BKI | 16/C | Thermocont TT

TT-, TV-, TW-, TB-, TL-, TRTEMPERATURE TRANSMITTERS
INSTALLATION AND PROGRAMMING MANUAL
1. Edition
0408
Manufacturer:
NIVELCO Process Control Co.
H-1043 Budapest, Dugonics u. 11.
Phone: -369-7575 ♦ Fax: -369-8585
e-mail:sales@nivelco.com ♦ www.nivelco.com
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc♦ 1 / 16
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 2 / 16
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 3 / 16
CONTENTS
1. INTRODUCTION ................................................................................................................................................................................................. 5
2. ORDER CODES.................................................................................................................................................................................................. 5
3. TECHNICAL DATA............................................................................................................................................................................................. 6
3.1 GENERAL DATA............................................................................................................................................................................................. 6
3.2 ADDITIONAL DATA FOR EX APPROVED VERSIONS ........................................................................................................................................... 7
3.3 DIMENSIONS ................................................................................................................................................................................................. 8
3.4 ACCESSORIES............................................................................................................................................................................................... 9
4. INSTALLATION AND ELECTRIC CONNECTION ............................................................................................................................................. 9
4.1 WIRING....................................................................................................................................................................................................... 10
4.2 SAFETY REGULATIONS FOR THE EX APPROVED UNITS .................................................................................................................................... 10
5. PUTTING INTO OPERATION, PROGRAMMING............................................................................................................................................. 11
5.1 PROGRAMMING ........................................................................................................................................................................................... 11
5.1.1 Display and keys of the SAP 202 display module ......................................................................................................................... 12
5.1.2 Steps of programming ................................................................................................................................................................... 13
5.1.3 Parameters – descriptions and programming................................................................................................................................ 14
5.2 ERROR CODES ............................................................................................................................................................................................ 16
5.3 HART COMMUNICATION .............................................................................................................................................................................. 16
6. MAINTENANCE AND REPAIR......................................................................................................................................................................... 16
7. STORAGE......................................................................................................................................................................................................... 16
8. WARRANTY...................................................................................................................................................................................................... 16
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 4 / 16
Thank you for choosing NIVELCO instrument
We are sure that you will be satisfied throughout its use!
1. INTRODUCTION
THERMOCONT T-500/600 series 2-wire temperature transmitters are suitable for measuring, indicating and transmitting temperature of ordinary and hazardous
gases, fumes, liquids and masses. The Pt100 sensor of the unit is accommodated in normal or plastic coated stainless steel tube manufactured with different
intrusion length end process connection. Intelligent electronics and HART communication provides application possibilities for the most different tasks.
2. ORDER CODES
THERMOCONT T
TYPE
Transmitter up to 200 °C
Transmitter up to 600 °C
Transmitter up to 200 °C
with plastic coated probe
Tx + display up to 200 °C
Tx + display up to 600 °C
Tx + display up to 200 °C
with plastic coated probe
–
–
CODE
PROCESS CONNECTION
CODE
HOUSING
CODE
SENSOR
CODE
T
V
Wall mount
½” BSP
3/ ” BSP
4
½” NPT
M 20 x 1,5
1” Triclamp
1½” Triclamp
2” Triclamp
DN 25 pipe coupling
DN 40 pipe coupling
DN 50 pipe coupling
DN 50, St. St. flange
+ PTFE
2” ANSI St. St. flange
+ PTFE
1” NPT reinforced casing
W
C
D
H
J
L
K
N
O
P
R
Aluminium
Plastic
5
6
Without
Class A
Class B
0
1
2
W
B
L
R
INTRUSION
60 mm
160 mm
250 mm
400 mm
500 mm
1000 mm
1500 mm
2000 mm
2500 mm
3000 mm
CODE
0
1
2
3
4
5
6
7
8
9
OUTPUT / EX
4 … 20 mA
4 … 20 mA / HART
4 … 20 mA / EEx ia
4 … 20 mA / HART / EEx ia
4 … 20 mA / EEx d
4 … 20 mA / HART / EEx d
4 … 20 mA / EEx d ia
4 … 20 mA / HART / EEx d ia
CODE
2
4
6
8
A
B
C
D
F
A
S
Not all combinations possible!
Ex certified units should have aluminium housing and Ex tag in the order code
Requirement for housing position „B”; „C”; „D” i.e. other than„A; should be specified with the order (See 3.3 Dimensions)
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 5 / 16
3. TECHNICAL DATA
3.1 GENERAL DATA
TYPE
Range
Probe
Maximum pressure **
Output
Output
current
Display
Accuracy
Display
Mode
Resolution
Pt 100 Class A
TR…-………-…
TW…-………-…
TV…-………-…
TL…-………-…
T…W-………-…
-50 °C...+200 °
-50 °C...+600°C
Pt 100 sensor in PFA coated St. St. (DIN 1.4571) tube
Pt 100 sensor in St. St. (DIN 1.4571) tube
2.5 MPa (25 bar) in +20 °C ; 1.6 MPa (16 bar) in +400 °C
4…20 mA / HART
4 … 20 mA limits of the output signal: 3.9 … 20.5 mA
minimum loop resistance with HART R tmin = 250 ohm
6 digit LCD, symbols, engineering units, bargraph
0.1 °C (0.1 °F)
0.4 °C (0.4 °F)
± (0.3+ |0.0025 t | ) °C
± (1.5+ |0.004 t | ) °C
± (0.4+ |0.0055 t | ) °C
Pt 100 Class B
Temp. coefficient
Pt 100 Class A
Pt 100 Class B
Temp. coefficient
Error indicaton
Power supply
Output load
Ambient temperature
Electric protection
Ingress protection
Process connection and intrusion **
Electric connection
Housing
Wetted parts **
with plastic housing
Mass
with aluminium housing
TT…-………-…
TB…-………-…
± (1.5+ |0.006 t | ) °C
± 0,02°C / °C
± (0.2+ |0.0025 t | ) °C
± (1.5+ |0.004 t | ) °C
± (0.35+ |0.0055 t | ) °C
± (1.5+ |0.006 t | ) °C
± 0.002 °C / °C
By current output 3.8 mA or 22 mA
10V…36V DC
RL = (Us – 10 V) / 0.022 A, Us = supply voltage
- 40 °C …+70 °C
with display – 25 °C …+70 °C
Class III
IP 65
According to order code
Through plastic cable gland: M 20 x1,5 using shielded two-wire cable with diameter: ∅ 6 …12 mm and cross section: 0,25 … 1,5 mm2
Powder paint coated, cast aluminium (öAlSi12) or fibre-glass reinforced plastic
Powder paint coated cast aluminium (öAlSi12)
PFA, PTFE
Stainless steel: DIN 1.4571
ca. 0.5 kg + probe 0.5 kg/m type T…W … ca. 0.9 kg
ca. 0.9 kg + probe 0.5 kg/m type T…W … ca. 0.5 kg
* t = reading temperature
** No data for type T…W …
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 6 / 16
3.2 ADDITIONAL DATA FOR EX APPROVED VERSIONS
Type
Protection mode
Protection mark
T…… – 5…… – 6Ex
T…… – 5…… – 8Ex
T…… – 5……-AEx
T…… – 5……-BEx
T…… – 5……-CEx
T…… – 5……-DEx
Intrinsically safe
Flame proof casing
Flame proof casing and intrinsically safe
II 1 G EEx ia IIB T6...T1 +600°C
II 2 G EEx d IIB T6...T1 +600°C
Umax = 30 V
Imax = 140 mA
Pmax = 1,0 W
Ci < 20 nF Li < 200 µH
Ex approved power supply data
Cable gland
Ambient temperature
II 1/2 G EEx d ia IIB T6...T1 +600°C
Umax = 30 V
Imax = 140 mA
Pmax = 1,0 W
Ci < 20 nF Li < 200 µH
–
Metal M 20 x1,5 cable diameter 6…12 mm
Metal M 20 x1,5 cable diameter: 9 … 11 mm
– 40 °C…+70 °C
with display – 25 °C…+70 °C
– 40 °C…+70 °C
with display – 20 °C…+70 °C
Housing
Paint coated aluminium
Maximum temperatures allowed for the Ex approved units
Temperature
class
T6
T ambient
60°C
T medium
80° C
T5
T4
T3
95°C
130°C
195°C
T2
T1
295°C
440°C
70°C
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 7 / 16
3.3 DIMENSIONS
EXPLOSION
~89
~89
INSTRINSICALLY SAFE
273
273
~97
TR… – ……… – …
TW… – ……… – …
TT… – ……… – …
TB… – ……… – …
TV… – ……… – …
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 8 / 16
TL… – ……… – …
~97
Ø20
Intrusion length
max 5000 mm
Intrusion length
Intrusion length
Ø20
FLAME PROOF CASING
T…… – 5…… – 6Ex
T…… – 5…… – 8Ex
max 5000 mm
-50 °C… +600 °C
Intrusion length
-50 °C… +200 °C
PROOF TYPES
~306
TYPES
~303
ORDINARY
T…… – 5…… – AEx
T…… – 5…… – BEx
T…… – 5…… – CEx
T…… – 5…… – DEx
HOUSING POSITIONS
"B"
120
108
~ 137
120
108
"C"
"D"
Requirement for housing position other than„A; should be specified with the order
Without sensor
T…W – …00 – …
~ 163
"A"
VERSION FOR WALL MOUNTING
With sensor
T…W – ……0 – …
3.4 ACCESSORIES
•
•
•
•
Installation and Programming Manual
Warranty Certificate,
Manufacturer’s Declaration,
2 cable glands
4. INSTALLATION AND ELECTRIC CONNECTION
•
•
•
Place of installation should be selected so that proper place should be available for handling.
Housing of the units with flange or threaded connection can be rotated. After installing the unit housing can be turned to reach best position for reading display.
Device should be fastened with two nuts of M4.
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 9 / 16
4.1 WIRING
•
•
•
•
•
•
•
•
Transmitters are used in 2-wire systems with power supply of 10 … 36 V
DC. Resistance of the units in the loop depends on the voltage of the
power supply.
For wiring shielded cable suggested in the Technical Data should be used.
After removal of the housing cover and taking out the display module (if
any), the screw terminals can be accessed. Cover of the flame proof
housing can be removed after unhooking the clamp.
The unit should be grounded by the inner or outer grounding screw.
Loop should be connected to terminal 3 (+) and 4 (-). Other terminals are
for internal connection of the Pt sensor.
The Pt100 sensor for types T…W-………-… should be wired as shown on
drawing at the right.
Switch on the unit and make necessary programming.
After wiring and programming ensure proper sealing and closing of the
cover (and fastening of the clamp with the flame proof models).
!
6 5 4 3 2 1
–
+
6 5 4 3 2 1
Ex
Ex
The screening is
to be grounded at
one point only
–
+
Mains
Pt 100
The Pt100 sensor for types
T…W-…00-… should be wired
as shown on drawing
The unit may be damaged by electrostatic discharge (EDS) via its terminal, thus apply the precautions commonly used to avoid electrostatic
discharge e.g. by touching a properly grounded point before removing the cover of the enclosure.
4.2 SAFETY REGULATIONS FOR THE EX APPROVED UNITS
•
•
•
Intrinsically safe units should be powered by duty certified intrinsically safe [EEx ia IIB] or [EEx ia IIC] device with features as per technical data above.
Plastic coated probes may be charged electrostatically therefore such units should only be used for measurement of conductive medium and its specific
resistance must not exceed 104 Ωm, even under the most unfavourable conditions and at the most unfavourable place.
The Ex device should be grounded by its grounding screw.
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 10 / 16
5. PUTTING INTO OPERATION, PROGRAMMING
COM LED
Display unit
comnnector
Transmitter installed and wired correctly will operate after powering
according to the Manufacturer’s (Default) or to the last settings.
Operability is indicated by lighting of the LED VALID.
4 ... 20 mA loop current
and supply HART
I- I+
1/2” NPT
1/2” NPT
M 20 x 1,5
GND
M 20 x 1,5
Unit with removed cover and without SAP-202 display module
5.1 PROGRAMMING
Adjustment of the unit to the conditions of the application will be carried out by programming parameters with the aid of the push buttons and following the procedure
on the display of the SAP-202 module. Manufacturer’s setting is as below:
DEFAULT
− Current output: 4 mA assigned to –50°C and 20 ma assigned to +200°C (+600°C),
− Noise suppression: 50 Hz
− Error indication: Iout = 3,8 mA
The THERMOCONT is fully operational without the SAP-202 display module (incorporated in types TB†-†††, TL†-††† , and TR†-†††).
It is for programming and/or displaying measurement values.
The unit will measure during programming in accordance with the parameters set previously. The new, modified parameters will only be effective after
returning to the Measurement Mode
If the transmitter is left in Programming Mode by mistake, it will automatically return to Measurement Mode after 3 minutes and will operate with the parameters
entered during the last completed programming.
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 11 / 16
5.1.1 Display and keys of the SAP 202 display module
%
Programming
keys
%
Programming
keys
4...20mA
SAP-202
display
Symbols on the screen
•
– pointer (showing to the
relevant engineering unit)
•
°C – temperature grade Celsius
•
mA – current output (lighting)
•
%
– display in percentage
PROG (blinking) – indicating programming
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 12 / 16
Symbols on the frame
•
M
metric system
•
US
calculation system
•
°F
temp. in Fahrenheit
•
LED indication
•
COM indicating HART
communication
•
VALID indicating operability
5.1.2 Steps of programming
Programming will be performed by pressing and releasing the relevant one or two keys (simultaneously).
The following description is for overview only, detailed programming is to find in 5.1.3
For entering calibration value decimal point will
automatically turn up. Its position can not be changed.
yy :xxxx
y or yy
xxxx or xxxxx
parameter address (0, 1, …19)
parameter value (dcba) or
calibration/measurement value
bargraph
OPERATION OF PROGRAMMING KEYS
E
+
(for minimum 3 sec!) *
+
pressing Keys
E
+
+
/
X
sign –
0
1
2
X
0
:
9
X
0
:
9
X
0
:
9
X
0
:
9
OPERATION
Enter or exit programming mode (Return to the Measurement mode means saving modifications of parameter value)
GET VALUE – function for automatic setting. Actual/measured value will be accepted as value to be programmed.
SET will be displayed for confirmation
while Parameter address blinking
to select parameter address and go to parameter value
Cancel all modifications of the actual programming
procedure. CANCEL will be displayed for warning.
Reset all parameter values to the manufacturer’s setting.
(Default). LOAD will be displayed for warning
Move blinking (changeability) of the digit to the left
while Parameter value blinking
to save parameter value and return to parameter address
Neglect modification of the parameter value (if any) and return
to the parameter address CANCEL will be displayed
Reset to the factory value of the relevant parameter address.
LOAD will be displayed for warning
Modify the blinking digit (increase or decrease value, minus sign) or scroll up/down … 8, 9, “ –“ ,0, 1, 2, …
Notes:
Double key pressing is indicated by “+” * Make sure that E would be pressed first!
If after pressing E blinking does not spring over from the parameter address to the parameter value this means that
•
the parameter is either a read-out type, or
•
the secret code prevents the modification (see P19)
If the modification of the parameter value is not accepted i.e. the parameter value keeps blinking after pressing ENTER
•
the modified value is either out of the range, or
•
the code entered is not a valid one
E
,
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 13 / 16
5.1.3 Parameters – descriptions and programming
P0:
---a
Assignment of the (lowest) measured temperature to 4 mA
P1:
---a
Assignment of the (highest) measured temperature to 20 mA
The lowest and highest (limit) value of the temperature range is to be assigned to the 4 and 20 mA output current. This can be performed by two
methods
a: manually i.e. by entering the relevant values in P0 and P1 (Make sure that values to be programmed does not exceed the range of the unit in
question, the modification of the parameter value will not be accepted i.e. after pressing E the parameter value will remain blinking and refuse to
return to the address.)
The procedure to assign for instance +160°C to 4 mA in P0 is the following: press E +
to enter programming mode, go to P1 with E , enter 160
and press E to go back to the parameter address, finally press E + to exit programming/return to measurement mode).
b: automatically i.e. using the GET VALUE function at being in P0 and P1. For this method the probe should be in a medium with the required (zero
and high limit value) temperature. Successful setting will be indicated by the message SET displayed.
FACTORY DEFAULT: P0 -50°C
P1 +200°C or +600°C respectively
P7:
---a
Offset of characteristic
Displayed (and transmitted) temperature value can be diverted from that of measured by the sensor. This represents an offset of the characteristic so
that the displayed value will be throughout the whole range in line with a - for instance - control measurement, performed by a control thermometer.
Difference value should be entered here with its mathematical sign ( -) if it is minus.
FACTORY DEFAULT: 0
P9:
---a
Current generator test
In this parameter the actual current output (corresponding to the measured process value) will be displayed. Pressing E the blinking) current value
can be set for any value between 3,9 and 20.5 mA. The current output has to show the same value, which can be checked by an ampere meter.
P10: - - - a
Engineering unit
a
0
1
FACTORY DEFAULT: 0
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 14 / 16
Engineering unit
Celsius
Fahrenheit
P11: - c - -
Noise suppression and displayed value
c
0
1
Noise supression
50 Hz
60 Hz
d
0
1
Displayed value
Temperature (°C or F see P10)
%
FACTORY DEFAULT: 0 0
P12: - - - a
Error indication
Find explanation of errors in 5.2
a
0
1
Error indication
3.8 mA
22 mA
FACTORY DEFAULT: 0
P13: - - - -
HART short address
THERMOCONT involved in HART multidrop usage should be addressed here. Value of parameter is described in the Manual for the Eview software
supplied with the HART capable THERMOCONT.
P14: - - - -
Software version
The software number of your transmitter can be viewed in this parameter.
P19: - - - -
Secret code
Settings can be protected by a 4 digit number (secret code) other than 0 entered as value of this parameter. If the secret code is active the symbol
PROG is lighting and the value of the parameters can only be viewed. . If there is no secret code or it is not active the symbol PROG is blinking.
For opening secret code the old code should be entered. For modifying or deleting the secret code (modifying to 0000) the new code can only be
entered after opening old code. The procedure is as below: Go to P19 press E to select parameter address and go to parameter value, enter the old
code; press E to go to address and E again to return to value; enter new code or 0000.
FACTORY DEFAULT: 0000
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 15 / 16
5.2 ERROR CODES
In case of error the LED VALID will be blinking, and Errx message will be displayed indicating the following errors:
Error Code (x)
1
Error description
Sensor error or
exceeding default range by more than 10%
Memory error
Causes and solutions
Contact local agent
Modify programming
Contact local agent
3
Programming error: same value in P0 and P1
Modify programming
0
5.3 HART COMMUNICATION
HART capable transmitters would communicate with the Nivelco made MULTICONT interface according to the HART standard. MULTICONT provides for the
powering and makes possible remote programming of the transmitters while (transmitter parameter values and) measurement data can be forwarded from the
MULTICONT on RS485 line.
6. MAINTENANCE AND REPAIR
The unit does not require regular maintenance. In case of need the diaphragm might be carefully cleaned. All repairs will be carried out in the premises of the
Manufacturer only.
7. STORAGE
Ambient temperature:
Relative humidity:
-25 °C ...+60 °C
max. 98 %
8. WARRANTY
Nivelco undertakes warranty of 2 (two) years in compliance with details described on the Warranty Certificate.
tbj5242a0600p_01.doc
2004. November 19.
Technical specification may be changed without notice.
BKI 04 ATEX 113X♦ tbj5242a0600p_01.doc ♦ 16 / 16