FIRE DETECTION
FIRE DETECTION
ELKRON. THE HI-PROTECTION COMPANY
2
THE HI-PROTECTION COMPANY
Another safe and secure day. Since 1974 Elkron has been committed to
guarantee Security to any type of application, from small home systems
to large installations. As a leading company in its sector and confirming
its position with 14 Quality marks in many different countries, 21 International Patents registered, 1600 different products designed and developed, and 27 million products sold. Elkron has made a huge progress
in research and innovation expressing new and unique solutions and
gaining a steady international reputation in Security.
As a fundamental achievement for its constant commitment to total
quality, Elkron has always complied with the strictest international standards, generating a permanent
process to check that such professional standards are constantly maintained as well as to ensure a continuous improvement of
the products, respecting all the
operating phases, from the initial product concept, to design,
manufacturing, sales and distribution, and finally to customer
support. Last but not the least,
Elkron is a leading participator as
coordinators and experts, in domestic (CEI) and European (CENELEC) standardisation projects.
www.elkron.com
3
THE FIRE ELKRON OFFER
CONVENTIONAL FIRE SYSTEMS
C/302
C/54
Single Zone central unit, with microprocessor in polycarbonate, suitable
for controlling fire stop doors.
Compact central unit, with microprocessor, suitable for small size
fire and gas systems. 4 detection
lines 32 max detectors per zone.
PAGE
PAGE
14
13
C/7000
DETECTORS
Modular conventional fire detection
central unit, with 16 bit microprocessor, 4 detection zones expandable up to 16.
Optical smoke detectors, optical
heat detectors, differential heat
detectors, combustible gas detectors.
PAGE
PAGE
16
17
BUTTONS
Alarm push-buttons with recommissoning, with glass breaking and unbreakable.
PAGE
19
ADDRESSED FIRE SYSTEMS
AREA 54/1
AREA 54/4
Analogue central unit, with 16 bit microprocessor, to manage fire systems with
single detection line, where up to 128
out of smoke detectors, gas detectors,
heat detectors, pushbuttons actuators
and interfaces to control external equipPAGE
ment can be connected.
Modular analogue central unit, with
multiprocessor, having 4 LOOPs
max. The unit is provided with base
with 1 MR/128 module (128 addresses). Expandable up to 512
addresses by 3 additional line moPAGE
dules.
AREA 54/8
AREA 54/16
Modular analogue central unit, with
multiprocessor, having 8 LOOPs
max. The unit is provided with 1
MR/128 module (128 addresses).
Expandable up to 1024 addresses
PAGE
by 7 additional line modules.
Modular analogue central unit, with
multiprocessor, having 16 LOOPs max.
The unit is provided with base with 1
MR/128 module (128 addresses).
Expandable up to 2048 addresses by
PAGE
15 additional line modules.
DETECTORS
BUTTONS
Optical smoke detectors, optical
heat detectors, differential heat detectors,
Alarm push-buttons with recommissoning, with glass breaking and unbreakable.
23
25
PAGE
31
UNIVERSAL BASES
Universal connection bases with or
without relay for conventional, digital and analogic detectors.
PAGE
36
4
24
26
PAGE
33
DUCTED DETECTION
The analysis chamber for ducted
detection was designed to check for
the presence of smoke in air ducts
and allows to timely detect a spreading fire.
PAGE
36
THE FIRE ELKRON OFFER
FAP500 DIGITAL FIRE DETECTION SYSTEM
FAP541
FAP544
Microprocessor control unit with 1
loop line. Possibility of managing up
to 128 points for loop (64 for open
line).
Microprocessor control unit with
1 loop line expandable up to 4.
Possibility of managing up to 128
points for loop (64 for open line).
PAGE
PAGE
40
41
FAP548
FAP5416
Microprocessor control unit with
1 loop line expandable up to 8.
Possibility of managing up to 128
points for loop (64 for open line).
Microprocessor control unit with
1 loop line expandable up to 16.
Possibility of managing up to 128
points for loop (64 for open line).
PAGE
PAGE
41
41
DETECTORS
BUTTONS
Optical smoke detectors, optical
heat detectors, differential heat detectors, combustible gas
PAGE
detectors.
44
Alarm push-buttons with recommissoning, with glass breaking and unbreakable.
PAGE
FIRE EXSTINGUISHING
43
GAS DETECTION
ATEX CONTROL UNITS
CDS
Fire extinguishing control unit with
one channel expandable up to 2.
PAGE
48
ST/PL4
Gas detection control unit allowing
the connection of
max 8 detectors. PAGE
52
ST/MTLSB
Gas detection control unit allowing the
connection of max
108 detectors.
EXPLOSIVES AND TOXIC GAS DETECTORS
TYPE EX II 3GD
TYPE EX II 2GD
Petrol Vapour / Propane Gas /
Butane Gas / Carbon Monoxide
Methane Gas / GPL Gas
Petrol Vapour / Propane Gas /
Butane Gas / Carbon Monoxide
Methane Gas / GPL Gas
PAGE
PAGE
53
FLAME DETECTORS
55
LIQUID DETECTOR
RU-ADPE
RA-209
Flame detector immediately responding to infrared
thermal radiation released by fire. The detector is tuned to flame pulses in order to ignore sunlight and
lamps.
Electronic detector to detect the presence of (uninflammable) liquids. Detecting the presence of water
is through 4 support gilt feet, which put the detector
into alarm by switching a relay placed inside it.
PAGE
56
PAGINA
57
5
THE FIRE ELKRON OFFER
SPECIAL HEAT DETECTOR
RTS/2 - RTS/4 - RTS/6
RLB/1 - RLB/2
IP65 Special heat detector based on
the deformation of a bimetallic element
which closes a dry contact as the temperature is reached.
Thermosensitive linear detectors calibrated to 68°
and 105° (certified).
PAGE
PAGE
57
59
LINEAR DETECTORS
S/2-100
SF-100
Linear detector suitable for all environments characterised in high ceilings,
where using smoke optical detectors
results to be particularly hard.
Fire and heat linear detector.
The system includes three units: Transmitting unit (TX), Receiving unit (RX),
co-ordination unit.
PAGE
PAGE
59
60
OPTICAL-ACOUSTIC INDICATORS
VISUAL REPEATER
PANELS
Optical/acoustic
signalling single and
double face panel.
Visual repeater allowing to
show the alarm status of a
detector installed in hidden
spaces.
PAGE
PAGE
64
66
ELECTRONIC BELLS
Bell with classic appearance for fire alarm
systems and other warnings.
PAGE
67
SOUNDERS
Outdoor red self-powered siren made in
die-cast aluminium.
ELECTROMAGNETS
Red siren for premises
evacuation in compliance with with regulation
626/94.
Electromagnetic stop implemented in order to keep open
fire or transit doors and release them in case of fire.
PAGE
PAGE
68
68
EXPLOSION PROOF SYSTEMS
6
T/800
T/800S
T/800L
The optical/acoustic system includes the body of siren T/800S
and the body of visual repeater
T/800L. These shells are made
of a casting of cast iron G-20 uni
5007.
Siren made of a
casting of cast
iron G-20 uni
5007 with a diffusing cone of
plastic material
(ABS);
Visual
repeater
made up of a shell
made of a casting
of cast iron G-20
uni 5007.
PAGE
69
ALPHABETIC INDEX
PRODUCT’S NAME
1370/15
CODE
MM7100123
PAGE
68
PRODUCT’S NAME
FDTD500
CODE
SD9000121
PAGE
45
1370/30
MM7300123
68
FIRE TRACER
SC4R00123
62
1469
SB4600123
20
FKP500
KP5200121
42
1471
SB5700123
20
FM500
SD6000121
43
2470
SB4400121
20
FMR500
SB6100121
43
3465/24
HS1900123
67
FOGLIO/54
SW2900121
34
3470
SB4300123
20
HP500F
HS5000121
68
4460/24
HS1700123
67
INT8C/24V
IL1010123
61
4476/24
HS7300123
67
INT-SONG/54
HS1010121
15
4479/24
HS7200123
67
IO500
SC3A00121
42
82425 SBG
PS7900123
70
IOM500
SC3B00121
42
82450 BG
PS8000123
70
ISO ZB
SC4200121
30
AREA 54/16L
SC3800121
26
ISO/BASE
SC4H00121
29
AREA54/1L
SC3900121
23
ISO/BASE-IP
SC6G00121
30
AREA54/4L
SC1900121
24
ISO/BP
SC6H00121
29
AREA54/8L
SC4100121
25
ISO/C
SC2210121
30
ASD
SC2R00123
62
ISO/MINI
SC4000121
30
AST
AT7100123
62
ITS500
IT1610121
43
BP/212
SD3700121
17
KATA
BP/212T
SD8900121
18
LAN/54
IL7500123
61
SC7910121
34
BPA/212
SD3600121
31
LAN/TCP/IP500
IT1510121
43
BPA/212-T
SD5800121
31
LR500
SR1100121
66
BPG/213 CH4
SD3300121
19
LR500SI
SR1200121
66
BPG/213 GPL
SD1J00121
19
MAPPA/54
SW2700121
34
BPT/214
SD3500121
18
MAPPE/FAP500
SW3600121
43
BTA/206
SD3400121
32
MAS/DIN-2000
SC2110121
28
C/54
SC1800121
14
MAS/IP-2000
SC8710121
28
C/7000
SC5200121
16
MC/19
SC1C10121
27
C/7000-R
SC5300121
16
MCR/DIN-2000
SC9110121
29
C302
SC6000121
13
MCS/54
SC6810121
17
CDS
SC3600121
49
MGSM500
CT6010121
43
CONSOLLE/54
KP3400121
32
MI/410
SC2010121
28
DBS
SD9H10123
62
MI/410-S
SC9610121
28
DFS
RT7100123
62
ML7000
SC1A10121
17
DRS
SD8H10123
62
MMS/54
SC1B10121
34
DSE/626
HS2100123
68
MOD/54-E
SC2510121
15
DTS
RT7200123
62
MOD/54-R
SC2410121
15
EM100P
MM9000123
68
MODEM54
CT7300123
34
EM50P
MM7000123
68
MPSTN500
CT5910121
43
ES50
SD8P00123
61
MR/128
SC2810121
27
ES80
SD9R00123
61
MR7000
SC7810121
17
ESPCDS
SC3500121
49
MRS/232/485-DIN
SC9310121
34
FA128
SC3310121
42
MSP/54
SC2B10121
23
FAP541
SC6100121
40
P 445
SB3500121
20
FAP5416
SC6700121
41
P/406
SB3000121
70
FAP544
SC6200121
41
P/406
SB4300123
20
FAP548
SC6600121
41
P/410
SB3600121
33
FDO500
SD4800121
44
P/420
SB2100121
33
FDOT500
SD9K00121
45
P/430
SB2200121
33
FDT500
SD5700121
44
P/435
SB3900121
33
7
ALPHABETIC INDEX
PRODUCT’S NAME
CODE
PAGE
PRODUCT’S NAME
CODE
PAGE
P 440
SB3800121
19
ST/PL4
SC6R00123
52
PICO
SC3R00123
62
ST/PL4/ESP
SC7R10123
52
PUNTO/54
SW3100121
34
ST/S3REL
SC5R10123
57
R/820
SD3L10121
36
STG/BOX
ST0510123
53
RA/209
SD2B00121
57
STG/IN8
SC9R10123
53
RA/209-S
SD7L00121
57
STG/MTSLB
SC8R00123
52
RB 1212
RB1110113
70
STG/OUT16
SC1S10123
53
RB 15
RB0810113
70
T/800
FH3500121
69
RB 19
RB0310113
70
T/800L
SR0200121
69
RB 24
RB0510113
70
T/800S
HS1800121
69
RB 612
RB0910113
70
TB24
FH2700121
65
RB06
RB0410113
70
TLG/54
SW2800121
34
RB12
RB0210113
70
TM220
FH2800121
65
RLB/1
SD6P00121
59
TM224
FH3100121
65
RLB/2
SD5P00121
59
TM24
FH2600121
64
RS232/485
IT1410121
42
TMSV
FH5400121
65
RTS/2
SD2C00123
57
VAL TEST
SI7100123
56
RTS/4
SD4C00123
58
WMB/138V15
ST0610123
53
RTS/6
SD3C00123
58
ZB/200
SD2700121
36
RU-ADPE
SD7100121
56
ZB/201
SD2800121
36
S/2-100 + INT8 C
IL1500123
59
ZB/204
SD9D00121
36
S1604VB
SD2T00123
53
ZB/210
SD4300121
36
ZB/212
SD1N00121
36
ZB/215
ZC7100121
36
S1606CO
SD7T00123
53
S1702VB
SD3T00123
54
S1703CO
SD8T00123
54
S2096BU
SD6T00123
53
S2096GP
SD4T00123
54
S2096ME
SD9S00123
54
S2096PR
SD5T00123
53
S2097BU
SD4U00123
55
S2097GP
SD2U00123
55
S2097ME
SD9T00123
55
S2097PR
SD3U00123
55
S2097VB
SD1U00123
55
S2131CO
SD5U00123
55
ADM
IL1110123
61
SD500
SD4K00121
46
SD500M
SD4S00121
46
SD500R
SD5K00121
46
SD500-RM
SD6S00121
46
SD515
SD2V00121
46
SF-100 + INT8 C
IL1400123
60
SOFT/54
SW2300121
SOFT/FAP500
SW3500121
43
SONG/54
HS0910121
27
SP/410
SC2610121
28
SP/410-S
SC4E10121
28
SPTB
SF5000121
64
SSM
SP7600123
61
8
INDEX
CONVENTIONAL
FIRE DETECTION
SYSTEMS
C/302..............................13
C/54................................14
C/7000............................16
DETECTORS....................17
BUTTONS........................20
ADDRESSED
FIRE DETECTION
SYSTEMS
AREA 54/1......................23
AREA 54/4......................24
AREA 54/8......................25
AREA 54/16....................26
DETECTORS....................31
CENTRALIZATION............34
UNIVERSAL
BASES
DUCTED
DETECTION
UNIVERSAL BASES..........36
DUCTED DETECTION........36
FAP 500
DIGITAL
SYSTEMS
FAP 541..........................40
FAP 544..........................41
FAP 548..........................41
FAP 5416........................41
ACCESSORIES.................43
DETECTORS....................44
EXTINGUISHING
CONTROL UNIT
EXTINGUISHING C.U.........48
SPECIAL
DETECTORS
GAS DETECTION C.U........52
GAS DETECTORS.............53
FLAME DETECTORS.........56
SPECIAL HEAT DET..........57
LINEAR DETECTORS........59
SUCTION SYSTEMS.........62
OPTICAL
ACOUSTIC
INDICATORS
PANEL.............................64
OPTICAL REPEATER.........66
BELLS.............................67
SOUNDERS.....................68
ELECTROMAGNETS..........68
EXPLOSION PROOF .........69
10
CONVENTIONAL
FIRE DETECTION
SYSTEMS
C/302 CONTROL UNIT................. pag. 13
C/54 CONTROL UNIT................... pag. 14
C/7000 CONTROL UNIT............... pag. 16
CONVENTIONAL DETECTORS...... pag. 17
CONVENTIONAL BUTTONS.......... pag. 20
11
CONVENTIONAL FIRE DETECTION SYSTEMS
CONVENTIONAL SYSTEMS
Conventional fire detection system by Elkron is proved to be the ideal system for all the systems
which do not need a large extent to be available.
Anyhow, central unit models, of which one is expandable up to 16 lines with 32 detectors, allow
to implement systems fully covering any small to medium firm typology and are proved to be
perfectly suitable for residential installations too.
The system is completed by its wide range of smoke detectors, gas detectors, pushbuttons and
relating signalling.
C/54 SYSTEM
MOD/54-E
CONTROL UNIT ZONES (N.4)
Electrovalve
Output
Module
1
2
32 MAX
points
per zone
3
MOD/54R
Actuators
module
4
Bells/Panels
Output
C/7000 SYSTEM
CONTROL UNIT ZONES
MCS/54
Printer
Module
1
2
3
MR7000
32 MAX
points per
zone
4
4 actuation
relays
module
EXPANSION MODULE (N.4)
1
2
Bells/Panels
Output
3
ML7000
4 Zone
Expansion
12
4
32 MAX
points per
zone
CONVENTIONAL FIRE DETECTION SYSTEMS
SINGLE ZONE CONTROL UNIT
Control Unit C/302
C/302 cod. SC6000121
Single Zone central unit, with microprocessor in polycarbonate, suitable for
controlling fire stop doors.
• Internally provided with a smoke optical detector and a heat probe having 60°
C intervention threshold.
• The unit is capable to manage either up to 15 (optic or heat) conventional
detectors or 2 gas detectors (BPG/213 model) on a conventional line set to
single permission.
• Output for electromagnets; the output is capable to support up to 6
electromagnets.
• Supply voltage: 230 Vac 50 Hz
• Output voltage: 24 Vdc
• Max current: 300 mA
• Smoke detector: Optical with Tyndall effect
• Heat detector: Heat probe calibrated to 60° C
• Visual alarm: 1 red led, 1 24 V 2W lamp
• Sound alarm: Buzzer
• Operation temperature: -10°C to +50°C
• Alarm relay output: 1A @ 30 Vdc
• Protection degree: IP 32
• Dimensions (HxLxD): 71 x 283 x 113mm
• Weight (not including batteries): 700 g
C/302
13
CONVENTIONAL FIRE DETECTION SYSTEMS
FOUR ZONE CONTROL UNIT
C/54 Control Unit
C/54 cod. SC1800121
Compact central unit, with microprocessor, suitable for small size fire and
gas systems.
• Composed of a red plastic enclosure made in ABS for wall mounting.
• Italian or English language front side.
• The unit has four independent detection lines, with maximum capacity of 30
devices per line. Each detection line corresponds to a single zone and can be
set to either single or double permission.
• The central unit is also equipped with a dry contact relay output for failure,
a controlled line for bells and sirens and an output for electromagnets
control.
• The central unit is equipped with an electronic circuit to recharge and control
the batteries.
• Leak towards the earth signalling on central unit panel.
• Mechanical key to enable programming functions and/or commands
(silencing, resetting, cutting off, etc.)
• Facility for adding, into the central unit, an optional module allowing to have
either 8 zone relay outputs or a module allowing to control a solenoid valve
(MOD54E).
• Number of zones: 4, independent
• Max number of detectors per zone: 30 (Smoke, heat, pushbuttons)
• In compliance with EN 54 parts 2 – 4
• Supply voltage: 230 Vac 50 Hz
• Output voltage: 23 Vdc – 27.6 Vdc
• Max current: 500 mA
• Assignable batteries: 2 x 12V – 7.5 Ah
• Failure central repetition: 1 A 30Vdc relay
• Controlled siren output
• Output for electromagnets
• Relative Humidity: 95 % Max RH non condensing
• Operation temperature: -5° to +50° C
• Protection degree: IP 32
• Dimensions (HxLxD): 386 x 269 x 96 mm
• Weight (not including batteries): 2,7 Kg
• Accessories: control module for siren line (INT-SONG/54 or SONG/54)
Control board for solenoid valve (MOD/54-E), Board with 4 relays for line
alarms (MOD/54-R)
14
C/54
CONVENTIONAL FIRE DETECTION SYSTEMS
FOUR ZONE CONTROL UNIT
Accessories for C/54 control unit
MOD/54-R cod. SC2410121
Module allowing C/54 central unit to increment and differentiate actuation
control for each zone.
• The module has 4 aggregated relays (NC or NO max. 1A - 30 VDC): Alarm
1 - Alarm 2 - Exclusion - Mains failure.
• Each Zone has:
• One controlled output for plates, sirens or bells.
• One output for either electromagnets or self-powered siren.
• One exchange dry contact relay (Closed - Normally Closed - Normally Open
max. 1 A - 30 VDC), that can be set on either Alarm 1 (Default) or Alarm 2
events.
• Max current which can be supplied by module: 500 mA
MOD/54-R
MOD/54-E cod. SC2510121
Module allowing C/54 central unit to have a dedicated output for controlling
a solenoid valve by a programmable activation lag.
• The module has 4 aggregated relays (NC or NO max. 1A - 30 VDC): Alarm
1 - Alarm 2 - Exclusion - Mains failure.
• The module also has following outputs:
N° 1 line for manually resetting solenoid electrovalve
N° 1 output line for the optical/acoustic signalling that cannot be silenced.
• Max current which can be supplied by module: 500 mA
MOD/54-E
SONG/54 cod. HS0910121
Module to check and actuate bells/plates/sirens.
• It is to be used on controlled outputs in central units.
• The module is to be installed immediately near the device to be checked.
• Dimensions (HxL):
25x30 mm
SONG/54
INT-SONG/54 cod. HS1010121
Intermediate module to check and actuate bells/plates/sirens.
• It is to be used on controlled outputs in central units.
• The module is to be installed immediately near the device to be checked.
• Dimensions (HxL): 25x30 mm
INT-SONG/54
15
CONVENTIONAL FIRE DETECTION SYSTEMS
MODULAR CONTROL UNIT 4 UP TO 16 ZONES
C/7000
C/7000 cod. SC5200121
Modular conventional fire detection central unit, with 16 bit microprocessor,
4 detection zones expandable up to 16.
• Software in 2 languages (Italian and English), which can be selected by user.
• Facility for connecting up to 32 devices per zone.
• Facility for associating a 16-character text per zone / zone group.
• Backlit alphanumeric display with 4 lines by 20 characters.
• 6 programmable access passwords.
• Relay actuation control independent of the zones.
• Central unit walk test with programmable self-resetting time.
• Evacuation function (Master Alarm) which can be either actuated from
keyboard or associated to a single zone.
• Chronological history log with 50 events.
• Programmable central unit alarm timing.
• Auxiliary input which can be set by resetting, acquisition or Master Alarm.
• Number of zones: 4, independent, expandable to 16
• Max number of detectors per zone: 32 (Smoke detectors, heat detectors,
pushbuttons)
• Backlit LCD display with 4 lines by 20 characters.
• 6 programmable access passwords
• In compliance with EN 54 parts 2 – 4
• Chronological history log with 50 events.
• Supply voltage: 230 Vac 50 Hz
• Output voltage: 27.6 Vdc
• Max Current: 500mA
• Assignable batteries: 2 x 12V – 7.5 Ah
• Signalling outputs: 2 Alarm relays of 3 A 30Vdc prog. for Alarms 1 2 3
1 Failure relay of 3 A 30Vdc (Closed /NO or Closed/NC)
1 Programmable relay of 3 A 30Vdc (C/NO or C/NC)
• Controlled siren outputs
• Operation temperature: -5° to +50° C
• Relative humidity: 93 % non condensing
• Protection: IP 31
• Dimensions (HxLxD): 454x377x132 mm
• Weight (not including batteries): 9 Kg
C/7000-R cod. SC5300121
• Same characteristics of C/7000 but with 4 relays freely programmable
on board
16
C/7000
CONVENTIONAL FIRE DETECTION SYSTEMS
MODULAR CONTROL UNIT 4 UP TO 16 ZONES
Accessories for C/7000 control unit
SONG/54 cod. HS0910121
Control module for siren line.
INT-SONG/54 cod. HS1010121
Intermediate control module for siren line.
ML7000
ML7000 cod. SC1A10121
Expansion module for 4 lines.
MR7000 cod. SC7810121
MR7000
Expansion module for 4 relays.
MCS/54 cod. SC6810121
Module for connecting a printer.
MCS/54
CONVENTIONAL DETECTORS
Optical Smoke Detector
BP/212 cod. SD3700121
Low profile conventional optical smoke detector.
• Correct operation signalling is from a flashing green led placed on the cap.
• Alarm signalling is from a red led placed on the cap.
• On the detector there are two open collector outputs, one for correct
operation signalling, the other for alarm signalling.
• A detector characteristic feature is its intervention threshold self-adjusting
capability on its being put on.
• Correct operation green led
• Alarm red led
• Alarm output: 100 mA (O.C.)
• Operation principle: Tyndall effect
• Supply voltage: 11 – 30 Vdc
• Alarm repetition: O.C. 100 mA max
• Operation repetition: O.C. 10 mA max
• Absorption: 100 µA 18 Vdc at rest , 22 mA 18 Vdc on alarm status
• Magnetic test
• Operation temperature: da –20 a +50 °C
• Relative humidity: 95% max non condensing
• EN 54 part 7 certified.
• Associable to following bases: ZB/200, ZB/201, ZB/204
• Dimensions (HxLxD): Ø 100 x H 45 mm
BP/212
17
CONVENTIONAL FIRE DETECTION SYSTEMS
CONVENTIONAL DETECTORS
Optical heat detector
BP/212 T cod. SD8900121
Low profile conventional optic heat detector with heat probe having 70° C
intervention temperature.
• Correct operation signalling is from a flashing green led placed on the cap.
• Alarm signalling is from a red led placed on the cap.
• On the detector there are two open collector outputs, one for correct
operation signalling, the other for alarm signalling.
• Correct operation green led
• Alarm red led
• Alarm output: 100 mA (O.C.)
• Operation principle: Tyndall effect
• Supply voltage: 11 – 30 Vdc
• Alarm repetition: O.C. 100 mA max
• Operation repetition: O.C. 10 mA max
• Absorption: 100 µA 18 Vdc at rest 22 mA 18 Vdc on alarm status
• Magnetic test
• Operation temperature: da –20 a +50 °C
• Relative humidity: 95% max non condensing
• EN 54 part 7 certified.
• Associable to following bases: ZB/200, ZB/201, ZB/204
• Dimensions: Ø 100 x H 45 mm
BP/212T
Differential heat detector
BPT/214 cod. SD3500121
Low profile conventional (thermo-speedometric) differential ratio of rise heat
detector with 58°C maximum intervention temperature.
• Correct operation signalling is from a flashing green led placed on the cap.
• Alarm signalling is from a red led placed on the cap.
• Correct operation green led
• Alarm red led
• Alarm output: 100 mA (O.C.)
• Operation principle: pair of heat probes
• Supply voltage: 11 – 30 Vdc
• Alarm repetition: O.C. 100 mA max
• Absorption: 100 µA 18 Vdc at rest 22 mA 18 Vdc on alarm status
• In compliance with EN 54 part 5
• Magnetic test
• Operation temperature: –20 a +50 °C
• Relative humidity: 95% max non condensing
• Associable to following bases: ZB/200, ZB/201, ZB/204
• Dimensions: Ø 100 x H 45 mm
18
BPT/214
CONVENTIONAL FIRE DETECTION SYSTEMS
CONVENTIONAL DETECTORS
METHANE gas detector
BPG/213 CH4 cod. SD3300121
Methane gas detector with semiconductor (semiconductor head FIGARO) having 2 intervention thresholds which can be calibrated and are independent.
• Both alarm thresholds are stored and transmit, to control central unit, two
quite differentiated signals allowing to operate by steps on actuations on field.
• Operation voltage: 12 – 30 Vdc
• Average absorption with fixed supply: 45 mA a 27 Vdc
• Pre-alarm absorption: 20 mA a 18 Vdc
• Alarm absorption: 40 mA a 18 Vdc
• Alarm signal repetition: 100 mA (O.C.)
• Pre-alarm visual repetition: yellow led
• Visual alarm repetition: red led
• Relative humidity: 95% max non condensing
• Adjustable alarm threshold: 5% to 100% E.L.L.
• Detectable gasses: methane
• Dimensions: Ø 100 x H 45 mm
BPG/213 CH4
GPL gas detector
BPG/213 GPL cod. SD1J00121
GPL gas detector with semiconductor (semiconductor head FIGARO) having 2
intervention thresholds which can be calibrated and are independent.
• Both alarm thresholds are stored and transmit, to control central unit, two
quite differentiated signals allowing to operate by steps on actuations on field.
• Operation voltage: 12 – 30 Vdc
• Average absorption with fixed supply: 45 mA a 27 Vdc
• Pre-alarm absorption: 20 mA a 18 Vdc
• Alarm absorption: 40 mA a 18 Vdc
• Alarm signal repetition: 100 mA (O.C.)
• Pre-alarm visual repetition: yellow led
• Visual alarm repetition: red led
• Relative humidity: 95% max non condensing
• Adjustable alarm threshold: 5% to 100% E.L.L.
• Detectable gasses: GPL
• Dimensions: Ø 100 x H 45 mm
BPG/213 GPL
CONVENTIONAL PUSH BUTTONS
Buttons
P440 cod. SB3800121
Red alarm conventional pushbutton with recommissioning.
• Visual alarm repetition: red led
• Weight: 100 g
• Alarm absorption: 20 mA @ 18 Vdc
• Actuation Type: Recommissioning
• Dimensions (HxLxD): 110 x 110 x 42 mm
P440
19
CONVENTIONAL FIRE DETECTION SYSTEMS
CONVENTIONAL PUSH BUTTONS
Buttons
P445 cod. SB3500121
Red alarm conventional pushbutton with breaking.
• Visual alarm repetition: red led
• Alarm absorption: 20 mA @ 18 Vdc
• Actuation Type: Breaking
• EN54 part 1
• Weight: 100 g
• Dimensions (HxLxD): 110 x 110 x 42 mm
P445
1469 cod. SB4600123
Break glass outdoor red alarm conventional pushbutton made in die-cast
aluminium.
• Alarm absorption: 20 mA @ 18 Vdc
• Actuation Type: Breaking
• Protection degree: IP 65
• Alarm resistance: 820 ohm 2W
• Weight: 400 g
• Dimensions (HxLxD): 95x95x 42 mm
1469
2470 cod. SB4400121
Break glass red alarm conventional pushbutton with transparent protection
cover.
• Visual alarm repetition: red led
• Weight: 180 g
• Alarm absorption: 20 mA @ 18 Vdc
• Actuation Type: Breaking
• Protection degree: IP 54
• Alarm resistance: 820 ohm 2W
• Dimensions (HxLxD): 85x85x52 mm
2470
3470 cod. SB4300123
Break glass red alarm conventional pushbutton.
• Visual alarm repetition: red led
• Weight: 120 g
• Alarm absorption: 20 mA @ 18 Vdc
• Actuation Type: Breaking
• Protection degree: IP 30
• Alarm resistance: 820 ohm 2W
• Dimensions (HxLxD): 84 x 120 x 31 mm
3470
P/406 cod. SB3000121
Pushbutton for fire manual signalling, with explosion proof shell, for areas
with a potentially explosive atmosphere.
• Hammer for glass breaking provided. Pushbutton made of diecast material,
red colour epoxy painting.
• Cable entry holes: 2x3/4 gas
• Classified: II 2GD EEx d IIB T6, EEx d IIB + H2 T6
• Certified: CESI 03 ATEX 050
• Operation temperature: -20 C° to + 50 C°
• Weight: 1.1 kg
1471 cod. SB5700123
Hammer
20
P/406
ADDRESSED
FIRE DETECTION
SYSTEMS
AREA 54/1................................. pag. 23
AREA 54/4................................. pag. 24
AREA 54/8................................. pag. 25
AREA 54/16............................... pag. 26
ACCESSORIES............................ pag. 27
DETECTORS............................... pag. 31
BUTTONS................................... pag. 33
CENTRALIZATION....................... pag. 34
21
ADDRESSED FIRE DETECTION SYSTEMS
ADDRESSED SYSTEMS
A technological innovation from Elkron-Sira proposes a last generation multiprocessor fire analogue detection system. It is a system for all applications, even the widest ones, and for all environmental typologies. AREA54 series is provided with central units from 1 loop, for 128 addresses,
up to 32 loops, for 4,096 addresses. The system can be fully managed and programmed either
directly from local keyboard or smoothly by PC, via dedicated software (SOFT/54).
AREA54/4
SP/410
REMOTE
PANELS
LINEAR
DETECTOR
BPA/212
+ ZB200
EXTERNAL
POWER
SUPPLY
UNITS
MI/410
RS485
RS232
MAS/DIN-2000
MR/128
PROGRAMMING
SOFTWARE
MAPPING
SOFTWARE
BTA/206
+ ZB200
LR500
P430
LOOP LINE
128 MAX
DEVICES
BPA/212
+ ZB200
22
PANEL
LR500
ADDRESSED FIRE DETECTION SYSTEMS
128 ADDRESSES CONTROL UNITS
AREA54/1L Control Unit
AREA54/1L cod. SC3900121
Analogue central unit, with 16 bit microprocessor, to manage fire systems
with single detection line.
• It is possibile to connect up to 128 out of smoke detectors, gas detectors,
heat detectors, pushbuttons actuators and interfaces to control external
equipment can be connected.
• Detection line can be programmed in following configurations:
4 open lines (max 32 devices per line)
1 loop line (max 128 devices)
2 loop lines (max 64 devices per line).
• 1 RS232 output towards PC
• LCD display with 8 lines by 40 characters
• Event log: 1000 events
• Signalling outputs:
Alarm Relay 1 or 3 (1A@30 Vdc), NO/NC contact
Alarm Relay 2 (5A@30 Vdc)
Failure or exclusion Relay (5A @ 30 Vdc) NO/NC contact
Network in Relay (1A @ 30 Vdc) NO/NC contact
• Controlled siren output for optical/acoustic indicators
• Controlled output for self-powered sirens
• In compliance with EN54/2-4
• Input voltage: 230 Vdc 50 Hz
• Ouput voltage:27 Vdc 500 mA
• Battery management, check and charge: 700 mA
• Assignable batteries: max 2 x 12V – 15 Ah
• Operation temperature: -5 to + 50°C
• Base made in metal sheet and front side made in ABS.
• Dimensions (HxLxD): 450 x 350 x 160 mm.
AREA54/1L
Accessories for AREA54/1L control unit
MSP/54 cod. SC2B10121
Module allowing Console 54, printer and a PC workstation to be connected
to AREA54/1 central unit.
• CENTRONICS opto-isolated port for connecting a printer
• RS 232 opto-isolated output for connection to a personal computer
• 485 opto-isolated output for connecting remote panels
• Dimensions (HxL): 160x65
MSP/54
23
ADDRESSED FIRE DETECTION SYSTEMS
4 LOOP CONTROL UNIT
AREA54/4L Control Unit
AREA 54/4L cod. SC1900121
Modular analogue central unit, with multiprocessor, having 4 LOOPs max.
• The unit is provided with base with 1 MR/128 module (128 addresses).
• Expandable up to 512 addresses by 3 additional line modules.
• By a two-lead closed or open loop detection line, up to 128 out of smoke
detectors, gas detectors, heat detectors, pushbuttons, actuators and
interfaces to control external equipment can be connected to each module.
• 1 RS232 opto-isolated bi-directional output towards PC.
• 1 RS485 opto-isolated serial output for communication from and to remote
keyboard.
• LCD display with 8 lines by 40 characters.
• Programming from keyboard and PC.
• 120 software zones.
• 60 device groups.
• 60 zone assemblies.
• Event log: 1000 events.
• Signalling outputs:
Alarm 1, Alarm 2, Alarm 3 relays
Failure relay
Exclusion relay
Network in relay
• Controlled output for self-powered external siren.
• Controlled output for self-powered external siren.
• Controlled siren output for optical/acoustic indicators.
• In compliance with EN54/2-4.
• Input voltage: 230 Vdc 50 Hz.
• Ouput voltage:27 Vdc max 1.5A.
• Battery management, check and charge: 700 mA.
• Casing: steel painted with epoxy powders.
• Assignable batteries: max 2 x 12V – 15 Ah.
• Operation temperature: -5 to + 50°C.
• Available also in Rack 19” version.
• LCD display with 16 lines by 40 characters.
• Dimensions (HxLxD): 400 x 480 x 136 mm.
24
AREA 54/4L
ADDRESSED FIRE DETECTION SYSTEMS
EXPANDABLE CONTROL UNITS (UP TO 1024 ADDR.)
AREA54/8L Control Units
AREA54/8L cod. SC4100121
Modular analogue central unit, with multiprocessor, having 8 LOOPs max.
• The unit is provided with 1 MR/128 module (128 addresses).
• Expandable up to 1024 addresses by 7 additional line modules.
• By a two-lead closed or open loop detection line, up to 128 out of smoke
detectors, heat detectors, gas detectors, pushbuttons, actuators and
interfaces to control external equipment can be connected to each module.
• 1 RS232 opto-isolated bi-directional output towards PC.
• 1 RS485 opto-isolated serial output for communication from and to remote
keyboard.
• LCD display with 16 lines by 40 characters
• Programming from keyboard and PC.
• 240 software zones.
• 120 device groups.
• 120 zone groups
• Event log: 1000 events
• Signalling outputs:
Alarm 1 relay, Alarm 2, Alarm 3
Failure relay
Exclusion relay
Network in relay
• Controlled output for self-powered external siren.
• Controlled siren output for optical/acoustic indicators.
• In compliance with EN54 part 4 N°1293 - CPD - 0040 and EN 54 part 2
• Input voltage: 230 Vdc 50 Hz
• Ouput voltage:27 Vdc max 1.5A
• Battery management, check and charge:
700 mA
• Casing: steel painted with epoxy powders
• Dimensions (hxlxd): 500x482x145 mm
• Assignable batteries: max 2 x 12V – 15 Ah
• Operation temperature: -5 to + 50°C
• Available also in Rack 19” version
• LCD display with 16 lines by 40 characters
• 1 MC/19 module for an independent repetition of the alarm, failure and
exclusion status of each line
AREA 54/8L
25
ADDRESSED FIRE DETECTION SYSTEMS
EXPANDABLE CONTROL UNITS (UP TO 1024 ADDR.)
AREA54/16L Control Unit
AREA54/16L cod. SC3800121
Modular analogue central unit, with multiprocessor, having 16 LOOPs max.
The unit is provided with base with 1 MR/128 module (128 addresses).
• Expandable up to 2048 addresses by 15 additional line modules.
• By a two-lead closed or open loop detection line, up to 128 out of smoke
detectors, gas detectors, heat detectors, pushbuttons, actuators and
interfaces to control external equipment can be connected to each module.
• 1 RS232 opto-isolated bi-directional output towards PC.
• 1 RS485 opto-isolated serial output for communication from and to remote
keyboard.
• LCD display with 16 lines by 40 characters.
• Programming from keyboard and PC.
• 480 software zones.
• 240 device groups.
• 240 zone groups.
• Event log: 1000 events
• Signalling outputs:
Alarm 1 relay, Alarm 2, Alarm 3
Failure relay
Exclusion relay
Network in relay
• Controlled output for self-powered external siren.
• Controlled siren output for optical/acoustic indicators.
• In compliance with EN54/2-4
• Input voltage: 230 Vdc 50 Hz
• Ouput voltage:27 Vdc max 1.5A
• Battery management, check and charge: 700 mA
• Casing: steel painted with epoxy powders
• Assignable batteries: max 2 x 12V – 15 Ah
• Operation temperature: -5 to + 50°C
• Available also in Rack 19” version
• LCD display with 16 lines by 40 characters
• 2 MC/19 module for an independent repetition of the alarm, failure and
exclusion status of each line.
• Dimensions (HxLxD): 770 x 482 x 155 mm
26
AREA 54/16L
ADDRESSED FIRE DETECTION SYSTEMS
ACCESSORIES FOR ADDRESSED SYSTEMS
Line Module
MR/128 cod. SC2810121
Addressable line module allowing to acquire, pilot and check a closed or open
type detection line on which up to 128 addressed devices can be mounted.
• Fully managed by microprocessor.
• RS485 57600 bps serial asynchronous communication.
• Autonomous operation in case of control unit failure.
• Managed by microprocessor.
• Module addressing 1 – 32.
• Relay for release from RS485 in case of failure.
• 27 Vdc supply.
• Dimensions (hxl): 110 x 65 mm.
MR/128
Modules
MSP/54 cod. SC2B10121
Module allowing a parallel 80 column printer with continuous form to be
connected.
• Dimensions (hxl): 185 x 45 mm
MSP/54
SONG/54 cod. HS0910121
Module to check and activate bells/plates/sirens. It is to be used on controlled outputs in central units.
• The module is to be installed immediately near the device to be checked.
• Dimensions (hxl): 25 x 30 mm.
SONG/54
INT-SONG/54 cod. HS1010121
Module to check and activate bells/plates/sirens. It is to be used on controlled outputs in central units.
• The module is to be installed immediately near the device to be checked.
• Dimensions (hxl): 25 x 30 mm.
MC/19 cod. SC1C10121
Independent display panel of the alarm, failure and exclusion status of each
line.
• The module only concerns AREA54 central units with 8 or 16 lines in Rack
19” version.
• Dimensions (hxlxp): 89 x 482 x 28 mm.
INT-SONG/54
MC/19
27
ADDRESSED FIRE DETECTION SYSTEMS
ACCESSORIES FOR ADDRESSED SYSTEMS
Modules
SP/410 cod. SC2610121
Analogue addressed multi-purpose interface allowing to control dry contact
equipment or input for impulsive contacts and to reset connected equipment,
e.g. linear detectors, bathe tie rods or normally open pushbuttons, etc.
• Working voltage: 18 Vdc modulated
• Assorbimento medio: 150 µA.
• Average absorption: 150 µA.
• Operation temperature: -20° C to + 50° C.
• Relative humidity: 95 % Max RH non condensing.
• Dimensions (DIN guide) (HxLxD): 44 x 110 x 21 mm.
SP/410
SP/410-S cod. SC4E10121
Same as SP/410 but in IP55 enclosure.
• Dimensions (hxlxp): 105 x 170 x 82 mm.
MI/410 cod. SC2010121
Analogue addressed interface allowing to control equipment with dry and
not impulsive contacts, e.g. pushbuttons, switches, technological contacts,
heat sensing cables, by using proper connection.
• Working voltage: 18 Vdc modulated.
• Average absorption: 100 µA
• Alarm repetition (O.C): 100 mA Max
• Visual Alarm repetition: red led
• Operation temperature: -20°C to + 50°C
• Relative humidity: 95 % Max RH non condensing
• Dimensions (HxLxD): 44 x 67 mm.
MI/410
MI/410-S cod. SC9610121
Same as MI/410 but in IP55 version.
• Dimensions (HxLxD): 90 x 130 x 58 mm.
MAS/DIN-2000 cod. SC2110121
Analogue addressed actuation module allowing to manage accessory devices
arranged on field (plates, sirens, shutters, auxiliary relays, electromagnets,
etc.).
• The module has 4 open collector electronic repetitions (100mA) which define
fault, alarm 1, alarm 2, reset conditions and a repetition with the switching
by a relay which can be preselected via a jumper in order that the module can
operate in case of failure, alarm 1, alarm 2 or reset.
• Supply voltage: 20÷30Vdc
• Working voltage: 18 Vdc modulated
• Rest absorption: 200 mA
• Alarm absorption: 30 mA
• Alarm repetition (O.C): 100 mA max
• Relay output: 1A @ 24Vdc
• Operation temperature: -10 ÷ 50°C
• Dimensions (HxLxD): 65 x 110 x 35 mm.
MAS/IP-2000 cod. SC8710121
Same as MAS/DIN-2000 but in IP55 version.
• Dimensions (HxLxD): 105 x 170 x 82 mm.
28
MAS/DIN-2000
ADDRESSED FIRE DETECTION SYSTEMS
ACCESSORIES FOR ADDRESSED SYSTEMS
Modules
MCR/DIN-2000 cod. SC9110121
Analogue addressed module with collective addressing. The module allows to
manage a secondary line, made up of conventional detectors. Max number
of elements is 10.
• The interface has 4 O.C. repetitions and 4 relays for failure, alarm 1, alarm
2 reset status.
• Supply voltage: 20÷30Vdc
• Working voltage: 18Vdc modulated
• Rest absorption: 1 mA
• Alarm absorption: 20 mA per alarmed relay
• Repetition outputs (O.C.): 100 mA max
• Relay output: 1A @ 24Vdc
• Operation temperature: -10÷50°C • Dimensions (HxLxD): 112 x 168 x 50 mm.
MCR/DIN-2000
ISO/BP cod. SC6H00121
Short-circuit analyser module for lines for analogue detections; the module
is designed to ensure the operation of the detectors and/or pushbuttons
that are connected to the same line, in case a short-circuit occurs.
• The module is contained in smoke detector cap.
• On the two sides of the cap there are yellow leds having the task of signalling
the section where the short-circuit is being detected.
• For detection line connection, ZB/200 base is used.
• The module needs no additional power supply.
• Working voltage: 18 Vdc modulated
• Average absorption: 250 µA
• Operation temperature: -20°C to + 50°C
• Protection degree: IP 43
• Dimensions: Ø 100 mm H.45 mm
ISO/BP
ISO/BASE cod. SC4H00121
Short-circuit analyser module for lines for analogue detections; the module
is designed to ensure the operation of the detectors and/or pushbuttons
that are connected to the same line, in case a short-circuit occurs.
• Yellow leds having the task of signalling the section where the short-circuit is
being detected.
• The module is contained in ZB/215 connector block.
• The module needs no additional power supply.
• Working voltage: 18 Vdc modulated
• Average absorption: 250 µA
• Operation temperature: -20°C to + 50°C
• Relative humidity: 95 % Max RH non condensing
• Dimensions: Ø 100 mm H.45 mm
ISO/BASE
29
ADDRESSED FIRE DETECTION SYSTEMS
ACCESSORIES FOR ADDRESSED SYSTEMS
Modules
ISO/C cod. SC2210121
Short-circuit analyser module for lines for analogue detections; the module is
designed to ensure the operation of the detectors and/or pushbuttons that are
connected to the same line, in case a short-circuit occurs.
• Yellow leds having the task of signalling the section where the short-circuit is
being detected.
• The module is contained in S/215 connector block.
• The module needs no additional power supply.
• Working voltage: 18Vdc modulated
• Average absorption: 250 µA
• Operation temperature: -20 to + 50°C
• Relative humidity: 95 % Max RH non condensing
• Dimensions: Ø 100 mm H 45 mm
ISO/C
ISO/BASE-IP cod. SC6G00121
Same as ISO/C but in IP55 version.
• Dimensioni (hxlxp): 90x130x58 mm.
ISO ZB cod. SC4200121
Short-circuit analyser module for lines for analogue detections; the module is
designed to ensure the operation of the detectors and/or pushbuttons that are
connected to the same line, in case a short-circuit occurs.
• The module is contained in a ZB200 base
• The module needs no additional power supply.
• Working voltage: 18Vdc modulated
• Average absorption: 250 µA
• Operation temperature: -20 to + 50°C
• Relative humidity: 95 % Max RH non condensing
• Dimensions: Ø 100 mm H 45 mm
ISO/MINI cod. SC4000121
Short-circuit analyser module for lines for analogue detections; the module is
designed to ensure the operation of the detectors and/or pushbuttons that are
connected to the same line, in case a short-circuit occurs.
• The module is contained in S/215 connector block.
• The module needs no additional power supply.
• Working voltage: 18Vdc modulated
• Average absorption: 250 µA
• Operation temperature: -20 to + 50°C
• Relative humidity: 95 % Max RH non condensing
• Dimensions: Ø 100 mm H 45 mm
30
ISO/BASE-IP
ADDRESSED FIRE DETECTION SYSTEMS
DETECTORS FOR ADDRESSED SYSTEMS
Optical Detector
BPA/212 cod. SD3600121
Low profile smoke optical addressed analogue detector.
• Visual operation signal is provided by two red leds placed on the cap, which
flashes at each call from the central unit.
• The alarm signal from the central unit puts leds on steady.
• Operation principle: Tyndall effect
• Supply voltage: 18 Vdc modulated
• Absorption: 280 µA at rest
• Alarm repetition: O.C. 100 mA max
• Visual alarm repetition: 2 red leds
• Dimensions: Ø 100 x H 45 mm
• Magnetic test
• Operation temperature: –20 to +55 °C
• Relative humidity: 95% max non condensing
• EN 54 part 7 certified
• Associable to following bases: ZB/200, ZB/201, ZB/204
BPA/212
Optical heat detector
BPA/212-T cod. SD5800121
Low profile optic heat addressed analogue detector with heat probe with
intervention temperature.
• Visual operation signal is provided by two red leds placed on the cap, which
flashes at each call from the central unit.
• The alarm signal from the central unit puts leds on steady.
• Operation principle: Tyndall effect+heat probe
• Supply voltage: 18 Vdc modulated
• Absorption: 280 µA at rest
• Alarm repetition: O.C. 100 mA max
• Visual alarm repetition: 2 red leds
• Dimensions: Ø 100 x H 45 mm
• Magnetic test
• Operation temperature: –20 to +55 °C
• Relative humidity: 95% max non condensing
• Protection degree: IP 43
• Associable to following bases: ZB/200, ZB/201, ZB/204
BPA/212T
31
ADDRESSED FIRE DETECTION SYSTEMS
DETECTORS FOR ADDRESSED SYSTEMS
Differential HEAT DETECTOR
BTA/206 cod. SD3400121
Low profile maximum temperature thermo-speedometric and heat addressed analogue detector.
• Visual operation signal is provided by two red leds placed on the cap, which
flashes at each call from the central unit.
• The alarm signal from the central unit puts leds on steady.
• Operation principle: Double heat probe
• Supply voltage: 18 Vdc modulated
• Absorption: 300 µA at rest
• Alarm repetition: O.C. 100 mA max
• Visual alarm repetition: 2 red leds
• Size: Ø 100 x H 45 mm
• Magnetic test
• Operation temperature: –20 to +55 °C
• Relative humidity: 95% max non condensing
• EN 54 part 5 certified
• Associable to following bases: ZB/200, ZB/201, ZB/204.
BTA/206
REMOTE PANEL
Consolle 54
CONSOLLE/54 cod. KP3400121
Remote Panel useful for repeating and displaying active events and commands from and to the Central Units of AREA 54 series.
• The panel is housed in a enclosure the design of which was studied in order
that the panel can be used both as a desk panel and wall panel.
• AREA 54 series can manage up to 32 remote panels placed at a maximum
distance of 1200 m.
• Backlit display with 8 lines by 20 characters displays and repeats all events
occurring at the central unit.
• A backlit keyboard provided with specific keys for commands from and to the
Central Unit is available to user.
• From the keyboard, events from the central unit can be acquired, lag time
for alarm can be incremented if programmed at the central unit, sirens can
be entered /cut off, a general reset can be performed and a functional test
can be made on all visual signalling (LED).
• Alarm and Fault status is acoustically signalled by a local buzzer, which is
disabled from the keyboard.
• Supply voltage: 17 to 30 Vdc
• Absorption: 70 mA @ 24 Vdc at rest
• 200 mA @ 24 Vdc with lit keyboard and display
• Connection:
4-lead bus 485
• Alarm output: Relay 1 A @ 30Vdc
• Operation temperature: -5° C to + 50° C
• Relative humidity: 95 % maximum non condensing
• Protection degree: IP 43
• Dimensions (HxLxD): 195 x 290 x 50 mm.
32
CONSOLLE/54
ADDRESSED FIRE DETECTION SYSTEMS
BUTTONS FOR ADDRESSED SYSTEMS
Buttons
P/430 cod.SB2200121
Red alarm analogue pushbutton with recommissioning.
• Visual alarm repetition: red led
• Dimensions (HxLxD): 110 x 110 x 42 mm
• Weight: 100 g
• Average absorption: 100 µA @ 18 Vdc
• Actuation Type: Recommissioning
P/430
P/435 cod. SB3900121
Red alarm conventional pushbutton with breaking.
• Visual alarm repetition: red led
• Dimensions (HxLxD): 110 x 110 x 42 mm
• Weight: 100 g
• Average absorption: 100 µA @ 18 Vdc
• Actuation Type: Breaking
P/410 cod. SB3600121
P/435
P/420 cod. SB2100121
P/410
Break glass addressed analogue pushbutton with accident-prevention glass
red in colour.
• Visual alarm repetition: red led
• Average absorption: 100 µA @ 18 Vdc
• Alarm repetition: 100 mA. Max.
• Dimensions (HxLxD): 64x120x555 mm
• Weight: 120 g
• Protection degree: IP 30
Break glass addressed red alarm analogue pushbutton with transparent
protection cover.
• Visual alarm repetition: red led
• Dimensions (HxLxD): 85x85x52 mm
• Weight: 180 g
• Average absorption: 100 µA @ 18 Vdc
• Actuation Type: Breaking
• Protection degree: IP 54
P/420
33
ADDRESSED FIRE DETECTION SYSTEMS
ACCESSORIES FOR CENTRALISATION
Centralisation
MRS/232/485-DIN cod. SC9310121
Module to convert signals from RS232 to RS485 allowing serial communication between apparatuses up to 1,200 mt distance.
• Available also in IP 55 version, MRS/232/485-IP coded.
• Power supply: 12 – 24 Vdc
• Absorption: 50 mA
• Operation: -5° C to + 50 °C
• Dimensions (HxLxD): 67x112x45 mm
MAPPA/54 cod. SW2700121
Software for graphic map system, capable to connect up to 18 central units
through serial line, LAN network or modem.
• For system configuration it is necessary to insert graphic map sheets
(SHEET/54) and devices on field (POINT/54).
MMS/54 cod. SC1B10121
Module enabling the central units of AREA54 series to following functions:
- Connecting and managing a modem
- Connecting central units in Master / Slave configuration.
• Dimensions (hxl): 180X65 mm
• 1 serial connector 485 for connecting Master/Slave central units.
• 1 connector DB9 for connection to modem
MODEM54 cod. CT7300123
56K analogue modem
LAN/54 cod. SC7910121
MODEM54
TLG/54 cod. SW2800121
LAN/54
Module allowing connection to a LAN (Local Area Network) of analogue central units of AREA 54 series.
• Communication protocol is of TCP/IP UDP type.
• Power Supply: 24 Vdc
• Dimensions (HxLxD): 110x85 mm
Program providing functions for unloading, displaying and printing the chronological history log of AREA54 central units.
• The program allows to constantly keep under control the operation of central
units, to execute commands remotely and to inquire and modify the status of
AREA54 central units.
• Communication between central units and PC can be implemented by serial
connections, by connections through the network, by connections via Modem
(also simultaneously).
FOGLIO/54 cod. SW2900121
Graphic map leaf from autocad support
PUNTO/54 cod. SW3100121
Graphic map point from autocad support
SOFT/54 cod. SW2300121
Software for local/remote AREA54 programming
34
UNIVERSAL
CONNECTION
BASES
DUCTED
DETECTION
35
UNIVERSAL CONNECTION BASES
UNIVERSAL CONNECTION
BASES
FOR CONVENTIONAL AND AREA54 DETECTORS
ZB/200 cod. SD2700121
Universal base for smoke and thermo-speedometric optical sensors for
conventional analogue and digital systems.
ZB/201 cod. SD2800121
Universal base with 12 Vdc dry contact relay for repeating the alarm status
• The base is suitable for conventional systems and burglar-proof systems. The
base is also suitable for smoke and thermo-speedometric optical sensors.
ZB/204 cod. SD9D00121
Universal base with 24 Vdc dry contact relay for repeating the alarm status.
• The base is suitable for conventional systems and burglar-proof systems. The
base is also suitable for smoke and thermo-speedometric optical sensors.
ZB/210 cod. SD4300121
Universal base with coding for connecting conventional detectors for
analogue systems.
ZB/212 cod. SD1N00121
Base with local alarm signalling.
• The base can manage a LR500 visual repeater. The base must be supplied
through an external power.
ZB/215 cod. ZC7100121
Base support for ZB series low profile bases.
DUCTED
DETECTION
DUCTED DETECTION
R/820 cod. SD3L10121
The analysis chamber for ducted detection was designed to check for the
presence of smoke in air ducts and allows to timely detect a spreading fire.
• Inside the analysis chamber there can be located analogue and digital optical
smoke detectors, as well as conventional optical smoke detectors. Inside the
chamber there is placed ZB/200 connection base.
• Container in thermoplastic material; on container cover there is a window in
plexiglas for sensor local alarm visual control.
• Two PVC probes 500 mm long.
• Dimensions (HxLxD): 107x81x46 mm
36
R/820
FAP500
DIGITAL
SYSTEM
FAP 54/1.................................... pag. 40
FAP 54/4.................................... pag. 41
FAP 54/8.................................... pag. 41
FAP 54/16.................................. pag. 41
ACCESSORIES............................ pag. 42
BUTTONS................................... pag. 43
DETECTORS............................... pag. 44
37
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM
From Elkron research, FAP 500 series is born, i.e. a new smoke detection digital system.Within
Elkron fire system there is included from today FAP 500 series, i.e. a new modular, flexible digital
system, EN54-approved and available in 4 control unit models with 1 to 8 loops, all with extension capability. System main evolution, differentiating the system from anything else present on
the market, is the capability of self-learning the address in any installation mode. In addition, the
system is provided with a short circuit isolator integrated in all components. FAP 500 system
enables both easily interface to shut off systems and assure an excellent protection level. This is
why, with FAP 500, Elkron fire system is also a Hi-protection system.
System high flexibility.
FAP500 system is a clear evolution over control units present on the market, as enabling to connect all control unit models to the network, interface to shut off systems and assure an excellent
performance level joined to simple installation, programming and management. The system is
modular, flexible and includes 4 control unit models:
• control unit with 1 loop (FAP 541)
• control unit with 2 loops with extension capability to 4 (FAP 544)
• control unit with 4 loops e with extension capability to 8 (FAP 548)
• control unit with 8 loops with extension capability to 16 (FAP 5416)
The line can be connected in 3 different ways, guaranteeing the point (detector, device, pushbutton, etc...) to be automatically pre-learned:
• line with closed loop
• open lines (entering/exiting connection)
• open lines (parallel connection)
Easy programming.
Thanks to this flexibility, all system needs can be best met, so making installation step much easier. Each configuration type can be easily programmed via either control unit keyboard or PC.
All control units are prearranged for communicating within the network through a LAN TCP/
IP interface, a communication port for Master/Slave functions, a printer connection port, an
optically isolated RS485 port for interfacing repeater panels and shut off control units, an USB
port for downloading data and system configuration via PC, a communication interface for transmitting events via GPRS/GSM/PSTN.
All is under control, remotely too, thanks to new software platform enabling Elkron systems to
interact among one another and remotely transmit all system information.
38
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM
FAP 500 SERIES CONTROL UNITS
The new control unit FAP544 is modular that is possible to expand the standard configuration
with functions and peripherics. It is possible to manage a minimum of 2 up to 4 addressed
loop.
Connectibility
RS485 communication port
Communication port for LAN TCP/IP network
Printer connection port
Communication port for MASTER/SLAVE connection
Connection for 16 remote panels
Managing configuration / programming / remote assistance sw via PC
Managing graphic maps / remote management
External communication via GPRS
External communication via PSTN
EXTERNAL
POWER SUPPLY
UNITS
CONTROL
FOR REMOTE
PANELS (16 MAX)
CONTROL UNIT RELAY
CONTROLLED RELAY OUTPUT
SELF-POWERED SOUNDER OUTPUT
ALARM RELAY 1
ALARM RELAY 2
FAULT RELAY
PROGRAMMABLE RELAY
FDO500 +
SD500
KEYPAD
ELECTROMAGNETS
PANEL
PRINTER
MODULE
IMO500
MODULE
PS2
RS232/485
MODULE
LINEAR DETECTORS
FDT500 +
SD500R
RS232
OUTPUT
MASTER/SLAVE
FOR EXTINGUISHING
CONTROL UNITS AND
FAP500 CONTROL UNITS
IO500
MODULE
LAN
LR500SI
PANEL
O/A
EXPANSION
MODULE
FA128
FM500R
USB
LOOP LINE
128 POINTS MAX
PC PROGRAMMING
FDOT500 +
SD500R
LR500SI
39
FAP500 DIGITAL SYSTEM
1 LOOP LINE CONTROL UNIT
FAP541 Control Unit
FAP541 cod. SC6100121
Microprocessor control unit with 1 loop line
• Configuration: 1 loop line (class A) or 2 open lines (class B)
• Possibility of managing up to 128 points for loop (64 for open line).
• Point self-learning and point logic address.
• Backlit graphic display 4 x 40 characters
• Event log: 1000 events
• Chronological history directly shown on display.
• 10 passwords programmable on 3 levels.
• 480 programmable zones.
• USB port for local PC connection for programming via SW
• Possibility of monitoring detector signal/noise ratio level
• Real time clock with built-in buffer battery
• Non volatile memory
• Control unit outputs: 5 (alarm 1, alarm2, failure, programmable (mains
failure/exclusion)
• Internal buzzer
• Programmable alarm threshold: for zone, for individual point
• Exclusion of individual point /zone
• Power supply: 230Vca
• Max. current: 1.5A@24Vcc
• Battery charge limit and battery charge check
• Battery housing: 2 12 @12Vcc batteries
• Possibility of implementing at least 2 Km loop with 2 x 1.5 mm2 screeened
cable
• Noise immunity up to 30Vm
• Common dialogue protocol for all system control units
• Dimensions: 490 (L) x 350 (H) x 145 (D) mm
• COMPLIANT WITH EN54 STANDARDS, part 2 and part 4
40
FAP541
FAP500 DIGITAL SYSTEM
4, 8 AND 16 LOOP LINE CONTROL UNITS
FAP544 Control Unit
FAP544 cod. SC6200121
Microprocessor control unit with 2 loop lines expandable to 4
• Basic configuration: 2 loop lines (class A) or 4 open lines (class B)
• Max. configuration: 4 loop lines (class A) or 8 open lines (class B)
• Possibility of managing up to 128 points for loop (64 for open line).
• Point self-learning and point logic address.
• Backlit graphic display 240*128 - 4.7 “.
• Event log: 1000 events
• Chronological history directly shown on display.
• 10 passwords programmable on 3 levels.
• 480 programmable zones.
• USB port for local PC connection for programming via SW
• Possibility of monitoring detector signal/noise ratio level
• Real time clock with built-in buffer battery
• Non volatile memory
• Control unit outputs: 5 (alarm 1, alarm2, failure, programmable (mains
failure/exclusion)
• Internal buzzer
• Programmable alarm threshold: for zone, for individual point
• Exclusion of individual point /zone
• ON/OFF by password
• Power supply: 230Vac
• Max. current: 2A@24Vdc
• Battery charge limit and battery charge check
• Battery housing: two 12 @12Vdc batteries
• Possibility of implementing at least 2 Km loop with 2 x 0.75 mmÇ cable
(screened and NOT screened)
• Noise immunity up to 30Vm
• Common dialogue protocol for all system control units
• Dimensions: 490 (L) x 350 (H) x 145 (D) mm
• COMPLIANT WITH EN54 STANDARDS, part 2 and part 4
FAP544
FAP548 Control Unit
FAP548 cod. SC6600121
Microprocessor control unit with 4 loop lines expandable to 8.
• Same as FAP544
FAP5416 Control Unit
FAP5416 cod. SC6700121
Microprocessor control unit with 8 loop lines expandable to 16.
• Same as FAP544
41
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM: MODULES AND ACCESSORIES
Expansion module
FA128 cod. SC3310121
1 loop expansion module
• The expansion module enables to expand the control unit by 1 loop line or
2 open lines. 128 points (detectors, push-buttons, interfaces, etc.) can be
connected. The module, to be directly installed on the control unit backplane,
enables the acquisition and control of the connected devices. Connection
with devices can be implemented with closed loop line or with open loop line.
Configuration is made during programming.
FA128
Accessories
FKP500 cod. KP5200121
Remote Panel
• The repeating panel enables active and constant monitoring of every event.
The FAP500 control unit can manage up to 16 remote panels; connection
to the control unit and to other panels (if any) is made by means of RS485
opto-isolated port. Panel identification address is made via on board switch.
Information is displayed through backlit display with 4 lines x 40 characters.
Power supplies, exclusions/reset, alarms and failures are indicated by a
series of leds. The user has a keypad fitted with dedicated keys for controls
from/to the control unit.
IO500 cod. SC3A00121
Multipurpose module 1 input/ 1 output
• This module enables to interface on FAP500 digital system, stable conventional
detectors with dry contacts (NC/NO), to connect probes or other devices
fitted with pulse controls. Moreover the same interface can pilot actuators
(e.g.: panels, plates, electromagnets, sirens, etc.) and check the line control.
Each input / output can be programmed.
• Power supply: 10 ÷ 24Vdc
• Absorption: 250 mA @ 24Vdc
• Relay output: 1A, 30Vdc, resistive load
• Alarm repeat output: 12mA max
• Working temperature: -5 ÷ 50 °C
• Relative humidity: 95% max non condensing
IOM500 cod. SC3B00121
Multipurpose module 4 inputs/ 4 outputs
• This interface features the same characteristics as module IO500, it
enables to connect stable conventional detectors with dry contacts (NC/
NO), to connect probes or other devices fitted with pulse controls and to
pilot actuators (e.g.: panels, plates, electromagnets, sirens, etc.) and check
the line control, but it features 4 programmable inputs and 4 programmable
outputs.
RS232/485 cod. IT1410121
RS232/485 interface for MASTER/SLAVE and remote panel
42
IO500
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM: MODULES AND ACCESSORIES
Accessories
SOFT/FAP500 cod. SW3500121
Configuration SW
• This software enables to acquire the system characteristics by reading
the control unit data; to unload and to programme the configuration and
parameters of each individual point
MAPPE/FAP500 cod. SW3600121
Supervision software with graphic maps
• This software enables full network management of one or more control units.
It is possible to manage and assist the system in local or remotely.
LAN/TCP/IP500 cod. IT1510121
LAN/TCP/IP interface
• It enables to connect several control units on a LAN network.
ITS500 cod. IT1610121
Printer interface.
MGSM500 cod. CT6010121
Modem interface for GSM.
MPSTN500 cod. CT5910121
Modem interface for PSTN.
FAP500 SYSTEM: BUTTONS
Buttons
FM500 cod. SD6000121
Break glass manual pushbutton, complete with self-learning circuit
• Fire alarm pushbuttons are used for signalling an alarm manually. To use the
break glass pushbutton model just press the glass in the middle in order to
break it and to operate the internal switch. These pushbuttons are provided
with a special tool to be used to perform the TEST, to open the cover and to
replace the glass. The alarm state is shown by the switching on of a red LED.
Compliant with Standards: EN54 part 11
FM500
FMR500 cod. SB6100121
Manual recommissioning pushbutton, complete with self-learning circuit and
short-circuit isolator.
• To use the recommissioning pushbutton model just press the glass in the
middle in order to push it inwards, thereby operating the switch. These
pushbuttons are provided with a special tool to be used to perform the TEST
and to replace the glass. The alarm state is shown by the switching on of a
red LED. Compliant with Standards: EN54 part 11
FMR500
43
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM: DETECTORS
Photo-optical smoke detector
FDO500 cod. SD4800121
Low profile photo-optical smoke detector, complete with self-learning circuit
and short-circuit isolator.
• Smoke detectors work according to the light scattering principle caused by
smoke particles present in the air. The smoke detector has the automatic gain
control function; a microcontroller calculates reading compensation to keep
constant sensitivity and corrects any level increase due to dust depositing
into the analysis cell. Smoke detectors shall be installed in places protected
against draughts which may divert the flow of combustion particles and in
places where the common activities performed do not cause gas material
fires.
• Power supply: 20Vdc (modulated voltage between -15% and + 10%)
• Average absorption at rest: 250 mA@20Vdc
• Absorption at alarm: 2mA@20Vdc
• Two-colour led: red alarm - green regular operation
• Relative humidity max: 93%
• Working temperature: 0 ÷ 50°C
RIVELATORI
CONVENZIONALI
•
Weight: 70 g
• Dimensions: ø 90 x 31 (H) mm
• Certificato EN54 parte 7, certification number: 1293-CPD-0082
FDO500
Heat detector
FDT500 cod. SD5700121
Low profile heat detector, complete with self-learning circuit and short-circuit isolator.
• Heat detectors monitor the temperature values in the area where they are
installed.
• A microcontroller analyses and compares the signal received from a NTC
type temperature detector and activates the alarm if the read temperature
exceeds 58°C.
• Power supply: 20Vdc (modulated voltage between -15% and + 10%)
• Average absorption at rest: 250 mA@20Vdc
• Absorption at alarm: 2mA@20Vdc
• Static alarm threshold: 58°
• Two-colour led: red alarm - green regular operation
• Relative humidity max: 93%
• Working temperature: 0 ÷ 50°C
• Weight: 70 g
• Dimensions: ø 90 x 40 (H) mm
• Compliant with EN54 Standards, part 5 class A1S, certification number:
1293-CPD-0084.
44
FDT500
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM: DETECTORS
Thermo-speedometric detector
FDTD500 cod. SD9000121
Low profile thermo-speedometric detector, complete with self-learning circuit and short-circuit isolator.
• Thermo-speedometric detectors monitor temperature rise in the area where
they are installed. A microcontroller analyses and compares the signal
received from a NTC type temperature detector and activates the alarm if
the read temperature rise exceeds 5°C per minute.
• Power supply: 20Vdc (modulated voltage between -15% and + 10%)
• Average absorption at rest: 250 mA@20Vdc
• Absorption at alarm: 2mA@20Vdc
• Static alarm threshold: 58°
• Two-colour led: red alarm - green regular operation
• Relative humidity max: 93%
• Working temperature: 0 ÷ 50°C
• Weight: 70 g
• Compliant with EN54 Standards, part 5 class A1R, certification number:
1293-CPD-0085.
FDTD500
Optical- heat detector
FDOT500 cod. SD9K00121
Low profile optical- heat detector, complete with self-learning circuit and
short-circuit isolator.
• Double technology detectors (smoke-heat) base their operating principle on
the light scattering principle caused by smoke particles present in the air
(TYNDALL effect) and on temperature monitoring within the area where they
are installed. A microcontroller analyses and compares the signal received
from a NTC type temperature detector and activates the alarm if the read
temperature exceeds 58°C. The smoke detector has the automatic gain
control function; a microcontroller calculates reading compensation to keep
sensitivity constant in time.
• Power supply: 20Vdc (modulated voltage between -15% and + 10%)
• Average absorption at rest: 250 mA@20Vdc
• Absorption at alarm: 2mA@20Vdc
• Static alarm threshold: 58°
• Two-colour led: red alarm - green regular operation
• Relative humidity max: 93%
• Working temperature: 0 ÷ 50°C
• Weight: 70 g
• Dimensions: ø 90 x 40 (H) mm
• Compliant with EN54 standards part 7 and part 5 class A1, certification
number: 1293-CPD-0083
FDOT500
45
FAP500 DIGITAL SYSTEM
FAP500 SYSTEM: BASES FOR DETECTORS
Standard base
SD500 cod. SD4K00121
Digital detector standard base.
• The base is standard for all digital detectors of the FAP500 series.
• Material: ABS
• Colour: white
• Dimensions: 90 mm
SD500M cod. SD4S00121
Digital detector standard base, FAP500 series - package with 10 pcs.
SD500R cod. SD5K00121
Digital detector standard base with alarm repetition.
• The base is standard for all digital detectors of the FAP500 series, its output
enables to directly pilot (through the loop supply) the outdoor gem LR500SI
• Material: ABS
• Colour: white
• Dimensions: 90 mm
• Alarm repetition output: 12 mA@24Vdc
SD500-RM cod. SD6S00121
Digital detector standard base with alarm repetition, FAP500 series package with 10 pcs
SD515cod. SD2V00121
Base support for series 500 bases
46
EXTINGUISHING
CONTROL
UNIT
47
EXTINGUISHING CONTROL UNIT
EXTINGUISHING
CONTROL UNIT
FDT500
FDT500
IO500
TM24
LOOP 1
OUT 2
OUT 1
FMR500
FMR500
UNBLOCK
PUSH
BUTTON
EXTINGUISHING
SYSTEMS
REMOTE
CONTROL
SWITCH
48
EXTINGUISHING CONTROL UNIT
CDS CONTROL UNIT
CDS cod. SC3600121
Extinguishing control panel fitted with one module expandable to 2
• CDS extinguishing control panel is a non-expandable, 1 loop, microprocessorbased control panel that shares all FAP500 system devices and also
incorporates a extinguishing module with provisions for expansion to 2.
• CDS has been designed so as to fully comply with EN 12094-1 and EN54-4
European Norms.
• Certification No.: 0051-CPD-0177.
FIRE EXTINGUISHING MODULE CHARACTERISTICS
• Flux meter input
• Pressure switch input
• Emergency extension input
• Manual discharge activation input
• Input for discharge activation through an external control panel
• Release “ON” relay (NO or NC contact, 1A max)
• Emergency extension relay (NO or NC contact ,1A max)
• Evacuation siren output (250 mA max.)
• Release output 1 (Pilot, 750mA max)
• Release output 2 (Solenoid valve, 750mA max)
CDS
DETECTION LINES CHARACTERISTICS
• Configuration: 1 loop line (class A) or 2 open lines (class B).
• Possibility of managing up to 128 points per loop.
• Point self-addressing and point logic address.
• Backlit display: 4 x 40 characters
• Event log: 1.000 events
• Chronological event log available on the display directly.
• 10 passwords programmable on 3 levels.
• 480 programmable zones.
• USB port for connection to local PC for programming via SW
• Possibility of monitoring detector signal/noise ratio level
• Real time clock with built-in buffer battery
• Non-volatile memory
• Control panel outputs: 5 (alarm 1, alarm2, failure, programmable (mains
failure/exclusion)
• Internal buzzer
• Programmable alarm threshold: for zone, for individual point
• Exclusion of individual point /zone
• Power supply: 230Vac
• Max. current: 1.5A@24Vdc
• Battery charge limit and battery charge check
• Battery housing: two 12 @12Vdc batteries
• Possibility of implementing max 2 Km loop with 2 x 0.75 mm² with screened
cable
• Noise immunity up to 30Vm
• Common communication protocol for all system control panels
• Dimensions: 490 (L) x 350 (H) x 145 (D) mm
ESPCDS cod. SC3500121
ESPCDS
Expansion to 1 module for extinguishing control panel.
49
50
GAS, LIQUIDS,
HEAT AND
LINEAR
DETECTORS
AND CONTROL
UNITS
GAS DETECTION CONTROL UNIT.pag. 52
TOXIC AND EXPLOSIVES GAS DET.... pag. 53
FLAME DETECTOR...................... pag. 56
LIQUID PRESENCE DETECTOR..... pag. 57
SPECIAL HEAT DETECTOR........... pag. 57
LINEAR DETECTOR..................... pag. 59
SUCTION SYSTEMS.................... pag. 62
51
DETECTORS AND CONTROL UNITS
ATEX VERSION CONTROL UNITS
Gas Detection Control Units
ST/PL4 cod. SC6R00123
Gas detection central unit allowing the connection of 4 minimum number to
8 maximum number of inflammable toxic gasses or oxygen detectors (through optional board) with 4-20 mA proportional output.
• For each input it is possible to set the type of detector, suitable measure
range and alarm level values.
• Concentration values measured are shown on a backlit liquid crystal display.
• The central unit has 5 relay outputs, 4 of which are associated to Failure,
Alarm 1, Alarm 2, Alarm 3 and one is an auxiliary relay output that can be
associated to one of the four above statuses.
• By adding an optional module, in addition to the 4 inputs there are also
implemented 16 open collector outputs.
• Housing: Metallic enclosure
• Dimensions (hxlxd): 225x360x110 mm
• Display: backlit LCD with 16 characters for 2 lines
• Power supplay: 230 Vac
• Absorption: 80 mA at rest, 160 mA on alarm status, 240 mA with
expansion board
• Relay outputs: 1 A @ 24 Vdc 5 A @ 24 Vdc (relay AUX)
• Operation temperature: -0 to - 40°C
• Relative humidity: 15-85% non condensing
ST/PL4
ST/PL4/ESP cod. SC7R10123
Expansion module for 4 inputs, 16 O.C. outputs that can be set for Alarm 2
or Alarm 3 ST/PL4 for central unit.
• O.C. outputs: 250 mA
STG/MTSLB cod. SC8R00123
Gas detection central unit allowing the connection of 8 minimum number to
104 maximum number of inflammable toxic gasses or oxygen detectors with
4-20 mA proportional output.
• The connection is through (optional) remote concentrators arranged on
RS485 serial line.
• The central unit has inside it 4 output relays to interface towards the field,
and 4 open collector outputs.
• The unit can be configured with detectors that differ from one another as
both gas detected and activation thresholds.
• Both explosive and toxic gas detectors can be configured.
• The central unit can store up to 800 events.
• Housing: Metallic enclosure
• Dimensions (hxlxd): 420x440x140 mm
• Display: backlit LCD with 256x64 dots
• Power supplay: 230 Vac
• Expansibility: Up to 64 O.C. outputs with 8 STG/OUT16 optional modules
• Operation temperature: -0 to - 40°C
• Relative humidity: 15-85% non condensing
52
STG/MTSLB
DETECTORS AND CONTROL UNITS
ATEX VERSION CONTROL UNITS
Accessories for ATEX control units
STG/IN8 cod. SC9R10123
Remote module for 8 board inputs
STG/OUT16 cod. SC1S10123
Remote module for 16 open collector programmable board outputs
STG/BOX cod. ST0510123
Metallic enclosure for containing a STG/IN8 or STG/OUT16 module
WMB/138V15 cod. ST0610123
Metallic enclosure with 12 Vdc 1.5 A supply for containing a STG/IN8 or
STG/OUT16 module.
TOXIC AND EXPLOSIVES GAS DETECTORS
Gas detectors are used to detect the presence of combustibles in concentrations
that can be expressed as a percentage of Explosiveness Lower Limit (%ELL) and
of toxics that can be expressed as parts per million (ppm) or in the detection of
oxygen deficiency or excess.
For explosive mixtures detectors a catalytic sensor is used, while for toxics
detectors an electrochemical cell sensor is used.
The detector is fully controlled by a 10 bit microprocessor. The detectors provide
either a current proportional output (4-20 mA) or relay contacts through an
optional board.
GAS DETECTORS, EX II 3GD TYPE
S1604VB cod. SD2T00123
Petrol vapours detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
• STS3REL relay board cannot be used.
S2096PR cod. SD5T00123
EX II 3GD
Propane gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S2096BU cod. SD6T00123
Butane gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S1606CO cod. SD7T00123
CO (Carbon Monoxide) detector 4-20 mA, 0-300 ppm
• Electrochemical cell sensor.
• Absorption: 30 mA@12Vcc.
• STS3REL relay board cannot be used.
53
DETECTORS AND CONTROL UNITS
TOXIC AND EXPLOSIVES GAS DETECTORS
GAS DETECTORS, EX II 3GD TYPE
S2096ME cod. SD9S00123
Methane gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S1702VB cod. SD3T00123
Petrol vapours detector 4-20 mA, 0-100% LEL
• Pellistor sensor.
• Absorption: 30 mA@12Vcc.
• Alarm output: 2 relays 1A@30Vcc.
• Fault output: 1 relay 1A@30Vcc.
• Suitable for parking lots.
S2096GP cod. SD4T00123
LPG gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S1703CO cod. SD8T00123
CO (Carbon Monoxide) detector 4-20 mA, 0-300 ppm
• Electrochemical cell sensor.
• Absorption: 30 mA@12Vcc.
• Alarm output: 2 relays 1A@30Vcc.
• Fault output: 1 relay 1A@30Vcc.
• Suitable for parking lots.
MAIN CHARACTERISTICS OF GAS DETECTORS
Power supply
12 – 24Vcc – 20% + 15%
Auto-zero routine
Zero drift compensation
Light indications
Blinking LED
Precision
± 10% full scale
Warm-up time
5 minutes
Stabilization time
< 2 minutes
Response time
< 15 sec. T50; < 25 sec T90 (flammable gas version)
Air velocity
< di 6 mS
Digital filter
Sampled values variable averages
Resolution
1.024 points
IP protection
IP55
Weight
350 g
Dimensions (L) x (H) x (D) mm
106 x 170 x 65
Reference Standards
EN50014 EN50018 EN50021 (essential safety
requirements EEx-n) / EN61779-1/4 (performances)
Atex marking
CE 722 Ex II 3GD Ex nA d IIC T6 IP55 T85°C
54
DETECTORS AND CONTROL UNITS
TOXIC AND EXPLOSIVES GAS DETECTORS
GAS DETECTORS, Ex II 2GD TYPE
S2097VB cod. SD1U00123
Petrol vapours detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S2097ME cod. SD9T00123
Methane gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
EX II 2GD
S2131CO cod. SD5U00123
CO (Carbon Monoxide) detector 4-20 mA, 0-500 ppm
• Electrochemical cell sensor.
• Absorption: 30 mA@12Vcc.
S2097PR cod. SD3U00123
Propane gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S2097GP cod. SD2U00123
LPG gas detector 4-20 mA, 0-100% LIE
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
S2097BU cod.SD4U00123
Butane gas detector 4-20 mA, 0-100% LEL
• Catalytic sensor: Nemoto.
• Absorption: 130 mA@12Vcc.
MAIN CHARACTERISTICS OF GAS DETECTORS
Power supply
12 – 24Vcc – 20% + 15%
Auto-zero routine
Zero drift compensation
Light indications
Blinking LED
Precision
± 10% full scale
Warm-up time
5 minutes
Stabilization time
< 2 minutes
Response time
< 15 sec. T50; < 25 sec T90 (flammable gas version)
Air velocity
< di 6 mS
Digital filter
Sampled values variable averages
Resolution
1.024 points
IP protection
IP66
Weight
950 g
Dimensions (L) x (H) x (D) mm
110 x 135 x 80
Reference Standards
EN50014 EN50018 EN50021 (essential safety
requirements EEx-n) / EN61779-1/4 (performances)
Atex marking
CE 722 Ex II 2GD Ex d IIC Ex tD A21 IP65 T85°C
55
DETECTORS AND CONTROL UNITS
TOXIC AND EXPLOSIVES GAS DETECTORS
Accessories for gas detectors
ST/S3REL cod. SC5R10123
Board with three relays for gas detectors.
• It allows to have contacts free from voltage.
• The first output is associated to failure or Watch-Dog. The second output can
be associated to either alarm 1 or alarm 2 of detector. The third output can
be associated to either alarm 2 or alarm 3 of detector.
• Relay contacts current carrying capacity: 50mA @ 24 Vdc; 100 mA @ 12
Vdc.
VAL TEST cod. SI7100123
Test kit containing instruments necessary to execute requested functionality tests.
• It contains a flowmeter valve and a fitting suitable to connect the tanks to the
detectors, in order to create a well defined titrated atmosphere.
INFRARED FLAME DETECTOR
RU-ADPE cod. SD7100121
Flame detector immediately responding to infrared thermal radiation released by fire. The detector is tuned to flame pulses in order to ignore sunlight
and lamps.
• It is contained in IP66 explosion proof enclosure.
• It needs 24 Vdc supply, with wide tolerance on its value, and provides two
types of outputs: a wide range switching contact SPDT and a static signal on
NPN collector.
• Both outputs go into alarm after a certain lag and go back to a rest condition
as fire is over.
• Lag time is normally calibrated to 5 seconds; however, it can be ranging 1
to 10 seconds.
• Sensitivity is calibrated to 2 - 3%, i.e. a 10 cm flame at a 5 m distance, or a
20 cm flame at a 10 m distance.
• View field is a 90° cone; however, beyond 90°, the detector can still see,
although with reduced sensitivity; and, by reflection, it can even see zones in
shade behind obstacles.
• On detector front side, a red LED warns about test or alarm status.
• Casing: explosion proof aluminium alloy.
• Painting: epoxy, grey RAL7035.
• Implementation: II 2 GD EEx-d IIC T6 IP66.
• Certified: CESI 01 ATEX 036.
• Compliance with: directive ATEX 94/9 CENELEC EN 50014 (CEI 31.8) EN
50018 (CEI 31.1)
• Dimensions (mm): 230 x 230 x 154h main body only.
• Weight: 10 kg including detector.
• Cables input: 1’’ Gas.
56
DETECTORS AND CONTROL UNITS
LIQUID DETECTOR
Liquid detector
RA/209 cod. SD2B00121
Electronic detector to detect the presence of (uninflammable) liquids.
• Detecting the presence of water is through 4 support gilt feet, which put the
detector into alarm by switching a relay placed inside it.
• For higher protection, RA/209 model is provided with a humidity detector
having a sensivity that can be regulated by an inner trimmer.
• Facility for connecting 10 external probes of RA/209S model.
• Container material: Thermoplastic, white colour
• Operation voltage: 12 - 27 Vdc
• Average absorption: 3.5 mA at 27 Vdc
• Operation temperature: +5 to +50 °C
• Dimensions: 64 x 96 x 30 mm
SPECIAL HEAT DETECTOR
Heat Detectors
RTS/2 cod. SD2C00123
IP65 Special heat detector based on the deformation of a bimetallic element
which closes a dry contact as the temperature is reached. This makes the
detector easy to be interfaced with any board type.
• The heat detector is suitable for detection in environments where potentially
explosive atmospheres may be present. Its construction is complying with
sector specific regulations (ATEX).
• The detector can operate based on the type of heat probe being used as
follows:
• DF: Gradient detector. The intervention only occurs when temperature
increment is higher than 13 °C per minute.
• SD: Semidifferential detector. The intervention always occurs as calibration
temperature is reached; further, an intervention lead occurs when temperature
increment is higher than 15°C per minute.
• MAX: Maximum temperature detector.The intervention only occurs when
calibration temperature is reached.
• Code SD2500123 is referred to a detector with a 60° C calibration
temperature. Different grades are available to specify in the command.
• Operation principle: Bimetallic element deformation
• Protection degree: IP 65
• Working temperature:190 C° MAX
• Relative humidity: 98%
• Weight: 0,9 Kg
• Bimetallic component: Nilvar-Brass
• Regulation range: -40 + 190 C°
• Intervention threshold: On Request /mod SD Max 88 C°
• Alarm condition: Normally closed contact
• Contacts current carrying capacity: 2,5 A
• Working voltage: 48 Vdc
• Enclosure material: Aluminium alloy
• Dimensions: 110 x 13 x 70 mm
RTS72
57
DETECTORS AND CONTROL UNITS
SPECIAL HEAT DETECTOR
Heat detector
RTS/4 cod. SD4C00123
IP55 heat detector based on the deformation of a bimetallic element which
closes a dry contact as the temperature is reached.
• This makes the detector easy to be interfaced with any board type.
• The detector can operate based on the type of heat probe being used as
follows:
DF: Gradient detector. The intervention only occurs when temperature
increment is higher than 13 °C per minute.
SD: Semidifferential detector. The intervention always occurs as calibration
temperature is reached; further, an intervention lead occurs when temperature
increment is higher than 15°C per minute.
MAX: Maximum temperature detector. The intervention only occurs when
calibration temperature is reached.
• Code SD4J00123 is referred to a detector with a 60° C calibration
temperature. Different grades are available to specify in the command.
• Operation principle: Bimetallic element deformation
• Protection degree: IP 55
• Working temperature:190 C° MAX
• Relative humidity: 98%
• Weight: 0,4 Kg
• Bimetallic component: Nilvar-Brass
• Regulation range: -40 + 190 C°
• Intervention threshold: On Request /mod SD Max 88 C°
• Alarm condition: Normally closed contact
• Contacts current carrying capacity: 2,5 A
• Working voltage: 48 Vdc
• Enclosure material: Aluminium alloy
• Dimensions: 92x167x67 mm
RTS/6 cod. SD3C00123
IP65 Special heat detector based on the deformation of a bimetallic element
which closes a dry contact as the temperature is reached. This makes the
detector easy to be interfaced with any board type.
• The heat detector is suitable for detection in environments where potentially
explosive atmospheres may be present. Its construction is complying with
sector specific regulations (ATEX).
• Code SD7E00123 is referred to a detector with a 60° C calibration
temperature. Different grades are available to specify in the command.
• Heat probe is UL/FM certified.
• Operation principle: Bimetallic element deformation
• Relative humidity: 98%
• Weight: 0,4 Kg
• Bimetallic component: Nilvar
• Regulation range: on order fixed calibration
• Alarm condition: Normally closed contact
• Contacts current carrying capacity: 2 A
• Working voltage: 24 Vdc
• Sensor material: steel
• Enclosure material: Aluminium alloy
• Dimensions: 100 x 193,5 x 70 mm
58
RTS/4
DETECTORS AND CONTROL UNITS
SPECIAL HEAT DETECTOR
Heat Detector
RLB/1 cod. SD6P00121
Linear heat detector, 68°C calibration (certified)
• Packaging: 100 m skein
RLB/2 cod. SD5P00121
Linear heat detector, 105°C calibration (certified)
• Packaging: 100 m skein
LINEAR DETECTORS
Smoke Linear Detector
S/2-100 + INT8C cod. IL1500123
Linear detector suitable for all environments characterised in high ceilings,
where using smoke optical detectors results to be particularly hard.
• The system includes three units: Transmitting unit (TX), Receiving unit (RX),
co-ordination unit (not including INT8C/24V interface module).
• The operation principle of linear detector is based on TX units to emit a
beam of infrared rays. The beam runs through the zone to be monitored
and radiates Receiving unit (RX). On running through monitored zone, the
beam collects information about possible fire arising and carries it to RX. RX
processes this information and draws from it a number of electrical signals,
each corresponding to a single fire sign examination. Successive processing
allows to diagnose the presence of smoke in monitored environment.
• On Transmitting unit there are present following leds: Power supply signalling
green led, Receiving unit status repetition yellow led.
• On Receiving unit there are present following leds: Power supply signalling
green led, Emitted and received IR intensity level yellow led, Fire alarm red
led.
• Linear detector is suitable for lengths of 5 m to 150 m.
• Maximum operative width: 15 m.
• High aligning facility.
• Brackets, for improved wall application, already included.
• Obligatory connection interface INT/8C (not included).
• Obligatory calibration instrument ADM (not included).
• Operation voltage: 24 Vdc
• Absorption in mA Tx:
5-15m
20,0
55-75m
24,0
15-35m 21,8
75-100m 38,6
35-55m 22,7
100-150m 65,5
• Absorption in mA Rx: Normal operation 47,7 - Fault 66,7 - Alarm 64,0.
• Operation temperature: da -20 a + 55 C°
• Operative homologation: EN 54/12
• Protection degree: IP 44
• Weight: Tx Unit 1,257 g, Rx Unit 1,447 g.
• Dimensions with bracket:
Tx
224 x 119 x 313 mm
Rx
224 x 119 x 313 mm
• Dimensions without bracket: Tx
220 x 119 x 148 mm.
Rx
220 x 119 x 148 mm
• Certificate EN54 part 12 Certificate N° 0786 - CPD - 20215.
S/2-100
59
DETECTORS AND CONTROL UNITS
LINEAR DETECTORS
Fire and smoke linear detectors
SF-100 + INT8C cod. IL1400123
Fire and smoke linear detector.
• The system includes three units: Transmitting unit (TX), Receiving unit (RX),
co-ordination unit (not including INT8C/24V interface module).
• The operation principle of linear detector is based on TX units to emit a
beam of infrared rays. The beam runs through the zone to be monitored
and radiates Receiving unit (RX). On running through monitored zone, the
beam collects information about possible fire arising and carries it to RX. RX
processes this information and draws from it a number of electrical signals,
each corresponding to a single fire sign examination.
• Successive processing allows to diagnose the presence of smoke in monitored
environment.
• On Transmitting unit there are present following leds: Power supply signalling
green led. Receiving unit status repetition yellow led
• On Receiving unit there are present following leds: Power supply signalling
green led. Emitted and received IR intensity level yellow led. Fire alarm red
led.
• Linear detector is suitable for lengths of 5 m to 150 m.
• Maximum operative width: 15 m.
• High aligning facility.
• Brackets, for improved wall application, already included.
• Obligatory connection interface INT/8C (not included).
• Obligatory calibration instrument ADM (not included).
• Operation voltage:
24 Vdc
• Absorption in mA Tx:
5-15m
20,0
15-35m
21,8
35-55m
22,7
55-75m
24,0
75-100m
38,6
100-150m
65,5
• Absorption in mA Rx: Normal operation 47,7 - Fault 66,7 - Alarm 64,0.
• Operation temperature: from -20 to + 55 C°
• Operative homologation: EN 54/12
• Protection degree: IP 44
• Weight: Tx Unit 1,257 g, Rx Unit 1,447 g.
• Dimensions with bracket:
Tx
224 x 119 x 313 mm
Rx
224 x 119 x 313 mm
• Dimensions without bracket: Tx
220 x 119 x 148 mm.
Rx
220 x 119 x 148 mm
• Certificate EN54 part 12 N° 0786 - CPD - 20215.
60
SF-100
DETECTORS AND CONTROL UNITS
LINEAR DETECTORS
Accessories
INT8C/24V cod. IL1010123
Interface module allowing the connection and operation of the Tx and Rx
units of smoke linear detector.
• The module has two relays inside it: one alarm relay and one failure relay
to be used for connecting the apparatus to conventional central units, or
analogue or digital input modules.
• Failure relay can be either normally energised (active safety) or normally not
energised.
• Facility for delaying the failure by 0 to 90 seconds through a second jumper.
• Operation principle: 24 Vdc
• Absorption with not energised out of order relay: Normal operation 16,4mA
@ 24 Vdc, Alarm: 22,4mA @ 24 Vdc, Failure: 22,2mA @ 24 Vdc
• Absorption with energised out of order relay: Normal operation 25,0mA @
24 Vdc, Alarm: 15,7mA @ 24 Vdc, Failure:
30,6mA @ 24 Vdc.
• Dimensions (hxlxp): 130 x 130 x 58 mm.
INT8C/24V
ADM cod. IL1110123
ADM instrument, associated to an analogue tester, was designed in order
to best perform the management functions of sensitivity thresholds required
by the nature of environmental disturbances present in environments to be
protected.
• The use of ADM instrument is necessary for models: ES 25-1; ES 50; ES
100; S/2-100 and SF-100.
• Operation voltage: 8-12 V
• Battery down indication: < 8 V
• Typical absorption : 2 mA
• Absorption: 1.6 – 2,2 mA max
• Operation time: 300 hours
• Dimensions: 60x36x18 mm
ADM
ECO series reflexion linear detector
ES50 cod. SD8P00123
Infrared ray linear smoke detector, for flush-mounting, working range: 50m
• Consisting of ECO transmitting and receiving units and reflector with
articulated joint
• EN 54 certified - part 12 N. 0786-CPD-20214
• Operating voltage: 12Vdc to 24Vdc
• Outputs: alarm relay 1A@30Vdc
• Optical failure relay 170mA@30Vcc
• Working temperature: - 20° + 50°C
• Protection: IP44
• Dimensions: 103 (H) x 103 (L) x 63 (D) mm
ES50
ES80 cod. SD9R00123
Same as ES50 but with 80 m range.
KATA cod. IL7500123
Reflexion unit
KATA
SSM cod. SP7600123
Pair of articulated joints for TX and reflector for the detectors of ECO
series.
61
DETECTORS AND CONTROL UNITS
ASPIRATING SYSTEMS
ASD cod. SC2R00123
Aspirating single-pipe sampling unit.
• For PVC/ABS ø 3/4” pipe, max pipe length: 100 m. Power supply: 24Vdc,
smoke detectors not included.
PICO cod. SC3R00123
Laser aspiration smoke detector, single-pipe.
• For PVC/ABS ø 3/4” pipe, max length: 100 m. Power supply: 24Vdc.
ASD
FIRE TRACER cod. SC4R00123
Fire Tracer with 4 aspirating pipes, 1 detection zone.
• For 4 aspirating pipes PVC/ABS ø 3/4” pipe sections, 50m each. Power
supply: 24Vdc, complete with diaphragm/ device control, event display.
PLEASE CONTACT THE SALE NETWORK FOR ACCESSORIES
FIRE TRACER
ACCESSORIES FOR DETECTORS CHECK
AST cod. AT7100123
Fibreglass telescopic extension pole 6 m max
DFS cod. RT7100123
Smoke detector tester.
• (DBS bottle required)
DBS cod. SD9H10123
DRS
Smoke detector test bottle.
DTS cod. RT7200123
Heat detector tester.
DRS cod. SD8H10123
Universal tool for removing and refitting any type of detectors
62
DFS
OPTICALACOUSTIC
INDICATORS
POWER SUPPLY
BATTERIES
PANELS..................................... pag. 64
OPTIC REPEATER.......................... pag. 66
BELLS........................................ pag. 67
SOUNDERS................................ pag. 68
ELECTROMAGNETS..................... pag. 68
EXPLOSION PROOF DEVICES...... pag. 69
POWER SUPPLY/BATTERIES ....... pag. 70
63
OPTICAL-ACOUSTIC INDICATORS
PANELS
Optical Acoustic Panels
TM24 cod. FH2600121
• Optical/acoustic signalling single face panel
• Power supply : 12 – 24 Vdc
• Max consumption: 100 mA
• Lighting by high efficiency leds
• Buzzer sound pressure: 85dB at 1m
• Steady/flashing light, selectable
• Continuous/intermittent sound, selectable
• Protection against polarity reverse
• Working temperature: -10°C ÷ + 50°C
• Material: self-extinguishing ABS, class V0
• Protection: IP 40
• The following pictographs are available as standard: Fire alarm, Withdraw
from premises, Extinguishing in progress, Gas alarm, Fire alarm.
TM24
TB24 cod. FH2700121
Optical/acoustic signalling double face panel
• Power supply : 12 – 24 Vdc
• Max consumption: 100 mA
• Lighting by high efficiency leds
• Buzzer sound pressure: 85dB at 1m
• Steady/flashing light, selectable
• Continuous/intermittent sound, selectable
• Protection against polarity reverse
• Working temperature: -10°C ÷ + 50°C
• Material: self-extinguishing ABS, class V0
• Protection: IP 40
• The following pictographs are available as standard: Fire alarm, Withdraw
from premises, Extinguishing in progress, Gas alarm, Fire alarm.
TB24
SPTB cod. SF5000121
Bracket for optical/acoustic signalling double face panel TB24
TM220 cod. FH2800121
230Vac self-powered optical/acoustic signalling single face panel
• Power supply : 230Vac
• Max consumption: 100 mA
• Lighting by high efficiency leds
• Buzzer sound pressure: 85dB at 1m
• Steady/flashing light, selectable
• Continuous/intermittent sound, selectable
• Protection against polarity reverse
• Buffer battery: 3.6 V 1.5Ah Ni-Cd
• Alarm endurance: 1 hour
• Working temperature: -10°C ÷ + 50°C
• Material: self-extinguishing ABS, class V0
• Protection: IP 40
• The following pictographs are available as standard: Fire alarm, Withdraw
from premises, Extinguishing in progress, Gas alarm, Fire alarm.
64
TM220
OPTICAL-ACOUSTIC INDICATORS
PANELS
Optical Acoustic Panels
TM224 cod. FH3100121
24Vdc self-powered optical/acoustic signalling double face panel
• Power supply : 24Vdc
• Max consumption: 100 mA
• Lighting by high efficiency leds
• Buzzer sound pressure:
85dB at 1m
• Steady/flashing light, selectable
• Continuous/intermittent sound, selectable
• Protection against polarity reverse
• Buffer battery: 3.6 V 1.5Ah Ni-Cd
• Alarm endurance: 1 hour
• Working temperature: -10°C ÷ + 50°C
• Material: self-extinguishing ABS, class V0
• Protection: IP 40
• The following pictographs are available as standard: Fire alarm, Withdraw
from premises, Extinguishing in progress, Gas alarm, Fire alarm.
TM224
TMSV cod. FH5400121
Single-face optical/sound plate with speech synthesizer
• Power supply: 24Vdc
• Absorption: 180 mA
• 8 pre-recorded messages
• 3 voice alarm zones
• free combination of pre-recorded messages
• 1 customized message
• 4 operating modes: SPEECH - SOUND - SOUND + SPEECH - SPEECH +
SOUND
• Dimensions (L) x (H) x (D) mm: 365 x 180 x 50
TMSV
65
OPTICAL-ACOUSTIC INDICATORS
VISUAL REPEATERS
Outdoor visual repeaters
LR500 cod. SR1100121
Outdoor visual repeater
• Visual repeater allowing to show the alarm status of a detector installed
in hidden spaces. Suitable for all ELKRON detectors with ZB204 base or
SD500R base.
• Power supply: 12 – 24Vdc
• Absorption: 11 mA
• Terminal connection
• Working temperature: -10°C ÷ + 55°C
• Weight: 30 g
• Protection: IP40
• Case material: ABS, class VO
• 2 high efficiency red leds
• Steady/flashing light, selectable
• Dimensions: 65.5 (L) x 60.6 (H) x 23.6 (D) mm
LR500
LR500SI cod. SR1200121
Outdoor visual repeater for FAP500 digital systems
• Visual repeater allowing to show the alarm status of a detector installed in
hidden spaces and to indicate detector regular operation (green led flashing).
Suitable for all ELKRON detectors with SD500R base. This repeater can only
be used with FAP500 detectors.
• Power supply: 12 – 24Vdc
• Absorption: 11 mA
• Terminal connection
• Working temperature: -10°C ÷ + 55°C
• Weight: 30 g
• Protection: IP40
• Case material: ABS, class VO
• 2 high efficiency white leds
• 1 high efficiency green led
• Steady/flashing light, selectable
• Dimensions: 65.5 (L) x 60.6 (H) x 23.6 (D) mm
66
LR500SI
OPTICAL-ACOUSTIC INDICATORS
ELECTRONIC BELLS
Bells
4476/24 cod. HS7300123
Bell with classic appearance for fire alarm systems and other warnings.
• The internal movement with motor, pinion and striker, jointly with the external
bell in steel produces a powerful sound with a low current consumption.
• Power supply:24 Vdc
• Average absorption: 25 mA
• Sound pressure at 1 metre distance: 93/95 dB
• Operation temperature: -10°C ÷ +50°C
• Protection degree: IP 42
4476/24
4460/24 cod. HS1700123
Electronic bell with sophisticated appearance and innovative technology fully
covered with polyurethane resin ensuring high protection and resistance
degree.
• Maximum control of sound signal through 28 tones that can be selected
during installation by 5 internal dip-switches and through volume control by
trimmer.
• Installation is made simple by siren bayonet joint on siren base and by double
pins allowing to shunt connections.
• Enclosure material: Thermoplastic body, red colour
• Power supply:24 Vdc
• Average absorption: 16 mA
• Sound pressure at 1 metre distance: 102 dB
• Operation temperature: -10°C ÷ +70°C
• Protection degree: IP 54
4460/24
4479/24 cod. HS7200123
Electronic bell with sophisticated appearance and innovative technology for
fire alarm systems and other warnings.
• Combining a miniaturised solenoid to a built-in control circuit, excellent
acoustic performance, minimum current consumption and high reliability are
allowed.
• Power supply doubled pins and cap latching make the bell particularly easy
to be installed.
• IP 55 protection degree allows bell outdoor use; however, the bell can also be
mounted in indoor environments.
• Power supply:24 Vdc
• Average absorption: 30 mA
• Operation temperature: -10°C ÷ +55°C
• Sound pressure at 1 metre distance: 93-95 dB
• Protection degree: IP 55
4479/24
3465/24 cod. HS1900123
Piezoelectric sounder for indoor with xenon lamp
• Power Supply: 24Vcc.
• Absorption: 170 mA.
• Sound pressure at 1 m: 110 dB.
• Colour: red.
3465/24
67
OPTICAL-ACOUSTIC INDICATORS
SOUNDERS
HP500F cod. HS5000121
Outdoor red self-powered siren made in die-cast aluminium.
Provided with signalling flash with incandescent lamp.
• Operation voltage: 24 Vdc
• Protection degree: IP 43
• Sound pressure: 104 dB (A) at 3 mt distance
• Operation temperature: -25° C / +55° C
• Assignable accumulator: 12 V 2,1 Ah
• Dimensions (hxlxd): 265x210x65 mm.
HP500F
DSE/626 cod. HS2100123
Red siren for premises evacuation in compliance with with regulation
626/94. Two-tone alarm, xenon visual signalling.
• Operation voltage: 230 Vac
• Protection degree: IP 44
• Sound pressure: 104 dB (A) at 3 mt distance
• Operation temperature: -25° C / +55° C
• Assignable accumulator: 12 V 2,1 Ah
• Dimensions (hxlxd): 265x210x65 mm
• Weight: 2,1 Kg.
DSE/626
ELECTROMAGNETS
Electromagnetic Stop
1370/15 cod. MM7100123
Electromagnetic stop implemented in order to keep open fire or transit doors and release them in case of fire.
• The magnet has two mounting positions on magnet body and, by bracket
provided (15 cm bracket), allows the stop to be installed both as a wall stop
and as a floor stop. Complete with unlocking pushbutton. It is available a
model with 30 cm bracket with code MM7300123.
• Hooking force: 50 kg, actual
• Working voltage: 24 Vdc
• Absorption: 65 mA
• Operation temperature: -10 °C to + 55 C°
• Weight: 1,2 Kg
1370/30 cod. MM7300123
Same as 1370/15 with 30cm bracket.
EM50P cod. MM7000123
Door holder electromagnet with release button. Power 24 Vdc. Holding
force 50 Kg.
EM100P cod. MM9000123
Door holder electromagnet with release button. Power 24 Vdc. Holding
force 100 Kg.
68
1370/15
EXPLOSION PROOF DEVICES
EXPLOSION PROOF
DEVICES
BUTTON
P/406 cod. SB3000121
Manual fire alarm pushbutton, with explosion-proof casing, for areas with
potentially explosive atmosphere.
• Emergency break glass hammer provided as standard. Pushbutton in diecast material, red epoxy paint.
• Holes for cables: 2x3/4 gas thread.
• Classification: II 2GD EEx d IIB T6, EEx d IIB+H2 T6.
• Certification: CESI 03 ATEX 050.
• Working temperature: –20°C/+50°C.
• Weight: 1.1 Kg.
P/406
OPTICAL-ACOUSTIC INDICATORS
T/800 cod. FH3500121
The optical/acoustic system includes the body of siren T/800S and the body
of visual repeater T/800L. These shells are made of a casting of cast iron
G-20 uni 5007. The two bodies are connected to each other.
• Working voltage: 27 Vdc
• Alarm absorption: 180 mA
• Weight: 3 kg
T/800
T/800S cod. HS1800121
Siren made of a casting of cast iron G-20 uni 5007 with a diffusing cone of
plastic material (ABS); inside the body there is placed an electronic circuit
for acoustic activation.
• Working voltage: 27 Vdc
• Alarm absorption: 180 mA
• Sound level: 60 db at 1 mt at 24 V
• Protection degree: IP 65
• Weight: 3 kg
T/800S
T/800L cod. SR0200121
Visual repeater made up of a shell made of a casting of cast iron G-20 uni
5007. The body of the visual repeater is provided with a gem on cover cap
of unbreakable (polycarbonate) material.
• Inside the body there are placed a bakelite lamp holder and a 30 Volt 5
Watt lamp; on the lamp holder there are arranged the pins for connecting
repeater activation system.
• Working voltage: 10,5 to 36 Vdc
• Alarm absorption: 200 mA
• Protection degree: IP 65
• Weight: 3 kg
T/800L
69
POWER SUPPLY UNITS AND BATTERIES
POWER SUPPLY UNITS
AND BATTERIES
POWER SUPPLY UNITS
82425 SBG cod. PS7900123
Power supplier with 27.6 V output voltage in switching version and current 2.5 A.
• High protection degree against overload, polarity inversions, short circuit.
Power supplier status is signalled by 4 external leds: network in (Green) led,
battery charger functionality (Green) led, battery down (Red) led, failure (Red)
led. Provided with key for opening and closing the front lid.
• Primary power supply:230 Vac
• Protection degree: IP 30
• Operation temperature: +5 °C to +40 °C
• EN 54-4 certified
82450 BG cod. PS8000123
Power supplier with 27.6 V output voltage in switching version and current 5 A
• High protection degree against overload, polarity inversions, short circuit.
Power supplier status is signalled by 4 external leds: network in (Green) led,
battery charger functionality (Green) led, battery down (Red) led, failure (Red)
led. Provided with key for opening and closing the front lid.
• Primary power supply:230 Vac
• Protection degree: IP 30
• Operation temperature: +5 °C to +40 °C
• EN 54-4 certified
BATTERIES
RB06 cod. RB0410113
12 V 7,2 Ah Water Proof rechargeable battery
RB12 cod. RB0210113
6 V 1,3 Ah Water Proof rechargeable battery.
RB 19 cod. RB0310113
12 V 2,2 Ah Water Proof rechargeable battery.
RB 15 cod. RB0810113
12 V 18 Ah Water Proof rechargeable battery.
RB 24 cod. RB0510113
12 V 26 Ah Water Proof rechargeable battery.
RB 612 cod. RB0910113
6 V 12 Ah Water Proof rechargeable battery.
RB 1212 cod. RB1110113
12 V 12 Ah Water Proof rechargeable battery.
70
71
72