Mitsubishi Electric | MUZ-FD35VA-E1 | Service manual | Mitsubishi Electric MUZ-FD35VA-E1 Service manual

Revision C:
• Errors in TROUBLESHOOTING have been
corrected.
Please void OBH489 REVISED EDITION-B.
SPLIT-TYPE AIR CONDITIONERS
OUTDOOR UNIT
SERVICE MANUAL
HFC
utilized
No. OBH489
REVISED EDITION-C
R410A
Models
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA -
E1
E1
,
E2
E1
E1
E1
Indoor unit service manual
MSZ-FD•VA Series (OBH488)
CONTENTS
MUZ-FD25/35
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 8
5. OUTLINES AND DIMENSIONS ························ 9
6. WIRING DIAGRAM·········································· 10
7. REFRIGERANT SYSTEM DIAGRAM ············· 13
8. PERFORMANCE CURVES ····························· 15
9. ACTUATOR CONTROL ··································· 29
10. SERVICE FUNCTIONS···································· 30
11. TROUBLESHOOTING ····································· 31
12. DISASSEMBLY INSTRUCTIONS ···················· 55
PARTS CATALOG (OBB489)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Use the specified refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Revision A:
• MUZ-FD25VAH- E2 has been added.
• Power outlet has been corrected.
Revision B:
• MUZ-FD50VA-
E1
has been added.
Revision J:
• Errors in TROUBLESHOOTING have been corrected.
2
1
TECHNICAL CHANGES
MUZ-FD25VA - E1
MUZ-FD25VAH - E1
MUZ-FD35VA - E1
MUZ-FD35VAH - E1
MUZ-FD50VA - E1
1. New model
MUZ-FD25VAH - E1 → MUZ-FD25VAH - E2
1. Power outlet
E1 :
12 A,
E2 :
10 A
3
2
PART NAMES AND FUNCTIONS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
MUZ-FD50VA
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
ACCESSORIES
Drain socket
Drain cap
MUZ-FD25/35VA
1
-
MUZ-FD50VA
1
2
4
3
SPECIFICATION
Outdoor model
MUZ-FD25VA
Power supply
Cooling
Capacity
Rated frequency (Min.-Max.)
Heating
kW
Electrical data
Breaker Capacity
Power input 1 (Total)
Running current 1 (Total)
Power factor 1 (Total)
Starting current 1 (Total)
Coefficient of performance
(COP) 1 (Total)
Model
Output
Compressor
Current 1
A
Cooling
Heating
Cooling
Heating
Cooling
Heating
A
%
A
Cooling
Heating
Cooling
Heating
Refrigeration oil (Model)
Model
Cooling
Fan motor
Current 1
Heating
Dimensions W × H × D
Weight
Dehumidification
Cooling
High
Cooling
Low
High
Air flow 1
Heating
Med.
Low
Cooling
Sound level 1
Heating
High
Cooling
Low
Fan speed
High
Heating
Med.
Low
Fan speed regulator
Refrigerant filling capacity (R410A)
Special remarks
W
W
A
L
A
mm
kg
/h
m3/h
dB(A)
rpm
kg
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor
Dry-bulb temperature 27°C
Outdoor Dry-bulb temperature 35°C
Heating: Indoor
Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
Single phase, 230 V, 50 Hz
2.5 (1.1-3.5)
3.5 (1.1-4.0)
3.5 (0.8-4.0)
3.2 (1.5-5.5)
3.2 (1.5-6.3)
4.0 (1.5-6.3)
4.0 (1.3-7.7)
E1 : 12
10
10
12
E2 : 10
485
850
835
610
865
850
2.4
3.9
3.8
2.9
4.0
3.9
88
95
96
91
94
95
2.9
4.0
3.9
5.15
4.12
4.19
5.25
4.62
4.71
SNB130FGBH
900
1.88
3.31
3.21
2.30
3.33
3.23
0.45 (NEO22)
RC0J50-EA
0.27
0.32
0.30
0.35
800 × 550 × 285
36
1.4
2.0
1,872
1,086
2,016
1,776
1,386
47
46
50
810
490
870
770
610
3
1.15
Wet-bulb temperature
19°C
Wet-bulb temperature
6°C
5
MUZ-FD50VA
Power supply
Cooling
Capacity
kW
Rated frequency (Min.-Max.)
Heating
Breaker Capacity
A
Cooling
Power input 1 (Total)
W
Heating
Cooling
Running current 1 (Total)
A
Heating
Cooling
%
Power factor 1 (Total)
Heating
Starting current 1 (Total)
A
Cooling
Coefficient of performance
(COP) 1 (Total)
Heating
Model
Output
W
Compressor
Cooling
Current 1
A
Heating
Refrigeration oil (Model)
L
Model
Cooling
Fan motor
A
Current 1
Heating
Dimensions W × H × D
mm
Weight
kg
Dehumidification
Cooling
/h
High
Cooling
Med.
Low
m3/h
Air flow 1
High
Heating
Med.
Low
Cooling
Sound level 1
dB(A)
Heating
High
Cooling
Med.
Low
Fan speed
rpm
High
Heating
Med.
Low
Fan speed regulator
Refrigerant filling capacity (R410A)
kg
Single phase, 230 V, 50 Hz
5.0 (1.5-5.8)
5.8 (1.5-7.8)
16
1,500
1,550
6.7
6.9
98
98
6.9
3.33
3.74
SNB172FDGH
1,200
5.40
5.62
0.45 (NEO22)
RC0J60-AA
Electrical data
Outdoor model
0.72
Special remarks
840 × 850 × 330
55
1.7
–
2,940
1,680
2,940
2,940
2,100
54
56
–
800
480
800
800
580
2
1.55
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor
Dry-bulb temperature 27°C
Outdoor Dry-bulb temperature 35°C
Heating: Indoor
Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
Wet-bulb temperature
19°C
Wet-bulb temperature
6°C
6
Specifications and rated conditions of main electric parts
Item
Current transformer
Smoothing capacitor
Diode module
Fuse
Defrost heater
Intelligent power module
Expansion valve coil
Reactor
Current-detecting resistor
Current-limiting PTC thermistor
Terminal block
Relay
R.V.coil
Heater protector
IGBT
Model
(CT)
(CT761, CT781)
(C61, C62, C63)
(DB61)
(DB65)
(F61)
(F701, F801, F901)
(H)
(IPM)
(LEV)
(L61)
(R61, R62)
(R825)
(R937, R938, R939)
(PTC64, PTC65)
(TB1, TB2)
(X63)
(X64)
(X66)
(21S4)
(26H)
(TR821)
MUZ-FD25VA
—
—
—
Model
MUZ-FD25VAH
MUZ-FD35VA
20 A
15 A
620 μF 420 V
15 A 600 V
25 A 600 V
T20AL250V
T3.15AL250V
230 V 130 W
—
20 A 600 V
DC 12 V
23.0 mH
180 mΩ 5 W (2 elements)
25 mΩ 5 W
430 mΩ 2 W
33 Ω
3P
3 A 250 V
20 A 250 V
3 A 250 V
—
AC 220 - 240 V
Open 45°C
—
30 A 600 V
MUZ-FD50VA
Item
(CT1, CT2)
(CT61)
Smoothing capacitor
(CB1, CB2, CB3)
(F64)
Fuse
(F801)
Expansion valve coil
(LEV)
(IPM)
Intelligent power module
(HC930)
High pressure switch
(HPS)
Reactor
(L)
Power factor correct module
(PFC)
Current-limiting PTC thermistor
(PTC64, PTC65)
(R937A, R937B)
Current-detecting resistor
(RS1, RS2, RS3, RS4)
Solenoid coil relay
(SSR61)
Terminal block
(TB1, TB2)
Relay
(X64)
R.V. coil
(21S4)
20 A
20 A
560 μF 450 V
T2.0AL250V
T3.15AL250V
DC 12 V
15 A 600 V
3 A 600 V
ACB-DB156
600 μH 20 A
20 A 600 V
33 Ω
1.1 Ω 2 W
40 mΩ 7 W (2 elements)
0.5 A 600 V
3P
20 A 250 V
AC 220 - 240 V
Current transformer
7
MUZ-FD35VAH
230 V 130 W
3 A 250 V
Open 45°C
4
NOISE CRITERIA CURVES
MUZ-FD35VA MUZ-FD35VAH
MUZ-FD25VA MUZ-FD25VAH
SPL(dB(A))
FUNCTION
COOLING
46
HEATING
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
NC-10
10
FUNCTION
SPL(dB(A))
COOLING
47
HEATING
50
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
63
125
250
500
1000
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
FUNCTION
SPL(dB(A))
COOLING
54
HEATING
56
LINE
1m
MICROPHONE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
NC-10
125
2000
4000
8000
Test conditions
Cooling : Dry-bulb temperature 35 °C
Heating : Dry-bulb temperature 7 °C Wet-bulb temperature
OUTDOOR UNIT
63
NC-20
NC-10
BAND CENTER FREQUENCIES, Hz
MUZ-FD50VA
10
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
LINE
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
8
6 °C
5
OUTLINES AND DIMENSIONS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Unit: mm
REQUIRED SPACE
Drain hole ø42 (25/35VA)
Drain hole ø33 (25/35VAH)
100
re
r mo
mo
m
0
10
mm
or m
Bolt pitch for
installation
304-325
ore
44
Air in
Open two sides of left,
right, or rear side.
17.5
40
2 holes 10 × 21
Air out
22.3
350
mm
or m
ore
re
r mo
mo
m
200
Service panel
23
Liquid refrigerant pipe joint
Refrigerant pipe (flared) ø6.35
150
69
Gas refrigerant pipe joint
Refrigerant pipe (flared) ø9.52
99.5
10
164.5
280
35°
550
Handle
43°
285
344.5
400
Air in
Basically open 100 mm or more
without any obstruction in front
and on both sides of the unit.
302.5
170.5
Service port
500 Bolt pitch for installation
800
MUZ-FD50VA
Open as a rule
500 mm or more if
the front and both
sides are open
REQUIRED SPACE
515
299
66
Drain holes ø33
Air in
40
51
34
Air in
360
330
100 mm or more
200 mm or more if
there are obstacles
to both sides
100
mm
or m
ore
170
Air out 500
840
121
4 holes 10 × 21
80
350
Open as a rule
500 mm or more if the back,
both sides and top are open
mm
or m
ore
Service panel
850
Liquid refrigerant
pipe joint
Refrigerant pipe
155
90
35°
30°
430
(flared) ø6.35
Gas refrigerant
pipe joint
Refrigerant pipe
198
9
(flared) ø12.7
6
WIRING DIAGRAM
MUZ-FD25VA MUZ-FD35VA
10
MUZ-FD25VAH
MUZ-FD35VAH
11
MUZ-FD50VA
12
7
REFRIGERANT SYSTEM DIAGRAM
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Refrigerant pipe ø9.52
(with heat insulator)
Unit: mm
4-way valve
Muffler
Stop valve
(with service port)
Discharge
temperature
thermistor
RT62
Flared connection
Outdoor
heat
exchanger
Muffler
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Compressor
Defrost
thermistor
RT61
Capillary tube
ø3.0×ø1.8×600(×2)
Flared connection
Refrigerant pipe ø6.35
(with heat insulator)
Strainer
#100
Capillary tube
ø3.0×ø2.0×240
LEV
R.V. coil
heating ON
cooling OFF
Stop valve
(with strainar)
Refrigerant flow in cooling
Refrigerant flow in heating
MUZ-FD50VA
Refrigerant pipe ø12.7
(with heat insulator)
Muffler
4-way valve #100
Stop valve
(with service port)
Flared connection
Discharge
temperature
thermistor
RT62
High-pressure
switch
Defrost
thermistor
RT61
Outdoor
heat
exchanger
Ambient
temperature
thermistor
RT65
Compressor
Outdoor heat
exchanger
temperature
thermistor
RT68
Flared connection
LEV
Strainer
Receiver #100
Stop valve
Refrigerant pipe ø6.35
(with heat insulator)
Capillary tube
ø3.6×ø2.4×50
13
Strainer
#100
R.V. coil
heating ON
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length
A
Max. Height difference
B
Gas
MUZ-FD25
MUZ-FD35
20
12
9.52
MUZ-FD50
30
15
12.7
Liquid
6.35
Indoor
unit
Max. Height
difference
B
Max. Length
A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
5m
6m
7m
1,150
0
0
0
MUZ-FD25
MUZ-FD35
Refrigerant piping length (one way)
8m
9 m 10 m 11 m 12 m 13 m
14 m
15 m
20 m
90
270
300
450
120
150
180
210
240
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 5)
Refrigerant piping length (one way)
Model
Outdoor unit
precharged
7m
10 m
15 m
20 m
25 m
30 m
MUZ-FD50
1,550
0
90
240
390
540
690
Calculation: X g = 30 g/m × (Refrigerant piping length (m) – 7)
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
14
8
PERFORMANCE CURVES
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been provided to clarify the
operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature:
°C [WB]
(2) Indoor outlet air wet-bulb temperature:
°C [WB]
Cooling
(3) Outdoor intake air dry-bulb temperature:
°C [DB]
(4) Total input:
W
(5) Indoor intake air dry-bulb temperature:
°C [DB]
(6) Outdoor intake air wet-bulb temperature:
°C [WB]
Heating
(7) Total input:
W
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at
service.
}
}
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
Wet and dry bulb
thermometers
FRONT VIEW
Wet and dry bulb
thermometers
BACK VIEW
8-1. CAPACITY AND INPUT CURVES
9.3
5.5
7.7
8.5
5.1
7.0
7.7
4.6
6.3
7.0
4.1
5.7
6.3
3.7
5.1
5.6
1.5
Capacity correction factors
8.4
Indoor intake air Wet-bulb
temperature( )
1.4
1.3
1.2
26
1.1
24
1.0
22
20
18
0.9
-10
MUZ-FD50VA
MUZ-FD35VA
6.0
MUZ-FD35VAH
10.1
MUZ-FD25VA
9.1
MUZ-FD25VAH
Indoor air Wet-bulb temperature
difference (°C)
Cooling capacity (at Rated frequency)
6.5
-5
0
5
10
15
20
25
30
Outdoor intake air Dry-bulb temperature(°C)
15
35
40
45
7.0
7.7
4.6
6.3
7.0
4.1
5.7
6.3
3.7
5.1
5.6
3.3
4.5
4.9
1.3
Input correction factors
5.1
1.2
22
20
18
24
26
1.1
1.0
0.9
Indoor intake air Wet-bulb
temperature(°C)
0.8
-10
MUZ-FD50VA
MUZ-FD35VAH
MUZ-FD35VA
8.5
MUZ-FD25VAH
7.7
MUZ-FD25VA
Indoor air Wet-bulb temperature
difference (°C)
Total input (Cooling : at Rated frequency)
5.5
-5
0
5
10
15
20
25
30
35
40
45
Outdoor intake air Dry-bulb temperature (°C)
19.3
23.7
1.2
14.6
17.7
21.7
13.3
16.1
19.7
12.0
14.5
17.7
10.6
12.9
15.8
9.3
11.3
13.8
8.0
9.7
11.8
6.7
8.0
9.9
5.3
6.4
7.9
Capacity correction factor
16.0
ure
rat
1.1
1.0
0.8
In
0.7
o
do
r in
e
tak
D
air
lb
bu
ry-
0.9
pe
tem
(
)
15
20
26
0.6
0.5
0.4
-20
MUZ-FD50VA
MUZ-FD35VAH
1.3
MUZ-FD35VA
25.6
MUZ-FD25VAH
20.9
MUZ-FD25VA
Indoor air Dry-bulb temperature
difference (°C)
Heating capacity (at Rated frequency)
17.3
-15
-10
-5
0
5
10
Outdoor intake air Wet-bulb temperature (°C)
15
19.3
23.7
1.2
14.6
17.7
21.7
13.3
16.1
19.7
12.0
14.5
17.7
10.6
12.9
15.8
9.3
11.3
13.8
8.0
9.7
11.8
6.7
8.0
9.9
5.3
6.4
7.9
Input correction factor
16.0
1.1
1.0
0.9
0.8
Indo
air
take
or in
bu
Dry-
C
re (°
ratu
mpe
lb te
)
26
20
15
0.7
0.6
0.5
0.4
-20
MUZ-FD50VA
MUZ-FD35VAH
1.3
MUZ-FD35VA
25.6
MUZ-FD25VAH
20.9
MUZ-FD25VA
Indoor air Dry-bulb temperature
difference (°C)
Total input (Heating : at Rated frequency)
17.3
-15
-10
-5
0
5
10
Outdoor intake air Wet-bulb temperature (°C)
15
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
16
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
MUZ-FD25VA MUZ-FD25VAH
1.5
1.0
0.5
4
Input correction factors
0.5
Capacity correction factors
1.0
2.0
Correction of Heating input
Correction of Heating capacity
2.0
2.5
Input correction factors
Capacity correction factors
Correction of Cooling input
Correction of Cooling capacity
1.5
1.5
1.0
0.5
0.0
0.0
0.0
0
50
100
150(Hz)
0
50
100
150(Hz)
0
50
100
150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
3
2
1
0
0
50
100
150(Hz)
The operational frequency of compressor
MUZ-FD35VA
Correction of Cooling input
1.0
1.0
0.5
0.5
0.0
0
50
100
150(Hz)
0.0
0
50
100
Correction of Heating capacity
2.0
1.5
1.0
0.5
0.0
0
150(Hz)
3
Capacity correction factors
1.5
Input correction factors
Capacity correction factors
1.5
Capacity correction factors
Correction of Cooling capacity
50
100
2
1
0
0
150(Hz)
Correction of Heating input
50
100
150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
MUZ-FD35VAH
Correction of Cooling input
1.0
1.0
0.5
0.5
0.0
0
50
100
150(Hz)
0.0
0
50
100
Correction of Heating capacity
2.0
150(Hz)
3
Capacity correction factors
1.5
Input correction factors
Capacity correction factors
1.5
Capacity correction factors
Correction of Cooling capacity
1.5
1.0
0.5
0.0
0
50
100
150(Hz)
Correction of Heating input
2
1
0
0
50
100
150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor
MUZ-FD50VA
0
50
100
The operational frequency of
compressor (Hz)
1.5
1.5
1.0
0.5
0.0
0
50
100
The operational frequency of
compressor (Hz)
17
Correction of Heating capacity
1.0
0.5
0.0
0
2.0
Capacity correction factors
0.5
Correction of Cooling input
Capacity correction factors
1.0
0.0
2.0
Input correction factors
Capacity correction factors
1.5
Correction of Cooling capacity
50
100
150
The operational frequency of
compressor (Hz)
Correction of Heating input
1.5
1.0
0.5
0.0
0
50
100
150
The operational frequency of
compressor (Hz)
8-3. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
Dry-bulb temperature (°C)
20
25
30
Relative humidity (%)
50
60
70
1.0
10
0.8
8
0.6
0.4
15
1.2
12
1.0
10
0.8
8
6
0.6
4
0.4
1.4
14
1.2
12
1.0
10
0.8
8
0.6
6
0.4
4
0.2
15
0.2
20
25
30
35
50
60
70
Ambient temperature(°C)
Ambient humidity(%)
MUZ-FD50VA
MPa [Gauge]
14
15
MUZ-FD35VAH
1.4
14
1.2
12
1.0
10
0.8
8
6
0.6
6
4
0.4
4
20
25
30
35
50
60
70
Ambient temperature(°C)
Ambient humidity(%)
MPa [Gauge]
12
0.2
1.4
kgf/cm2 [Gauge]
1.2
MUZ-FD35VA
MPa [Gauge]
14
kgf/cm2 [Gauge]
1.4
0.2
15
20
25
30
35
50
60
70
Ambient temperature(°C)
Ambient humidity(%)
kgf/cm2 [Gauge]
MPa [Gauge]
MUZ-FD25VA MUZ-FD25VAH
20
25
30
35
50
60
70
Ambient temperature(°C)
Ambient humidity(%)
NOTE:
The unit of pressure has been changed to MPa on the international system of units (SI unit system)
The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm2 [Gauge])
18
kgf/cm2 [Gauge]
Outdoor low pressure
Outdoor unit current
MUZ-FD25VA MUZ-FD25VAH
MUZ-FD35VAH
MUZ-FD35VA
(A) 2.4
(A) 4.0
(A) 4.0
2.2
3.5
3.5
2.0
3.0
3.0
1.8
15
2.5
15
30
35(°C)
20
25
70
(%)
50
60
Ambient temperature(°C)
Ambient humidity(%)
30
35(°C)
20
25
70
(%)
50
60
Ambient temperature(°C)
Ambient humidity(%)
2.5
15
30
35(°C)
20
25
70
(%)
50
60
Ambient temperature(°C)
Ambient humidity(%)
MUZ-FD50VA
(A) 6.5
6.0
5.5
5.0
4.5
15
20
50
25
60
30
70
35
Ambient temperature (°C)
Ambient humidity (%)
HEAT operation
Condition:
Dry bulb temperature (°C)
Wet bulb temperature (°C)
Indoor
20.0
14.5
2
1
Outdoor
7
15
6
12
20.0
14.5
Operation: Test run operation (Refer to 8-3.)
Outdoor unit current
MUZ-FD25VA MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
(A) 6.0
(A) 6.0
(A) 6.0
5.5
5.5
5.5
5.0
5.0
5.0
4.5
4.5
4.5
4.0
0 2 5
10
15
20
Ambient temperature(°C)
25
4.0
10
15
20
0 2 5
Ambient temperature(°C)
MUZ-FD50VA
(A) 8.5
8.0
7.5
7.0
6.5
6.0
0 2 5
10
15
20
25
Ambient temperature (°C)
19
25
4.0
10
15
20
0 2 5
Ambient temperature(°C)
25
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD25VA MUZ-FD25VAH
CAPACITY: 2.5 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.85
INPUT: 485 W
OUTDOOR DB (°C)
21
25
27
30
SHF
INPUT
21
18
2.94
1.97
0.67
388
2.81
1.88
0.67
407
2.70
1.81
0.67
427
2.60
1.74
0.67
446
21
20
3.06
1.68
0.55
407
2.94
1.62
0.55
432
2.85
1.57
0.55
441
2.75
1.51
0.55
461
22
18
2.94
2.09
0.71
388
2.81
2.00
0.71
407
2.70
1.92
0.71
427
2.60
1.85
0.71
446
22
20
3.06
1.81
0.59
407
2.94
1.73
0.59
432
2.85
1.68
0.59
441
2.75
1.62
0.59
461
22
22
3.19
1.50
0.47
422
3.08
1.45
0.47
449
3.00
1.41
0.47
461
2.88
1.35
0.47
480
23
18
2.94
2.20
0.75
388
2.81
2.11
0.75
407
2.70
2.03
0.75
427
2.60
1.95
0.75
446
23
20
3.06
1.93
0.63
407
2.94
1.85
0.63
432
2.85
1.80
0.63
441
2.75
1.73
0.63
461
23
22
3.19
1.63
0.51
422
3.08
1.57
0.51
449
3.00
1.53
0.51
461
2.88
1.47
0.51
480
24
18
2.94
2.32
0.79
388
2.81
2.22
0.79
407
2.70
2.13
0.79
427
2.60
2.05
0.79
446
24
20
3.06
2.05
0.67
407
2.94
1.97
0.67
432
2.85
1.91
0.67
441
2.75
1.84
0.67
461
24
22
3.19
1.75
0.55
422
3.08
1.69
0.55
449
3.00
1.65
0.55
461
2.88
1.58
0.55
480
24
24
3.35
1.44
0.43
441
3.23
1.39
0.43
466
3.15
1.35
0.43
480
3.05
1.31
0.43
504
25
18
2.94
2.44
0.83
388
2.81
2.33
0.83
407
2.70
2.24
0.83
427
2.60
2.16
0.83
446
25
20
3.06
2.17
0.71
407
2.94
2.09
0.71
432
2.85
2.02
0.71
441
2.75
1.95
0.71
461
25
22
3.19
1.88
0.59
422
3.08
1.81
0.59
449
3.00
1.77
0.59
461
2.88
1.70
0.59
480
25
24
3.35
1.57
0.47
441
3.23
1.52
0.47
466
3.15
1.48
0.47
480
3.05
1.43
0.47
504
26
18
2.94
2.56
0.87
388
2.81
2.45
0.87
407
2.70
2.35
0.87
427
2.60
2.26
0.87
446
26
20
3.06
2.30
0.75
407
2.94
2.20
0.75
432
2.85
2.14
0.75
441
2.75
2.06
0.75
461
26
22
3.19
2.01
0.63
422
3.08
1.94
0.63
449
3.00
1.89
0.63
461
2.88
1.81
0.63
480
26
24
3.35
1.71
0.51
441
3.23
1.64
0.51
466
3.15
1.61
0.51
480
3.05
1.56
0.51
504
26
26
3.45
1.35
0.39
466
3.35
1.31
0.39
490
3.30
1.29
0.39
504
3.20
1.25
0.39
519
27
18
2.94
2.67
0.91
388
2.81
2.56
0.91
407
2.70
2.46
0.91
427
2.60
2.37
0.91
446
27
20
3.06
2.42
0.79
407
2.94
2.32
0.79
432
2.85
2.25
0.79
441
2.75
2.17
0.79
461
27
22
3.19
2.14
0.67
422
3.08
2.06
0.67
449
3.00
2.01
0.67
461
2.88
1.93
0.67
480
27
24
3.35
1.84
0.55
441
3.23
1.77
0.55
466
3.15
1.73
0.55
480
3.05
1.68
0.55
504
27
26
3.45
1.48
0.43
466
3.35
1.44
0.43
490
3.30
1.42
0.43
504
3.20
1.38
0.43
519
28
18
2.94
2.79
0.95
388
2.81
2.67
0.95
407
2.70
2.57
0.95
427
2.60
2.47
0.95
446
28
20
3.06
2.54
0.83
407
2.94
2.44
0.83
432
2.85
2.37
0.83
441
2.75
2.28
0.83
461
28
22
3.19
2.26
0.71
422
3.08
2.18
0.71
449
3.00
2.13
0.71
461
2.88
2.04
0.71
480
28
24
3.35
1.98
0.59
441
3.23
1.90
0.59
466
3.15
1.86
0.59
480
3.05
1.80
0.59
504
28
26
3.45
1.62
0.47
466
3.35
1.57
0.47
490
3.30
1.55
0.47
504
3.20
1.50
0.47
519
29
18
2.94
2.91
0.99
388
2.81
2.78
0.99
407
2.70
2.67
0.99
427
2.60
2.57
0.99
446
29
20
3.06
2.66
0.87
407
2.94
2.56
0.87
432
2.85
2.48
0.87
441
2.75
2.39
0.87
461
29
22
3.19
2.39
0.75
422
3.08
2.31
0.75
449
3.00
2.25
0.75
461
2.88
2.16
0.75
480
29
24
3.35
2.11
0.63
441
3.23
2.03
0.63
466
3.15
1.98
0.63
480
3.05
1.92
0.63
504
29
26
3.45
1.76
0.51
466
3.35
1.71
0.51
490
3.30
1.68
0.51
504
3.20
1.63
0.51
519
30
18
2.94
2.94
1.00
388
2.81
2.81
1.00
407
2.70
2.70
1.00
427
2.60
2.60
1.00
446
30
20
3.06
2.79
0.91
407
2.94
2.67
0.91
432
2.85
2.59
0.91
441
2.75
2.50
0.91
461
30
22
3.19
2.52
0.79
422
3.08
2.43
0.79
449
3.00
2.37
0.79
461
2.88
2.27
0.79
480
30
24
3.35
2.24
0.67
441
3.23
2.16
0.67
466
3.15
2.11
0.67
480
3.05
2.04
0.67
504
30
26
3.45
1.90
0.55
466
3.35
1.84
0.55
490
3.30
1.82
0.55
504
3.20
1.76
0.55
519
31
18
2.94
2.94
1.00
388
2.81
2.81
1.00
407
2.70
2.70
1.00
427
2.60
2.60
1.00
446
31
20
3.06
2.91
0.95
407
2.94
2.79
0.95
432
2.85
2.71
0.95
441
2.75
2.61
0.95
461
31
22
3.19
2.65
0.83
422
3.08
2.55
0.83
449
3.00
2.49
0.83
461
2.88
2.39
0.83
480
31
24
3.35
2.38
0.71
441
3.23
2.29
0.71
466
3.15
2.24
0.71
480
3.05
2.17
0.71
504
31
26
3.45
2.04
0.59
466
3.35
1.98
0.59
490
3.30
1.95
0.59
504
3.20
1.89
0.59
519
32
18
2.94
2.94
1.00
388
2.81
2.81
1.00
407
2.70
2.70
1.00
427
2.60
2.60
1.00
446
32
20
3.06
3.03
0.99
407
2.94
2.91
0.99
432
2.85
2.82
0.99
441
2.75
2.72
0.99
461
32
22
3.19
2.77
0.87
422
3.08
2.68
0.87
449
3.00
2.61
0.87
461
2.88
2.50
0.87
480
32
24
3.35
2.51
0.75
441
3.23
2.42
0.75
466
3.15
2.36
0.75
480
3.05
2.29
0.75
504
32
26
3.45
2.17
0.63
466
3.35
2.11
0.63
490
3.30
2.08
0.63
504
3.20
2.02
0.63
519
NOTE
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
20
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD25VA MUZ-FD25VAH
CAPACITY: 2.5 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.85
INPUT: 485 W
OUTDOOR DB (°C)
35
40
46
SHF
INPUT
21
18
2.45
1.64
0.67
475
2.25
1.51
0.67
504
2.08
1.39
0.67
524
21
20
2.58
1.42
0.55
495
2.40
1.32
0.55
519
2.23
1.22
0.55
548
22
18
2.45
1.74
0.71
475
2.25
1.60
0.71
504
2.08
1.47
0.71
524
22
20
2.58
1.52
0.59
495
2.40
1.42
0.59
519
2.23
1.31
0.59
548
22
22
2.73
1.28
0.47
514
2.55
1.20
0.47
543
2.38
1.12
0.47
563
23
18
2.45
1.84
0.75
475
2.25
1.69
0.75
504
2.08
1.56
0.75
524
23
20
2.58
1.62
0.63
495
2.40
1.51
0.63
519
2.23
1.40
0.63
548
23
22
2.73
1.39
0.51
514
2.55
1.30
0.51
543
2.38
1.21
0.51
563
24
18
2.45
1.94
0.79
475
2.25
1.78
0.79
504
2.08
1.64
0.79
524
24
20
2.58
1.73
0.67
495
2.40
1.61
0.67
519
2.23
1.49
0.67
548
24
22
2.73
1.50
0.55
514
2.55
1.40
0.55
543
2.38
1.31
0.55
563
24
24
2.88
1.24
0.43
534
2.70
1.16
0.43
558
2.55
1.10
0.43
582
25
18
2.45
2.03
0.83
475
2.25
1.87
0.83
504
2.08
1.72
0.83
524
25
20
2.58
1.83
0.71
495
2.40
1.70
0.71
519
2.23
1.58
0.71
548
25
22
2.73
1.61
0.59
514
2.55
1.50
0.59
543
2.38
1.40
0.59
563
25
24
2.88
1.35
0.47
534
2.70
1.27
0.47
558
2.55
1.20
0.47
582
26
18
2.45
2.13
0.87
475
2.25
1.96
0.87
504
2.08
1.81
0.87
524
26
20
2.58
1.93
0.75
495
2.40
1.80
0.75
519
2.23
1.67
0.75
548
26
22
2.73
1.72
0.63
514
2.55
1.61
0.63
543
2.38
1.50
0.63
563
26
24
2.88
1.47
0.51
534
2.70
1.38
0.51
558
2.55
1.30
0.51
582
26
26
3.03
1.18
0.39
553
2.85
1.11
0.39
577
2.68
1.04
0.39
601
27
18
2.45
2.23
0.91
475
2.25
2.05
0.91
504
2.08
1.89
0.91
524
27
20
2.58
2.03
0.79
495
2.40
1.90
0.79
519
2.23
1.76
0.79
548
27
22
2.73
1.83
0.67
514
2.55
1.71
0.67
543
2.38
1.59
0.67
563
27
24
2.88
1.58
0.55
534
2.70
1.49
0.55
558
2.55
1.40
0.55
582
27
26
3.03
1.30
0.43
553
2.85
1.23
0.43
577
2.68
1.15
0.43
601
28
18
2.45
2.33
0.95
475
2.25
2.14
0.95
504
2.08
1.97
0.95
524
28
20
2.58
2.14
0.83
495
2.40
1.99
0.83
519
2.23
1.85
0.83
548
28
22
2.73
1.93
0.71
514
2.55
1.81
0.71
543
2.38
1.69
0.71
563
28
24
2.88
1.70
0.59
534
2.70
1.59
0.59
558
2.55
1.50
0.59
582
28
26
3.03
1.42
0.47
553
2.85
1.34
0.47
577
2.68
1.26
0.47
601
29
18
2.45
2.43
0.99
475
2.25
2.23
0.99
504
2.08
2.05
0.99
524
29
20
2.58
2.24
0.87
495
2.40
2.09
0.87
519
2.23
1.94
0.87
548
29
22
2.73
2.04
0.75
514
2.55
1.91
0.75
543
2.38
1.78
0.75
563
29
24
2.88
1.81
0.63
534
2.70
1.70
0.63
558
2.55
1.61
0.63
582
29
26
3.03
1.54
0.51
553
2.85
1.45
0.51
577
2.68
1.36
0.51
601
30
18
2.45
2.45
1.00
475
2.25
2.25
1.00
504
2.08
2.08
1.00
524
30
20
2.58
2.34
0.91
495
2.40
2.18
0.91
519
2.23
2.02
0.91
548
30
22
2.73
2.15
0.79
514
2.55
2.01
0.79
543
2.38
1.88
0.79
563
30
24
2.88
1.93
0.67
534
2.70
1.81
0.67
558
2.55
1.71
0.67
582
30
26
3.03
1.66
0.55
553
2.85
1.57
0.55
577
2.68
1.47
0.55
601
31
18
2.45
2.45
1.00
475
2.25
2.25
1.00
504
2.08
2.08
1.00
524
31
20
2.58
2.45
0.95
495
2.40
2.28
0.95
519
2.23
2.11
0.95
548
31
22
2.73
2.26
0.83
514
2.55
2.12
0.83
543
2.38
1.97
0.83
563
31
24
2.88
2.04
0.71
534
2.70
1.92
0.71
558
2.55
1.81
0.71
582
31
26
3.03
1.78
0.59
553
2.85
1.68
0.59
577
2.68
1.58
0.59
601
32
18
2.45
2.45
1.00
475
2.25
2.25
1.00
504
2.08
2.08
1.00
524
32
20
2.58
2.55
0.99
495
2.40
2.38
0.99
519
2.23
2.20
0.99
548
32
22
2.73
2.37
0.87
514
2.55
2.22
0.87
543
2.38
2.07
0.87
563
32
24
2.88
2.16
0.75
534
2.70
2.03
0.75
558
2.55
1.91
0.75
582
32
26
3.03
1.91
0.63
553
2.85
1.80
0.63
577
2.68
1.69
0.63
601
NOTE
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
21
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VA
CAPACITY: 3.5 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.85
INPUT: 850 W
OUTDOOR DB (°C)
21
25
27
30
SHF
INPUT
21
18
4.11
2.76
0.67
680
3.94
2.64
0.67
714
3.78
2.53
0.67
748
3.64
2.44
0.67
782
21
20
4.29
2.36
0.55
714
4.11
2.26
0.55
757
3.99
2.19
0.55
774
3.85
2.12
0.55
808
22
18
4.11
2.92
0.71
680
3.94
2.80
0.71
714
3.78
2.68
0.71
748
3.64
2.58
0.71
782
22
20
4.29
2.53
0.59
714
4.11
2.43
0.59
757
3.99
2.35
0.59
774
3.85
2.27
0.59
808
22
22
4.46
2.10
0.47
740
4.31
2.02
0.47
786
4.20
1.97
0.47
808
4.03
1.89
0.47
842
23
18
4.11
3.08
0.75
680
3.94
2.95
0.75
714
3.78
2.84
0.75
748
3.64
2.73
0.75
782
23
20
4.29
2.70
0.63
714
4.11
2.59
0.63
757
3.99
2.51
0.63
774
3.85
2.43
0.63
808
23
22
4.46
2.28
0.51
740
4.31
2.20
0.51
786
4.20
2.14
0.51
808
4.03
2.05
0.51
842
24
18
4.11
3.25
0.79
680
3.94
3.11
0.79
714
3.78
2.99
0.79
748
3.64
2.88
0.79
782
24
20
4.29
2.87
0.67
714
4.11
2.76
0.67
757
3.99
2.67
0.67
774
3.85
2.58
0.67
808
24
22
4.46
2.45
0.55
740
4.31
2.37
0.55
786
4.20
2.31
0.55
808
4.03
2.21
0.55
842
24
24
4.69
2.02
0.43
774
4.52
1.94
0.43
816
4.41
1.90
0.43
842
4.27
1.84
0.43
884
25
18
4.11
3.41
0.83
680
3.94
3.27
0.83
714
3.78
3.14
0.83
748
3.64
3.02
0.83
782
25
20
4.29
3.04
0.71
714
4.11
2.92
0.71
757
3.99
2.83
0.71
774
3.85
2.73
0.71
808
25
22
4.46
2.63
0.59
740
4.31
2.54
0.59
786
4.20
2.48
0.59
808
4.03
2.37
0.59
842
25
24
4.69
2.20
0.47
774
4.52
2.12
0.47
816
4.41
2.07
0.47
842
4.27
2.01
0.47
884
26
18
4.11
3.58
0.87
680
3.94
3.43
0.87
714
3.78
3.29
0.87
748
3.64
3.17
0.87
782
26
20
4.29
3.22
0.75
714
4.11
3.08
0.75
757
3.99
2.99
0.75
774
3.85
2.89
0.75
808
26
22
4.46
2.81
0.63
740
4.31
2.71
0.63
786
4.20
2.65
0.63
808
4.03
2.54
0.63
842
26
24
4.69
2.39
0.51
774
4.52
2.30
0.51
816
4.41
2.25
0.51
842
4.27
2.18
0.51
884
26
26
4.83
1.88
0.39
816
4.69
1.83
0.39
859
4.62
1.80
0.39
884
4.48
1.75
0.39
910
27
18
4.11
3.74
0.91
680
3.94
3.58
0.91
714
3.78
3.44
0.91
748
3.64
3.31
0.91
782
27
20
4.29
3.39
0.79
714
4.11
3.25
0.79
757
3.99
3.15
0.79
774
3.85
3.04
0.79
808
27
22
4.46
2.99
0.67
740
4.31
2.88
0.67
786
4.20
2.81
0.67
808
4.03
2.70
0.67
842
27
24
4.69
2.58
0.55
774
4.52
2.48
0.55
816
4.41
2.43
0.55
842
4.27
2.35
0.55
884
27
26
4.83
2.08
0.43
816
4.69
2.02
0.43
859
4.62
1.99
0.43
884
4.48
1.93
0.43
910
28
18
4.11
3.91
0.95
680
3.94
3.74
0.95
714
3.78
3.59
0.95
748
3.64
3.46
0.95
782
28
20
4.29
3.56
0.83
714
4.11
3.41
0.83
757
3.99
3.31
0.83
774
3.85
3.20
0.83
808
28
22
4.46
3.17
0.71
740
4.31
3.06
0.71
786
4.20
2.98
0.71
808
4.03
2.86
0.71
842
28
24
4.69
2.77
0.59
774
4.52
2.66
0.59
816
4.41
2.60
0.59
842
4.27
2.52
0.59
884
28
26
4.83
2.27
0.47
816
4.69
2.20
0.47
859
4.62
2.17
0.47
884
4.48
2.11
0.47
910
29
18
4.11
4.07
0.99
680
3.94
3.90
0.99
714
3.78
3.74
0.99
748
3.64
3.60
0.99
782
29
20
4.29
3.73
0.87
714
4.11
3.58
0.87
757
3.99
3.47
0.87
774
3.85
3.35
0.87
808
29
22
4.46
3.35
0.75
740
4.31
3.23
0.75
786
4.20
3.15
0.75
808
4.03
3.02
0.75
842
29
24
4.69
2.95
0.63
774
4.52
2.84
0.63
816
4.41
2.78
0.63
842
4.27
2.69
0.63
884
29
26
4.83
2.46
0.51
816
4.69
2.39
0.51
859
4.62
2.36
0.51
884
4.48
2.28
0.51
910
30
18
4.11
4.11
1.00
680
3.94
3.94
1.00
714
3.78
3.78
1.00
748
3.64
3.64
1.00
782
30
20
4.29
3.90
0.91
714
4.11
3.74
0.91
757
3.99
3.63
0.91
774
3.85
3.50
0.91
808
30
22
4.46
3.53
0.79
740
4.31
3.40
0.79
786
4.20
3.32
0.79
808
4.03
3.18
0.79
842
30
24
4.69
3.14
0.67
774
4.52
3.03
0.67
816
4.41
2.95
0.67
842
4.27
2.86
0.67
884
30
26
4.83
2.66
0.55
816
4.69
2.58
0.55
859
4.62
2.54
0.55
884
4.48
2.46
0.55
910
31
18
4.11
4.11
1.00
680
3.94
3.94
1.00
714
3.78
3.78
1.00
748
3.64
3.64
1.00
782
31
20
4.29
4.07
0.95
714
4.11
3.91
0.95
757
3.99
3.79
0.95
774
3.85
3.66
0.95
808
31
22
4.46
3.70
0.83
740
4.31
3.57
0.83
786
4.20
3.49
0.83
808
4.03
3.34
0.83
842
31
24
4.69
3.33
0.71
774
4.52
3.21
0.71
816
4.41
3.13
0.71
842
4.27
3.03
0.71
884
31
26
4.83
2.85
0.59
816
4.69
2.77
0.59
859
4.62
2.73
0.59
884
4.48
2.64
0.59
910
32
18
4.11
4.11
1.00
680
3.94
3.94
1.00
714
3.78
3.78
1.00
748
3.64
3.64
1.00
782
32
20
4.29
4.24
0.99
714
4.11
4.07
0.99
757
3.99
3.95
0.99
774
3.85
3.81
0.99
808
32
22
4.46
3.88
0.87
740
4.31
3.75
0.87
786
4.20
3.65
0.87
808
4.03
3.50
0.87
842
32
24
4.69
3.52
0.75
774
4.52
3.39
0.75
816
4.41
3.31
0.75
842
4.27
3.20
0.75
884
32
26
4.83
3.04
0.63
816
4.69
2.95
0.63
859
4.62
2.91
0.63
884
4.48
2.82
0.63
910
NOTE
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
22
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VA
CAPACITY: 3.5 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.85
INPUT: 850 W
OUTDOOR DB (°C)
35
40
46
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
21
18
3.43
2.30
0.67
833
3.15
2.11
0.67
884
2.91
1.95
0.67
918
21
20
3.61
1.98
0.55
867
3.36
1.85
0.55
910
3.12
1.71
0.55
961
22
18
3.43
2.44
0.71
833
3.15
2.24
0.71
884
2.91
2.06
0.71
918
22
20
3.61
2.13
0.59
867
3.36
1.98
0.59
910
3.12
1.84
0.59
961
22
22
3.82
1.79
0.47
901
3.57
1.68
0.47
952
3.33
1.56
0.47
986
23
18
3.43
2.57
0.75
833
3.15
2.36
0.75
884
2.91
2.18
0.75
918
23
20
3.61
2.27
0.63
867
3.36
2.12
0.63
910
3.12
1.96
0.63
961
23
22
3.82
1.95
0.51
901
3.57
1.82
0.51
952
3.33
1.70
0.51
986
24
18
3.43
2.71
0.79
833
3.15
2.49
0.79
884
2.91
2.29
0.79
918
24
20
3.61
2.42
0.67
867
3.36
2.25
0.67
910
3.12
2.09
0.67
961
24
22
3.82
2.10
0.55
901
3.57
1.96
0.55
952
3.33
1.83
0.55
986
24
24
4.03
1.73
0.43
935
3.78
1.63
0.43
978
3.57
1.54
0.43
1020
25
18
3.43
2.85
0.83
833
3.15
2.61
0.83
884
2.91
2.41
0.83
918
25
20
3.61
2.56
0.71
867
3.36
2.39
0.71
910
3.12
2.21
0.71
961
25
22
3.82
2.25
0.59
901
3.57
2.11
0.59
952
3.33
1.96
0.59
986
25
24
4.03
1.89
0.47
935
3.78
1.78
0.47
978
3.57
1.68
0.47
1020
26
18
3.43
2.98
0.87
833
3.15
2.74
0.87
884
2.91
2.53
0.87
918
26
20
3.61
2.70
0.75
867
3.36
2.52
0.75
910
3.12
2.34
0.75
961
26
22
3.82
2.40
0.63
901
3.57
2.25
0.63
952
3.33
2.09
0.63
986
26
24
4.03
2.05
0.51
935
3.78
1.93
0.51
978
3.57
1.82
0.51
1020
26
26
4.24
1.65
0.39
969
3.99
1.56
0.39
1012
3.75
1.46
0.39
1054
27
18
3.43
3.12
0.91
833
3.15
2.87
0.91
884
2.91
2.64
0.91
918
27
20
3.61
2.85
0.79
867
3.36
2.65
0.79
910
3.12
2.46
0.79
961
27
22
3.82
2.56
0.67
901
3.57
2.39
0.67
952
3.33
2.23
0.67
986
27
24
4.03
2.21
0.55
935
3.78
2.08
0.55
978
3.57
1.96
0.55
1020
27
26
4.24
1.82
0.43
969
3.99
1.72
0.43
1012
3.75
1.61
0.43
1054
28
18
3.43
3.26
0.95
833
3.15
2.99
0.95
884
2.91
2.76
0.95
918
28
20
3.61
2.99
0.83
867
3.36
2.79
0.83
910
3.12
2.59
0.83
961
28
22
3.82
2.71
0.71
901
3.57
2.53
0.71
952
3.33
2.36
0.71
986
28
24
4.03
2.37
0.59
935
3.78
2.23
0.59
978
3.57
2.11
0.59
1020
28
26
4.24
1.99
0.47
969
3.99
1.88
0.47
1012
3.75
1.76
0.47
1054
29
18
3.43
3.40
0.99
833
3.15
3.12
0.99
884
2.91
2.88
0.99
918
29
20
3.61
3.14
0.87
867
3.36
2.92
0.87
910
3.12
2.71
0.87
961
29
22
3.82
2.86
0.75
901
3.57
2.68
0.75
952
3.33
2.49
0.75
986
29
24
4.03
2.54
0.63
935
3.78
2.38
0.63
978
3.57
2.25
0.63
1020
29
26
4.24
2.16
0.51
969
3.99
2.03
0.51
1012
3.75
1.91
0.51
1054
30
18
3.43
3.43
1.00
833
3.15
3.15
1.00
884
2.91
2.91
1.00
918
30
20
3.61
3.28
0.91
867
3.36
3.06
0.91
910
3.12
2.83
0.91
961
30
22
3.82
3.01
0.79
901
3.57
2.82
0.79
952
3.33
2.63
0.79
986
30
24
4.03
2.70
0.67
935
3.78
2.53
0.67
978
3.57
2.39
0.67
1020
30
26
4.24
2.33
0.55
969
3.99
2.19
0.55
1012
3.75
2.06
0.55
1054
31
18
3.43
3.43
1.00
833
3.15
3.15
1.00
884
2.91
2.91
1.00
918
31
20
3.61
3.42
0.95
867
3.36
3.19
0.95
910
3.12
2.96
0.95
961
31
22
3.82
3.17
0.83
901
3.57
2.96
0.83
952
3.33
2.76
0.83
986
31
24
4.03
2.86
0.71
935
3.78
2.68
0.71
978
3.57
2.53
0.71
1020
31
26
4.24
2.50
0.59
969
3.99
2.35
0.59
1012
3.75
2.21
0.59
1054
32
18
3.43
3.43
1.00
833
3.15
3.15
1.00
884
2.91
2.91
1.00
918
32
20
3.61
3.57
0.99
867
3.36
3.33
0.99
910
3.12
3.08
0.99
961
32
22
3.82
3.32
0.87
901
3.57
3.11
0.87
952
3.33
2.89
0.87
986
32
24
4.03
3.02
0.75
935
3.78
2.84
0.75
978
3.57
2.68
0.75
1020
32
26
4.24
2.67
0.63
969
3.99
2.51
0.63
1012
3.75
2.36
0.63
1054
NOTE
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
23
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VAH
CAPACITY: 3.5 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.85
INPUT: 835 W
OUTDOOR DB (°C)
21
25
27
30
SHF
INPUT
21
18
4.11
2.76
0.67
668
3.94
2.64
0.67
701
3.78
2.53
0.67
735
3.64
2.44
0.67
768
21
20
4.29
2.36
0.55
701
4.11
2.26
0.55
743
3.99
2.19
0.55
760
3.85
2.12
0.55
793
22
18
4.11
2.92
0.71
668
3.94
2.80
0.71
701
3.78
2.68
0.71
735
3.64
2.58
0.71
768
22
20
4.29
2.53
0.59
701
4.11
2.43
0.59
743
3.99
2.35
0.59
760
3.85
2.27
0.59
793
22
22
4.46
2.10
0.47
726
4.31
2.02
0.47
772
4.20
1.97
0.47
793
4.03
1.89
0.47
827
23
18
4.11
3.08
0.75
668
3.94
2.95
0.75
701
3.78
2.84
0.75
735
3.64
2.73
0.75
768
23
20
4.29
2.70
0.63
701
4.11
2.59
0.63
743
3.99
2.51
0.63
760
3.85
2.43
0.63
793
23
22
4.46
2.28
0.51
726
4.31
2.20
0.51
772
4.20
2.14
0.51
793
4.03
2.05
0.51
827
24
18
4.11
3.25
0.79
668
3.94
3.11
0.79
701
3.78
2.99
0.79
735
3.64
2.88
0.79
768
24
20
4.29
2.87
0.67
701
4.11
2.76
0.67
743
3.99
2.67
0.67
760
3.85
2.58
0.67
793
24
22
4.46
2.45
0.55
726
4.31
2.37
0.55
772
4.20
2.31
0.55
793
4.03
2.21
0.55
827
24
24
4.69
2.02
0.43
760
4.52
1.94
0.43
802
4.41
1.90
0.43
827
4.27
1.84
0.43
868
25
18
4.11
3.41
0.83
668
3.94
3.27
0.83
701
3.78
3.14
0.83
735
3.64
3.02
0.83
768
25
20
4.29
3.04
0.71
701
4.11
2.92
0.71
743
3.99
2.83
0.71
760
3.85
2.73
0.71
793
25
22
4.46
2.63
0.59
726
4.31
2.54
0.59
772
4.20
2.48
0.59
793
4.03
2.37
0.59
827
25
24
4.69
2.20
0.47
760
4.52
2.12
0.47
802
4.41
2.07
0.47
827
4.27
2.01
0.47
868
26
18
4.11
3.58
0.87
668
3.94
3.43
0.87
701
3.78
3.29
0.87
735
3.64
3.17
0.87
768
26
20
4.29
3.22
0.75
701
4.11
3.08
0.75
743
3.99
2.99
0.75
760
3.85
2.89
0.75
793
26
22
4.46
2.81
0.63
726
4.31
2.71
0.63
772
4.20
2.65
0.63
793
4.03
2.54
0.63
827
26
24
4.69
2.39
0.51
760
4.52
2.30
0.51
802
4.41
2.25
0.51
827
4.27
2.18
0.51
868
26
26
4.83
1.88
0.39
802
4.69
1.83
0.39
843
4.62
1.80
0.39
868
4.48
1.75
0.39
893
27
18
4.11
3.74
0.91
668
3.94
3.58
0.91
701
3.78
3.44
0.91
735
3.64
3.31
0.91
768
27
20
4.29
3.39
0.79
701
4.11
3.25
0.79
743
3.99
3.15
0.79
760
3.85
3.04
0.79
793
27
22
4.46
2.99
0.67
726
4.31
2.88
0.67
772
4.20
2.81
0.67
793
4.03
2.70
0.67
827
27
24
4.69
2.58
0.55
760
4.52
2.48
0.55
802
4.41
2.43
0.55
827
4.27
2.35
0.55
868
27
26
4.83
2.08
0.43
802
4.69
2.02
0.43
843
4.62
1.99
0.43
868
4.48
1.93
0.43
893
28
18
4.11
3.91
0.95
668
3.94
3.74
0.95
701
3.78
3.59
0.95
735
3.64
3.46
0.95
768
28
20
4.29
3.56
0.83
701
4.11
3.41
0.83
743
3.99
3.31
0.83
760
3.85
3.20
0.83
793
28
22
4.46
3.17
0.71
726
4.31
3.06
0.71
772
4.20
2.98
0.71
793
4.03
2.86
0.71
827
28
24
4.69
2.77
0.59
760
4.52
2.66
0.59
802
4.41
2.60
0.59
827
4.27
2.52
0.59
868
28
26
4.83
2.27
0.47
802
4.69
2.20
0.47
843
4.62
2.17
0.47
868
4.48
2.11
0.47
893
29
18
4.11
4.07
0.99
668
3.94
3.90
0.99
701
3.78
3.74
0.99
735
3.64
3.60
0.99
768
29
20
4.29
3.73
0.87
701
4.11
3.58
0.87
743
3.99
3.47
0.87
760
3.85
3.35
0.87
793
29
22
4.46
3.35
0.75
726
4.31
3.23
0.75
772
4.20
3.15
0.75
793
4.03
3.02
0.75
827
29
24
4.69
2.95
0.63
760
4.52
2.84
0.63
802
4.41
2.78
0.63
827
4.27
2.69
0.63
868
29
26
4.83
2.46
0.51
802
4.69
2.39
0.51
843
4.62
2.36
0.51
868
4.48
2.28
0.51
893
30
18
4.11
4.11
1.00
668
3.94
3.94
1.00
701
3.78
3.78
1.00
735
3.64
3.64
1.00
768
30
20
4.29
3.90
0.91
701
4.11
3.74
0.91
743
3.99
3.63
0.91
760
3.85
3.50
0.91
793
30
22
4.46
3.53
0.79
726
4.31
3.40
0.79
772
4.20
3.32
0.79
793
4.03
3.18
0.79
827
30
24
4.69
3.14
0.67
760
4.52
3.03
0.67
802
4.41
2.95
0.67
827
4.27
2.86
0.67
868
30
26
4.83
2.66
0.55
802
4.69
2.58
0.55
843
4.62
2.54
0.55
868
4.48
2.46
0.55
893
31
18
4.11
4.11
1.00
668
3.94
3.94
1.00
701
3.78
3.78
1.00
735
3.64
3.64
1.00
768
31
20
4.29
4.07
0.95
701
4.11
3.91
0.95
743
3.99
3.79
0.95
760
3.85
3.66
0.95
793
31
22
4.46
3.70
0.83
726
4.31
3.57
0.83
772
4.20
3.49
0.83
793
4.03
3.34
0.83
827
31
24
4.69
3.33
0.71
760
4.52
3.21
0.71
802
4.41
3.13
0.71
827
4.27
3.03
0.71
868
31
26
4.83
2.85
0.59
802
4.69
2.77
0.59
843
4.62
2.73
0.59
868
4.48
2.64
0.59
893
32
18
4.11
4.11
1.00
668
3.94
3.94
1.00
701
3.78
3.78
1.00
735
3.64
3.64
1.00
768
32
20
4.29
4.24
0.99
701
4.11
4.07
0.99
743
3.99
3.95
0.99
760
3.85
3.81
0.99
793
32
22
4.46
3.88
0.87
726
4.31
3.75
0.87
772
4.20
3.65
0.87
793
4.03
3.50
0.87
827
32
24
4.69
3.52
0.75
760
4.52
3.39
0.75
802
4.41
3.31
0.75
827
4.27
3.20
0.75
868
32
26
4.83
3.04
0.63
802
4.69
2.95
0.63
843
4.62
2.91
0.63
868
4.48
2.82
0.63
893
NOTE
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
24
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VAH
CAPACITY: 3.5 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.85
INPUT: 835 W
OUTDOOR DB (°C)
35
40
46
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
21
18
3.43
2.30
0.67
818
3.15
2.11
0.67
868
2.91
1.95
0.67
902
21
20
3.61
1.98
0.55
852
3.36
1.85
0.55
893
3.12
1.71
0.55
944
22
18
3.43
2.44
0.71
818
3.15
2.24
0.71
868
2.91
2.06
0.71
902
22
20
3.61
2.13
0.59
852
3.36
1.98
0.59
893
3.12
1.84
0.59
944
22
22
3.82
1.79
0.47
885
3.57
1.68
0.47
935
3.33
1.56
0.47
969
23
18
3.43
2.57
0.75
818
3.15
2.36
0.75
868
2.91
2.18
0.75
902
23
20
3.61
2.27
0.63
852
3.36
2.12
0.63
893
3.12
1.96
0.63
944
23
22
3.82
1.95
0.51
885
3.57
1.82
0.51
935
3.33
1.70
0.51
969
24
18
3.43
2.71
0.79
818
3.15
2.49
0.79
868
2.91
2.29
0.79
902
24
20
3.61
2.42
0.67
852
3.36
2.25
0.67
893
3.12
2.09
0.67
944
24
22
3.82
2.10
0.55
885
3.57
1.96
0.55
935
3.33
1.83
0.55
969
24
24
4.03
1.73
0.43
919
3.78
1.63
0.43
960
3.57
1.54
0.43
1002
25
18
3.43
2.85
0.83
818
3.15
2.61
0.83
868
2.91
2.41
0.83
902
25
20
3.61
2.56
0.71
852
3.36
2.39
0.71
893
3.12
2.21
0.71
944
25
22
3.82
2.25
0.59
885
3.57
2.11
0.59
935
3.33
1.96
0.59
969
25
24
4.03
1.89
0.47
919
3.78
1.78
0.47
960
3.57
1.68
0.47
1002
26
18
3.43
2.98
0.87
818
3.15
2.74
0.87
868
2.91
2.53
0.87
902
26
20
3.61
2.70
0.75
852
3.36
2.52
0.75
893
3.12
2.34
0.75
944
26
22
3.82
2.40
0.63
885
3.57
2.25
0.63
935
3.33
2.09
0.63
969
26
24
4.03
2.05
0.51
919
3.78
1.93
0.51
960
3.57
1.82
0.51
1002
26
26
4.24
1.65
0.39
952
3.99
1.56
0.39
994
3.75
1.46
0.39
1035
27
18
3.43
3.12
0.91
818
3.15
2.87
0.91
868
2.91
2.64
0.91
902
27
20
3.61
2.85
0.79
852
3.36
2.65
0.79
893
3.12
2.46
0.79
944
27
22
3.82
2.56
0.67
885
3.57
2.39
0.67
935
3.33
2.23
0.67
969
27
24
4.03
2.21
0.55
919
3.78
2.08
0.55
960
3.57
1.96
0.55
1002
27
26
4.24
1.82
0.43
952
3.99
1.72
0.43
994
3.75
1.61
0.43
1035
28
18
3.43
3.26
0.95
818
3.15
2.99
0.95
868
2.91
2.76
0.95
902
28
20
3.61
2.99
0.83
852
3.36
2.79
0.83
893
3.12
2.59
0.83
944
28
22
3.82
2.71
0.71
885
3.57
2.53
0.71
935
3.33
2.36
0.71
969
28
24
4.03
2.37
0.59
919
3.78
2.23
0.59
960
3.57
2.11
0.59
1002
28
26
4.24
1.99
0.47
952
3.99
1.88
0.47
994
3.75
1.76
0.47
1035
29
18
3.43
3.40
0.99
818
3.15
3.12
0.99
868
2.91
2.88
0.99
902
29
20
3.61
3.14
0.87
852
3.36
2.92
0.87
893
3.12
2.71
0.87
944
29
22
3.82
2.86
0.75
885
3.57
2.68
0.75
935
3.33
2.49
0.75
969
29
24
4.03
2.54
0.63
919
3.78
2.38
0.63
960
3.57
2.25
0.63
1002
29
26
4.24
2.16
0.51
952
3.99
2.03
0.51
994
3.75
1.91
0.51
1035
30
18
3.43
3.43
1.00
818
3.15
3.15
1.00
868
2.91
2.91
1.00
902
30
20
3.61
3.28
0.91
852
3.36
3.06
0.91
893
3.12
2.83
0.91
944
30
22
3.82
3.01
0.79
885
3.57
2.82
0.79
935
3.33
2.63
0.79
969
30
24
4.03
2.70
0.67
919
3.78
2.53
0.67
960
3.57
2.39
0.67
1002
30
26
4.24
2.33
0.55
952
3.99
2.19
0.55
994
3.75
2.06
0.55
1035
31
18
3.43
3.43
1.00
818
3.15
3.15
1.00
868
2.91
2.91
1.00
902
31
20
3.61
3.42
0.95
852
3.36
3.19
0.95
893
3.12
2.96
0.95
944
31
22
3.82
3.17
0.83
885
3.57
2.96
0.83
935
3.33
2.76
0.83
969
31
24
4.03
2.86
0.71
919
3.78
2.68
0.71
960
3.57
2.53
0.71
1002
31
26
4.24
2.50
0.59
952
3.99
2.35
0.59
994
3.75
2.21
0.59
1035
32
18
3.43
3.43
1.00
818
3.15
3.15
1.00
868
2.91
2.91
1.00
902
32
20
3.61
3.57
0.99
852
3.36
3.33
0.99
893
3.12
3.08
0.99
944
32
22
3.82
3.32
0.87
885
3.57
3.11
0.87
935
3.33
2.89
0.87
969
32
24
4.03
3.02
0.75
919
3.78
2.84
0.75
960
3.57
2.68
0.75
1002
26
4.24
2.67
0.63
952
3.99
2.51
0.63
994
3.75
2.36
0.63
1035
32
NOTE
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
25
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD50VA
CAPACITY: 5.0 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.77
INPUT: 1500 W
OUTDOOR DB (°C)
21
25
27
30
SHF
INPUT
21
18
5.88
3.47
0.59
1200
5.63
3.32
0.59
1260
5.40
3.19
0.59
1320
5.20
3.07
0.59
1380
21
20
6.13
2.88
0.47
1260
5.88
2.76
0.47
1335
5.70
2.68
0.47
1365
5.50
2.59
0.47
1425
22
18
5.88
3.70
0.63
1200
5.63
3.54
0.63
1260
5.40
3.40
0.63
1320
5.20
3.28
0.63
1380
22
20
6.13
3.12
0.51
1260
5.88
3.00
0.51
1335
5.70
2.91
0.51
1365
5.50
2.81
0.51
1425
22
22
6.38
2.49
0.39
1305
6.15
2.40
0.39
1388
6.00
2.34
0.39
1425
5.75
2.24
0.39
1485
23
18
5.88
3.94
0.67
1200
5.63
3.77
0.67
1260
5.40
3.62
0.67
1320
5.20
3.48
0.67
1380
23
20
6.13
3.37
0.55
1260
5.88
3.23
0.55
1335
5.70
3.14
0.55
1365
5.50
3.03
0.55
1425
23
22
6.38
2.74
0.43
1305
6.15
2.64
0.43
1388
6.00
2.58
0.43
1425
5.75
2.47
0.43
1485
24
18
5.88
4.17
0.71
1200
5.63
3.99
0.71
1260
5.40
3.83
0.71
1320
5.20
3.69
0.71
1380
24
20
6.13
3.61
0.59
1260
5.88
3.47
0.59
1335
5.70
3.36
0.59
1365
5.50
3.25
0.59
1425
24
22
6.38
3.00
0.47
1305
6.15
2.89
0.47
1388
6.00
2.82
0.47
1425
5.75
2.70
0.47
1485
24
24
6.70
2.35
0.35
1365
6.45
2.26
0.35
1440
6.30
2.21
0.35
1485
6.10
2.14
0.35
1560
25
18
5.88
4.41
0.75
1200
5.63
4.22
0.75
1260
5.40
4.05
0.75
1320
5.20
3.90
0.75
1380
25
20
6.13
3.86
0.63
1260
5.88
3.70
0.63
1335
5.70
3.59
0.63
1365
5.50
3.47
0.63
1425
25
22
6.38
3.25
0.51
1305
6.15
3.14
0.51
1388
6.00
3.06
0.51
1425
5.75
2.93
0.51
1485
25
24
6.70
2.61
0.39
1365
6.45
2.52
0.39
1440
6.30
2.46
0.39
1485
6.10
2.38
0.39
1560
26
18
5.88
4.64
0.79
1200
5.63
4.44
0.79
1260
5.40
4.27
0.79
1320
5.20
4.11
0.79
1380
26
20
6.13
4.10
0.67
1260
5.88
3.94
0.67
1335
5.70
3.82
0.67
1365
5.50
3.69
0.67
1425
26
22
6.38
3.51
0.55
1305
6.15
3.38
0.55
1388
6.00
3.30
0.55
1425
5.75
3.16
0.55
1485
26
24
6.70
2.88
0.43
1365
6.45
2.77
0.43
1440
6.30
2.71
0.43
1485
6.10
2.62
0.43
1560
26
26
6.90
2.14
0.31
1440
6.70
2.08
0.31
1515
6.60
2.05
0.31
1560
6.40
1.98
0.31
1605
27
18
5.88
4.88
0.83
1200
5.63
4.67
0.83
1260
5.40
4.48
0.83
1320
5.20
4.32
0.83
1380
27
20
6.13
4.35
0.71
1260
5.88
4.17
0.71
1335
5.70
4.05
0.71
1365
5.50
3.91
0.71
1425
27
22
6.38
3.76
0.59
1305
6.15
3.63
0.59
1388
6.00
3.54
0.59
1425
5.75
3.39
0.59
1485
27
24
6.70
3.15
0.47
1365
6.45
3.03
0.47
1440
6.30
2.96
0.47
1485
6.10
2.87
0.47
1560
27
26
6.90
2.42
0.35
1440
6.70
2.35
0.35
1515
6.60
2.31
0.35
1560
6.40
2.24
0.35
1605
28
18
5.88
5.11
0.87
1200
5.63
4.89
0.87
1260
5.40
4.70
0.87
1320
5.20
4.52
0.87
1380
28
20
6.13
4.59
0.75
1260
5.88
4.41
0.75
1335
5.70
4.28
0.75
1365
5.50
4.13
0.75
1425
28
22
6.38
4.02
0.63
1305
6.15
3.87
0.63
1388
6.00
3.78
0.63
1425
5.75
3.62
0.63
1485
28
24
6.70
3.42
0.51
1365
6.45
3.29
0.51
1440
6.30
3.21
0.51
1485
6.10
3.11
0.51
1560
28
26
6.90
2.69
0.39
1440
6.70
2.61
0.39
1515
6.60
2.57
0.39
1560
6.40
2.50
0.39
1605
29
18
5.88
5.35
0.91
1200
5.63
5.12
0.91
1260
5.40
4.91
0.91
1320
5.20
4.73
0.91
1380
29
20
6.13
4.84
0.79
1260
5.88
4.64
0.79
1335
5.70
4.50
0.79
1365
5.50
4.35
0.79
1425
29
22
6.38
4.27
0.67
1305
6.15
4.12
0.67
1388
6.00
4.02
0.67
1425
5.75
3.85
0.67
1485
29
24
6.70
3.69
0.55
1365
6.45
3.55
0.55
1440
6.30
3.47
0.55
1485
6.10
3.36
0.55
1560
29
26
6.90
2.97
0.43
1440
6.70
2.88
0.43
1515
6.60
2.84
0.43
1560
6.40
2.75
0.43
1605
30
18
5.88
5.58
0.95
1200
5.63
5.34
0.95
1260
5.40
5.13
0.95
1320
5.20
4.94
0.95
1380
30
20
6.13
5.08
0.83
1260
5.88
4.88
0.83
1335
5.70
4.73
0.83
1365
5.50
4.57
0.83
1425
30
22
6.38
4.53
0.71
1305
6.15
4.37
0.71
1388
6.00
4.26
0.71
1425
5.75
4.08
0.71
1485
30
24
6.70
3.95
0.59
1365
6.45
3.81
0.59
1440
6.30
3.72
0.59
1485
6.10
3.60
0.59
1560
30
26
6.90
3.24
0.47
1440
6.70
3.15
0.47
1515
6.60
3.10
0.47
1560
6.40
3.01
0.47
1605
31
18
5.88
5.82
0.99
1200
5.63
5.57
0.99
1260
5.40
5.35
0.99
1320
5.20
5.15
0.99
1380
31
20
6.13
5.33
0.87
1260
5.88
5.11
0.87
1335
5.70
4.96
0.87
1365
5.50
4.79
0.87
1425
31
22
6.38
4.78
0.75
1305
6.15
4.61
0.75
1388
6.00
4.50
0.75
1425
5.75
4.31
0.75
1485
31
24
6.70
4.22
0.63
1365
6.45
4.06
0.63
1440
6.30
3.97
0.63
1485
6.10
3.84
0.63
1560
31
26
6.90
3.52
0.51
1440
6.70
3.42
0.51
1515
6.60
3.37
0.51
1560
6.40
3.26
0.51
1605
32
18
5.88
5.88
1.00
1200
5.63
5.63
1.00
1260
5.40
5.40
1.00
1320
5.20
5.20
1.00
1380
32
20
6.13
5.57
0.91
1260
5.88
5.35
0.91
1335
5.70
5.19
0.91
1365
5.50
5.01
0.91
1425
32
22
6.38
5.04
0.79
1305
6.15
4.86
0.79
1388
6.00
4.74
0.79
1425
5.75
4.54
0.79
1485
32
24
6.70
4.49
0.67
1365
6.45
4.32
0.67
1440
6.30
4.22
0.67
1485
6.10
4.09
0.67
1560
32
26
6.90
3.80
0.55
1440
6.70
3.69
0.55
1515
6.60
3.63
0.55
1560
6.40
3.52
0.55
1605
NOTE
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
26
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD50VA
CAPACITY: 5.0 kW
INDOOR INDOOR
DB (°C) WB (°C)
SHF: 0.77
INPUT: 1500 W
OUTDOOR DB (°C)
35
40
46
SHF
INPUT
21
18
4.90
2.89
0.59
1470
4.50
2.66
0.59
1560
4.15
2.45
0.59
1620
21
20
5.15
2.42
0.47
1530
4.80
2.26
0.47
1605
4.45
2.09
0.47
1695
22
18
4.90
3.09
0.63
1470
4.50
2.84
0.63
1560
4.15
2.61
0.63
1620
22
20
5.15
2.63
0.51
1530
4.80
2.45
0.51
1605
4.45
2.27
0.51
1695
22
22
5.45
2.13
0.39
1590
5.10
1.99
0.39
1680
4.75
1.85
0.39
1740
23
18
4.90
3.28
0.67
1470
4.50
3.02
0.67
1560
4.15
2.78
0.67
1620
23
20
5.15
2.83
0.55
1530
4.80
2.64
0.55
1605
4.45
2.45
0.55
1695
23
22
5.45
2.34
0.43
1590
5.10
2.19
0.43
1680
4.75
2.04
0.43
1740
24
18
4.90
3.48
0.71
1470
4.50
3.20
0.71
1560
4.15
2.95
0.71
1620
24
20
5.15
3.04
0.59
1530
4.80
2.83
0.59
1605
4.45
2.63
0.59
1695
24
22
5.45
2.56
0.47
1590
5.10
2.40
0.47
1680
4.75
2.23
0.47
1740
24
24
5.75
2.01
0.35
1650
5.40
1.89
0.35
1725
5.10
1.79
0.35
1800
25
18
4.90
3.68
0.75
1470
4.50
3.38
0.75
1560
4.15
3.11
0.75
1620
25
20
5.15
3.24
0.63
1530
4.80
3.02
0.63
1605
4.45
2.80
0.63
1695
25
22
5.45
2.78
0.51
1590
5.10
2.60
0.51
1680
4.75
2.42
0.51
1740
25
24
5.75
2.24
0.39
1650
5.40
2.11
0.39
1725
5.10
1.99
0.39
1800
26
18
4.90
3.87
0.79
1470
4.50
3.56
0.79
1560
4.15
3.28
0.79
1620
26
20
5.15
3.45
0.67
1530
4.80
3.22
0.67
1605
4.45
2.98
0.67
1695
26
22
5.45
3.00
0.55
1590
5.10
2.81
0.55
1680
4.75
2.61
0.55
1740
26
24
5.75
2.47
0.43
1650
5.40
2.32
0.43
1725
5.10
2.19
0.43
1800
26
26
6.05
1.88
0.31
1710
5.70
1.77
0.31
1785
5.35
1.66
0.31
1860
27
18
4.90
4.07
0.83
1470
4.50
3.74
0.83
1560
4.15
3.44
0.83
1620
27
20
5.15
3.66
0.71
1530
4.80
3.41
0.71
1605
4.45
3.16
0.71
1695
27
22
5.45
3.22
0.59
1590
5.10
3.01
0.59
1680
4.75
2.80
0.59
1740
27
24
5.75
2.70
0.47
1650
5.40
2.54
0.47
1725
5.10
2.40
0.47
1800
27
26
6.05
2.12
0.35
1710
5.70
2.00
0.35
1785
5.35
1.87
0.35
1860
28
18
4.90
4.26
0.87
1470
4.50
3.92
0.87
1560
4.15
3.61
0.87
1620
28
20
5.15
3.86
0.75
1530
4.80
3.60
0.75
1605
4.45
3.34
0.75
1695
28
22
5.45
3.43
0.63
1590
5.10
3.21
0.63
1680
4.75
2.99
0.63
1740
28
24
5.75
2.93
0.51
1650
5.40
2.75
0.51
1725
5.10
2.60
0.51
1800
28
26
6.05
2.36
0.39
1710
5.70
2.22
0.39
1785
5.35
2.09
0.39
1860
29
18
4.90
4.46
0.91
1470
4.50
4.10
0.91
1560
4.15
3.78
0.91
1620
29
20
5.15
4.07
0.79
1530
4.80
3.79
0.79
1605
4.45
3.52
0.79
1695
29
22
5.45
3.65
0.67
1590
5.10
3.42
0.67
1680
4.75
3.18
0.67
1740
29
24
5.75
3.16
0.55
1650
5.40
2.97
0.55
1725
5.10
2.81
0.55
1800
29
26
6.05
2.60
0.43
1710
5.70
2.45
0.43
1785
5.35
2.30
0.43
1860
30
18
4.90
4.66
0.95
1470
4.50
4.28
0.95
1560
4.15
3.94
0.95
1620
30
20
5.15
4.27
0.83
1530
4.80
3.98
0.83
1605
4.45
3.69
0.83
1695
30
22
5.45
3.87
0.71
1590
5.10
3.62
0.71
1680
4.75
3.37
0.71
1740
30
24
5.75
3.39
0.59
1650
5.40
3.19
0.59
1725
5.10
3.01
0.59
1800
30
26
6.05
2.84
0.47
1710
5.70
2.68
0.47
1785
5.35
2.51
0.47
1860
31
18
4.90
4.85
0.99
1470
4.50
4.46
0.99
1560
4.15
4.11
0.99
1620
31
20
5.15
4.48
0.87
1530
4.80
4.18
0.87
1605
4.45
3.87
0.87
1695
31
22
5.45
4.09
0.75
1590
5.10
3.83
0.75
1680
4.75
3.56
0.75
1740
31
24
5.75
3.62
0.63
1650
5.40
3.40
0.63
1725
5.10
3.21
0.63
1800
31
26
6.05
3.09
0.51
1710
5.70
2.91
0.51
1785
5.35
2.73
0.51
1860
32
18
4.90
4.90
1.00
1470
4.50
4.50
1.00
1560
4.15
4.15
1.00
1620
32
20
5.15
4.69
0.91
1530
4.80
4.37
0.91
1605
4.45
4.05
0.91
1695
32
22
5.45
4.31
0.79
1590
5.10
4.03
0.79
1680
4.75
3.75
0.79
1740
32
24
5.75
3.85
0.67
1650
5.40
3.62
0.67
1725
5.10
3.42
0.67
1800
32
26
6.05
3.33
0.55
1710
5.70
3.14
0.55
1785
5.35
2.94
0.55
1860
NOTE
Q
SHC
SHF
INPUT
Q
SHC
SHF
INPUT
Q
SHC
Q : Total capacity (kW)
SHC : Sensible heat capacity (kW)
SHF : Sensible heat factor
INPUT : Total power input (W)
27
DB : Dry-bulb temperature
WB : Wet-bulb temperature
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-FD25VA MUZ-FD25VAH
CAPACITY: 3.2 kW
INDOOR
DB (°C)
INPUT: 610 W
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
2.02
397
2.43
476
2.85
537
3.26
580
3.68
616
4.06
634
4.48
647
21
1.92
427
2.30
506
2.72
561
3.10
604
3.52
634
3.90
653
4.30
677
26
1.73
458
2.14
537
2.53
592
2.94
634
3.36
665
3.74
683
4.16
702
MUZ-FD35VA
CAPACITY: 4.0 kW
INDOOR
DB (°C)
INPUT: 865 W
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
2.52
562
3.04
675
3.56
761
4.08
822
4.60
874
5.08
900
5.60
917
21
2.40
606
2.88
718
3.40
796
3.88
856
4.40
900
4.88
926
5.38
960
26
2.16
649
2.68
761
3.16
839
3.68
900
4.20
943
4.68
969
5.20
995
MUZ-FD35VAH
CAPACITY: 4.0 kW
INDOOR
DB (°C)
INPUT: 850 W
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
2.52
553
3.04
663
3.56
748
4.08
808
4.60
859
5.08
884
5.60
901
21
2.40
595
2.88
706
3.40
782
3.88
842
4.40
884
4.88
910
5.38
944
26
2.16
638
2.68
748
3.16
825
3.68
884
4.20
927
4.68
952
5.20
978
MUZ-FD50VA
CAPACITY: 5.8 kW
INDOOR
DB (°C)
INPUT: 1550 W
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
3.65
1008
4.41
1209
5.16
1364
5.92
1473
6.67
1566
7.37
1612
8.12
1643
21
3.48
1085
4.18
1287
4.93
1426
5.63
1535
6.38
1612
7.08
1659
7.80
1721
26
3.13
1163
3.89
1364
4.58
1504
5.34
1612
6.09
1690
6.79
1736
7.54
1783
NOTE Q: Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
28
9
ACTUATOR CONTROL
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds
15 seconds
ON
Compressor
OFF
ON
Outdoor fan
motor
OFF
9-2. R.V. COIL CONTROL
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
<COOL>
<HEAT>
5 seconds
Compressor
ON
OFF
R.V.coil
ON
OFF
5 seconds
Outdoor fan ON
OFF
motor
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
MUZ-FD25/35
Sensor
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Purpose
Compressor
Protection
Cooling: Coil frost prevention
Heating: High pressure protection
Cooling: High pressure protection
Heating: Defrosting
Protection
Cooling: Low ambient temperature operation
Heating: Defrosting (Heater)
Low outside temperature operation
29
○
○
○
○
○
○
○
○
LEV
○
○
○
○
○
○
Actuator
Outdoor
fan motor R.V.coil
○
○
○
○
○
○
○
Indoor fan
motor
Defrost
heater
○
○
MUZ-FD50
Sensor
Purpose
Discharge temperature
thermistor
Indoor coil temperature
thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature
thermistor
Outdoor heat exchanger
temperature thermistor
10
Protection
Cooling: Coil frost prevention
Heating: High pressure
protection
Heating: Defrosting
Protection
Cooling: Low ambient temperature operation
Cooling: Low ambient temperature operation
Cooling: High pressure
protection
Compressor
LEV
○
○
○
○
○
○
○
○
○
○
○
○
Actuator
Outdoor fan
motor
R.V.coil
Indoor fan
motor
○
○
○
○
○
○
SERVICE FUNCTIONS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
10-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
MUZ-FD25/35
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to
11-6-1.)
Jumper wire
Soldered
(Initial setting)
JS
None
(Cut)
Defrost finish temperature (°C)
5
10
MUZ-FD50
1. Turn OFF the power supply for the air conditioner before making the setting.
2. Set the 4th Dip Switch of SW1 on the outdoor electronic control P.C. board to
ON to change the defrost finish temperature. (Refer to 11-6-2.)
4th Dip Switch of SW1
OFF
(Initial setting)
Defrost finish temperature (°C)
ON
12.2
ON
1
2
3
4
8.3
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature.
The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 20°C or
below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
MUZ-FD25/35
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
MUZ-FD50
[How to activate pre-heat control]
1. Turn OFF the power supply for the air conditioner before making the setting.
2. Set the 2nd Dip Switch of SW1 on the outdoor electronic control P.C. board to
ON to activate pre-heat control function. (Refer to 11-6-2.)
30
ON
1
2
3
4
11
TROUBLESHOOTING
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Incorrect
Correct
Lead wiring
Housing point
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
31
11-2. FAILURE MODE RECALL FUNCTION
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details
can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Confirm that the indicators on
the LCD screen shown in the right figure are all displayed. Then release the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit. 1
1. Regardless of normal or abnormal condition, a short
beep is emitted once the signal is received.
Does POWER lamp on the indoor unit blink at the interval of
0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep
is emitted at the same timing as the blinking of
POWER lamp. 2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnormalities that can not be recalled with this way.
Confirm if outdoor unit is abnormal according to the detailed outdoor
unit failure mode recall function. (Refer to 11-2.2)
No
(OFF)
Yes
(Blinks)
Judgment of indoor/outdoor abnormality
Before blinking, does POWER lamp stay ON for 3 seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
Yes
No
The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the
outdoor unit failure mode table. (Refer to 11-2.3)
Make sure to check at least two consecutive blinking cycles. 3
The indoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the indoor unit
failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
Blinking at 0.52.5-second OFF second interval
Blinking at 0.52.5-second OFF second interval
ON
OFF
Beeps
Repeated cycle
Beeps
Repeated cycle
Beeps
Repeated cycle
3.Blinking pattern when the outdoor unit is abnormal:
Blinking at 0.52.5-second OFF
3-second ON
second interval
2.5-second OFF
3-second ON
Blinking at 0.5second interval
ON
OFF
No beep
Repeated cycle
Beeps
No beep
Repeated cycle
32
Beeps
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal.
Confirm if outdoor unit is abnormal according to the following procedures.
Confirm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO
COOL or TOO WARM button to adjust the set temperature to 25°C. 1
Does POWER lamp on the indoor unit blink at the
interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of POWER
lamp. 2
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
No
(OFF)
Yes
(Blinks)
The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (11-2.3.).
Make sure to check at least two consecutive blinking cycles. 2
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Release the failure mode recall function according to the left mentioned procedure.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when outdoor unit is abnormal:
2.5-second OFF
ON
OFF
3-second ON
No beep
Repeated cycle
Blinking at 0.5second interval
2.5-second OFF
3-second ON
No beep
Repeated cycle
Beeps
33
Blinking at 0.5second interval
Beeps
Repeated cycle
3. Outdoor unit failure mode table
MUZ-FD25/35
POWER lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
OFF
None (Normal)
2-time flash
2.5 seconds
OFF
Outdoor power system
3-time flash
2.5 seconds
OFF
Discharge temperature
thermistor
Defrost thermistor
1-time flash every
2.5 seconds
Fin temperature thermistor
3-time flash
2.5 seconds OFF
P.C. board temperature
thermistor
4-time flash
2.5 seconds OFF
Ambient temperature
thermistor
2-time flash
2.5 seconds OFF
Overcurrent
11-time flash
2.5 seconds OFF
4-time flash
2.5 seconds
OFF
Compressor synchronous
abnormality (Compressor
start-up failure protection)
5-time flash
2.5 seconds
OFF
—
—
—
Overcurrent protection stop is
continuously performed 3 times within
1 minute after the compressor gets
started.
• Reconnect
connectors.
• Refer to 11-5. "How
to check inverter/
compressor".
• Check stop valve.
• Refer to 11-5.
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identified by checking
the blinking pattern of
LED.
12-time flash
2.5 seconds OFF
Discharge temperature
6-time flash
2.5 seconds
OFF
High pressure
7-time flash
2.5 seconds
OFF
Fin temperature/ P.C. board
temperature
8-time flash
2.5 seconds
OFF
Outdoor fan motor
9-time flash
2.5 seconds
OFF
10-time flash
2.5 seconds
OFF
Nonvolatile memory data
11-time flash
2.5 seconds
OFF
DC voltage
8-time flash
2.5 seconds OFF
Each phase current of
compressor
9-time flash
2.5 seconds OFF
12-time flash
2.5 seconds
OFF
Overcurrent Compressor
open-phase
10-time flash
2.5 seconds OFF
—
7-time flash
2.5 seconds OFF
—
5-time flash
2.5 seconds OFF
Discharge temperature
—
Stop valve (Closed valve)
Remedy
—
—
14-time flash
2.5 seconds
OFF
Condition
14-time flash
2.5 seconds OFF
Thermistor shorts or opens during
compressor running.
Large current flows into intelligent
power module.
Waveform of compressor current is
distorted.
—
—
○
○
○
○
• Reconnect
compressor connector.
• Refer to 11-5. "How
to check inverter/
compressor".
• Check stop valve.
—
○
• Reconnect
compressor connector.
• Refer to 11-5. "How
to check inverter/
compressor".
—
○
—
○
—
○
—
○
Temperature of discharge temperature
thermistor exceeds 116°C, compressor
stops.
Compressor can restart if discharge
temperature thermistor reads 100°C or
less 3 minutes later.
• Check refrigerant
circuit and refrigerant
amount.
• Refer to 11-5. "Check
of LEV".
Temperature indoor coil thermistor
exceeds 70°C in HEAT mode.
Temperature defrost thermistor
exceeds 70°C in COOL mode.
• Check refrigerant
circuit and refrigerant
amount.
• Check stop valve.
Temperature of fin temperature
thermistor on the inverter P.C. board
exceeds 75 ~ 80°C, or temperature of
P.C. board temperature thermistor on
the inverter P.C. board exceeds 70 ~
75°C.
• Check around outdoor
unit.
• Check outdoor unit air
passage.
• Refer to 11-5. "Check
of outdoor fan motor".
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
• Refer to 11-5. "Check
of outdoor fan motor".
Refer to 11-5. "Check
of inverter P.C. board".
Nonvolatile memory data cannot be
read properly.
• Replace the inverter
P.C. board.
Temperature of discharge temperature • Refer to 11-5. "Check
thermistor has been 50°C or less for
of LEV".
20 minutes.
• Check refrigerant
circuit and refrigerant
amount.
DC voltage of inverter cannot be
• Refer to 11-5. "How
detected normally.
to check inverter/
compressor".
Each phase current of compressor
cannot be detected normally.
Large current flows into intelligent
• Reconnect
power module (IPM).
compressor connector.
The open-phase operation of
• Refer to 11-5. "How
compressor is detected.
to check inverter/
The interphase short out occurs in the compressor".
output of the intelligent power module
(IPM).
The compressor winding shorts out.
Closed valve is detected by
compressor current.
• Check stop valve
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
34
Indoor/outdoor Outdoor unit
unit failure
failure mode
mode recall recall
function
function
—
○
○
○
—
○
—
○
—
○
○
○
MUZ-FD50VA
POWER lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
LED1
LED2
OFF
None (Normal)
Lighting
Lighting
2-time flash
Outdoor power system
Lighting
Lighting Overcurrent protection stop is continuously
performed 3 times within 1 minute after the
compressor gets started, or when converter
protection stop or bus-bar voltage protection
stop is continuously performed 3 times within 3
minutes after start-up.
3-time flash
Discharge temperature
thermistor
Defrost thermistor
5-time flash
—
—
• Check the connection of the
compressor connecting wire.
• Refer to 11-5. "How to
check inverter/compressor".
• Check the stop valve.
○
—
Once
Lighting
Once
Lighting
Twice
Lighting
3 times
P.C. board temperature
thermistor
Lighting
4 times
• Replace the outdoor
electronic control P.C. board.
Outdoor heat exchanger
temperature thermistor
Lighting
9 times
• Refer to 11-5. "Check of
outdoor thermistors".
Overcurrent
Discharge temperature
Once
Lighting
6-time flash
High pressure
Lighting
7-time flash
Fin temperature
3 times
P.C. board temperature
4 times
8-time flash
Outdoor fan motor
Lighting
9-time flash
Nonvolatile memory data
Lighting
10-time flash Discharge temperature
11-time flash
Indoor/outdoor
unit failure
mode recall
function
Lighting
Ambient temperature
thermistor
Fin temperature thermistor
4-time flash
Remedy
Condition
Lighting
Communication error between Lighting
P.C. boards
Current sensor
Lighting
Thermistor shorts or opens during compressor
running.
• Refer to 11-5. "Check of
outdoor thermistors".
○
Goes out 28 A current flows into intelligent power module. • Reconnect compressor
connector.
• Refer to 11-5. "How to
check inverter/compressor.
• Check the stop valve.
Lighting Discharge temperature exceeds 116°C during • Check refrigerant circuit and
operation. Compressor can restart if discharge
refrigerant amount.
temperature thermistor reads 100°C or less 3
• Refer to 11-5. "Check of
minutes later.
LEV".
Lighting The outdoor heat exchanger temperature
exceeds 70°C during cooling or the indoor gas
pipe temperature exceeds 70°C during heating.
Goes out The fin temperature exceeds 87°C during
operation.
Goes out The P.C. board temperature exceeds 70°C
during operation.
Lighting Failure occurs continuously three times within
30 seconds after the fan gets started.
5 times Nonvolatile memory data cannot be read
properly.
Lighting The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 39°C for more than 20 minutes.
6 times Communication error occurs between the
electronic control P.C. board and power board
for more than 10 seconds.
The communication between boards protection
stop is continuously performed twice.
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air
passage.
• Refer to 11-5. "Check of
outdoor fan motor".
• Refer to 11-5. "Check of
outdoor fan motor".
• Replace the outdoor
electronic control P.C. board.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-5. "Check of
LEV".
• Check the connecting wire
between outdoor electronic
control P.C. board and
power board.
7 times A short or open circuit is detected in the current • Replace the power board.
sensor during compressor operating.
5 times
Goes out Zero cross signal cannot be detected while the
compressor is operating.
The protection stop of the zero cross detecting
circuit is continuously performed 10 times.
Converter
5 times
Bus-bar voltage
(1)
Bus-bar voltage
(2)
Even if this protection stop
is performed continuously
3 times, it does not mean
the abnormality in outdoor
power system.
5 times
6 times
• Check the connecting wire
among electronic control
P.C. board, noise filter P.C.
board and power board.
Goes out A failure is detected in the operation of the
• Check the voltage of power
converter during operation.
supply.
• Replace the power board.
Goes out The bus-bar voltage exceeds 400 V or falls to
200 V or below during compressor operating.
Goes out The bus-bar voltage exceeds 400 V or falls to 50 • Check the voltage of power
V or below during compressor operating.
supply.
• Replace the outdoor
electronic control P.C. board.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
35
—
—
—
—
○
—
—
○
—
○
Current sensor protection stop is continuously
performed twice.
Zero cross detecting circuit
—
—
○
—
11-3. TROUBLESHOOTING CHECK TABLE
MUZ-FD25/35
No.
1
Symptom
Outdoor unit
does not operate.
Abnormal point/
Condition
1-time flash every Outdoor power sys2.5 seconds
tem
LED indication
3
6-time flash
2.5 seconds OFF
11-time flash
2.5 seconds OFF
14-time flash
2.5 seconds OFF
5
6
7
8
Outdoor control sys- Nonvolatile memory data cannot be read properly.
tem
(POWER lamp of the indoor unit lights up or flashes 7-time.)
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
Stop valve/
Closed valve is detected by compressor current.
Closed valve
Outdoor unit
Outdoor unit is defective.
(Other abnormality)
Overcurrent protection
Large current flows into intelligent power module.
4-time flash
2.5 seconds OFF
Fin temperature
/P.C. board temperature thermistor
overheat protection
High pressure protection
Temperature of fin temperature thermistor on the heat sink
exceeds 75 ~ 80°C or temperature of P.C. board temperature
thermistor on the inverter P.C.board exceeds 70 ~ 75°C.
10
5-time flash
2.5 seconds OFF
11
8-time flash
2.5 seconds OFF
Compressor synThe waveform of compressor current is distorted.
chronous abnormality
10-time flash
2.5 seconds OFF
Outdoor fan motor
12
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
12-time flash
2.5 seconds OFF
13-time flash
2.5 seconds OFF
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
Each phase current
of compressor
DC voltage
Each phase current of compressor cannot be detected normally.
DC voltage of inverter cannot be detected normally.
Frequency drop by
current protection
Frequency drop by
high pressure protection
Current from power outlet is nearing breaker capacity.
13
14
15
Outdoor unit
operates.
16
17
18
Outdoor unit
operates.
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost
thermistor exceeds 70°C in COOL mode.
Temperature of indoor coil thermistor exceeds 55°C in HEAT
mode, compressor frequency lowers.
• Refer to 11-2.2. "Flow chart of the
detailed outdoor unit failure mode
recall function".
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-5. "Check of outdoor
fan motor".
• Check refrigerant circuit and refrigerant amount.
• Check stop valve.
• Reconnect connector of compressor.
• Refer to 11-5. "How to check inverter/compressor".
• Refer to 11-5. "Check of outdoor
fan motor.
• Refer to 11-5. "Check of inverter
P.C. board.
• Refer to 11-5. "How to check inverter/compressor".
• Refer to 11-5. "How to check inverter/compressor".
The unit is normal, but check the
following.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Indoor coil thermistor reads 8°C or less in COOL mode, compressor frequency lowers.
4-time flash
2.5 seconds OFF
Frequency drop by
discharge temperature protection
7-time flash
2.5 seconds OFF
Low discharge temperature protection
Temperature of discharge temperature thermistor exceeds 111 • Check refrigerant circuit and refrig°C, compressor frequency lowers.
erant amount.
• Refer to 11-5. "Check of LEV".
• Refer to 11-5. "Check of outdoor
thermistors".
Temperature of discharge temperature thermistor has been 50 • Refer to 11-5. "Check of LEV".
°C or less for 20 minutes.
• Check refrigerant circuit and refrigerant amount.
8-time flash
2.5 seconds OFF
PAM protection
PAM: Pulse Amplitude Modulation
9-time flash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
The overcurrent flows into IGBT (Insulated Gate Bipolar transistor: TR821) or the bus-bar voltage reaches 320 V or more,
PAM stops and restarts.
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The flashing frequency shows the number of times
(Example) When the flashing frequency is “2”.
0.5-second ON
ON
OFF
• Refer to 11-5. "How to check miswiring and serial signal error.
• Check stop valve.
Frequency drop by
defrosting in COOL
mode
19
20
• Replace inverter P.C. board.
• Reconnect connector of compressor.
• Refer to 11-5. "How to check inverter/compressor".
• Check stop valve.
Discharge tempera- Temperature of discharge temperature thermistor exceeds 116 • Check refrigerant circuit and refrigture overheat protec- °C, compressor stops. Compressor can restart if discharge
erant amount.
tion
temperature thermistor reads 100°C or less 3 minutes later.
• Refer to 11-5. "Check of LEV".
'Outdoor unit 2-time flash
stops and
2.5 seconds OFF
restarts 3
minutes later'
is repeated.
3-time flash
2.5 seconds OFF
9
Remedy
Overcurrent protection stop is continuously performed 3 times • Reconnect connector of compreswithin 1 minute after the compressor gets started.
sor.
• Refer to 11-5. "How to check inverter/compressor".
• Check stop valve.
Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, • Refer to 11-5. "Check of outdoor
defrost thermistor, P.C. board temperature thermistor or ambi- thermistors".
ent temperature thermistor shorts or opens during compressor
running.
2
4
Condition
2.5-second OFF
This is not malfunction. PAM protection will be activated in the following cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
• Check if the connector of the compressor is correctly connected.
Refer to 11-5. "How to check
inverter/compressor".
Inverter P.C. board (Parts side)
the LED blinks after every 2.5-second OFF.
0.5-second ON
2.5-second OFF
36
LED
Flashing →
MUZ-FD50VA
No.
1
2
LED indication Abnormal point/ ConCondition
dition
LED1(Red) LED2(Yellow)
Outdoor unit
Outdoor power system Overcurrent protection stop is continuously performed 3 times
does not operwithin 1 minute after the compressor gets started, or when
ate.
converter protection stop or bus-bar voltage protection stop is
Lightning Twice
continuously performed three times within 3 minutes after startup.
Discharge temperature A short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 10 minLightning 3 times thermistor
utes of compressor start-up.
Symptom
3
4
Lightning 4 times
Lightning 5 times
Fin temperature
thermistor
P.C. board temperature thermistor
Ambient temperature
thermistor
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
A short circuit is detected in the thermistor during operation, or
an open circuit is detected in the thermistor after 5 minutes (in
cooling) and 10 minutes (in heating) of compressor start-up.
Remedy
• Check the connection of the compressor connecting wire.
• Refer to 11-5. "How to check inverter/compressor".
• Check the stop valve.
• Refer to 11-5. "Check of outdoor
thermistors".
• Refer to 11-5. "Check of outdoor
thermistors".
• Replace the outdoor electronic
control P.C. board.
• Refer to 11-5. "Check of outdoor
thermistors".
A short circuit is detected in the thermistor during operation, or
an open circuit is detected in the thermistor after 5 minutes of
compressor stat-up.
7
The communication fails between the indoor and outdoor unit 3 • Refer to 11-5. "How to check
minutes.
miswiring and serial signal error.
Nonvolatile memory The nonvolatile memory data cannot be read properly.
• Replace the outdoor electronic
Lightning 7 times data
control P.C. board.
Current sensor
Current sensor protection stop is continuously performed twice. • Replace the power board.
Lightning 8 times
8
Lightning 11 times
9
Lightning 12 times
5
6
’Outdoor unit
stops and
restarts 3 min10 utes later’ is
repeated.
Lightning 6 times
Serial signal
Communication error The communication protection stop between boards is continu- • Check the connecting wire bebetween P.C. boards ously performed twice.
tween outdoor electronic control
P.C. board and power board.
Zero cross detecting The protection stop of the zero cross detecting circuit is concircuit
tinuously performed 10 times.
lPM protection
• Check the connecting wire among
outdoor electronic control P.C.
board, noise filter P.C. board and
power board.
Overcurrent is detected after 30 seconds of compressor start- • Reconnect compressor connector.
up.
• Refer to 11-5. "How to check inverter/compressor".
• Check the stop valve.
Overcurrent is detected within 30 seconds of compressor start- • Check the power module (PAM
up.
module).
Twice
Goes
out
Lock protection
11
3 times
Goes
out
Discharge tempera- Discharge temperature exceeds 116°C during operation and
ture protection
compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
• Check the amount of gas and refrigerant circuit.
• Refer to 11-5. "Check of LEV".
12
4 times
Goes
out
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-5. "Check of outdoor
fan motor".
13
5 times
Goes
out
Fin temperature protection
P.C. board temperature
protection
High-Pressure protection
14
8 times
Goes
out
The fin temperature exceeds 87°C during operation.
The P.C. board temperature exceeds 70°C during operation.
The outdoor heat exchanger temperature exceeds 70°C during • Check the amount of gas and the
cooling or indoor gas pipe temperature exceeds 70°C during
refrigerant circuit.
heating.
• Check the stop valve.
Converter protection A failure is detected in the operation of the converter during
operation.
Bus-bar voltage pro- The bus-bar voltage exceeds 400 V or falls to 200 V or below
tection (1).
during compressor operating.
• Replace the power board.
Zero cross detecting Zero cross signal cannot be detected while the compressor is
circuit protection
operating.
• Check the connecting wire among
outdoor electronic control P.C.
board, noise filter P.C. board and
power board.
• Check the voltage of power supply.
• Replace the power board or the
outdoor electronic control P.C.
Bus-bar voltage pro- The bus-bar voltage exceeds 400 V or falls to 50 V or below
board.
tection (2)
during compressor operating.
• Refer to 11-5. "Check of bus-bar
voltage".
Failure occurs continuously three times within 30 seconds after • Refer to 11-5. "Check of outdoor
Goes Outdoor fan motor
the fan gets started.
fan motor".
out
Current sensor pro- A short or open circuit is detected in the current sensor during • Replace the power board.
8 times tection
compressor operating.
Communication be- Communication error occurs between the outdoor electronic
• Check the connecting wire between P.C. boards
control P.C. board and power board for more than 10 seconds
tween outdoor electronic control
11 times protection
P.C. board and power board.
Goes
out
15
9 times
16
13 times
17
Lighting
18
Lighting
19
Lighting 12 times
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 11-6.2.
2. LED is lighted during normal operation.
Outdoor electronic control P.C. board(Parts side)
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
0.5-second ON
ON
OFF
2.5-second OFF
2.5-second OFF
37
LED2 LED1
Lighting
0.5-second ON
No.
20
Symptom
Outdoor unit
operates.
21
LED indication Abnormal point/ Condition
LED1(Red) LED2(Yellow)
Primary current protection
Once
Lighting
Secondary current protection
High-Pressure protection
Twice Lighting
Defrosting in cooling
22
3 times
23
4 times
24
25
26
5 times
Outdoor unit
operates
9 times
Lighting
Condition
Remedy
These symptoms do not mean any
abnormality of the product, but
check the following points.
The current of the compressor exceeds 13 A.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
The indoor gas pipe temperature exceeds 45°C during heating. • Check if indoor/outdoor unit aircirculation is short cycled.
The indoor gas pipe temperature falls 3°C or below during
cooling.
Discharge temperature The discharge temperature exceeds 100°C during operation. • Check refrigerant circuit and refrigprotection
erant amount.
• Refer to 11-5. "Check of LEV".
Lighting
• Refer to 11-5. "Check of outdoor
thermistors’’.
Lighting
Low discharge temperature protection
The input current exceeds 15 A.
The frequency of the compressor is kept 80 Hz or more and
• Refer to 11-5. "Check of LEV".
the discharge temperature is kept under 39°C for more than 20 • Check refrigerant circuit and refrigminutes.
erant amount.
Cooling high-pressure The outdoor heat exchanger temperature exceeds 58°C during This symptom does not mean any
protection
operation.
abnormality of the product, but
check the following points.
• Check if indoor filters are clogged.
Lighting
• Check if refrigerant is short.
• Check if indoor/outdoor unit air
circulation is short cycled.
Lighting
Lighting
Inverter check mode
The unit is operated with emergency operation switch.
Normal
—
38
—
—
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
Part name
Defrost thermistor (RT61)
Check method and criterion
Figure
Ambient temperature
thermistor (RT65)
Measure the resistance with a tester.
Fin temperature
thermistor (RT64)
Refer to 11-6. "Test point diagram and voltage," 1. "Inverter P.C.
board", or 2. "Outdoor electronic control P.C. board", the chart of thermistor.
Outdoor heat exchanger
temperature thermistor
(RT68)
Measure the resistance with a tester. Before measurement, hold the
thermistor with your hands to warm it up.
Discharge temperature
thermistor (RT62)
Refer to 11-6. "Test point diagram and voltage," 1. "Inverter P.C.
board", or 2. "Outdoor electronic control P.C. board", the chart of thermistor.
Measure the resistance between terminals using a tester.
(Temperature: -10 ~ 40°C)
Compressor
Normal
25/35
U-V
U-W
V-W
0.82 ~ 1.11 Ω
0.60 ~ 0.82 Ω
Color of lead wire
RED – BLK
BLK – WHT
WHT – RED
RED BLK
W
50
Measure the resistance between lead wires using a tester.
(Temperature: -10 ~ 40°C)
Outdoor fan motor
WHT
V
WHT
Normal
U
RED BLK
W
25/35
50
11 ~ 16 Ω
12 ~ 17 Ω
V
U
Measure the resistance using a tester.
(Temperature: -10 ~ 40°C)
R. V. coil (21S4)
Normal
25/35
50
1.19 ~ 1.78 kΩ
1.15 ~ 1.71 kΩ
Measure the resistance using a tester.
(Temperature: -10 ~ 40°C)
Expansion valve coil
(LEV)
Color of lead wire
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
WHT
Normal
RED
37 ~ 54 Ω
YLW BRN BLU
Measure the resistance using a tester.
(Temperature: -10 ~ 40°C)
Defrost heater
MUZ-FD•VAH
High pressure switch
(HPS)
MUZ-FD50
LEV
ORN
Normal
349 ~ 428 Ω
Pressure
3.7 ± 0.15 MPa
4.8 +0.05
-0.1 MPa
Close
Open
39
11-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
MUZ-FD25/35
Disconnect the connector (CN61) between
compressor and the intelligent power module
(IPM).
See 11-5.
Check the voltage between terminals.
Are the voltages balanced?
Yes
No
Replace the inverter P.C. board.
See 11-5.
Check the compressor.
“Check of open phase”.
“Check of compressor”.
MUZ-FD50
Disconnect the terminal of the compressor. 3 minutes after turning on the power
supply, start EMERGENCY OPERATION.
• After the outdoor fan starts running, wait for 1 minute or more before measuring the voltage.
• Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
Measure the voltage between each lead
wire leading to the compressor.
U (BLK) - V (WHT)
V (WHT) - W (RED)
W (RED) - U (BLK)
Is output balanced?
Yes
Is the input voltage to the outdoor
electronic control P.C. board 370 V or
more?
Yes
Turn OFF power supply of indoor and
outdoor unit, and measure the compressor winding resistance between the
compressor terminals.
Is the resistance between each terminal
normal? (Refer to 11-4.)
Yes
No
No
Replace the power board.
<<Judgement>>
0 second
Compressor starts
1 second
Abnormal
(IPM failure)
(Compressor winding short)
2 seconds
Abnormal
(Compressor lock out)
(Starting defect)
No
Replace the compressor.
Reconnect the lead wire of compressor, and
turn ON power supply to indoor and outdoor
unit.
3 minutes later, starts EMERGENCY OPERATION.
10 seconds
Abnormal
(Poor contact,)
(Outdoor P.C. board defect)
(Disconnected connector)
Abnormal
(Refrigerant circuit defect)
(Closed valve)
Does the compressor run for 10
seconds or more after it starts?
No
Yes
After the compressor is heated with a
drier, does the compressor start? 1
Yes
No
Refer to <<Judgement>>.
Check the refrigerant
circuit.
Check the stop valve.
Refer to <<Judgement>>.
Replace the compressor.
Compressor start failure. Activate pre-heat
control.
(Refer to 10-2. "PRE-HEAT CONTROL
SETTING")
10 minutes
Normal
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
Heating part
40
B Check of open phase
MUZ-FD25/35
● With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 8-3.)
<<Measurement point>>
At 3 points
BLK (U)-WHT (V)
Measure AC voltage between the lead wires at 3 points.
BLK (U)-RED (W)
WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board flashes 9 times. (Refer to 11-6.1.)
C Check of compressor
MUZ-FD25/35
Refer to 11-5. “Check of compressor
winding”.
Is the compressor normal?
Yes
Refer to 11-5. “Check of compressor
operation time”.
Does the compressor operate continuously?
Yes
No
No
Replace the compressor.
Refer to 11-5.
OK.
41
“Check of compressor start failure”.
D Check of compressor winding
MUZ-FD25/35
● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
Measure the resistance between the lead wires at 3 points.
BLK-RED
WHT-RED
<<Judgement>>
Refer to 11-4.
0 [Ω] ················Abnormal [short]
Infinite [Ω] ·······Abnormal [open]
NOTE: Be sure to zero the ohmmeter before measurement.
<<Judgement>>
E Check of compressor operation time
MUZ-FD25/35
● Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(TEST RUN OPERATION: Refer to 8-3.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
0 second
Compressor starts
1 second
Abnormal
(IPM failure)
(Compressor winding short)
2 seconds
Abnormal
(Compressor lock out)
(Starting defect)
10 seconds
Abnormal
(Poor contact)
(Outdoor P.C. board defect)
(Disconnected connector)
Abnormal
(Refrigerant circuit defect)
(Closed valve)
10 minutes
Normal
F Check of compressor start failure
MUZ-FD25/35
Confirm that ~ is normal.
•Electrical circuit check
. Contact of the compressor connector (Including CN61)
. Output voltage of inverter P.C. board and balance of them (See 11-5. )
. Direct current voltage between DB61(+) and (-) on the inverter P.C. board
. Voltage between outdoor terminal block S1-S2
Does the compressor run for 10 seconds or
more after it starts?
Yes
Check the refrigerant circuit.
Check the stop valve.
No
After the compressor is heated with a drier,
does the compressor start? 1
No
Replace the compressor.
Yes
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
Compressor start failure. Activate pre-heat control.
(Refer to 10-2. "PRE-HEAT CONTROL SETTING")
Heating part
42
G Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see
below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal?
(Refer to 11-6.1. or 11-6.2.)
Yes
No
Replace the thermistor except RT64.
When RT64 is abnormal, replace the inverter P.C.
board or the outdoor power board.
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
Yes
No
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
OK.
(Cause is poor contact.)
MUZ-FD25/35
Thermistor
Symbol
Connector, Pin No.
Defrost
RT61 Between CN641 pin1 and pin2
Discharge temperature
RT62 Between CN641 pin3 and pin4
Fin temperature
RT64 Between CN642 pin1 and pin2
Ambient temperature
RT65 Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Board
Inverter P.C. board
MUZ-FD50
Thermistor
Symbol
Connector, Pin No.
Defrost
RT61 Between CN661 pin 1 and pin 2
Discharge temperature
RT62 Between CN661 pin 3 and pin 4
Outdoor heat exchanger temperature RT68 Between CN661 pin 7 and pin 8
Ambient temperature
RT65 Between CN663 pin 1 and pin 2
Fin temperature
RT64 Between CN3 pin 1 and pin 2
Board
Outdoor electronic control P.C. board
Outdoor power board
H Check of R.V. coil
MUZ-FD25/35
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4.
In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Replace the inverter
P.C. board.
Yes
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Replace the 4-way valve.
43
Replace the inverter
Yes P.C. board.
MUZ-FD50
• Heating operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 230 VAC between pin1 and
pin 2 at connector CN912?
Yes
No
Turn OFF power supply of indoor and outdoor unit.
Disconnect the connector CN912 in noise filter
P.C. board. Is there normal
resistance to R.V. coil?
No
Replace the R.V. coil.
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C.
board.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in HEAT mode.
Is there voltage 12 VDC between the connector CN781
pin 5 (+) and pin 3 (-)?
No
Replace the outdoor
electronic control P.C.
board.
Yes
Yes
Replace the noise filter P.C. board.
Replace the 4-way valve.
• Cooling operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 230 VAC between pin1 and
pin 2 at connector CN912?
No
If the connector CN912 is disconnected or
R.V. coil is open, voltage occurs between
terminals even when the control is OFF.
Replace the 4-way valve.
1. Turn OFF power supply of indoor and outdoor unit, and
disconnect the connector CN781 in the outdoor electronic
control P.C. board.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in COOL mode.
Is there voltage 12 VDC between the connector
CN781 pin 5 (+) and pin 3 (-)?
No
Replace the noise filter P.C. board.
Yes
Replace the outdoor electronic control P.C. board.
44
I Check of outdoor fan motor
MUZ-FD25/35
Disconnect CN932 from the inverter P.C. board,
and measure the resistance of the outdoor fan
motor.
Is the resistance of outdoor fan motor normal?
(Refer to 11-4.)
Yes
No
Replace the outdoor fan motor.
Replace the inverter P.C. board.
MUZ-FD50
Disconnect CN932 from the outdoor electronic control
P.C. board, and measure the resistance of the outdoor
fan motor.
Is the resistance of outdoor fan motor
Yes
normal? (Refer to 11-4.)
No
Turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
No
No
Does the voltage between each terminal become 5 and 0
VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
Yes
Replace the outdoor fan motor.
Replace the outdoor electronic control P.C. board.
45
J Check of power supply
MUZ-FD25/35
Disconnect the connector (CN61)
between compressor and intelligent
power module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does POWER lamp on the indoor
unit light up?
Yes
Is there voltage 260 - 300 VDC
between DB61 (+) and DB61 (–) on
the inverter P.C. board?
(Refer to 11-6.1.)
No
Rectify indoor/outdoor
connecting wire.
No
Yes
Check the electric parts in main circuit.
Yes
Is there voltage 230 VAC
between the indoor terminal
block S1 and S2?
Does LED on the inverter P.C.
board light up or flash? (Refer
to 11-6.1.)
Yes
If light up, OK.
If flash, refer to 11-3.
No
No
Replace the indoor
electronic control P.C.
board.
Replace the inverter
P.C. board.
260 - 300 VDC
DB61
Inverter P.C. board
(Solder side)
MUZ-FD50
Check the connecting of parts of main power
supply circuit.
Turn ON power supply.
Is there voltage of 230 VAC in the power supNo
ply terminal block?
Yes
Is the output voltage from the noise filter P.C.
board 230 VAC?
Yes
No
Check the power supply cable.
Is fuse (F64) blown?
Yes
Replace the fuse.
Is the input voltage to the power board 230
VAC?
Yes
No
Replace the reactor.
Is the input voltage to the outdoor electronic
control P.C. board 325 VDC?
Yes
No
Replace the power board.
Replace the outdoor electronic control P.C. board.
46
No
Replace the noise filter
P.C. board.
K Check of LEV (Expansion valve)
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TOO COOL button on the remote controller at
the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Confirm that the indicators on the LCD screen
shown in the right figure are all displayed.
Then release the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
on touching it ?
No
Is LEV coil properly fixed to
the expansion valve?
No
Yes
Does the resistance of LEV
coil have the characteristics? Yes
(Refer to 11-4.)
No
Replace the LEV coil.
1. Regardless of normal or abnormal condition, a short beep
is emitted once the signal is received.
Yes
OK
Properly fix the LEV coil to the expansion valve.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board or
CN795 on the outdoor electronic control P.C.
board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 ~ 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Yes
Replace the expansion valve.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
47
No
Replace the inverter P.C.
board or the outdoor
electronic control P.C.
board.
L Check of inverter P.C. board
MUZ-FD25/35
Check the outdoor fan motor.
(Refer to 11-5. .)
Is the fuse (F901) blown on the inverter P.C. board?
Yes
No
Inverter P.C. board
(Solder side)
Check the connection of the connectors
(CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
CN932
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the inverter P.C. board.
Does the LED flash 10 times?
Yes
(10-time flash)
No
Check the corresponding parts
following LED indication.
(Refer to 11-3.)
Replace the inverter P.C. board.
48
M How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage in the
power supply?
Yes
Check the power supply.
No
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does AREA-L lamp light up? <Confirmation of
the power to the indoor unit>
No
Yes
Is serial signal error indicated 6 minutes later?
Yes
Is there any miswiring, poor
contact, or wire disconnection
of the indoor/outdoor connecting wire?
No
Yes
Correct them.
No
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
B connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3. 1
1. Miswiring may damage indoor electronic control P.C. board
during the operation.
Be sure to confirm the wiring is correct before the operation
starts.
3. Be sure to check this within 3 minutes after turning ON. After
3 minutes, LED blinks 6 times. Even when the inverter P.C.
board or the outdoor electronic control P.C. board is normal,
LED blinks 6 times after 3 minutes.
Turn ON the power supply.
Does the LED on the inverter P.C. board or
the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-secondON quick blinking"? 3
Yes
A
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
Is serial signal
error indicated 6
minutes later?
Yes
B
• Reinstall
either the unit
or the light
away from
each other.
• Attach a filter
No on remote
control receiving section
of the indoor
unit.
Turn OFF the power supply.
Remove the short-circuit between
outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 VDC
between outdoor terminal block S2 and
S3? <Confirmation of serial signal>
Yes
Is there rated voltage between
indoor terminal block S1 and S2?
<Confirmation of power voltage>
Yes
No
(Lighted
or not
lighted)
Is there any error of the indoor/outdoor connecting wire,
such as the damage of the wire,
Yes
intermediate connection, poor
contact to the terminal block?
No
No
No
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
2
2. Be careful of the residual voltage of smoothing
capacitor.
Is there any error of the indoor/outdoor connecting wire,
such as the damage of the wire,
Yes
intermediate connection, poor
contact to the terminal block?
No
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
49
Replace the indoor/
outdoor connecting
wire.
Replace the indoor/
outdoor connecting
wire.
N Electromagnetic noise enters into TV sets or radios
Is the unit earthed?
Yes
Is the distance between the antennas
and the indoor unit within 3 m, or is the
distance between the antennas and the
outdoor unit within 3 m?
No
Earth the unit.
No
Yes
Extend the distance between the antennas and
the indoor unit, and/or the antennas and the
outdoor unit.
Is the distance between the TV sets or
radios and the indoor unit within 1 m, or
is the distance between the TV sets or
radios and the outdoor unit within 3 m?
No
Yes
Extend the distance between the TV sets and/or
radios and the indoor unit, or the TV sets or
radios and the outdoor unit.
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in the antenna wiring?
No
Yes
Replace or repair the antenna.
Replace or repair the coaxial cable.
Yes
Extend the distance between the indoor/outdoor
connecting wire of the air conditioner and the wiring of the antennas.
Is the indoor/outdoor connecting wire
of the air conditioner and the wiring of
the antennas close?
No
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength
or the installation condition (combination of specific conditions such as antennas or wiring).
Check the following before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of :
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric field intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifier such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller
for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the
electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the
indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
50
O Check of defrost heater
MUZ-FD25VAH MUZ-FD35VAH
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-6.1.
2. Is the resistance of defrost heater normal? Refer to 11-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5°C or
below, and let the defrost thermistor continue to read -1°C or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
water etc...
Is there 230 VAC between CN722 and
the inverter P.C. board? Refer to 11-6.1.
on
Not the problem of the inverter P.C. board.
Yes
No
Replace the inverter P.C. board.
P Check of bus-bar voltage
MUZ-FD50
•Check the voltage of power supply.
•Confirm outdoor unit failure mode
recall function. (Refer to 11-2.2)
Confirm LED1 indication lamp on
the outdoor electronic control P.C.
board.
Blink 5 times
Replace the power board.
Blink 6 times
Replace the outdoor electronic control P.C. board.
Turn ON power supply. Start
operation.
Confirm LED1 indication lamp
on the outdoor electronic control P.C. board.
Blink 9 times
Lighting
Replace the outdoor electronic control P.C. board.
Turn ON power supply. Start
operation.
Lighting
Normal.
Lighting
Replace the outdoor electronic control P.C. board.
Confirm LED1 indication lamp
on the outdoor electronic control P.C. board.
Blink 9 times
Replace the power board.
Turn OFF power supply before removing P.C. board.
51
11-6. TEST POINT DIAGRAM AND VOLTAGE
1. Inverter P.C. board
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
C62
C63
Smoothing Smoothing
capacitor
capacitor
DB61
Bus-bar voltage
260 - 300 VDC
(-)
(+)
Back side of unit
CN722
C61
Heater
Smoothing F701 Fuse
capacitor T3.15AL250VAC connector
MUZ-FD•VAH
F801 Fuse
T3.15AL250VAC
230 VAC
CN721
R.V.coil
230 VAC
F901 Fuse
T3.15 AL250V
Output to
drive
compressor
(LDU,
LDV,
LDW)
100
CN641 Discharge
temperature thermistor
(RT62)
CN643
Ambient temperature
thermistor(RT65)
CN641
Defrost thermistor
(RT61)
CN644
Outdoor heat exchanger
temperature thermistor (RT68)
CN642
Fin temperature
thermistor (RT64)
Front side of unit
CN932
Output to drive outdoor
fan motor
230 VAC
CN724
LEV
connector
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
200
80
JK
Jumper wire
for pre-heat
control setting
Fin temperature thermistor(RT64)
160
Discharge temperature thermistor(RT62)
700
60
600
50
40
30
20
10
-10
0
10 20 30
Temperature( )
40
140
Resistance(k )
70
Resistance(k )
Resistance(k )
JS
Jumper wire
for changing
defrost setting
180
90
0
-20
LED
500
400
300
120
100
80
60
200
40
100
20
0
0
10
20
30
40
50
60
70
80
Temperature( )
52
90 100 110 120
0
0
10 20 30 40 50 60 70 80
Temperature( )
2. Outdoor electronic control P.C. board
Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
Fin temperature thermistor (RT64) Outdoor heat exchanger temperature thermistor (RT68)
200
500
400
140
120
100
80
60
300
40
200
20
0
100
10
20
30
40
50
60
70
80
90
70
60
50
40
30
0
20
10 20 30 40 50 60 70 80
Temperature (°C)
0
80
10
100 110 120
0
-20
10
20
30
40
CN781
12 VDC
GND (power board)
(–)Rush current relay
(–)R.V. coil
CN702
GND Signal reception
(From power board)
15V 5V DC pulse wave
15V
Ambient temperature
CN663
thermistor (RT65)
CN701
Signal transmission
(To power board)
5V DC pulse wave
Outdoor heat exchanger
temperature thermistor (RT68)
Defrost thermistor (RT61)
Discharge temperature
thermistor (RT62)
5V
GND CN931
5V DC
pulse wave
0
Temperature (°C)
(–)
(+)
(–)
(+)
(+)
(–)
CN932
20-90V AC
-10
(+)
To fan
motor
CN661
Temperature (°C)
LEV
Resistance (k )
600
90
160
Resistance (k )
Resistance (k )
700
0
100
180
Discharge temperature thermistor (RT62)
CN795
12V DC
pulse wave
MUZ-FD50VA
LED 1
LED 2
SW1
Bus-bar
voltage
CN801
325 - 370
VDC
Input
F801
FUSE
T3.15AL250V
CN601
230 VAC
Input
Serial signal
5 - 10 VDC
CN681
High pressure switch
53
3. Noise filter P.C. board
MUZ-FD50VA
CN901
To electronic
control P.C.
board
CN902
To power
board
CN903
To power
board
230 VAC
Input
CN912
R.V. coil
230 VAC
230 VAC
Output
CN61
230 VAC
Output
F64 FUSE
T2AL250V
NR64 VARISTOR
4. Outdoor power board
MUZ-FD50VA
Connect to the compressor
Voltage among phases: 5 to 180 V
Connect to the earth
325-370 VDC
Output
(Red)
(+) 1
CN2
Connect to the controller board
(+)1-5(–): Signal transmission
(To electronic control P.C. board)
5 VDC pulse wave
(+)2-5(–): Zero cross signal
3-4 : Not used
(+)6-5(–): 15 V
(+)7-5(–): 15 V
(–) 3
(White)
CN3
Fin temperature thermistor RT64
Signal reception (From
electronic control P.C. board)
5 VDC pulse wave
CN5
Primary current detection
(Connect to the noise filter)
54
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Locking lever
(2) The terminal with this connector has the
locking mechanism.
Slide the sleeve.
Pull the terminal while
pushing the locking
lever.
Hold the sleeve, and
pull out the terminal
slowly.
Connector
12-1. MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
Photo 1
(1) Remove the screw fixing the service panel.
(2) Pull down the service panel and remove it.
(3) Disconnect the power supply and indoor/outdoor connecting wire.
(4) Remove the screws fixing the top panel.
(5) Remove the top panel.
(6) Remove the screws fixing the cabinet.
(7) Remove the cabinet.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
Screws of the
top panel
Screws of
the top panel
Back
panel
Photo 2
Screws of
the cabinet
Service
panel
Screw of the
cabinet
Screw of the
service panel
Direction to
remove
Screws of
the cabinet
55
Hooks
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN722 (Defrost heater)
CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the relay panel.
(5) Remove the inverter assembly.
(6) Remove the screw of the earth wire and screw of the
T.B.support.
(7) Remove the relay panel from the inverter assembly.
(8) Remove the inverter P.C. board from the relay panel.
Photo 3
Screws of the
relay panel
Photo 4 (Inverter assembly)
Inverter
P.C. board
Heat sink
3. Removing R.V. coil
Screw of the
T.B.support
T.B.support
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Relay panel
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
Photo 5
Screw of the
earth wire
R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(Photo 5)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
56
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
Photo 6
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN932 (Fan motor)
(3) Remove the propeller nut.
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
Outdoor heat
exchanger temperature thermistor
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm2 (0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the brazed part of pipes connected with 4-way valve.
Defrost thermistor
Photo 7
Propeller
Screws of the outdoor fan motor
Propeller nut
Photo 8
Brazed parts of 4-way valve
57
12-2. MUZ-FD50VA
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
Photo 1
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Remove the screws of the service panel.
Remove the screws of the top panel.
Remove the screw of the valve cover.
Remove the service panel.
Remove the top panel.
Remove the valve cover.
Disconnect the power supply and indoor/outdoor connecting wire.
(8) Remove the screws of the cabinet.
(9) Remove the cabinet.
(10) Remove the screws of the back panel.
(11) Remove the back panel.
Screw of the top panel
Screws of the cabinet
Screws
of the
back
panel
Screws
of the
cabinet
Photo 2
Screw of the top panel
Screws
of the
cabinet
Screw
of the
service
panel
Screw
of the
valve
cover
58
Screws of
the back
panel
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, outdoor electric
control P.C. board, power board, noise filter P.C.
board and reactor.
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Remove the back panel. (Refer to 1.)
(3) Disconnect the following connectors:
<Electronic control P.C. board>
CN931 and CN932 (Fan motor)
CN795 (LEV)
CN661 (Discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor)
CN663 (Ambient temperature thermistor)
<Noise filter P.C. board>
CN912 (R.V. coil)
(4) Remove the compressor connector.
(5) Remove the screws fixing the relay panel.
(6) Remove the inverter assembly.
(7) Disconnect all connectors and lead wires on the electronic
control P.C. board.
(8) Remove the outdoor electronic control P.C. board from the
inverter assembly.
(9) Disconnect the reactor lead wire.
(10) Remove the screws of the reactor, and remove the reactor.
(11) Remove the screws fixing the power board assembly.
(12) Disconnect all connectors and lead wires on the power
board.
(13) Remove the power board from the inverter assembly.
(14) Disconnect all connectors and lead wires on the noise filter
P.C. board.
(15) Remove the noise filter P.C. board from the inverter assembly.
Photo 3 (Inverter assembly)
Screws of the power board assembly
Screws of the relay panel
Photo 4
Screws of the reactor
59
OPERATING PROCEDURE
PHOTOS
3. Removing the defrost thermistor, discharge temperature thermistor, outdoor heat exchanger temperature
thermistor and ambient temperature thermistor
Photo 5
Outdoor heat
exchanger temperature thermistor
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Remove the back panel. (Refer to 1.)
(3) Disconnect the following connectors:
<Electronic control P.C. board>
CN661 (Discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor)
CN663 (Ambient temperature thermistor)
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the discharge temperature thermistor from its holder. (Photo 7)
(6) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(7) Pull out the ambient temperature thermistor from its holder.
Ambient temperature
thermistor
Defrost thermistor
Photo 6
4. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Disconnect the following connectors:
<Electronic control P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller.
(4) Remove the screws fixing the fan motor.
(5) Remove the fan motor.
Screws
of the
outdoor
fan motor
60
OPERATING PROCEDURE
PHOTOS
5. Removing the compressor and 4-way valve
Photo 7
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 MPa.
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed part of 4-way valve and pipe.
Brazed part of the
discharge pipe
Discharge temperature
thermistor
Brazed part of the
suction pipe
Photo 8
6. Removing R.V. coil
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Remove the back panel. (Refer to 1.)
(3) Disconnect the following connectors:
<Noise filter P.C. board>
CN912 (R.V. coil)
(4) Remove the R.V. coil.
R.V. coil
Brazed parts of 4-way valve
61
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2007 MITSUBISHI ELECTRIC CO.,LTD
Distributed in Jul. 2011. No. OBH489 REVISED EDITION-C
Distributed in Nov. 2008. No. OBH489 REVISED EDITION-B 5
Distributed in Oct. 2007. No. OBH489 REVISED EDITION-A 6
Distributed in Aug. 2007. No. OBH489 6
Made in Japan
New publication, effective Jul. 2011
Specifications subject to change without notice.
Download PDF