CompoNet (PDF/10,8Mo) [F]

CompoNet (PDF/10,8Mo) [F]
Product News
Open Network for High-Speed Control
CompoNet
● CompoNet Master Unit
CS1W-CRM21/CJ1W-CRM21
● CompoNet Slave Unit
CRT1 Series
● CompoNet Repeater Unit
CRS1 Series
Fast and
Intelligent
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
2
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
New Lineup
Unconventional!
Super thin!
● Thinnest slaves in the industry.
● Fit in small spaces in panels or devices.
● Attachable with DIN Track or screws.
New
CompoNet Digital I/O
Slaves 16 points with MIL
Connector
Actual Size
● CRT1-VID16ML/VOD16ML(-1)
Wide selection of CompoNet slaves.
3
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
A new global standard for smarter
control networking
What is
CompoNet?
Ethernet
Seamless CIP messaging through multiple layers of
networks means you can access intelligent field devices
from anywhere in your control system, and without having
to program communications code in your controller.
Internet layer
Controller Link
By combining OMRON's application experience with proven
CIP communications technology, CompoNet provides an
efficient networking solution for smart sensors, actuators
and remote I/O. Fast I/O data exchange and easy setup are
combined with transparent messaging for access to
intelligent field devices.
Controller layer
Using CompoNet as the control network shortens your
development time, reduces wiring, and simplifies
troubleshooting and machine maintenance.
All to help you build the best machines in less time.
What is CIP?
DeviceNet
CompoNet
Device layer
CIP (Common Industrial Protocol) was developed as a communications protocol
for industrial applications. Initially used in DeviceNet on CAN networks, it is now
an open standard operating on several different physical layers.
The main advantage of CIP is its seamless data transfer between different layers
of CIP networks. Whether transferring cyclic I/O data, configuration settings or
downloading control programs, you will not have to worry which device is
connected where.
Sensor &
Actuator layer
Therefore you can freely choose the best CIP network for each part of your
system, and mix them any way you want.
CompoNet is an ODVA network
The CIP communications standard, as used in the
EtherNet/IPTM, DeviceNetTM and CompoNetTM networks,
is controlled by the ODVA, the Open DeviceNet Vendors
Association. With nearly 300 member companies
worldwide developing a wide variety of products, the
ODVA promotes the advantages of seamless
networking, and makes sure that products adhere to the
standard for easy interconnection between vendors.
OMRON, as one of the four founding members of the
ODVA, plays a leading role in developing future
technologies for industrial networking.
Simple
Open
Network
Setting
● Global Standard
INDEX
● Easy Interconnection
Concept
CompoNet Network Specifications
CompoNet Open-network Information
CompoNet Product Introductions
CompoNet Family
Note: CompoNet and DeviceNet are registered trademarks of the ODVA.
6
14
15
16
20
ODVA Website:http://www.odva.org/
4
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
5
CompoNet - Achieve more with less effort.
Conventional
With
traditionalnetworks
networksare
foreither
sensors
fast,and
butactuators,
simple limitedmany
issues remained
unanswered:
insufficient
number of control
capacity
buses for
control, or complex
informationpoints andsystems
performance,
low degree and
of freedom
in wiring
exchange
for configuration
monitoring.
work, information
onlyoffers
on control
data.mix of high speed,
CompoNet,
however,
the ideal
CompoNet
is a global
open network
that solves
these
ample
capacity,
and ease-of-use
needed
to let you
build
production
site problems
at a single
stroke with
the
best machine,
the smartest
warehouse,
or the most
unprecedented
network
supports
flexible
conveyorperformance.
system. AndThe
what
is moreflexibly
important,
you
connected
suchtime,
as extensively
distributed sensors,
can
achievedevices,
this in less
due to simplified
and increasingwiring,
numbers
of control
for machinery and
programming,
device
setup points
and troubleshooting.
● Preventive maintenance data
● Smart diagnostics
● Transparent CIP messaging
Intelligence
Built-in
● Extensive error detection
● Network segmentation to
isolate faults
High
Performance
● 1000 I/O points in less than 1 ms
● Up to 2,560 points
● Up to 384 nodes
Simple
Setting
Easy
Installation
6
Fast
Troubleshooting
● Automatic baud rate detection
● Decimal node address setting
● Status display
● VCTF cable
● Fast wiring system
● Flexible layout
● Bit-level distribution
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
7
CompoNet enhances machine performance!
In electronic parts production, every millisecond counts
Simple Setting
CompoNet is up and running in minutes. Set the master's mode and baud rate, and the address on
each slave. Then plug in and go; no software settings required.
Communications status on
Master Unit display
Reduce
setting mistakes
Slaves adjust to the
Master's baud rate
Only address
setting required.
With CompoNet
Easy decimal setting!
Master Unit
CS1W-CRM21
Master Unit
CJ1W-CRM21
Easy Installation
High Performance, Large Capacity
Splitting production machines into logical
modules allows easy customization to meet
specific end-user demands.
To keep high performance, a fast and easy-toextend network is required. The efficiency of
CompoNet delivers fast cycle times, even when
extending the network with repeaters.
Each Master Unit can control up to 2,560
I/O points in up to 384 nodes.
CompoNet flat cable and isolation-displacement connectors make installation fast and faultless.
Power and communications are combined in one cable.
Branch connectors allow you to easily add or remove devices for maintenance and
troubleshooting.
Repeater Units can link sections of different cable types, allowing mixed topology networks.
● Alternatively, you can use simple twisted-pair cable and power each node individually.
Master Unit
CS1W-CRM21
Master Unit
CJ1W-CRM21
Flat Cable, Trunk Line and
Branch Line Connector
Connector
Flat Connector
Plug
Multidrop
Connector
Round cable I (2-conductor cable) or round cable II (4-conductor cable)
Open Type
Connector
(for connecting Units)
Conventional
general-purpose
field network
Block
Special Tool
10-100 ms
64 word
input nodes
(1,024 points)
CompoNet
64 word
output nodes
(1,024 points)
128 bit
input nodes
(256 points)
128 bit
output nodes
(256 points)
Removable Terminal Block
Standard
Flat Cable I
Digital I/O Slave Unit
Standard
Flat Cable I
B
Block
Block
A
D
Round cable I
(2-conductor
cable)
Expansion Unit
Block
C
1 ms
8
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Round cable I
(2-conductor
cable)
9
CompoNet helps you decrease engineering!
In warehouse automation, efficient wiring saves cost
Intelligence Built-in
All CompoNet slaves contain early-warning systems that monitor system performance continuously.
The transparent CIP communications of CompoNet makes it easy to access the diagnostic data in
each device.
■ Smart Features
● Set limit values in each slave to detect reduced machine performance
before breakdown.
SAP (Smart Active Parts)
● Smart Active Parts are drag-and-drop objects to
show slave data on your HMI.
CX-Integrator
● Used to set and monitor the network, the
Master Unit, and Slave Units.
FB (Function Blocks)
● PLC Function Blocks for access to
maintenance data reduce programming
effort.
As time passes . . .
1s
Threshold
● Scaling
● Peak/bottom hold and
top/valley hold
● Comparator
Analog Slave Unit
Flexible Installation
● Using CompoNet flat cable and repeaters allows easy
extensions and changes in network layout.
By using repeaters, long branch lines can cover a wide area
with less cable.
Conveyor lines require just one or two I/O points every few
meters. Dust- and splash-proof IP54 bit slaves allow
efficient installation with reduced cabling, directly on the
line.
Easy extension
CompoNet Master Unit
The cylinder
is slipping!
Fast Troubleshooting
Indication on the Master Unit helps to quickly assess the network status.
The CX-Integrator helps you identify wiring errors, power failures or malfunction.
By creating network segments separated by repeaters, faults can be isolated to reduce the impact
on overall operation.
■ Network Isolation
■ Extensive Error Detection
#01
CompoNet
Round cable I (2-conductor cable)
#01
ID02S
#02
ID02S
#33
ID02S
Address
error
Bit Slave Units
Repeater Unit
Repeater Unit
CRS1-RPT01
Long branch
line
t Cable
Relay box
S
d Fla
heathe
II
Disconnection error
#11
ID02S
Bit-by-bit distribution
#12
OD02S
#13
ID02S
Format
error
Isolated branch line
10
Repeater Unit
Isolation
#02
Communications
power supply
2s
● Communications power supply
● Total ON time monitor
monitoring
● Sensor inrush current
● I/O power supply connection check
response
● Unit ON time monitor
● Error log
Bit-level Distribution
● Mount them wherever you need them.
Digital I/O Slave Unit
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Available branch line
11
The open CompoNet system is prepared for the future.
Supported by the members of the ODVA
worldwide, CompoNet allows you to select the
best devices for your application.
OMRON's technology and the ODVA's certification
will assure plug-and-play operation between
devices from different vendors.
Function Block Library
Smart Active Parts Library
The function block library is a collection of functional
objects for Programmable Controllers (PLCs).
The function blocks provided by OMRON can be
incorporated into user programming to reduce
design work and increase standardization and quality
of control device interfaces.
The SAP library is a collection of screen parts for Programmable
Terminals. The parts provided by OMRON can be incorporated into
user-created screens to reduce design work and increase standardization and quality for control device interfaces.
SAP (Smart Active Parts)
http://www.omron.com/
CX-Integrator
The CompoNet Family
SYSMAC CS/CJ Series
Unit Adaptor, CP1W-EXT01, enables
CP1H (CJ
using the CJ1W-CRM21 with CP1H.)
Various device manufactures
are planning for CompoNet
products.
NS-series Programmable
Terminal
Page 20 to 22
CompoNet Master Units
Round cable I (2-conductor cable)
Terminating Resistor
Repeater Unit
Repeater Unit
Repeater Unit
CX-Integrator
Flat Connector Socket
Flat Connector Plug
Standard Flat Cable I
Terminating Resistor
Sheathed Flat Cable II
Round cable II (4-conductor cable)
Bit Slaves with Connectors
Flat Connector Socket
Flat Connector Plug
Terminating Resistor
Digital I/O Slave with
e-CON Connector
Digital I/O Slave with
MIL Connector
Digital I/O Slave with
MIL Connector
Digital I/O Slaves with 2-tier
Screw Terminal Block
Digital I/O Slaves with 3-tier
Screw Terminal Block
Terminating Resistor
Sensor
Communications Unit
Bit Slaves with Clamp
Terminals I/O Units
SmartSlice CompoNet
Communications Unit
Digital I/O Slaves
with Screw Terminal Block
Slaves with Relay Outputs
Slaves with SSR Outputs
Digital I/O Slave with
e-CON Connector
Digital I/O Slaves with
Clamp Terminal Block
Sensor
Communications Unit
Sensor
Communications Unit
Bit Slaves with Connectors
Analog I/O Slave Units
Bit Slave Units
Smart Sensor
Controller
Smart Sensor
Controller
Smart Sensor
Controller
Word Slave Units
12
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
13
CompoNet
Network Specifications
Cable Types, Baud Rates, and Maximum Distances
This section provides specifications on the maximum cable length and maximum number of nodes for each type of cable.
Do not exceed these specifications.
Master Unit
Sub-trunk line
Branch
line
Branch
line
Branch
line
Branch line
Sub-branch line
Repeater
Unit
Sub-trunk line
Slave Unit
Slave Unit
Sub-branch line
Repeater
Unit
Repeater
Unit
Trunk line
Branch line
Multidrop
Sub-trunk line
T-branching
Sub-branch line
Slave Unit
Terminating
resistor
Repeater
Unit
Sub-trunk line
Sub-trunk line
Sub-trunk line
Branch
line
Branch line
Repeater
Unit
Sub-trunk line
Repeater
Unit
Branch line
Trunk line
Slave Unit
■ Restrictions (at Baud Rate of 4 Mbits/s (No Branch Lines))
Maximum number of Slave
Units per segment
(See note 2.)
Cable type
Maximum length per segment
(maximum length with
Repeater Units)
Branch line length
per segment
Total branch line length
per segment
Round cable I
30 m (90 m)
0 m (See note 1.)
0 m (See note 1.)
---
32 nodes
Flat cable I, flat cable II, and
round cable II
30 m (90 m)
0 m (See note 1.)
0 m (See note 1.)
---
32 nodes
Branch location restrictions
Note 1: T-branches cannot be connected (only multidrop connections are possible).
2: Number of nodes including Repeater Units
■ Restrictions (at Baud Rate of 3 Mbits/s)
Cable type
Maximum length per segment
(maximum length with
Repeater Units)
Round cable I
30 m (90 m)
Branch line
length per
segment
0.5 m
Total branch
line length
per segment
Branch
location
restrictions
8m
3 branches/m
Maximum number of
nodes per branch
(See note 1.)
1 node
Sub-branch Total sub-branch Maximum number of
line
line
Slave Units per segment
length per
length
(See note 2.)
segment
per segment
0m
0m
32 nodes
Flat cable I, flat cable II, and
30 m (90 m)
0.5 m
8m
3 branches/m
1 node
0m
0m
32 nodes
round cable II
Note 1: The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be connected to one branch line using multidrop or T-branch connections (sub-branches).
2: Number of nodes including Repeater Units
■ Restrictions (at Baud Rate of 1.5 Mbits/s)
Cable type
Round
cable I
Without branches
With branches
Flat cable I, flat cable II, and
round cable II
Maximum length per segment
(maximum length with
Repeater Units)
Branch line
length per
segment
Total branch
line length
per segment
Branch
location
restrictions
100 m (300 m)
0m
(See note 3.)
0m
(See note 3.)
---
Maximum number of
nodes per branch
(See note 1.)
---
Sub-branch Total sub-branch Maximum number of
line
line
Slave Units per segment
length
length per
(See note 2.)
per segment
segment
---
30 m (90 m)
2.5 m
25 m
3 branches/m
3 nodes
0m
30 m (90 m)
2.5 m
25 m
3 branches/m
3 nodes
0.1 m
(See note 4.)
--0m
2m
(See note 4.)
32 nodes
32 nodes
32 nodes
Note 1: The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be connected to one branch line using multidrop or T-branch connections (sub-branches).
2: Number of nodes including Repeater Units
3: T-branches cannot be connected (only multidrop connections are possible).
4: T-branch connections from sub-branch lines.
■ Restrictions (at Baud Rate of 93.75 kbits/s)
Cable type
Round cable I
Maximum length per segment
(maximum length with
Repeater Units)
500 m (1500 m)
Flat cable I, flat cable II, and
round cable II
Branch line
length per
segment
6m
Total branch
line length
per segment
Branch
location
restrictions
120 m
3 branches/m
Maximum number of
nodes per branch
(See note 1.)
1 node
No restrictions to a total length per segment of 200 m
Sub-branch Total sub-branch Maximum number of
line
line
Slave Units per segment
length per
length
(See note 2.)
segment
per segment
---
---
32 nodes
32 nodes
Note 1: The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be connected to one branch line using multidrop or T-branch connections (sub-branches).
2: Number of nodes including Repeater Units
14
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
CompoNet
Open-network Information
OMRON actively promotes open networks.
OMRON sells CompoNet-compatible ASICs
and MPUs while providing development
support with a specialized team.
Adopting this open network effectively
reduces development costs and shortens
development time by simplifying the
development of CompoNet devices. The
following two types of CompoNet slaves are
available to match the characteristics of the
device to be developed.
Design Guidelines
CompoNet Chip
• Recommended
circuit
• Recommended
components
• Mounting
specifications
+
Bit Slave Units
Thirty-two or fewer I/O
For bit-level ON/OFF control
I/O port interface
Word Slave
Units
Interface for 256 points
User-set messages can be sent and
received.
DPRAM I/F
Masters
Communications for 1,280 inputs and
1,280 outputs
User-set messages can be sent and received.
DPRAM I/F
Easy development
Easy procedures
Reliable connections
Refer to the following for inquiries regarding open networks.
Technology Development Center Headquarters, Integration Strategy & Business Development Center,
Telephone: +81-77-565-5315, Email: [email protected]
The latest information is available on the following site.
http://www.omron.com/
From the home page, select Products Index - FA System Devices - Open Technology
● Range of Open Technology
CompoNet
Master Unit
CompoNet
Slave Configuration
Word Slave
Bit Slave
Physical layer
Physical layer
Communications ASIC
Communications ASIC
Communications MPU
Communications MPU
DPRAM
Bit signal
User circuit
(2 to 16 I/O points)
Master Configuration
AB, DB
User MPU (0 to 32 bytes I/O + messages)
DPRAM
Master ASIC
Master MPU
Physical layer
16 inputs
16 outputs
2 inputs
2 outputs
15
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
CompoNet
Product Introductions
Master Units
■ Master Units
CJ Series
CS Series
CJ1W-CRM21
CS1W-CRM21
Word Slaves
Digital I/O Slaves
■ Two-tire Screw
Terminal Block
■ Screw Terminal Block
and Relay Outputs or
SSR Outputs
● Input Units
● Relay Outputs
CRT1-ID08(-1)
CRT1-ROS08
CRT1-ID16(-1)
CRT1-ROS16
● Output Units
● SSR Outputs
CRT1-OD08(-1)
CRT1-ROF08
CRT1-OD16(-1)
CRT1-ROF16
● I/O Units
CRT1-MD16(-1)
■ Three-tier Screw
Terminal Block
● Input Units
● I/O Units
CRT1-ID08TA(-1)
CRT1-MD16TA(-1)
CRT1-ID08TAH(-1)
CRT1-MD16TAH(-1)
CRT1-ID16TA(-1)
CRT1-ID16TAH(-1)
● Output Units
CRT1-OD08TA(-1)
CRT1-OD08TAH(-1)
CRT1-OD16TA(-1)
CRT1-OD16TAH(-1)
Analog I/O Slaves
Expansion Units
■ Analog Input Unit
CRT1-AD04
■ Analog Output Unit
CRT1-DA02
16
■ Input Units
XWT-ID08(-1)
XWT-ID16(-1)
■ Output Units
XWT-OD08(-1)
XWT-OD16(-1)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Word Slaves
Digital I/O Slaves
■ Vertical Slaves with e-CON Connectors
■ Vertical Slaves with MIL Connectors
CRT1-VID08S(-1)
CRT1-VID16ML(-1)
CRT1-VID32ML(-1)
CRT1-VOD08S(-1)
CRT1-VOD16ML(-1)
CRT1-VOD32ML(-1)
CRT1-VMD32ML(-1)
■ Horizontal Slaves with e-CON Connectors
● Input Units
● I/O Units
CRT1-ID16S(-1)
CRT1-MD16S(-1)
CRT1-ID16SH(-1)
CRT1-MD16SH(-1)
CRT1-ID32S(-1)
CRT1-MD32S(-1)
CRT1-ID32SH(-1)
CRT1-MD32SH(-1)
● Output Units
CRT1-OD16S(-1)
CRT1-OD16SH(-1)
CRT1-OD32S(-1)
CRT1-OD32SH(-1)
■ Horizontal Slaves with Clamp Terminal Blocks
CRT1-ID08SL(-1)
CRT1-ID16SL(-1)
CRT1-OD08SL(-1)
CRT1-OD16SL(-1)
CRT1-MD16SL(-1)
SmartSlice GRT1 Series
■ CompoNet Communications Unit
■ SmartSlice I/O Units
GRT1-ID4(-1)
GRT1-OD4(-1)
GRT1-ROS2
GRT1-CRT
GRT1-AD2
GRT1-DA2C
GRT1-DA2V
GRT1-TS2P
GRT1-CT1(-1)
17
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
CompoNet
Product Introductions
Bit Slaves
Bit Slave with Connectors
■ IP20 Input Units
Bit Slaves with Clamps
■ IP54 Input Units with Connectors
with Connectors
CRT1B-ID02S(-1)
CRT1B-ID02SP(-1)
CRT1B-ID04SP(-1)
IP20 Output Units
with Connectors
CRT1B-OD02S(-1)
IP54 Output Units with
Connectors
CRT1B-OD02SP(-1)
■ IP54 I/O Units with Clamps
CRT1B-MD04SLP(-1)
Repeater Unit
■ Repeater Unit
CRS1-RPT01
Peripheral Devices
With CompoNet, connectors can be attached to communications
■ There are three types of cable used with CompoNet.
cables and Units to connect to Units and branch or extend cables.
● Round Cable I (VCTF 2-conductor cable), Commercially Available
The communications cable connection and branching methods
● Standard Flat Cable I: DCA4-4F10
depend on the type of cable and the type of branch.
● Sheathed Flat Cable II: DCA5-4F10
■ The terminating resistors, connectors, and tools depend on the
type of cable.
Round cable I (2-conductor cable)
Commercially
available
● Open Type Connector
(for connecting Units)
DCN4-TB4
● Terminating Resistor
DRS1-T
Round cable I (4-conductor cable)
Commercially
available
● Open Type Connector
(for connecting Units)
DCN4-TB4
● Terminating Resistor
DCN4-TM4
● Special Tool for
Standard Flat Cable I
DWT-A01
● Flat Connector Socket
DCN4-TR4
18
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Standard Flat Cable I
● Flat Connector Socket
DCN4-TR4
● Terminating Resistor
DCN4-TM4
● Special Tool for
Standard Flat Cable I
DWT-A01
DCA4-4F10
● Flat Connector Plug
DCN4-BR4
● Multidrop Connector
DCN4-MD4
Sheathed Flat Cable II
● Flat Connector Socket
DCN5-TR4
● Terminating Resistor
DCN5-TM4
● Special Tool for Sheathed
Flat Cable II
DWT-A02
DCA5-4F10
● Flat Connector Plug
DCN5-BR4
Optional Products
■ Attachment Bracket
CRT1-ATT01
CRT1-ATT02
For Digital I/O Slaves - 16 points
with MIL connector
CRT1-VID16ML/VOD16ML(-1)
For Digital I/O Slaves - 8 points
with e-CON connector
CRT1-VID08S/VOD08S(-1)
19
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Family
Overseas sales areas:
Koganei Corporation
Europe, North America, Asia-Pacific
Solenoid Values
+81-42-383-7271
UR L
CompoNet-compatible Solenoid
Valves: JA Series
CompoNet-compatible Solenoid
Valves: F Series
www.koganei.co.jp
Features
1. Thin and Compact: Valve width of only 10 mm with effective
area of 3.5 mm2.
2. Lower power consumption.
Standard: 0.5 W Low current type: 0.25 W
3. Two 3-port valves in one body.
Features
1. Single/double dual-use valves.
2. Three of valve widths: 10, 15 and 18 mm
3. Uses dual-use fittings for different tube sizes.
Overseas sales areas:
IAI Corporation
Europe, North America, China, Asia-Pacific
UR L
ROBO CYLINDER
http://www.intelligentactuator.com/
Controller
Controller for RCA Series
ROBO CYLINDER:
ACON-C/CG
ACON-C
PCON-C
Controller for RCP2 Series
ROBO CYLINDER:
PCON-C/CG
Features
1. Designed for 24 VDC servomotors.
2. Multipoint positioning: up to 512 points.
3. High speed: Up to 800 mm/s.
Features
1. Designed for 24 VDC pulse motors.
2. Multipoint positioning: up to 512 points.
3. High power in lower speed range.
Controllers, Signal Towers, and Converters
Available soon
Overseas sales areas:
PATLITE Corporation
+81-72-948-8110
Available soon
Europe, North America, China, Asia-Pacific
UR L
CompoNet Supported
Signal Tower:
www.patlite.co.jp
Features
1. Use of ultra-bright LED enhanced for illumination.
2. Two selectable sound patterns with adjustable volume.
LE-K3(B)P/W-RYG
CompoNet Supported
Wall-Mount Signal Tower:
WEP-K3(B)-RYG
Available soon
Features
1. A 37.5 mm-thin design that significantly enhances integration with
equipment as a built-in signal system.
2. Clear vertical cut lens enhanced for illumination over a wide
perspective.
3. Built-in audible alarm.
JSK Co., Ltd.
+81-72-661-4071
Componet-serial
Transducer:
CHU-001
UR L
www.nihon-seigyo.co.jp
Features
1. Connects to bar-code readers.
2. Allows setting from CompoNet master.
3. Supplies power to bar-code reader.
Available soon
20
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Overseas sales areas:
3M Company
Europe, North America, China, Asia-Pacific
UR L
www.3M.com/interconnects
Mini-Clamp Connector:
3710x-xxxx-000 FL
Features
1. IDC technology reduces process/cost of wire termination.
2. Crimped using standard pliers to reduce tool costs.
3. Design offers multiple gauges and wire size diameters.
Overseas sales areas:
Tyco Electronics AMP K.K
UR L
RITS Connector (e-CON):
X-1473562-4
www.tycoelectronics.com
Features
1. New Chisel Press Contacts for sensor cables.
2. No special crimping tool required for easy termination.
3. Two contact points for good connection and more security.
Overseas sales areas:
Honda Connectors, Inc
+81-6-6376-4717
Europe, North America, China, Asia-Pacific, Southeast Asia
UR L
Connector:
www.honda-connectors.co.jp
Features
HCN-MD4SMUG( )+
1. One piece connector.
2. Low profile.
3. The current tool can be used for assembly.
Available soon
SWCC Showa Cable Systems Co., Ltd.
+81-3-3597-7117
CompoNet Cable
A
UR L
B
Available soon
Overseas sales areas:
China, Taiwan, Asia-Pacific
www.swcc.co.jp/
Features
A
B
Connectors
+81-44-844-8080
Europe, North America, China, Taiwan, Asia-Pacific
C
TCN-F1 Flat Cable I (4-wire)
TCN-F2 Flat Cable II (4-wire, with sheath)
TCN-R1 Round Cable I (2-wire)
C
Overseas sales areas:
Kuramo Electric Co., Ltd.
+81-778-22-1500
KOMP-FII
UR L
www.kuramo.co.jp
KOMP Series
CompoNet Flat Cable I:
CompoNet Flat Cable II: CompoNet Round
KOMP-FII
Cable I and II:
KOMP-FI
KOMP-RI
KOMP-RI and KOMP-RII
Features
1. Heat resistance (90°)
2. Flame resistance (Vertical Tray Flame Test)
3. UL certification (UL13, CL2) (under development)
Available soon
Cables
KOMP-FI
North America, China, Asia-Pacific
Features
1. Heat resistance (90°)
Available
2. Flame resistance (Vertical Tray Flame Test)
3. Flame resistance (Vertical Tray Flame Test)
4. UL certification (UL13 PTLC, UL444 CM) (under development)
soon
Nichigoh Communication Electric Wire Co., Ltd
+81-72-923-5104
UR L
www.nichigoh.co.jp
FCII
UNICOMPO
FCI (CompoNet Flat I)
FCII (CompoNet Flat II)
RCI (CompoNet Round I)
RCII (CompoNet Round II)
FCI
RCI
RCII
Under development
Features
1. Scheduled acquisition of CE marking and UL/Cul certification.
2. NFPA70(NEC) listing.
3. Excellent oil resistance (UNICOMPO FCII, RCI, RCII)
21
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Family
Kanetsu Co., Ltd
Overseas sales area: China
+81-75-662-0996
[email protected]
UR L
www.kanetuu.co.jp
CompoNet Flat Cable I and II
Daiko. E.W.
KCNF
Features
1. Enables using unique isolation-displacement
connectors for CompoNet.
2. Easy one-step IDC connection without
insulation stripping.
3. UL AWM, compliant.
Taiyo Electric Wire & Cable Co., Ltd.
KCNF-J
Features
1. Enables using unique isolation-displacement
connectors for CompoNet.
2. PVC jackets with polarity guide line for IP54
system.
3. Easy one-step IDC connection without insulation
stripping.
4. UL AWM, compliant.
Cables
Oil-resistant and Highly Flexible Round Cable II for CompoNet
Taiyo Electric Wire & Cable Co., Ltd.
Hanshin Electric Wire & Cable Co., Ltd.
KCNR-4
MRC-4
Features
1. The cable can be used for mobile and
oil-resistant wiring.
2. Insulation colors as recommended by
CompoNet specification.
3. UL AWM, compliant.
Features
1. The cable can be used for mobile and
oil-resistant wiring.
2. Round cable for low cost installation.
3. UL AWM, CSA compliant.
Available soon
CompoNet Round Cable I and II
Onamba Co., Ltd
Kawai Cable, Ltd.
VCTF-2C & VCTF-4C
VCTF-2C & VCTF-4C
Feature
Round cable for low cost installation.
22
Feature
Round cable for low cost installation.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
CompoNet
Information
The CX-One now includes the CompoNet Tool.
(Auto-updating is available from March 2008.)
The CX-Integrator allows online reading of
the system configuration for PLC networks
and serial communications from a personal
computer. It makes monitoring network
connections, parameter settings, and
network diagnosis from a computer very
simple.
A file converter from CompoNet Tool to CX-Integrator is
available.
Please contact the OMRON sales division.
Windows Version
Connectable with Round Cable II (4-conductor cable).
Officially approved by ODVA in November 2007. See page 14 for wiring restrictions.
● ODVA Website
h t t p : //w w w .od va. o rg
Visit ODVA's website for products that conform with CompoNet.
23
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
MEMO
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year
(or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
Consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
This catalog mainly provides information that is necessary for selecting suitable models, and does
not contain precautions for correct use. Always read the precautions and other required information
provided in product operation manuals before using the product.
The application examples provided in this catalog are for reference only. Check functions and
safety of the equipment before use.
Never use the products for any application requiring special safety requirements, such as nuclear
energy control systems, railroad systems, aviation systems, medical equipment, amusement
machines, vehicles, safety equipment, or other application involving serious risk to life or property,
without ensuring that the system as a whole has been designed to address the risks, and that the
OMRON products are properly rated and installed for the intended use within the overall equipment
or system.
Note: Do not use this document to operate the Unit.
OMRON Corporation
Industrial Automation Company
Control Devices Division H.Q.
Network Devices Department
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81) 75-344-7116/Fax: (81) 75-344-7149
2-2-1 Nishikusatsu, Kusatsu-shi,
Shiga, 525-0035 Japan
Tel: (81) 77-565-5219/Fax: (81) 77-565-5569
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Authorized Distributor:
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
OMRON Industrial Automation Global: www.ia.omron.com
© OMRON Corporation 2006 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Printed in Japan
Cat. No. R140-E1-04
0508 (1106) (H)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]