INSTALLATION
INSTRUCTIONS
SINGLE STAGE HEAT PUMPS
LOW VOLTAGE
CONTROL CIRCUIT WIRING
MODELS
W**H
W**H*D
S**H
S**H*D
T**H
T**H*D
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual :
Supersedes:
File:
Date:
2100-516H
2100-516G
Volume III Tab 16
03-28-14
Manual
Page
2100-516H
1 of 19
Contents
Installation Instructions
Wiring – Low Voltage Wiring...................................... 3
Operating Voltage Range........................................... 3
Low Voltage Connection............................................ 3
Wiring Diagram
Figure 11 Heat Pump w/CS2000A*......................... 15
Figures
Tables
Figure 1 Basic HP w/Opt. Elec. Heat...................... 5
Table 1
Diagram to Use w/Unit & Vents................. 3
Figure 2 HP w/Opt. MFAD, CRV & ERV Vent. Pkg. .
w/Programmable T-Stat............................ 6
Table 2
Operating Voltage Range.......................... 3
Table 3
Wall Thermostat........................................ 3
Figure 3
HP w/Opt. MFAD, CRV & ERV Vent. Pkg. .
w/Non-Programmable T-Stat..................... 7
Table 4
Humidity Controls...................................... 4
Table 5
CO2 Controller........................................... 4
Figure 4 HP w/Opt. MFAD, CRV & ERV Vent. Pkg. .
w/Non-Programmable Thermostat with ....
CO2 Controller..........................................8
Table 6
Thermostat Wire Size................................ 4
Figure 5 Heat Pump w/Opt. Economizer
"E" Vent Option......................................... 9
Figure 6 HP w/Dehumidification Sequence & No
Vent Pkg. Using T-Stat Comb................. 10
Figure 7 HP w/Dehumidification Sequence w/
Non-Programmable T-Stat.......................... 11
Figure 8 HP w/Dehumidification Sequence & Opt.
MFAD, CRV, & ERV Vent Pkg.
Using Elec. T-Stat with Combination
Temp. & Humidity Control....................... 12
Figure 9 HP w/Dehumidification Sequence & Opt.
MFAD, CRV & ERV Vent. Pkg.
Using Non-Prog. T-Stat.
(No Occupied Signal).............................. 13
Figure 10 HP w/Dehumidification Sequence & Opt.
MFAD, CRV & ERV Vent. Pkg.
Using Non-Prog. T-Stat. with
CO2 Controller......................................... 14
Figure 11 Heat Pump w/CS2000A*......................... 15
Figure 12 W**H1 Dehum. with Economizer and
#8403-060 Thermostat (EIFM)
"E" Vent Option....................................... 16
Figure 13 1-Stage HP w/Opt. Elec. Heat with or w/o .
.Dehum. with ECONWM* Style Economizer
"W" or "T" Vent Option............................ 17
Figure 14 HP w/Opt. CRVMP Vent Pkg. with
Programmable T-Stat.............................. 18
Figure 15 HP w/Opt. MFAD, CRV & ERV Vent Pkg. .
with Non-Programmable T-Stat............. 19
Manual 2100-516H
Page
2 of 19
TABLE 1
DIAGRAM TO USE WITH UNIT AND VENTS
System
Vent
None
CRV, ERV, MFAD
CRVMWH-3
CHCRV-5
EIFM
Economizer
ECONWM*
Vent Code
X
R, M, V, P
C
E
T, W, S
Thermostat
Programmable
Programmable
Programmable
Programmable
Programmable
CS2000A*
All
Model Series
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Heat Pump
S**H
T**H
W**H
1
1
3&4
2
15
14
N/A
5
N/A
13
11
Heat Pump with
Dehumidification
S**H*D
T**H*D
W**H*D
7
6
9 & 10
8
N/A
14
N/A
12
N/A
13
N/A
WIRING – LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary
voltage transformers. All equipment leaves the factory
wired on 240V tap. For 208V operation, reconnect
from 240V to 208V tap. The acceptable operating
voltage range for the 240V and 208V taps are:
TABLE 2
OPERATING VOLTAGE RANGE
TAP
RANGE
240V
253 – 216
208V
220 – 187
NOTE: The voltage should be measured at the field power
connection point in the unit and while the unit
is operating at full load (maximum amperage
operating condition).
An 18 gauge copper, color-coded thermostat cable is
recommended. The connection points are shown in this
Manual. See Table above.
Low Voltage Connection
These units use a grounded 24-volt AC low voltage
circuit.
“L” terminal is compressor lockout output. This
terminal is activated on a high or low pressure trip by the
electronic heat pump control. This is a 24 VAC output.
“W2” terminal is second stage heat (if equipped).
“O1” terminal is the ventilation input. This terminal
energizes any factory installed ventilation option.
“E” terminal is the emergency heat input. This terminal
energizes the emergency heat relay.
“W3” terminal is the dehumidification input. This
terminal energizes compressor, blower and three-way
valve.
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
Fan Only
Energize G
Cooling Mode
Energize Y, G
Heat Pump Heating
Energize Y, G, B
2nd Stage Heating
w/Heat Pump (if employed)
Energize G, W2, Y, B
Ventilation
Energize G, O1
Emergency Heat
Energize B, W2, E, G
Dehumidification
Energize W3
The “R” terminal is the hot terminal and the “C”
terminal is grounded.
TABLE 3
WALL THERMOSTAT
“G” terminal is the fan input.
“Y” terminal is the compressor input.
“B” terminal is the reversing valve input. The reversing
valve must be energized for heating mode.
“R” terminal is the 24 VAC hot.
Part Number
Predominate Features
2 stage Cool, 2 stage Heat - Conventional
8403-058
1 stage Cool, 2 stage Heat - Heat Pump
(TH5220D1151) Electronic Non-Programmable
Auto or Manual changeover
“C” terminal is the 24 VAC grounded.
8403-060
(1120-445)
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
Dehumidification Output
Manual 2100-516H
Page
3 of 19
TABLE 4
HUMIDITY CONTROLS
Part Number
8403-038
(H600A1014)
8403-047
(H200-10-21-10)
Predominate Features
SPDT switching, pilot duty 50VA @ 24V
Humidity range 20-80% RH
Electronic dehumidistat SPST closes-on-rise
Humidity range 10-90% with adjustable stops
TABLE 5
CO2 CONTROLLER
Part Number
Predominate Features
8403-067
Normally Open SPST relay closes-on-rise
24V dual wave length sensor. Default setting
950ppm, adjustable to 0-2000ppm
Default off setting 1000ppm, adjustable to
0-200 ppm can be calibrated
TABLE 6
THERMOSTAT WIRE SIZE
Transformer
VA
55
Manual 2100-516H
Page
4 of 19
FLA
Wire
Gauge
Maximum
Distance
In Feet
2.3
20 gauge
18 gauge
16 gauge
14 gauge
12 gauge
45
60
100
160
250
FIGURE 1
BASIC HEAT PUMP WITH OPTIONAL ELECTRIC HEAT
NO ECONOMIZER or VENTILATION PACKAGES
Low Voltage Wiring Diagram
Thermostat
#TH5220D1151
Bard part #8403-058
C
G
R
Rc
Y
O/B
Aux
L
1 Stage Cool
2 Stage Heat
E
1
Thermostat
Bard part #8403-060
C
G
R
24V Low Voltage
Terminal Block
C
G
R
"L" is constant 24V output when
thermostat is in Em Heat mode
Y1 O/B
Y1
Y
B
W2
Y O/D W1/E
W1 W2 W3
1
E
L
Y2
A
L
DH O1
Electronic
Programmable
Unit
1 Factory Jumper Installed
MIS-2645 C
Manual 2100-516H
Page
5 of 19
FIGURE 2
HEAT PUMP WITH OPTIONAL MFAD, CRV & ERV
VENTILATION PACKAGING WITH PROGRAMMABLE THERMOSTAT (RECOMMENDED)
Figure 2
4
Heat Pump with Optional MFAD, CRV, and ERV
Ventilation Packaging with Programmable Thermostat (Recommended)
Low Voltage Wiring Diagram
Thermostat
Bard part #8403-060
C
G
R
Y1
Y2 W1/E W2 O/B
L
Y O/D
1
2
3
4
5
A
Electronic
Programmable
Optional CO2 Controller
Bard part #8403-067
6
2
24V Low Voltage
Terminal Block
C
G
3
Black
R
Y
Orange
Y1
E
B
CRV
ERV
L
O1
Brown/White
Ventilation Packages
MFAD
1 Factory Jumper Installed
2 Do not connect "A" from tstat #8403-060
if optional CO2 controller is used.
Connect orange wire to "G" only if
3 optional CO controller is used.
2
Must be configured to programmable and fan
4 set to programmed for the "A" output to function
during scheduled occupied periods
Manual 2100-516H
Page
6 of 19
W1 W3 DH
1
Red
Black
W2
Red
MIS-2633 C
Unit
FIGURE 3
HEAT PUMP WITH OPTIONAL MFAD, CRV and ERV VENTILATION
PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL)
Low Voltage Wiring Diagram
Thermostat
#TH5220D1151
Bard part #8403-058
C
G
R
Rc
E
Y
AUX
O/B
1 Stage Cool
2 Stage Heat
L
1
24V Low Voltage
Terminal Block
C
G
R
"L" is constant 24V output when
thermostat is in Em Heat mode
Y
Y1
E
W2
B
W1 W3
1
3
Black
Black
MIS-2646 C
Orange
Red
CRV
ERV
MFAD
Ventilation
Packages
L
DH O1
Unit
2
Brown/White
Red
1
Factory Jumper Installed
2
Add jumper, ventilation will be active
whenever blower operates.
3
Do not connect orange wire.
Manual 2100-516H
Page
7 of 19
FIGURE 4
HEAT PUMP WITH OPTIONAL MFAD, CRV and ERV VENTILATION
PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT WITH CO2 CONTROLLER
"L" is constant 24V output when
thermostat is in Em Heat mode
Low Voltage Wiring Diagram
Thermostat
#TH5220D1151
Bard part #8403-058
C
G
R
Rc
Y
E
AUX
L
O/B
1 Stage Cool
2 Stage Heat
1
2
1
24V Low Voltage
Terminal Block
C
G
2
Black
R
Y1
Orange
Y
W2
1 Factory Jumper Installed
Connect orange wire to "G"
2 only if optional CO2 controller
is used.
B
4
W1 W3 DH
5
Optional CO2 Controller
Bard part #8403-067
6
O1
L
Unit
1
Red
Black
Manual 2100-516H
Page
8 of 19
E
3
CRV
ERV
Brown/White
Ventilation Packages
MFAD
Red
MIS-2634 E
FIGURE 5
HEAT PUMP WITH OPTIONAL EIFM ECONOMIZER
“E” VENT OPTION
Figure 5
Heat Pump with Optional Economizer
Low Voltage Wiring Diagram
Thermostat
Bard part #8403-060
C
R
O/B
24V Low Voltage
Terminal Block
C
R
B
W1
W1/E
W2
L
G
E
W2
L
G
A
Y
Y1 YO/D
Y1 DH O1 W3
1
Pink
Yellow
F
Orange
E
Black
1
Blue
Black
Y2
Y1
2 Stage Cool
2 Stage Heat
Unit
Purple
2
3
MIS-2648 C
Economizer
Wiring Harness
1 Factory Jumper Installed.
Must be configured for economizer with YO/D output to
2 be active as first stage cooling.
3 These wires are used in special control applications only.
Manual 2100-516H
Page
9 of 19
FIGURE 6
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE AND NO VENTILATION PACKAGE
USING THERMOSTAT #8403-060 COMBINATION TEMPERATURE & HUMIDITY CONTROLLER
Figure 6
Heat Pump with Dehumidification Sequence and No Ventilation Package
using Thermostat part #8403-060 Combination Temperature and Humidity Controller.
Low Voltage Wiring Diagram
2
Thermostat
Bard part #8403-060
C
G
R
Y1
C
G
R
Y1
W1/E
Y2
W2 YO/D O/B
L
A
L
O1
Electronic
Programmable
MIS-2636 A
24V Low Voltage
Terminal Block
Y
E
1
W1 W2 W3
B
DH
Unit
1 Factory Jumper Installed.
2 Must be configured for "No economizer"
for YO/D to be active for humidity control
Manual 2100-516H
Page
10 of 19
FIGURE 7
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE
WITH NON-PROGRAMMABLE THERMOSTAT
Low Voltage Wiring Diagram
Thermostat
#TH5220D1151
Bard part #8403-058
C
G
R
Rc
E
Y
AUX
O/B
L
1
24V Low Voltage
Terminal Block
C
G
R
1 Stage Cool
2 Stage Heat
"L" is constant 24V output when
thermostat is in Em Heat mode
Y
Y1
E
W2
B
W1 W3
L
DH O1
Unit
1
2
Electronic Humidistat
Bard part #8403-047
Mechanical Humidistat
Bard part #8403-038
6
5
3
Red
4
1 Factory Jumper Installed.
Yellow
2 Jumper needs to be added.
MIS-2649 B
Manual 2100-516H
Page
11 of 19
FIGURE 8
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION
PACKAGING USING ELECTRONIC THERMOSTAT WITH COMBINATION TEMPERATURE &
HUMIDITY CONTROL WITH OPTIONAL CO2 CONTROLLER
Figure 8
Heat Pump with Dehumidification Sequence and Optional MFAD, CRV, and ERV Ventilation
Packaging using Electronic Thermostat with Combination Temperature and Humidity Control
with Optional CO 2 Controller
2
Thermostat
Bard part
#8403-060
Low Voltage Wiring Diagram
C
G
R
Y1
Y2 O/B W2 YO/D
A
W1/E
2 Stage
Cool
2 Stage
Heat
L
3
1
24V Low
Voltage
Terminal
Block
C
G
R
Y1
Y
B
W2 W3 W1
2
3
4
DH
5
6
Optional CO2 Controller
Bard part #8403-067
O1
E
L
1
3
Black
Black
Orange
Red
CRV
Brown/White
ERV
Ventilation Packages
MFAD
1 Factory Jumper Installed
Must be configured to "no economizer" to make YO/D output
2 active for humidity control. Must be configured to programmable
and fan set to programmed fan for the "A" output to function
during scheduled occupied periods.
2
Do not connect "A" from thermostat if optional CO
3 controller is used. Connect orange wire to "G" only
when optinal CO 2 controller is used.
Manual 2100-516H
Page
12 of 19
Red
MIS-2637 C
Unit
FIGURE 9
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION
PACKAGING USING A NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL)
Low Voltage Wiring Diagram
Thermostat
Bard part #8403-058
C
G
R
Rc
E
Y
AUX
L
O/B
1
24V Low Voltage
Terminal Block
C
G
R
Y1
1 Stage Cool
2 Stage Heat
"L" is constant 24V output when
thermostat is in Em Heat mode
Y
E
W2
B
W1 W3 DH O1
L
Unit
1
Red
Orange CRV
ERV
Black
2
Brown/White
Ventilation
Packages
MFAD
RED
4
Black
1 Factory Jumper Installed.
3
Electronic Humidistat
Bard part #8403-047
6
5
3
Red
2 Add jumper, ventilation will be
active whenever blower operates.
4
3 Jumper needs to be added.
Yellow
4 Orange wire is not connected.
Mechanical Humidistat
Bard part #8403-038
MIS-2638 C
Manual 2100-516H
Page
13 of 19
FIGURE 10
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION
PACKAGING USING A NON-PROGRAMMABLE THERMOSTAT WITH CO2 CONTROLLER
"L" is constant 24V output when
thermostat is in Em Heat mode
Low Voltage Wiring Diagram
C
G
R
Rc
Thermostat
#TH5220D1151
Bard part #8403-058
Y
AUX
E
O/B
1 Stage
Cool
2 Stage
Heat
L
1
1
2
3
4
5
6
Optional CO2 Controller
Bard part #8403-067
24V Low Voltage
Terminal Block
C
G
R
Y1
Y
W2
B
W1 W3 DH
O1
E
L
1
Red
Orange CRV
ERV
3
Black
MFAD
Black
Brown/White
Ventilation
Packages
1 Factory Jumper Installed.
2
Electronic Humidistat
Bard part #8403-047
6
5
3
Red
2 Jumper needs to be added.
4
Yellow
Mechanical Humidistat
Bard part #8403-038
Manual 2100-516H
Page
14 of 19
Red
3 Connect Orange wire to "G".
MIS-2639 E
Unit
FIGURE 11
HEAT PUMP WITH CS2000A2
Figure 11
HP WITH CS2000
WH/SH HEAT PUMP CONNECTION DIAGRAM
DO NOT CONNECT "L" UNTIL AFTER
8403-060 CONTROLLER IS CONFIGURED
TO CS2000 = YES
TEMPERATURE/HUMIDITY
CONTROLLER BARD P/N 8403-060
YELLOW
G
C
R
O/B
Y1
W2
L
W1/E
1
THERMOSTAT TH5220D1151
BARD P/N 8403-058
IF OPTIONAL VENT PACKAGE IS
INSTALLED, THE "G" WIRE MUST
BE CONNECTED TO ASSURE
CONTINUOUS BLOWER DURING
OCCUPIED PERIODS WHEN VENT
SYSTEM IS "ON". THE "G" WIRE
MUST ALSO BE CONNECTED
FOR PRE-PURGE OPERATION
(SEE STEP 2, FUNCTION SWITCH
SETTINGS).
BARD VENTILATION
PACKAGE (OPTIONAL)
NOTE: IF FACTORY INSTALLED
DISCONNECT AND TAPE RED
AND ORANGE WIRES
R
G
C
Aux
O/B
Y
L
E
BLUE
RED
RC
R
6
1
01
C
R
G
Y
Y1
W1 W2
B
5
L
E
8403-047
H200-10-21-10
DEHUMIDSTAT
UNIT 24V
TERMINALS
HUMIDITY CONTROLLER
CONNECTIONS USED ONLY
FOR OPTIONAL DEHUMIDIFICATION
CIRCUIT THAT MUST BE FACTORY
INSTALLED IN HEAT PUMP
NC C
NO C
VENT
BR/W
OPTIONAL
LIGHTING
CONTROL
NC
PWR
C
NC
HVAC FAN
FACTORY JUMPER - SEE
SEARCH TIME DETAIL
ON PAGE 3
AREA OCCUP. REM
+
NO C NC -
LIGHTING CONTROL
RELAY NORMALLY
CLOSED CONTACTS
LIGHTS
3
1
BK
WERV
OR
CRV
MANUAL SWITCH
FIELD SUPPLIED
4
W3
O
2
8403-038
H600A1014
HUMIDITY
CONTROLLER
YO/D
+
-
+
PWR PRECOND DOOR
NO C NC
HVAC
MAN.
OVERIDE
(24 HRS)
REMOTE
MOTION
DETECTOR
(OPTIONAL)
NORMALLY
OPEN
CONTACTS
CS2000A2
ENERGY MONITOR
1
JUMPER IS FACTORY INSTALLED.
2
LIGHTING CONTROL CIRCUIT
IS OPTIONAL AND FIELD
SUPPLIED. LIGHTING CONTROL
RELAY REQUIRES NORMALLY
CLOSED CONTACTS AND MUST
BE SIZED ACCORDING TO
CONTROLLED LOAD.
RECOMMENDED SWITCH SETTINGS SHOWN BELOW
FUNCTION SWITCHES
LEARN
PRE P
MODE
RATE
SEARCH-TIME
N/C
STAGE
AUX
DEMAND 2
DEMAND 1
TEMPERATURE SWITCHES
90
84
81
78
68
65
62
58
54
48
4093-140 L
Manual 2100-516H
Page
15 of 19
FIGURE 12
W**H1 DEHUM. WITH ECONOMIZER
& #8403-060 THERMOSTAT (EIFM)
“E” VENT OPTION
W**H1 Dehum. with Econ.
and #8403-060 Thermostat
Green
Red
White
Brown
C
G
R
E
W2
Orange
L
O/B
YOD
L
W1 O/B
Y2 Y1
Light Blue
W2
Y
Y1 W3
Light Blue
W1E
Blue
R
Orange
G
Black
WH Unit
Low Voltage
Term. Strip
C
Black
Thermostat Part #8403-060*
Yellow
Y2
Blue
! DANGER
*ELECTRICAL SHOCK HAZARD
*DISCONNECT POWER BEFORE
SERVICING.
F
Purple
2
4
5
6
1
3
RELAYS AND
ASSOCIATED WIRING
ARE FIELD INSTALLED
2
4
5
6
1
3
Dehum. Relay
Part #8201-062
E
Pink
Heat Relay
Part #8201-062
Black
Blue
Economizer
Vent Option
Y1
*Thermostat Model Configuration Notes:
1.) Configured for "Heat Pump"
2.) Configured for "Multi-Stage"
3.) Configured for "No Economizer"
4.) Configured CS2000A Attached = NO
4200-001 B
Manual 2100-516H
Page
16 of 19
FIGURE 13
1-STAGE HEAT PUMP WITH OPTIONAL ELECTRIC HEAT
WITH OR WITHOUT DEHUMIDIFICATION
WITH ECONWM STYLE ECONOMIZER
“W” OR “T” VENT OPTION
C
R
B
Black
Red
W1
W2
L
G
E
W2
L
G
A
Y
Brown/white
3
Economizer
Wiring Harness
YO/D
Y2
Y1
Purple
24V Low Voltage
Terminal Block
W1/E
Y1 DH O1 W3
Yellow/red
O/B
Yellow
R
1
Orange
C
Blue
Thermostat
part #8403-060
Pink
Low Voltage Wiring Diagram
2
Yellow/White
1
Must be energized to enable minimum position. NOTE: Economizer Control Default Setting
is 10V (100%). Depending upon application may require setting to lower value.
2
Must be configured for heat pump / multistage/ no economizer/
to enable YO/D output to be active as dehumidification output
3
Factory Jumper Installed.
MIS-2981 B
Manual 2100-516H
Page
17 of 19
FIGURE 14
HEAT PUMP WITH OPTIONAL CRVMWH-3 OR CHCRV-5
VENTILATION PACKAGING WITH PROGRAMMABLE THERMOSTAT (RECOMMENDED)
Low Voltage Wiring Diagram
4
Thermostat
Bard part #8403-060
C
G
R
Y1 Y2 W1/E W2 O/B
L
Y O/D
A
Electronic
Programmable
3
1
2
3
4
5
Optional CO2 Controller
Bard part #8403-067
6
2
24V Low Voltage
Terminal Block
C
G
Black
1 Factory Jumper Installed
R
Y
E
Y1
Yellow
Red
B
W1 W3 DH
3 Wire only needed for dehumidification units
Must be configured to programmable and fan
4 set to programmed for the "A" output to function
during scheduled occupied periods
L
O1
Unit
1
Orange
CHCRV-5
OR
CRVMWH-3 Ventilation
Package
2 Do not connect "A" from tstat #8403-060
if optional CO2 controller is used.
Manual 2100-516H
Page
18 of 19
W2
MIS-2997 C
FIGURE 15
HEAT PUMP WITH OPTIONAL CRVMWH-3 OR CHCRV-5 VENTILATION
PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL)
Low Voltage Wiring Diagram
Thermostat
#TH5220D1151
Bard part #8403-058
C
G
R
Rc
Y
E
AUX
O/B
E
W2
B
1 Stage Cool
2 Stage Heat
L
1
24V Low Voltage
Terminal Block
C
G
R
Y
Y1
Yellow
W1 W3
1
L
DH O1
Unit
2
Red
Black
MIS-2998 A
CHCRV-5
OR
CRVMWH-3
Orange
Ventilation
Package
1
Factory Jumper Installed
2
Add jumper, ventilation will be active
whenever blower operates.
Manual 2100-516H
Page
19 of 19