Carrier | 59SC2A | Product Data - Royal Mechanical LLC

59SC2A
Comfort™ Series Single---Stage
4---Way Multipoise
Condensing Gas Furnace
Series 100
Product Data
A11263
The 59SC2 Multipoise Comfort Series Condensing Gas Furnace
features energy efficiency of 92.1% AFUE gas efficiency and
workhorse PSC blower motor. This gas furnace also features
4--way multipoise installation flexibility, and is available in eight
model sizes. The 59SC2 can be vented for direct vent/two--pipe,
ventilated combustion air, or single--pipe applications. All units
meet California Air Quality Management District emission
requirements, are design certified in Canada, and are certified for
mobile/manufactured home use.
STANDARD FEATURES
S 4--Way multipoise design for upflow, downflow or horizontal
installation.
S Installation flexibility with a 360--degree rotating elbow.
S More than twelve different venting options, including optional
through--the cabinet downflow and horizontal venting.
S Ideal condensing furnace height 35” cabinet: short enough for
taller coils, but still allows enough room for service.
S Silicon Nitride Power Heatt Hot Surface Igniter.
S Aluminized--steel primary heat exchanger.
S Stainless steel condensing secondary heat exchanger.
S High--quality corrosion--resistant prepainted steel cabinet with
hemmed edges for safety.
S Factory--configured ready for upflow applications.
S Direct--vent/sealed combustion, single--pipe venting or
ventilated combustion air.
S PSC blower motor, single--speed inducer motor, and
single--stage gas valve.
S Self--diagnostics with SuperBrite LED.
S Approved for Twinning applications (60--14 through 120--20
sizes, only)
S Propane convertible (see accessory list).
S Approved for Manufactured Housing/Mobile Home applications
with MH accessory kit.
S Convenient Air Purifier and Humidifier connections.
S Residential installations may be eligible for consumer financing
through the Retail Credit program.
S Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. water column with all
present air inlets, air outlets, and condensate drain port(s) sealed.
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
1
CERTIFIED
CASING
DIMENSIONS (IN.)
RATED HEATING
OUTPUT†
HEATING AIRFLOW
SAP ORDERING NO.
59SC2A040S14--10
59SC2A060S14--10
59SC2A060S17--14
59SC2A080S17--16
59SC2A080S21--20
59SC2A100S21--14
59SC2A100S21--20
59SC2A120S24--20
H
D
W
(BTUH)
AFUE
CFM‡
Heating
ESP
(in. WC)
35
35
35
35
35
35
35
35
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
14.2
14.2
17.5
17.5
21.0
21.0
21.0
24.5
39,000
58,000
58,000
78,000
78,000
97,000
97,000
117,000
92.1%
92.1%
92.1%
92.1%
92.1%
92.1%
92.1%
92.1%
820
840
980
1040
1695
1510
1680
2245
0.10
0.12
0.12
0.15
0.15
0.20
0.20
0.20
COOLING CFM
@ 0.5 ESP
(in. WC)
MOTOR HP-SPEED
APPROX SHIP
WEIGHT (LB)
625-905
675-1130
650-1420
810-1600
1335-1970
915-1545
1345-2065
1320-2105
1/2 - 4
1/2 - 4
1/2 - 5
3/4 - 5
3/4 - 5
1/2 - 4
3/4 - 5
3/4 - 5
123
127
144
154
162
169
169
186
† Capacity in accordance with DOE test procedures. Ratings are position dependent. See rating plate.
‡ Heating CFM at factory default blower motor heating tap settings.
ESP --- External Static Pressure
59SC2A
FEATURES AND BENEFITS
HYBRID HEATR Dual Fuel System — This system can provide
more control over your monthly energy bills by automatically
selecting the most economical method of heating. With HYBRID
HEAT components, our system automatically switches between the
gas furnace and the single--stage electric heat pump as outside
temperatures change to maintain greater efficiency and comfort
than with any traditional single-source heating system. The heat
pump also delivers high-efficiency cooling in the summer.
Power Heatt Igniter — Carrier’s unique SiN igniter is not only
physically robust but it is also electrically robust. It is capable of
running at line voltage and does not require complex voltage
regulators as do other brands. This unique feature further enhances
the gas furnace reliability and continues Carrier’s tradition of
technology leadership and innovation in providing a reliable and
durable product.
Reliable Heat Exchanger Design — The aluminized steel, clam
shell primary heat exchanger was re--engineered to achieve greater
efficiency out of a smaller size. The first two passes of the heat
exchanger are based on the current 80% product, a design with
more than ten years of field-proven performance and success.
These innovations, paired with the continuation of a crimped,
no-weld seam create an efficient, robust design for this essential
component.
The condensing heat exchanger, a stainless steel fin and tube
design, is positioned in the furnace to extract additional heat.
Stainless steel coupling box componentry between heat exchangers
has exceptional corrosion resistance in both natural gas and
propane applications.
4-Way Multipoise Design — One model for all applications –
there is no need to stock special downflow or horizontal models
when one unit will do it all. The new heat exchanger design allows
these units to achieve the certified AFUE in all positions.
Direct or Single-pipe Venting, or Optional Ventilated
Combustion Air — This furnace can be installed as a 2-pipe
(Direct Vent) furnace, in an optional ventilated combustion air
application, or in single-pipe, non-direct vent applications. This
provides added flexibility to meet diverse installation needs.
Sealed Combustion System — This furnace brings in combustion
air from outside the furnace, which results in especially quiet
operation. By sealing the entire combustion vestibule, the entire
furnace can be made quieter, not just the sound of the burners.
Monoport Burners — The burners are specially designed and
finely tuned for smooth, quiet combustion and economical
operation.
Bottom Closure — Factory-installed for side return; easily
removable for bottom return. The multi-use bottom closure can
also serve for roll-out protection in horizontal applications, and act
as the bottom closure for the optional return air base accessory.
Blower Access Panel Switch — Automatically shuts off 115-v
power to furnace whenever blower access panel is opened.
Quality Registration — Our furnaces are engineered and
manufactured under an ISO 9001 registered quality system.
Certifications — This furnace is CSA (AGA and CGA) design
certified for use with natural and propane gases. The furnace is
factory--shipped for use with natural gas. A CSA listed gas
conversion kit is required to convert furnace for use with propane
gas. The efficiency is AHRI efficiency rating certified. This furnace
meets California Air Quality Management District emission
requirements.
2
SPECIFICATIONS
Airflow Capacity and Blower Data
Certified External Static
Pressure (in. w.c.)
Airflow Delivery
@ Rated ESP (CFM)
040-10 060-10 060-14 080-16 080-20 100-14 100-20
40,000
60,000
60,000
80,000
80,000 100,000 100,000
39,000
58,000
58,000
78,000
78,000
97,000
97,000
92.1
92.1
92.1
92.1
92.1
92.1
92.1
40 - 70 40 - 70 40 - 70 40 - 70 40 - 70 40 - 70 40 - 70
High Heat
(22 - 39) (22 - 39) (22 - 39) (22 - 39) (22 - 39) (22 - 39) (22 - 39)
(BTUH)
(BTUH)
AFUE % (ICS)
040-10
0.10
0.5
820
905
2
2.5
060-10
0.12
0.5
840
1130
2.5
3
0.5
6.2
0.5
6.2
4
11 x 7
4
11 x 7
Electrical Data
040-10
Input Voltage
Volts-Hertz-Phase
Operating Voltage Range
Min-Max
Maximum Input Amps
Amps
6.8
Unit Ampacity
Amps
9.5
Minimum Wire Size
AWG
14
Feet
39
Maximum Wire Length
@ Minimum Wire Size
(M) (11.9)
Maximum Fuse/Ckt Bkr
Amps
15
(Time-Delay Type Recommended)
Transformer Capacity (24vac output)
Heating
External Control Power Available
Cooling
060-10
060-14
7.0
9.7
14
38
(11.6)
8.4
11.5
14
32
(9.8)
15
15
Controls
040-10
Gas Connection Size
Burners (Monoport)
2
Gas Valve (Redundant)
Manufacturer
Minimum Inlet Gas pressure (in. wc)
Maximum Inlet Gas pressure (in. wc)
Gas Conversion Kit - Natural to Propane
Gas Conversion Kit - Propane to Natural
Manufactured (Mobile) Home Kit
Ignition Device
Limit Control
165
Heating Blower Control (Heating Off-Delay)
Cooling Blower Control (Time Delay Relay)
Communication System
Thermostat Connections
Accessory Connections
060-10
Cooling Capacity (tons)
Heating
Cooling
High Heat
Cooling
400 CFM/ton
350 CFM/ton
Direct-Drive Motor Type
Direct-Drive Motor HP
Motor Full Load Amps
RPM Range
Speed Selections
Blower Wheel Dia x Width
Air Filtration System
Filter Used for Certified Watt Data*
in.
060-14 080-16 080-20 100-14
0.12
0.15
0.15
0.20
0.5
0.5
0.5
0.5
980
1040
1695
1510
1420
1600
1970
1545
3.5
4
5
4
4
4.5
5.5
4.5
Permanent Split Capacitor (PSC)
0.5
0.75
0.75
0.5
6.8
7.9
13.8
6.5
500 - 1150
5
5
5
4
11 x 8
11 x 8
11 x 10 11 x 10
Field Supplied
KGAWF**06UFR
080-16
080-20
115-60-1
104-127
9.6
14.5
13.0
19.1
14
12
28
30
(8.5)
(9.1)
15
20
120-20
120,000
117,000
92.1
40 - 70
(22 - 39)
100-20
0.20
0.5
1680
2065
5
6
120-20
0.20
0.5
2245
2105
5
6
0.75
13.8
0.75
14.1
5
11 x 10
5
11 x 11
100-14
100-20
120-20
7.6
10.4
14
35
(10.7)
14.6
19.2
12
29
(8.8)
14.9
19.6
12
29
(8.8)
15
20
20
40 VA
27.9 VA
34.6 VA
060-14
080-16 080-20 100-14 100-20
1/2" - NPT
3
4
4
5
5
White Rogers
4.5
13.6
KGANP50011SP
KGAPN42011SP
KGAMH0601KIT
Silicon Nitride
180
170
200
180
180
Adjustable: 90, 120, 150, 180 seconds
90 seconds
none
Com 24V, R, W, G, Y
EAC (115vac); HUM (24vac)
3
165
* See Accessory List for part numbers available.
3
120-20
6
160
59SC2A
Heating Capacity and Efficiency
Input
High Heat
Output
High Heat
Efficiency
Certified Temperature
Rise Range ºF (ºC)
MODEL NUMBER NOMENCLATURE
Example of Model Number
1-2
Family
59
3
Htg. Stages
T
4
Tier
N
5
Base Effy.
6
6
Major Series
A
7-9
Htg. Cap.
11 - 12
Width
17
10
Motor
V
060
13
Voltage
--
14
Minor Series
--
08 - 800 CFM
10 - 1000 CFM
12 - 1200 CFM
14 - 1400 CFM
16 - 1600 CFM
18 - 1800 CFM
20 - 2000 CFM
22 - 2200 CFM
Family
S - Single Stage
T - Two Stage
M - Modulating
C - Comfort
P - Performance
N - Infinity
0 - +90 AFUE
2 - +92 AFUE
3 - +93 AFUE
5 - +95 AFUE
6 - +96 AFUE
7 - +97 AFUE
14 - 14.2”
17 - 17.5”
21 - 21.0”
24 - 24.5”
Major Series
15 - 16
Airflow
14
Minor Series
Voltage
040=40,000 BTU
060=60,000 BTU S - Standard
080=80,000 BTU E - Energy Efficient
100=100,000 BTU V - Variable Speed
120=120,000 BTU
140=140,000 BTU
Not all familes have these models.
59SC2A
A12373
FURNACE COMPONENTS
GAS BURNER
HOT SURFACE
IGNITER
MANUAL RESET
ROLLOUT SWITCH
FLAME
SENSOR
MANUAL RESET
ROLLOUT SWITCH
GAS VALVE
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
OPERATING INSTRUCTIONS
NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE
OPERATING INSTRUCTIONS
INSIDE DOOR FIGURE).
INDUCER MOTOR
ASSEMBLY
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
BLOWER DOOR
SAFETY SWITCH
MEDIA CABINET
BLOWER AND
MOTOR
FURNACE
CONTROL
BOARD
CAPACITOR/
POWER CHOKE
(IF USED)
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
A11408
4
ACCESSORIES
Venting Accessories
Vent Kit - Through the Cabinet
Vent Terminal - Concentric - 2” (51 mm)
Vent Terminal - Concentric - 3” (76 mm)
Vent Terminal Bracket - 2” (51 mm)
Vent Terminal Bracket - 3” (76 mm)
Vent Kit --- Rubber Coupling
Condensate Drainage Accessories
Freeze Protect Kit - Heat Tape
CPVC to PVC Drain Adapters - 1/2” CPVC to 3/4” PVC
Horizontal Trap Grommet - Direct Vent
Condensate Neutralizer Kit
External Trap Kit
Ductwork Adapter Accessories
Furnace Base Kit for Combustible Floors
Coil Adapter Kits --- No Offset
Coil Adapter Kits --- Single Offset
Coil Adapter Kits --- Double Offset
Return Air Base (Upflow Applications) 14.0 ---in. wide
Return Air Base (Upflow Applications) 17.5 ---in. wide
Return Air Base (Upflow Applications) 21.0 ---in. wide
Return Air Base (Upflow Applications) 24.5 ---in. wide
IAQ Device Duct Adapters 20.0 ---in. IAQ to 16 in. Side Return
IAQ Device Duct Adapters 24.0 ---in. IAQ to 16 in. Side Return
Gas Conversion Accessories
Mobile Home Kit
Gas Conversion Kit - Nat to LP
Gas Conversion Kit - LP to Nat
Gas Orifice Kit - #42 (Nat Gas)
Gas Orifice Kit - #43 (Nat Gas)
Gas Orifice Kit - #44 (Nat Gas)
Gas Orifice Kit - #45 (Nat Gas)
Gas Orifice Kit - #46 (Nat Gas)
Gas Orifice Kit - #47 (Nat Gas)
Gas Orifice Kit - #48 (Nat Gas)
Gas Orifice Kit - #54 (LP)
Gas Orifice Kit - #55 (LP)
Gas Orifice Kit - #56 (LP)
Gas Orifice Kit - 1.25mm (LP)
Gas Orifice Kit - 1.30mm (LP)
Control Accessories
Twinning Kit
IAQ Accessories
Filter Rack --- Side Return for 1” Filters
Filter Rack --- Bottom Return for 1” Filters --- 14.2” wide
Filter Rack --- Bottom Return for 1” Filters --- 17.5” wide
Filter Rack --- Bottom Return for 1” Filters --- 21.0” wide
Filter Rack --- Bottom Return for 1” Filters --- 24.5” wide
Filter Pack (6 pack) --- Washable - 16x25x1
Filter Pack (6 pack) --- Washable - 24x25x1
EZ-Flex Filter - 16” (406 mm)
EZ-Flex Filter - 20” (508 mm)
EZ-Flex Filter - 24” (610 mm)
EZ-Flex Filter with End Caps - 16” (406 mm)
EZ-Flex Filter with End Caps - 20” (508 mm)
EZ-Flex Filter with End Caps - 24” (610 mm)
Cartridge Media Filter - 16” (406 mm)
Cartridge Media Filter - 20” (508 mm)
Cartridge Media Filter - 24” (610 mm)
EZ Flex Cabinet Side or Bottom Return 4” Filters --- 16”
EZ Flex Cabinet Side or Bottom Return 4” Filters --- 20”
EZ Flex Cabinet Side or Bottom Return 4” Filters --- 24”
D = Used with the model furnace
PART NUMBER
040--- 10 060--- 10 060--- 14 080--- 16 080--- 20 100-14
KGADC0101BVC
KGAVT0701CVT
KGAVT0801CVT
KGAVT0101BRA
KGAVT0201BRA
KGAAC0101RVC
D
KGAHT0101CFP
KGAAD0110PVC
KGACK0101HCK
P908 ---0001
KGAET0201ETK
D
D
D
D
D
D
D
D
D
D
D
D
KGASB0201ALL
KGADA0101ALL
KGADA0201ALL
KGADA0301ALL
KGARP0301B14
KGARP0301B17
KGARP0301B21
KGARP0301B24
KGAAD0101MEC
KGAAD0201MEC
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGAMH0601KIT
KGANP50011SP
KGAPN42011SP
LH32DB207
LH32DB202
LH32DB200
LH32DB205
LH32DB208
LH32DB078
LH32DB076
LH32DB203
LH32DB201
LH32DB206
LH32DB209
LH32DB210
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
100-20
120-20
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
See Venting Tables
See Venting Tables
D
D
D
D
All DV Horizontal
D
D
D
D
D
20”x25” IAQ Devices
24”x25” IAQ Devices
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGATW0701HSI
KGAFR0801SRE
KGBFR0401B14
KGBFR0501B17
KGBFR0601B21
KGBFR0701B24
KGAWF1306UFR
KGAWF1506UFR
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
EXPXXUNV0016
EXPXXUNV0020
EXPXXUNV0024
FILXXCAR0016
FILXXCAR0020
FILXXCAR0024
EZXCABCC0016
EZXCABCC0020
FILCABXL0024
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
Use with EZXCAB---1016
Use with EZXCAB---1020
Use with EZXCAB---1024
Use with EZXCAB---1016
Use with EZXCAB---1020
Use with EZXCAB---1024
Use with FILCABXL ---1016
Use with FILCABXL ---1020
Use with FILCABXL ---1024
D
D
D
D
5
59SC2A
DESCRIPTION
AIR DELIVERY - CFM (BOTTOM RETURN WITH FILTER)
UNIT
SIZE
040---10
060---10
59SC2A
060---14
080---16
080---20
100---14
100---20
120---20
RETURN-AIR
CONNECTION
SIDE/BOTTOM
SIDE/BOTTOM
SIDE/BOTTOM
SIDE/BOTTOM
BOTTOM or
TWO-SIDES 3,4
SIDE/BOTTOM
BOTTOM or
TWO-SIDES 3,4
BOTTOM or
TWO-SIDES 3,4
EXTERNAL STATIC PRESSURE (IN.W.C.)
SPEED
TAPS 2
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Black
1100
1055
1010
960
905
850
795
740
685
620
Yellow
955
915
875
830
790
740
695
645
590
530
Blue
820
795
765
730
695
655
615
570
515
460
Red
730
710
680
655
625
595
555
515
465
400
Black
1340
1295
1245
1190
1130
1065
1005
895
815
725
Yellow
1035
1010
980
945
910
865
795
730
665
605
Blue
Red 5
845
825
810
785
755
710
670
625
570
515
770
750
730
710
675
640
600
560
510
455
Black
1665
1615
1550
1485
1420
1345
1270
1190
1105
985
Yellow
1340
1320
1295
1260
1215
1165
1110
1045
925
850
Orange
1050
1045
1035
1015
995
960
915
845
785
725
Blue
985
980
975
950
930
900
845
795
740
690
Red 5
735
720
700
675
650
620
595
560
520
480
Black
1870
1810
1740
1670
1600
1525
1440
1355
1270
1180
Yellow
1525
1495
1460
1415
1365
1305
1240
1170
1090
990
Orange
1375
1355
1330
1300
1260
1210
1155
1090
1025
940
Blue
1045
1040
1030
1010
985
960
920
875
825
745
Red 5
880
865
850
835
810
785
750
715
665
605
Black
2360
2250
2160
2065
1970
1880
1785
1685
1580
1455
Yellow
2100
2030
1960
1885
1805
1720
1635
1545
1440
1305
Orange
1840
1810
1765
1725
1665
1590
1515
1430
1335
1240
Blue
1705
1685
1660
1615
1570
1510
1445
1370
1280
1135
Red
1425
1410
1385
1365
1335
1290
1245
1190
1120
1050
Black
1750
1705
1660
1605
1545
1475
1405
1305
1220
1140
Blue
1550
1510
1470
1430
1380
1320
1245
1170
1095
1015
Yellow
1290
1255
1220
1180
1130
1075
1020
960
885
800
Red 5
1085
1045
1010
960
915
865
805
740
665
595
Black
2415
2330
2245
2155
2065
1965
1865
1760
1645
1530
Yellow
2130
2075
2010
1945
1865
1785
1695
1600
1490
1375
Orange
1830
1815
1785
1740
1685
1625
1550
1470
1370
1255
Blue
1690
1680
1655
1620
1580
1530
1465
1385
1295
1185
Red
1415
1405
1390
1370
1345
1305
1260
1200
1125
1050
Black
2440
2360
2295
2215
2105
1975
1815
1710
1575
1405
Blue
2300
2245
2185
2090
2005
1855
1745
1635
1505
1370
Yellow
1805
1780
1750
1705
1650
1595
1515
1430
1330
1230
Orange 5
1560
1550
1535
1505
1470
1420
1360
1285
1205
1130
Red 5
1390
1385
1370
1345
1320
1285
1230
1175
1105
1035
NOTE:
1. A filter is required for each return ---air inlet. Airflow performance includes a 3/4 ---in. (19 mm) washable filter media such as contained in a factory ---authorized accessory filter rack. See accessory list. To determine airflow performance without this filter, assume an additional 0.1 in. w.c.. available external static
pressure.
2. Blower speed taps are not always in the same order. Factory default blower connections are as follows:
a. Heating airflow --- BLUE (also used for Continuous Fan)
b. Cooling airflow --- BLACK (enabled when the Y terminal is energized)
ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.
3. Airflows over 1800 CFM require bottom return, two ---side return, or bottom and side return. A minimum filter size of 20” x 25” (508 x 635 mm) is required.
4. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
5. Highlighted areas indicate that this airflow range is beyond the range allowed for heating. THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOLING.
6
MAXIMUM EQUIVALENT VENT LENGTH - FT. (M)
Table 1 – Maximum Equivalent Vent Length -- Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 2 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
0 to 2000
(0 to 610)
2001 to 3000
(610 to 914)
3001 to 4000
(914 to 1219)
4001 to 4500
(1219 to 1370)
Unit Size
BTU/Hr
DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE)
1-1/2
50
(15.2)
30
(9.1)
20
(6.1)
NA
NA
NA
45
(13.7)
27
(8.2)
17
(5.2)
NA
NA
NA
39
(11.9)
23
(7.0)
15
(4.6)
NA
NA
NA
36
(11.0)
21
(6.4)
14
(4.3)
NA
NA
NA
40,000 3
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
2
210
135
70
25
NA
NA
198
127
64
22
NA
NA
184
119
59
19
NA
NA
177
115
56
17
NA
NA
Vent Pipe Diameter (in.) 1
2-1/2
(64.0)
250
(76.2)
NA 2
(41.1)
235
(71.6)
265
(21.3)
175
(53.3)
235
(7.6)
110
(33.5)
235
15
(4.6)
100
10
(3.0)
90
(60.4)
232
(70.7)
NA
(38.7)
222
(67.7)
250
(19.5)
165
(50.3)
222
(6.7)
104
(31.7)
223
11
(3.4)
93
NA
80
(56.1)
214
(65.2)
NA
(36.3)
210
(64.0)
235
(18.0)
155
(47.2)
210
(5.8)
98
(29.9)
211
8
(2.4)
86
NA
79
(53.9)
205
(62.5)
NA
(35.1)
204
(62.2)
228
(17.1)
150
(45.7)
202
(5.2)
94
(28.7)
205
NA
83
NA
69
3
4
(80.8)
(71.6)
(71.6)
(30.5)
(27.4)
(76.2)
(67.7)
(68.0)
(28.3)
(24.4)
(71.6)
(64.0)
(64.3)
(26.2)
(24.1)
(69.5)
(61.6)
(62.5)
(25.3)
(21.0)
NA
NA
265
265
250
210
NA
NA
249
250
237
185
NA
NA
232
236
224
158
NA
NA
224
229
217
146
(80.8)
(80.8)
(76.2)
(64.0)
(75.9)
(76.2)
(72.2)
(56.4)
(70.7)
(71.9)
(68.3)
(48.2)
(68.3)
(69.8)
(66.1)
(44.5)
NOTES: See notes at end of venting tables.
See Table 3 for altitudes over 4500 ft. (1370 M)
ELBOW CONFIGURATIONS
VENT TERMINAL CONFIGURATIONS
Concentric
Long
Medium
Mitered
Standard
A11580
Table 2 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)
Pipe Diameter (in):
1-1/2
2
2-1/2
3
4
Mitered 90º Elbow
8
(2.4)
8
(2.4)
8
(2.4)
8
(2.4)
8
(2.4)
Medium Radius 90º Elbow
5
(1.5)
5
(1.5)
5
(1.5)
5
(1.5)
5
(1.5)
Long Radius 90º Elbow
3
(0.9)
3
(0.9)
3
(0.9)
3
(0.9)
3
(0.9)
Mitered 45º Elbow
4
(1.2)
4
(1.2)
4
(1.2)
4
(1.2)
4
(1.2)
Medium Radius 45º Elbow
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
Long Radius 45º Elbow
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
Tee
16
(4.9)
16
(4.9)
16
(4.9)
16
(4.9)
16
0
(0.0)
0
(0.0)
0
(0.0)
0
(0.0)
Concentric Vent Termination
Standard Vent Termination
NA
0
(0.0)
7
NA
0
(0.0)
(4.9)
NA
0
(0.0)
59SC2A
Altitude
FT (M)
Venting System Length Calculations
The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent
length of elbows used in the venting system from Table 2.
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer’s data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one
foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Tables 1 and 3.
Example 1
59SC2A
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M). Venting system includes, FOR EACH PIPE, 100 feet (30 M) of vent pipe,
95 feet (28 M) of combustion air inlet pipe, (3) 90_ long radius elbows, (2) 45_ long radius elbows and a factory accessory concentric vent
kit.
Can this application use 2--in. (50 mm ND) PVC/ABS DWV vent piping?
Measure the required linear length of air inlet and vent pipe; insert the
longest of the two here:
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the
3
x
3 ft
vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the
2
x
1.5 ft
vent or inlet pipe)
Add equiv length of vent termination
100 ft
Use length of the longer of the vent
or air inlet piping system
=
9 ft.
From Table 2
=
3 ft.
From Table 2
0 ft.
Total Equivalent Vent Length (TEVL)
112 ft.
From Table 2
From Vent Manufacturer’s instructions;
zero for PVC/ABS DWV
Add all of the above lines
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
127 ft.
YES
For 2” pipe from Table 1
Therefore, 2” pipe may be used
Add correction for flexible vent pipe, if any
0 ft.
Example 2
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) Venting system includes, FOR EACH PIPE, 100 feet (30 M) of vent pipe,
95 feet (28 M) of combustion air inlet pipe, (3) 90_ long radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6 M)
of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
Assume that one meter of flexible 60 mm or 80 mm polypropylene pipe equals 2 Meters of PVC/ABS pipe. VERIFY FROM VENT
MANUFACTURER’S INSTRUCTIONS.
Can this application use 60 mm (O.D.) polypropylene vent piping? If not what size piping can be used?
Measure the required linear length of air inlet and vent pipe; insert the
longest of the two here:
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the
3
x
3 ft
vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the
0
x
vent or inlet pipe)
Add equiv length of vent termination
9M
x 3 ft/M
Add correction for flexible vent pipe, if any
1.8
x
20 ft
Total Equivalent Vent Length (TEVL)
100 ft
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
=
9 ft.
From Vent Manufacturer’s instructions
=
0 ft.
From Vent Manufacturer’s instructions
=
=
18 ft.
36 ft.
163 ft.
From Vent Manufacturer’s instructions
From Vent Manufacturer’s instructions
Add all of the above lines
127 ft.
For 2” pipe from Table 1
Therefore, 60mm pipe may NOT be used;
try 80 mm
NO
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
250 ft.
YES
8
Use length of the longer of the vent
or air inlet piping system
For 3” pipe from Table 1
Therefore, 80 mm pipe may be used
MAXIMUM EQUIVALENT VENT LENGTH - FT. (M) (CONTINUED)
Table 3 – Maximum Equivalent Vent Length -- Ft. (M)
4501 to 10,000 Ft. (0 to 1370 M) Altitude
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 2 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
4501 to 5000
(1370 to 1524)
5001 to 6000
(1524 to 1829)
6001 to 7000
(1829 to 2134)
7001 to 8000
(2134 to 2438)
8001 to 9000
(2438 to 2743)
9001 to 10,000
(2743 to 3048)
DIRECT VENT (2-PIPE) AND SINGLE-PIPE
Vent Pipe Diameter (in.) 1
2
2-1/2
3
Unit Size
1-1/2
40,000
33
(10.1)
171
(52.1)
196
(59.7)
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
40,000
60,000
80,000
100,000
120,000
140,000 4
20
13
NA
NA
NA
27
16
11
NA
NA
NA
21
13
NA
NA
NA
NA
15
10
NA
NA
NA
NA
10
7
NA
NA
NA
NA
5
NA
NA
NA
NA
NA
(6.1)
(4.0)
111
54
16
NA
NA
158
103
49
12
NA
NA
145
96
44
10
NA
NA
133
89
40
NA
NA
NA
121
82
35
NA
NA
NA
110
76
31
NA
NA
NA
(33.8)
(16.5)
(4.9)
198
146
91
NA
NA
179
186
137
85
NA
NA
162
174
120
79
NA
NA
146
163
120
73
NA
NA
130
152
111
67
NA
NA
115
142
103
62
NA
NA
(60.4)
(44.5)
(27.7)
(8.2)
(4.9)
(3.4)
(6.4)
(4.0)
(4.6)
(3.0)
(3.0)
(2.1)
(1.5)
(48.2)
(31.4)
(14.9)
(3.7)
(44.2)
(29.3)
(13.4)
(3.0)
(40.5)
(27.1)
(12.2)
(36.9)
(25.0)
(10.7)
(33.5)
(23.2)
(9.4)
(54.6)
(56.7)
(41.8)
(25.9)
(49.4)
(53.0)
(36.6)
(24.1)
(44.5)
(49.7)
(36.6)
(22.3)
(39.6)
(46.3)
(33.8)
(20.4)
(35.1)
(43.3)
(31.4)
(18.9)
NA 2
221
195
200
80
60
NA
207
183
188
74
50
NA
194
171
178
68
41
NA
181
159
167
62
32
NA
168
148
157
56
23
NA
156
137
147
51
16
4
NA
(67.4)
(59.4)
(61.0)
(24.4)
(18.3)
(63.1)
(55.8)
(57.3)
(22.6)
(15.2)
(59.1)
(52.1)
(54.3)
(20.7)
(12.5)
(55.2)
(48.5)
(50.9)
(18.9)
(9.8)
(51.2)
(45.1)
(47.9)
(17.1)
(7.0)
(47.5)
(41.8)
(44.8)
(15.5)
(4.9)
NA
216
222
211
134
NA
NA
200
208
199
109
NA
NA
185
195
187
87
NA
NA
170
182
175
63
NA
NA
156
170
164
42
NA
NA
142
157
153
20
(65.8)
(67.7)
(64.3)
(40.8)
(61.0)
(63.4)
(60.7)
(33.2)
(56.4)
(59.4)
(57.0)
(26.5)
(51.8)
(55.5)
(53.3)
(19.2)
(47.5)
(51.8)
(50.0)
(12.8)
(43.3)
(47.9)
(46.6)
(6.1)
NOTES:
1. Use only the vent pipe sizes shown for each furnace. It is NOT necessary to choose the smallest diameter pipe possible for venting.
2. NA --- Not allowed. Pressure switch will not close, or flame disturbance may result.
3. Total equivalent vent lengths under 10’ for 40,000 BTUH furnaces from 0 to 2000 ft. (0 to 610 M) above sea level require use of an outlet choke plate .
Failure to use an outlet choke when required may result in flame disturbance or flame sense lockout.
4. Not all furnace families include 140,000 BTUH input models.
5. Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by local authorities having jurisdiction.
6. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
7. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
8. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
9. The minimum pipe length is 5 ft. (1.5 M) linear feet (meters) for all applications.
10. Use 3 ---in. (76 mm) diameter vent termination kit for installations requiring 4 ---in. (102 mm) diameter pipe.
9
59SC2A
Altitude
FT (M) 5
MAXIMUM ALLOWABLE EXPOSED VENT LENGTHS INSULATION TABLE - FT. (M)
Maximum Length of Uninsulated and Insulated Vent Pipe-Ft (M)
Single Stage
Furnace
Input
Winter Design
Temp ° F (° C)
20 (-10)
0 (-20)
40000
-20 (-30)
-40 (-40)
59SC2A
20 (-10)
0 (-20)
60000
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
80000
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
100000
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
120000
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
140000
-20 (-30)
-40 (-40)
Pipe
Length in
Ft. & M
No Insulation
3/8-in. (9.5 mm) Insulation
1/2-in. (12.7 mm) Insulation
Pipe Diameter-inches (mm)
Pipe Diameter-inches (mm)
Pipe Diameter-inches (mm)
1 1/2
2
2 1/2
3
4
1 1/2
2
2 1/2
3
4
1 1/2
2
2 1/2
3
4
(38)
(51)
(64)
(76)
(102)
(38)
(51)
(64)
(76)
(102)
(38)
(51)
(64)
(76)
(102)
Ft.
48
42
42
N/A
N/A
50
122
111
N/A
N/A
50
144
130
N/A
N/A
M
14.6
12.8
12.8
N/A
N/A
15.2
37.2
33.8
N/A
N/A
15.2
43.9
39.6
N/A
N/A
Ft.
25
19
17
N/A
N/A
50
75
66
N/A
N/A
50
90
79
N/A
N/A
M
7.6
5.8
5.2
N/A
N/A
15.2
22.9
20.1
N/A
N/A
15.2
27.4
24.1
N/A
N/A
Ft.
14
7
5
N/A
N/A
50
52
45
N/A
N/A
50
64
55
N/A
N/A
M
4.3
2.1
1.5
N/A
N/A
15.2
15.8
13.7
N/A
N/A
15.2
19.5
16.8
N/A
N/A
Ft.
7
0
0
N/A
N/A
50
38
31
N/A
N/A
50
48
40
N/A
N/A
M
2.1
0.0
0.0
N/A
N/A
15.2
11.6
9.4
N/A
N/A
15.2
14.6
12.2
N/A
N/A
Ft.
30
61
61
54
N/A
30
135
163
142
N/A
30
135
191
166
N/A
M
9.1
18.6
18.6
16.5
N/A
9.1
41.1
49.7
43.3
N/A
9.1
41.1
58.2
50.6
N/A
Ft.
30
31
30
23
N/A
30
113
100
85
N/A
30
135
120
101
N/A
M
9.1
9.4
9.1
7.0
N/A
9.1
34.4
30.5
25.9
N/A
9.1
41.1
36.6
30.8
N/A
Ft.
24
17
15
7
N/A
30
81
70
57
N/A
30
98
85
70
N/A
M
7.3
5.2
4.6
2.1
N/A
9.1
24.7
21.3
17.4
N/A
9.1
29.9
25.9
21.3
N/A
Ft.
15
8
5
0
N/A
30
61
52
40
N/A
30
75
64
51
N/A
M
4.6
2.4
1.5
0.0
N/A
9.1
18.6
15.8
12.2
N/A
9.1
22.9
19.5
15.5
N/A
Ft.
20
70
78
70
60
20
70
175
183
154
20
70
175
215
181
M
6.1
21.3
23.8
21.3
18.3
6.1
21.3
53.3
55.8
46.9
6.1
21.3
53.3
65.5
55.2
Ft.
20
42
41
33
21
20
70
132
111
89
20
70
157
133
107
M
6.1
12.8
12.5
10.1
6.4
6.1
21.3
40.2
33.8
27.1
6.1
21.3
47.9
40.5
32.6
Ft.
20
25
23
14
1
20
70
94
77
57
20
70
113
94
71
M
6.1
7.6
7.0
4.3
0.3
6.1
21.3
28.7
23.5
17.4
6.1
21.3
34.4
28.7
21.6
Ft.
20
14
12
3
0
20
70
71
56
38
20
70
86
70
50
M
6.1
4.3
3.7
0.9
0.0
6.1
21.3
21.6
17.1
11.6
6.1
21.3
26.2
21.3
15.2
Ft.
N/A
25
99
89
78
N/A
25
110
233
265
N/A
25
110
235
229
M
N/A
7.6
30.2
27.1
23.8
N/A
7.6
33.5
71.0
80.8
N/A
7.6
33.5
71.6
69.8
Ft.
N/A
25
55
46
33
N/A
25
110
145
117
N/A
25
110
173
140
M
N/A
7.6
16.8
14.0
10.1
N/A
7.6
33.5
44.2
35.7
N/A
7.6
33.5
52.7
42.7
Ft.
N/A
25
34
24
11
N/A
25
110
103
79
N/A
25
110
124
97
M
N/A
7.6
10.4
7.3
3.4
N/A
7.6
33.5
31.4
24.1
N/A
7.6
33.5
37.8
29.6
Ft.
N/A
23
20
11
0
N/A
25
95
77
55
N/A
25
110
94
70
M
N/A
7.0
6.1
3.4
0.0
N/A
7.6
29.0
23.5
16.8
N/A
7.6
33.5
28.7
21.3
Ft.
N/A
N/A
15
99
86
N/A
N/A
15
100
219
N/A
N/A
15
100
250
M
N/A
N/A
4.6
30.2
26.2
N/A
N/A
4.6
30.5
66.8
N/A
N/A
4.6
30.5
76.2
Ft.
N/A
N/A
15
51
38
N/A
N/A
15
100
130
N/A
N/A
15
100
156
M
N/A
N/A
4.6
15.5
11.6
N/A
N/A
4.6
30.5
39.6
N/A
N/A
4.6
30.5
47.5
Ft.
N/A
N/A
15
28
14
N/A
N/A
15
100
88
N/A
N/A
15
100
108
M
N/A
N/A
4.6
8.5
4.3
N/A
N/A
4.6
30.5
26.8
N/A
N/A
4.6
30.5
32.9
Ft.
N/A
N/A
15
14
0
N/A
N/A
15
85
62
N/A
N/A
15
100
79
M
N/A
N/A
4.6
4.3
0.0
N/A
N/A
4.6
25.9
18.9
N/A
N/A
4.6
30.5
24.1
Ft.
N/A
N/A
10
90
99
N/A
N/A
10
90
210
N/A
N/A
10
90
210
M
N/A
N/A
3.0
27.4
30.2
N/A
N/A
3.0
27.4
64.0
N/A
N/A
3.0
27.4
64.0
Ft.
N/A
N/A
10
61
47
N/A
N/A
10
90
153
N/A
N/A
10
90
183
M
N/A
N/A
3.0
18.6
14.3
N/A
N/A
3.0
27.4
46.6
N/A
N/A
3.0
27.4
55.8
Ft.
N/A
N/A
10
35
21
N/A
N/A
10
90
104
N/A
N/A
10
90
128
M
N/A
N/A
3.0
10.7
6.4
N/A
N/A
3.0
27.4
31.7
N/A
N/A
3.0
27.4
39.0
Ft.
N/A
N/A
10
20
NA
N/A
N/A
10
90
75
N/A
N/A
10
90
94
M
N/A
N/A
3.0
6.1
NA
N/A
N/A
3.0
27.4
22.9
N/A
N/A
3.0
27.4
28.7
*Not all families have these models.
10
RETURN AIR TEMPERATURE
This furnace is designed for continuous return--air minimum temperature of 60_F (15_C) db or intermittent operation down to 55_F (13_C)
db such as when used with a night setback thermometer. Return--air temperature must not exceed 80_F (27_C) db. Failure to follow these
return air limits may affect reliability of heat exchangers, motors and controls.
80
/ 27˚C
60
/ 16˚C
59SC2A
SUPPLY AIR
A10490
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITION
Rear
Front (Combustion air openings in furnace and in structure)
Required for service**
All Sides of Supply Plenum**
Sides
Vent
Top of Furnace
CLEARANCE
0 (0 mm)
1 in. (25 mm)
24 in. (610 mm)*
1 in. (25 mm)
0 (0 mm)
0 (0 mm)
1 in. (25 mm)
* Recommended
**Consult your local building codes
COMBUSTION--AIR PIPE FOR NON--DIRECT (1--PIPE) VENT APPLICATION
FIELD-SUPPLIED
2-IN. (51 mm) DIA.
MITERED RADIUS
PVC 90° ELBOW
FIELD-SUPPLIED
2-IN. (51 mm) DIA.
PVC PIPE
12” (300 mm) MINIMUM
A12376
NOTE: See Installation Instructions for specific venting configurations.
11
DOWNFLOW SUBBASE
LOCATING
TAB
1 1/4-IN. TYP
PLENUM
OPENING
B
A
D
1
2
3
4
LOCATING
TAB
C
FACTORY-SUPPLIED
FIELD-INSTALLED
INSULATION
4
A97427
2
1
A88207
Assembled
59SC2A
3
Disassembled
DIMENSIONS (IN. / MM)
PLENUM OPENING*
FLOOR OPENING
HOLE NO. FOR
WIDTH
ADJUSTMENT
FURNACE
CASING WIDTH
FURNACE IN DOWNFLOW
APPLICATION
B
C
D
14--- 3/16 (360)
Furnace with or without Cased Coil
Assembly or Coil Box
11--- 3/16
(322)
19 (483)
13--- 7/16
(341)
20--- 5/8
(600)
4
17--- 1/2 (445)
Furnace with or without Cased Coil
Assembly or Coil Box
15--- 1/8
(384)
19 (483)
16--- 3/4
(426)
20--- 5/8
(600)
3
21 (533)
Furnace with or without Cased Coil
Assembly or Coil Box
18--- 5/8
(396)
19 (483)
20--- 1/4
(514)
20--- 5/8
(600)
2
24--- 1/2 (622)
Furnace with or without Cased Coil
Assembly or Coil Box
22--- 1/8
(562)
19 (483)
23--- 3/4
(603)
20--- 5/8
(600)
1
A
*The plenum should be constructed 1/4 ---in. (6 mm) smaller in width and depth than the plenum dimensions shown above.
Concentric Vent Kit
Downflow Subbase
A93086
A88202
A concentric vent kit allows vent and combustion--air pipes to
terminate through a single exit in a roof or side wall. One pipe
runs inside the other allowing venting through the inner pipe and
combustion air to be drawn in through the outer pipe.
One base fits all furnace sizes. The base is designed to be installed
between the furnace and a combustible floor when no coil box is
used or when a coil box other than a Carrier cased coil is used. It is
CSA design certified for use with Carrier branded furnaces when
installed in downflow applications.
12
MEDIA FILTER CABINET
25-5/8"
(651mm)
24-1/4”
(616mm)
Opening with Flanges Bent
23-1/8”
(588mm)
Opening
23-5/8"
(600mm)
23-3/8”
(594mm)
B Opening
59SC2A
A
Duct Side
Furnace Side
23-3/4”
(603mm)
Centerline Screw Slots
5 3 4"
(146mm)
Media Filter
A
B
Cabinet
16" (406mm) 17" (432mm) 16" (406mm)
20" (508mm) 21" (533mm) 20" (508mm)
24" (610mm) 25" (635mm) 24" (610mm)
NOTE: Media cabinet is matched to the bottom opening on furnace. May also be used for side return.
A12428
TYPICAL WIRING SCHEMATIC
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
W
FIVE WIRE
THREE-WIRE
HEATING-ONLY
C
R
G
Y
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE
PHASE
BLOWER DOOR SWITCH
BLK
W
BLK
WHT
WHT
GND
115-V FIELDSUPPLIED
DISCONNECT
GND
AUXILIARY
J-BOX
C
O
N
T
R
O
L
R
208/230-V
SINGLE
PHASE
G
COM
GND
NOTE 1
CONDENSING
UNIT
Y
24-V
TERMINAL
BLOCK
FURNACE
TWO
WIRE
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A11387
13
59SC2
FURNACE SIZE
040--- 10
060--- 10
060--- 14
080--- 16
080--- 20
100--- 14
100--- 20
120--- 20
25 1/8
[638.7]
14
A
CABINET WIDTH
B
OUTLET WIDTH
C
BOTTOM INLET WIDTH
D
AIR INTAKE
14--- 3/16 (361)
12--- 1/2 (319)
12--- 9/16 (322)
7--- 1/8 (181)
17--- 1/2 (445)
15--- 7/8 (403)
16 (406)
8--- 3/4 (222)
21 (533)
19--- 3/8 (492)
19--- 1/2 (495)
10--- 1/2 (267)
24--- 1/2 (622)
22--- 7/8 (581)
23 (584)
12--- 1/4 (311)
21
[534.0]
26 5/16
[668.8]
22
[558.3] (BOTH SIDES)
1 (BOTH SIDES)
[25.4]
7/8
[22.2]
THERMOSTAT ENTRY
SIDE INLET
2 1/2
[63.5]
7/8
[22.2]
7/8
[22.2]
7/8
[22.2]
4
[101.6]
CONDENSATE DRAIN TRAP
LOCATION
AIR FLOW
19 1/8
[485.8]
20 5/8
[522.7]
23 5/16
[592.9]
26 3/8
[670.0]
26 11/16
[678.1]
TOP VIEW
6 11/16
[170.1]
6 15/16
[176.1]
D
SEE NOTE #3
14 13/16
[376.3]
16 9/16
[420.9]
17 5/16
[439.2]
7/8
[22.2] POWER CONN
3
[76.2]
VENT
1 3/4
[44.5]
GAS CONN
3
[76.2]
AIR INTAKE
3
[76.2]
AIR INTAKE
3
[76.2]
VENT
2 3/10
[58.4]
23 7/16
[595.6] 25 3/16
[639.1]
22 15/16
[581.9]
20 1/4
[513.9]
28 5/8
[726.4]
28 3/16
[715.9]
11/16
[17.5]
32 5/8
[829.5]
5/8
[15.8]
NOTE: ALL DIMENSIONS IN INCH [MM]
C
BOTTOM RETURN
WIDTH
AIR FLOW
B
OUTLET WIDTH
A
2 1/2
[63.5]
1 5/16
[33.3]
6 1/16
[154.0]
16 9/16
[420.9]
17 7/16
[442.3]
20 1/4
[513.9] 18 1/16
[458.6]
24
[609.7]
28 3/8
[720.4]
28 5/8
[726.9]
29 13/16
[757]
11/16
[17.5]
35
[889.0]
3
[76.2 ]
3
[76.2]
AIR INTAKE
2
NEXT SHEET
SD5024-4
PART NUMBER
7/8
[22.2]
4
[101.6]
SIDE INLET
7/8
[22.2] POWER CONN
7/8
[22.2]
1 3/4
[44.5]
GAS CONN
7/8
[22.2]
AIR FLOW
20 5/8
[522.7]
21 1/16
[535.8]
21 15/16
[557.4]
26 3/8
[669.9]
26 11/16
[678.1]
28 3/4
[730.5]
29 1/2
[749.3]
REV
E
SHT
1
BOTTOM INLET
21 5/8
[549.5]
23 3/8
[592.0]
26 5/16
[668.8]
7/8
[22.2]
THERMOSTAT ENTRY
NOTES:
1. Doors may vary by model.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle.
b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle.
c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle.
d. Return air above 1800 CFM at 0.5 in. w.c. ESP on 24.5" casing, requires one of the following
configurations: 2 sides, 1 side and a bottom or bottom only. See Air Delivery table in this
document for specific use to allow for sufficient airflow to the furnace.
3. Vent and Combustion air pipes through blower compartment must
use accessory “Vent Kit - Through the Cabinet”. See accessory list for
current part number.
59SC2A
DIMENSIONAL DRAWING
SHIP WT.
LB (KG)
A12267
123.0 (55.4)
127.0 (57.2)
144.0 (64.8)
154.0 (69.3)
161.5 (72.7)
168.5 (75.8)
168.5 (75.8)
186.0 (83.7)
GUIDE SPECIFICATIONS
System Description
Furnish a ______________________ 4--way multipoise gas--fired
condensing furnace for use with natural gas or propane (factory-authorized conversion kit required for propane).
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit
will carry the CSA Blue StarR and Blue FlameR labels. Unit
efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and PSC Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of PSC type shall be
permanently lubricated with sleeve bearings, of _______hp, and
have multiple speeds from 500--1150 RPM operating only when
115--VAC motor inputs are provided. Blower motor shall be direct
drive and soft mounted to the blower housing to reduce vibration
transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media
Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted
galvanized steel.
Draft Inducer Motor
Draft inducer motor shall be single--speed PSC design.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass corrosion--resistant
aluminized steel of fold--and--crimp sectional design and applied
operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel
flow--through of fin--and--tube design and applied operating under
negative pressure.
Controls
Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control, a
self--test feature that checks all major functions of the furnace, and
a replaceable automotive--type circuit protection fuse. Multiple
operational settings available, including blower speeds for heating,
cooling. Continuous fan speed is the same as the selected heating
speed.
Operating Characteristics
Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________AFUE.
Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure.
Dimensions shall be: depth_________in. (mm); width
__________in. (mm); height___________in. (mm) (casing only).
Height shall be_________in. (mm) with A/C coil and
_________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size
of HACR--type designated circuit breaker shall be _________
amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
15
59SC2A
General
59SC2A
Copyright 2012 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Edition Date: 09/12
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
Catalog No: 59SC2A ---02PD
Replaces: 59SC2A--- 01PD