBUS )
●
®
Applications
The Murphy Display and Diagnostic Module is a
low-cost solution for your instrumentation needs
on stationary or mobile equipment applications.
®
† MODBUS® is a registered trademark of AEG
Schneider Automation Inc. Function code supported 03 MODBUS® 16-bit integer holding registers.
* A voltage converter is required for 24 volts
systems for the back light.
Dimensions
IMPORTANT: The MDDM-MOD display is best
viewed either straight on or at the 6 o’clock position.
Panel 0.30 in. (8 mm)
Alarm (LED)
Amber
maximum thickness
Shutdown
(LED) Red
Mounting
Clamp
Ø2.03 in.
(52 mm)
MDDM
Mounting
Clamp
Ø2.062 in. (52 mm) Dia.
Connector Option “B” DeutschTM
P/N: 12047931
8-Way Connector
1.88 in. (48 mm)
Wires Length
3 in. (76 mm)
P/N: DT04-08PA
8-Way Connector
1.78 in. (45 mm)
How to Order
To order the MDDM use the model number designation diagram below:
MDDM 20 M – B – B
Model
MDDM = Murphy Display &
Diagnostic Module
Size
20 = 2-1/16 in. (52 mm) Mounting hole.
Communications
M = Modbus®†
Connector
B = DeutschTM (DT04-08PA)
C = Metri-PackTM (12047931)
D = AMP/DeutschTM (12047931)
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA
+1 281 633 4500 fax +1 281 633 4588
e-mail [email protected]
MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P.; México 78384
+52 444 8206264 fax +52 444 8206336
Villahermosa Office +52 993 3162117
e-mail [email protected]
www.murphymex.com.mx
Accessories
P/N: DT04-3P
3-Way Connector
1.78 in. (45 mm)
(MDDM20M-D Applications)
MLVC2412 (Regulator for 24 VDC) = 78-00-0023
Header Board Power Harness (for 24 VDC) = 78-00-0036
Header Board Assembly = 78-00-0024
Warranty
A limited warranty on materials and workmanship is given with this
FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm
FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
+44 1722 410055 fax +44 1722 410088
e-mail [email protected]
www.fwmurphy.co.uk
MURPHY SWITCH OF CALIFORNIA
41343 12th Street West
Palmdale, California 93551-1442; USA
+1 661 272 4700 fax +1 661 947 7570
e-mail [email protected]
www.murphyswitch.com
MACQUARRIE CORPORATION
1620 Hume Highway
Campbellfield, Vic 3061; Australia
+61 3 9358 5555 fax +61 3 9358 5558
e-mail [email protected]
RE
FW Murphy
P.O. Box 470248
Tulsa, Oklahoma 74147 USA
+1 918 317 4100
fax +1 918 317 4266
e-mail [email protected]
www.fwmurphy.com
Bezel Type
Blank = A-20 Type
A = A-20 Type Black
B = SAE Type Low Profile
Wires Length
25 in. (635 mm)
GI
D
Connector Option “C” Metri-PackTM
Wires Length
3 in. (76 mm)
P/N: MTA-156
5-Way Connector
0.656 in. (17 mm)
E
2.13 in.
(54 mm)
Option “D” AMP/DeutschTM
Scroll
Down
Scroll Up
Mounting Hole
STER
USA–ISO 9001:2000 FM 28221
UK–ISO 9001:2000 FM 29422
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Printed in U.S.A.
MDB-02106B page 2 of 2
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement