ENDA ETC1311 DIGITAL THERMOSTAT
Thank you for choosing ENDA ETC1311 temperature controller.
* 35 x 77mm sized.
* On-Off control.
* TC Typ “J” or “K” or Pt100 input.
* Temperature compensation.
* In the case of probe failure, heating can be selected on, off or periodical running.
* Upper and lower limits of the setpoint can be adjusted.
* Set value can be adjusted by using single key.
* Having CE mark according to European Norms.
OUT
ENDA
°C
ETC1311
Order Code : ETC1311---
1 2 3
1 - Input
FE.....Fe-Const (J)
RT.....Pt100
K.......NiCr-Ni (K)
2 - Supply Voltage
230VAC...230V AC
24VAC.....24V AC
12VAC.....12V AC
SM...........9-30V DC / 7-24V AC
Attention !
3 - Output
P......... Relay-16A
None...Relay-8A
SSR....Logic output
ENDA ETC1311 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations. During an installation, all of the cables that are connected to the device must be free of energy.
The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. The cables should not be close to the power cables or components.
ENDA
INDUSTRIAL ELECTRONICS
ETC1311-K-230VAC
DIGITAL THERMOSTAT
SN: XXXXXXXXX
ENDA
INDUSTRIAL ELECTRONICS
ETC1311-FE-230VAC-P
DIGITAL THERMOSTAT
SN: XXXXXXXXX
ENDA
INDUSTRIAL ELECTRONICS
ETC1311-RT-12VAC
DIGITAL THERMOSTAT
SN: XXXXXXXXX
K (NiCr-Ni) J (Fe-CuNi)
Pt100
-
+
1 2 3 4 5 6 7 8 9 10 11 12 1 2
Equipment is protected throughout by DOUBLE INSULATION.
3 4 5 6 7 8
-
9 10 11 12
+
1 2
Holding screw 0.4-0.5Nm
3 4 5 6 7 8 9 10 11 12
NOTE:
SUPPLY:
184-253V AC
50/60Hz 3VA
4
5
Line
Neutral
Fuse
F 100 mA
250V AC
Switch
230V AC
Supply
Fuse should be connected
Cable size: 1,5mm²
Note:
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator.
Technical Specifications
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50°C/-25 ... 70°C (with no icing)
Max. relative humidity
Rated pollution degree
31°C decreasing linearly 50% at 40 °C
According to EN 60529 Front panel : IP65
Rear panel : IP20
Height
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gasses.
ELECTRICAL CHARACTERISTICS
Supply voltage /
Power consumption
Wiring
Scale
230VAC +10%/-20%, 50/60Hz, 24VAC±10%,50/60Hz or 24Vac/dc (9-30Vdc or 7-24Vac)
Max. 4VA
2.5mm² screw-terminal connections.
TE Typ “J” or “K”: 0 ... +600°C / Pt100: -100...600°C
Sensitivity/Accuracy
Indicator
EMC
± 0.5% (of full scale) / ± 1 digit
3 digits, 14mm, 7 parts red LED
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
Safety requirements EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
OUTPUT
HEAT OUT
Life expectancy for relay
For ETC1311-XX ; Relay: 250V AC, 8A( for resistive load ), NO+NC.
For ETC1311-XXP ; Relay: 250V AC, 16A(for resistive load), NO.
For ETC1311-XX ; Mechanical 30.000.000; Electrical 100.000 operation.
For ETC1311-XXP ; Mechanical 30.000.000; Electrical 30.000 operation.
CONTROL
Control type
Control algorithm
Hysteresis
Single-setpoint control
On-Off control
Adjustable between 1 ... 20°C.
HOUSING
Housing type
Dimensions
Weight
Enclosure material
Suitable for flush-panel mounting.
W77xH35xD71mm
Approx. 250g ( after packing the device and a probe )
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Dimensions
77mm
OUT
Depth
71mm
ENDA
°C
ETC1311
For removing mounting clamps:
Push out the flush-mounting clamp in direction 1 as shown in the figure below. Then, pull out the clamp in direction 2.
5mm
K (NiCr-Ni)
+
12
-
11 10 9 8 7 6 5 4 3 2 1
INDUSTRIALELECTRONICS
T THERMOSTA
-K-230VAC 11
DIGITAL
ETC13
ENDA
SN: XXXXXXXXX
Flush mounting clamp
1
Panel cut-out
71mm
Flush mounting clamp
2
Panel
Rubber packing
Note :1) Panel thickness should be maximum
7 mm.
2) If there is no 60mm free space at the back side of the device, it would be difficult to remove it from the
Panel
SURAN
Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
1./2 ETC1311-E
E-mail : [email protected]
Internet : www.suran-elektronik.de
HEATING OUT
LED Displayed process value in the run mode, parameter name or value in programming mode.
OUT
Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates.
°C
Used for selecting parameters and decreasing the setpoint value in the programming mode and for decreasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates.
ENDA ETC1311
Process
Value
Con
200
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode.
SET
While holding key, setpoint value of the selected parameter appears and by using and keys the value can be adjusted.
Run mode
SeC
199 200
If no key is pressed for 3 seconds
When pressed or key, temperature set value flashes and by using and keys the value can be adjusted.
If no key is pressed for 3 seconds run mode is returned.
SET
If key is pressed and held for 3 seconds, programming mode is entered.
Programming Mode
If key is pressed, run mode is entered.
SET
Con
Hys
Upl
LoL
Eon
Ect oFS
SEC
Aco
PARAMETER TABLE
Menu of Configuration parameters
MIN MAX UNIT DEF.SET
Switch hysteresis for the setpoint. (When temperature falls to SET-HYS, output relay becomes active.)
1 20 °C 1
The upper limit of the setpoint.
The lower limit of the setpoint.
LoL
0
600
UPL
0 100
°C 600
°C 0
In the case of error, on time rate of the relay output.
In the case of error, period of the relay output.
% Ect 0
10 250 sec 30
Offsetvalue (can be adjusted from -99...+99C° to a desired value)
Menu of Parameter security
Hys
Switch hysteresis for the setpoint.
Cod
Access code for menu of security.
Enter 311 then press key.
ASE
Security parameter for menu of configuration.
Non
Pye
=
=
Pno
=
Menu is invisible.
Parameters of menu are changeable.
Parameters of menu are only visible.
Security parameter for temperature set value.
Pye
=
Pno
=
Set value is changeable.
Set value is only visible.
Upl
The upper limit of the setpoint.
Lol
The lower limit of the setpoint.
Aco
Ase
Security parameter for menu of configuration.
Non
= Menu is invisible.
Pye
Pno
= Parameters of menu are changeable.
= Parameters of menu are only visible.
Security parameter for temperature set value.
Pye
= Set value is changeable.
Pno
= Set value is only visible.
Eon
In the case of error, on time rate of the relay output.
Error Messages
---
Means, temperature value is higher than the scale.
___
Pfa
Means, temperature value is lower than the scale.
Means, temperature sensor is broken or over temperature.
Ect
In the case of error, period of the relay output.
oFS
Offsetvalue (can be adjusted from -99...+99C°)
2./2 ETC1311-E