- Home
- Domestic appliances
- Climate control
- Heat pumps
- Bard
- WHS 18WH5
- Installation instructions
- 16 Pages
Bard WHS 18WH5, WHS 24WH5 wall mounted heat pump Installation Instructions
Below you will find brief information for wall mounted heat pump WHS 18WH5, wall mounted heat pump WHS 24WH5. This is a wall mounted heat pump unit with fresh-air intake capability and comes with a filter. It can operate on both heating and cooling modes, and has a built-in defrost cycle to avoid ice buildup on the outdoor coil. The unit is designed for use with or without duct work.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
16
MANUAL 2100-037E INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS MODELS IBWHS 2LWHS IMPORTANT The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. Any heat pump is more critical of proper operating, charge and an adequate duct system than a straight air conditioning unit. All duct work supply and return, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct werk or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. if damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier's agent. GENERAL The refrigerant system is complately assembled and charged. All internal wiring is complete, The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts. These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit, These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly "Starting Procedure" and any tags and/or labels attached to the equipment, While these instructions are intended as a general recommended guide, they dc not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. INSTALLATION Size of unit far a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America {ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 908. Where local regulations are at a variance with instructions, installer should adhere to local codes, DUCT WORK Design the duct work according to methods given by the Air Conditloning Contractors of America. When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct werk to the equipment in order to keep the noise transmission to a minimum. A one-inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See page 5 for further details. FILTER A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door, FRESH AIR INTAKE All units are built with a fresh air inlet hole punched in the service panel. The fresh air damper assembly is shipped with each unit, and must be attached at the installation site. See Figure 1 for typical installation procedure. The fresh air damper assembly Is standard equipment with the unit because of the variety of state or local codes requiring fresh air capability. All capacity, efficiency and cost of operation information as required for Department of Energy "Energyguide" Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency. The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit. WALL MOUNTING 1. Two holes, the size of the supply and return air openings must be cut through the wall as shown in Figure 2. 2. On wood-frame wails, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. 3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit. 4. Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity. 5. Some instailations may not require any return air duct. It is recommended that on this type of installation that a filter grille be located in the wali. Fiiters must be of sufficient size to allow a maximum velocity of 400 FPM. NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation oniy in a single story structure, WIRING - MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or "HACR Type" circuit breaker size. Each outdoor unit is marked with a "Minimum Circuit Ampacity," This means that the field wiring used must be sized to carry that amount of current. Depending con the installed Kw of electric heat, there may be two field power circuits required, If this is the case, the unit serial plate wilt so indicate. Some models are suitable only for connection with copper wire, while others can be wired with either copper or aluminum wire. Each unit and/or wiring diagratn will be marked "Use Copper Conductors Only" or "Use Copper or Aluminum Conductors." These instructions MUST BE adhered ta. Refer to the National Electricat Code for complete current carrying capacity data on the various insulation grades of wiring material. The electrical data lists fuse and wire sizes (60°F copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters, uu The unit rating piate lists a "Maximum Time Delay Relay Fuse" or "HACR Type" circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor. WIRING - 24Y CONTROL CIRCUIT Nine (9) wires should be run from thermostat subbase to the 24V terminal board in the unit. A nine conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown on most of the wiring diagrams and are also shown below. D000 OOO at ® О ОФО © OQ nena 00000 98 & 8 008 Unit 24V Terminal Board IMPORTANT NOTE: Only the thermostat and subbase combinations as shown above will work with this equipment. The stat and subbase MUST be matched, and correct operation can be assured only by proper selection and application of these paris. CONDENSATE DRAIN A plastic drain hose extends from the drain pan at the top of the unit down to the unit base, There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage. COMPRESSOR MALFUNCTION RELAY (Single Phase Models Oniy) Actuation of the green “check” lamp is accomplished by a voltage type relay which is factory installed. Any condition such as loss of charge, defective capacitor, defective contactor, etc., that will prevent compressor from operating will cause green lamp to activate. This is a signal to the operator of the equipment to place system in emergency heat position. PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure curves can be found later in the manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressura curve to the unit by model number. SEQUENCE OF OPERATION Cooling - Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation, or can be energized by manual fan switch on subbase for constant air circulation. Heating - A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing "Auto" changeover fram cycie to cycle and the other constantly energizing solenoid coil during heating season and thus eliminating pressure equalization noise except during defrost, are to be used, On "Auto" option, a circuit is completed from R-Wi and R-Y on each heating "on" cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no "Auto" changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbasa is placed In "Heat" position, the "8" terminal being constantly energized from R. A thermostat demand for heat completes R-Y circuit, pulling Im compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. COMPRESSOR CUT-OFF THERMOSTAT £ OUTDOOR THERMOSTATS Heat pump compressor operation at outdoor temperatures below 0°F are neither desirable nor advantageous in terms of efficiency. Since most equipment at time of manufacture is not designated for any specific destination of the country, and most of the equipment is installed in areas not approaching the lower outdoor temperature range, the compressor cut-offs are not factory installed. Outdoor thermostats are available to hoid off various banks of electric heat until needed as determined by outdoor temperature. Tha set point of either type of thermostat is variable with geographic region and sizing of the heating equipment to the structure. Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points. COMPRESSOR CUT-OFF AND OUTDOOR THERMOSTAT WIRING See specific wiring information on pages. HEAT ANTICIPATION Both of the thermostats shown below have a fixed heat anticipator for stage 1 with no adjustment required. Stage 1 has an adjustable anticipator for the W2 connection and fixed for the Wi connection. Both the W2 and W3 circuits are controlled by the stage 2 bulb. The only heat anticipator that needs to be checked is stage 2 and it should be set to match the load carried by the W2 circuit. The normal factory wiring provides for only one electric heat contactor to be controlled by W2, and the anticipator should be set at .4#0A. If special field wiring is done, it is best to actuaily measure the load but a good rule is .40A for each heat contactor controlied by W2, WALL THERMOSTAT AND SUBBASE COMBINATIONS Group | Thermostat Subbase Predominant Feature A 8403-017 8404-009 Heat or Cool (7) (T874R1129) | {Q674L 1181} |] No Auto 8 8403-018 a404-010 Automatic Heat-Cool (T874N 1023) | Qe74F 1261) Changeover Position No automatic changeover position--must manuaily place in heat or cool. Reversing vaive remains energized at ail times system switch is in heat position (except during defrost cycle}. No pressure equalization noise when thermostat is satisfied on either heating or cooling. e Allows thermostat to control both heating and cooling operation when set in "AUTO" position. Reversing valve de-energizes at end of each "ON" heating cycle. IMPORTANT NOTE: Both thermostat and subbase combinations shown above incorporate the following features: Man-Auto fan switch, Off-Heat-Cool-Em. Heat Switch, and two (2) indicator lamps—one for emergency heat and one for compressor malfunction. THERMOSTAT INDICATOR LAMPS The red lamp marked “EM.HT." comes on and stays on whenever the system switch is placed in the emergency heat position. The green lamp marked “check” will come on if there is any problem that prevents the compressor from running when it is supposed to be. EMERGENCY HEAT POSITION The operator of the equipment must manually place the system switch in this position. This is done when there is a known problem with the indoor section, or when the green "check" lamp comes on indicating a problem. DEFROST CYCLE The defrost cycle is controlled by time and temperature. The 24 volt timer motor runs all the time the compressor is in operation. When the outdoor temperature is in the lower 40°F temperature range or colder, the outdoor coil temperature is 32°F or below, This temperature is sensed by the defrost thermostat mounted near the bottom of the outdoor coil on a return bend. The defrost thermostat closes at approximately 32°F. Every 60 (or 30) minutes that the compressor is running, contacts 3-5 close for 7 minutes, with contacts 3-4 closed for the first 430 seconds of that 7 minutes. If the defrast thermostat is closed, the defrost relay energizes and places the system in defrost mode. An interlocking circuit is created with timer contacts 3-5 and defrost relay contacts 7-9 in series. During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops. electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 51°F, the defrost thermostat opens, de-energizing the defrost relay and returning the system to heating operation. If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, contacts 3-5 of the defrost timer will open after 7 minutes and restore the system to heating operations automatically. There are two time settings on the defrost timer--30 minutes and 60 minutes. Most models are shipped wired on the 60 minute setting for greatest operating economy. If special Circumstances require a change to the shorter time, remove wire connected to terminal 5/60 and reconnect to terminal 5/30. There is a manual advance knab located on the timer. This can be used to advance timer to contact closure point if it is desired to check out defrost cycle operation, without waiting for time to elapse. DEFROST TIMER WIRING See Note NOTE: All models are connected to 5/60 terminal (60 minute). Any model can be changed from 60 minutes to 30 minutes by unplugging from 5/60 terminal and reconnecting to 5/30 terminal as shown by dotted line. SERVICE HINTS 1. Caution homeowner to maintain clean air fiiters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs. Z. Switching to heating cycle at 75°F or higher outside temperature may cause 8 nuisance trip of the manual reset high pressures switch. 3. The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired opsrating mode before trying to diagnose any reported service problems. 4. Check all power fuses or circuit breakers to bs sure that they are the correct rating. 5. Periodic cleaning of the outdoor coil to permit full and unrestrictad airflow circulation is essential. IMPORTANT INSTALLER NOTE For improved start-up performance wash the indoor coil with a dishwasher detergent. CRANKCASE HEATERS All units are provided with some form of compressor crankcase heat. Some single phase units utilize the compressor motor start winding in series with a portion of the run capacitor to generate heat within the compressor shell to prevent liquid refrigerant migration, Some three phase units utilize a wraparound type of crankcase heater that warms the compressor oil from the outside. Some single and three phase models have an insertion well-type heater located in the lower section of the compressor housing. This is a seif-regulating type heater that draws only enough Power to maintain the compressor at a safe temperatura. Some form of crankcase heat is essential to prevent liquid refrigerant from migrating to the compressor, causing oil pump out on compressor start-up and possible valve failure due to compressing a liquid. Refer to unit wiring diagram to find exact type of crankcasa heater used. The following decal is affixed to ail outdoor units detaiiing start-up procedure. This is very important, Please read carefully. IMPORTANT THESE PROCEDURES MUST BE FOLLOWED AT INITIAL START-UP AND AT ANY TIME POWER HAS BEEN REMOVED FOR 12 HOURS OR LONGER, TO PREVENT COMPRESSOR DAMAGE WHICH MAY RESULT FROM THE PRES ENCE OF LIOWWD REFRIGERANT N THE COMPRESSOR CRAMNKCASE +, MAKE CERTANS THE ROOM THERMO STAT IS IN THE "OFF" POSITION. (THE COMPRESSOR IS NOT TQ OPERATE). 2. APPLY POWER BY CLOSING THE SYS TEM DISCOMNMECT SWATCH THIS ENER- GES THE COMPRESSOR HEATER WHICH EYAPQRATES THE LICUAD RE: FPIGERANT IN THE CRANKGASE. 3 ALLOW 4 HOURS DA 60 MINUTES PER POUND OF REFRIGERANT №4 THE 3Y§- TEM AS NOTED OM THE UNIT RATING PLATE, WHICHEVER 13 GREATER 4. AFTER PROPERLY ELAPSED TIME TraE THERMOSTAT MAY BE SET TO OPER. THE COMPRESOR 5. EXCEPT AS REQUIREO FOR SAFETY VALE SEFACHG — Y M 7061 061 Note: If this unit is operated in cooling below a 65% outdoor ambient temperature, the installation of low ambient control (LAC-1 and 8201-008 relay) to unit is required. lh UNIT MODELS 20WA ¿WA 18WH 24WH Model FADIO ESS Fresh Air Cover With Adjustable Damper Service Door — Model FADIO > ton of opening. Fresh Air Cover Assembly и With two SCTEWS. —_— FIGURE 1 ui MODEL Fresh Air Cover With Adjustable Damper Insert top flange of fresh ————0- | air cover into opening in service door and push top of cover assembly all the way to UNIT MODELS 30WA 36WA 30WH 36WH 42WA FAD2S LOWA 60WA 48WH 6OWH Model FAD25 Service Door FIGURE 2 RIGHT SIDE VIEW WALL VIEW ~~ 1" clearance on a A ; 11 four sides of Flashing a . : supply air duct is (Water Seal) required from K combustible Y materials Г} == | Fr TT Supply | | à P Air P Supply Air Opening | D L | Duct | | t | {| Е y 8 ° RA $ a - © | | M — Heater Access at J — — — — № Panel (see E a note 6) Q |e ° Q , | Return Air a Duct Return Air Opening Е С o a o | d Side 6 Mounting @ Bracket G . G Bottom Mounting Bracket ——_ a a E “a : : “i Sl weir N Structure nd — = В — = MODEL A B с D E Е G Jl x |1 M NIP {nq IWR Tn 32-1/4 | 13-1/2 |69-3/8 | 8 |20-1/21 12| 27-1/2 | 20 | 22 | 10 {19-172} 24 {10 {31 30WA , 36WA ’ 38-1/4 | 15-1/4 74 8 8 4 - 7 Tn 36WH ни / / 1 14 | 32-5/8 | 28 | 30 | 10 1 34 | 10 | 31 + HWA, 60 _ u8WH 60WH 42 22 84 10 30 16 | 26-5/8 | 50 | 32 } 12 29 34 | 10 | 42 MOUNTING INSTRUCTIONS 1. Thesa units are secured by wall mounting brackets which 4. Be sure to obsarva the P dimension when attaching the secure the unit to the outside wal! surface at both sides side brackets. This will assure that no screws ares driven and at the bottom. into the unit sides damaging any internal parts. One-half inch sheet metal screws are recommended. 2. The unit itsalf is suitable for "0" inch clearance, but the supply air duct flange and the first few feet of supply 5. For additional mounting rigidity, the return air and supply air duct requira } inch clearance to combustible material. air (depending upon wall construction} frames or collars If combustibie wall, use K and L dimensions for sizing, If can be drilled and screwed or welded to the structural wall non-combustible, use D and J. itself. Be sure to observe required clearance if combustible wall. 3, After the wall opening positions have been selected, lay sui *se position for the bottom and side brackets. Fasten the brac::2t- see to cha wall (type of fasteners will depend on wafti construction}. Meintein 30 inches minimum clearsnce on right side of unit to allow access to heat strip. FAN BLADE SETTING DIMENSIONS Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the outdoor coil. RATED CFM AND E.S.P. (WET COIL--COOLING) Any service work requiring removal or adjustment in the fan Rated Rated Recommended and/or motor area will require that the dimensions below be Model CFM E.S.P Airflow Range checked and blade adjusted in or out on the motor shaft — 9 accordingly. 18WHs5 650 . 35 585 - 725 24WH5 825 .15 740 - 910 = COMPRESSOR CUT-OFF AND QUTDOOR THERMOSTAT WIRING MODEL | DIM, A 18WH5 5 [Unit 24V Terminal Board | 20WHs 5 (5) (9) (7) ооо нее ВН | jumper | TE TEE — —]—] —# epi ely poy ES o A EE WN outdoor thermostat used as compressor cutoff, нА а REFRIGERANT CHARGE The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6" from CFM--DRY COIL WITH FILTER Rated E.S.P. Made! Model Airflow 95°F OD Temp. 82°F OD Temp. Inches H,0 18WH5-24WH5 18W 650 - - ‚ 0 1085 HS 66 - 68 71-73 4 1040 2UWHE 825 51 - 53 62 - 64 .2 970 ‚3 910 „4 830 The above suction line temperatures are based upon 80°F dry .5 730 bulb/67°F wet bulb {50% R.H.) temperature and rated airflow across the evaporator during cooling cycle. ELECTRICAL INFORMATION WIRING INFORMATION ** Operating Max |No.Field | Internal | Required (1) [ Min. Ckt. | Field Power Ground Rated Voltage Heater* | Unit | Power Fuses Overcurrent | Ampacity Wiring Wire Size Model | Volts/Ph Range KW Amps| Circuits | Ckt.A/B| Protection Ckt.A/B Ckt. A/B Ckt, A/B 19WH5 | 230/208-1 { 197-253 0 11.5 1 20 15 14 14 4 26.7 1 35 35 8 10 8 43,3 1 60 56 4 10 2UWH5 } 230/208-1 | 197-253 0 15 1 30 19 12 12 4 30,2 1 45 40 8 10 7.9 46.5 1 60 60 Ч 10 *Electric heaters are nominal Kw 8 240Y or 480V. oO Time delay fuses or "HACR Type" circuit **Based on 60%C copper wire. Other wiring materials breakers must be used for 60 and smaller must be rated for marked "Minimum Circuit Ampacity" sizes. Standard fuses or circuit breakers or greater. Not al! models approved for aluminum wire. are suitable for sizes 70 and larger. PACKAGED HEAT PUMP MODEL 18WH C. airflow) across the evaporator coil and should be wu. for reference purposes only. Specific information can be found : " ; " under section titled "Refrigerant Charge" elsewhere in manual. LOW SIDE PRESSURE--PSIG If there is any doubt as to correct operating charge being in the (SUCTION LINE) system, the charge should be removed, system evacuated, and recharged according to serial plate instructions. Heating curves airy based on MDE B.A. amparar, 2/86 не "Ч: РН TE año HAL ¿ama quie; ¿Bes : : hi di tans! “ima! За В Ч il Tal “im! fl el ii ri 62 A Mi au a tha A a sin PH dic REN uE al < }) mm en mm mm с oJ Od Od oJ pri — — — HIGH SIDE (DISCHARGE LINE) PRESSURE--PSIG 20 30 40 50 60 70 30 90 100 110 120 AIR TEMPERATURE ENTERING OUTDOOR COIL--DEGREE F. 10 2/86 PACKAGED HEAT PUMP MODEL 24WHS5 АЕ Cooling curves are based upon 80DB, 67W8 Temp. and rated CFM (airflow) across the evaporator coil and should be used for reference purposes only. Specific information can be found under section titled "Refrigerant Charge" elsewhere in manual. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated, and recharged according to serial plate instructions. Heating curves dre basse at TEE Ba, MET a Li = но = me E pi pi ih E je: Е dis id age dic a 148: Li: ap: ты фа; mi en с”) с”) с”) с”) с Cv с с с — HIGH SIDE (DISCHARGE LINE) PRESSURE--PSIG LOW SIDE PRESSURE--PSIG (SUCTION LINE) 20 130 40 50 60 70 80 90 100 110 120 AIR TEMPERATURE ENTERING OUTDOOR COIL--DEGREE F. 10 PARTS LIST SINGLE PACKAGE HEAT PUMPS Part No. Description 18WHS 24WHS5 | 5202-001 Accumulator X 5202- 006 Accumulator X 5152-030 Blower Housing 9-7 X X Г 5152-028 Blower Wheel 9-7 X X 5152-029 Blower Wheel 9-7 X X 8552-045 Capacitor 30/370V X 8552-002 Capacitor 5/370V X X 8552-004 Capacitor 7}/370V x x |_5811-031 Capillary Tube - Cool (2) 5811-019 Capillary Tube - Heat x 5811- 036 Capillary Tube - Cool (2) _ 5651-036 Check Valve X X 8000- 093 Compressor H22B153ABCA X 8000-090 Compressor H22B233ABCA x 5051- 041 Condenser Coil x x 5811-017 - Capillary Tube - Heat X 8401-007 Contactor - Compressor 25A X X 8401-006 Contactor - Heater 2P18 X X 8408-004 Defrost Mounting Plate X X 8408-015 Defrost Thermostat X X 5060- 041 Evaporator Coil x x 8552-032 Capacitor 35/370V X 5151-033 Fan Blade F10H8.7 x x 7004-006 Filter 14x25 x x 8604-041 Heat Strip 4Kw x x 8604-043 Heat Strip 8K w x X 8406-011 High Pressure Switch X X 8402-048 Limit Switch 160° X X 8102-009 Motor - Blower 1/6 hp X X 8103-016 Motor - Fan 1/5 hp x x | 8200-0259 Motor Mount - Fan x x 8201-009 Relay - Blower X X 8201-047 Relay - Defrost x x 8201-024 Relay - Compressor Fault X X 5650-004 Reversing Valve X 5650-009 Reversing Valve X 5650-008 Solenoid Coil X X 5210-002 Strainer (2) (2) 8607-010 Terminal Board X X 8607-013 Terminal Block 230V X X 8402-030 Thermal Cut-off X X 8612-012 Timer X X 8407-035 Transformer X X 8200-030 Motor Mount - Blower x x 5411-011 Motor Mounting Parts X X 5210-004 Strainer X X Minimum Net Billing $15.00. Supersedes all previous lists, Subject to change without notice. TB74N1024/ Q674F1261 — г or Compressor T874KR1129/ Internal Overload q674F1181 IMMERSION CRANKCASE HEATER Capacitor (SEE CHART Á) 1 Compressor 2 or Contactor Compress Fault 24V, Termina Relay Block Pressure Switch Reversing Valve Solenoid frost Relay 2 DH) Indoor Outdoor Motor Motor 7.5/370 5/370 > Capacltor Defrost Therm. Defrost Timer CHART A MODEL CAPACITOR WHS 30/370 Equip. 4WHS 35/370 Ground | | | | | | | | | | | | FACTORY WIRING FIELD WIRING Low Voltage Vol Disconnect USE COPPER For 208V operction move this | Fused i Switch: 7 CONDUCTORS ONLY wire to 208Y transformer tap. 18WH5 -24WH5 Heat Pump 401 /-H0ON 230/208-60-1 T874H1024/ G674F1261 or ST | T674R1129/ D Q674F1181 p т | Compressor с Internal Overload IMMERSION CRANKCASE HEATER CAPACITOR (SEE CHART A) 1 Compressor Contactor 2 compre ssor Relay gh Pressure Switch Reversing Valve Solenoid Outdoor Motor 5/310 > tor Capaci Defrost Timer 20A Circuit Dreaker for 184H5 I0A Circuit Breaker For2UYV}H5 Equip. Ground ALUMINUM WIRE USE COPPER OR For 2CAV operctivn move this /Nwire to 200% transformer tap, E L) EL 24V, Termina Block Indoor Motor 7.5/370 С T 0 5 5/3707 М5 FACTORY WIRING WIRING Low Voltage Voltage 1 WHS =2 4WHS Heat Pump e CHART A MODEL CAPACITOR] ВН [30/370 24445 135/370 Compressor Cc Defrost * Therm. Fused Disconnect Switch ? 230/208-60-1 Internal Overload Compressor Contactor Equip. Ground l == IMMERSION CRANKÇASE Capacitor gh Pressure Switch Reversing Yalve Solenoid Blower Terminal Block ЕЕ о or —~=1GH =H! HEATER r { SEE~CHART A) 1 2 ) i Compressor Fault Relay Relay Indoor Motor Outdoor Motor „97/370 5/370 > Capacitor Defrost Timer © © A For 208V operation mcva this wire to 208Y transformar tap. > 606006] HI | | | | FACTORY WIRING FIELD WIRING USE COPPER OR Low Voltage —_—— | | @ ©) OO wma’ | | | ONE 24y, Terminal Block cor) Heater Contactor Electric Heater 18N7H5,-24WI5 Heat Pump w/4Kvw (4011-1204 T874N1024/ £ O. qe74F1261 mer © Compressor T874R1129/ Q674F1181 с Internal Overload IMMERS JON CRANKCASE HEATER -—lal-lo © Capacitor(sre CHART | 2 Contactor Fou pe 24Y, Terminal Relay Block Switch Reversing Valve Solenoid Outdoor Motor 5/370 > Capacitor Haatar contactor © © 35A Circuit Breaker 45A Circuit Thermal Breaker Cutoff Haater Mies | | | = A ‘For 208V oparstion move this | | wire to 208V transformar tap. LOWS - 24WHS FACTORY WIRING FIELD WIRING Heat Pump 230/208-60-1 ALUMINUM WIRE High Voltage = it py — = | 1401-1218 E MODEL, 3 CAPACT TORY 1ANIS | 30/370 2415 | 35/370 Compressor — Pefrost Therm. Fused С Internal Overload IM4ERS ION CRANACASE HEATER (SEN CHART A) Capacitor Compressor 2 Contactor gh Pressure Switch Ruversing Yalve Solenoid 5/370 Capacitor Defrost Timer Terminal] Block QUID, GROUND ue Disconnect Switch wir we 230V 60Hz 1-Ph T874N1024/ Q674F1261 Compressor Fault Relay Blower Relay Thermal CutofE A Fer 208Y operation move this A wire to 708Y transfermer tap. or TB74R1129/ Q674F1181 DODGE 24Y. Terminal Block Heater Contactor Electric Heater FACTORY WIRING FIELD WIRING Low Voltage High Voltage [HE u USE COPPER OR ALUMINUM WIRE 1/5 KI 189015, 3 11| 5 (40! 1-130N A IRCUIT || | tt ACITOR 2/70 Internal Overload IMMERSION CRANKCASE HEATER (SEE CHART ABOVE) Capacitor Contactor 2 ) | Comprasacr Frau t Relay Switch Reversing Yalve Solenoid ” > it - use © т or al wire 230V 60Hx 1-Ph А A Indoor Outdoor Motor Motor - «5 Heater Contactor Thermal Cutoff 24Y. Terminal 1824110247 067471261 or T874R1129/ 067461181 5006 Block Electric Heater For 208V operation move thls wire to 208V transfcrmer tap. MEL — ¡WI [CIRCUIT BREAKER M5 LS DA 215 8 60 A, FACTORY WIRING Low Voltage Higrh Voltage A a SE EE CEE FIELD WIRING Г” TEE Ea wean a [нЕ СО 1845, 2645 | 401-1316
advertisement
Key Features
- Wall mounted
- Fresh air intake
- Heating and cooling operation
- Defrost cycle
- Ductwork compatibility
Frequently Answers and Questions
How do I install the fresh air damper assembly?
Refer to Figure 1 in the instruction manual for typical installation procedure.
What is the recommended clearance for the supply air duct?
The supply air duct flange and the first few feet of supply air duct require 1 inch clearance to combustible material.
What is the recommended air flow range for the 18WH5 model?
The recommended air flow range for the 18WH5 model is 585-725 CFM.
What type of thermostat can I use with this heat pump?
Only the thermostat and subbase combinations as shown in the instruction manual will work with this equipment. The stat and subbase MUST be matched.
How do I maintain the unit for optimal performance?
Maintain clean air filters at all times, do not needlessly close off supply and return air registers, and periodically clean the outdoor coil.