Split Sky Air

Split Sky Air
technical data
4-Way Blow
Ceiling Mounted Cassette
Split
Sky Air
air conditioning systems
FCQ-DAV3B
• Indoor Units • R-410A • FCQ-DAV3B
TABLE OF CONTENTS
FCQ-DAV3B
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional drawing
................................................. 5
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
7
9
Air flow pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• Split Sky Air • Indoor Units
1
• Indoor Units • R-410A • FCQ-DAV3B
1
t i y n k BU S 3 V r aAt o 0D i o 1- ld 4Q pnC- RFS•I
1
Features
Compact&stylish
•
•
Ideal for shops, restaurants or offices requiring maximum floor space
for furniture, decorations and fittings
The wired remote control provides you with a schedule timer,
enabling to program the air conditioning daily or weekly.
•
•
Fits flush into each ceiling
The optional remote ON/OFF enables you to start/stop the air
conditioning from a mobile phone via a telephone remote control
(field supply).
•
The optional forced OFF enables you to switch off the unit
automatically. E.g. when a window is opened, the unit switches off.
•
The ’home leave’ operation button prevents large temperature
differences by continuously operating at a minimum (heating mode)
or maximum (cooling mode) preset level while you’re out or sleeping.
It also allows the indoor temperature to return quickly to your
favourite comfort level.
•
Extremely quiet in operation
•
Air can be discharged in any of 4 directions
•
Possibility to shut 1 or 2 flaps for easy installation in corners or to use
1 or 2 branches
•
Air flow distribution for ceiling heights up to 4.2m without loss of
capacity.
•
Daikin remote controls give you easy control at your fingertips.
(heat pump)
(2 steps)
2
(optional)
(optional)
• Split Sky Air • Indoor Units
(twin
application
only)
(standard)
(optional)
• Indoor Units • R-410A • FCQ-DAV3B
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
Casing
Colour
Dimensions
Unit
Weight
Unit
Heat
Exchanger
Dimensions
Fan
Type
Air Flow Rate
Cooling
Fan
Motor
Sound Power
Sound
Pressure
Refrigerant
Type
Piping
connections
Liquid (OD)
Drain
Decoration
Panel
288
288
Width
mm
840
840
840
840
Depth
mm
840
840
840
840
kg
24.0
28.0
28.0
28.0
2
2
2
2
Fin Pitch
mm
1.20
1.20
1.20
1.20
Face
Area
m²
0.454
0.544
0.544
0.544
12
12
12
Nr of Rows
10
Type
2
Cross fin coil (Multi louver fins and Hi-XSS tubes)
Turbo fan
High
m³/min
19.0
30.0
30.0
30.0
Low
m³/min
14.0
21.0
24.0
25.0
QTS46F15M
QTS46E17M
QTS46E17M
QTS46E17M
30
120
120
120
Model
W
High
dBA
50.0
58.0
58.0
58.0
Low
dBA
44.0
48.0
51.0
53.0
High
dBA
34.0
43.0
43.0
43.0
Low
dBA
28.0
33.0
36.0
38.0
9.5
9.5
15.9
15.9
R-410A
Type
Flare connection
mm
9.5
9.5
Diameter
(OD)
mm
15.9
15.9
Diameter
(OD)
mm
Type
Flare connection
I.D. 25/O.D. 32
BYCP125DAW1
Colour
Weight
3
White
288
Model
Dimensions
FCQ140DAV3B
246
Diameter
(OD)
Gas
FCQ125DAV3B
mm
Output
(high)
Cooling
FCQ100DAV3B
Height
Nr of Stages
Fin
FCQ71DAV3B
White
H
mm
45
45
45
45
W
mm
950
950
950
950
D
mm
950
950
950
950
kg
5.5
5.5
5.5
5.5
Air Filter
Resin net with mold resistance
Safety Devices
Low pressure switch
Low pressure switch
Low pressure switch
High pressure switch
Fuse
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
In case of drain piping for the outdoor unit, a drain piping kit (option) is needed.
2-2
ELECTRICAL SPECIFICATIONS
Power Supply
FCQ71DAV3B
FCQ100DAV3B
1
1
Name
FCQ125DAV3B
FCQ140DAV3B
V3
Phase
1
1
Frequency
Hz
50
50
50
50
Voltage
V
230
230
230
230
• Split Sky Air • Indoor Units
3
• Indoor Units • R-410A • FCQ-DAV3B
3
Options
Item
Remark
FCQ∼D
71
Decoration panel
Fresh air intake kit
Replacement high effiency filter
Chamber type
KDD55DA160
With T-shape, without fan
KDD55DA16OK
KDDJ55XA160
(Colorimetric method 65%)
KAF556DA80
KAF556DA160
(Colorimetric method 90%)
KAF557DA80
KAF557DA160
(Colorimetric method 65%)
KAF552HA80
KAF552HA160
(Colorimetric method 90%)
KAF553HA80
KAF553HA160
Filter chamber
KDDF55DA160
Long life filter
KAF551CA160
Ultra-long life filter
KAF55DA160
Replacement ultra long-life filter
KAF55KA160H
Branch duct chamber
KDP55DA80
Chamber connection kit
Remote control
140
KDB55K160WA
Without T-shape and fan
Direct installation type
High efficiency filter
125
BYCP125DAW1
Panel spacer
3
100
KDP55DA160
KKSJ55KA160
Wired type
BRC1D528
Infrared type
BRC7EA51W
Central remote control
DCS302CA51
Unified ON/OFF control
DCS301BA51
Schedule timer
DST301BA51
Adapter for wiring
KRP1BA59 *1
Wiring adapter for electrical appendices (2)
KRP4AA53 *1
Installation box for adapter PCB
KRP1DA98
3D048828A
NOTE: *1: Installation box for adapter PCB (KRP1DA98) is necessary
4
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-DAV3B
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
FCQ71D
12-M4 Hole
860∼910 (Ceiling opening) (Note 4)
680 Suspension position
300 or less
Note 2
780 (Suspension position)
860∼890 (Ceiling opening) (Note 4)
Drain connection
side
Pipe connection side
Branch duct connection
4-M4 Hole
12-M4 Hole
Branch duct connection
Adjustable(0∼550)
C Arrow view
12-M4 Hole
4
B Arrow view
Outdoor air intake (direct connection)
D Arrow view
Branch duct
connection
12-M4 Hole
Required space
1500 mm or more *
1500 mm or more *
Decoration panel
BYCP125DJW1
White 10Y 9/0.5
Note:
1. Sticking location for manufacture’ s label
Manufacture’ s label for indoor unit: on the bell mouth inside suction
grille.
Manufacture’ s label for decoration panel: on the inner frame inside
suction grille.
2. In case of using an infrared remote control, this position will be a signal
receiver.
Refer to the drawing of infrared remote control in detail
3. When it may exceed 30°C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation (Thickness 10mm or
more of glasswool or polyethylene form) is required.
4. Though the installation is acceptable up to maximum of 910mm
square ceiling opening, keep the clearance of 35mm or less between
the main unit and the ceiling opening so that the panel overlap
allowance can be ensured.
1
2
3
4
5
6
7
8
1500 mm or more *
For height installation
35 or less
(Note 4)
Branch duct connection
1500 or more
35 or less
(Required space)
Suspension bolt
From the floor side 2500 or more
1500 mm or more *
* When the discharge grill is closed, the required
space is 200mm or more
Liquid pipe connection J9.5 Flare connection
Gas pipe connectionJ15.9 Flare connection
Drain pipe connection VP25 (O.D. J 32)
Power supply connection / wiring / remote control connection
Air outlet
Air suction grille
Corner decoration cover
3D033593B
Drain hose (option) O.D. J32 (outlet)
FCQ100∼140D
Note 2
300 or less
12-M4 Hole
860∼910 (Ceiling opening) (Note 4)
680 Suspension position
780 (Suspension position)
Pipe connection side
860∼890 (Ceiling opening) (Note 4)
Drain connection
side
Branch duct connection
B Arrow view
4-M4 Hole
12-M4 Hole
Adjustable(0∼550)
Branch duct connection
12-M4 Hole
C Arrow view
Branch duct
connection
Outdoor air intake (direct connection)
D Arrow view
12-M4 Hole
Required space
1500 mm or more *
1500 mm or more *
(Required space)
Decoration panel
BYCP125DJW1
White 10Y 9/0.5
Note:
1. Sticking location for manufacture’ s label
Manufacture’ s label for indoor unit: on the bell mouth inside suction
grille.
Manufacture’ s label for decoration panel: on the inner frame inside
suction grille.
2. In case of using an infrared remote control, this position will be a signal
receiver.
Refer to the drawing of infrared remote control in detail
3. When it may exceed 30°C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation (Thickness 10mm or
more of glasswool or polyethylene form) is required.
4. Though the installation is acceptable up to maximum of 910mm
square ceiling opening, keep the clearance of 35mm or less between
the main unit and the ceiling opening so that the panel overlap
allowance can be ensured.
• Split Sky Air • Indoor Units
1
2
3
4
5
6
7
8
From the floor side 2500 or more
For height installation
35 or less
(Note 4)
Branch duct connection
1500 or more
1500 mm or more *
35 or less
Suspension bolt
1500 mm or more *
* When the discharge grill is closed, the required
space is 200mm or more
Liquid pipe connection J9.5 Flare connection
Gas pipe connectionJ15.9 Flare connection
Drain pipe connection VP25 (O.D. J 32)
Power supply connection / wiring / remote control connection
Air outlet
Air suction grille
Corner decoration cover
3D048825A
Drain hose (option) O.D. J32 (outlet)
5
• Indoor Units • R-410A • FCQ-DAV3B
5
Piping diagram
FCQ-D
1
5
Heat exchanger
Model
FCQ71-100-125-140D
A
J9.52
B
J15.90
Field piping J A C1220T-O
To outdoor unit
Field piping J B C1220T-O
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
4D037995F
6
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-DAV3B
6
Wiring diagram
6-1
Wiring diagram
FCQ71-140D
Receiver / display unit
Notes
3
To outdoor unit
6
Note 5
Note 5
Note 2
Central remote
control
HO5VV-U4G2.5
Wired remote control
Simultaneous operation system
Indoor unit
(master)
Indoor unit
(slave)
To outdoor unit
1. In case using central remote control, connect it to the unit
in accordance with the attached installation manual.
2. Remote controller model varies according to the
combination system, confirm engineering data and
catalogs, etc. before connecting.
3. Confirm the method of setting the selector switch (SS1,
SS2) by installation manual and engeneering materials,
etc.
4. Ground the shield of the remote controller cord to the
indoor unit (in case of using shield wire). See technical
data and catalogues before connecting.
g Field wiring D Terminal
F
: Connector
h
: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black / WHT: White / RED: Red / YLW: Yellow
Switch box
(Indoor unit)
Remote control
A1P
A2P
A3P
HAP
KPR
M1F
M1P
M1S
R1T
R2T
Printed circuit board
(Power supply)
Printed circuit board
(Control)
Printed circuit board
(Humidity sensor unit)
Light emitting diode (service monitor green)
Magnetic relay (M1P)
Motor (indoor fan)
Motor (drain pump)
Motor (swing flap)
Thermistor (air)
Thermistor (coil)
S1L
Float switch
SS1
Selector switch (emergency)
X1M
Terminal strip (power)
X2M
Terminal strip (control)
PC
Power circuit
RC
Signal receiver circuit
TC
Signal transmission circuit
Z1C
Noise filter
Z2C
Noise filter
Wired remote control
R1T
Thermistor (air)
SS1
Selector switch (main/sub)
Receiver / display unit (attached to infrared remote control)
A4P,A5P Printed circuit board
BS1
Push button (on/off)
H1P
Light emitting diode (on-red)
H2P
Light emitting diode (timer-green)
H3P
Light emitting diode (filter sign-red)
H4P
Light emitting diode (defrost-orange)
SS1
Selector switch (main/sub)
SS2
Selector switch (wireless address set)
• Split Sky Air • Indoor Units
Connector for optional parts
X33A
Connector (adapter for wiring)
X35A
Connector (group control adapter)
3D048786A
7
• Indoor Units • R-410A • FCQ-DAV3B
6
Wiring diagram
6-2
External connection diagram
V3, Model
Power supply
1∼50Hz
230V
6
W1, Model
Power supply
1∼50Hz
220V-240V
Main switch
Main switch
Fuse
Fuse
H05VV-U4G
NOTES
1
2
3
4
5
6
7
8
9
8
Line voltage wiring
Control circuit wiring
All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.
Use copper conductors only.
See wiring diagrams for details.
Install fuse and mainswitch for safety.
All field wiring and components must be provided by a licensed electrician.
The unit shall be grounded in compliance with the applicable local and national codes.
Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific
installation.
Never share a common power supply with other equipment.
• Split Sky Air • Indoor Units
4D048881
• Indoor Units • R-410A • FCQ-DAV3B
7
Sound data
7-1
Sound pressure spectrum
FCQ100D
FCQ71D
High
Low
Octave band sound pressure level
dB:(0dB = 0.0002 µ bar)
Octave band sound pressure level
dB:(0dB = 0.0002 µ bar)
7
approximate threshold
hearing for continuous
noise
4D049024A
NOTES
1
2
3
Octave band center frequency (Hz)
4D049025A
NOTES
Location of microphone
1
2
3
High
Low
Octave band sound pressure level
dB:(0dB = 0.0002 µ bar)
Octave band sound pressure level
dB:(0dB = 0.0002 µ bar)
3
Location of microphone
FCQ140D
approximate threshold
hearing for continuous
noise
1
2
Octave band center frequency (Hz)
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
FCQ125D
NOTES
Low
approximate threshold
hearing for continuous
noise
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
4D049026A
High
High
Low
approximate threshold
hearing for continuous
noise
4D049027A
Octave band center frequency (Hz)
NOTES
Location of microphone
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
• Split Sky Air • Indoor Units
1
2
3
Octave band center frequency (Hz)
Location of microphone
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
9
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
FCQ71D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
8
FCQ71D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049080A
10
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
3
FCQ100D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
8
FCQ100D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049084A
• Split Sky Air • Indoor Units
11
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
FCQ125D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
8
FCQ125D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049082A
12
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
FCQ140D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
8
FCQ140D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049086A
• Split Sky Air • Indoor Units
13
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
FCQ71D
Heating - air velocity distribution
4-way discharge, air flow direction: down
8
FCQ71D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049081A
14
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
3
FCQ100D
Heating - air velocity distribution
4-way discharge, air flow direction: down
8
FCQ100D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049085A
• Split Sky Air • Indoor Units
15
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
FCQ125D
Heating - air velocity distribution
4-way discharge, air flow direction: down
8
FCQ125D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049083A
16
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-DAV3B
8
Air flow pattern
3
FCQ140D
Heating - air velocity distribution
4-way discharge, air flow direction: down
8
FCQ140D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049087A
• Split Sky Air • Indoor Units
17
Split - Sky Air
ISO14001 assures an effective environmental
management system in order to help protect
human•health•and the environment from the potential
impact of our activities, products and services and to
assist in maintaining and improving the quality of
the•environment.
Daikin units comply with the European
regulations that guarantee the safety of
the product.
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.
Daikin Europe N.V. is participating in the
EUROVENT Certification Programme.
Products are as listed in the EUROVENT
Directory of Certified Products.
EEDE06-1/3 • 05/2006
Prepared in Belgium by Lannoo
The present publication is drawn up by way of
information only and does not constitute an offer
binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this publication to the
best of its knowledge. No express or implied warranty
is given for the completeness, accuracy, reliability or
fitness for particular purpose of its content and the
products and services presented therein. Specifications
are subject to change without prior notice. Daikin
Europe N.V. explicitly rejects any liability for any direct
or indirect damage, In the broadest sense, arising from
or related to the use and/or interpretation of this
publication. All content is copyrighted by Daikin
Europe N.V..
Zandvoordestraat 300
B-8400 Ostend - Belgium
www.daikineurope.com
ÉEEDE06-1/3ÇËÍ