floor standing unit
Rising energy and general building services running costs have led
end users to expect far more than just cooling and heating from
their air conditioning. A truly complete and acceptable system
therefore, must be energy efficient, economic to run, easy to
install, flexible, reliable and user friendly.
Fresh air must also be supplied without increasing energy consumption
and central management and control facilities have gained in
importance, particularly for medium to large sized buildings.
The Daikin Hi-VRV system meets all these requirements:
Air Conditioning
HRV
DAIKIN
NETWORK
SOLUTION
Ventilation
Control & Management
VRV
VRV Variable Refrigerant Volume
76
VRVII OUTDOOR UNITS
RXQ-M7
RXYQ-M7
REYQ-M7
77
77
78
79
VRVII INDOOR UNITS
1. Cassette units
FXZQ-M
FXFQ-M7
FXCQ-M7
FXKQ-M
80
80
81
82
83
2. Concealed ceiling units
FXDQ-M7
FXDQ-N
FXSQ-M7
FXMQ-M
84
84
85
86
87
3. Wall mounted units
FXAQ-M
88
88
4. Ceiling suspended units
FXHQ-M
89
89
5. Floor standing units
FXNQ-M
FXLQ-M
90
90
91
HI-VRV SELECTION PROGRAMME
92
HRV
93
www.daikineurope.com
VRV air conditioning can be found in offices, restaurants, theatres,
hospitals, universities, museums, shops - in short, in any location
where the provision of a balanced, pleasant working environment
can improve the lifestyle and comfort of the individual.
75
VRV
Variable
Refrigerant
Volume
Daikin Europe has achieved a quantum leap forward in commercial
air conditioning technology by the introduction of its VRV II, the
www.daikineurope.com
world’s first R-410A operated variable refrigerant flow system.
Available in cooling only, heat pump and heat recovery versions,
the new system, which represents a considerable advance over
earlier VRV systems, demonstrates Daikin’s innovative application
of new technology and the latest HFC refrigerants to its VRV
product programmes.
Many new features and installation benefits are incorporated in
VRV II. Its operating range for example – 5hp, then 8hp to 48hp in
76
2hp increment steps (22 system combinations), is wider than any
of its contemporaries. Furthermore, its ability to run no less than
40 indoor units in heat recovery as well as heat pump format
cannot at present be matched by other comparable systems.
The ability to control each conditioned zone keeps VRVII system
running costs to an absolute minimum. Furthermore, only those
areas calling for air conditioning need to be cooled or heated and
the system can be shut down completely in unoccupied rooms.
Modular design enables Daikin VRVII outdoor units to be joined
together in rows with an outstanding degree of uniformity. The
design of the outdoors units is sufficiently compact to allow them
to be taken up to the top of a building in a commercial elevator,
overcoming site transportation problems.
RXQ-M7
Inverter cooling only
8,10HP
www.daikineurope.com
5HP
77
COOLING ONLY
RXQ-M7W1B
Equivalent horsepower
Number of outdoor units
Minimum capacity index
Maximum capacity index
Cooling capacity
Power input
COP
Dimensions
Weight
Sound pressure level
Sound power level
Air flow rate
Operation range
Number of connectable indoor units
Refrigerant type
Power supply
HP
kW
kW
Height
Width
Depth
mm
mm
mm
kg
dB(A)
dB(A)
m3/min
°CDB
5
5
1
62.5
162.5
14.0
3.79
3.69
1,600
635
765
160
54
72
75
8
W1
8
8
1
100
260
22.4
6.97
3.21
1,600
930
765
230
57
78
175
-5~43
13
R-410A
3N~, 50Hz, 400V
10
10
1
125
325
28.0
9.00
3.11
1,600
930
765
230
58
78
180
16
RXYQ-M7
Inverter heat pump
www.daikineurope.com
18,20HP
78
28,30,32HP
38,40,42HP
HEAT PUMP
RXYQ-M7W1B
Nominal cooling capacity
Nominal heating capacity
Power input
cooling
heating
cooling
heating
height
width
depth
COP
Dimensions
Weight
Sound pressure levels
Sound power level
Air flow rate
Operation range
cooling
heating
Refrigerant type
Power supply
5
14.0
16.0
3.79
4.34
3.69
3.69
1,600
635
765
160
54
72
75
kW
kW
kW
kW
mm
mm
mm
kg
dB(A)
dB(A)
m3/min
°CDB
°CWB
8
22.4
25.0
6.97
6.89
3.21
3.63
1,600
930
765
230
57
78
175
10
28.0
31.5
9.00
9.31
3.11
3.38
1,600
930
765
230
58
78
180
12
33.5
37.5
10.60
10.80
3.16
3.47
1,600
1,240
765
260
60
80
210
14
40.0
45.0
14.30
12.90
2.80
3.49
1,600
1,240
765
300
60
80
210
16
44.5
50.0
15.60
14.00
2.85
3.57
1,600
1,240
765
300
60
80
210
-5 ~ 43
-20 ~ 15.5
R-410A
3N~, 50Hz, 400V
W1
HEAT PUMP
RXYQ-M7W1B
Modules
Equivalent horsepower
Number of outdoor units
Minimum capacity index
Maximum capacity index
Cooling capacity
Heating capacity
Power input
COP
Dimensions
Weight
Number of connectable indoor units
5
1
RXYQ5M
RXYQ8M
RXYQ10M
RXYQ12M
RXYQ14M
RXYQ16M
10
12
14
16
1
1
18
20
22
24
26
1
1
2
1
1
1
1
1
1
HP
cooling
heating
cooling
heating
height
width
depth
8
kW
kW
kW
kW
mm
mm
mm
kg
5
1
62.5
162.5
14.0
16.0
3.79
4.34
3.69
3.69
1,600
635
765
160
8
8
1
100
260
22.4
25.0
6.97
6.89
3.21
3.63
1,600
930
765
230
13
10
1
125
325
28.0
31.5
9.00
9.31
3.11
3.38
1,600
930
765
230
16
12
1
150
390
33.5
37.5
10.60
10.80
3.16
3.47
1,600
1,240
765
260
19
14
1
175
455
40.0
45.0
14.30
12.90
2.80
3.49
1,600
1,240
765
300
20
28
18
2
225
585
50.4
56.5
16.00
16.20
3.15
3.49
1,600
1,860
765
460
20
20
2
250
650
56.0
63.0
18.00
18.60
3.11
3.39
1,600
1,860
765
460
20
22
2
275
715
61.5
69.0
19.60
20.10
3.14
3.43
1,600
2,170
765
490
22
32
34
36
38
40
42
2
2
1
1
1
1
1
1
1
16
1
200
520
44.5
50.0
15.60
14.00
2.85
3.57
1,600
1,240
765
300
20
30
24
2
300
780
68.0
76.5
23.30
22.20
2.92
3.45
1,600
2,170
765
530
32
1
26
2
325
845
72.5
81.5
24.60
23.30
2.95
3.50
1,600
2,170
765
530
32
1
28
2
350
910
78.0
87.5
26.20
24.80
2.98
3.53
1,600
2,480
765
560
32
1
1
2
30
32
2
2
375 400
975 1,040
84.5 89.0
95.0 100
29.90 31.20
26.90 28.10
2.83 2.85
3.53 3.56
1,600 1,600
2,480 2,480
765
765
600 600
32
32
1
34
3
425
1,105
96.0
108
32.30
31.50
2.97
3.43
1,600
3,100
765
760
34
1
36
3
450
1,170
101
113
33.60
32.60
3.01
3.47
1,600
3,100
765
760
36
1
38
3
475
1,235
106
119
35.20
34.10
3.01
3.49
1,600
3,410
765
790
38
44
46
48
1
2
46
3
575
1,495
129
145
45.50
40.90
2.84
3.55
1,600
3,720
765
900
40
3
48
3
600
1,560
134
150
46.90
42.10
2.86
3.56
1,600
3,720
765
900
40
1
1
1
40
3
500
1,300
113
127
38.90
36.20
2.90
3.51
1,600
3,410
765
830
40
2
42
3
525
1,365
117
132
40.20
37.40
2.91
3.53
1,600
3,410
765
830
40
2
44
3
550
1,430
123
138
41.80
38.80
2.94
3.56
1,600
3,720
765
860
40
REYQ-M7
Heat recovery
34,36HP
44,46,48HP
www.daikineurope.com
22,24,26HP
HEAT RECOVERY
REYQ-M7W1B
Nominal cooling capacity
Nominal heating capacity
Power input
cooling
heating
cooling
heating
height
width
depth
COP
Dimensions
Weight
Sound pressure level
Sound power level
Air flow rate
Operation range
cooling
heating
Refrigerant type
Power supply
8
22.4
25.0
6.97
6.89
3.21
3.63
1,600
930
765
245
57
78
175
kW
kW
kW
kW
mm
mm
mm
kg
dB(A)
dB(A)
m3/min
°CDB
°CWB
10
28.0
31.5
9.00
9.31
3.11
3.38
1,600
930
765
245
58
78
180
12
33.5
37.5
10.60
10.80
3.16
3.47
1,600
1,240
765
295
60
80
210
-5~43
-20~15.5
R-410A
3N~, 50Hz, 400V
W1
14
40.0
45.0
14.30
12.90
2.80
3.49
1,600
1,240
765
340
60
80
210
16
44.5
50.0
15.60
14.00
2.85
3.57
1,600
1,240
765
340
60
80
210
79
* Sound power levels were not available at time of publication
HEAT RECOVERY
REYQ-M7W1B
Modules
Equivalent horsepower
Number of outdoor units
Minimum capacity index
Maximum capacity index
Cooling capacity
Heating capacity
Power input
COP
Dimensions
Weight
Number of connectable indoor units
8
1
REYQ8M
REYQ10M
REYQ12M
REYQ14M
REYQ16M
12
14
16
1
18
1
1
20
22
24
26
2
1
1
1
1
1
1
HP
cooling
heating
cooling
heating
height
width
depth
10
kW
kW
kW
kW
mm
mm
mm
kg
8
1
100
260
22.4
25.0
6.97
6.89
3.21
3.63
1,600
930
765
245
13
10
1
125
325
28.0
31.5
9.00
9.31
3.11
3.38
1,600
930
765
245
16
12
1
150
390
33.5
37.5
10.60
10.80
3.16
3.47
1,600
1,240
765
295
19
14
1
175
455
40.0
45.0
14.30
12.90
2.80
3.49
1,600
1,240
765
340
20
28
18
2
225
585
50.4
56.5
16.00
16.20
3.15
3.49
1,600
1,860
765
490
20
20
2
250
650
56.0
63.0
18.00
18.60
3.11
3.39
1,600
1,860
765
490
20
22
2
275
715
61.5
69.0
19.60
20.10
3.14
3.43
1,600
2,170
765
540
22
32
34
36
38
40
42
2
2
1
1
1
1
1
1
1
16
1
200
520
44.5
50.0
15.60
14.00
2.85
3.57
1,600
1,240
765
340
20
30
24
2
300
780
68.0
76.5
23.30
22.20
2.92
3.44
1,600
2,170
765
585
32
1
26
2
325
845
72.5
81.5
24.60
23.30
2.95
3.50
1,600
2,170
765
585
32
1
28
2
350
910
78.0
87.5
26.20
24.80
2.98
3.53
1,600
2,480
765
635
32
1
1
30
2
375
975
84.5
95.0
29.90
26.90
2.83
3.53
1,600
2,480
765
680
32
1
2
32
2
400
1,040
89.0
100
31.20
28.10
2.85
3.56
1,600
2,480
765
680
32
34
3
425
1,105
96.0
108
32.30
31.50
2.97
3.43
1,600
3,100
765
830
34
1
36
3
450
1,170
101
113
33.60
32.60
3.01
3.47
1,600
3,100
765
830
36
1
38
3
475
1,235
106
119
35.20
34.10
3.01
3.49
1,600
3,410
765
880
38
44
46
48
1
2
46
3
575
1,495
129
145
45.50
40.90
2.84
3.55
1,600
3,720
765
1,020
40
3
48
3
600
1,560
134
150
46.90
42.10
2.86
3.56
1,600
3,720
765
1,020
40
1
1
1
40
3
500
1,300
113
127
38.90
36.20
2.90
3.51
1,600
3,410
765
925
40
2
42
3
525
1,365
117
132
40.20
37.40
2.91
3.53
1,600
3,410
765
925
40
2
44
3
550
1,430
123
138
41.80
38.80
2.94
3.56
1,600
3,720
765
975
40
FXZQ-M
4-Way blow ceiling mounted
cassette (600 mm x 600 mm)
www.daikineurope.com
FXZQ-M
80
•
•
•
New and extremely compact casing
(575mm in depth) enables unit to fit
flush into ceilings and match standard
architectural modules, without cutting
ceiling tiles
Modern style decoration panel in super
white (RAL9010)
Whisper quiet operation with sound
pressure levels as low as 25dBA
Excellent low draught characteristics
• Auto swing:
Vertical auto swing moves the discharge
flaps up and down to distribute air
effectively throughout the room. Since
the flaps can move to a 0-degree
position, virtually no draught can be
experienced
•
•
5 different air flow patterns:
Any one of 5 air flow patterns can be
freely selected between 0 and 60 degrees
and will then be maintained during the
operational cycle of the air conditioner.
Air can be discharged in any of 4
directions. Possibility to shut 1 or 2 flaps
for easy installation in corners
2-way blow
optional
3
2
4
4
1
1
3
3
2
optional
4-way blow
3
2
optional
4
1
2
3
4
2
1
3
4
1
2
4
1
3-way blow
Ceiling void is 295mm
0°
0°
60°
60°
FXZQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
Wired remote control
DECORATION PANEL
Dimensions (HxWxD)
Weight
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
VE
cooling
heating
mm
kg
20
2.2
2.5
73
64
25
2.8
3.2
73
64
9.0/7.0
30/25
47
9.0/7.0
30/25
47
32
3.6
4.0
76
68
286x575x575
18
9.5/7.0
32/26
49
R-410A
1~, 50Hz, 220-240V
BRC7E531W
BRC7E530W
BRC1D517
BYFQ60BW1
55x700x700
2.7
40
4.5
5.0
89
80
50
5.6
6.3
115
107
11.0/8.0
36/28
53
14.0/10.0
41/33
58
FXFQ-M7
4-Way blow
ceiling mounted cassette
•
•
•
•
Compact and lightweight
Possibility to shut 1 or 2 flaps for easy
installation in corners
1 or 2 branches can be used for better
air distribution
Choice of 3 auto-swing positions for
maximum comfort : standard, draught
prevention or ceiling soiling prevention
•
•
•
Single branch - 8 patterns
Branched
Branched
Branched
Branched
optional
optional
optional
except VRV
Inverter
Cooling only
81
2 branches - 3 patterns
Closed
Closed
Requires only 240mm of ceiling space
(298mm for model 80 and above)
Easy to fit decoration panel
Drain pump with increased lift of 750 mm
fitted as standard
Closed
Closed
Closed
Branched
Branched
Branched
Closed
Closed
Closed
Closed
Branched
Branched
Branched
Closed
Closed
Branched
Branched
Closed
Closed
Branched
Closed
Piping location
Branched
previous pattern
FXFQ-M7V1B
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level
Refrigerant type
Power supply
Infrared remote control
Wired remote control
DECORATION PANEL
Dimensions (HxWxD)
Weight
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
V1
cooling
heating
mm
kg
20
2.2
2.5
90
75
25
2.8
3.2
90
75
32
3.6
4.0
90
75
40
4.5
5.0
97
82
50
5.6
6.3
106
90
63
7.1
8.0
118
101
80
9.0
10.0
173
159
14/10
32/28
49
16/11
33/28
50
R-410A
1~, 50Hz, 230V
BRC7C513W
BRC7C512W
BRC1D517
BYC125KJW1
40x950x950
5
18/14
34/29
51
28/20
38/32
54
230x840x840
24
13/10
31/28
48
13/10
31/28
48
www.daikineurope.com
FXFQ80,100,125M7
13/10
31/28
48
100
11.2
12.5
184
169
288x840x840
28
28/21
40/33
56
125
14.0
16.0
230
215
31/24
45/36
61
FXCQ-M7
2-Way blow
ceiling mounted cassette
www.daikineurope.com
FXCQ20,25,32M7
•
•
•
Slim unit can be installed in a ceiling void
of only 355mm
Easy installation : depth of all units
is 600mm
Auto-swing mechanism ensures even
room air and temperature distribution
and prevents ceiling soiling
1
2
Standard
Ceiling soiling
prevention
•
•
•
Quiet operation
Leaves maximum floor and wall space
for furniture and decorations
Easy to clean flat suction grille
optional
optional
optional
except VRV
Inverter
Cooling only
82
10˚
10˚
65˚
65˚
30˚
30˚
65˚
65˚
Note:
Set standard to 2-way discharge when shipped.
High ceiling types 1 and 2 will be set for remote control
operation.
FXCQ-M7V1B
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level
Refrigerant type
Power supply
Infrared remote control
Wired remote control
DECORATION PANEL
Dimensions (HxWxD)
Weight
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
20
2.2
2.5
77
44
7/5
33/28
45
25
2.8
3.2
92
59
305x780x600
26
9/6.5
35/29
50
V1
cooling
heating
mm
kg
BYBC32GJW1
53x1,030x680
8
32
3.6
4.0
92
59
40
4.5
5.0
130
97
50
5.6
6.3
130
97
9/6.5
35/29
50
31
12/9
35.5/30.5
50
305x995x600
32
12/9
35.5/30.5
50
R-410A
1~, 50Hz, 230V
BRC7C67
BRC7C62
BRC1D517
BYBC50GJW1
53x1,245x680
8.5
63
7.1
8.0
161
126
305x1,180x600
35
16.5/13
38/33
52
BYBC63GJW1
53x1,430x680
9.5
80
9.0
10.0
209
176
125
14.0
16.0
256
233
305x1,670x600
47
26/21
40/35
54
48
33/25
45/39
60
BYBC125GJW1
53x1,920x680
12
FXKQ-M
Ceiling mounted
corner cassette
•
•
•
Specific design for use in rooms with
shallow ceiling voids
Auto-swing mechanism ensures even
room air and temperature distribution
Choice of 3 auto-swing positions for
maximum comfort : standard, draught
prevention or ceiling soiling prevention
•
Optimum air flow conditions are created
by either downward or frontal air
discharge (via optional grille) or a
combination of both
optional
optional
optional
except VRV
Inverter
Cooling only
Downward discharge
1
2
3
Standard
Draught
prevention
Ceiling soiling
prevention
10˚
10˚
65˚
40˚
Frontal
discharge
83
30˚
65˚
Closed by decoration panel
Combination
Note:
Set standard to 1-way discharge when shipped.
High ceiling types 1 and 2 will be set for remote control
operation.
•
Leaves maximum floor and wall space
for furniture, decoration and fittings
FXKQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
25
2.8
3.2
66
46
11/9
38/33
*
32
3.6
4.0
66
46
215x1,110x710
31
11/9
38/33
*
cooling
heating
* Sound power levels were not available at time of publication
mm
kg
40
4.5
5.0
76
56
13/10
40/34
*
63
7.1
8.0
105
85
215x1,310x710
34
18/15
42/37
*
R-410A
1~, 50Hz, 220-240V
BRC4C63
BRC4C61
BRC1D517
VE
Wired remote control
DECORATION PANEL
Dimensions (HxWxD)
Weight
www.daikineurope.com
FXKQ63M
BYK45FJW1
70x1,240x800
8.5
BYK71FJW1
70x1,440x800
9.5
FXDQ-M7
Concealed ceiling unit
(small)
www.daikineurope.com
FXDQ20,25M7
•
•
•
Designed for hotel use
Compact dimensions, can easily be
mounted in a ceiling void
Since only the suction and discharge
grilles are visible, the system will blend in
any interior décor
•
•
•
Extremely quiet in operation, both
indoors and outdoors
The air suction direction can be altered
from rear to bottom suction
Standard air suction filter
optional
optional
optional
except VRV
Inverter
Cooling only
84
FXDQ-M7V1B
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level
Refrigerant type
Power supply
Infrared remote control
Wired remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
V1
cooling
heating
20
2.2
2.5
25
2.8
3.2
50
50
230x502x652
17
6.7/5.2
7.4/5.8
37/32
50
R-410A
1~, 50Hz, 230V
BRC4C64
BRC4C62
BRC1D517
FXDQ-N
Slim concealed ceiling unit
•
Slim design for flexible installation
•
•
•
200mm
•
•
Compact dimensions, can easily be
mounted in a ceiling void of only 240mm
•
•
Quiet operation: down to 29 dBA sound
pressure level
Blends unobtrusively with any interior
décor
Can be installed in both new and existing
buildings
Leaves maximum floor and wall space for
furniture, decorations and fittings
Medium external static pressure facilitates
unit use with flexible ducts of varying
lengths
Drain-up pump with 750mm lift fitted as
standard
optional
optional
optional
except VRV
Inverter
Cooling only
85
Air filter
Suction Chamber
[Duct connection]
Ceiling
FXDQ-NVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level
Refrigerant type
Power supply
Infrared remote control
Cooling
Heating
kW
kW
W
W
mm
kg
m3/h
dB(A)
dB(A)
VE
Cooling
Heating
Wired remote control
* Sound power levels were not available at time of publication
20
2.2
2.5
150
137
25
2.8
3.2
150
137
26
9.5/7.5
33/29
*
26
9.5/7.5
33/29
*
32
3.6
4.0
150
137
200x900x620
26
10.5/8.5
33/29
*
www.daikineurope.com
FXDQ20-50NVE
40
4.5
5.0
160
147
50
5.6
6.3
165
152
27
10.5/8.5
34/30
*
28
12.5/10.0
35/31
*
R-410A
1~, 50Hz, 220-240V
BRC4C64
BRC4C62
BRC1D517, BRC2A51, BRC3A61
63
7.1
8.0
181
168
200x1,100x620
31
16.5/13.0
36/32
*
FXSQ-M7
Concealed ceiling unit
www.daikineurope.com
FXSQ40,50M7
86
•
•
•
•
Blends unobtrusively with any interior
décor
Leaves maximum floor and wall space
for furniture decoration and fittings
Drain pump fitted as standard
Long life filter fitted as standard
•
•
•
Air suction direction can be altered from
rear to bottom suction
The quiet operation of this model is ideal
for exclusive stores and offices
High external pressure facilitates unit use
with flexible ducts of varying lengths
optional
optional
optional
except VRV
Inverter
Cooling only
FXSQ-M7V1B
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level
Refrigerant type
Power supply
Infrared remote control
Wired remote control
DECORATION PANEL
Dimensions (HxWxD)
Weight
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
20
2.2
2.5
110
90
30
9/6.5
32/28
50
25
2.8
3.2
110
90
300x550x800
30
9/6.5
32/28
50
V1
cooling
heating
mm
kg
BYBS32DJW1
55x650x500
3
32
3.6
4.0
114
94
40
4.5
5.0
127
107
30
9.5/7
33/28
51
30
11.5/9
33/29
56
50
5.6
6.3
143
123
300x700x800
31
15/11
35/31
58
R-410A
1~, 50Hz, 230V
BRC4C64
BRC4C62
BRC1D517
BYBS45DJW1
55x800x500
3.5
63
7.1
8.0
189
169
300x1,000x800
41
21/15.5
35/30
56
BYBS71DJW1
55x1,100x500
4.5
80
9.0
10.0
234
214
51
27/20
37/31
55
100
11.2
12.5
242
222
300x1,400x800
51
28/20.5
38/33
56
BYBS125DJW1
55x1,500x500
6.5
125
14.0
16.0
321
301
52
38/28
40/35
65
FXMQ-M
Concealed ceiling unit
(large)
•
•
•
Leaves maximum floor and wall space
for furniture decoration and fittings
Complete range of models (5 > 31.5kW)
Ideal for use in large areas
•
Reduction in necessary installation space
thanks to built-in drain pump (available
as accessory)
optional
optional
optional
except VRV
Inverter
Cooling only
www.daikineurope.com
FXMQ80,100,125M
87
optional
FXMQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
VE
cooling
heating
Wired remote control
* Sound power levels were not available at time of publication
40
4.5
5.0
211
211
50
5.6
6.3
211
211
39/35
*
44
14/11.5
39/35
*
63
7.1
8.0
211
211
80
9.0
10.0
284
284
100
11.2
12.5
411
411
42/38
*
45
19.5/16
43/39
*
63
29/23
43/39
*
390x720x690
125
14.0
16.0
619
619
200
22.4
25.0
1,294
1,294
390x1,110x690
R-410A
1~, 50Hz, 220-240V
BRC4C64
BRC4C62
BRC1D517
65
36/29
45/42
*
250
28.0
31.5
1,465
1,465
470x1,380x1,100
137
58/50
48/45
*
72/62
48/45
*
FXAQ-M
Wall mounted unit
www.daikineurope.com
FXAQ40,50,63M
•
•
•
•
•
New design with compact casing
Dramatic weight reduction of 48%
compared to the previous series
Fits neatly on a wall
Auto-swing mechanism ensures efficient
air distribution via louvers that close
automatically when the unit is switched
off
5 different discharge angles can be
programmed via the remote control
•
•
Both horizontal flaps and front panel can
easily be removed and washed
Discharge angle automatically returns to
its previous position on restart (initial
setting 10° for cooling and 70° for
heating)
optional
optional
optional
except VRV
Inverter
Cooling only
10° Cooling
70° Heating
optional
88
•
10°
25°
40°
55° 70°
All maintenance operations can be
carried out from the front of the unit
FXAQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
V1
cooling
heating
Wired remote control
* Sound power levels were not available at time of publication
20
2.2
2.5
16
24
7.5/4.5
35/29
*
25
2.8
3.2
22
27
290x795x230
11
8/5
36/29
*
32
3.6
4.0
27
32
40
4.5
5.0
20
20
9/5.5
37/29
*
12/9
39/34
*
R-410A
1~, 50Hz, 220-240V
BRC7E619
BRC7E618
BRC1D517
50
5.6
6.3
27
32
290x1,050x230
14
15/12
42/36
*
63
7.1
8.0
50
60
19/14
46/39
*
FXHQ-M
Ceiling suspended unit
•
•
•
•
•
Reduced sound pressure level
Leaves maximum floor and wall space
for furniture decoration and fittings
Can be installed both in new and
existing buildings
Use of W-shaped Coanda flap enhances
horizontal and vertical air circulation
characteristics
Wider air discharge thanks to Coanda
effect: up to 100 degrees
•
•
•
Easy installation and maintenance
Long life filter fitted as standard
Drain pump kit available as accessory
optional
optional
optional
except VRV
Inverter
Cooling only
optional
89
100°
Coanda effect
FXHQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
VE
cooling
heating
Wired remote control
* Sound power levels were not available at time of publication
www.daikineurope.com
FXHQ32M
32
3.6
4.0
111
111
195x960x680
24
12/10
36/31
*
63
7.1
8.0
115
115
195x1,160x680
28
17.5/14
39/34
*
R-410A
1~, 50Hz, 220-240V
BRC7E66
BRC7E63W
BRC1D517
100
11.2
12.5
135
135
195x1,400x680
33
25/19.5
45/37
*
FXNQ-M
Concealed
floor standing unit
www.daikineurope.com
FXNQ20,25M
•
•
•
Ideal for installation beneath a window
All models are available with remote
control
The connecting port faces downward,
eliminating the need to attach auxiliary
piping
Connecting
port
optional
optional
optional
except VRV
Inverter
Cooling only
Refrigerant
piping
90
FXNQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
VE
cooling
heating
Wired remote control
* Sound power levels were not available at time of publication
20
2.2
2.5
49
49
25
2.8
3.2
49
49
32
3.6
4.0
90
90
610x930x220
19
7/6
35/32
*
40
4.5
5.0
90
90
50
5.6
6.3
110
110
610x1,070x220
23
7/6
35/32
*
8/6
35/32
*
610x1,350x220
27
11/8.5
38/33
*
R-410A
1~, 50Hz, 220-240V
BRC4C64
BRC4C62
BRC1D517
63
7.1
8.0
110
110
14/11
39/34
*
16/12
40/35
*
FXLQ-M
floor standing unit
•
•
•
•
Ideal for installation beneath a window
All models are available with remote
control
The floor standing model requires very
little installation space
Running the pipes from connections at
the back enables the unit to be wall
mounted for easy cleaning
optional
Wall mounted
optional
optional
except VRV
Inverter
Cooling only
Floor standing
www.daikineurope.com
FXLQ20,25M
91
FXLQ-MVE
INDOOR UNIT
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD)
Weight
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Power supply
Infrared remote control
cooling
heating
kW
kW
W
W
mm
kg
m3/min
dB(A)
dB(A)
VE
cooling
heating
Wired remote control
* Sound power levels were not available at time of publication
20
2.2
2.5
49
49
25
2.8
3.2
49
49
32
3.6
4.0
90
90
600x1,000x222
25
7/6
35/32
*
40
4.5
5.0
90
90
50
5.6
6.3
110
110
600x1,140x222
30
7/6
35/32
*
8/6
35/32
*
600x1,420x222
36
11/8.5
38/33
*
R-410A
1~, 50Hz, 220-240V
BRC4C64
BRC4C62
BRC1D517
63
7.1
8.0
110
110
14/11
39/34
*
16/12
40/35
*
Selection programme
A simple to use, Daikin Hi-VRV air conditioning computerised
selection programme, designed for use with Windows95®,
Windows98® and WindowsNT® systems, enables consulting
engineers, design and build contractors, property developers and
architects etc. to plan a Daikin air conditioning project on a step
by step basis, complete with detailed drawings, bills of quantities
and costs.
The programme thus enables VRV air conditioning systems to be
engineered precisely and economically (without oversizing units),
thereby ensuring optimum operating cycles and maximum energy
efficiency.
www.daikineurope.com
FEATURES :
92
• the Hi-VRV selection programme offers 3 separate modes to
accommodate different design formats according to customer
requirements:
1. EXPERT MODE :
once the cooling and heating loads in the different rooms have
been calculated, the software will select the most appropriate
system plus an estimate of the power consumption
2. QUICK MODE :
based on calculated system loads, the software will select the
most appropriate system
3. DRAWING MODE :
selecting the indoor and outdoor units from a list enables the
user to design a system in no time at all
• autoCAD and scanned drawings can be used to help draw up a
floor plan
• piping diameters can be automatically calculated
• indoor and outdoor units, headers and joints etc can be
automatically selected
Windows95®, Windows98® and WindowsNT® are registered trademarks of Microsoft
corporation.
HRV
Heat recovery ventilation
Clean outdoor air
Total heat
exchanged foul air
The Daikin heat recovery ventilation system modulates the
temperature and humidity of incoming fresh air to match indoor
conditions. A balance is thus achieved between indoor and
outdoor ambients, enabling the cooling or heating load placed on
the air conditioning system to be reduced significantly.
HRV units can be controlled individually or integral with the air
conditioning system (Daikin VRV or Sky Air series).
www.daikineurope.com
Foul indoor air
Total heat
exchanged
clean air
93
VAM-FA
Air flow rate
Sound pressure level (max.) (1)
External static pressure (max.)
Temperature exchange efficiency
Enthalpy exchange efficiency
Dimensions
Weight
Duct diameter
Power supply
(1) Sound pressure level is measured in heat exchange mode.
heating
cooling
H
W
D
m3/h
dBA
Pa
%
%
%
mm
mm
mm
kg
mm
VAM150FA7VE VAM250FA7VE VAM350FA7VE VAM500FA7VE VAM650FA5/7VE VAM800FA5/7VE VAM1000FA5/7VE VAM1500FA5/7VE VAM2000FA5/7VE
150
250
350
500
650
800
1,000
1,500
2,000
27/28.5
28/29
32/34
33/34.5
34.5/35.5
36/37
36/37
39.5/41.5
40/42.5
69
64
98
98
93
137
157
137
137
74
72
75
74
74
74
75
75
75
58
58
61
58
58
60
61
61
61
64
64
65
62
63
65
66
66
66
269
269
285
285
348
348
348
710
710
760
760
812
812
988
988
988
1,498
1,498
509
509
800
800
852
852
1,140
852
1,140
24
24
33
33
48
48
61
132
158
Ø 100
Ø 150
Ø 150
Ø 200
Ø 200
Ø 250
Ø 250
Ø 350
Ø 350
VE: 1~, 50Hz, 220-240V
94
www.daikineurope.com
In order to realise maximum efficiency, commercial air conditioning
systems must be subject to precise, 24 hour control.
Daikin manufactures and markets a complete suite of advanced
computerised central control and monitoring systems designed to
simplify air conditioning management and reduce energy usage
running costs.
Dedicated Daikin central control can be applied to both VRV and
mixed VRV/SkyAir and Split installations with up to 1,024 indoor
units and can also be integrated with building management
systems.
www.daikineurope.com
Daikin computerised control systems not only provide the highly
sophisticated regulation and day to day monitoring necessary for
modern, hi tech air conditioning installations – they also provide
owners, landlords and tenants of commercial buildings with valuable
performance data on consumption as well as a wide range of
operating parameters.
95
Control systems
CENTRALISED CONTROL SYSTEMS
Centralised remote control
Unified on/off control
Schedule timer
96
96
96
96
DAIKIN NETWORK SOLUTION
Intelligent Touch Controller
Intelligent Manager
DMS-IF
BACnet Gateway
97
97
98
99
99
Centralised
Control Systems
Centralised control of the VRV system can be achieved via 3 user
friendly compact controls: centralised remote control, unified
on/off control and schedule timer. These controls may be used
independently or in combination where 1 group = several (up to 16)
indoor units in combination and 1 zone = several groups in
combination.
A centralised remote control is ideal for use in tenanted
commercial buildings subject to random occupation, enabling
indoor units to be classified in groups per tenant (zoning).
The schedule timer programmes the schedule and operation
conditions for each tenant and the control can easily be reset
according to varying requirements.
DCS302C51
CENTRALISED REMOTE CONTROL
www.daikineurope.com
Providing individual control of 64 groups (zones) of indoor units.
96
• a maximum of 64 groups (128 indoor units, max. 10 outdoor
units) can be controlled
• a maximum of 128 groups (128 indoor units, max. 10 outdoor
units) can be controlled via 2 centralised remote controls in
separate locations
• zone control
• group control
• malfunction code display
• maximum wiring length of 1,000m (total: 2,000m)
• air flow direction and air flow rate of HRV can be controlled
• expanded timer function
DCS301B51
UNIFIED ON/OFF CONTROL
Providing simultaneous and individual control of 16 groups of
indoor units.
•
•
•
•
•
a maximum of 16 groups (128 indoor units) can be controlled
2 remote controls in separate locations can be used
operating status indication (normal operation, alarm)
centralised control indication
maximum wiring length of 1,000m (total: 2,000m)
DST301B51
SCHEDULE TIMER
Enabling 64 groups to be programmed.
•
•
•
•
a maximum of 128 indoor units can be controlled
8 types of weekly schedule
a maximum of 48 hours back up power supply
a maximum wiring length of 1,000m (total: 2,000m)
Daikin network solutions
Allows detailed & easy monitoring and operation of VRV systems (max. 64 control groups).
Up to 3kWh meters
(with pulse output/locally procured)
Modem
(field supply)
A/C power proportional distribution pulse input x 3 systems
RS232C
Communication
line
Outdoor unit
Slot loading
Forced shutdown
PCMCIA
card
(optional)
Indoor unit
Unified ON/OFF control
Display or print out power
proportional distribution
Fire alarm
Note:
There are restrictions in applicable areas and release times,
therefore please consult your local dealer for details
}
For Power
Proportional
Distribution
Maximum 64 groups
Remote control
Can also be used with
other A/C equipment
than VRV
Easy connectable to existing
VRV super wiring system
www.daikineurope.com
DIII-NET x 1 line
97
LANGUAGES
POWERFUL FUNCTIONS
CONNECTABLE TO :
•
•
•
•
•
• Automatic
cooling/heating changeover
• Heating optimization
• Temperature limit
• Yearly schedule
• Power proportional distribution
(optional)
• Fire emergency stop control
• Flexible timer functionality (several
schedules up to a full year)
• Flexible grouping in zones
• History data
• Password security (system set-up)
•
•
•
•
English
French
German
Italian
Spanish
SIMPLE OPERATION
• User friendly full colour LCD
• Touch panel
• Icon display
COST PERFORMANCE
• Labour saving
• Easy installation
• Compact design:
limited installation space
• Overall energy saving
VRV
HRV
Sky Air (via interface adapter)
Split (via interface adapter)
Daikin network solutions
The ideal solution for control
and management of maximum
1,024 VRV indoor units.
Intelligent Processing
unit (IPU)
4 units max.
· Operation Status
Monitoring
· Schedule Management
· Tenant Management
...etc
www.daikineurope.com
Fire alarm Security
98
Centralised
control systems
HRV
VRV System
SYSTEM LAYOUT
• Up to 1,024 indoor units can be
controlled (by 4 iPUs)
• Ethernet TCPIP / 10 base/T communication
• Integrated digital contacts on the
Intelligent Processing Unit (iPU)
· 19 general input ports
· 2 digital outputs
• Stand alone operation of the iPU
for minimum 48 hours
• Compatible with UPS shutdown
software
MANAGEMENT
• Proportional power consumption
division
• Operational history management
(start/stop, malfunction, operation
hours)
• Generation of reports (graphics &
tables) (daily, weekly, monthly)
•
•
•
•
Peak load shedding
Advanced tenant management
Sliding temperature
Eco mode
CONTROL
• Individual
control
(setpoint,
start/stop, fan speed) (max. 1,024
indoor units)
• Group control (100 groups)
• Schedule control (128 programs)
• Fire emergency stop control (32
programs)
• Interlocking control
• Setpoint limitation
• Automatic cool-heat change-over
• Power failure/release control
• Temperature limit (automatic start)
• Timer extension
MONITORING
• Visualisation via a Graphical User
Interface (GUI) featuring free
layout
• Operation mode of indoor &
outdoor units
• Fault indication
• Indication filter replacement
• Setpoint indication
• Operation time monitoring
• Multi PC
• On-line help
LON® bus
over ethernet
LONWORKS® Networks
~
Compatible Gateway
• Interface for LON connection to
LONWORKS® networks
• Communication via LON® protocol
(twisted pair wire)
• 64 units connectable per DMS-IF
• Unlimited site-size
• Quick and easy installation
LON® BMS
Security
Fire
alarm · Elevator
· Pump
· Lighting
...etc
Power supply facility
~
Centralised
control systems
www.daikineurope.com
HRV
VRV system
99
Integrated control system
connecting VRV system with
BMS system
• Interface for BMS system
• Communication via BACnet
protocol
(connection
via
Ethernet)
• 256 units connectable per
BACnet gateway
• Unlimited sitesize
• Easy and fast installation
BACnet
over ethernet
~
BMS
Fire alarm Security
· Elevator
· Pump
· Lighting
...etc
Power supply facility
HRV
VRV system
~
Centralised
control systems
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF