2408 2404
MODELS
Programmer/Controllers
Product data
• High stability control
• Up to twenty programs
• 16 ramp/dwell segments
• Heating and cooling
• Motorised Valve output
• Customised operation
• Load diagnostics
• Heater current display
• Multiple alarms on a single output
• One-shot tuner with overshoot inhibition
• 24V Supply option
• Auto/manual button
• DC retransmission
• 10amp output (2404 only)
• Transmitter supply
• Transducer supply
• PDSIO master setpoint retransmission or setpoint input
• Digital communications
• Plug-in from front
• Compliant with
European EMC and low voltage safety directives
• 3 Year warranty
Features
The 2404/2408 is a versatile, high stability temperature or process controller, with self and adaptive tuning, in 1/4 DIN and 1/8 DIN sizes. It comes with a standard 8 segment setpoint programmer, with options for one, four or twenty programs of 16 segments each.
It has a modular hardware construction which accommodates a wide range of plug-in modules. It will accept up to three I/O modules and two communication modules. Two
Digital inputs and an optional alarm relay are included as part of the fixed hardware build. The hardware is configurable for heating, cooling, alarms and other functions. A transmitter power supply option is available, as is a 5 or 10V transducer supply option.
The 2404/2408 is fully configurable on-site.
The programmer can have up to 8 programmable outputs which can be set in each segment to trigger external events. The two digital inputs can be used to run, hold and reset the program. Parallel operation of several programmers can be performed with synchronisation chosen at the end of any desired segments.
Precise control
An advanced PID control algorithm gives stable ‘Straight-line’ control of the process. A one-shot tuner is provided to set up the initial PID values and to calculate the overshoot inhibition parameters. In addition an adaptive tuner will handle processes with continually changing characteristics. On electrically heated loads, power feedback is used to stabilise the output power and hence the controlled temperature against supply voltage fluctuations. Dedicated cooling algorithms ensure optimum control of fan, water and oil cooled systems.
Universal input
A universal input circuit with an advanced analogue to digital convertor samples the input at 9Hz and continuously corrects it for drift. This gives high stability and rapid response to process changes. High noise immunity is achieved by rejection of 50/60Hz pick-up and other sources of noise. Sensor diagnostics are also provided. The input will accept all standard thermocouples, the Pt100 resistance thermometer and linear millivolts, milliamps or DC volts.
Input filtering from OFF to 999.9 seconds is included.
Customised operation
A custom LED display provides a bright, clear display of the process value and setpoint.
Tactile push buttons ensure positive operation. Access to other parameters is simple and easy to understand and can be customised to present only those parameters that need to be viewed or adjusted. All other parameters are locked away under password protection.
A front panel auto/manual button is provided.
Alarms
Up to four process alarms can be combined onto a single output. They can be full scale high or low, deviation from setpoint, rate of change or load failure alarms. Alarm messages are flashed on the main display. Alarms can be configured as latching or non-latching and also as ‘blocking’ type alarms which means that they will become active only after they have first entered a safe state.
Digital communications
Available with either EIA485 2 wire, 4 wire or EIA232. With industry-standard protocols including: Modbus®, Eurotherm Bisync, and SPI.
PDSIO Load diagnostic
OP1 OP2
2404
SP2 REM
(PDS Heater Break Detect)
PDSIO 2-wire
Connection
TE10 solid state relay
Supply
Heater
PDSIO Load diagnostics
PDSIO (Pulse Density Signalling I/O) is a major innovation in the
2404/2408. When used in combination with a Eurotherm
TE10 solid state relay (SSR), it allows the logic output of a
2404/2408 to transmit the power demand signal and simultaneously read back load fault alarms.
These alarms will be flashed as messages on the controller front panel.
Two alarm conditions will be detected, either SSR failure indicating an open or short circuit condition in the SSR and heater circuit failure indicating either fuse failure, heater open circuit or line supply absent.
PDSIO Setpoint transmission
Master Setpoint
Generator
2404
OP1 OP2
SP2 REM
(PDS Output)
PDSIO Master
Setpoint Transmission
OP1 OP2
2408
Slave Controllers
OP1 OP2
2408
PDSIO master setpoint transmission
PDSIO can be used to digitally transmit the setpoint profile to a number of slave Series 2000 controllers.
If any slave zone departs from the required setpoint by more than a pre-settable amount, a signal from any slave can be transmitted back to the master causing the program to freeze until the error is corrected. Digital accuracy is preserved using PDSIO.
SP2 REM
(PDS Input)
SP2 REM
(PDS Input)
Technical specification
Process inputs
General
Thermocouple
RTD/PT100
Process
Range
Sample rate
Calibration accuracy
Resolution
± 100mV and 0 to 10Vdc (auto ranging)
9Hz (110mS)
0.2% of reading, ±1 LSD or ±1°C/F
<1.6µV for ± 100mV range, <0.2mV for 10Vdc range
Linearisation accuracy No discernable error
Zero drift with ambient temperature < 0.1µV per °C for ±100mV range, 0.1mV per °C on 10Vdc range
Gain drift with ambient temperature < 0.004% of reading per °C
Input filter OFF to 999.9secs
Zero and span offset
Types
Cold junction compensation
Type
Bulb current
Lead compensation
Range
Type
Application
User adjustable over the full display range
See sensor inputs table
Automatic compensation typically >30 to 1 rejection of ambient temperature change
External references 0, 45 and 50°C
3-wire, Pt100
0.2mA
No error for up to 22 ohms balanced in all 3 leads
±100mV, 0 to 20mA or 0 to 10Vdc (All configurable between limits)
Linear, Square root or custom 8 point
Process value, remote setpoint, setpoint trim, power limit. Value pos. slidewire
330
Ω to 15Kohm
Digital inputs
Type
Application
Single and triple input: Contact closure or 24Vdc logic input
Manual select, 2nd setpoint, 2nd PID, keylock, setpoint rate limit enable,
Program run, hold, reset, synchronisation and fast run
Outputs
Relay
Logic
Triac
High Current
Analogue
Transmitter supply
Transducer supply
Rating: 2-pin relay Min: 12V, 100mA dc. Max: 2A, 264Vac resistive (single and dual modules available)
Rating: change-over, alarm relays Min: 6V, 1mA dc. Max: 2A, 264Vac resistive
Application Heating, cooling, alarms or program event
Rating
Application
18Vdc at 24mA (isolated and non-isolated versions available)
Heating, cooling, alarms or program event
PDSIO mode 1: Logic heating with load failure alarm
PDSIO mode 2: Logic heating with load/SSR failure alarm and load current
Rating
Application
Rating
Application
Range
Application
Rating
Voltage
Bridge resistance
Internal shunt resistance display
1A, 30 to 264Vac resistive (single and dual modules available)
Heating, cooling or program event
10amp, 264Vac resistive
Heating (2404 only)
0 to 20mA (into 600
Ω max) or 0 to 10Vdc (Isolated and non-isolated versions available)
Heating or cooling or process output. PV retransmission or setpoint retransmission
24Vdc at 20mA
5 or 10Vdc
300
Ω to 10k
Ω
30.1k
Ω at 25%, used for calibration of 350
Ω bridge
Communications
Digital
PDSIO
Transmission standard
Protocols
Setpoint input
Setpoint output
Update time
EIA 485 or EIA232 at 1200, 2400, 4800, 9600, 19,200 baud
Modbus® or Eurotherm Bisync or DeviceNet
Setpoint input from master PDSIO controller. Holdback to master controller
Master setpoint retransmission to slave PDSIO controllers
500mS
Control functions
Control
Tuning
Alarms
Modes
Application
Auto/manual
Setpoint rate limit
Cooling algorithms
One-shot tune
Adaptive Tune
Automatic droop compensation
Types
Modes
PID or PI with overshoot inhibition, PD, P only or On/Off
Heating, cooling or process output
Bumpless transfer or forced manual output
OFF to 999.9 degrees or display units per second, minute or hour
Linear; Water (non-linear); Fan (minimum on time), Oil and proportional only
Automatic calculation of PID and overshoot inhibition parameters
Continuous assessment of the PID values
Automatic calculation of manual reset value when using PD control
Full scale high or low. Deviation high, low, or band. Rate of change
Latching or non-latching. Normal or blocking action
Up to four process alarms can be combined onto a single output
Programmer parameters
Programs
Segments
Ramp
Dwell
Holdback
End Segment
Cycles
Event outputs
Timing accuracy
General
Display
Dimensions & weight
Supply
Temperature and RH
Panel sealing
Electromagnetic compatibility
Safety standards
Atmospheres
One, up to four or up to twenty programs
16 segments per program
Ramp Rate or Time to Target
Hours, Minutes or Seconds ( 0.1 to 999.9 )
Hours, Minutes or Seconds ( 0.0 to 999.9 )
Per Program or per Segment ( 0.0 to 999.9 )
Dwell, Reset or Set output level
Continuous or 1 to 999
Up to eight – relay, logic or triac
±2% of duration
Dual, 4 digit x 7 segment high intensity LED
96W x 96H x 150D mm. 600g
85 to 264Vac, 48 to 62Hz. 10watts max (or 20 to 29Vac or dc)
Operating: 0 to 55°C, RH: 5 to 95% non-condensing. Storage: -10 to 70°C
IP65
Meets generic emissions standard EN50081-2 for industrial environments
Meets general immunity requirements of EN50082-2(95) for industrial environments
EN61010, installation category 2. (voltage transients must not exceed 2.5kV)
Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not suitable for use above 2000m or in corrosive or explosive atmospheres without further protection.
Ordering information
Hardware coding
Model
Number
Function
Supply
Voltage
Module 1 Module 2 Module 3
Alarm
Relay
10amp
Output
Omit for 2408
Comms 1 Comms 2 Manual
Model Number
Panel size
2408 48 x 96mm
2404 96 x 96mm
Profibus units
2408f 48 x 96mm
2404f 96 x 96mm
Function (2408)
PID control
CC Controller only
CG 1x 8 seg Prog
CP 1x16 seg Prog
P4 4x16 seg Prog
CM 20x16 seg Prog (note 1)
On/Off Control
NF Controller only
NG 1x8 seg Prog
NP 1x16 seg Prog
N4 4x16 seg Prog
NM 20x16 seg Prog (note 1)
Motorised valve control
VC Valve positioner
VG 1x8 seg Prog
VP 1x16 seg Prog
V4 4x16 seg Prog
VM 20x16 seg Prog
(note 1)
Function (2404)
PID control
CC Controller only
CG 1x 8 seg Prog
CP 1x16 seg Prog
P4 4x16 seg Prog
CM 20x16 seg Prog (note 1)
On/Off Control
NF Controller only
NG 1x8 seg Prog
NP 1x16 seg Prog
N4 4x16 seg Prog
NM 20x16 seg Prog (note 1)
Motorised valve control
VC Valve positioner
VG 1x8 seg Prog
VP 1x16 seg Prog
V4 4x16 seg Prog
VM 20x16 seg Prog
(note 1)
Supply Voltage
VH 85-264Vac
VL 20-29Vac/dc
Module 1
XX Not fitted
Relay: 2-pin
R2 Fitted unconfigured
RH Heating output
RU Valve raise output
Relay: change over
R4 Fitted unconfigured
YH Heating output
RP Valve raise (note 6)
Or alarm 1 from table A
Logic: (Non-isolated)
L2 Fitted unconfigured
LH Heating output
M1 PDS Heater break detect (note 2)
M2 PDS Current monitoring (note 3)
Logic: (Isolated)
LO Single logic OP
Triac
T2 Fitted unconfigured
TH Heating output
TU Valve raise output
DC control (Isolated)
D4 Fitted unconfigured
H6 0-20mA PID heating
H7 4-20mA PID heating
H8 0-5V PID heating
H9 1-5V PID heating
HZ 0-10V PID heating
Digital I/O (unconfig’d)
TK Triple contact input
TL Triple logic input
TP Triple logic output
Dual relay
RR Fitted unconfigured
RD Heat + cool
RM VP raise & lower OPs
Dual triac
TT Fitted unconfigured
TD Heat + cool
TM VP raise & lower OPs
Logic+relay
LR Fitted unconfigured
LD Heat + cool
QC Mode 2 + cool
Logic+triac
LT Fitted unconfigured
GD Heat & cool
QD Mode 2 + cool
Transducer PS
G3 5Vdc transducer PSU
G5 10Vdc transducer PSU
Table A: alarm codes
FH High alarm
FL Low alarm
DB Dev. band alarm
DL Dev. low alarm
DH Dev. high alarm
Module 2
XX Not fitted
Relay: 2-pin
R2 Fitted unconfigured
RC Cooling output
RW Valve lower output
Relay: change over
R4 Fitted unconfigured
YC Cooling output
RL Valve lower (note 6)
PO Program event 1
(note 7)
PE Program END output
Or alarm 2 from table A
Dual relay
RR Fitted unconfigured
PP Program events 1 & 2
(note 7)
Logic: (Non-isolated)
L2 Fitted unconfigured
LC Cooling output
Logic: (Isolated)
LO Single logic OP
Triac
T2 Fitted unconfigured
TC Cooling output
TW Valve lower output
DC control (Isolated)
D4 Fitted unconfigured
C6 0-20mA PID cooling
C7 4-20mA PID cooling
C8 0-5V PID cooling
C9 1-5V PID cooling
CZ 0-10V PID cooling
Digital I/O (unconfig’d)
TK Triple contact input
TL Triple logic input
TP Triple logic output
Power supply
MS 24Vdc transmitter
DC retran. (Isolated)
Select from Table B
Potentiometer input
VU Fitted unconfigured
VS Valve position feedback
VR Setpoint input
Transducer PS
G3 5V transducer PSU
G5 10V transducer PSU
Table B: DC retransmission
D6 Fitted unconfigured
First character
V- PV retrans
SSetpoint retrans
O- Output retrans
ZError retrans
Second character
-1 0-20mA
-2 4-20mA
-3 0-5V
-4 1-5V
-5 0-10V
Module 3
XX Not fitted
Relay: 2-pin
R2 Fitted unconfigured
Relay: change over
R4 Fitted unconfigured
PO Program event 4
(not e 7)
PE Program END output
Or alarm 3 from table A
Logic (Non-isolated)
L2 Fitted unconfigured
Logic: (Isolated)
LO Single logic OP
Triac
T2 Fitted unconfigured
Dual relay
RR Fitted unconfigured
PP Program event 4 & 5
(note 7)
Digital I/O (unconfig’d)
TK Triple contact input
TL Triple logic input
TP Triple logic output
Power supply
MS 24Vdc transmitter
DC remote input
D5 Fitted unconfigured
W2 4-20mA setpoint
W5 0-10V setpoint
WP Second PV input
DC retran. (Isolated)
Select from Table B
Potentiometer input
VU Fitted unconfigured
VS Valve position feedback
VR Setpoint input
Transducer supply
G3 5V transducer PSU
G5 10V transducer PSU
Alarm Relay
XX Not fitted
Alarm 4 relay
RF Fitted unconfigured
Table A alarm options plus:
RA Rate of change alarm
PDS Alarms
LF Heater break detect
HF Current monitoring heater break
SF Current monitoring
SSR failure
PO Program event 7
(note 7)
PE Program END output
10amp Output
XX Not fitted
R6 Fitted unconfigured.
RH Heating
Comms 1
XX Not fitted
2 wire, RS485
Y2 Fitted unconfigured
YM Modbus protocol
YE EI-Bisync protocol
(note 1)
RS232
A2 Fitted unconfigured
AM Modbus protocol
AE EI-Bisync protocol
(note 1)
4 wire RS422
F2 Fitted unconfigured
FM Modbus protocol
FE EI-Bisync protocol
(note 1)
PDS Output
M7 Fitted unconfigured
PT PV retrans
TS Setpoint retrans
OT Output retrans
Profibus Module
PB High speed RS485
DeviceNet
DN DeviceNet
Comms 2
XX Not fitted
PDS Input
M6 Fitted unconfigured
RS Setpoint input
PDS Output
M7 Fitted unconfigured
PT PV retrans
TS Setpoint retrans
OT Output retrans
Manual
XXX No manual
ENG English
FRA French
GER German
NED Dutch
SPA Spanish
SWE Swedish
ITA Italian
Note 1.
Not available with profibus controllers
Note 2.
PDS heater break detect will transmit the power demand to a TE10S Solid State Relay and read back a heater break alarm.
Note 3.
PDS current monitoring will transmit the power demand signal to a TE10S Solid State Relay and read back load current and open and short circuit alarms.
Note 4.
Setpoint limits: Include the decimal position required in the displayed value. Up to one for temperature inputs, up to two for process inputs.
Configuration coding (optional)
Sensor
Input
Setpoint
Min note 4
Setpoint
Max note 4
Display
Units
Digital
Input 1
Digital
Input 2 Control Power
Options
Cooling Buttons Program
Sensor Input
Standard Sensor Inputs
J J Thermocouple
K K Thermocouple
T T Thermocouple
L L Thermocouple
N N Thermocouple-Nicrosil/Nisil
R R Thermocouple-Pt/Pt13%Rh
S S Thermocouple-Pt /Pt10%Rh
B B Thermocouple-Pt/Pt30%Rh -6%Rh
P Platinel II Thermocouple
Z RTD/PT100 DIN 43760
Factory downloaded input
C C Thermocouple - W5%Re/W26%Re (Hoskins)
D D Thermocouple - W3%Re/W25%Re
E E Thermocouple
1 Ni/Ni18%Mo Thermocouple
2 Pt20%Rh/Pt40%Rh Thermocouple
3 W/W26%Re (Engelhard) Thermocouple
4 W/W26%Re (Hoskins) Thermocouple
5 W5%Re/W26%Re (Engelhard) Thermocouple
6 W5%Re/W26%Re (Bucose) Thermocouple
7 Pt10%Rh/Pt40%Rh Thermocouple
8 Exegen K80 I.R. pyrometer
Process Inputs (scaled to setpoint min and max)
F -100 to +100mV linear
Y 0 to 20mA linear (note 4)
A 4 to 20mA linear (note 4)
W 0 to 5Vdc linear
G 1 to 5Vdc linear
V 0 to 10Vdc linear
Setpoint
Min
Setpoint
Max
Min °C Max
-210 1200
-200 1372
-200
-200
-250
-50
-50
400
900
1300
1768
1768
0
0
1820
1369
-200 850
Min °C Max
0 2319
0
-250
0
0
0
2399
1000
1399
1870
2000
0
10
0
200
-45
2010
2300
2000
1800
650
Min °C Max
-1999 9999
-1999
-1999
-1999
9999
9999
9999
-1999
-1999
9999
9999
Note 5.
An external 1% current sense resistor is supplied as standard. If greater accuracy is required, a
0.1% 2.49
Ω can be ordered as part no. SUB2K/249R.1.
Note 6
Only available with Profibus controller.
Note 7.
Not available with 8 segment programmer
Display Units
C Celsius
F Fahrenheit
K Kelvin
X Linear input
XX Disabled
AM Manual select
SR Remote SP select
S2 Second setpoint
EH Integral hold
AC Alarm acknowledge
RP SP rate limit enabled
RN Run program
HO Hold program
RE Reset program
RH Run/hold prog
KL Keylock
NT Run/Reset
TN Reset/Run
HB Program holdback
Digital Input 1 & 2
P2 Second PID
ST One shot tune enable
AT Adaptive tune enable
FA Select full access level
RB Simulates UP button
LB Simulates DOWN button
SB Simulates SCROLL button
PB Simulates PAGE button
B1 Least sig. BCD digit
B2 2nd BCD digit
B3 3rd BCD digit
B4 4th BCD digit
B5 5th BCD digit
B6 Most significant digit
SY Standby-all O/Ps OFF
SC Prog synchronisation
SG Skip segment
(without changing
SP)
PV Select PV2
AG Advance to end of segment
(& step to target SP)
M5 CTX (mode 5)
Input 2 only
Options
Control action
XX Reverse acting (standard)
DP Direct acting
Power feedback
XX Enabled on logic, relay & triac heating
PD Feedback disabled
Cooling options
XX Linear cooling
CF Fan cooling
CW Water cooling
CL Oil cooling
CO On/Off cooling
Front panel buttons
XX Enabled
MD Auto/manual disabled
MR Auto/man & run/hold disabled
RD Run/hold disabled
Programmer time units
XX Dwell & ramp in mins
HD Dwell time in hours
HR Ramp rate in units/hrs
Example ordering code:-
2408 - CC - VH - LH - RC - FL - FH - YM - TS - K - 0 - 1000 - C - AM - S2 - XX - XX - XX - MD - XX
2408, PID Controller, 85 to 264Vac, Logic heating, Relay cooling, Low alarm relay, High alarm relay, RS485, Modbus comms,
PDSIO setpoint retrans, Type K Thermocouple, 0 to 1000°C, Auto/manual select, 2nd setpoint select, Manual button disabled.
96
Dimensional details
All dimensions in mm
2408
150
48
2408
OP1 OP2
SP2 REM
AUTO
MAN
Panel cut-out
-0.0
+0.8
92 x
45
-0.0
+0.6
2404
96
96
OP1
OP2
SP2
REM
2404
Panel cut-out
92 x 92
-0.0
+0.8
150
Rear terminal connections
Modules 1, 2 and 3 are plug-in modules.
They can be any one of the types shown in the ordering information on previous pages
2408 2404
2C
2D
3A
3B
3C
3D
1A
1B
1C
1D
2A
2B
1
M
O
D
U
L
E
M
O
D
U
L
E
2
U
L
E
M
O
D
3
JA
JB
JC
C
O
M
M
S
2
JD
JE
JF
HA
HB
HC
C
O
M
M
S
1
HD
HE
HF
L
N
Line
100 to 240Vac
Neutral
Earth
LA
Input 1
Input 2
LB
LC
Common
AA
AB
AC
VI
V+
V-
Alarm relay
Thermocouple
RTD/
PT100
+
PV
-
24
N
+
20 to 29Vac/dc
-
Neutral
Earth
Low voltage supply
Line
Load
4D
5A
5B
4A
4B
4C
5C
5D
6A
6B
6C
6D
C
U
R
R
E
N
T
H
I
G
H
O
U
T
P
U
T
1D
2A
2B
1A
1B
1C
2C
2D
3A
3B
3C
3D
1
U
L
E
M
O
D
U
L
E
M
O
D
2
M
O
D
U
L
E
3
HA
HB
HC
M
S
1
C
O
M
HD
HE
HF
JA
JB
JC
M
S
2
C
O
M
JD
JE
JF
L
N
Line
100 to 240Vac
Neutral
Earth
LA
Input 1
LB
Input 2
LC
Common
24
N
AA
AB
AC
VI
V+
V-
Alarm relay
Thermocouple
RTD/
PT100
+
PV
-
+
20 to 29Vac/dc
-
Neutral
Earth
Low voltage supply
EUROTHERM LIMITED UK
Faraday Close Durrington Worthing BN13 3PL
Tel. +44 (0)1903 268500 Fax +44 (0)1903 695666
Email [email protected]
www.eurotherm.co.uk
EUROTHERM US
741-F Miller Drive Leesburg VA 20175-8993
Tel. 1-703-443-0000 Fax 1-703-669-1300
Email [email protected]
www.eurotherm.com
EUROTHERM WORLDWIDE www.eurotherm.co.uk
© Copyright Eurotherm Limited 2004
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
Part No. HA026553 Issue 3.1
2408/2404 Data sheet Printed in England 08.04