Empire Heating Systems DV-55T-1 Owner's Manual

Add to my manuals
20 Pages

advertisement

Empire Heating Systems DV-55T-1 Owner's Manual | Manualzz

INSTALLATION INSTRUCTIONS

AND

OWNER'S MANUAL

FAN TYPE

DIRECT VENT

WALL FURNACE

MODEL

DV-55T-1

Installer: Leave this manual with the appliance.

Consumer: Retain this manual for future reference.

This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by state or local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

WARNING: If not installed, operated and maintained in accordance with the manufacturer's instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.

WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

— WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any phone in your building.

• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire department.

— Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Page 1

Page 2

TABLE OF CONTENTS

SECTION PAGE

Important Safety Information ......................................................................................................................3

Vent Kit Information ....................................................................................................................................3

Safety Information for Users of LP Gas ......................................................................................................4

Requirements for Massachusetts ..................................................................................................................5

Introduction ..................................................................................................................................................6

Specifications ...............................................................................................................................................6

Gas Supply ............................................................................................................................................... 7-8

Clearances ...................................................................................................................................................8

Installation Instructions .......................................................................................................................... 9-11

Lighting Instructions .................................................................................................................................12

Pilot Flame Characteristics .......................................................................................................................13

Main Burner Flame Characteristics ..........................................................................................................13

Wiring ........................................................................................................................................................14

Service and Maintenance Suggestions .......................................................................................................15

How to Order Repair Parts .........................................................................................................................16

Parts List ...................................................................................................................................................16

Parts View ..................................................................................................................................................17

Service Notes ....................................................................................................................................... 18-19

13118-8-0709

IMPORTANT SAFETY INFORMATION

THIS IS A HEATING APPLIANCE

DO NOt OPeRate tHIS aPPLIaNCe WItHOUt FRONt PaNeL INStaLLeD.

Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies.

• Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.

• Young children should be carefully supervised when they are in the same room as the appliance.

• Clothing or other flammable material should not be placed on or near the appliance.

• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.

• Keep burner and control compartment clean.

• Vent cap hot while furnace is in operation.

• Installation and repair should be done by a qUALIFIED

SERVICE PERSON. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.

• Do not put anything around the furnace that will obstruct the flow of combustion and ventilation air.

• Do keep the appliance area clear and free from combustible material, gasoline and other flammable vapors and liquids.

• Do examine venting system periodically and replace damaged parts.

• Do make a periodic visual check of pilot and burners.

Clean and replace damaged parts.

• CAUtIon: Pilot hole cover must be kept tightly closed during operation.

• Do not use this heater if any part has been under water.

Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.

VEnt KIt InFoRMAtIon

Attention: the DV-55t direct vent wall furnaces are provided with vent kit, DV4t-59-1 for wall depths of 5" to 9". For wall depths greater than 9", refer to accessories, Page 6. Listed below are the vent kits.

Attention: the minimum wall depth for installation of a DV-55t MUST BE 5". If the wall depth is less than 5" you can order DV-

822, refer to accessories, Page 6 or refer to Figure 10 and Figure 11 with accompanying text, Page 11.

13118-8-0709 Page 3

SAFETY INFORMATION FOR USERS OF LP-GAS

Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the members of your household. Someday when there may not be a minute to lose, everyone's safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.

LP-GAS WARNING ODOR

If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.

That's your signal to go into immediate action!

• Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.

• Get everyone out of the building, vehicle, trailer, or area. Do that IMMeDIateLY.

• Close all gas tank or cylinder supply valves.

• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until firefighters declare them to be safe.

• Use your neighbor's phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.

Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.

NO ODOR DETECTED - ODOR FADE

Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you

can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. thinking about smelling a gas odor can make it easier to smell.

The odorant in LP-gas is colorless, and it can fade under some

circumstances. For example, if there is an underground leak, the movement of the gas through soil can filter the odorant. Odorants in LP-Gas also are subject to oxidation. this fading can occur if there is rust inside the storage tank or in iron gas pipes.

the odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. that will take some of the odorant out of the gas, reducing its odor intensity.

LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.

SOME POINTS TO REMEMBER

Learn to recognize the odor of LP-gas. Your local LP-Gas

Dealer can give you a "Scratch and Sniff" pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your

LP-Gas Dealer.

• If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.

to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.

• If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.

• Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.

• Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed

• If you experience a complete "gas out," (the container is under no vapor pressure), turn the tank valve off immediately.

If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.

Page 4 13118-8-0709

REqUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. the sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VEnt DIRECtLY BELoW. KEEP

CLEAR OF ALL OBSTRUCTIONS”.

1. INStaLLatION OF CaRBON MONOXIDe DeteCtORS. at the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed.

In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. aPPROVeD CaRBON MONOXIDe DeteCtORS. each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPa 720 and be ANSI/UL 2034 listed and IAS certified.

4. INSPeCtION. the state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR

5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. the equipment listed in Chapter 10 entitled

“equipment Not Required to Be Vented” in the most current edition of NFPa 54 as adopted by the Board; and

2. Product approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS

EQUIPMENT VENTING SYSTEM PROVIDED.

When the manufacturer of Product approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. a complete parts list for the venting system design or venting system.

(e) A copy of all installation instructions for all Product approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

13118-8-0709 Page 5

INTRODUCTION

Introduction always consult your local Building Department regarding regulations, codes or ordinances which apply to the installation of a direct vent wall furnace.

Instructions to Installer

1. Installer must leave instruction manual with owner after installation.

2. Installer must have owner fill out and mail warranty card supplied with furnace.

3. Installer should show owner how to start and operate furnace and thermostat.

Warning:

Any change to this furnace or its control can be dangerous. This is a heating appliance and any panel, door or guard removed for servicing an appliance must be replaced prior to operating the appliance.

General Information

This furnace is design certified in accordance with American National

Standard/CSa Standard Z21.86 and CSa 2.32 by the Canadian Standards association, as a fan type direct vent wall furnace to be installed according to these instructions.

Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.

Important all correspondence should refer to complete Model Number, Serial Number and type of gas.

Notice: During initial firing of this unit, its paint will bake out and smoke will occur. to prevent triggering of smoke alarms, ventilate the room in which the unit is installed.

Installation on Rugs and Tile

If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.

The base referred to above does not mean the fire-proof base as used on wood stoves. the protection is for rugs that are extremely thick and light colored tile.

Installation in Residential Garages

Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18" above the floor.

Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term "qualified agency" means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.

State of Massachusetts: the installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.

the installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54* Natural

Gas and Propane Installation Code, CSA B149.1.

*Available from the American National Standards Institute, Inc., 11 West 42nd St., New York,

N.Y. 10036.

High Altitudes

For altitudes/elevations above 2,000 feet, input ratings should be reduced at the rate of 4 percent for each 1,000 feet above sea level. Canadian High

Altitudes for locations having an elevation above mean sea level between

2,000 feet (610m) and 4,500 feet (1370m), the manifold pressure is to be decreased from 4.0" w.c. to 3.2" w.c. for Natural Gas and from 10.0" w.c. to 8.0" w.c. for Propane Gas.

Piezo Pilot Ignitor Instructions

Depressing the red button completely causes a spark to occur at the pilot. this is a substitute for a match which requires opening the pilot hole cover.

to light the pilot, it is important that the electrode be 1/8" from the thermocouple. The spark must occur at the point the burner flame hits the thermocouple. the end of the electrode will be red hot with the pilot on.

On a new installation with air in the gas line, it is suggested that a match be used. the match will light the pilot faster than the piezo under this condition.

Model DV-55t

Input- BtU/HR 55,000

Height 82 3/8"

Width

Depth

Gas Inlet

16"

11 1/2"

1/2" Pipe

CFM 400

Page 6

SPECIFICATIONS

accessories

SOR-1

SOK-1

*DV-822

DV4t-812-1

DV4t-1219

Register, Side Outlet

Side Outlet Kit, 10" Boot assembly

Vinyl Siding Vent Kit

Vent Kit (8" to 12" wall depth)

Vent Kit (12" to 19" wall depth

*DV-822, Vinyl vent kit, adds 3" to wall depth. You must include the three (3) additional inches for

TOTAL wall depth when ordering a vent kit.

13118-8-0709

GAS SUPPLY

Locating Gas Supply

The gas line can enter the unit either through the floor or outside wall. the gas line opening should be made at this time. Location of the opening will be determined by the position of floor joists and the valve and union used for servicing.

3/4" Recommended Gas Pipe Diameter

Pipe Length

(Feet)

Schedule 20 Pipe

Inside Diameter

Nat.

L.P.

Tubing, Type L

Outside Diameter

Nat.

L.P.

0-10

10-40

1//2"

12.7mm

1/2"

12.7mm

40-100 1/2"

12.7mm

100-150 3/4"

19mm

3/8"

9.5mm

1/2"

12.7mm

1/2"

12.7mm

1/2"

12.7mm

1/2"

12.7mm

5/8"

15.9mm

3/4"

19mm

7/8"

22.2mm

3/8"

9.5mm

1/2"

12.7mm

1/2"

12.7mm

3/4"

19mm a manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. this should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made. never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

a gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. this should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

— aNS Z21.24 appliance Connectors of Corrugated Metal tubing and Fittings

— aNS Z21.45 assembled Flexible appliance Connectors of

Other than all-Metal Construction the above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

Figure 1

Consult the current National Fuel Gas Code, aNSI Z223.1 CaN/

CGA-B149 (.1 or .2) installation code.

Installing a New Main Gas Cock each appliance should have its own manual gas cock.

13118-8-0709

Figure 2

Method of Installing a Tee Fitting Sediment Trap

Pressure Testing of the Gas Supply System

1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2. the appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

3. the appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Page 7

Figure 3

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 4.0" w.c. at the valve outlet with the inlet pressure to the valve from a minimum of 6.0" w.c. for the purpose of input adjustment to a maximum of 7.0" w.c. Propane gas models will have a manifold pressure approximately 10.0" w.c. at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. for the purpose of input adjustment to a maximum of 13.0" w.c. a 1/8" N.P.t. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.

the built-in regulator comes on at approximately 1/4th pressure and full on in 10 seconds.

CLEARANCES

Clearances

1. In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation.

2. The DV4T-59-1, 5" to 9" wall depth is the standard vent kit provided with the DV-55T. See Accessories Page 6 to order vent kits for wall depths of 8" to 12" or 12" to 19".

The use of tubes not supplied by the manufacturer results in unsatisfactory performance.

3. the DV-55t can be attached to the wall or recessed into the wall up to 4 inches in depth but the minimum 5 inches vent/air intake system wall depth must be maintained. Example: If furnace is recessed into the wall at a depth of 4 inches, the minimum wall depth must be 9 inches.

4. The wall in which the furnace is recessed has (0) zero clearance to the furnace sides and top.

5. When using side discharge registers, SOR-1 or SOK-1, the furnace cannot be recessed into the wall.

6. Clearance to sidewall or combustible material is 4 inches.

7. Ceiling clearance is 4 inches.

8. Floor and rear wall clearance is (0) zero inches.

9. Clearance of 18 inches is required to sidewall or combustible material when flush mounted SOR-1, side outlet register is used. See Figure 4.

10. the minimum distance from the center of the vent cap to the nearest outside corner or obstruction is 24 inches. the vent terminal of a direct vent appliance with an input over

50,000 BtU per hour shall be located at least 12 inches from any opening through which flue gases could enter a building. The bottom of the vent terminal and the air intake shall be located at least

12 inches above grade.

WARNING: The nearest point of the vent cap should be a minimum horizontal distant of six (6) feet from any pressure regulator. In case of regulator malfunction, the six

(6) feet distance will reduce the chance of gas entering the vent cap.

Figure 4

Page 8 13118-8-0709

INSTALLATION INSTRUCTIONS

Locating Wall Opening the furnace is to be located on an outside wall. Locate wall studs so that wall opening will be located between wall studs. the furnace is 16 inches in width and normal 16 inches on center studs will not allow the furnace to be recessed into the wall unless a stud is repositioned. the wall opening required as shown in Figure 5 is a diameter of 7 1/2 inches.

a template is provided in furnace carton for positioning furnace on the wall. also, refer to Figure 5 for positioning the furnace on wall and for locating gas line connection.

Installing Optional Side Outlets

Side outlet register, SOR-1 may be installed on one or both sides of the furnace at the required clearances of 18 inches to adjacent wall or combustible material as shown in Figure 4.

1. Locate and cut the 5 1/2" square opening in the cabinet side using the template from the kit, exposing the inner liner knock-out.

2. Remove the knock-out.

3. Place the register on the 5 1/2" opening with the louvers set for the desired direction and mark the mounting holes using the register as a template.

4. Drill two (2) 1/8" diameter holes in cabinet side and fasten the register in place with two (2) 10 x 1" screws provided.

Side outlet kit, 10" boot assembly with register, SOK-1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall as shown in Figure 7.

1. Locate and cut the 5 1/2" square opening in the cabinet side using the template from the kit, exposing the inner liner knock-out.

2. Remove the knock-out.

3. Using the inner and outer boots as hole templates, mark and drill eight (8) 1/8" diameter holes in the inner liner and cabinet side.

4. Using Figure 7 locate and cut a 6 3/4" square opening through walls.

5. Prepare wall opening for the vent-air intake system (see

Locating Wall Opening).

6. With furnace in place, after checking alignment of side outlet opening in wall and furnace, place the 9 3/8" x 9 3/8" side outlet wall plate over outer boot, pass the outer boot through the wall and attach side outlet wall plate to furnace side of wall with two (2) 10 x 1" screws provided.

7. Fasten outer boot to the cabinet side with four (4) 8 x 1/4" screws provided.

8. Position and attach inner boot to inner liner with four (4) 8 x 1/4" screws provided.

9. Locate the register with its louvers positioned for the desired air discharge direction and mark the mounting holes using the register as a template.

10. Drill two (2) 1/8" diameter holes in the wall and fasten the register in place with two (2) 10 x 1" screws provided.

Figure 5

Figure 6 Figure 7

13118-8-0709 Page 9

Using Plastic Expansion Anchors

1. After locating mounting holes, drill two (2) 5/16" diameter holes into the wall.

2. Insert two (2) plastic expansion anchors provided into the holes.

3. Tighten two (2) 10 x 1" screws provided into the plastic expansion anchors. (See Figure 9)

Figure 8

Locating Electric Supply a 7/8" diameter knockout is provided at the bottom of the left and right side panels. A three-prong (grounding) plug assembly is located within the control compartment (bottom) of the furnace.

Please remove 7/8" knockout from appropriate side panel when routing plug assembly to an electrical outlet.

Installation of Three-prong (Grounding) Plug Assembly

1. Disconnect nylon cap on 3' plug assembly from nylon plug on wiring harness. Remove 3' plug assembly from control compartment (bottom) of the furnace.

2. Remove 7/8" knockout from appropriate side panel.

3. Insert nylon cap on 3' plug assembly into the 7/8" hole in the side panel.

4. Connect nylon cap on 3' plug assembly to nylon plug on the wiring harness.

5. Place 7/8" strain relief bushing around the cord of the 3' plug assembly. Insert 7/8" strain relief bushing into the 7/8" hole in the side panel.

Attention! the 7/8" strain relief bushing is located within the same envelope as the Installation Instructions and Owner's Manual.

Attaching Furnace to Wall

Place collar on four inch flue tube against combustion chamber back. align clearance holes on collar with screw holes in combustion chamber back. Attach four inch flue tube to combustion chamber back with four (4) 10 x 1/2" screws.

Place collar on six inch air tube against air drop. align clearance holes on collar with screw holes in air drop. attach six inch air tube to air drop with eight (8) 10 x 1/2" screws.

Refer to Figure 5 for the location of the 7 1/2" diameter wall opening for the furnace. after the wall opening has been located and cut, position flue outlet on furnace in center of wall opening. Insert tubes through wall opening. When attaching furnace to the wall remove that portion of baseboard and molding on the wall which is behind the furnace. attach furnace to wall, at the outer casing top, with two (2) plastic expansion anchors provided and to floor, at the outer casing bottom, with two (2) 10 x 1 1/2" screws provided.

Figure 9

Attention! the screw holes on the outer casing bottom are off-set above the floor approximately 3/8". Do not over-tighten screws and distort the off-set on the outer casing bottom. Distortion of the outer casing bottom will not allow the lower front panel to be attached to the furnace.

Installing Vent Assembly

Attention: DO NOT attempt to cut vent tubes. When you order appropriate vent kit for measured wall depth the vent tubes will fit together.

1. Place caulking (not provided) beneath the collar of the outside mounting plate. Use additional caulking to correct uneven wall surface, such as clapboard.

2. Insert six inch air tube on outside mounting plate INTO six inch air tube attached to air drop. Place four inch flue tube on vent cap OVER four inch flue tube attached to combustion chamber.

Position the outside mounting plate so that six inch air tube has a slight downward slope to the outside. The downward

slope is necessary to prevent the entry of rainwater. attach outside mounting plate to exterior wall with four (4) 10 x 1 1/2" screws.

3. Installation is completed.

Reassembly And Resealing Vent-Air Intake System

When vent-air intake system is removed for servicing the furnace, the following steps will assure proper reassembly and resealing of the vent-air intake assembly.

Page 10 13118-8-0709

INSTALLATION INSTRUCTIONS (continued)

1. Remove old caulking beneath the collar of the outside mounting plate. apply new caulking beneath the collar of the outside mounting plate. Use additional caulking to correct uneven wall surface, such as clapboard.

2. Insert six inch air tube on outside mounting plate INTO six inch air tube attached to air drop. Position the outside mounting plate so that six inch air tube has a slight downward slope to the outside. The downward slope is necessary to prevent the

entry of rainwater. attach outside mounting plate to exterior wall with four (4) 10 x 1 1/2" screws.

3. Place four inch flue tube on vent cap OVER four inch flue tube attached to combustion chamber. attach vent cap to outside mounting plate with three (3) 10 x 1/2" screws.

4. Reassembly and resealing vent-air intake system is completed.

Installing a Vent Near a Window Ledge,

Other Type of Projection or on Siding (vinyl, aluminum, etc.)

Direct vent furnaces are designed to be installed on a uniform outside wall. When the wind comes from any angle (up, down or from either side), it must hit the vent cap equally over both the air inlet and the flue outlet portions of the vent. Any wall projection, such as a door or window casing, which disturbs the wind on one side of the air inlet section will result in back pressure on the flue section smothering the flame and eventual pilot outage.

When the vent cap is to be installed on siding or it appears that a projection within 6" of any side of the air inlet section could shield the air inlet section, the entire vent should be supported away from the wall at least the distance of the projection. 2" x 4" framing whose outside dimensions match the overall dimensions of the mounting plate is recommended. the 2" x 4" framing protects siding from possible warpage or discoloration. all joints can then be sealed and painted. the wall depth plus the additional depth of the 2" x 4" framing should not exceed a total depth of 19" for

DV-55T. (See Figure 10)

Vinyl siding vent kit, DV-822, is available from empire Comfort

Systems, Inc. the depth is 3", which enables the vent cap to be extended away from siding or projections. the wall depth plus the additional 3" depth of the vinyl siding vent cap extension should not exceed a total depth of 19" for DV-55T. (See Figure 11)

Warning: When vinyl siding vent kit, DV-822 or 2" x 4" framing is added to an existing installation (furnace is installed) do not attempt to add sections of pipe to the flue outlet tube or air inlet tube. An air tight seal is required for both tubes. Refer to Parts List, page 16 to order tubes.

Figure 10 Figure 11

13118-8-0709 Page 11

LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch;

do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above.

2. Set the thermostat to lowest setting.

3. Turn off all electric power to the appliance.

4. Remove control access panel (lower front panel).

5. Turn gas control knob clockwise to "OFF."

10. Push and hold red reset button down completely and repeatedly push the ignitor button until the pilot burner is lit. Pilot may also be lit with a match. Continue to hold the red reset button down for about one (1) minute after the pilot is lit. Release button and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through

10.

• If button does not pop up when released, stop and immediately call a qualified service technician or gas supplier.

• If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.

11. Replace pilot access cover.

12. Turn gas control knob counterclockwise

"ON."

to

6. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, StoP!

Follow "B" in the safety information above. If you don't smell gas, go to the next step.

7. Remove the pilot access cover located on the combustion chamber.

8. Find pilot - follow metal tube from gas control. The pilot is located between the two burner tubes behind the pilot access cover.

9. Turn gas control knob counterclockwise

LOT."

to "PI-

13. Replace control access panel (lower front panel).

14. Turn on all electric power to the appliance.

15. Set thermostat to desired setting.

TO TURN OFF GAS TO APPLIANCE

1. Set the thermostat to lowest setting.

2. Turn off all electric power to appliance if service is to be performed .

3. Remove control access panel (lower front panel).

4. Push in gas control knob slightly and turn clockwise

to "OFF." Do not force.

5. Replace control access panel (lower front panel).

Page 12 13118-8-0709

PILOT FLAME CHARACTERISTICS

The correct pilot flame (Figure 12) will be blue, extending past the thermocouple. The flame will surround the thermocouple just below the tip.

Natural gas pilots require adjusting when the inlet gas pressure is above 5" w.c. Remove the pilot cover screw on the control valve

(Figure 3, page 8), and turn the adjustment screw clockwise to reduce flame. Replace pilot cover screw to eliminate gas leaking at that control valve opening.

LP gas (propane) will not require adjustment.

After use, cleaning may be required for the proper flame.

PROPeR FLaMe aDJUStMeNt

Figure 12

MAIN BURNER FLAME CHARACTERISTICS

The correct flame will be a short blue inner flame with a much larger light blue outer flame. The main burner (Figure 13) shows the approximate height of each part of the flame for each gas. The burner does not have a primary air adjustment. The flame will be correct if the factory-set pressure and orifice opening are used. After the furnace has been operating, the burner ports may be blocked by foreign matter carried in by combustion air. therefore, cleaning of the burner may be needed for proper flame.

to clean burner port disconnect the gas supply to the valve, and remove the eight screws fastening the burner door. after removing the burner door from the combustion chamber, remove rear burner, pilot burner and front burner. With front and rear burners removed from furnace, force water into the ribbon ports and dry with air pressure.

Figure 13

13118-8-0709 Page 13

WIRING

the appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the

National Electrical Code, ANSI/NFPA 70 or Canadian Electrical

Code, CSA C22.1, if an external electrical source is utilized. This appliance is equipped with a three-prong [grounding] plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do

not cut or remove the grounding prong from this plug. For an ungrounded receptacle, an adapter, which has two prongs and a wire for grounding, can be purchased, plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw.

With this wire completing the ground, the appliance cord plug can be plugged into the adapter and be electrically grounded. a 7/8 " hole is provided in the junction box for use with a conduit connector if local codes require this type of protection.

Thermostat Installation the thermostat should be installed in the same room as the furnace

4' to 5' above the floor and away from another heat source (cooking stove, hot water heater, etc.) including walls and doorways with a heat source in an adjoining room. Do Not Install Thermostat on Outside Wall.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

Page 14

Figure 14

13118-8-0709

SERVICE & MAINTENANCE SUGGESTIONS

Replacing Fan and Oiling the Motor the fan motor should be cleaned and oiled once each heating season. to reach the motor, withdraw the metal shroud surrounding the fan blade by removing the screws on each side. Oil holes are located on the top at each end of the motor. Use a few drops of #10 motor oil. to clean the motor, blow air through its ventilation openings with a vacuum cleaner or low pressure air source.

If fan motor is replaced, the silicone rubber gaskets, see Page 16,

Index No. 4, Part No. 712059, should also be replaced. the gaskets must be stretched to fit the motor bolts into the gasket holes and then the motor and gaskets installed on the motor mounting bars.

GENERAL : All furnaces have been fire-tested to check for proper operation. This includes, main burner flame, pilot flame, fan operation, fan control, limit control and automatic valve operation.

If the furnace fails to function on initial installation, it is advisable to re-check the following:

1. 115 volts to the junction box.

2. Inlet gas pressure.

3. the 24 volt system.

4. type of gas being used and that shown on the rating label.

the Service Department at empire Comfort Systems, Inc. may be contacted to assist in servicing furnace or call a qualified serviceman..

Servicing the Pilot and Main Burners, Pilot Orifice,

thermocouple, and Main Burner orifices: Disconnect the gas supply at the inlet to the control valve. then remove the burner door to which the above components are attached.

Servicing The Fan Motor: the upper front panel, the shroud surrounding the fan blade and fan blade must be removed. See

"Replacing Fan and Oiling the Motor" paragraph above.

Spark Igniter Does Not Light Pilot: With air in the gas line, such as when the furnace is first installed or was off all summer, the pilot flame may be too lean to ignite on the first few trials. Turn the control valve knob to pilot position and depress the red reset button.

Holding the button down continually to bleed the line:

1. Use lighter rod to light pilot with a match.

2. Use the piezo ignitor at 30 second intervals until it lights.

If Electrode Does Not Produce Spark:

1. Check wire connections.

2. Check gap for pilot burner to the electrode tip. Should be between 1/8" and 3/16". electrode wire and tip must be more than 1/4" away from all other metal components.

If Pilot Does Not Light By Any Means:

1. Check valve knob for being in the "Pilot" position.

2. Check pilot adjustment for being full open (counterclockwise to open).

3. If gas is available in the supply tubing, the pilot orifice and/or pilot burner is probably restricted by a spider web. Clean pilot assembly and relight.

If Pilot Does not Remain on After Releasing Knob:

1. Follow instructions and hold button down longer and harder.

2. Determine if pilot flame extends past thermocouple; if not, adjust input or clean pilot burner.

3. Replace thermocouple if millivolts read less than 15 millivolts.

Pilot Outage During Normal Operation:

1. Check air inlet tube for a good tight fit at both ends (6" diameter tube).

2. Check burner door and pilot hole cover for tight seal.

3. Check input by manifold pressure gauge or gas meter.

Main Gas Valve Does Not Open When Thermostat Is Turned

To On:

1. Check for 24 volts to valve by removing one wire and touching to the SAME TERMINAL it was on. terminal should have a light spark. DO NOT SHORT ACROSS

TERMINALS, AS IT WILL BURN OUT THE WALL

THERMOSTAT.

2. thermostat wires at the wall may be shorted, so check for a faulty thermostat.

3. to check for line voltage to furnace, remove lower front panel and switch compartment cover and short across twoterminal fan control to allow fan to operate. (Figure 14)

13118-8-0709 Page 15

HOW TO ORDER REPAIR PARTS

Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the service person/dealer.

All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following appropriate illustration and list. Be sure to give all this information.

Furnace Model Number

Furnace Serial Number

Part Description

Part Number

Type of Gas (Propane or Natural)

Do not order bolts, screws, washers or nuts. they are standard hardware items and can be purchased at any local hardware store.

Shipments contingent upon strikes, fires and all causes beyond our control.

Empire Comfort Systems, Inc. Nine eighteen Freeburg ave. Belleville, IL 62220-2623

PARTS LIST

PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.

Index

No.

Part

Number Description

Index

No.

Part

Number Description

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

23

24

25

26

27

28

29

30

31

31

17

18

19

20

21

22

11762

R-618

11764

M-147

R-619

11787

11766

DV-558

11759

DV-613

13057

M-177

13104

13062

M-178

13106

13064

13059

13053

DV-1387

M-176

13113

R-1536

11765

R-630

R-1941

DV-832

DV-562

DV-826

R-685

R-622-L

R-622-N

OUteR CaSING tOP

MOTOR MOUNT - 4 REQUIRED

MOTOR MOUNTING BAR - 2 REQ'D

GASKET - 2 REQUIRED

MOtOR

FaN BLaDe

FaN HOUSING

FRONt PaNeL- UPPeR

SIDE PANEL - 2 REQUIRED

INNeR SHIeLD - RIGHt

OUtLet tUBe - INNeR aSSeMBLY

(INCLUDES 12 &13)

GaSKet - OUtLet COLLaR

OUtLet tUBe - INNeR WeLDeD aSSeMBLY

INNeR tUBe - INNeR aSSeMBLY

(INCLUDES 15 & 16)

GaSKet - INLet COLLaR

INLet tUBe - INNeR WeLDeD aSSeMBLY

INLet tUBe - OUteR aSSeMBLY

OUtLet tUBe - OUteR aSSeMBLY

VeNt CaP aSSeMBLY WeLDeD aIR DROP WeLDeD aSSeMBLY

GaSKet - FLUe OUtLet FLaNGe

COMBUStION CHaMBeR WeLDeD aSSeMBLY

BUSHING

SWItCH COMPaRtMeNt

LIMIt CONtROL

FaN CONtROL

SWItCH COMPaRtMeNt COVeR

FRONt PaNeL - LOWeR

ReaR BURNeR aSSeMBLY tHeRMOCOUPLe

PILOt WItH ORIFICe - LPG GaS

PILOt WItH ORIFICe - Nat GaS

39

40

41

42

42

43

44

45

32

33

34

34

35

36

37

38

45

46

47

48

49

50

51

52

53

54

55

DV-808

DV-824

P-88-41

P-88-53

DV-687

M-148

M-155

DV-781

DV-064

DV-775

M-147

DV-622

DV-973

DV-779

P-112

R-5655

R-2148

UH-810

R-1995

UH-451

11760

R-1515

R-2708

DV-571

DV-671

DV-765

DV-764

56

57

R-690-B

R-1404

58 DV-614

NOt SHOWN R-9832

NOt SHOWN R-9833

NOt SHOWN R-6389

NOt SHOWN R-734

PILOt tUBING

FRONt BURNeR aSSeMBLY

ORIFICE - NAT GAS - 2 REQUIRED

ORIFICE - LPG GAS - 2 REQUIRED

MaNIFOLD

GaSKet - MaNIFOLD

GaSKet-OBSeRVatION HOLe COVeR

LIGHtING HOLe COVeR aSSeMBLY

COVeR PLate-OBSeRVatION HOLe

SeaL BRaCKet

GaSKet - tUBING SeaL

BURNeR DOOR - Nat GaS

BURNeR DOOR - LPG GaS

GaSKet - BURNeR DOOR

MaNIFOLD UNION

GaS VaLVe - LPG GaS

GaS VaLVe - Nat GaS tRaNSFORMeR MOUNtING BRaCKet tRaNSFORMeR

JUNCtION BOX COVeR

OUteR CaSING BOttOM

BUSHING

PIeZO IGNItOR

CONtROL COMPaRtMeNt DIVIDeR

MaNIFOLD SUPPORt

GASKET - CHAMBER AIR INLET (TOP &

BOTTOM) - 2 REQUIRED

GASKET - CHAMBER AIR INLET (SIDES)

- 2 REQUIRED

CORD Set

BUSHING

INNeR SHIeLD - LeFt

WIRING aSSeMBLY UPPeR

WIRING aSSeMBLY LOWeR tHeRMOStat

LIGHteR ROD

USE ONLY MANUFACTURER'S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INjURY OR DEATH.

Page 16 13118-8-0709

PARTS VIEW

13118-8-0709 Page 17

SERVICE NOTES

Page 18 13118-8-0709

SERVICE NOTES

13118-8-0709 Page 19

Page 20

EMPIRE

Comfort Systems empire Comfort Systems Inc.

918 Freeburg ave. Belleville, IL 62220

If you have a general question about our products, please e-mail us at [email protected].

If you have a service or repair question, please contact your dealer.

www.empirecomfort.com

13118-8-0709

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals