Siemens | CU230P-2 | User manual | PICS

Add to my manuals
16 Pages

advertisement

Siemens | CU230P-2 | User manual | PICS | Manualzz

s

SINAMICS

BACnet Protocol Implementation Conformance

Statement (PICS)

Basic documentation

1/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

CPS

1.5

1.6

1.7

1.8

1

1.1

1.2

1.3

1.4

1.9

Contents

SINAMICS G120 CU230P-2 .........................................................................3

Product description .......................................................................................3

BACnet standardized device profile (Annex L) .............................................3

BACnet interoperability building blocks supported (Annex K).......................4

Standard object types supported ..................................................................7

Segmentation capability ..............................................................................16

Data Link Layer options ..............................................................................16

Device address binding...............................................................................16

Networking options......................................................................................16

Character sets supported............................................................................16

2/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

CPS

1 SINAMICS G120 CU230P-2

Date

Vendor name

Product name

Product model number

BACnet protocol version

Application software version

Firmware revision

: 07 March 2012

: Siemens Building Technologies (Vendor ID 7)

: SINAMICS G120 CU 230P-2 HVAC

: SINAMICS G120 CU 230P-2 BT

HVAC: 6SL3243-0BB30-1HAx

BT: 6SL3243-6BB30-1HAx

: 1.5

: 1.0

: 04.40

1.1 Product description

SINAMICS G120 is a modular drive inverter system that comprises various function units. These are essentially:

 Control Unit (CU)

 Power Module (PM)

The CU controls and monitors the PM and the connected motor in several operating modes that can be selected. It supports communications to a local control as well as to monitoring devices and equipment. The PMs has a power range from 0.37 kW to 250 kW. This product supports native BACnet directly to MS/TP LAN.

1.2 BACnet standardized device profile (Annex L)

 BACnet Advanced Workstation

BACnet Operator Workstation

BACnet Operator Display

 BACnet Building Controller

BACnet Advanced Application Controller

BACnet Application Specific Controller

BACnet Smart Sensor

 BACnet Smart Actuator

(B-AWS)

(B-OWS)

(B-OD)

(B-BC)

(B-AAC)

(B-ASC)

(B-SS)

(B-SA)

3/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

Data sharing

Alarm and event management

1.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – Read Property-A

Data Sharing – Read Property-B

Data Sharing – Read Property Multiple-A

Data Sharing – Read Property Multiple-B

Data Sharing – Write Property-A

Data Sharing – Write Property-B

Data Sharing – Write Property Multiple-A

Data Sharing – Write Property Multiple-B

Data Sharing – Change of Value -A

Data Sharing – Change of Value -B

Data Sharing – Change of Value Property -A

Data Sharing – Change of Value Property -B

Data Sharing – Change of Value-Unsolicited-A

Data Sharing – Change of Value-Unsolicited-B

Data Sharing – View-A

Data Sharing – Advanced View-A

Data Sharing – Modify-A

Data Sharing – Advanced Modify-A

Alarm and Event – Notification-A

Alarm and Event – Notification Internal-B

Alarm and Event – Notification External-B

Alarm and Event – ACK-A

Alarm and Event – ACK-B

Alarm and Event – Alarm Summary-A

Alarm and Event – Alarm Summary-B

Alarm and Event – Enrollment Summary-A

Alarm and Event – Enrollment Summary-B

Alarm and Event – Information-A

Alarm and Event – Information-B

Alarm and Event – Life Safety-A

Alarm and Event – Life Safety-B

Alarm and Event – View Notifications-A

Alarm and Event – Advanced View Notifications-A

Alarm and Event – View and Modify-A

Alarm and Event – Advanced View and Modify-A

Alarm and Event – Alarm Summary View-A

Alarm and Event – Event Log View-A

Alarm and Event – Event Log View and Modify-A

Alarm and Event – Event Log Internal-B

 Alarm and Event – Event Log External-B

DS-RP-A

DS-RP-B

DS-RPM-A

DS-RPM-B

DS-WP-A

DS-WP-B

DS-WPM-A

DS-WPM-B

DS-COV-A

DS-COV-B

DS-COVP-A

DS-COVP-B

DS-COVU-A

DS-COVU-B

DS-V-A

DS-AV-A

DS-M-A

DS-AM-A

AE-N-A

AE-N-I-B

AE-N-E-B

AE-ACK-A

AE-ACK-B

AE-ASUM-A

AE-ASUM-B

AE-ESUM-A

AE-ESUM-B

AE-INFO-A

AE-INFO-B

AE-LS-A

AE-LS-B

AE-VN-A

AE-AVN-A

AE-VM-A

AE-AVM-A

AE-AS-A

AE-ELV-A

AE-ELVM-A

AE-EL-I-B

AE-EL-E-B

4/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

Scheduling

Trending

Device management



Scheduling – A

Scheduling – Internal-B

Scheduling – External-B



Scheduling – Advanced View Modify-A



Scheduling – View Modify-A



Scheduling – Weekly Schedule-A



Scheduling – Weekly Schedule Internal-B



Scheduling – Readable-B

SCHED-A

SCHED-I-B

SCHED-E-B

SCH-AVM-A

SCH-VM-A

SCH-WS-A

SCH-WS-I-B

SCH-R-B

 Trending – Viewing and Modifying Trends-A

Trending – Viewing and Modifying Internal-B

Trending – Viewing and Modifying External-B



Trending – Viewing and Modifying Multiple Values-A

T-VMT-A

T-VM-I-B

T-VM-E-B

T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B



Trending – Automated Multiple Value Retrieval-A

Trending – Automated Multiple Value Retrieval-B

T-AMVR-A

T-AMVR-B



Trending – View-A



Trending – Advanced View and Modify-A



Trending – Archival-A



Trending – Automated Trend Retrieval-A

Trending – Automated Trend Retrieval-B

T-V-A

T-AVM-A

T-A-A

T-ATR-A

T-ATR-B

Device Management – Dynamic Device Binding-A

Device Management – Dynamic Device Binding-B

Device Management – Dynamic Object Binding-A

Device Management – Dynamic Object Binding-B



Device Management – Device Communication Control-A

Device Management – Device Communication Control-B

Device Management – Private Transfer-A

Device Management – Private Transfer-B



Device Management – Text Message-A



Device Management – Text Message-B



Device Management – Time Synchronization-A

Device Management – Time Synchronization-B

Device Management – UTC Time Synchronization-A

Device Management – UTC Time Synchronization-B



Device Management – Reinitialize Device-A

Device Management – Reinitialize Device-B

 Device Management – Backup and Restore-A

Device Management – Backup and Restore-B

 Device Management – Restart-A

Device Management – Restart-B

DM-DDB-A

DM-DDB-B

DM-DOB-A

DM-DOB-B

DM-DCC-A

DM-DCC-B

DM-PT-A

DM-PT-B

DM-TM-A

DM-TM-B

DM-TS-A

DM-TS-B

DM-UTC-A

DM-UTC-B

DM-RD-A

DM-RD-B

DM-BR-A

DM-BR-B

DM-R-A

DM-R-B

5/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

Device management

Network management

 Device Management – List Manipulation-A

Device Management – List Manipulation-B

 Device Management – Object Creation and Deletion-A

 Device Management – Object Creation and Deletion-B

 Device Management – Virtual Terminal-A

Device Management – Virtual Terminal-B

Device Management – Automatic Network Mapping-A

Device Management – Automatic Device Mapping-A

DM-LM-A

DM-LM-B

DM-OCD-A

DM-OCD-B

DM-VT-A

DM-VT-B

DM-ANM-A

DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A

Network Management – Connection Establishment-B

Network Management – Router Configuration-A

Network Management – Router Configuration-B

NM-CE-A

NM-CE-B

NM-RC-A

NM-RC-B

6/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

1.4 Standard object types supported

Object type Supported Can be created dynamically

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Calendar

Command

Device

Event Enrollment

File

Group

Loop

Multi-State Input

Multi-State Output

Notification Class

Program

Schedule

Averaging

Multi-State Value

Trend Log

Life-Safety-Point

Life-Safety-Zone

Accumulator

Pulse-Converter

Event Log

Global Group

Trend Log Multiple

Load Control

Structured-View

Access Door

(unassigned)

Access Credential

Access Point

Access Rights

Access User

Access Zone

Credential Data Input

Network Security

Bitstring Value

Characterstring Value

Can be deleted dynamically

7/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

Object type

Date Pattern Value

Date Value

Datetime Pattern Value

Datetime Value

Integer Value

Large Analog Value

Octetstring Value

Positive Integer Value

Time Pattern Value

Time Value

Supported

Can be created dynamically

Can be deleted dynamically

8/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

Analog Input

Properties

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Update_Interval

Units

Min_Pres_Value

Max_Pres_Value

Resolution

COV_Increment

Time_Delay

Notification_Class

High_Limit

Low_Limit

Deadband

Limit_Enable

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name supported Readable/

Writable

R

Range restrictions

R

R

R

R

R

R

R

R

W

9/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

Analog Value Properties

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Status_Flags

Event_State

Reliability

Out_Of_Service

Units

Priority_Array

Relinquish_Default

COV_Increment

Time_Delay

Notification_Class

High_Limit

Low_Limit

Deadband

Limit_Enable

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name supported

Readable/

Writable

R

Range restrictions

R

R

R

R

R

R

R

R

10/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

Binary Input Properties

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Polarity

Inactive_Text

Active_Text

Change_Of_State_Time

Change_Of_State_Count

Time_Of_State_Count_Reset

Elapsed_Active_Time

Time_Of_Active_Time_Reset

Time_Delay

Notification_Class

Alarm_Value

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name supported

R

Readable/

Writable

R

Range restrictions

R

R

R

R

R

R

R

R

R

11/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

Binary Output Properties

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Polarity

Inactive_Text

Active_Text

Change_Of_State_Time

Change_Of_State_Count

Time_Of_State_Count_Reset

Elapsed_Active_Time

Time_Of_Active_Time_Reset

Minimum_Off_Time

Minimum_On_Time

Priority_Array

Relinquish_Default

Time_Delay

Notification_Class

Feedback_Value

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name supported

Readable/

Writable

R

Range restrictions

R

R

W

R

R

R

R

R

R

R

R

R

12/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

Binary Value Properties

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Status_Flags

Event_State

Reliability

Out_Of_Service

Inactive_Text

Active_Text

Change_Of_State_Time

Change_Of_State_Count

Time_Of_State_Count_Reset

Elapsed_Active_Time

Time_Of_Active_Time_Reset

Minimum_Off_Time

Minimum_On_Time

Priority_Array

Relinquish_Default

Time_Delay

Notification_Class

Alarm_Value

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name supported

Readable/

Writable

R

Range restrictions

R

R

W

R

R

R

R

R

R

R

R

13/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

Device Properties

Object_Identifier

Object_Name

Object_Type

System_Status

Vendor_Name

Vendor_Identifier

Model_Name

Firmware_Revision

Application_Software_Version

Location

Description

Protocol_Version

Protocol_Revision

Protocol_Services_Supported

Protocol_Object_Types_Supported

Object_List

Structured_Object_List

Max_APDU_Length_Accepted

Segmentation_Supported

Max_Segments_Accepted

VT_Classes_Supported

Active_VT_Sessions

Local_Time

Local_Date

UTC_Offset

Daylight_Savings_Status

APDU_Segment_Timeout

APDU_Timeout

Number_Of_APDU_Retries

List_Of_Session_Keys

Time_Synchronization_Recipients

Max_Master

Max_Info_Frames

Device_Address_Binding

Database_Revision

Configuration_Files

Last_Restore_Time

Backup_Failure_Timeout

Backup_Preparation_Time

Restore_Preparation_Time

Restore_Completion_Time

Backup_And_Restore_State

Active_COV_Subscriptions

Slave_Proxy_Enable

Manual_Slave_Adress_Binding

14/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS) supported Readable/

Writable

R

Range restrictions

R

R

R

R

R

R

R

R

R

R

R

R

R

R 480

R

R

R

R

R

R

R

R

Properties

Auto_Slave_Discovery

Slave_Address_Binding

Last_Restart_Reason

Time_Of_Device_Restart

Restart_Notification_Recipients

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Profile_Name supported

Readable/

Writable

Range restrictions

15/16

Building Automation BACnet Protocol Implementation Conformance Statement (PICS)

1.5 Segmentation capability

Able to transmit segmented messages Window size 0

 Able to receive segmented messages Window size 0

1.6 Data Link Layer options

The simultaneously supported Data Link Layers of a product are listed with the product model number.

 BACnet IP, (Annex J)

 BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s) : 9600

: 19200

: 38400

: 76800

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s)

Point-To-Point, modem, (Clause 10), baud rate(s)

 LonTalk, (Clause 11), medium

 Other

1.7 Device address binding

Yes

No Is static device binding supported?

1.8 Networking options

Router, Clause 6 (remote management functionality/BACnet PTP)

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD) 1)

Number of BDT entries: 0

Number of FDT entries: 0

Does the BBMD support registrations by foreign devices?

Yes

No

1) if product supports IP

1.9 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

ANSI X3.4

IBM / Microsoft DBCS

ISO 8859-1

ISO 10646 (UCS-2)

ISO 10646 (UCS-4)

JIS C 6226

16/16

Building Automation DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS)

CPS

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project