BAXI Solar Thermal Domestic Hot Water System Instructions
The BAXI Solar Thermal Domestic Hot Water System is a high-quality system designed to heat water using the sun's energy. This system can provide up to 60% of a dwelling's annual hot water requirement, reducing reliance on fossil fuels. It works by capturing the sun's energy through solar collector panels, transferring it to a heat transfer fluid, and then using this heated fluid to raise the temperature of water stored in a solar storage cylinder. A conventional boiler or electric immersion heater provides supplementary heating when needed.
Advertisement
Advertisement
2nd Fix Solar Manual
© Baxi Heating UK 2012
Please read these instructions before installing or commissioning.
This Solar Thermal Domestic Hot Water System should only be installed by a competent person.
PLEASE LEAVE THESE INSTRUCTIONS WITH THE
USER FOR SAFE KEEPING.
Index
© Baxi Heating UK Ltd 2012. All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means, or stored in any retrieval system of any nature (including in any database), in each case whether electronic, mechanical, recording or otherwise, without prior written permission of the copyright owner, except for permitted fair dealing under Copyrights, Designs and Patents Act 1988.
Applications for the copyright owner’s permission to reproduce or make other use of any part of this publication should be made, giving any details of the proposed use to the following address:
The Company Secretary, Baxi Heating UK Ltd, Brooks House, Coventry Road, Warwick CV34 4LL.
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a copyright work may be liable to criminal prosecution and civil claims for damages.
2 Index
3 Introduction to Solar
4 Hydraulic station specifications
5 Differential temperature controller specifications
6 Ancillary components
Expansion vessel
Solar heat transfer fluid
7 Cylinder specifications
Unvented
Cistern-fed vented
9 Safety information
11 Installation of hydraulic station
Parts list
Identification of components
Pipework installation - general
Installing the hydraulic station - positioning
Installing the wall brackets and hydraulic station
Installing the safety group
Connecting the solar expansion vessel
Connecting pipework
17 Commissioning of system
Air test
Flushing and filling the pipework
19 Installation of solar controller
Appliance installation
Opening the controller
Electrical connection overview
230/240V~ connections
Solar gain measurement
Connection of temperature sensors
Control of auxiliary heat input
24 Commissioning of hydraulic station
Ensure the solar primary system is free from air
Setting the system pressure
25 Commissioning of solar controller
Main menu
Control button
Menu “info”
Menu “programming”
Menu “Manual operation”
Menu “Basic adjustment”
Overview of display and operating elements
Controller functions
General controller functions
Cylinder heating by solar primary system
Systems with two storage cylinders
Rotational speed regulation
Thermostat (heating)
Thermostat (cooling)
Tube collector
Sensor monitoring
Flow monitoring
System protection function
Frost protection
Energy productivity measurement
Operating hours meter
37 Setting the system flow rate
Checking and adjusting the flow rate
Installation of the thermal insulation
Commissioning record
41 Maintenance
Check heat transfer fluid
Maintenance of the collector
Cylinder
42 Fault Finding
Failures with error message
45 Spares
Spare parts and accessories
46 Warranty
Standard warranty terms & conditions
2 © Baxi Heating UK 2012
6
8
10
12
13
6
7
8
9
10
11
12
13
14
1
2
3
4
5
Cold Supply for Domestic Hot Water
Domestic Hot Water Outlet
Auxiliary Discharge Arrangement
Solar Collector 1
Solar Collector 2 (For East / West Array Installation)
Collector Sensor 1 (PT 1000)
Collector Sensor 2 (PT 1000)
Solar Pumping Station with Controller
Solar Pumping Station Cascade Module
Solar Expansion Vessel
Auxiliary Heat Source (Central Heating Boiler)
Flow Meter on a ‘COMMON’ Return (Accessory code 84515064)
Solar Fluid Discharge Vessel (Accessory code 720294601)
Thermostatic Blending Valve (Accessory code 720223301)
5
9
4
7
4
6
8
3
14
10
12
13
3
14
2
11
Fig. 1
1
2
11
1.1
Description
1. Thank you for purchasing a high quality Solar Thermal
Domestic Hot Water System.
2. The sun is the ultimate source of most of our renewable energy supplies. Energy from the sun is clean and abundant.
3. There is a widely held opinion that the UK does not have enough sun to make solar systems worthwhile. In fact parts of the UK have annual solar radiation levels equal to 60% of those experienced at the equator.
4. However, this energy is not received uniformly throughout the year. Some 70% of UK annual radiation is received over the period April to September and 25% is received in the months of June and July.
5. Solar water heating technology captures energy from the sun and transfers this to a water heater to raise the water temperature therefore reducing the reliance on fossil fuel energies such as gas, oil and electricity. Up to 60% of a dwelling’s annual hot water requirement can be provided by a solar water heating system. The balance is provided by traditional means via a second heat exchanger connected to a fossil fuel boiler or electrical heating by electric boiler or immersion heater.
6. The water heating system provides all the principal components required for an efficient solar water heating system.
The sun’s energy is captured by a series of solar collector panels through which a special heat transfer fluid is pumped. As the fluid passes through the collector panels its temperature is raised. The heated fluid is circulated through a heat exchanger coil in the base of the solar storage cylinder transferring the heat gained to the stored water, gradually raising its temperature. The cooled fluid then returns to the collector panel to be heated again. Heating by the solar coil is controlled by a solar differential temperature controller that ensures the system will only operate when there is useful solar heating gain at the collector panel. As the sun’s energy input to the collector panels is variable supplementary heating by a conventional boiler or electric immersion heater should be provided. The optional cylinders that can be supplied with the package provide a supplementary heat exchanger coil and immersion heater as standard.
1
Fig. 2
© Baxi Heating UK 2012 3
Fig. 3 System Module
2.0
Hydraulic station specifications
2.1
Technical data
Dimensions
System Module
Pump Station
Cascade Module
Pump Station
(Height/Width/Depth)
375/250/190mm
375/190/190mm
Flow and return connections
(compression fittings) 22mm
Maximum working temperature:
Maximum working pressure:
Pressure Relief Valve setting:
Circulating Pump:
Circulating Pump voltage:
Power consumption Setting 1:
Setting 2:
Setting 3:
Maximum Pump Head:
Maximum Pump Capacity:
Flow meter scale:
160°C
6 bar
6 bar
Baxi
230/240 V ~
45W / 45W
68W / 65W
90W / 85W
6 metres
4.5 m3/h / 3.5 m3/h
2 to 15 l/min
Fig. 4 Cascade Module
4 © Baxi Heating UK 2012
Fig. 5
© Baxi Heating UK 2012
3.0
Differential temperature controller
3.1
Technical data
Housing
Material
Dimensions
L x W x D in mm weight
Ingress protection
100% recyclable ABS
175 x 134 x 56 ca. 360 g
IP40 according to VDE 0470
Electrical values
Operating voltage
Interference grade
Max. conductor cross-section
230/240V ~ 50 Hz
N according to VDE 0875
Temperature sensor / temperature range
Test voltage
PTF6 - 25°C to 200°C
PT1000, 1,000 kΩ at 0°C
4 kV 1 min according to
VDE 0631
230V / 240V Switching voltage
Capability per one switch output
Total capability of all outputs
Fuse protection
1A / ca. 230VA for cos j = 0,7-1,0
2A / ca. 460VA maximum fine-wire fuse 5 x 20mm, 2A/T
(2 amperes, slow)
Features
Self explanatory, menu driven operation
Adjustable control values
System monitoring
Energy yield, (solar gain) measurement
Suitable for flat plate and evacuated tube type collectors
Reheat thermostat function
Can be used in a number of system configurations
5
Expansion vessel
Ø300mm
3
/
4
”
Fig. 6
4.0
Ancillary components
4.1
Expansion vessel
1. Membrane expansion tanks for solar primary heating circuit. Manufactured according to the Directive PED 97/23/CE
(approved noZ-DDK-MUC-02-396876-04).
2. Butyl membrane suitable for solar primary heating fluid, DIN
4807-3 approval.
Maximum working temperature +110°C.
Maximum percentage of glycol 50%.
Connection: 3/4” BSP male parallel
3. Expansion vessel supplied with wall mounting bracket and self sealing vessel connection that will allow removal of the vessel for maintenance without losing solar heat transfer fluid.
4.2
Solar heat transfer fluid
1. The system uses a sealed system indirect solar primary circuit which must be filled with the solar heat transfer fluid provided.
This is a Pre-mixed (40% glycol / 60% water) Solar thermal transfer fluid, based on1,2 - propylene glycol with corrosion inhibitors. It is Non-toxic, odourless, bio-degradable.
2. DO NOT mix the fluid with other types.
3. The use of chemical resistant gloves and suitable eye protection is required when handling.
4. A full safety data sheet is available on request.
5. The system should be filled when there is no direct radiation from the sun. If direct radiation occurs the collector panels should be shaded by covering them during filling and flushing.
6. Although the solar heat transfer fluid is non corrosive and biodegradable appropriate precautions should be taken when handling.
7. Wash with soap and water if the fluid comes into contact with skin.
8. If fluid gets into eyes, immediately rinse with large quantities of clear running water.
9. The solar heat transfer fluid must be pumped into the system.
The pump can be electric or manual but must be capable of producing a pressure of at least 2 bar. The system should be thoroughly flushed to remove any contaminants in the solar primary circuit prior to filling with the heat transfer fluid
10. The fluid is supplied in 20litre container.
Weight of container full - 21kg.
11. Systems found to have low glycol concentrations will not be covered by the warranty.
6 © Baxi Heating UK 2012
Unvented system - schematic diagram
6
4
8
10
12
Note: Indirect twin coil unit shown.
13
3
14
5.0
Cylinder specifications
2
11
Fig. 7
1
5.1
Unvented
Nominal capacities 210, 250 and 300 litre.
Rating Immersion heater(s) 1 x 3 kW (indirect models),
2 x 3kW (direct models) @ 240V~.
Outer casing White plastic coated corrosion proofed steel.
Thermal insulation CFC/HCFC-free (ODP zero) flameretardant expanded polyurethane (60mm thick). GWP 3.1
(Global Warming Potential).
Cylinder Duplex stainless steel.
Pressure testing To 15 bar.
Heat unit Titanium element/s, incorporated into an easily removable heater plate, should replacement be necessary. Rated 3.0kW @ 240V~.
Primary coil (for Auxiliary boiler heating) 22mm diameter stainless steel. Coil in coil design for improved performance
Solar coil 25mm diameter stainless steel. Coil in coil design and large surface area for improved performance.
Thermostat
Direct models: Element thermostat adjustable from 10°C to
70°C.
Indirect models: Factory-fitted cylinder thermostat adjustable to 70°C.
Solar: Factory fitted control pocket suitable for insertion of solar controller temperature probe.
Factory fitted safety features:
Direct models: Manually re-settable cut-out on heating element operates at 85°C.
Indirect models: High limit thermal cut-out operates at 85°C.
Wired in series with two-port motorised valve (supplied) to provide primary over temperature protection when using auxiliary (boiler) coil.
All models: Temperature and Pressure Relief Valve, factory set to operate at 10 bar and 90°C.
High limit thermal cut-out operating at 85°C at solar coil position. Wired in series with the solar differential temperature controller to provide over temperature protection if overheating occurs from solar collector panels.
N.B. This must be used in an unvented installation to comply with the requirements of Building Regulation G3.
Anode Not required.
For full technical and performance specification see cylinder installation instructions.
The cylinders are unvented so installation must comply with
Building Regulation G3 and / or other local regulatory requirements.
© Baxi Heating UK 2012 7
Vented system - schematic diagram
Note: Direct unit shown. Auxiliary heating by immersion heater.
Fig. 8
5.0
Cylinder specifications
5.2
Cistern-fed vented
Nominal capacities 210, 250 and 300 litre.
Rating Immersion heater(s) 1 x 3 kW (indirect models),
2 x 3kW (direct models) @ 240V~.
Outer casing White plastic coated corrosion proofed steel.
Thermal insulation CFC/HCFC-free (ODP zero) flameretardant expanded polyurethane (60mm thick). GWP 3.1
(Global Warming Potential).
Water container Duplex 2304 stainless steel. 40 metres
(4 bar) maximum working head.
Heat unit Titanium element/s, incorporated into an easily removable heater plate, should replacement be necessary.
Rated 3.0kW @ 240V~.
Primary coil (for auxiliary boiler heating) 22mm diameter stainless steel. Coil in coil design for improved performance.
Solar coil 25mm diameter stainless steel. Coil in coil design and large surface area for improved performance.
Thermostat
Direct models: Element thermostat adjustable from 10°C to
70°C.
Indirect models: Factory-fitted cylinder thermostat from 10°C to 70°C.
Solar: Factory fitted control pocket suitable for insertion of solar controller temperature probe.
Safety features Thermostats with manually resettable thermal cut-out.
High limit thermal cut-out operating at 85°C at solar coil position. Wired in series with the solar differential temperature controller to provide over temperature protection if overheating occurs from solar collector panels.
Anode Not required.
For full technical and performance specification see cylinder installation instructions.
Detailed installation and commissioning instructions are supplied with the cylinders.
NOTE: The system is also compatible with cylinders configured for solar DHW systems. For installation and specification details refer to the manufacturers instructions supplied with the solar cylinder.
Any system installed using an unvented cylinder must comply with Building Regulations G3 and/or other Local Regulations.
8 © Baxi Heating UK 2012
© Baxi Heating UK 2012
6.0
Safety Information
6.1
Safety
1. In order to reduce the number of deaths and major accidents attributable to work at height, the Health and Safety Executive has introduced comprehensive regulations and guidance that should be followed by all businesses working at height.
2. We consider in the following paragraphs some of the main features of the regulations and guidance. This is, however, only a limited summary and it is recommended that all businesses planning on undertaking solar water heating installations obtain a copy of the regulations and guidance issued by the Health and
Safety Executive and carefully consider the contents.
3. The regulations and guidance state that you are required to carry out a risk assessment for all work conducted at height and to put in place arrangements for:
• Eliminating or minimising risks from work at height.
• Safe systems of work for organising and performing work at height.
• Safe systems for selecting suitable work equipment.
• Safe systems for protecting people from the consequences of work at height.
4. The regulations and guidance highlight a hierarchy for safe work at height:
• Avoid the risk by not working at height if practicable.
• Prevent falls, where it is not reasonably practicable to avoid work at height; you are required to take suitable and sufficient steps to prevent the risk of a fall including selecting the most suitable work equipment
(in accordance with the regulations).
• Mitigate the consequences of a fall; where the risk of a person or object falling still remains, take suitable and sufficient measures to minimise the distance and consequences of any fall.
5. Collective protection measures, such as guard rails on scaffold, should be given priority over personal protection measures, such as safety harnesses.
6. Within the regulations’ framework, you are required to: a) Assess the risk to help you decide how to work safely.
b) Follow the hierarchy for safe work at height (i.e. avoid, prevent and mitigate).
c) Plan and organise your work properly, taking account of weather conditions and the possibility of emergencies.
d) Make sure those working at height are competent.
e) Make use of appropriate work equipment.
f) Manage the risks from working on or around fragile surfaces and from falling objects.
g) Inspect and maintain the work equipment to be used and inspect the place where the work will be carried out
(including access and egress).
7. When preparing to install a solar water heating system, it is required that you perform a risk assessment in relation to work at height and plan how you will organise your work, taking into account the site, the weather conditionsand the experience and competence of colleagues or contractors who may be working at height with you.
9
10 © Baxi Heating UK 2012
6.0
Safety Information
6.1
Safety (cont)
Risk Assessments
8. The HSE has published a number of very useful free publications that advise how to undertake risk assessments.
9. Two of these that you should obtain are:
Five Steps to Risk Assessment.
A Guide to Risk Assessment Requirements.
10. The five steps outlined in the HSE leaflet are:
Step 1: Look for the hazards, this will mean looking at the site and identifying significant hazards. These could be features such as a steep roof, a fragile surface where the collectors may be mounted, uneven ground or obstructions where access to the roof might be required.
Step 2: Decide who may be harmed and how, this might mean considering the particular risks that young workers or trainees might face and thinking about the residents of the household or visitors who could be hurt by your activities.
Step 3: Evaluate the risks and decide which precautions should be made, you should consider how likely it is that each hazard will cause harm, decide which precautions you might take and then assess, after you have taken those precautions, whether the remaining risk will be high, medium or low. Where you identify remaining risks, you should consider which further action you could take to control the risks so that harm is unlikely.
Step 4: Record your findings, if you have fewer than five employees you do not need to write anything down, though it is useful to keep a written record of what you have done. If you employ five or more people you must record the significant findings of your assessment. You must also tell your employees about your findings. You need to be able to show that a proper check was made, that you considered who might be affected, that you dealt with all the obvious significant hazards, that the precautions you propose are reasonable and that the remaining risk is low.
Step 5: Review your assessment if necessary, each solar water heating installation may bring its own challenges and present its own particular hazards. You should therefore be careful not to rely on a “standard” risk assessment for installing a solar water heating system in a house, but review the particular hazards for each new situation. The issue of work equipment must be considered, but at the preparation stage you should consider where scaffold or other access equipment might be positioned and look out for any obvious obstacles to this, such as a conservatory or porch. In addition to the risks associated with work at height, you should also consider the risks associated with lifting and carrying solar collectors, using electric drills and using blow lamps or blow torches for soldering. This is not an exclusive list and so you should consider all aspects of the proposed installation to assess whether there are additional risks that need to be taken into account.
6
Fig. 9 (Diagrams not to scale)
2
1
7.0
Installation of hydraulic station
4
3
7.1
Parts list
4.
5.
2.
3.
Before commencing the installation check all listed components are contained in the following cartons.
Hydraulic Station carton:
1.
Hydraulic pump station with insulation incorporating wall mounting bracket.
Solar differential temperature controller.
Safety group, comprising-
Pressure relief valve, pressure gauge and fill & drain valve.
22mm compression fitting nut and olive(4 off).
Sensor extension cable (13m) (not shown).
7
7.
8.
Ancillary component carton:
6.
Solar expansion vessel complete with mounting bracket and strap assembly.
Expansion vessel connecting hose.
Expansion vessel self sealing connection.
8
© Baxi Heating UK 2012 11
6
1 2
5
Fig. 10
3
4
7.0
Installation of hydraulic station
7.2
Identification of components
–
–
1. The main components of the hydraulic station are:
– Two isolating valves (Fig. 10, Item 1 & 2) with integral thermometers which display the solar primary flow and return temperatures.
–
–
A safety group (Fig. 10, Item 3, supplied unconnected), which protects the solar primary circuit. The pressure relief valve and pressure gauge are integrated in the safety group.
A non-return valve in both feed and return prevents the possibility of gravity circulation in the solar primary circuit.
A solar circulation pump (Fig. 10, Item 4).
A flow meter with fill & drain valve and shut-off valve
(Fig. 10, Item 5).
2. The heat transfer fluid is circulated by the solar circulation pump integrated in the hydraulic pump station (Fig. 10).
3. The hydraulic station has a solar differential temperature controller (Fig. 10 Item 6) integrated into the front insulation moulding. This is pre-wired to the solar pump.
12 © Baxi Heating UK 2012
Fig. 11
6
4 Static
Height (m)
© Baxi Heating UK 2012
8
10
12
13
3
14
7.0
Installation of hydraulic station
2
11
7.3
6
7
4
5
2
3
See Fig. 11
1 Cold Supply for Domestic Hot Water
Domestic Hot Water Outlet
Auxiliary Discharge Arrangement
Solar Collector 1
Solar Collector 2 (For East / West Array Installation)
Collector Sensor 1 (PT 1000)
Collector Sensor 2 (PT 1000)
8
9
Solar Pumping Station with Controller
Solar Pumping Station Cascade Module
10 Solar Expansion Vessel
11 Auxiliary Heat Source (Central Heating Boiler)
12 Flow Meter on a ‘COMMON’ Return
(Accessory code 84515064)
13 Solar Fluid Discharge Vessel
(Accessory code 720294601)
14 Thermostatic Blending Valve
(Accessory code 720223301)
1
7.4
Pipework installation - general
1. In Solar Heating Systems, the collectors, the hydraulic station and solar cylinder (Fig. 11, Item 1) must be connected with brazed or silver soldered copper pipes, compression fittings or the multifit accessory flexible steel tube and insulation. (See brochure for details ) N.B. Plastic pipes MUST NOT be used.
2. Connections supplied are suitable for pipe diameters of
22mm. However for short pipe runs (up to 10m flow and return) the use of 15mm diameter pipe is acceptable.
3. All connections and joints must be resistant to temperatures of up to 150°C and resistant to glycol.
4. If any pipe sealants are used these should be resistant to glycol and be able to withstand temperatures of up to 150°C.
5. The difference in height between the highest point in the pipework (collector) and the level of the hydraulic pump station determines the static head for the system. The static head is 0.1 bar times this height in metres. This static head is used when setting the expansion vessel precharge pressure and the system pressure.
6. If the static head is greater than 1.5 bar (15m) then a larger expansion vessel may be required for larger collector arrays.
7. If the pipe runs between the solar collector and pump station are short (<6m) then a protection vessel (Accessary
No. 5131963) should be installed between the pump station and expansion vessel.
8. Earthing pipework
All solar primary pipework between the solar collectors, hydraulic station and solar cylinder should be earth bonded in accordance with current IEE wiring regulations.;
13
Fig. 12
6
4
8
10
12
13
See Section 7.3 for Key
3
14
7.0
Installation of hydraulic station
2
11
1
7.4
Pipework installation - general (cont)
9. Venting the pipework
The hydraulic station the component includes an air collector/separator and bleed point so an automatic air vent is not necessary. Any section of solar pipework that falls and rises again should be fitted with an additional air vent valve to relieve any trapped air which may cause air locking in the system. The automatic air vent and isolating valve used must be compatible with solar primary systems, i.e. be resistant to glycol and temperatures up to 180ºC.
10. Insulating the pipework
External pipework should be insulated with high temperature resistant materials and be protected against UV degradation.
The insulation must be peck-proof and rodent-proof. Internal pipework, especially through unheated spaces such as a loft space, should also be insulated with high temperature resistant materials. Mark the outside of any insulation to identify the flow and return pipes. The collectors are supplied with 2x2m pre insulated flexible stainless steel tubes. Additional lengths (30m) of stainless steel flexible tubes and high temperature insulation can be supplied.
14 © Baxi Heating UK 2012
Fig. 13
Fig. 14
1
2
6
3
7.0
Installation of hydraulic station
7.5
Installing the hydraulic station - positioning
1. It is usual to install the hydraulic station and solar differential temperature controller near to the solar cylinder. However this does not have to be the case, the hydraulic station can be installed anywhere convenient on the solar primary pipework although adequate access will be necessary for commissioning and maintenance (See also comments regarding system static head given in Section 7.4).
2. The solar differential controller should also be accessible for system operational monitoring. If not in close proximity to the solar cylinder it will be necessary to extend the solar cylinder temperature sensor cable, refer to section 9.6 for details of how to do this.
3.It is recommended that the upper mounting bracket of the hydraulic station is positioned approx. 1600 to 1700mm above the floor level for ease of access and operation of the controls, see Fig. 13.
4. When choosing the site for the hydraulic station provision of a discharge pipe from the safety group and the location of the solar expansion vessel must be considered.
4
7.6
Installing the wall brackets and hydraulic station
1. Remove the front insulation moulding (Fig 14. Item 1) by pulling forward whilst holding the solar differential controller moulding (Fig 14. Item 2) in place, carefully remove the solar differential controller mounting by pulling forward and disconnect the pump cable connector (Fig 14. Item 3).
2. Place the hydraulic assembly on the wall at the desired location and mark the fixing positions through the holes in the mounting brackets.
5
3. Remove the hydraulic assembly from the mounting brackets
(Fig 14. Item 4) and remove rear insulation moulding (Fig 14.
Item 5).
4. Drill and plug the mounting positions and screw the mounting brackets into position.
5. Push the rear insulation moulding over the wall brackets and refit the hydraulic assembly (Fig 14. Item 6) to the mounting clips on the wall brackets.
4
© Baxi Heating UK 2012 15
Fig. 15
Fig. 16
Fig. 18
3
Fig. 17 Flow from panel
Return to panel
2
2
3
1
3
Return to hydraulic station
2
4
1
Flow to cylinder
Return from cylinder
4
To a suitable container
(e.g. Solar fluid discharge vessel
Accessory No. 720294601)
1
5
7.0
Installation of hydraulic station
7.7
Installing the safety group
1. Connect the safety group (Fig 15 Item 1) to the connection on the hydraulic station return isolating valve assembly (Fig 15
Item 3). Ensure that the pre-fitted gasket is securely in place on the safety group prior to connection.
7.8
Connecting the solar expansion vessel
1. Mount the solar expansion vessel (Fig 16 Item 1) adjacent to the hydraulic station (Fig 16 Item 2) so that the vessel can be connected to the vessel connection of the safety group (Fig 16
Item 3) using the flexible pipe (Fig 16 Item 4) supplied. (Note:
Solar expansion vessel, mounting bracket, self sealing connection and flexible pipe are supplied in the Ancillary Components kit).
2. The vessel must be mounted as shown (connection to top) and securely supported using the wall bracket supplied. The self sealing vessel connection should be screwed onto the vessel connection before connecting the flexible pipe (Fig. 16 Item 5).
3. DO NOT replace the solar expansion vessel with either a potable water expansion vessel or boiler sealed system vessel.
4. The charge pressure of the solar expansion vessel must be adjusted (when the fluid circuit is empty or de-pressurised) to a pressure equal to the static head + 0.4 bar, or a minimum of 1.2
bar. (NOTE: the static head is the height difference between the highest point in the pipework (collector) and the hydraulic station in metres x 0.1 bar. The charge pressure should not normally exceed 1.9 bar - see also Section 7.4.
7.9
Connecting pipework
1. Connect the flow and return pipes to the pump station via compression fittings (Fig 17 Item 1). Fittings are for 22mm o/dia pipe. Support the hydraulic assembly when tightening connections.
2. Installing a drain valve
It is recommended to install a device for draining the solar heating system (tee piece with drain valve, Fig. 18) into the flow and return at the lowest point in the solar heating system. The drain and its rubber seal must be suitable for solar applications.
3. Connecting the solar cylinder
For detailed installation instructions refer to the installation instructions supplied with the solar cylinder.
Return from cylinder
Flow to cylinder
16 © Baxi Heating UK 2012
Fig. 19
45°
4 5
Fig. 20
Fig. 21
1
1
2 6
Filling pump
Filter
Solar fluid
3
Read at top of float
3
7
8.0
Commissioning of system
8.1
Air Test
1. An air test may be used on the pipework to detect any gross leakage prior to flushing and filling with solar heat transfer fluid.
Pressurise the system to a maximum of 1 bar to check for leaks.
2. Ensure that the solar expansion vessel pre-charge pressure has been set prior to flushing and filling.
8.2
Flushing and Filling the pipework
1. Before the system is commissioned the pipework must be flushed to remove any contaminants. This must be done using the solar heat transfer fluid as it will be impossible to fully drain all parts of the system.
2. Connect the flushing pipes to the fill & drain valve on the safety group (Fig. 19 Item 1) and to the fill & drain valve on the flow meter (Fig. 19 Item 2).
3. Open the fill & drain valves.
4. Turn the slot of the adjusting screw (Fig. 19 Item 3) in the return so the slot is vertical to open the non-return valve.
5. Turn the left hand isolating valve with integral thermometer in the flow (Fig. 19 Item 4) in the direction indicated by the arrow
(to a 45° position) to open the non-return valve.
6. Ensure that the right hand isolating valve with integral thermometer in the return (Fig. 19 Item 5) is open indicated by the dot on the thermometer bezel being at the top.
7. Turn the slot of the flow meter adjusting screw (Fig. 19 Item
6) in the return vertically to open the flow limiter (Fig. 19 Item
7).
8. Flush the solar primary pump by pumping the fluid into the system via the fill and drain valve on the safety group (Fig. 19
Item 1).
9. Close right hand isolating valve (dot on thermometer bezel at
9 o’clock position). Flush solar primary pipework and collector via the fill and drain valve on the safety group. If reusing flushed fluid ensure this is filtered before re-introducing into the system. (see Fig. 20). Use a suitable container of a large enough volume to collect the fluid.
10. When satisfied that all pipework and component parts have been thoroughly flushed, the system can be filled.
2
© Baxi Heating UK 2012 17
18 © Baxi Heating UK 2012
8.0
Commissioning of system
8.3
Flushing and Filling the pipework (cont)
11. Pour an amount of the solar heat transfer fluid into the filling pump.
12. Close the fill and drain valve - safety group (Fig. 19 Item 1) and the fill and drain valve - flow meter (Fig. 19 Item 2) and pressurise the pump slightly prior to filling the system. If an electric pump is being used follow the instructions with the pump.
13. Fully open the fill and drain valve on the safety group (Fig 19, item 1) and pump fluid into the system. Whilst pumping, open the flow meter drain valve (Fig 19, item 2) slightly to allow the air to vent out of the system.
14. When the pump is down to approximately 1 litre isolate the fill and drain valves. Vent the filling pump and refill with solar heat transfer fluid.
15. Re-pressurise the filling pump and repeat steps 3 and 4 above until fluid is seen discharging from the drain valve on the flow meter. (Fig 19, item 2). Close the drain valve.
16. Continue filling at the fill and drain valve on the safety group
(Fig 19, item 1) until the system pressure reaches 2 bar.
17. At this point the circulation pump should be vented. If the system pressure drops, repressurise using the procedure above.
18. After venting the pump and checking that the system pressure is 2 bar, close the fill and drain valve on the safety group (Fig. 19
Item 1), and check the system for leaks.
19. Turn the left hand isolating valve (Fig 19, item 4) back 45° clockwise until the dot on the bezel is back at 12 o’clock.
20. Turn the right hand isolating valve (Fig. 19 Item 5) back 90° clockwise until the dot on the bezel is back at 12:00 O’clock.
21. Turn the slot of the adjusting screw (Fig. 19 Item 3) back to the horizontal position.
Fig. 22
Solar differential controller
Hydraulic Station
Solar Coil over-temp cut-out
Pump pre-wired
(mounted on hydraulic station)
L
N
E
Double pole isolating switch
230V/240V~
Mains supply
9.0
Installation of solar controller
Terminal block for extending collector sensor
Solar panel sensor
The collector panel temperature sensor should be installed in the sensor pocket at the collector array flow connector as part of the first fix process. Ensure that the cable from this sensor can be identified for connection to the pump station wiring centre. Use the 13m extension cable supplied if required.
9.1
Appliance installation
1. Always disconnect from the mains before opening the controller cover. The solar differential temperature controller is designed to be mounted on the front of the hydraulic station. Alternatively it can be removed from the insulation and be wall mounted (see panel below). In the case of wall mounting the pump cable may need to be lengthened.
Cylinder sensor
Alternative mounting option
In the case of wall installation proceed in the following way:
Drill installation holes according to the dimensions shown below. Screw in two upper screws up to 6 mm distance. Open the appliance as described in section 10.2
and hang it onto two screws. Now two lower screws can be mounted. Tighten all screws. Do not overtighten to avoid damage to the controller backplate.
126mm
84mm
118mm
9.2
Opening the controller
1. Always disconnect from the mains before opening the controller cover.
2. No tools are required to open the controller. The front of the controller is secured by two latches which engage with the controller backplate.
3. It can be opened by gently pulling the lower side edges outwards and then hinging the front upwards.
© Baxi Heating UK 2012 19
Fig. 23
240 Volts
PE PE A3 A2 A1 L
F U S E
Fuse rating T 2A L 250V
T1 T2 T3 T4 T5 T6 T7
PE PE N N N N
Mains 230/240V connections
M1 M2 M3 M4 M5 M6 M7
Low Voltage (SELV) connections
N
A3
N
PE
T1 & M1
T2 & M2
T3 & M3
T4 & M4
T5 & M5
T6 & M6
Terminal
Reference
L
N
A1
N
A2
T7 & M7
Description
240V Supply Live
240V Supply Neutral
Switched Output to Solar Pump
Solar Pump Neutral
Switched Output - Live 2 (For East West Array or Dual Tanks)
Switched Output 2 Neutral
Switched Output - Live 3 (For Auxiliary Heat Control)
Switched Output 3 Neutral
Earth Connection
Temperature Sensor Collector 1 (Tc1)
Temperature Sensor Storage Tank 1 (Ts1)
Temperature Sensor Collector 2/Storage Tank 2 (Tc2 / Ts2)
Temperature Sensor Collector Return (Tret)
Temperature Sensor for 2nd temperature differential controller (Tth)
Frost Protection or 2nd temperature differential controller
Flow Meter (Optional)
Fig. 24
L
N
E
Double pole isolating switch
230V/240V~
Mains supply
Solar differential controller
Solar coil over-temp cut-out
Hydraulic Station
9.0
Installation of solar controller
9.3
Electrical connection overview
1. Always disconnect from the mains before opening the controller cover. The electrical installation must conform to all current Wiring Regulations and be carried out by a competent electrician.
2. The connection of all electrical cables is to the terminal block located on the backplate of the controller. The terminals on the right side of the terminal block are for extra low voltage connections (temperature sensors and flow transmitters). The terminals on the left side of the terminal block are for 230/240 V~ connections.
General connection guidelines.
3. In the case of all connecting wires the outer sheath should be stripped back to 80mm. The individual conductor sleeving should be stripped approx. 10mm.
4. Cables are inserted in the controller through knockouts provided in the controller backplate.
5. Flexible cables must be secured against straining by suitable strain relief bushes or devices.
6. The controller must be earthed.
9.4
230/240V~ connections
1. For 230V connections you must follow the following points:
2. The mains supply to the controller should be via a suitable double pole isolating switch with a contact separation of at least 3mm in both poles. Additionally the controller should be wired via the solar coil over temperature cutout such that power is interrupted to the controller and hydraulic station in the event of the cylinder overheating (see Fig. 24).
3. Controllers are intended for the operation in 230/240V~
/50Hz mains. Any motorised valves connected must be suitable for this voltage.
4. All earth wires must be connected to terminals marked with
PE. Any bare wire earth conductors must be sleeved with green/yellow sleeving.
5. The neutral terminals (N) are electrically connected and are not switched.
6. All switch outputs (A1, A2 and A3) are 230/240V~ closers. If potential-free contacts are needed, appropriate accessories are required.
20 © Baxi Heating UK 2012
Fig. 25
Type 0:
1 collector, 1 storage tank
9.0
Installation of solar controller
Tret
Collector
Tret
P1
FM
Tc1
Storage tank
Tth
Ts1
Type 2:
1 collector, 2 storage tanks with 2 pumps
Collector
Tc1
Storage tank1
Tth
Ts1
Storage tank2
Ts2
FM
P1 P2
Tret
Type 4:
2 collectors, 1 storage tank with 2 pumps
Collector 1
Tc2 Tc1
Storage tank1
Tth
Ts1
P2 P1
Tret
FM
2
4
System type
Type Description
0 1 collector array, 1 storage cylinder
1 collector array, 2 storage cylinder (pump-pump)
2 collector array, 1 storage cylinder (pump-pump)
A1
P1
P1
P1
9.5
Solar Gain measurement
1. For solar gain (energy productivity) measurement in System type ‘0’, it is necessary to fit the collector return sensor as shown in the diagram in Fig. 25. and input the correct flow value.
2. For System types 2 and 4, the collector return sensor must be securely attached to the common return pipework using the securing tiles supplied and then covered by insulation. Use cable ties (not supplied) to ensure good attachment and accurate readings.
3. The solar gain of the system is calculated on the basis of the temperature difference between the collector flow and return and the solar primary circulation flow rate.
4. The function is factory set-up as ‘on’ in the Solar Differential
Temperature Controller.
5. For System Type 2 the additional pump (P2) can be ordered as an accessory, Part No. 7202943 together with appropriate sensor for cylinder 84515063.
6. For System type 4 use the East/West kit accessory as required
(See Sales Brochure).
Key
Tc1
Tc2
Tth
Ts1
Ts2
Tret
P1
P2
FM
Tfr *
* not shown
Description
Temperature Sensor - Collector 1
Temperature Sensor - Collector 2
Temperature Sensor - Thermostat
Temperature Sensor - Storage 1
Temperature Sensor - Storage 2
Temperature Sensor - Collector Return
Circulation Pump 1
Circulation Pump 2
Flow Meter
Temperature Sensor - Frost Protection
Output terminal designation (see Fig. 23)
A2
-
A3
Cooling or thermostat or diff. controller
P2
P2
Cooling or thermostat or diff. controller
Cooling or thermostat or diff. controller
System
Type
0
2
4
System Description
1 collector array, 1 storage cylinder
1 collector array, 2 storage cylinders
2 collector arrays, 1 storage cylinder
T1
Tc1
Tc1
Tc1
T2
Ts1
Ts1
Ts1
T3
-
Ts2
Tc2
T4
Tret
Tret
Tret
T5
Tth
Tth
Tth
NOTE: The solar gain flowmeter must be connected to sensor terminals marked T7 where fitted (see Fig. 23).
© Baxi Heating UK 2012
T6
Tfr
Tfr
Tfr
T7
FM
FM
FM
21
Fig. 26
9.0
Installation of solar controller
Block Wiring Schemes
A. I n conjunction with auxiliary heating by boiler - no reheat control by solar controller.
L
3A Fused Supply
N E L
Boiler Terminal Strip
PL N E SL L N
Programmer
E DHW ON CH ON
1
1
7
2
2
10
3
3 4
3
1
5
4
6
3
2
7
2
3
8
10
5
9
1
10
5
1 2 3 7
Terminal Box (Not supplied)
6
9.6
Connection of temperature sensors
1. The controller uses precise platinum temperature sensors type PT1000. The controller is supplied with 3 sensors ready wired. The sensor with black silicone sheathing (supplied with the first fix kit) must be used for the solar panel sensor.
1 2 3
Cylinder Auxiliary Controls
E
6 9 2
1 2
Room Stat
N
3 2 2
3
G/Y
2
BL BR GR
DHW 2 Port Valve
9 1 5
OR
11
G/Y BL BR
CH 2 Port Valve
GR OR
12 See Fig. 23
4 2 3
L N
CH Pump
E
A1 N PE
PE L
1
Solar
Controller
L 3
N A1 N A2 N
Solar Differential Controller
T1 T2 T4 T7 11 12
Solar Pump
E
A1 N PE
1 2 E
Solar O/Temp Cutout
11 12
Solar Pump 2
E
Note: For Boilers without Pump over run CH Pump Live Supply to 5
A1 N PE
11 12
Solar Pump
E
A1 N PE
11 12
Solar Pump 2
E
2. Installation / cabling of temperature sensors: a) Mount the sensors in the pockets provided in the collector and storage tank. When installing into the collector panel sensor pocket the sensor should be secured by sealing with
UV resistant High Temperature Silicone sealant.
b) The wires of the temperature sensors can be lengthened.
Up to 15m long you need a 2 x 0,5mm2 cross-section, up to
50m 2 x 0,75mm2. In the case of long connections (collector) shielded extension lead must be used. DO NOT run sensor leads adjacent to mains carrying voltage conductors (at least
50mm separation is recommended).
B. In conjunction with auxiliary heating by boiler - reheat control via solar controller.
L
3A Fused Supply
N E L
Boiler Terminal Strip
PL N E SL L
Programmable Room Stat
N 1 2
3
PE
1
1
7
2
2
10
3
3
1 2 3
Cylinder Auxiliary Controls
E
4
3
8
L
2
N
1
5
3
4
6
3
2
7
2
3
8
10
5
9
1
10
5
G/Y
2
BL BR GR
DHW 2 Port Valve
6 1 5
OR
1 2 1 6
Terminal Box (Not supplied)
11
G/Y
12
BL BR
CH 2 Port Valve
GR
7 2
OR
A1 N A3 N A2 N
Solar Differential Controller
4
L
2
N
CH Pump
See Fig. 23
T1 T2 T4
3
E
T5 T7
1 8 3
A1 N PE
11 12
Solar Pump
E
A1 N PE
1 2 E
Solar O/Temp Cutout
11 12
Solar Pump 2
E c)Temperature sensors are supplied connected to the appropriate terminals, refer to Fig 26. The sensors are polarity free.
d) Sensors MUST NOT be connected to the 230/240V~ terminals.
9.7
Control of Auxiliary heat input
1. When using the reheat function the operation of the auxiliary heat input device can be controlled via output A3 from the controller (see fig. 23(c)).
2. The reheat sensor cable is connected to terminals T5 of the solar controller (see page 20) and the sensor element be inserted into the controls pocket at the auxiliary heater level.
3. N.B. The maximum switching current of the controller is 2A so if switching an electrical immersion heater this MUST be done via a relay (see Fig. 26 Block Wiring Scheme C) order accessory code No. 5122765.
1
1
3
PE
C. Solar Cylinder with auxiliary heating by immersion heater.
Boiler
3 Amp Fused Supply
L N E
Immersion
13 Amp Fused Supply
L N E
1
2
2
8
L
8
3
3
2
N
3
4
11
4
5
12
5
6
Relay
6
7 8 9 10
A1 N
A3
A3 N A2 N
Solar Differential Controller
N 4 7
T1
7
Terminal Box (Not supplied)
See Fig. 23
T2 T4 T5 T7
5 6
1 2 E
Solar O/Temp Cutout
1 5 CoM No
Auxiliary Immersion Heater Relay
L N
Immersion Heater
E
4. If using a boiler for auxiliary input, the output from the reheat function should be integrated into the boiler control circuit.
22 © Baxi Heating UK 2012
Fig. 26
9.0
Installation of solar controller
D. Auxiliary heating by boiler with 3 port mid position valve system
- no reheat control by solar controller.
L
3A Fused Supply
N E L
Boiler Terminal Strip
PL N E SL L N
Programmer
E DHW ON DHW OFF CH ON
1
1
8
2
2
5
3
3
7
1 2 3
Cylinder Auxiliary Controls
E
6 9 2
4
3
1
5
4
6
3
2
7
2
3
8
10
5
9 10
NOT USED
3
G/Y
2
BL BR
2 Port Valve
GR
9 7 5
OR
1 2
Room Stat
N
3 2 11
G/Y BL WH GR
3 Port Mid Position Valve
12
OR
See Fig. 23
1 2 3
Terminal Box (Not supplied)
8
4 2
7
3
L N
CH Pump
A1 N
E
PE
6
9.8
1. Key to abbreviations:
SL
G/Y
BL
BR
L
N
E
PL
GR
OR
WH
-
-
-
-
-
-
-
-
-
-
PE L
1
Solar
Controller
L 3
N A1 N A2 N
Solar Differential Controller
T1 T2 T4 T7 11 12
Solar Pump
E
A1 N PE
Live
Neutral
Earth
Switched Live
Green and Yellow
Blue
Brown
Grey
Orange
White
2. The wiring schemes assume the use of an unvented Solar
DHW cylinders.
1 2 E
Solar O/Temp Cutout
11 12
Solar Pump 2
E
3. These diagrams are presented for guidance only, terminal numbers may differ between different manufacturers equipment.
E. Auxiliary heating by boiler with 3 port mid position valve system
- reheat control by solar controller.
1
1
8
L
3A Fused Supply
N E
2
2
5
3
3
7
4
3
L
1
5
4
6
3
Boiler Terminal Strip
PL N E
2
7
2
SL
3
8
5
5
9 10
NOT USED
L
Programmable Room Stat
N 1 2
1 2 1
Terminal Box (Not supplied)
9
1
3
PE
2
6
L
3
Cylinder Auxiliary Controls
E G/Y
3
BL BR GR
DHW 2 Port Valve
2 9 7
OR
5
2
N A1
11 12
G/Y BL WH GR
3 Port Mid Position Valve
8 2
OR
N A2 N A3 N
Solar Differential Controller
T1 T2
4
L N
CH Pump
See Fig. 23
2 3
E
T4 T5 T7
1 6 3
1 2 E
Solar O/Temp Cutout
A1 N PE
11 12
Solar Pump
E
A1 N PE
11 12
Solar Pump 2
E
4. Baxi accept no liability for any loss or damage arising from any errors or omissions that may be inadvertently contained within these diagrams.
5. The various ancillary equipment manufacturers should be consulted to confirm the correct operation of their products within the system.
6. The Warranty only applies to equipment and controls supplied with the system.
© Baxi Heating UK 2012 23
Fig. 27
1
2
10.0
Commissioning of hydraulic station
10.1
Ensure the solar primary system is free from air
1. Switch on the power supply to the solar differential temperature controller.
2. Manually switch the circulation pump ON and OFF via the solar differential temperature controller (see section 11.5) to pump fluid around the solar primary system.
3. Turn the pump off and open the airbleed screw on the air separator (Fig. 27 Item 1). Bleed any air from the air separator.
If the system pressure drops top up by opening the fill and drain valve (Fig. 27 Item 2) on the safety group and pumping in more solar fluid to restore the pressure. This must be repeated until the pressure remains stable.
10.2
Setting the system pressure
1. During commissioning, the system pressure should be 0.7
bar above the static pressure (1 metre height differential equals 0.1 bar). However, it must be at least 1.5 bar and no higher than 2.2 bar.
2. Determine the system pressure when the system is cold
(20°C). This should be recorded on the Commissioning
Record Sheet.
3. If the pressure is too low you should pump additional heat transfer fluid into the system; the fill & drain valve on the safety group (Fig. 27 Item 2) needs to be opened for this purpose.
When system pressure is correctly set, ensure the fill and drain valve is closed and remove filling hose from safety group.
24 © Baxi Heating UK 2012
4
3
5
Fig. 28
Diagram of all possible symbols
1
2
Display Screen
© Baxi Heating UK 2012
1
3
2
4
5
Control Button
Scroll upwards
Main Menu
Sub-Menu
Scroll downwards or select required main menu
Scroll left or exit to main menu
Scroll right or select to edit function
Example Screen - Programming Menu
11.0
Commissioning of solar controller
On completion of commissioning the Solar Controller, note all the required information in the Solar Commissioning Record Sheet at the end of Section 12.
11.1
Main Menu
To make the operation of the controller clear, operating and display functions are divided into 4 main menus.
Info Indication of current measured values.
Indication of system condition.
Indication of error messages.
Indication of operating hours and energy productivity (if installed).
Programming Changes to programmable values
(parameters).
Manual operation Switching on and off connected pumps and auxiliary devices.
WARNING - During manual operation there is no automatic regulation of the system. Temperature control is isolated.
System temperature could be extremely high.
Basic adjustment Information about basic adjustment for system function. To carry out any changes to this menu it must be selected within the first minute after switching the appliance on.
IMPORTANT:Adjustment and changes in this menu must only be carried out by a competent installer or service engineer.
Each active menu is shown in the upper line of the display by its corresponding icon.
11.2
Control Button
When in the Main Menu the control button functions are as follows:
Item 2 - Scroll upwards- no function in this menu
Item 3 - Scroll left - moves left through the main menu options
Item 4 - Scroll down - selects the menu option currently flashing and gives access to the submenu
Item 5 - Scroll right - moves right through the main menu options
Once the sub-menu has been accessed, the flashing symbol becomes static and the button functions are then as follows:
Item 2 - Scroll upwards- moves up through the available
Item 3 - Scroll left functions of the sub-menu
- return to main menu
Item 4 - Scroll down - moves down through the available functions of the sub-menu
Item 5 - Scroll right - select to edit the function displayed.
The selected function will flash if it is available for editing. Use 2 to increase the required value and 4 to reduce it.
Use 5 to OK.
25
Fig. 29
Indication e.g.
75 °C min
12°C max
105°C
52 °C min
40°C max
65°C
60°C
60°C
35°C
25 °C
1234 h
927 kWh
26 © Baxi Heating UK 2012
11.0
Commissioning of solar controller
Press or to scroll up or down to the required sub function.
The icon will flash, press to select the function. Reset by pressing or for increase/decrease values. Press press to confirm and disappears.
ok?
11.3
Menu “Info”
In this menu mode all measured values and operating states are shown.
If the values are marked as “reset possible”, they may be reset in the following way:
Choose the value with buttons and
Reset value by means of the button
Message “OK?” confirm with = no or = yes
Meaning
Indication of current collector(s) temperature.
Reset possible?
No
Indication of minimum collector(s) temperature.
Resettable to current temperature.
Indication of maximum collector(s) temperature.
Resettable to current temperature.
Indication of current temperature storage tank(s).
Indication of minimum temperature storage tank(s).
Resettable to current temperature.
Indication of maximum temperature storage tank(s).
Resettable to current temperature.
Displays current return temperature
Yes
Yes
No
Yes
Yes
No
Heating, Cooling, Temperature difference controller T1…T6
No
1
Temperature difference controller for heat consumer fitted (not supplied as standard).
2
Antifreeze sensor
Indication of universal temperature measuring points (T6).
* Only displayed if temperature sensor fitted (not supplied as standard).
Operating hours for charging storage tank(s).
Resettable to 0 h.
1 2
Energy productivity for storage tank(s).
Resettable to 0 h.
No
No
Yes
Yes
Fig. 30
11.0
Commissioning of solar controller
Press or to scroll up or down to the required sub function.
The icon will flash, press to select the function. Reset by pressing or for increase/decrease values. Press press to confirm and disappears.
ok?
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if necessary, changed. The default factory setting will usually give efficient and problem free operation. However Baxi recommend the following parameters marked * must be left at the default settings. Any change to the Baxi recommended settings will invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Indication Meaning Value range
Typical adjustment
Indication max
65 °C
Maximum permissible temperature
(15 - 95°C
Tank 2)
Storage tank 1 or 2: switch-on differential (dTon)
3 - 40K
65°C*
MAX
7K dT max
7 K dT min
3 K
Min
100
13:21
40 °C
Storage tank 1 or 2: switch-off differential (dToff)
2 - 35K 3K
2
Adjustment of pump rotational speed.
100% = rotational speed regulation set to 'off'
30% - 100% 100%
Time
0:00 - 23:59 12:00
Switch-on temperature for
Heating/Cooling function
20 - 90°C 40°C dT min
3K min
00:00
1(2,3) max
23:59
1(2,3) min
06:00
4 max
20:00
4 dT
10 K
Hysteresis for Heating/Cooling function
1 - 30K 10K
Meaning
Temperature difference controller.
Hysteresis dT min
Timeframe 1(2,3): Start
Value range
2 - 35K
Typical adjustment
3K
0:00 - 23:59 00:00
Timeframe 1(2,3): Stop
0:00 - 23:59 23:59
Timeframe 1(2,3): Start for the collector function 0:00 - 23:59 06:00
Timeframe 1(2,3):
Stop for the collector function 0:00 - 23:59 20:00 dT max
7K
Temperature difference controller. Hysteresis dT max
3 - 40K 7K
© Baxi Heating UK 2012 27
Fig. 31
Indication
3
11.0
Commissioning of solar controller
Press or to scroll up or down to the required sub function.
The icon will flash, press to select the function. Reset by pressing or for increase/decrease values. Press press to confirm and disappears.
ok?
11.5
Menu “Manual operation”
1. For commissioning, service and test purposes the solar primary system can be manually operated. For this purpose the switch outputs may be disconnected or connected.
WARNING - During manual operation there is no automatic regulation of the system. Temperature control is isolated.
System temperature could be extremely high.
2. To avoid inadmissible operating states this mode of operation changes into “Indication” after approximately 8 hours and the automatic regulation is activated again.
NOTE: Exiting this menu will automatically return the system to normal operation.
Meaning
Switching on/off switch output A1 (solar circulation pump) by hand.
Value range
0 = off
1 = on
Switching on/off switch output A2
(pump2/valve1) by hand.
0 = off
1 = on
Switching on/off switch output A3 (cooling, thermostat or 2 nd
temperature difference controller function) by hand.
0 = off
1 = on
28 © Baxi Heating UK 2012
Fig. 32
11.0
Commissioning of solar controller
Press or to scroll up or down to the required sub function.
The icon will flash, press to select the function. Reset by pressing or for increase/decrease values. Press press to confirm and disappears.
ok?
Indication
Line / value
0 -- 0
1 -- 120 °C
Description
Collector protection function
Collector protection function
Value range
Factory set - up
0 = off
1 = on
110..150°C 120°C
2 -- 0
3 -- 40 °C
4 -- 0
Recooling function
(only if the collector protection is on)
Recooling storage tank temperature
Tube collector function - time-controlled
0 = off
1 = on
30..90°C 40°C
0 = off
1 = on
5 -- 2
Note: This Solar Controller has the ability to calculate the energy yield without the use of a flow meter. The Flow
Meter is now available as an accessory - Code no. 5122979.
6 -- 11
7 -- 100
Energy yield measurement 'Off'
0
Energy yield measurement with flow meter
Energy yield measurement without flow meter
Energy yield measurement - sets glycol type
Energy yield measurement - glycol mixture
1
2
0…11
0 ... 100%
5% - steps
-----
No value shown, when item 5 is set to 0
8… 10
Adjustment value when item 5 is set to 1
0.5 – 25Litres per impulse
2
11
100
10
11.6
Menu “Basic adjustment”
1. Adjustment and changes in this menu must be carried out only by a competent installer or service engineer.
Incorrect adjustments may adversely affect the function of controller and solar primary system.
2. To avoid accidental changes in menu “Basic adjustment”, it is not editable in normal functioning but has only a display function. To be able to carry out any changes, this menu must be chosen within the first minute after switching on the appliance. The basic adjustment menu is ‘blocked’ automatically one minute after switching on if the menu is not accessed.
9 -- 240
10 -- 1
11 -- 0
12 -- 6
13 -- 3°C
14 -- 2
15 -- 5
16 -- 0
Multiple tank storage systems.
Controller response time in seconds
30 - 480 240
First priority storage tank selection
Antifreeze function
Anti-freeze function.
Reference sensor selection
Anti-freeze function start temperature
1 - 2
1 = on
1 - 6
-20 °C ... +7 °C
Independent controller function
Independent controller reference sensor
System diagram
0 = off
1 = cooling
2 = thermostat
1 - 6
0 - 4
1
0 = off
6
3
2
5
0
3
4
5
0
1
2
© Baxi Heating UK 2012
Anro
IIexan E, Glythermin
Antifrogen L
Antifrogen N
IIexan E
IIexan P
9
10
11
6
7
8
Tyfocor L5.5 - supplied
Dowcal 10
Dowcal 20
Dowcal N
Tyfocor LS
Fernox S1
For correct operation of the system, Baxi recommend the settings shown above.
29
11.0
Commissioning of solar controller
11.7
Overview of display and operating elements
Fig. 33
Graphic symbol Description
Measuring points assignment
Temperature measuring point collector array 1
Temperature measuring point collector array 2
Temperature measuring point storage tank 1 solar
(storage tank 1 charging)
Temperature measuring point storage tank solar
(storage tank 2 charging)
Temperature measuring point collector - return
Temperature measuring point storage tank
(auxiliary heating)
Antifreezing sensor or universal temperatures measuring point (T6) (no sensor monitoring)
Auxiliary heating temperature
!
ok?
Indication in operation
Operating hours, energy productivity measurement
Status indication
Solar circulation pump Symbol revolves when solar circulation pump is on
Switch output 1 is active
Switch output 2 is active
Switch output 3 is active
Reference to system fault
Safety query for value changes which are to be stored
Appears when switch output 1 is active (on)
Appears when switch output 2 is active (on)
Appears when switch output 3 is active (on)
Display flashes when a fault occurs in the system
Input value can be either rejected or accepted
30 © Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.8
Overview of display and operating elements
(cont)
Fig. 34
Graphic symbol dT min max min
0:00
1
Max
23:59
1
ºC
K h kWh
Description
Indicator values
Temperature difference
Min value
Max value
Time period 1 start
Indication in operation
Appears when minimum values are indicated
Appears when maximum values are indicated
Appears when the differential controller is active
(timeframe 1-3) or tube collector is active (timeframe 4)
Time period 1 stop Appears when the differential controller is active
(timeframe 1-3) or tube collector is active (timeframe 4)
Display of all values, display flashes when a value is changed
5 x 7 segment display.
Presentation of figures 00000 to 99999
Temperature in Celsius
Temperature difference in Kelvin
Operating hours
Productivity indication in kWh
© Baxi Heating UK 2012 31
32 © Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.9
Controller functions
1. The differential temperature controller contains many functions to regulate and monitor the solar primary system.
Including
- controller functions for heating the solar cylinder
- functions for system protection and system monitoring
- additional functions (other accessories may be required to achieve these functions).
11.10
General controller functions
1. The controller collects the temperatures from various measuring points and determines the right time to charge the storage tank on account of programmed (additional) functions and controller parameters.
11.11
Cylinder heating by solar primary system
1. Switching action can be adjusted through dTmax (dTon) and dTmin (dToff). The solar cylinder is heated by operating the solar pump on output A1 up to the set maximum storage temperature (65°C). Pump operation starts when the collector temperature exceeds the cylinder temperature by more than dTon and continues while the collector temperature is above cylinder temperature + dToff, as set in the programming menu. dTon cannot be set lower than dToff
+ 1K.
Corresponding values in menu
“Programming”
Maximum temperature dT max (dT on)
Switch-on temperature difference dT min (dT off)
Switch-off temperature difference
11.12
Systems with two storage cylinders
1. For systems with more than one storage cylinder (System
Type 2) the cylinder heating can be optimised depending on the energy supply. Usually the cylinder with lower priority will have a lower temperature than that with the higher priority.
Re-directing the energy to the lower priority cylinder will lower the temperature in the collector array.
2. To check the collector temperature the heating of the lower priority cylinder will be interrupted for a short while at fixed intervals. If the heating requirement for the higher priority cylinder is fulfilled then the lower priority cylinder will be heated.
3. The higher priority cylinder can be selected in the
“Basic Adjustment” menu point no. 10.
11.0
Commissioning of solar controller
11.13
Rotational speed regulation
1. The solar circulation pump on 230V-outputs A1 and A2 can be operated either in switch-mode (two-point controller) or in a rotational speed regulated way. If the rotational speed regulation is activated the pump power is adjusted by a controller so that switch-on temperature difference “Storage tank dTmax” is kept constant as much as possible. At lower deviation of “Storage tank dTmax” the pump is operated with the lowest power till the switch-off wave is reached.
“Basic adjustment”
--dT
10k
TTh
40ºC on
A3 off
Fig. 35
T[ºC]
Thermostat
(Storage top)
Heating on (A3)
Corresponding values in menu
“Programming”
Rotational speed min <100% t
11.14
Thermostat (heating)
1. The thermostat is an independent control circuit from the storage loading. Thus, auxiliary heating of the top area of the storage cylinder is made possible.
The output A3 will be:
• Switched on, when the temperature falls below the adjusted start level.
• Switched off, when the temperature reaches the adjusted start level + hysteresis.
“Basic adjustment”
14 -- 2
15 -- 5
Corresponding values in menu
“Programming”
Start temperature max ºC
Hysteresis dT in K
Time period (1…3) Start: min time
Time period (1…3) Stop: max time
“Basic adjustment”
14 -- 1
15 -- 5
11.15
Thermostat (cooling)
1. In order to optimise the energy yield, it could be useful to
“redirect” the solar energy, or to take it away from the storage when the storage temperature reaches a pre-set level.
When the sensor reaches the start temperature, output A3 will be switched on. When the temperature level falls below the start temperature hysteresis, the output A3 will be switched off.
Corresponding values in menu
“Programming”
Start temperature max ºC
Hysteresis dT in K
Time period (1…3) Start: min time
Time period (1…3) Stop: max time
© Baxi Heating UK 2012 33
“Basic Setting”
4 -- 1
Indication
X
11.0
Commissioning of solar controller
11.16
Tube collector
1. The function “tube collector” can be switched off/on in the
“Basic setting” menu – point 4. Timeframe 4 in the “Program” menu makes it possible to activate this function during certain periods of the day. When activated, the solar pump will be switched on every 30 minutes for a period of 30 seconds to check for any heat gain in the collector.
Corresponding values in menu
“Programming”
Time period (4) Start: min time
Time period (4) Stop: max time
11.17
Sensor monitoring
1. The sensors and their connecting cables are constantly monitored for any break or short circuit. If a faulty sensor is
!
scrolling up and down you can detect the source of the error.
!
The use of the wrong type of temperature sensors can also give to an error message
Meaning
Short circuit on temperature sensor of the current measuring point
Break on temperature sensor of the current measuring point, circulation error at activated energy productivity measurement
34 © Baxi Heating UK 2012
Indication
+ !
11.0
Commissioning of solar controller
11.18
Flow monitoring
1. If during normal operation the flow temperature rises above
90°C a warning indication will be shown.
2. If the energy productivity measurement option is deactivated, the temperature difference between collector and storage tank is checked. If the temperature differential exceeds
60K + dTmax an error message will occur, as under normal system operation where the pump is running, large temperature differences would not normally be seen.
3. If the energy productivity measurement option is activated, the flow rate is checked, if no flow is detected for 15 minutes an error message will be seen (Applicable if Flow Meter fitted).
NOTE: these error conditions will automatically reset after a short period of operation once normal flow/temperature conditions are restored.
Meaning
Fluid flow is above 90°C (indication) / Missing circulation in solar circuit
11.19
System protection function
1. The system protection function switches the system off if the
“maximum collector temperature” is exceeded by 10K. As soon as the temperature drops below the “maximum collector temperature”, the system restarts. This function has priority and is always active, regardless of whether the collector protection is on or off.
11.20
Frost protection
1. This function can be switched on or off by using item 11 in the “Basic adjustments” menu. The start temperature can be adjusted with item 13. Furthermore, a frost protection sensor can be selected (T1-T6, point 12).
2. If the measured value is lower than the start temperature, the solar pump is activated until the adjusted frost protection start temperature +5K is reached. The minimum runtime of the pump is 5 minutes.
3. For safety reasons the function is deactivated if the temperature of the priority storage falls below 5ºC.
© Baxi Heating UK 2012 35
“Basic Setting”
5 -- 1
11.0
Commissioning of solar controller
11.21
Energy productivity measurement
1. For the purposes of energy productivity measurement (solar gain), a sensor on the collector return line and an optional flow meter are required. The yield value is calculated from the values of the temperature difference between the collector and collector return line and the value measured by the flow meter. This function is switched on and off in the “Basic settings” menu.
Corresponding values in menu
“Programming”
---
“info”
XXXX kWh
11.22
Operating hours meter
1. When the storage tank is being charged by a pump, the operating hours meter records for each separate pump. The number of operating hours can be read in the “info” menu.
This may be reset to ‘0’.
“Programming”
---
Corresponding values in menu
“info”
XXXX h
36 © Baxi Heating UK 2012
Fig. 36
2
Table 1
Flow rate
(when system is cold)
Area
2m 2
3m 2
4m 2
5m 2
6m 2 l/min
2 - 4
3 - 6
4 - 8
5 - 10
6 - 12
Fig. 37
5
4
3
1
3
1
12.0
Setting the system flow rate
12.1
Checking and adjusting the flow rate
1. Adjust the flow rate when the system is cold (approx 20°C)
(see Fig. 36).
2. The flow rate should be adjusted to give the optimum flow rate depending on the number and type of collector(s) connected.
3. Manually operate the solar pump (See Section 11.5).
4. Set the solar pump speed selector (Fig. 36 Item 5) so that the required flow rate is achieved or exceeded with the lowest possible setting. The flow limiter adjusting screw (Fig. 36
Item 3) can be used to fine-tune the flow rate.
5. Depending on the number and type of collectors installed, set the required flow rate from table (See Table 1).
6. The float in the flow meter will indicate the circulation flow rate through the flow meter sight glass (Fig. 36 Item 4).
7. Adjust screw of the flow limiter (Fig. 36 Item 3) with a screwdriver, until the upper edge of the float in the sight glass indicates the required flow rate (Fig. 36 Item 4). Turn the screw anticlockwise to increase the flow.
8. Ensure that the float is stable when the pump is running.
9. Set manual pump operation to off (See Section 11.5).
12.2
Installation of the thermal insulation
1. Refit the controller mounting moulding (Fig. 37 Item 1) onto the rear moulding.
2. Push the front thermal insulation (Fig. 37 Item 2) against the rear thermal insulation section (Fig. 37 Item 3) until it clips into place.
2
© Baxi Heating UK 2012 37
Commissioning record
The following chart should be completed during Commissioning of the system.
Installer: _______________________________ BPEC No.:
Contact details: _______________________________
_______________________________
Serial Nos. Cylinder _______________________________
Original commissioning date: _______________________________ Collector _________________
General Commissioning
Pump Station Serial Number: ___________________________
Solar differential temperature controller - operational parameters
All pipework correctly installed, identified and earth bonded
❑
If any factory values are changed please enter the new values in the table below.
Solar expansion vessel charge pressure checked and set before filling the system
Solar primary system filled with heat transfer fluid supplied
System pressure test carried out
Air vented from system
Exposed pipework insulated using high-temp and weather resistant insulation (bird/rodent-proof) collector installation weatherproof
Collector fixings checked and secure
Hydraulic Station
System pressure when cold
Solar primary flow when cold
Isolating/non-return valves (flow and return) in operating position
❑
❑
❑
❑
❑
❑
❑
❑ bar bar l/min
Adjustable in menu
"Programming"
Storage tank1:
Maximum storage temperature
Storage tank1: switch-on difference (dTon)
Storage tank1: switch-off difference (dToff)
Storage tank2:
Maximum storage temperature
Storage tank2: switch-on difference (dTon)
Storage tank2: switch-off difference (dToff)
Minimum pump power on rotational speed regulation
Switch-on temperature of thermostat function
Hysteresis of thermostat function
2nd temperature differential controller maximum temperature Tmax
2nd temperature differential controller hysteresis dTmax
Typical
7 K
3 K
100%
40°C
10 K
65°C
7 K
Current adjustment adjustment
65°C
7 K
3 K
90°C
*
*
Solar Collectors
Collector visually inspected for defects
Collector temperature sensors correctly installed and secured
Pipe entry points to building weatherproof
Solar Differential Temperature Controller
Record all operational parameters set
(see separate table)
Pump operation tested in automatic and manual modes
All cables correctly installed and secured
Suitably fused isolating device installed
Controller earthed
Solar Cylinder
Cylinder installed and commissioned in accordance with cylinder installation instructions
❑
❑
❑
❑
❑
❑
❑
❑
❑
Adjustable in menu
"Basic adjustments"
Switching on or off the function collector protection
Temperature at which the collector protection function is active
Switching on or off the function recooling (only when the collector protection is on)
Temperature to which the storage tank is recooled when collector protection function is on
Function for time-controlled circulation in operation with tube collectors
Switching on or off the function energy productivity measurement
Choice of glycol types used
Mixture ratio of coolants
Litres per min
Switching on or off the function antifreezing
Temperature at which the antifreezing is active
Alternative choice of the cooling, thermostat function or the 2nd temperature differential controller
System type
Time control in secs
Storage priority
Typical
0 = off
120°C
0 = off
40°C
0 = off
2 = on
0 = Anro
50%
10 l/m
0 = off
3°C
2 type 0
240
1
Current adjustment adjustment
*
*
*
*
* Baxi recommends these settings are left at the default value.
38 © Baxi Heating UK 2012
© Baxi Heating UK 2012 39
40 © Baxi Heating UK 2012
13.0
Maintenance
13.1
Check heat transfer fluid
1. The heat transfer fluid must be checked every year with regard to its antifreeze and pH value. (7.0 - 9.5)
- Check antifreeze using antifreeze tester. Target value is approximately -21 deg C (40% concentration).
Replace fluid if necessary.
13.2
Maintenance of the collector
1. The collector or the collector array must be checked/serviced annually to check for any damage, leaks or contamination.
2. In areas where there may be a build up of dirt on the collector, only non-abrasive cleaning materials and methods should be used to clean the collectors and mounting system components.
13.3
Cylinder
1. Refer to manufacturer’s documentation.
© Baxi Heating UK 2012 41
14.0
Fault finding
14.1
Failures with error message
1. Some system failure modes can be recognised by the solar differential temperature controller and will be indicated by an error message on the controller display. Refer to the table below for details of possible errors and suggested measures to rectify.
NOTE: These error messages wil automatically reset when the fault has been rectified. In the case of the circulation error this may take a few minutes to clear once normal flow has resumed.
Error representation on display Possible reasons
• Sensor wire broken
!
flashing
• Sensor defect
• Sensor missing
!
flashing
Circulation error: no flow
+ flashing
!
Additionally at energy productivity measurement:
• Short circuit in sensor wire
• Sensor defect
• Error in pump connection
• Pump defect
• Air in the system
• Connection with flow meter defect
• Sensor wire broken
• Sensor defect
• Sensor missing
Measures
• Check wire
• Check sensor resistance, if necessary exchange sensor
• Check parameter settings and sensor installation requirements
• Check wire
• Check sensor resistance, if necessary exchange sensor
• Check cabling
• Exchange pump
• Check the float of the flow meter moves when the system runs (if visible)
• Check wire
• Check wire
• Check sensor resistance, if necessary exchange sensor
• Check parameter settings and sensor installation requirements
42 © Baxi Heating UK 2012
No display at solar differential temperature controller
Is the 230/240V~ power supply correctly wired
NO
Correct any wiring faults
YES
Is the 230/240V~ power supply switched on
NO
Switch on power supply
YES
Has thermal cutout on cylinder operated
(unvented systems only)
YES
Reset thermal cutout.
Investigate cause of operation and rectify
Note: Allow the cylinder to cool or draw off the hot water before resetting
NO
Is the 230/240V~ power supply at the controller terminal block
NO
YES
Check wiring and rectify
Is internal fuse operational
YES
Controller fault
Replace controller
NO
Replace internal fuse
14.0
Fault finding
Resistance table PT1000.
The correct function of temperature sensors can be checked on the basis of the following temperature resistance table with a resistance measuring instrument:
Temperature in ºC
-30
-20
-10
0
10
20
30
80
90
100
120
140
200
40
50
60
70
Resistance in Ohm
882
921
960
1000
1039
1077
1116
1309
1347
1385
1461
1535
1758
1155
1194
1232
1271
© Baxi Heating UK 2012 43
14.0
Fault finding
Pump symbol on controller rotates but pump does not operate
Is controller to pump connection correct and secure
NO
YES
Check connections and rectify as necessary
Is the pump siezed
YES
Can the impeller be revolved using a screwdriver after removing the air bleed screw
NO
YES Free impeller and replace air bleed screw
NO
Pump fault
Replace pump
Displayed temperatures on controller vary greatly over short time intervals
Are sensor cables laid alongside mains voltage cables
NO
YES
Seperate sensor cables from mains cables (Min. 50mm recommended) or use shielded cable
Have sensor cables been lengthened with unshielded cable
NO
YES Use shielded cable to extend sensor cable lengths
Do sensors give correct temperature v resistance readings
YES
Controller fault
Replace controller
NO
Are sensor connections correctly made
YES
Sensor fault
Replace sensor
NO
Rectify sensor connections
44 © Baxi Heating UK 2012
J1
E1
K1
1
C1
D1
L1
A1
F1
G1
15.0
Spares
15.1
Spare parts and Accessories
1. A number of Spare Parts are available should any part of the system require replacement. Use only genuine parts obtained from Baxi, use of other non Baxi parts may cause system malfunctions and will invalidate the warranty. Fitting of any spare parts must be carried out by a competent installer or authorised service engineer or agent.
Short Parts List
G1
J1
E1
F1
K1
L1
C1
D1
A1
B1
Key
No.
Description
No.
Connection Washer
Temperature Sensor
Solar Differential Temperature Controller
Insulation
Insulation Insert
Safety Group
Solar Primary Circulating Pump
Temperature Gauge
Solar Expansion Vessel 24Litres
Expansion Vessel Self-sealing Connection
Manufacturer’s
Part No.
5119535
720224801
720709001
720689701
720689901
720690901
720688101
720689101
5119548
5119779
© Baxi Heating UK 2012 45
46 © Baxi Heating UK 2012
16.0
Warranty
16.1
Standard Warranty Terms & Conditions
Flat Plate Solar Collectors 10 Years
Evacuated Tubes Collectors 5 Years
Solar Control Station 2 Years
To receive your free warranty please complete the form supplied with the system within 30 days of installation, or simply call heateam, the service division of Potterton on 0844
871 1568
Our promise to you
If you experience a fault with your new Solarflo system, we aim to provide a safe and high quality repair service supported by our dedicated national network of highly skilled engineers. If your installer can't resolve the problem for you, we will do everything we can to get an engineer out to you as quickly as possible. Nothing in this warranty will affect your statutory consumer rights.
What you need to do if you experience a problem with your system.
You should always contact your installer first because the fault may not be related to the Solarflo installation. If your installer confirms that the fault is within the Solarflo system itself and he/she decides they cannot repair it our friendly customer service team is on hand to help. Simply call our service division heateam on 0844 8711568 informing the operator that you are a Solarflo customer. They will be able to provide you with technical help or assist with booking an engineer visit if required. Our contact centre is open Monday to Friday 8am -
5pm, excluding Christmas Day and New Years Day.
When calling heateam you must have the following information to hand: -
Solarflo serial number (Affixed to Solar controller)
Solarflo system model number (Affixed to Solar controller)
Your Postcode and House Number
Your installer name, address details and contact details
Proof of purchase (if you do not have the Solarflo serial number or model number)
What this warranty covers
1. Free of charge repair or replacement of components found to be faulty from manufacture.
2. Free of charge replacement of the complete assemblies provided always that the failure is related to a manufacturing fault that cannot be repaired or is beyond repair.
3. The warranty runs from the date your product is installed.
What this warranty does not cover
4. Solarflo collectors that are installed damaged or damaged during installation. If a Solarflo collector is found to be damaged on delivery then it must not be installed, simply return it to your supplier for replacement under warranty.
5. Correctly specified solar fluid will protect the installation down to outside temperatures of -20°C. System failure resulting from incorrect fluid (thereby resulting in freezing fluid in the system) is not covered under warranty.
6. The warranty will become invalid if the failure is due to frost damage (see point 5), transient voltages, lightning strikes or any act of vandalism or misuse.
© Baxi Heating UK 2012
16.0
Warranty
16.1
Standard Warranty Terms & Conditions (cont)
7. This guarantee does not cover the effects of scale.
8. Tampering or modification will invalidate this warranty.
9. The installation must be in an appropriate location and its use is restricted to potable water.
10. Baxi Heating UK Ltd will only carry out warranty repair/replacement to Solarflo collectors which have safe access and that meet current Health & Safety working at heights requirements. The customer will cover the cost of any safety equipment e.g. scaffolding and lifting equipment etc. that is required to meet this standard and will appoint a contractor to carry this work out. heateam accepts no liability for any third party damage.
11. Repairs to Solarflo system that haven't been installed and commissioned properly, as set out in the installation and commissioning instructions.
12. Any other defects or failures, either in the connected system or outside of the Solarflo system itself
13. Installations within commercial settings for which this
Solarflo system was not designed.
14. Reimbursement of any third party repair or replacement costs that we haven't been told about and agreed with you in advance.
15. Compensation for consequential losses (e.g. loss of earnings, business losses, stress and inconvenience) arising from a product breakdown, including repair delays caused by factors outside our reasonable control.
16. heateam will not be liable for failures resulting from fair wear and tear, willful or accidental damage, negligence, abnormal working conditions, failure to comply with instructions (whether oral or in writing), misuse or alteration of the product without heateam’s approval.
17. Defects which are reported out with the warranty period will not be covered by this warranty.
18. Installations which have not been carried out by fully trained and competent person(s) will not be covered by this warranty.
19. Products that have been subjected to the following conditions will not be covered by the warranty: a) prolonged stagnation conditions or products that exhibit signs of extreme temperature exposure b) acts of god, explosions, floods, tempests, inclement weather, fire or accident c) war, sabotage, insurrection , civil disturbance or requisition d) acts, restrictions, regulations, by-laws, prohibitions or measures of any kind on the part of any Governmental,
Parliamentary or Local Authority e) theft or malicious damage
47
All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request.
B AXI
A Trading Division of Baxi Heating UK Ltd (3879156),
Brooks House, Coventry Road, Warwick. CV34 4LL
Technical Enquiries 0844 871 1568
Our contact centre is open Monday to Friday 8am to 6pm,
Weekends and Bank Holidays 8.30am to 2pm.
We are closed Christmas Day and New Years Day.
Website www.baxi.co.uk
e&oe
© Baxi Heating UK 2012
Comp No 720669102 (5/12)
Advertisement
Key features
- Solar energy capture
- Heat transfer fluid circulation
- Solar storage cylinder
- Supplementary heating
- Reduced fossil fuel reliance
- Up to 60% hot water requirement