DETECT Pc

Installation

The DETECT P is supplied in a universal version that fits all ventilation ducts, circular and rectangular.

40°C

-20°C

Figure 1. Permissible ambient temperature.

8 x Ø

D

4 x Ø D

Figure 4. Adapt the mounting plate of the pressure sensor to fit the duct to which you are securing it, either circular or rectangular.

6 x Ø D

Figure 2. Requirements for lengths of straight duct between the sensor an various types of obstructions.

Figure 5. The pressure hose is fitted differently depending on whether it is connected to a supply air duct or an extract air duct.

Calibration of pressure sensor

The pressure sensor needs to be zero calibrated after the installation in order for the 0-point to be adapted to the installation location.

After the sensor has been powered up for at least three minutes, release the pressure tubes, open the lid and press the calibration button for at least 3 seconds.

Figure 3. Clear space required for installation.

E

F 0

1 2 3 4

A B

Wiring

For particulars on electrical wiring, see CONTROL Zone.

Swegon reserves the right to alter specifications.

Figure 6. Zero calibration of pressure sensor.

20151007 / Art: 1545214 www.swegon.com