Below you will find brief information for Motor, Limit Switch, Torque Switch, Thermoswitch, Position Transmitter, Blinker Transmitter, Potentiometer, PTC Thermistor. This guide provides details on connecting AUMA motors, including 3-phase AC, 1-phase AC with capacitor and 1-phase AC motors. It also includes information on microswitches, limit switches, torque switches, thermoswitches, position transmitters, blinker transmitters, potentiometers, and PTC thermistors. This document is intended to help you understand the terminal plans for your AUMA product.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

AUMA Motor Terminal Plans | Manualzz
Terminal plans
KMS
Connections of motors - AUMA-motors
For DC, brake and two-speed motors, separate terminal plans are available.
ATTENTION !
Complete protection of AUMA pot-type motors is only achieved when correctly wiring the thermoswitches, embedded
in the winding (plugs/terminals 19 and 20).
3-Ph-AC motor
KMS TP.../...
1-ph AC motor with capacitor
for SA 07.1– SA 10.1
KMS 15TP.../...; KMS 26TP.../...
1-ph AC motor
for SG 05.1 – SG 12.1
KMS 1TP.../...
Th
Th
Th
M
M
M
3~
1~
1~
C
U1 V1 W1 19 20
U1 V1 W1 19 20
U1 V1 W1
L1 N
N L1
L1 N
N L1
19 20
Microswitches
ATTENTION !
Only the same potential can be switched on the two circuits of a microswitch. If different potentials are to be switched
simultaneously, the use of tandem switches imposes (two galvanically separate microswitches in one housing).
To ensure reliable signalisation, use the leading contacts (WSR 1/WOEL 1 or DSR 1/DOEL 1) and the lagging contacts
(WSR/WOEL or DSR/DOEL) for switching off.
II Tandem switch
I Single switch
6
Mechanical lifetime = 2 x 10 starts
Switching off
Signalisation
BK 2
RD 2
BK
RD
BK
RD
NO NC
NC NO
Voltage
Current type
AC current (inductive load)
cos phi = 0,8
DC current (resistitve load)
Switch rating Imax at
30 V
125 V
250 V
5A
5A
5A
2A
0.5 A
0.4 A
DSR 1/DOEL 1
WSR 1/WOEL 1
min. 5 V, max. 50 V
BK 2
RD 2
BK
RD
BK
RD
Gold plated contacts
DSR/DOEL
WSR/WOEL
min. 4 mA, max. 400 mA
Current
Wire colours: RD - red (NC contact), BK - black (NO contact)
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
1/4
Issue
1.10
Y000.183/002/en
KMS
Terminal plans
S1
S2
DSR
DOEL
Torque switch, closing, clockwise
Torque switch, opening, counterclockwise
S 1/2
S 2/2
DSR 1
DOEL 1
Torque switches, in tandem operation with DSR/DOEL
S3
S4
WSR
WOEL
Limit switch, closing, clockwise
Limit switch, opening, counterclockwise
S 3/2
S 4/2
WSR 1
WOEL 1
Limit switches, in tandem operation with WSR/WOEL
S6
S7
WDR
WDL
Limit switches, DUO for 2 intermediate positions, can be adjusted to any position
S 6/2
S 7/2
WDR 1
WDL 1
Limit switches, DUO for 2 intermediate positions in tandem operation with WDR/WDL
S5
F1
BI
2)
Th
Blinker transmitter
Thermoswitches (motor protection)
B1
B2
IWG
RWG
Inductive position transmitter
Electronic position transmitter 3- or 4-wire system
B3
B4
IWG
RWG
Inductive position transmitter
Electronic position trasnmitter 2-wire system
R1
H
Heater
1)
R2
R 2/2
Potentiometer
Potentiometer in tandem operation with R 2
R3
PTC thermistor (motor protection)
Basic equipment SA
Basic equipment SAR/SG
1)
2)
2)
.../001
TP 110
.../001
TP 100
1)
TP 400
TP 410
1)
TP 200
TP 210
1)
2)
2)
TP 102
TP 112
1) Blinker transmitter for SAR only if ordered additionally
2) Thermoswitches are standard for AUMA 1-ph and 3-ph motors only. Contacts open at 140°C and automatically return after cooling down.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
2/4
Issue
1.10
Y000.183/002/en
Terminal plans
KMS
1)
2)
2)
TP 114
TP 104
1)
2)
TP 150
3
2)
4
3
4
TP 140
For orders and arising questions, please indicate first the TP number of the terminals 1 – 24, then add designation of terminal
assignment 25 – 48. Separate documents are available for AUMA MATIC, AUMATIC and AUMA SEMIPACT.
Example: TP 110/201
Basic equipment SA and limit switch in tandem operation with WSR/WOEL
1)
TP 110
2)
.../201
suitable for use of
plug/socket connectors with screw-type terminals and
plug/socket connectors with spring cage terminals
.../001
.../301
.../041
.../341
1) Blinker transmitter for SAR only if ordered additionally
2) Thermoswitches are standard for AUMA 1-ph and 3-ph motors only. Contacts open at 140°C and automatically return after cooling down.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
3/4
Issue
1.10
Y000.183/002/en
KMS
Terminal plans
suitable for use of
plug/socket connectors with screw-type
terminals and
plug/socket connectors with spring
cage terminals
.../201
.../011
.../241
.../031
.../051
.../071
.../211
.../251
.../101
.../111
9TP.../231
9TP.../311
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
4/4
Issue
1.10
Y000.183/002/en

advertisement

Key Features

  • Motor Connection Plans
  • Microswitch Operation
  • Limit Switch Operation
  • Torque Switch Operation
  • Thermoswitch Protection
  • Position Transmitter Configuration
  • Blinker Transmitter Application
  • Potentiometer Configuration
  • PTC Thermistor Protection

Frequently Answers and Questions

How do I correctly wire thermoswitches for AUMA pot-type motors?
For complete protection of AUMA pot-type motors, ensure you correctly wire the thermoswitches, embedded in the winding (plugs/terminals 19 and 20).
What are the different types of AUMA motors that are covered in this document?
This document covers connection plans for 3-phase AC, 1-phase AC with capacitor and 1-phase AC motors.
What is the function of a microswitch and how do I use tandem switches?
Microswitches allow you to switch on two circuits simultaneously. If you need to switch different potentials simultaneously, it is recommended to use tandem switches (two galvanically separate microswitches in one housing).

Related manuals

Download PDF

advertisement