M-SERIES SINGLE ZONE SYSTEMS MSY-D

M-SERIES SINGLE ZONE SYSTEMS MSY-D
M-SERIES SINGLE ZONE SYSTEMS
MSY-D COOLING ONLY WALL-MOUNT AIR SYSTEMS
1. INDOOR UNITS....................................................................................................................................................MSY-D-2
2. OUTDOOR UNITS................................................................................................................................................MSY-D-3
3.SYSTEM...............................................................................................................................................................MSY-D-4
3-1. Specifications......................................................................................................................................MSY-D-4
3-2. External Dimensions...........................................................................................................................MSY-D-8
3-3. Center of Gravity...............................................................................................................................MSY-D-10
3-4. Electrical Wiring Diagrams................................................................................................................MSY-D-11
3-5. Refrigerant System Diagrams...........................................................................................................MSY-D-13
3-6. Capacity Correction Curve by Temperature......................................................................................MSY-D-14
3-7. Capacity Correction Table by Temperature.......................................................................................MSY-D-15
3-8. Capacity Correction Curve by Refrigerant Piping Length.................................................................MSY-D-16
3-9. Capacity Correction Table by Refrigerant Piping Length..................................................................MSY-D-17
3-10. Charge Calculations........................................................................................................................MSY-D-18
3-11. Air Flow Data...................................................................................................................................MSY-D-19
3-12. Sound Pressure Levels...................................................................................................................MSY-D-20
3-13. Standard Operation Range.............................................................................................................MSY-D-22
3-14. Accessories.....................................................................................................................................MSY-D-23
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-1
1. INDOOR UNITS
•MSY-D30NA-8
•MSY-D36NA-8
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-2
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
2. OUTDOOR UNITS
•MUY-D30NA-1
•MUY-D36NA-1
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-3
3-1. SPECIFICATIONS
• Wall-mounted indoor unit
• Standard Hybrid Catechin Prefilter and anti-allergy enzyme filter for high air-purification abilities
• Updated sleek, compact indoor unit design
• Auto fan speed control: Quiet, Low, Medium, High, and Super High
• Hand-held Wireless Remote Controller
• Advanced microprocessor control
• Auto restart following a power outage
• Anti-allergy Enzyme Filter
• Limited warranty: five years on parts and defects and seven years on the compressor
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-4
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
MSY-D30NA-8 MSY-D36NA-8
MSY-D30NA-8
Model name
Power supply
V, phase, Hz
MSY-D36NA-8
208/230 , 1 , 60
Max. fuse size (time delay)/ Disconnect switch
A
15
Min. circuit ampacity
A
1.0
Blower Motor (ECM)
F.L.A
0.76
Airflow
Low - Med. - High - Powerful
COOL Dry
(Wet)
CFM
HEAT Dry
Moisture removal
pt./h
Sensible Heat Factor
Cooling
Sound level
Low - Med. - High - Powerful
Heating
Cond. drain connection O.D.
389 - 639 - 848 - 887
(350 - 576 -763 - 798)
445 - 639 - 848 - 887
—
9.9
11.9
0.64
0.62
32 - 42 - 49 -51
dB(A)
34 - 42 - 49 - 50
—
in.
5/8
W
Dimensions
D
46-1/16
in.
11-5/8
H
Weight
14-3/8
Ib.
External finish
40
Munsell 1.0Y 9.2/0.2
Remote controller
Wireless type
Control voltage (by built-in transformer)
12-24 VDC
NOTE : Test conditions are based on ARI 210/240.
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-5
3-1. SPECIFICATIONS
MUY-D30NA-1 MUY-D36NA-1
MSY-D30NA-8
MSY-D36NA-8
30,700
(9,800 ~ 30,700)
33,200/34,600
(9,800 ~ 33,200) /
(9,800 ~ 34,600)
3,380
(620 ~ 3,380)
4,210/4,240
(620 ~ 4,210) /
(620 ~ 4,240)
9.1 [16.0]
7.9/8.2 [15.1]
MUY-D30NA-1
MUY-D36NA-1
Item Model name
Capacity
Rated (Minimum ~ Maximum)
Cooling 1
Btu/h
Power consumption
Rated (Minimum ~ Maximum)
(TOTAL)
Cooling 1
W
EER 1 [SEER] 3
Cooling
Outdoor unit model
Power supply V , phase , Hz
208/230 , 1 , 60
Max. fuse size (time delay)
A
25
Min. circuit ampacity
A
21
Fan Motor (ECM)
F.L.A
0.93
Model
Compressor
Refrigeration oil
TNB220FMCHT
R.L.A
16
L.R.A
20
cc
870 (NEO22)
Refrigerant control
Linear expansion valve
Cooling
Sound level 1
Heating
dB(A)
Defrost method
55
56
—
—
—
—
W
Dimensions
D
33-1/16
in.
13
H
Weight
33-7/16
Ib.
126
External finish
126
Munsell 3Y 7.8/1.1
Remote controller
Wireless type
Control voltage (by built-in transformer)
12 - 24 VDC
Refrigerant piping
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Connection method
Between the indoor & outdoor
units
Liquid
Gas
3/8 (0.0315)
in.
5/8 (0.0394)
Indoor
Flared
Outdoor
Height difference
Piping length
50
ft.
Refrigerant charge (R410A)
100
4 lb.
4 lb.
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-6
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
EFFICIENCY RATINGS
Outdoor Unit
Indoor Unit
SEER
EER
WALL-MOUNT COOLING ONLY
MUY-D30NA
MSY-D30NA
16
9.1
MUY-D36NA
MSY-D36NA
15.1
8.2
Note:
Efficiency values based on AHRI 210/240 test method.
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-7
3-2. EXTERNAL DIMENSIONS
Unit: inch
MSY-D30NA-8 MSY-D36NA-8
Indoor unit
4-11/16
7/8
2-11/16
11-5/8
5-3/8
Wall hole ø3
1/4
Air in
46-1/16
17-11/16
1/8
20-7/8
2-3/16
1-7/8
1-7/8
11-5/8
45-1/2
Installation plate
33-11/16
9-1/2
2-5/8
Air out
2-5/16
2-1/2
2-15/16
2-15/16
14-3/8
Piping
Drain hose
5-7/8
3/4
14-3/8
Liquid line
Gas line
Wireless remote controller
Joint
Drain hose
Piping
ø3/8 19-11/16
(Flared connection ø3/8)
ø5/8 16-7/8
(Joint connection ø5/8)
ø5/8
(Flared connection ø5/8)
Inslation ø1-1/8 Connected part ø9/16 O.D
Insulation
ø1-1/4 O.D
ø9/16 I.D
ø1-15/16 O.D
ø1-1/4 I.D
ø1-15/16 O.D
ø1-1/4 I.D
Required Space (Indoor Unit)
2-13/16 or more
3/8 or more
4-3/16 or more
9-3/8 or more
In case of left,left back,
or left under piping (using spacer) 5-1/8 or more
14-1/2 or more
8-11/16 or more
2-3/16 or more
4-11/16 or more
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-8
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-2. EXTERNAL DIMENSIONS
Unit: inch
Open as a rule
20 inch or more if the back,
both sides and top are open
4 in
. or
mo
re
14
in
. or
mo
re
4 inch or more /
8 inch or more if
there are obstacles
to both sides
REQUIRED SPACE
Open as a rule
20 inch or more if
the front and both
sides are open
MUY-D30NA-1 MUY-D36NA-1
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-9
3-3. CENTER OF GRAVITY
MSY-D30NA-8 MSY-D36NA-8
Unit: inch(mm)
C
a
c
B
A
A
B
C
a
b
c
MSY-D30NA-8
MSY-D36NA-8
18-1/8
(460)
7-1/2
(190)
7-1/2
(190)
46-1/16
(1170)
11-5/8
(295)
14-3/8
(365)
b
MUY-D30NA-1
MUY-D36NA-1
c
C
A
a
Model name
Unit: inch(mm)
Model name
A
B
C
a
b
c
MUY-D30NA-1
MUY-D36NA-1
11-13/16
(300)
5-7/8
(150)
13-3/8
(340)
33-1/16
(840)
13
(330)
33-7/16
(850)
B
b
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-10
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-4. ELECTRICAL WIRING DIAGRAMS
MUY-D36NA-8
MSZ-D30NA- 8 MSZ-D36NA- 8 MSY-D30NA- 8 MSY-D36NA- 8
MSY-D30NA-8
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-11
3-4. ELECTRICAL WIRING DIAGRAMS
MUY-D30NA- 1 MUY-D36NA- 1
MUY-D30NA-1
MUY-D36NA-1
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-12
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-5. REFRIGERANT SYSTEM DIAGRAMS
MSY-D30NA-8 MSY-D36NA-8
Indoor
heat
exchanger
Indoor coil
thermistor
RT13 (Sub)
Unit: inch (mm)
Refrigerant pipe ø5/8
(with heat insulator)
Indoor coil
thermistor
RT12 (Main)
Flared connection
Joint
Joint connection
Distributor
Room temperature
thermistorRT11
Flared connection
Strainer
Refrigerant flow in cooling
Refrigerant pipe ø3/8
(with heat insulator)
MUY-D30NA-1 MUY-D36NA-1
Oil separator
Refrigerant pipe 5/8
(with heat insulator)
Flared connection
Outdoor
heat
exchanger
Capillary tube
O.D. 0.071 x I.D. 0.024
x 39-3/8
( 1.8 x 0.6 x 1,000)
Strainer
#100
Service
port
High-pressure
Switch
Stop valve
(with service port)
Discharge
temperature
thermistor
RT62
Service
port
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor
RT68
Compressor
Flared connection
LEV
Stop valve
Refrigerant pipe 3/8
(with heat insulator)
Strainer
#100
Capillary tube
O.D. 0.142 x I.D. 0.094
x 1-31/32
( 3.6 x 2.4 x 50)
Refrigerant flow in cooling
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-13
3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT
DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-14
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
(1) M-SERIES COOLING CORRECTION
70
77
81
86
95
104
115
60
1.11
1.06
1.01
0.97
0.91
0.83
0.76
63
1.16
1.10
1.06
1.02
0.96
0.88
0.81
64
1.18
1.13
1.08
1.04
0.98
0.90
0.83
68
1.23
1.18
1.14
1.10
1.03
0.96
0.89
72
1.28
1.23
1.20
1.15
1.09
1.02
0.95
75
1.34
1.29
1.26
1.22
1.15
1.08
1.02
79
1.38
1.34
1.32
1.28
1.21
1.14
1.07
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-15
3-8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH
DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT
DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-16
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
(1) Cooling capacity correction
Refrigerant piping length (one way: ft.)
25 (std.)
40
65
100
1.0
0.95
0.878
0.713
MUY-D30NA-1
MUY-D36NA-1
(2) Maximum refrigerant piping length & maximum height difference
Refrigerant piping: ft
Model
Additional
piping
Max. length
A
Additional
piping
Max. height
B
100
50
MUY-D30NA-1
MUY-D36NA-1
Piping size: in.
Gas
Liquid
Outside
diameter
Minimum
Wall
thickness
Outside
diameter
Minimum
Wall
thickness
5/8
3/8
1/4
0.0315
Indoor
unit
Max. Height
difference
B
Additional Piping
Max. length
A
Outdoor unit
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-17
3-10. CHARGE CALCULATIONS
(1) ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calcualation.
Refrigerant piping length (one way): ft.
Model
Outdoor unit
precharged
25ft
30ft
40ft
50ft
60ft
70ft
80ft
90ft
100ft
MUY-D30NA-1
MUY-D36NA-1
4 lb.
0
1.08
3.24
5.40
7.56
9.72
11.88
14.04
16.20
NOTE: Calculation: X oz. = 1.08/5 oz./ft
(Refrigerant piping length (ft) - 25)
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-18
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-11. AIR FLOW DATA
OUTLET AIR SPEED AND COVERAGE
Model name
Mode
MSY-D30NA
MSY-D36NA
COOL
Function
Airflow
(CFM)
Air speed
(ft./s.)
Coverage (ft.)
Dry
321
16.3
23.5
Wet
286
14.5
21.0
● The air coverage is the figure up to the position where the air speed is 1 ft./s., when air is blown out horizontally
from the unit properly at the High speed position.
The coverage should be used only as a general guideline since it varies according to the size of the room and
furniture arranged inside the room.
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-19
3-12. SOUND PRESSURE LEVELS
MSY-D30NA-8
MSY-D36NA-8
Noise Criterion Curves
WALL
MSZ-D30NA
MSZ-D36NA
MSY-D30NA
MSY-D36NA
*MSY:Only cooling
UNIT
NOTCH
1m
SPL(dB(A))
LINE
49
● ●
COOL(Hi)
HEAT(Hi)
0.8m
MICROPHONE
Test
Ambient
temperature
conditions
are
based
on
JIS
Z8731
27℃
90
OCTAVE BAND SOUND PRESSURE LEVEL,dB re 0.002 MICRO BAR
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES,Hz
MSZ041
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-20
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS
MUY-D30NA-1
MUY-D36NA-1
DUE TO CONTINUES RESEARCH AND PRODUCT IMPROVEMENT
DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-21
3-13. STANDARD OPERATION RANGE
(1) INDOOR UNIT
MSY-D30NA-8 MSY-D36NA-8
OPERATING RANGE
Cooling
Indoor intake air temperature
Outdoor intake air temperature
Maximum
95˚ FDB, 71˚ FWB
115˚ FDB
Minimum
67˚ FDB, 57˚ FWB
67˚ FDB
(2) OUTDOOR UNIT
MUY-D30NA-1 MUY-D36NA-1
OPERATING RANGE
(A) POWER SUPPLY
Rated voltage
Guaranteed Voltage (V)
208/230 V
1 phase
60 Hz
Outdoor unit
Min.187
208
230
Max.253
(B) OPERATION
Intake air temperature (°F)
Mode
Cooling
Condition
Indoor
Outdoor
DB
WB
DB
WB
Standard temperature
80
67
95
—
Maximum temperature
90
73
115
—
Minimum temperature
67
57
14
—
Maximum humidity
78%
—
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-22
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES
(1) INDOOR UNIT
Part Number
Descriptions
Applicable model
C13-103
Blue Diamond Sensor Extension Cable - 15 Ft. CWMB1
Drain Pan Level Sensor/Control for indoor unit shut off to
prevent Drain Pan Overflow
DPLS1
Portable Central Controller (PCC) - controls up to 16
RedLINK Zones - requires an MHK1 on each indoor unit
DSD-400P
Wireless wall-mounted remote controller (MRCH1) with a
signal receiver (MIFH1) and cable (MRC1) all in one kit
MAC-1415FT-E
Anti-Allergy Enzyme Filter (qty of 2)
System Control Interface - MA, Contact terminal, and
MAC-333IF-E
M-NET Control Adapter, Supplemental heat and humidifier
adaptor
MCCH1
Outdoor Air Sensor - reads both outside temperature and
humidity displayed on MRCH1 and MCCH1 if installed
MHK1
Multi-functional hard wired controller (used specifically for
twinning, lead/lag, and 7 day programmable applications)
Requires MAC-333IF-E Adaptor
MOS1
Lockdown Bracket for wireless, hand-held, remote
controllers
PAC-YT53CRAU
3-Pole Disconnect Switch 30 Amps 600 volts rated for
interupting power supply at/near indoor unit - fits 2 X 4 utility
box
PAR-21MAAU
4 piece ( 1 pair) condensing unit wall mounting brackets painted steel
RCMKP1CB
Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic
SI30-115
Mini-Condensation pump - 115 volt application
SI30-230
Mini-Condensation pump - 230 volt application
TAZ-MS303
X87-721
All Models
Advanced Blue Diamond Mini-Condensation pump w/
Resevoir & Sensor - 208/230 volt application
Simple MA Remote Controller (requires MAC-333IF-E
interface for MSY/Z and MFZ indoor units)
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-23
3-14. ACCESSORIES
(1) INDOOR UNIT cont.
Part Number
Descriptions
Applicable model
MPLS385812T-10
3/8 x 5/8 x 10' / 1/2" Twin-Tube Insulation
MPLS385812T-15
3/8 x 5/8 x 15' / 1/2" Twin-Tube Insulation
MPLS385812T-30
MPLS385812T-50
Diamondback
Linesets
3/8 x 5/8 x 30' / 1/2" Twin-Tube Insulation
All Models
3/8 x 5/8 x 50' / 1/2" Twin-Tube Insulation
MPLS385812T-65
3/8 x 5/8 x 65' / 1/2" Twin-Tube Insulation
MPLS385812T-100
3/8 x 5/8 x 100' / 1/2" Twin-Tube Insulation
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-24
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES
(2) OUTDOOR UNIT
Part Number
Descriptions
CWMB1
4 piece ( 1 pair) condensing unit wall mounting brackets painted steel
DSD-400P
Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic
MAC-811DS
ULTRILITE1
Applicable model
Outdoor drain pan socket - Provides pipe connection to route
All Models
condensate out of drain pan
Condensing Unit Mounting Pad 16” x 36” x 3”
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.
MSY-D-25
Due to continuing improvement, above specification may be subject to change without notice.
MSY-D-26
2013 M-Series - MSY-D Wall-Mount Systems (June 2013)
© 2013 Mitsubishi Electric US, Inc.