Alpha-InnoTec SWC - Series Specifications

Add to my manuals
60 Pages

advertisement

Alpha-InnoTec SWC - Series Specifications | Manualzz
Operating Manual
UK
Brine/Water
Compact
Heat Pumps
SWC – Series
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Please read first
Symbols
This operating manual provides important information on
the handling of the unit. It is an integral part of the product
and must be stored so that it is accessible in the immediate
vicinity of the unit. It must remain available throughout the
entire service life of the unit. It must be handed over to subsequent owners or operators of the unit.
The symbols used in the operating manual have the following meaning:
Read the operating manual before working on or operating
the unit. This applies in particular to the chapter on safety.
Always follow all instructions completely and without restrictions.
It is possible that this operating manual may contain instructions that seem incomprehensible or unclear. In case of
questions or uncertainty, contact the factory customer service department or the manufacturer’s local service partner.
Since this operating manual was written for several different
models of the unit, always comply with the parameters for
the respective model.
This operating manual is intended only for persons assigned
to work on or operate the unit. Treat all constituent parts
confidentially. The information contained herein is protected by copyright. No part of this operating manual may
be reproduced, transmitted, copied, stored in electronic data
systems or translated into another language, either wholly
or in part, without the express written permission of the
manufacturer.
Information for operators.
Information or instructions for qualified technicians.
Danger!
Failure to observe this information could
result in immediate danger to life and limb.
Warning!
Failure to observe this information could
result in serious personal injury.
Caution!
Failure to observe this information could
result in moderate or slight personal injury.
Caution.
Failure to observe this information could
result in material damage.
Notice.
Emphasized information.
Reference to other sections of the operating
manual.
Reference to other instructions of the manufacturer.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Contents
Information for operators and
qualified technicians
Please read first............................................................................... 2
Symbols................................................................................................... 2
Intended use....................................................................................... 4
Exclusion of liability.................................................................. 4
EC conformity.................................................................................. 4
Safety....................................................................................................... 4
Customer service.............................................................................. 5
Warranty / Guarantee............................................................... 5
Disposal.................................................................................................. 5
Information for operators
Functioning principle of the heat pump system...... 6
Area of utilization........................................................................ 6
Operation.............................................................................................. 6
Cooling function......................................................................... 7
Care of the unit............................................................................... 8
Maintenance of the unit.......................................................... 8
Malfunctions.................................................................................... 8
Instructions for qualified technicians
Scope of delivery............................................................................. 9
Installation and assembly........................................................ 9
Installation area.................................................................................. 9
Transport to installation location................................................... 9
Installation.........................................................................................10
Installation of the hydraulic connections....................................11
Insulating the hydraulic connections...........................................13
Safety components..........................................................................13
Expansion vessels.............................................................................13
Installation of the heat pump
and heating regulator.....................................................19
Mounting and removal of the screen..........................19
Installation of the room thermostat
for the cooling function.............................................20
Hot-water tank...............................................................................21
Commissioning................................................................................22
Dismantling.......................................................................................23
Technical data/scope of delivery
SWC 60H(/K) – SWC 120H(/K).................................................24
SWC 140H(/K) – SWC 330(/K)..................................................26
Performance curves
Heating Capacity/COP / Power Consumption / Free Compression
SWC 60H(/K)...................................................................................28
SWC 70H(/K)...................................................................................29
SWC 80H(/K)...................................................................................30
SWC 100H(/K).................................................................................31
SWC 120H(/K).................................................................................32
SWC 140H(/K).................................................................................33
SWC 170H(/K).................................................................................34
SWC 230(/K)....................................................................................35
SWC 330(/K)....................................................................................36
Dimensional drawings and clearance dimensions
Size 1: Dimensional drawings........................................................38
Size 1: Clearance dimensions........................................................39
Size 2: Dimensional drawings........................................................40
Size 2: Clearance dimensions........................................................41
Terminal diagrams
SWC 60H(/K) – SWC 170H(/K).................................................42
SWC 230(/K) – SWC 330(/K)......................................................43
Circuit diagrams
SWC 60H(/K) – SWC 80H(/K)....................................................44
SWC 100H(/K) – SWC 170H(/K)...............................................46
SWC 230(/K)....................................................................................48
SWC 330(/K)....................................................................................50
Appendix
Electrical connections.........................................................14
EC declaration of conformity.........................................52
Rinsing and filling the unit..................................................16
Rinsing and filling the heat source...............................................17
Rinsing and filling the heating circuit...........................................17
Cleaning and rinsing of unit components...................................17
General checklist........................................................................53
Bleeding................................................................................................17
Bleeding the unit..............................................................................17
Bleeding the circulating pump of the heating circuit................17
Bleeding the circulating pump of the heat source....................17
Bleeding the heat source
for a unit without cooling function.......................................17
Bleeding the heat source
for a unit with cooling function.............................................18
Completion report for heat pump systems.................55
Notes......................................................................................................57
Customer service
Addresses in the event of a service call.....................................58
Overflow valve................................................................................18
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Intended use
Safety
The unit may be used only for the intended use. This means:
The unit is operational safe when used for the intended purpose. The construction and design of the unit conform to
the state of the art, all relevant DIN/VDE regulations and all
relevant safety regulations.
• for heating.
• for heating hot water.
• for cooling. (Availability of the cooling function depends on
the model).
“Cooling function” section.
Overview “Technical data/scope of delivery”.
Every person who performs work on the unit must comply
with the applicable accident prevention and safety regulations. This applies in particular to the wearing of personal
safety gear.
Notice:
The unit may be operated only within its technical parameters.
Every person who performs work on the unit must have
read and understood the operating manual prior to starting
any work. This also applies if the respective person has already worked with such a unit or a similar unit or has been
trained by the manufacturer.
Notify the responsible power supply company of the use of a heat pump or heat pump
system.
Exclusion of liability
The manufacturer will not be liable for damage resulting
from unauthorized use of the unit.
The manufacturer’s liability will also be voided in the following cases:
Danger!
Unit operates under high electric voltage!
Danger!
Only qualified technicians (trained heating,
cooling, refrigerant and electrical technicians) may perform work on the unit and its
components.
Warning!
Observe safety labels on and in the unit.
Danger!
Unit contains refrigerants!
• if work is performed on the unit and its components in a manner that does not comply with the
terms of this operating manual;
•if work is performed on the unit and its compo-
nents in an improper manner;
Leaking refrigerant could result in personal
injury or material damage.
– Shut down unit.
– Ventilate installation location.
– Notify the manufacturer’s authorized
service center.
• if work is performed on the unit that is not de-
scribed in this operating manual, and this work
was not expressly approved in writing by the
manufacturer;
• if the unit or components in the unit are modified,
redesigned or removed without the express written permission of the manufacturer.
Warning!
Caution.
For safety reasons:
Never disconnect the unit from the power
supply network.
EC conformity
The unit bears the CE mark of conformity.
EC declaration of conformity
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Customer service
For technical assistance, contact the factory customer service department or the manufacturer’s local service partner.
Overview “Customer service”.
Warranty / Guarantee
For warranty and guarantee conditions, please refer to the
purchase documents.
Notice:
Please contact your dealer concerning warranties and guarantees.
Disposal
When decommissioning the unit, always comply with applicable laws, directives and standards for the recovery, recycling
and disposal of materials and components of cooling units.
“Dismantling”.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Functioning principle of
the heat pump system
In a closed circuit, an environmentally compatible refrigerant is successively vaporized, condensed and liquefied. The
increase in pressure resulting from this process also causes
the temperature of the refrigerant to rise. This generates
high temperatures suitable for heating, for example by means
of floor or wall heating, or through radiators.
There are three ways to supply a heat pump with heat energy:
stored heat from the sun in the air, in the earth and in the
ground water. The heat generated from the respective heat
source (air, earth or water) and the heat pump is conveyed
to the heating system by means of a heat exchanger. Generally, water is used as a heating medium, and three types of
pumps - air/water, brine/water and water/water pumps – are
possible. A brine/water pump with floor heating, for example, takes about ¾ of the energy needed for heating from
the environment. Only about ¼ of the energy has to be supplied as electric power.
Example: drawing of a brine/water heat pump with floor
heating:
Operation
Your decision to purchase a heat pump or a heat pump
system is a long-term contribution to protecting the environment through low emissions and reduced primary
energy use.
You can operate and control the heat pump system with the
heat pump and heating regulator.
Notice:
Make sure that the control settings are correct.
Operating manual of the heat pump and heating
regulator.
To ensure that your heat pump or heat pump system operates efficiently and ecologically, the following are especially
important:
Notice:
Avoid unnecessarily high flow temperatures.
A lower flow temperature on the hot water
side increases the efficiency of the system.
When letting in fresh air, do not leave windows open for an
extended period in order to save energy and reduce your
heating costs.
Area of utilization
Taking into consideration the ambient conditions, limits of
application and the applicable regulations, every heat pump
can be utilized in new or existing heating systems.
Overview “Technical data/scope of delivery”.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Cooling function
The cooling function is available only for heat pumps with
the model designator K.
THE ROOM THERMOSTAT FOR THE COOLING FUNCTION
The room thermostat is used to switch the cooling function on and off:
It is not possible to retrofit heat pumps for cooling without
this designator. For the model designator, please refer to the
purchase documents. It is also on the rating plate attached
to the outside of the unit.
ICooling function on
Cooling function off
The heat pump regulation program activates the cooling
function only if the following conditions are fulfilled:
The cooling function is based on the principle of passive
cooling. An existing low temperature level is mixed to a temperature above the dew point and transferred to the heating
medium by means of a heat exchanger. The heat pump remains switched off during cooling; only the circulating pumps
for the heating circuit and the heat source are in operation.
The cooling power depends on the heat source temperature, which varies seasonally. For example, if the ground
stored more heat toward the end of the summer, the cooling power of a brine/water pump is reduced.
The effectiveness of passive cooling is generally not comparable to that of an air conditioning system.
Notice:
The use of the passive cooling function requires floor or wall heating.
• Heat pump model must have integrated cooling
function.
• Room thermostat for the cooling function must
be switched on.
• Temperature of the heat source must be ≥ +5 °C.
• Heat pump must not currently be occupied with
“heating” or “water heating”. If the heat pump regulation program sends the
command “water heating” to the heat pump, the
cooling function of the heat pump automatically
stops as long as the water is heating.
• The “Automatic” settings must be selected on
the heat pump and heating regulator under “Operating mode: cooling”.
• The outdoor temperature release set at the heat
pump and heating regulator must be exceeded.
Operating manual of the heat pump and heating
regulator.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Care of the unit
The outer surfaces of the unit can be cleaned with a damp
cloth and household cleaning products.
Do not use cleaning or care products that contain abrasives,
acids and/or chlorine. Such products would destroy the surfaces and could also damage the technical components of
the unit.
Maintenance of the unit
The cooling circuit of the heat pump requires no regular
maintenance.
The components of the heating circuit and the heat source
(valves, expansion vessels, circulating pumps) should be inspected annually by a qualified technician.
It is a good idea to have a maintenance contract with a
heating installation company. The company will conduct the
required maintenance at regular intervals.
Malfunctions
In the event of a malfunction, you can detect the cause of
the malfunction via the diagnostic program of the heat pump
and heating regulator.
Operating manual of the heat pump and heating
regulator.
Danger!
Service and repair work on the components
of the unit may be performed only by customer service personnel authorized by the
manufacturer.
Overview “Customer service”.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Scope of delivery
Installation and assembly
Example of scope of delivery:
Observe the following when performing all work:
Notice:
Always comply with applicable accident prevention regulations, with applicable statutory regulations, ordinances and directives.
Warning!
The heat pump or heat pump system may
be installed and assembled only by a qualified
technician!
Notice:
Observe the sound levels of the respective
model.
Overview “Technical data/scope of delivery”,
“Sound” section.
1Compact unit
2 Screen
3Vibration decouplers (only
for size 1 units)
4Expansion vessel for heat circuit
5 Safety components for heat
circuit and heat source
6Package with heat pump and heating
regulator, outdoor temperature
sensor, seals, sylomer strips, cap
valve and wall mount for heating
circuit expansion vessel, room
thermostat for cooling function
(only for models with designator
K), compensators (only for size 2
units; in additional cardboard box)
Proceed as follows:
Inspect delivery for outwardly visible signs of
damage…
Check to make sure that delivery is complete. Any defects or incorrect deliveries must be claimed
immediately.
Notice:
Note the model.
Installation area
Caution.
Install the heat pump only indoors.
The installation area must be frost-free and dry. It must meet
the requirements of DIN EN 378. It must also fulfill applicable local regulations.
Transport to installation location
To avoid damage during transport, you should transport the
unit to the final installation location in its original packaging (with angle bracket on the wooden pallet), using a lifting
truck.
If it is not possible to transport the unit to the final installation location using a lifting truck, you can also transport the
heat pump using a hand truck.
Danger!
Several people are required to transport the
unit. Do not underestimate the weight of the
heat pump.
Overview “Technical data/scope of delivery”, “General unit data” section.
Overview “Technical data/scope of delivery” or
rating plate on unit.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Danger!
The unit can tip when being removed from
the wooden pallet and during transport with
a hand truck. This can result in personal
injury and damage to the unit.
Installation
Danger!
Several people are required to install the
unit.
– Take suitable precautionary measures
to eliminate the danger of tipping.
We recommend removing the front panel to reduce the
weight of the unit for further transport.
Notice:
Take into account the size of the unit.
Overview “Technical data/scope of delivery”, “General unit data” section.
Loosen quick-release screws for the front panel.
Turn counter-clockwise 90°…
Notice:
Always comply with required clearance dimensions.
Overview “Dimensional drawings” and “Clearance
dimensions” for the respective size.
Lift front panel and set aside in a safe place.
Proceed as follows at the installation location:
Danger!
Make sure to secure unit against slipping
during transport.
Caution.
Caution.
Do not tilt the unit more than a maximum of
45° (in any direction).
The sylomer strips also provide for added stability
of the heat pump.They absorb sound and vibrations
transmitted to the underlying surface.
Place the sylomer strips under the heat pump as
follows:
10
Set unit on a solid and level, preferably sound-insulated surface…
Compensate for minor unevenness using the provided sylomer strips…
Caution.
Do not damage the hydraulic connections
under any circumstances.
Dispose of angle bracket, transport and packaging
material properly and in accordance with ecological
principles.
Never use components and hydraulic connections on the unit for purposes of transport.
Remove angle bracket, transport and packaging material from the unit…
•
Tip the unit slowly and carefully to one side…
Caution.
Never tilt the unit more than a maximum of
45°.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Warning!
Hands and fingers could be crushed during
the following tasks!
Secure unit in raised position so that it cannot accidentally tip back into the original position.
Installation of the hydraulic connections
Caution.
The heat source system must be designed
according to the specifications of the heat
pump guide.
•
Place one sylomer strip flush with the respective
outer edge of the unit…
Heat pump guide and “Hydraulic connection” instructions.
Notice:
Check to make sure that the diameters and
lengths of the pipes for the heating circuit
and the heat source are sufficiently dimensioned. The free compression of the circulating pumps must be able to deliver at least the
minimum flow rate required for your model.
Overview “Technical data/scope of delivery”, “Heat
source” and “Heating circuit” sections.
Danger!
•
Slowly and carefully tip the unit back into the original position…
Repeat steps •
sides of the unit.
through
•
Disconnect unit from power supply if it is
connected to the power supply!
Proceed as follows:
for the remaining
Place sylomer strips at right angles to each other,
with no space in between:
Install shut-off devices at the heating circuit…
Install shut-off devices at the heat source.
Notice:
During installation of the shut-off devices, the
compressor and liquefier of the heat pump
can be rinsed, if necessary.
Caution!
The condenser may be rinsed only by customer service personnel authorized by the
manufacturer.
Operating side
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Caution.
When installing the connections, always
secure the connections on the unit from
twisting, in order to prevent damage to the
copper pipes in the interior of the unit.
11
The connections for the heating circuit or the heat source
are located on the back of the unit:
installation on size 1 units
Proceed as follows:
We recommend installing a contamination filter
(screen size 0.9 mm) on the heat source inflow
(return flow) connection…
Connect the pipes of the heating circuit and the
heat source with the corresponding connections on
the back of the unit. Use vibration decouplers.
These are included in the scope of delivery. They must be
installed in order to prevent damage from vibrations to the
pipes.
Arrange the vibration decouplers in a quarter circle, as
shown in the following drawing:
1
2
3
4
Hot water outflow (forward flow)
Hot water inflow (return flow)
Heat source inflow (return flow)
Heat source outflow (forward flow)
A straight or extended hose arrangement for the vibration
decoupler is not permitted.
12
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
installation on size 2 units
Insulating the hydraulic connections
The included compensators must be used for connection
to the pipes:
The vibration decouplers and the pipes of the heat source
must be insulated so that they are sealed against vapor diffusion.
The compensators also serve as vibration decouplers.
Notice:
Insulate in accordance with applicable local
standards and directives.
Safety components
The compensators are packed in the extra box.
The safety components are packed in the extra box.
Proceed as follows:
The connections for the safety components are located at
the top rear on the outside of the unit.
We recommend installing a contamination filter
(screen size 0.9 mm) on the heat source inflow
(return flow) connection…
Screw the compensators by hand onto the connections on the unit until they bear against the rubber
gasket…
Screw the compensators by hand onto the pipes of
the heating circuit and the heat source until they
bear against the rubber gasket…
Using a suitable tool (e.g. a pipe wrench) to tighten
all connections one or two turns to achieve a tight
seal.
Do not overtighten. The rubber part of the compensators must not become twisted (torsion). This
could cause malfunctions and even serious damage
to the unit.
1Connection for heating
circuit safety component
2Connection for heat source
safety component
Proceed as follows:
Install safety component for the heating circuit…
Install safety component for the heat source.
Expansion vessels
The expansion vessel for the heat source is integrated in
the unit.
The expansion vessel for the heating circuit and the corresponding cap valve are included in the scope of delivery.They
must be integrated in the heating circuit on-site in compliance with the applicable standards and directives.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
13
Electrical connections
Observe the following when performing all work:
Danger!
Electrical connections may be installed only
by qualified electricians.
Danger!
Observe the relevant EN, VDE and/or applicable local safety regulations during the installation and during all electrical work.
Observe the technical connection conditions
of the responsible power supply company!
Loosen quick-release screws for the front panel.
Turn counter-clockwise 90°…
2 Size 2:
Switch cabinet closed.
Insert load and control leads in the openings provided on the back of the unit…
Lift front panel and set aside in a safe place…
Open electric switch cabinet (inside the unit on the
left)…
1 Cable duct size 1:
2Cable duct size 2:
1 Size 1:
Switch cabinet closed.
14
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Lay load and control leads in the cable duct inside
the unit all the way to the switch cabinet…
Caution.
Ensure clockwise rotary field of the load
power supply.
– An incorrect rotary field of the condenser during operation can cause
serious, irreparable damage to the condenser.
Caution.
Make sure to equip the power supply of the
heat pump with an all-pole circuit breaker.
The all-pole circuit breaker must have a contact gap
of at least 3mm.
Caution.
1 Size 1:
Switch cabinet opened.
Make sure to equip the power supply of the
heat pump with a 3-pole automatic cut-out.
Note the level of the release current.
Overview “Technical data/scope of delivery”, “Electric” section.
After completion of all electrical installation work,
close the switch cabinet inside the unit…
Screw on the front panel of the unit if no further
installation work inside the unit is to be performed
immediately.
2 Size 2:
Switch cabinet opened.
Install electrical connections according to the terminal diagram and the circuit diagrams…
„Terminal diagrams” and “Circuit diagrams” for the
respective model.
Danger!
Install electric connections only according
to the terminal diagram and the circuit diagrams that apply to your model.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
15
Rinsing and filling the unit
Size 2:
Danger!
Unit must be disconnected from the power
supply.
Open unit if this has not already been done…
Electrical connection work
and
.
Obtain overview of the interior of the unit.
Danger!
The electric switch cabinet inside the unit
must be closed with the cabinet’s cover!
Size 1:
1 Safety component for heating circuit
2 Safety component for heat source
3 Servo-motor at mixing valve (only
on units with model designator K)
4Overflow valve
5Circulating pump for heat source
6Expansion vessel for heat source
7Fill/empty cock for heat source
8Circulating pump for heating circuit
9Fill/empty cock for heating circuit
1 Safety component for heating circuit
2 Safety component for heat source
3 Servo-motor at mixing valve (only
on units with model designator K)
4Overflow valve
5Electric heating element
6Circulating pump for heat source
7Circulating pump for heating circuit
8Fill/empty cock for heat source
9Expansion vessel for heat source
10Fill/empty cock for heating circuit
16
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Rinsing and filling the heat source
Bleeding
Contamination and deposits in the heat source can cause
malfunctions.
Proceed as follows:
Place a bleeder at the highest point of the heat source
in the heat source outflow (forward flow)…
Proceed as follows:
Rinse heat source system thoroughly…
Thoroughly mix the anti-freeze agent, available as an
accessory, with water at the required ratio.Add only
anti-freeze mixed with water to the heat source…
The concentration of anti-freeze in the water
must be at least at the level specified for your
model.
Overview “Technical data/scope of delivery”, “Heat
source” section.
Check concentration of anti-freeze in the mixture…
Fill heat source with the anti-freeze mixture.
Rinsing and filling the heating circuit
Contamination and deposits in the heating circuit can cause
malfunctions.
Rinse heating circuit system thoroughly…
Fill heating circuit.
Cleaning and rinsing of unit components
Caution.
If necessary, place a bleeder at the highest point of
the heat source in the heat source inflow (return
flow)…
Place a bleeder at the highest point of the heating circuit in the heating circuit outflow (forward
flow)…
Caution.
If necessary, place a bleeder at the highest point
of the heating circuit in the heating circuit inflow
(return flow).
Bleeding the unit
The unit is bled automatically when the bleeders of the
safety components are open. If the heating circuit or heat
source is filled or emptied, the bleeding valves of the respective safety components open.
Bleeding the circulating pump of the heating circuit
Loosen the screw-on cap in the middle of the circulating
pump.
Bleeding the circulating pump of the heat source
Loosen the screw-on cap in the middle of the circulating
pump.
Unit components may be cleaned and rinsed
only by customer service personnel authorized by the manufacturer. Use only liquids
recommended by the manufacturer.
Rinsing of the liquefier with chemical cleaning agents must be followed by neutralization of residue and intensive rinsing with
water. Always observe the technical data of
the manufacturer of the heat exchanger.
Bleeding the heat source for a unit without cooling function
Bleeding is conducted automatically by means of the integrated bleeding function in the safety component.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
17
Bleeding the heat source for a unit with cooling function
The bleeding must be conducted manually.
Proceed as follows:
Release the servo-motor at the mixing valve inside
the unit…
Push switch on servo-motor down…
•
After 2 minutes, with the circulating pump running,
turn wrench clockwise until the regulator of the
servo-motor is at 100 %…
Leave at this setting for 2 minutes…
•
With the circulating pump running, turn wrench
counter-clockwise until the regulator of the servomotor is at 50 %…
Turning the regulator to 50 % means an even mixture in the 3-way mixing valve from A and B to AB.
Reset servo-motor of the mixing valve to automatic
as soon as bleeding is completed.
Adjust mixing valve…
Use the wrench included in the scope of delivery.
Alternatively: Use a size 6 Allen wrench.
•
Insert wrench in the servo-motor…
•
Switch on the circulating pump of the heat source
and allow to run…
Notice:
Push switch on servo-motor up.
•
Turn wrench counter-clockwise until the regulator
of the servo-motor is at 0 %…
Overflow valve
Set the overflow valve so that the spread between the forward and return flow is ≤ 10K (set at the factory to 200
mbar and sealed by paint).
18
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Installation of the heat pump
and heating regulator.
Suspend the heat pump and heating regulator in the
two square recesses in the front panel…
Lay the control cable for the regulator from the
inside of the unit through the sleeve in the front
panel to the outside…
Install the front panel on the unit…
Insert the control cable into the bushing provided
on the bottom of the heat pump and heating regulator.
Mounting and removal of the
screen
First, insert the screen at the bottom in the slot
provided on the front panel of the heat pump…
First, insert snap-in lugs on one side of the screen
from bottom to top in the slots provided on the
front panel of the unit…
Then, insert snap-in lugs on the other side of the
screen from bottom to top in the slots provided
on the front panel of the unit…
Finally, press the upper snap-in lugs of the screen
into the slots provided.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
19
Notice:
To remove the screen, release the snapin lugs in the reverse order, i.e. from top to
bottom, without the use of tools.
Caution.
The snap-in lugs have a tight fit. Press firmly
from the side against the screen toward the
middle, so that the snap-in lugs do not break
off.
Installation of the room
thermostat for the cooling
function
This chapter is relevant for you only if you are using a heat
pump with a model designator K.
Caution.
If floor heating systems are to be used for
cooling, the manufacturer must approve the
floor structure (especially the screed) for use
of the cooling function.
Use the room thermostat of the cooling function in a reference room as a reference variable. If the temperature in the
reference room falls below the set temperature, the cooling
function of the heat pump will automatically shut off.
Operating manual of the heat pump and heating
regulator, “Cooling” chapter.
Notice:
You must install the room thermostat in a
reference room in addition to single-room
regulators.
You must install single-room regulators for switching from heating to cooling (and vice versa).
20
Notice:
Always comply with the applicable standards
and directives.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Hot-water tank
If the heat pump will be used for heating hot water, you must
integrate special hot-water tanks in the heat pump system.
Notice:
The hot-water tank must be equipped with a
heat exchanger, which is adapted to the heating capacity of the heat pump.
We offer a variety of hot-water tanks for you to choose
from. They are optimized for use with your heat pump.
Notice:
Integrate the hot-water tank in the heat
pump system corresponding to the hydraulic
diagram for your system.
For heating hot water, you must install a 3-way switching
valve in the hot water outflow (forward flow).
The 3-way switching valve is an accessory and is not included in the scope of delivery.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
21
Commissioning
Proceed as follows:
The heat pump system will be commissioned by
customer service personnel authorized by the manufacturer. There is a fee for commissioning!
Conduct a thorough installation inspection and go
through the items on the general checklist.
“General checklist”.
The installation inspection will prevent damage to
the heat pump system that could be caused by incorrect installation work.
Make sure of the following:
• Clockwise rotary field of the load power
supply (condenser).
• Installation and assembly of the heat pump ac-
cording to the information in this operating manual.
• All electric installation work must be properly
completed.
• Installation of an all-pole circuit breaker must be
installed for the condenser. It must have a contact
gap of at least 3 mm. A 3-pole automatic cut-out
must be installed.
• The heating circuit and the heat source must be
rinsed, filled and bled thoroughly.
• All valves and shut-off devices of the heating circuit must be open.
• All valves and shut-off devices of the heat source
must be open.
• All pipe systems and components of the system
must be sealed.
Carefully fill out and sign the completion report for
heat pump systems.
“Completion report for heat pump systems”.
In Germany:
Send completion report for heat pump systems to
the manufacturer’s factory customer service department.
Outside of Germany:
Send completion report for heat pump systems to
the manufacturer’s local partner.
Overview “Customer service”.
22
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Dismantling
Danger!
Disconnect unit from power supply before
dismantling!
Danger!
Only qualified electrical technicians are allowed to disconnect the unit from the power
supply and de-install all electrical connections.
Danger!
Only qualified heating or cooling system
technicians are allowed to remove the unit
from the system.
Caution.
The anti-freeze mixture of the heat source
must not be allowed to enter the sewer
system.
Collect anti-freeze mixture and dispose of
properly.
Danger!
Only qualified cooling system technicians are
allowed to dismantle the unit and its components.
Caution.
Recycle or provide for proper disposal of unit
components, refrigerants and oil in accordance with the applicable regulations, standards and directives.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
23
Technical data/scope of delivery
Gerätebezeichnung
Heat pump type
Brine/water ı Air/water ı Water/water
• applicable ı — not applicable
Installation location
Indoors ı Outdoors
• applicable ı — not applicable
Conformity
Performance data
Limits of application
Sound
CE
Heating capacity/COP at
B0/W35
Standard point acc. to EN14511
B0/W45
Standard point acc. to EN14511
B0/W35
Standard point acc. to EN255
2 condensers
1 condensers
kW ı …
kW ı …
kW ı …
2 condensers
1 condensers
kW ı …
kW ı …
Heating circuit
°C
Heat source
°C
Additional operating points
…
Sound level measured at distance of 1m around the device (in reverberating room)
Heat source
dB(A)
Sound power level according to EN12102
dB
Volume flow: minimum flow rate ı nominal flow rate ı maximum flow rate
l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Anti-freeze agent
monoethylene glycol
minimum concentration ı frost proof down to
Heating circuit
General unit data
% ı °C
Volume flow: minimum flow rate ı nominal flow rate ı maximum flow rate
l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Dimensions (see dimensional drawing for the specified unit size)
unit size
Total weight (including cooling)
kg (kg)
Additional weight module 1
kg
Additional weight module 2
kg
Connections
Heating circuit
…
Heat source
Refrigerant
Electric
…
Refrigerant type ı Quantity
… ı kg
Voltage code ı all-pole circuit breaker heat pump *)
…ı A
Voltage code ı circuit breaker control voltage *)
…ı A
Voltage code ı circuit breaker electric heating element *)
Heat Pump
ı A
Effective power consumption in standard point B0/W35 according to EN14511: Power consumption ı current consumption ı cosφ
Maximum device current within the limits of application
A
Starting current: direct ı with soft starter
A ı A
Protection type
IP
Output electric heating element 3 ı 2 ı 1 phase
Components
kW ı kW ı kW
Circulating pump heating circuit at nominal flow rate: Power consumption ı current consumption
kW ı A
Circulating pump heat source at nominal flow rate: Power consumption ı current consumption
kW ı A
Passive cooling function
only for units with designator K: Cooling output at nominal volume flow (15 °C heat source, 25 °C heating water)
Safety equipment
Safety component heating circuit ı Safety component heat source
Heating and heat pump regulator
integrated: • yes — no
Heat source: Scope of delivery ı Volume ı Initial pressure
• yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure
• yes — no ı l ı bar
Overflow valve
Vibration decouplers
UK813196
24
kW
scope of delivery: • yes — no
scope of delivery: • yes — no
Electronic soft starter
Expansion vessels
kW ı A ı …
integrated: • yes — no
Heating circuit ı heat source
scope of delivery: • yes — no
*) comply with local regulations
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
n.n. = not detectable
SWC 60H(/K)
SWC 70H(/K)
SWC 80H(/K)
SWC 100H(/K)
SWC 120H(/K)
• ı — ı —
• ı — ı —
• ı — ı —
• ı — ı —
• ı — ı —
• ı —
• ı —
• ı —
• ı —
• ı —
•
•
•
•
•
—
5,7 ı 4,4
—
6,9 ı 4,4
—
8,9 ı 4,5
—
10,2 ı 4,6
—
11,7 ı 4,5
—
—
—
—
—
—
5,8 ı 4,7
—
7,0 ı 4,5
—
9,1 ı 4,7
—
10,3 ı 4,7
—
11,9 ı 4,7
20 – 65
20 – 65
20 – 65
20 – 65
20 – 62
-5 – 25
-5 – 25
-5 – 25
-5 – 25
-5 – 25
—
—
—
—
B–2 ı W65
40
40
40
40
40
53
53
53
53
53
1000 ı 1400 ı 2500
1250 ı 1650 ı 2500
1450 ı 1900 ı 4000
1600 ı 2200 ı 3500
1800 ı 2600 ı 3900
— ı —
— ı —
— ı —
— ı —
— ı —
0,52 (0,5) ı 1100
0,48 (0,46) ı 1250
0,68 (0,66) ı 1450
0,53 (0,50) ı 1600
0,51 (0,49) ı 2050
•
•
•
•
•
25 ı -13
25 ı -13
25 ı -13
25 ı -13
25 ı -13
500 ı 950 ı 1400
600 ı 1200 ı 1500
800 ı 1500 ı 1900
900 ı 1800 ı 2200
1000 ı 2000 ı 2400
— ı —
— ı —
— ı —
— ı —
— ı —
0,46 (0,45) ı 700
0,47 (0,46) ı 850
0,41 (0,40) ı 1100
0,34 (0,33) ı 1300
0,32 (0,30) ı 1450
1
1
1
1
1
200 (214)
202 (216)
203 (218)
206 (221)
209 (224)
—
—
—
—
—
—
—
—
—
—
G1"AG
G1“AG
G1"AG
G1"AG
G1¼"AG
G1"AG
G1“AG
G1"AG
G1"AG
G1¼"AG
R407c ı 1,8
R407c ı 2,0
R407c ı 2,1
R407c ı 2,2
R407c ı 2,9
3~/PE/400V/50Hz ı C10
3~/PE/400V/50Hz ı C10
3~/PE/400V/50Hz ı C10
3~/PE/400V/50Hz ı C10
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C10
3~/N/PE/400V/50Hz ı C10
3~/N/PE/400V/50Hz ı C10
3~/N/PE/400V/50Hz ı C10
3~/N/PE/400V/50Hz ı C10
1,29 ı 2,4 ı 0,78
1,57 ı 3,1 ı 0,73
1,98 ı 3,7 ı 0,78
2,22 ı 4,1 ı 0,78
2,6 ı 4,8 ı 0,78
4,0
5,0
5,9
6,9
7,5
27,4 ı —
29 ı —
30 ı —
— ı 20
— ı 25
20
20
20
20
20
6 ı 4 ı 2
6 ı 4 ı 2
6 ı 4 ı 2
6 ı 4 ı 2
6 ı 4 ı 2
0,08 ı n.n.
0,08 ı n.n.
0,08 ı n.n.
0,08 ı n.n.
0,08 ı n.n.
0,1 ı n.n.
0,2 ı n.n.
0,2 ı n.n.
0,2 ı n.n.
0,2 ı n.n.
3,7
5,3
6,9
8,3
10,2
• ı •
• ı •
• ı •
• ı •
• ı •
•
•
•
•
•
—
—
—
•
•
• ı 12 ı 0,5
• ı 12 ı 0,5
• ı 12 ı 0,5
• ı 12 ı 0,5
• ı 18 ı 0,5
• ı 25 ı 1,5
• ı 25 ı 1,5
• ı 25 ı 1,5
• ı 25 ı 1,5
• ı 25 ı 1,5
•
•
•
•
•
• ı •
• ı •
• ı •
• ı •
• ı •
813169-a
813190
813170-a
813171-a
813172-a
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
25
Technical data/scope of delivery
Gerätebezeichnung
Heat pump type
Brine/water ı Air/water ı Water/water
• applicable ı — not applicable
Installation location
Indoors ı Outdoors
• applicable ı — not applicable
Conformity
Performance data
Limits of application
Sound
CE
Heating capacity/COP at
B0/W35
Standard point acc. to EN14511
B0/W45
Standard point acc. to EN14511
B0/W35
Standard point acc. to EN255
2 condensers
1 condensers
kW ı …
kW ı …
kW ı …
2 condensers
1 condensers
kW ı …
kW ı …
Heating circuit
°C
Heat source
°C
Additional operating points
…
Sound level measured at distance of 1m around the device (in reverberating room)
Heat source
dB(A)
Sound power level according to EN12102
dB
Volume flow: minimum flow rate ı nominal flow rate ı maximum flow rate
l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Anti-freeze agent
monoethylene glycol
minimum concentration ı frost proof down to
Heating circuit
General unit data
% ı °C
Volume flow: minimum flow rate ı nominal flow rate ı maximum flow rate
l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı volume flow
bar (bar) ı l/h
Dimensions (see dimensional drawing for the specified unit size)
unit size
Total weight (including cooling)
kg (kg)
Additional weight module 1
kg
Additional weight module 2
kg
Connections
Heating circuit
…
Heat source
Refrigerant
Electric
…
Refrigerant type ı Quantity
… ı kg
Voltage code ı all-pole circuit breaker heat pump *)
…ı A
Voltage code ı circuit breaker control voltage *)
…ı A
Voltage code ı circuit breaker electric heating element *)
Heat Pump
ı A
Effective power consumption in standard point B0/W35 according to EN14511: Power consumption ı current consumption ı cosφ
Maximum device current within the limits of application
A
Starting current: direct ı with soft starter
A ı A
Protection type
IP
Output electric heating element 3 ı 2 ı 1 phase
Components
kW ı kW ı kW
Circulating pump heating circuit at nominal flow rate: Power consumption ı current consumption
kW ı A
Circulating pump heat source at nominal flow rate: Power consumption ı current consumption
kW ı A
Passive cooling function
only for units with designator K: Cooling output at nominal volume flow (15 °C heat source, 25 °C heating water)
Safety equipment
Safety component heating circuit ı Safety component heat source
Heating and heat pump regulator
integrated: • yes — no
Heat source: Scope of delivery ı Volume ı Initial pressure
• yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure
• yes — no ı l ı bar
Overflow valve
Vibration decouplers
UK813196
26
kW
scope of delivery: • yes — no
scope of delivery: • yes — no
Electronic soft starter
Expansion vessels
kW ı A ı …
integrated: • yes — no
Heating circuit ı heat source
scope of delivery: • yes — no
*) comply with local regulations
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
n.n. = not detectable
SWC 140H(/K)
SWC 170H(/K)
SWC 230(/K)
SWC 330(/K)
• ı — ı —
• ı — ı —
• ı — ı —
• ı — ı —
• ı —
• ı —
• ı —
• ı —
•
•
•
•
—
13,7 ı 4,5
—
16,7 ı 4,6
—
22,1 ı 4,3
31,8 ı 4,1
17,6 ı 4,5
—
—
—
—
—
13,9 ı 4,7
—
16,9 ı 4,7
—
22,5 ı 4,5
32,0 ı 4,3
17,9 ı 4,6
20 – 65
20 – 65
20 – 55
20 – 55
-5 – 25
-5 – 25
-5 – 25
-5 – 25
—
—
—
—
42
43
47
47
55
56
60
60
2350 ı 3100 ı 4700
2700 ı 3600 ı 5000
3700 ı 4900 ı 5900
5900 ı 7900 ı 10000
— ı —
— ı —
— ı —
— ı —
0,43 (0,41) ı 2350
0,36 (0,33) ı 2700
0,74 (0,68) ı 3700
0,42 (0,35) ı 5950
•
•
•
•
25 ı -13
25 ı -13
25 ı -13
25 ı -13
1200 ı 2400 ı 2900
1400 ı 2900 ı 3500
1900 ı 3900 ı 4500
2700 ı 5200 ı 6900
— ı —
— ı —
— ı —
— ı —
0,59 (0,57) ı 1700
0,58 (0,55) ı 2050
0,41 (0,38) ı 2700
0,70 (0,67) ı 3900
1
1
2
2
212 (227)
220 (235)
345 (360)
372 (390)
—
—
—
—
—
—
—
—
G1¼"AG
G1¼"AG
R1½"IG
R1½"IG
G1¼"AG
G1¼"AG
R1½"IG
R1½"IG
R407c ı 2,7
R407c ı 3,6
R407c ı 4,45
R407c ı 6,85
3~/PE/400V/50Hz ı C13
3~/PE/400V/50Hz ı C13
3~/PE/400V/50Hz ı C16
3~/PE/400V/50Hz ı C25
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C16
3~/N/PE/400V/50Hz ı C16
—
—
3,0 ı 5,8 ı 0,75
3,63 ı 6,7 ı 0,78
5,14 ı 9,5 ı 0,78
7,76 ı 14,4 ı 0,78
9,4
11,0
12,5
23,6
— ı 28
— ı 30
— ı 29,5
— ı 22
20
20
20
20
9 ı 6 ı 3
9 ı 6 ı 3
— ı — ı —
— ı — ı —
0,2 ı n.n.
0,2 ı n.n.
0,2 ı n.n.
0,36 ı n.n.
0,25 ı n.n.
0,25 ı n.n.
0,35 ı n.n.
0,35 ı n.n.
9,8
9,0
16,2
26,5
• ı •
• ı •
• ı •
• ı •
•
•
•
•
•
•
•
•
• ı 18 ı 0,5
• ı 18 ı 0,5
• ı 24 ı 0,5
• ı 24 ı 0,5
• ı 35 ı 1,5
• ı 35 ı 1,5
• ı 50 ı 1,5
• ı 50 ı 1,5
•
•
•
•
• ı •
• ı •
• ı •
• ı •
813173-a
813174-a
813175-a
813176-a
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
27
SWC 60H(/K)
Performance curves
Qh (kW)
COP
12
8
7
6
5
4
10
3
2
1
-10
8
-5
0
5
10
15
20
25
30
15
20
25
30
3,0
3,5
Temp„ (°C)
Pe (kW)
6
3
2
4
35°C
1
50°C
65°C
2
-10
-5
0
5
10
15
20
25
0
30
-10
-5
0
5
10
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
0,8
0,8
0,7
0,7
0,6
0,6
0,5
0,5
0,4
0,4
0,3
0,3
0,2
0,2
0,1
0,1
0,0
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
0,0
0,5
“”[m3/h]
ǻp”
1,0
1,5
2,0
2,5
“„[m3/h]
ǻp”†
ǻp„
ǻp„†
823000
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
28
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
SWC 70H(/K)
Performance curves
Qh (kW)
COP
14
8
7
6
5
4
12
3
2
1
-10
10
-5
0
5
10
15
20
25
30
15
20
25
30
3,0
3,5
Temp„ (°C)
Pe (kW)
8
5
4
3
6
35°C
2
50°C
1
65°C
4
-10
-5
0
5
10
15
20
25
0
30
-10
-5
0
5
10
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
0,8
0,8
0,7
0,7
0,6
0,6
0,5
0,5
0,4
0,4
0,3
0,3
0,2
0,2
0,1
0,1
0,0
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
0,0
0,5
1,0
“”
ǻp”
1,5
2,0
2,5
“„
ǻp”†
ǻp„
ǻp„†
823023
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
29
SWC 80H(/K)
Performance curves
Qh (kW)
COP
16
8
7
6
5
4
14
3
2
1
-10
12
-5
0
5
10
15
20
25
30
20
25
30
Temp„ (°C)
Pe (kW)
10
5
4
3
8
35°C
2
50°C
1
65°C
6
-10
-5
0
5
10
15
20
25
0
30
-10
-5
0
5
10
15
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
0,0
“”[m3/h]
ǻp”
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
“„[m3/h]
ǻp„
ǻp”†
ǻp„†
823001
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
30
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Performance curves
SWC 100H(/K)
Qh (kW)
COP
18
8
7
6
5
16
4
3
2
14
1
-10
-5
0
5
10
15
20
25
30
20
25
30
Temp„ (°C)
12
Pe (kW)
6
10
5
8
4
35°C
50°C
3
65°C
6
-10
-5
0
5
10
15
20
25
2
30
-10
-5
0
5
10
15
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
0,0
0,5
1,0
1,5
ǻp”
2,0
2,5
3,0
3,5
4,0
4,5
5,0
“„[m3/h]
“”[m3/h]
ǻp„
ǻp”†
ǻp„†
823002
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
31
SWC 120H(/K)
Performance curves
Qh (kW)
COP
22
8
7
6
20
5
4
3
18
2
1
-10
-5
0
5
10
15
20
25
30
20
25
30
16
Temp„ (°C)
14
Pe (kW)
6
12
5
4
35°C
10
50°C
3
65°C
8
-10
-5
0
5
10
15
20
25
2
30
-10
-5
0
5
10
15
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
0,0
0,5
ǻp”
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
“„[m3/h]
“”[m3/h]
ǻp„
ǻp”†
ǻp„†
823003
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
32
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Performance curves
SWC 140H(/K)
Qh (kW)
COP
24
8
7
6
22
5
4
3
20
2
1
18
-10
-5
0
5
10
15
20
25
30
20
25
30
Temp„ (°C)
16
Pe (kW)
14
8
7
12
6
5
35°C
10
50°C
4
65°C
3
8
-10
-5
0
5
10
15
20
25
2
30
-10
-5
0
5
10
15
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
0,0
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
“„[m3/h]
“”[m3/h]
ǻp”
0,5
ǻp„
ǻp”†
ǻp„†
823004
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
33
SWC 170H(/K)
Performance curves
Qh (kW)
COP
30
8
7
6
28
5
4
26
3
2
24
1
-10
-5
0
5
10
15
20
25
30
20
25
30
22
Temp„ (°C)
20
Pe (kW)
8
18
7
6
16
5
35°C
14
50°C
4
65°C
3
12
-10
-5
0
5
10
15
20
25
2
30
-10
-5
0
5
10
15
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
0,0
0,5
ǻp”
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
“„[m3/h]
“”[m3/h]
ǻp„
ǻp”†
ǻp„†
823005
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
34
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Performance curves
SWC 230(/K)
Qh (kW)
COP
38
8
7
36
6
5
34
4
3
32
2
1
30
-10
-5
0
5
10
15
20
25
30
15
20
25
30
7,0
8,0
28
Temp„ (°C)
26
Pe (kW)
24
8
7
22
6
20
5
35°C
18
50°C
4
65°C
3
16
-10
-5
0
5
10
15
20
25
2
30
-10
-5
0
5
10
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,2
1,1
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
0,0
1,0
2,0
3,0
“”[m3/h]
ǻp”
4,0
5,0
6,0
“„[m3/h]
ǻp„
ǻp”†
ǻp„†
823006
Legende: DE823000L
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
Legend:
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
35
SWC 330(/K)
Performance curves
Qh (kW)
COP
66
64
62
60
58
56
54
52
50
48
46
44
42
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
9
8
7
6
5
4
3
2
-10
-5
0
5
10
15
20
25
30
20
25
30
Temp„ (°C)
Pe (kW)
12
11
10
9
8
7
6
5
4
3
35°C 2VD
50°C 2VD
35°C 1VD
50°C 1VD
-10
-5
0
5
10
15
20
25
30
-10
-5
0
5
10
15
Temp„ (°C)
Temp„ (°C)
∆p (bar)
∆p (bar)
1,2
1,1
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
1,2
1,1
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0
1,0
2,0
3,0
4,0
5,0
6,0
7,0
8,0
0,0
1,0
ǻp”
2,0
3,0
4,0
5,0
6,0
7,0
8,0
9,0
“„[m3/h]
“”[m3/h]
ǻp„
ǻp”†
ǻp„†
823007
Legende: DE823000L
Legend:
“”
Volumenstrom Heizwasser
“„
Volumenstrom Wärmequelle
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe
Leistungsaufnahme
COP
Coeffiicient of performance / Leistungszahl
UK823000L/170408
“”
Volume flow, heating water
“„
Volume flow, heat source
Temp„
Temperature, heat source
Qh
Heating capacity
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p” / ∆p”†
Free compression, heating circuit / free compression, heating circuit with cooling
∆p„ / ∆p„†
Free compression, heat source / free compression, heat source with cooling
VD
Condensers
36
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
37
Size 1: Dimensional drawings
Legend:
UK819248a
All dimensions in mm.
A
Front view
B
Top view
C
Rear view
D
Control element
1
Heating water outflow (forward flow) DIN ISO 228
SWC 60… to SWC 100…: G1"AG
SWC120… to SWC 170…: G1¼"AG
2
Heating water inflow (return flow) DIN ISO 228
SWC 60… to SWC 100…: G1"AG
SWC120… to SWC 170…: G1¼"AG
3
Heat source inflow (return flow) DIN ISO 228
SWC 60… to SWC 100…: G1"AG
SWC120… to SWC 170…: G1¼"AG
4
Heat source outflow (forward flow) DIN ISO 228
SWC 60… to SWC 100…: G1"AG
SWC120… to SWC 170…: G1¼"AG
38
5
Ducts for electric/sensor cables
6
Safety components
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Size 1: Clearance dimensions
Legend:
UK819252b
All dimensions in mm.
A
Room height ≥ 2000
B
Unit installation on sylomer strips
C
Top edge of finished floor
D
Distance to next lateral object ≥ 20
E
Shaded area = free space for service purposes
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
39
Size 2: Dimensional drawings
Legend:
UK819253a
All dimensions in mm.
A
Front view
B
Top view
C
Rear view
D
Control element
1
Heating water outflow (forward flow) DIN 2999 R1½"AG
2
Heating water inflow (return flow) DIN 2999 R1½"AG
3
Heat source inflow (return flow) DIN 2999 R1½"AG
4
Heat source outflow (forward flow) DIN 2999 R1½"AG
5
Ducts for electric/sensor cables
6
Safety components
Attention! Included in scope of delivery:
4 x compensator DN 40, Rp 1½"IG DIN 2999
40
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Size 2: Clearance dimensions
Legend:
UK819255b
All dimensions in mm.
A
Room height ≥ 2000
B
Unit installation on sylomer strips
C
Top edge of finished floor
D
Distance to next lateral object ≥ 20
E
Shaded area = free space for service purposes
F
In the event of offset mounting of the compensators the dimension 400 can be
reduced to ≥ 250.
The bracket must be provided by the customer.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
41
1
Zustand
-F12
Änderung
N
5
L1
20.02.2007
L1
Name
2
N
PE
2
6
4
1
2
5
2
3
EVU
7
-Y3
P
ASD
9
MZ1
MIS
M
11
GND
PEX
10
A1
ZW2/SST
ZW2/SST
-X4
12
13
6 - 17 kW
TRL
-X3
M
ZUP/ZIP
BUP
MA1
8
MOT
EVU
FP1
RFV
TB1
Ers. durch
SWC 60-170 terminal diagram
831120a
Brine pressure pressostat; provided by cust. if necessary
Accessories: Process water for changeover valve
Energy supplier contact; closed on release; bridge if no blocking interval
Pump for mixing circuit 1
Heating circuit circulation pump; internally wired
Charge/discharge/cooling mixer 1 open
Charge/discharge/cooling mixer 1 closed
Overload protection; internally wired
no function
Accessories: Remote control
External sensor
Sensor mixing circuit 1
Accessories: Process water sensor/thermostat
External return sensor
Brine circulation pump
Terminal strips on controller board (see sticker)
Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units
Control 230V
Auxiliary heating 3 x 400V
Power supply compressor 3 x 400V; Attention: Right-hand rot. field is mandatory!
Auxiliary circulation pump / circulation pump
Control signal of additional heat generator 1; internally wired
Control signal of additional heat generator 2 (alternative is general malfunction)
UK831120a
Function
Controller board; Attention: I-max = 6A/230VAC
Terminals in heat pump switchbox
Sub-distribution unit internal installation
3-pol. Cut out compressor; Attention: Right-hand rot. field is mandatory!
Cut out controller unit
Cut out auxiliary heating
Accessories: Transformer for dewpoint monitor
With cooling option: Room thermostat; bridge if not connected
Accessories with cooling option: Dewpoint monitor; bridge if not connected
GND
-X2
HUP
FP1
ZW1
ZW1
TA
-X0
L1
Brine water compact 6 - 17 kW
Ers. für
GND
5
PE
-Y2
PE
2
A1
A2
L1
Legend:
Name
A1
A2
A3
F10
F11
F12
T2
Y2
Y3
Terminals
ASD
BUP
EVU
FP1
HUP
MA1/MIS
MZ1/MIS
MOT
PEX
RFV
TA
TB1
TBW
TRL
VBO
X0-X4
X7
X7:PE,N,L1
X7:PE,N,L1,L2,L3
X7:PE,L1,L2,L3
ZUP/ZIP
ZW1
ZW2/SST
BUP
4
2
PE
Y2
PE
Urspr.
VBO
A2
L
N
24V
PE
Bearb. Georg Bächmann
Gepr.
ASD
-X7
N
-T2
N
230V
N
Norm
L1
3
3
N
Georg Bächmann Datum 08.12.2006
4
L2
-F11
L1
A3
N
2
L3
-F10
L2
Datum
14
15
Anlage
Ort
1
16
Bl von Anz 1/1
Blatt-Nr.
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
42
GND
TA
TBW
TBW
GND
TB1
PE
B10 A
GND
RFV
L3
1~N/PE/230V/50Hz
PE
3~PE/400V/50Hz
6-12 kW: C10 A
14-17 kW: C16 A
PE
3~N/PE/400V/50Hz
6-12 kW: C10 A
14-17 kW: C16 A
Terminal diagram
SWC 60H(/K) – SWC 170H(/K)
1
2
1
1
Zustand
-F10
4
L2
Änderung
L3
3
N
Datum
2
N
230V
N
3
Name
2
PE
2
5
A1
A2
2
Urspr.
5
4
1
3
2
5
2
EVU
6
-Y3
P
ASD
L1
7
MOT
7
Ers. für
Terminals
ASD
BUP
EVU
FP1
HUP
MA1/MIS
MZ1/MIS
MOT
PEX
RFV
TA
TB1
TBW
TRL
VBO
X0-X4
X7
X7:PE,N,L1
X7:PE,L1,L2,L3
ZUP/ZIP
ZW1
ZW2/SST
6
EVU
9
MIS
ZW2/SST
10
GND
RFV
11
23 - 33 kW
-X4
TRL
8
FP1
GND
PEX
TB1
8
9
Ers. durch
10
11
12
12
SWC 230-330 terminal diagram
Brine pressure pressostat; provided by cust. if necessary
Accessories: Process water for changeover valve
Energy supplier contact; closed on release; bridge if no blocking interval
Pump for mixing circuit 1
Heating circuit circulation pump; internally wired
Charge/discharge/cooling mixer 1 open
Charge/discharge/cooling mixer 1 closed
Overload protection; internally wired
no function
Accessories: Remote control
External sensor
Sensor mixing circuit 1
Accessories: Process water sensor/thermostat
External return sensor
Brine circulation pump
Terminal strips on controller board (see sticker)
Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units
Control 230V
Power supply compressor 3 x 400V; Attention: Right-hand rot. field is mandatory!
Auxiliary circulation pump / circulation pump
Control signal of additional heat generator 1
Control signal of additional heat generator 2 (alternative is general malfunction)
UK831122a
Function
Controller board; Attention: I-max = 6A/230VAC
Terminals in heat pump switchbox
Sub-distribution unit internal installation
3-pol. Cut out compressor; Attention: Right-hand rot. field is mandatory!
Cut out controller unit
Accessories: Transformer for dewpoint monitor
With cooling option: Room thermostat; bridge if not connected
Accessories with cooling option: Dewpoint monitor; bridge if not connected
GND
A1
MZ1
M
TA
-X3
M
ZUP/ZIP
BUP
MA1
ZW2/SST
ZW1
ZW1
GND
-X2
HUP
FP1
BUP
-X0
L1
Brine water compact 23 - 33 kW
Legend:
Name
A1
A2
A3
F10
F11
T2
Y2
Y3
VBO
4
PE
-Y2
PE
Bearb. Georg Bächmann
Gepr.
4
ASD
A2
PE
Y2
2
PE
Norm
L1
-X7
L
24V
PE
Georg Bächmann Datum 08.12.2006
A3
N
3
N
-T2
N
2
-F11
PE
20.02.2007
2
N
13
831122a
13
14
14
15
Anlage
Ort
15
1
16
16
Bl von Anz 1/1
Blatt-Nr.
43
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
GND
TA
TBW
TBW
GND
TB1
L1
B10 A
RFV
PE
1~N/PE/230V/50Hz
L1
3~PE/400V/50Hz
23kW: C16 A
33kW: C25 A
SWC 230(/K) – SWC 330(/K)
Terminal diagram
1
-X7
1
8
2
4
5
6
5
2
3
6
3
1
4
1
2
M
Datum
20.02.2007
2
3
-X7
4
14
-K5
L1 L2 L3 N PE
3~N/PE/400V/50Hz
Gepr.
Norm
4
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
1
4
3
6
5
5
2
-R1
5
Urspr.
L
L
-X1
P
+
-F1
HDP
-
b2 c4
a1
8
-X1
1
3
5
21
-K1
HD.
2 3
N..
1
8
-X1
P
2
2
2
+
-F2
NDP
A2
A1
VD1
-
2
4
6
22
9
a1
c4 b2
ND.
L..
9
2
-X0
-F4
Ers. durch
L
95
96
L
10
-X2
230VAC
EVU
EVU
11
-X3
11
SWC60-80H
-X2
L
10
L
N PE
M
1
1 2
HUP
-M4
12
-X3
-Y1
12
BUP
1
2
-X3
13
-
-STB
21
5
3
1
-X3
-K5
ZW1
N PE
M
1
13
817250b
-M3
L
1 2
VBO
7
N PE
N PE
7
Ers. für
MOT
6
-A1
-X0
-X7
1~N/PE/230V/50Hz
6
UK817250b
Function
Power supply compressor; right-hand rot. field is mandatory!
Power supply aux. heating
Controller supply
Controller board; Attention: I-max = 6A/230VAC
Energy supplier contact; closed on release; bridge if no blocking interval
High-pressure switch
Low-pressure switch
Contactor for compressor 1
Contactor for auxiliary heating
Compressor 1
Brine pump
Heating circulation pump
Mixer; installed with cooling option
Auxiliary heating
Safety temperature limiter heating element
Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units
Accessories: Process water for changeover valve
-M1
VD1
3
T1 T2 T3 PE
1 2 3
95
96
10
-K1
-F4
L1 L2 L3 N PE
3~PE/400V/50Hz
Änderung
Legend:
Operating materials
3~PE/400V/50Hz
3~N/PE/400V/50Hz
1~N/PE/230V/50Hz
A1
EVU
F1
HDP
F2
NDP
VD1
K1
K5
ZW1
VD1
M1
M3
BOSUP
HUP
M4
MIS
M16
R1
ZW1
STB
X7
Y1
BUP
1
Zustand
14
A1
ZW1
A2
2
4
6
22
14
-X3
5
5
5
MA1
M
MIS
-M16
1
15
A Z N PE
br swbl
MZ1
Anlage
Ort
15
Blatt-Nr.
1
16
16
Bl von Anz 1/2
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
44
Circuit diagram 1/2
SWC 60H(/K) – SWC 80H(/K)
SWC 60H(/K) – SWC 80H(/K)
Circuit diagram 2/2
-A1
RFV
Änderung
2
-X4
-R13
TB1 -
GND
TB1
Datum
20.02.2007
2
-Y2
3
-X7
TR
1
L
Y2
2
-Y2
3
-Y3
Gepr.
Norm
4
4
4
5
-Y3
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
5
-X4
-R9
TBW -
-Y4
TR
BWT
Urspr.
5
6
-X4
TA -
-R8
6
7
8
8
Legend:
Operating materials
A1
R4
TRL
R5
TVL
R6
THG
R7
TWE
TA
R8
TBW
R9
R10 RFV
R11 TWA
R12 CW
R13 TB1
Y2
Y3
Y4
BWT
7
Ers. für
9
-X5
-R4
TRL -
TRL
10
-X5
-R5
TVL -
GND
TVL
11
-X5
-R6
THG -
GND
THG
12
-X5
-R11
TWA -
TWA
GND
9
10
SWC60-80H
11
12
13
-X5
CW.
-CW
13
-X5
-R7
TWE -
GND
817250b
UK817250b
Function
Controller board; Attention: I-max = 6A/230VAC
Return sensor
Flow sensor
Hot gas sensor
Heat source input sensor
External sensor
Domestic hot water sensor
Accessories: Remote control
Heat source output sensor
Heat pump coding; SWC - 875 ohm
Sensor mixing circuit 1; installed with cooling option
With cooling option: Room thermostat; bridge if not connected
Accessories with cooling option: Dewpoint monitor; bridge if not connected
Accessories: Process water for thermostat
GND
Ers. durch
14
14
TWE
15
Anlage
Ort
15
Blatt-Nr.
2
16
16
Bl von Anz 2/2
45
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
-R12
1
-X4
-R10
RFV -
1
Zustand
GND
TBW
GND
GND
TA.
GND
-X7
1
-K1
2
5
6
5
3
4
6
3
1
2
4
1
2
R S T
3
4
15
-K5
2
1
4
3
6
5
5
6
-B1 L1 L2 L3 12
P
11
14
-A1
7
-X0
L
N PE
N PE
-M1
VD1
3
M
5
6
7
Ers. für
+
-X1
-K1
HD.
a1
b2 c4
2 3
N..
1
1
3
5
21
9
-X1
P
+
2
4
6
2
2
2
ND.
c4 b2
a1
10
-X0
2
L
95
96
L
L
11
EVU
-X2
230VAC
-X2
11
SWC100-170H
ANr.
-F4
10
12
-X2
12
-X3
L
13
-X3
N PE
M
1
1 2
HUP
-M4
-Y1
1
BUP
2
817251c
13
-X3
14
14
-
-X3
-STB
-K5
1
3
5
21
ZW1
N PE
M
-M3
L
1
1 2
VBO
9
-
-F2
NDP
A2
A1
VD1
Ers. durch
MOT
8
-X1
8
1~N/PE/230V/50Hz
P
1 2 3
-F20
L
-F1
HDP
-R1
-X7
-
-X7
L1 L2 L3 N PE
Gepr.
Norm
4
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
Urspr.
UK817251c
Function
Power supply compressor; right-hand rot. field is mandatory!
Power supply aux. heating
Controller supply
Controller board; Attention: I-max = 6A/230VAC
Phase sequence relay; if phase sequence in the order of 11 + 14 is closed
Energy supplier contact; closed on release; bridge if no blocking interval
High-pressure switch
Low-pressure switch
Overload relay for compressor 1
Brine pressure pressostat; provided by cust. if necessary
Contactor for compressor 1
Contactor for auxiliary heating
Compressor 1
Brine pump
Heating circulation pump
Mixer; installed with cooling option
Starting current limit
Auxiliary heating
Safety temperature limiter heating element
Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units
Accessories: Process water for changeover valve
Datum
20.02.2007
2
3~N/PE/400V/50Hz
T1 T2 T3 PE
U V W
95
96
10
9
-F4
-N1
L1 L2 L3 N PE
3~PE/400V/50Hz
Änderung
Legend:
Operating materials
3~PE/400V/50Hz
3~N/PE/400V/50Hz
1~N/PE/230V/50Hz
A1
B1
EVU
F1
HDP
NDP
F2
F4
F20
K1
VD1
K5
ZW1
M1
VD1
M3
BOSUP
HUP
M4
M16
MIS
N1
ZW1
R1
STB
X7
Y1
BUP
1
Zustand
5
5
5
MZ1
M
16
16
Bl von Anz 1/2
1
N PE
MIS
-M16
1
A Z
br sw bl
MA1
Blatt-Nr.
-X3
15
6
4
2
A2
A1
ZW1
Anlage
Ort
15
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
46
Circuit diagram 1/2
SWC 100H(/K) – SWC 170H(/K)
L..
ASD
EVU
SWC 100H(/K) – SWC 170H(/K)
Circuit diagram 2/2
-A1
RFV
Änderung
TB1
Datum
3
-Y2
-X7
TR
Gepr.
Norm
4
1
L
Y2
2
-Y2
4
3
-Y3
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
4
5
-Y3
5
Urspr.
5
6
-X4
-R9
TBW -
-Y4
BWT
TR
6
7
-X4
TA -
-R8
TA.
7
Ers. für
8
Legend:
Operating materials
A1
R4
TRL
R5
TVL
R6
THG
R7
TWE
R8
TA
R9
TBW
R10 RFV
R11 TWA
R12 CW
R13 TB1
Y2
Y3
BWT
Y4
8
9
10
-X5
-R4
TRL -
GND
TRL
11
-X5
-R5
TVL -
GND
TVL
12
-X5
-R6
THG -
GND
THG
13
-X5
-R11
TWA -
TWA
GND
10
SWC100-170H
ANr.
11
12
13
817251c
UK817251c
Function
Controller board; Attention: I-max = 6A/230VAC
Return sensor
Flow sensor
Hot gas sensor
Heat source input sensor
External sensor
Domestic hot water sensor
Accessories: Remote control
Heat source output sensor
Heat pump coding; SWC - 845 ohm
Sensor mixing circuit 1; installed with cooling option
With cooling option: Room thermostat; bridge if not connected
Accessories with cooling option: Dewpoint monitor; bridge if not connected
Accessories: Process water for thermostat
9
Ers. durch
14
-X5
14
CW.
-CW
GND
15
-X5
-R7
TWE -
Anlage
Ort
15
GND
Blatt-Nr.
TWE
2
16
16
Bl von Anz 2/2
47
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
2
-X4
-R13
TB1 -
GND
20.02.2007
2
-R12
1
-X4
-R10
RFV -
1
Zustand
GND
TBW
GND
GND
1
Änderung
2
-X7
3
8
-K1
-N1
L1 L2 L3 N PE
3~PE/400V/50Hz
1
4
3
6
5
4
2
R S T
M
-M1
VD1
3
T1 T2 T3 PE
1 2 3
U V W
Gepr.
Norm
4
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
5
5
Urspr.
6
6
-A1
-X0
-X7
L
L
-X1
P
+
-F1
HDP
-
a1
8
3
-X1
13
5
3
1
VD1
-K1
HD.
b2 c4
2
N..
1
8
A1
VD1
A2
2
4
6
-X1
P
4
4
4
-
+
-F2
NDP
14
9
-X0
10
L
10
L
-X2
230VAC
L
EVU
SWC230
ANr.
11
11
-X2
-X3
12
-X3
-Y1
N PE
M
1
12
-M4
L
1 2
HUP
9
a1
c4 b2
ND.
L..
Ers. durch
MOT
7
N PE
N PE
1~N/PE/230V/50Hz
7
Ers. für
UK817252b
Function
Power supply compressor; right-hand rot. field is mandatory!
Controller supply
Controller board; Attention: I-max = 6A/230VAC
Energy supplier contact; closed on release; bridge if no blocking interval
High-pressure switch
Low-pressure switch
Contactor for compressor 1
Compressor 1
Brine pump
Heating circulation pump
Mixer; installed with cooling option
Starting current limit
Pump thermocontact
Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units
Accessories: Process water for changeover valve
Datum
20.02.2007
2
Legend:
Operating materials
3~PE/400V/50Hz
1~N/PE/230V/50Hz
A1
EVU
HDP
F1
F2
NDP
K1
VD1
VD1
M1
M3
BOSUP
M4
HUP
M16
MIS
N1
WSK
X7
Y1
BUP
1
Zustand
BUP
1
2
13
-X3
N PE
M
1
-M3
L
1 2
VBO
817252b
13
14
3 4
WSK
14
-X3
MZ1
M
15
1
16
16
Bl von Anz 1/2
Blatt-Nr.
N PE
MIS
-M16
1
A Z
br sw bl
MA1
Anlage
Ort
15
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
48
Circuit diagram 1/2
SWC 230(/K)
EVU
SWC 230(/K)
Circuit diagram 2/2
-A1
RFV
Änderung
TB1
Datum
3
-Y2
-X7
TR
Gepr.
Norm
4
1
L
Y2
2
-Y2
4
3
-Y3
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
4
5
-Y3
5
Urspr.
5
6
-X4
-R9
TBW -
-Y4
BWT
TR
6
7
-X4
TA -
-R8
TA.
7
Ers. für
8
Legend:
Operating materials
A1
R4
TRL
R5
TVL
R6
THG
R7
TWE
R8
TA
R9
TBW
R10 RFV
R11 TWA
R12 CW
R13 TB1
Y2
Y3
Y4
BWT
8
9
10
-X5
-R4
TRL -
GND
TRL
11
-X5
-R5
TVL -
GND
TVL
12
-X5
-R6
THG -
GND
THG
13
-X5
-R11
TWA -
TWA
GND
10
SWC230
ANr.
11
12
13
817252b
UK817252b
Function
Controller board; Attention: I-max = 6A/230VAC per contact
Return sensor
Flow sensor
Hot gas sensor
Heat source input sensor
External sensor
Domestic hot water sensor
Accessories: Remote control
Heat source output sensor
Heat pump coding; SWC - 845 ohm
Sensor mixing circuit 1; installed with cooling option
With cooling option: Room thermostat; bridge if not connected
Accessories with cooling option: Dewpoint monitor; bridge if not connected
Accessories: Process water for thermostat
9
Ers. durch
14
-X5
14
CW.
-CW
GND
15
-X5
-R7
TWE -
Anlage
Ort
15
GND
Blatt-Nr.
TWE
2
16
16
Bl von Anz 2/2
49
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
2
-X4
-R13
TB1 -
GND
20.02.2007
2
-R12
1
-X4
-R10
RFV -
1
Zustand
GND
TBW
GND
GND
-X7
1
9
-K1
-N1
L1 L2 L3 N PE
3~PE/400V/50Hz
Änderung
1
2
2
3
4
5
6
9
-K1
11
12
3
9
-K2
4
1
2
3
4
5
6
R S T
9
-K2
U V W
-N2
U V W
1 2 3
R S T
1 2 3
-M2
VD2
3
M
T1 T2 T3 PE
-R20
T1 T2 T3 PE
M
3
-M1
VD1
Gepr.
Norm
4
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
11
12
5
-R21
5
Urspr.
6
6
-A1
-X0
-X7
L
L
-X1
N..
1
3
5
11
9
Ers. durch
2
4
6
4
4
4
5
a1
L
L
-X2
230VAC
L
EVU
MOT
SWC330
ANr.
11
11
EVU
10
10
-X0
1
L..
c4 b2
2
ND.
9
-X1
A2
A1
3
2
2
2
-F2 P
NDP - +
VD2
-K2
A1
1
6
4
2
A2
VD2
8
-X1
11
5
3
1
VD1
-K1
a1
b2 c4
2 3
HD.
8
VD1
7
N PE
-F1 P
HDP - +
N PE
1~N/PE/230V/50Hz
7
Ers. für
UK817253d
Function
Power supply compressor; right-hand rot. field is mandatory!
Controller supply
Controller board; Attention: I-max = 6A/230VAC
Energy supplier contact; closed on release; bridge if no blocking interval
High-pressure switch
Low-pressure switch
Contactor for compressor 1
Contactor for compressor 2
Contactor for thermo contact on heating circulation pump
Compressor 1
Compressor 2
Brine pump
Heating circulation pump
Mixer; installed with cooling option
Starting current limit compressor 1
Starting current limit compressor 2
Sump heating for compressor 1
Sump heating for compressor 2
Pump thermocontact
Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units
Accessories: Process water for changeover valve
Datum
20.02.2007
2
Legend:
Operating materials
3~PE/400V/50Hz
1~N/PE/230V/50Hz
A1
EVU
F1
HDP
NDP
F2
K1
VD1
K2
VD2
K6
VD1
M1
M2
VD2
M3
BOSUP
M4
HUP
M16
MIS
N1
N2
R20
R21
WSK
X7
Y1
BUP
1
Zustand
-K6
13
11
14
12
-X3
N PE
M
1
1 2 PE
L
-M4
12
-K6
3 4
HUP
WSK
11
13
12
-X3
A1
A2
14
-Y1
1
BUP
2
-X3
817253d
13
L
14
N PE
M
1
1 2 PE
VBO
-M3
14
3 4
WSK
15
MZ1
M
16
16
Bl von Anz 1/2
1
N PE
MIS
-M16
1
A Z
br sw bl
MA1
Blatt-Nr.
-X3
Anlage
Ort
15
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
50
Circuit diagram 1/2
SWC 330(/K)
SWC 330(/K)
Circuit diagram 2/2
-A1
RFV
Änderung
TB1
Datum
3
-Y2
-X7
TR
Gepr.
Norm
4
1
L
Y2
2
-Y2
4
3
-Y3
Bearb. Escher F.
Georg Bächmann Datum 17.05.1999
3
Name
4
5
-Y3
5
Urspr.
5
6
-X4
-R9
TBW -
-Y4
BWT
TR
6
7
-X4
TA -
-R8
TA.
7
Ers. für
8
Legend:
Operating materials
A1
R4
TRL
R5
TVL
R6
THG
R7
TWE
R8
TA
R9
TBW
R10 RFV
R11 TWA
R12 CW
R13 TB1
Y2
Y3
BWT
Y4
8
9
10
-X5
-R4
TRL -
GND
TRL
11
-X5
-R5
TVL -
GND
TVL
12
-X5
-R6
THG -
GND
THG
13
-X5
-R11
TWA -
TWA
GND
10
SWC330
ANr.
11
12
13
817253d
UK817253d
Function
Controller board; Attention: I-max = 6A/230VAC
Return sensor
Flow sensor
Hot gas sensor
Heat source input sensor
External sensor
Domestic hot water sensor
Accessories: Remote control
Heat source output sensor
Heat pump coding; SW2 - 160 ohm
Sensor mixing circuit 1; installed with cooling option
With cooling option: Room thermostat; bridge if not connected
Accessories with cooling option: Dewpoint monitor; bridge if not connected
Accessories: Process water for thermostat
9
Ers. durch
14
-X5
14
CW.
-CW
GND
15
-X5
-R7
TWE -
Anlage
Ort
15
GND
Blatt-Nr.
TWE
2
16
16
Bl von Anz 2/2
51
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
2
-X4
-R13
TB1 -
GND
20.02.2007
2
-R12
1
-X4
-R10
RFV -
1
Zustand
GND
TBW
GND
GND
EC declaration of conformity
The undersigned
confirms
that
the
following
designated
device(s)
as
designed
and
marketed
fill the standardized EC directives, the EC safety standards and the product-specific
In the event of modification of the device(s) without our approval, this declaration shall become invalid.
by
EC
us
fulstandards.
Designation of the device(s)
Heat Pump
Unit model
SWC 60H
SWC 80H
SWC 100H
SWC 120H
SWC 140H
SWC 170H
SWC 230
SWC 330
SWC 70H
Number
100 260
100 261
100 262
100 263
100 264
100 265
100 266
100 267
100 269
Unit model
SWC 60H/K
SWC 80H/K
SWC 100H/K
SWC 120H/K
SWC 140H/K
SWC 170H/K
SWC 230K
SWC 330K
SWC 70H/K
EC Directives
Standardized EN
89/392/EWG oder 98/37/EG
73/23/EWG
89/366/EWG
EN 378
EN 60529
EN 292/T1/T2
EN 294
Number
100 270
100 271
100 272
100 273
100 274
100 275
100 276
100 277
100 279
EN 349
EN 60335-1/-2-40
EN 55014-1/-2
EN 61000 3-2/-3-3
National Standards/Directives
DE
UVV BGV D4
DIN 8901
Company:
AT
CH
NEV (SR 743.26)
Place, date:
Kasendorf, 19.05.2006
Signature:
UK818046
52
Jesper Stannow
Technical Director
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
General checklist
for preparation of the completion report for heat pump systems
The general checklist is intended as an aid for the installation and assembly personnel. It makes no claim to be exhaustive. Nevertheless, all items must be checked carefully for compliance.
Heat source air
Channels closed and sealed
Weather protection screen installed
Rotary field of fan
□ Yes
□ Yes
□ O.K.
Heat source brine / heat source water
Heat source volume flow ¹)
Motor protection setting
Rotary field of heat source circulating pump
Heat source filled, air-free and sealed
Brine
Frost protection down to
Water
Water quality OK ²)
Well system
Other heat source
Heat Pump
Installation of condensate hose
Decoupled from structure
Vibration decouplers for the heating
circuit and heat source connections
installed
□ O.K.
........... A
□ O.K.
□ Yes
Heating
Volume flow ¹)
Heating system designed for maximum
Heating system filled, air-free and sealed
Low temperature heating
Radiator heating
All heating circuits can be opened
Forward flow tank
Return flow tank
Separating tank
Content
Additional heating
□ O.K.
...........°C
□ Yes
□ Yes
□ Yes
□ Yes
□ Yes
□ Yes
□ Yes
........... l
........ kW
...........°C
□ No □ Yes
□ Yes
□ Yes
□ No
□ O.K.
□ Yes
□ Yes
Hot water
with heat pump
Request with thermostat
Request with cooling
Volume flow ¹)
Heat exchanger surface
Connections sealed
Electric
Rotary field, power network
Protective measures inspected
Rotary field of condenser
Return flow sensor mounted
Outdoor sensor mounted
□ No
□ Yes
□ Yes
□ Yes
□ O.K.
......... m²
□ Yes
□
□ Yes
□ O.K.
□ Internal □ External
□ No □ Yes
¹) Checked with specification
²) Report of water analysis must be submitted
Checked on: .........................................
By: ...........................................................................................
Signature : ..............................................................................
In Germany the following applies:
Send this completed general checklist to the factory customer service department, together with the completion report for heat
pump systems.
Outside of Germany the following applies:
Send this completed general checklist to the manufacturer’s local partner, together with the completion report for heat pump systems.
Sending the completion report is also a request for a technician authorized by the manufacturer to commission your heat pump.
FAZ-WP Formblatt UK820522c Stand: 240407
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
53
Completion report for heat pump systems
in DE: to the Alpha-InnoTec customer service department
in AT: to the Alpha-InnoTec customer service department
in CH: to the Alpha-InnoTec customer service department
in all other countries:
To the manufacturer’s local partner
+49 (0) 9228 9906 199
+43 (0) 732 24 42 01 4
+41 (0) 62 748 20 01
Completion report and request for commissioning
During commissioning, the heat pump system will be inspected to ensure that it is functioning
properly. Technicians
authorized
by
the
manufacturer
ensure
that
all
factory
specifications
have
been checked and that the heat pump system can operate reliably over an extended period.
The factory commissioning involves costs and is mandatory for extension of the warranty services.
□
Initial commissioning
□
Heat pump type
Regulator type
Contractor
□
□
Re-commissioning
End customer / Operator
Electric
other company
□ Heating
Company
Contact
Name / First name
Street address
Street address
ZIP code / head office
ZIP code / city
Phone
Phone
Preferred date
Alternate date
Date / time
Date / time
Send the completed report 1 week before the preferred date together with the general checklist. If there is a conflict with the date,
you will be contacted by phone.
I/we hereby confirm that all preliminary work required for commissioning has been carried out and completed. A detailed and
thorough installation check has been conducted. The heat pump system is ready for operation.
Check once again:
Is the heating circuit filled and pressure tested; do the circulating pumps function properly?
Is the heat source system completed, inspected and OK?
Have the heating circuit, heat source system and circulating pumps been bled?
Are all electrical components permanently connected according to the circuit diagram; are all
sensors properly mounted?
Have all volume flows and water flow rates been checked and are they OK?
□ No
□ No
□ No
□ No
□ Yes
□ Yes
□ Yes
□ Yes
□ No
□ Yes
In the event that the heat pump system is not ready for operation and if installation work has to be performed by the commissioning
technician during commissioning, this will involve charges to the contractor. If the heat pump system is not ready for operation, the
commissioning technician can request a repeat commissioning, which will involve additional costs.
The contractor or an authorized representative must be present during commissioning.
The operator of the system should be present during commissioning in order to ensure that proper instruction is
received.
An acceptance report will be prepared during commissioning.
I, the undersigned, hereby request commissioning, in return for a fee.
Place, date
FAZ-WP Formblatt UK820522c Stand: 240407
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
Signature / company stamp
55
Notes
We reserve the right to modify technical specifications without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
57
Customer service
Addresses in the event of a service call
For a current list and additional partners of the manufacturer, please visit www.alpha.innotec.com.
DE
Alpha-InnoTec GmbH
Industriestrasse 3
95359 Kasendorf
Tel.: +49 (0) 9228 9906 190
Fax: +49 (0) 9228 9906 199
e-Mail:[email protected]
www.alpha-innotec.com
AT
Peter Riess
Mannheimstrasse 1
4040 Linz
Tel.: +43 (0) 22 44 20 18
Fax: +43 (0) 22 44 20 14
e-Mail: [email protected]
BE
NATHAN Import/Export N.V.-S.A.
Lozenberg 4
1932 Zaventem
Tel.: +32 (0) 27 21 15 70
Fax: +32 (0) 27 25 35 53
e-Mail: [email protected]
www.nathan.be
BR
THERMACQUA
AV. República Argentina
3021 Conj. 21 Piso L
CEP 80610-260 Portao Curtiba PR
Tel.: +55 (0) 41 301 566 59
Fax: +55 (0) 41 301 566 59
e-Mail: [email protected]
www.thermacqua.com.br
CH
Vertretung Alpha-InnoTec Schweiz
Calmotherm AG
Industriepark
6246 Altishofen
Tel.: +41 (0) 62 74820 00
Fax: +41 (0) 62 74820 01
e-Mail: [email protected]
www.alpha-innotec.ch
www.calmotherm.ch
58
Suisse romande
Calmotherm SA
a.v. de Provence 12
1007 Lausanne
Tel.: +41 (0) 21 661 31 43
Fax: +41 (0) 221 661 31 45
e-Mail: [email protected]
www.calmotherm.ch
Ticino
Giuliani SA
Via alla Torre 2
6850 Mendriso
Tel.: +45 (0) 91 646 08 81
Fax: +45 (0) 91 646 09 91
e-Mail: [email protected]
www.calmotherm.ch
CZ / SK
Tepelna Cerpadia AIT
nám. Republiky 15
614 00 Brno
Tel.: +42 (0) 545 21 40 03
Fax: +42 (0) 545 24 20 90
e-Mail: [email protected]
www.alpha-innotec.cz
DK
ASAP Energy
Damgade 34
6400 Sønderborg
Tel.: +45 (0) 74 4304 80
Fax: +45 (0) 74 4304 81
e-Mail: [email protected]
www.asap.dk
We reserve the right to modify this document without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
FR
Caldis SarL
Parc d‘activités Centr‘Alp
209, rue du Rocher de Lorzier
38430 Moirans
Tel.: +33 (0) 4 7691 30 01
Fax: +33 (0) 4 7635 55 90
e-Mail: [email protected]
www.caldis.fr
GB
(England / Wales)
3rd rock energy Ltd.
7 Trowbridge Road, Westbury
Wiltshire BA13 3AY
Tel.: +44 (0) 845 603 37 74
Fax: +44 (0) 845 280 33 66
e-Mail: [email protected]
www.3rdrockenergy.com
NL
NATHAN Import/Export B.V.
Impact 73
6921 RZ Duiven
Tel.: +31 (0) 26 445 98 45
Fax: +31 (0) 26 445 93 73
e-Mail: [email protected]
www.nathan.nl
NO
Ingv. Torgersen
Langgt. 38
4306 Sandnes
Tel.: +47 (0) 51 6605 95
Fax: +47 (0) 51 6605 94
e-Mail: [email protected]
www.alpha-innotec.no
HU
Thermo Kft.
Krisztina körút 27
1122 Budapest
Tel.: +36 (0) 1 356 20 46
Fax: +36 (0) 1 214 28 68
e-Mail: [email protected]
www.geosolar.hu
PL
Hydro-Tech
ul. Zakladowa 4d
62-510 Konin
Tel.: +48 (0) 63 245 34 79
Fax: +48 (0) 63 242 37 28
e-Mail: [email protected]
www.alpha-innotec.pl
www.hydro-tech.pl
IE
PowerTech Ireland Ltd.
40 Dovesky Road
BT79 9BU Omagh, Carrickmore
Tel.: +44 (0) 28 8076 00 88
Fax: +44 (0) 28 8076 04 95
e-Mail: [email protected]
www.powertechireland.co.uk
SE
Vämekyl Grossisten AB
Hammarbacken 46
19 149 Sollentuna
Tel.: +46 (0) 8 446 32 10
Fax: +46 (0) 8 732 46 20
e-Mail: [email protected]
www.vkg.se
IT
(Südtirol / Alto Adige)
PENKOFF
Gemsengasse 17
A – 6020 Innsbruck
Tel.: +43 (0) 5122 7647 90
Fax: +43 (0) 5122 7647 930
e-Mail: [email protected]
www.penkoff.com
SI
Zeus Solar d.o.o.
Mace 6
4205 Preddvor
Tel.: +38664 (0) 2 555 780
Fax: +38664 (0) 2 555 782
e-Mail: [email protected]
www.zeussolar.si
170408
LV
SIA „EVA-SAT“
Krasta iela 44
1003 Riga
Tel.: +371 (0) 75 054 80
Fax: +371 (0) 75 053 99
e-Mail: [email protected]
www.evasat.lv
We reserve the right to modify this document without prior notice.
UK830300/170717
© Alpha-InnoTec GmbH
59