Multi Zone Specification Hybrid Flex Inverter Submittal Data

Multi Zone Specification Hybrid Flex Inverter Submittal Data
Multi
Zone Specification
AUU9RLF and UTG-CCGF
Hybrid Flex Inverter Submittal Data
AUU9RML
Compact Cassette and Grille
Multizone Cassette
Job Name:_______________________________
Location: ________________________________
Engineer:________________________________
Submitted to: _____________________________
Submitted by:_____________________________
Power
V/Hz/P
230/60/1
Fan type
Turbo
Motor Type
E.C.M.
No. Motors
(W)
42-1
CFM
(Hi,Me,Lo,Qu)
318/288/259/230
Sound Pressure Level db (Hi,Me,Lo,Qu)
33/31/29/27
.15
F.L. A.
(A)
Refrigerant
410A
O.D. Discharge
in (mm)
1/4”(6.35)
3/8”(9.52)
O.D. Suction
in (mm)
Dimensions
HxWxD
Unit Uncrated
(in)
9-21/32 x 22-14/32 x 22-14/32
(mm)
(245x570x570)
Unit Crated
(in)
10-7/16 x 28-3/4 x 24-19/32
(mm)
(265x730x625)
Panel Uncrated
(in)
1-15/16 x 27-9/16 x 27-9/16
(mm)
(49x700x700)
Panel Crated
(in)
4-23/32 x 30-1/8 x 29-23/32
(mm)
(120x765x755)
Weight
Unit Net
lbs. (kg)
33 (15)
Unit Gross Shipping
lbs. (kg)
40 (18)
Panel Net
lbs. (kg)
5.7 (2.6)
Panel Gross Shipping
lbs. (kg)
10 (4.5)
Approval:_____________________Date:_______
Construction: ____________________________
Unit #:__________________________________
Drawing #:_______________________________
Reference:_______________________________
Cooling Capacity
Moisture Removal
(BTU/h)
pt/h (l/h)
_
9,000
2.5 (1.2)
Heating Capacity
(BTU/h)
___________
10,200
Temperature Setting Range
Cooling
°F(°C)
64~90 (18~32)
Heating
°F(°C)
60~88 (16~31)
Drain Pipe Size
OD in (mm)
Ø1 (25.4)
ID in (mm)
Ø3/4 (19.4)
Condensate Pump Lift*
in (mm)
28 (700)
Remote Control Type
Wired (Wireless Optional)
Electrical Connection**
AWG
14/3 with ground
*Pump is capable of providing 28” of lift at no more than 6” away
from the unit. Lift is measured from the suction of the pump which
is located at the bottom of the unit and not the outlet of the
condensate.
**Power and communication are fed from the outdoor unit.
Grille
(sold seperately)
Unit
Fujitsu General America, Inc.
Fairfield, NJ 07004
Toll Free: 1-888-888-3424
Fax: (973) 836-0447
www.fujitsugeneral.com
Note: Specifications are based on the following conditions.
Power source of specifications : 230V
Cooling: Indoor temperature of 80°F(26.67°C)DB / 67°F(19.44°C)WB, and outdoor temperature of 95°F(35°C)DB/75°F(23.89°C)WB.
Heating: Indoor temperature of 70°F(21.11°C)DB / 60°F(15.56°C)WB, and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB.
Pipe length : 16ft. (5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit]
Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]
Fujitsu products are subject to continuous improvements. Fujitsu reserves the right to modify product design, specifications and
information in this data sheet without notice and without incuring any obligations.