EUTECH INSTRUMENTS | ALPHA COND 550 - REV 5 | User manual | Thermo Scientific Alpha Process Products
Add to my manuals24 Pages
advertisement
Thermo Scientific
Alpha Process Products
•
Thermo Scientific Alpha 2000 Series Controllers
pH
•
ORP
•
Conductivity
•
Dissolved Oxygen
One Source.
Total Solution
Recognised internationally for industry-leading quality and accuracy, companies all over the world choose
Thermo Scientific Process Products for reliable process monitoring and control across a broad range of water and wastewater applications:
• Wastewater Treatment
• Drinking Water
• Chemical Processing
• F&B Manufacturing
• Seawater Desalination
• Pharmaceutical
• Power
• Electroplating
• Semiconductor
Consistent monitoring and control of water quality are vital in many industries. Thermo Scientific products are built to stand up to the demands of on-line continuous use, even under the most severe conditions. With the Alpha 2000 series, Thermo Scientific brings electrochemical processes in water and wastewater applications to a new level of reliability and versatility, offering flexible process control at an excellent price point.
Whether it’s pH, ORP, Conductivity or
Dissolved Oxygen you are measuring, the Alpha 2000 series delivers, accurately and consistently. Because at Thermo Scientific, reliability and ease-of-use aren’t just features – they’re fundamentals.
Reliability and ease-of-use aren’t just features – they’re fundamentals
2 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Thermo Scientific Alpha 2000 Series
Controllers/Transmitters:
The Controllers/Transmitters:
Thermo Scientific’s Alpha 2000
Series controllers combine simple six-button operation with exceptional performance. Reliable and durable, each controller is built for ease-ofuse and versatility, so it is easy to customise your processor according to your application needs. Meters come in ½ DIN wall and panel-mount or ¼ DIN panel-mount versions to suit your installation requirements.
•
•
•
Alpha pH 2000D
employs differential measurement technology, giving you a reliable system that measures pH/ORP accurately in harsh environments
Alpha pH 2000
features symmetrical mode of operation option for clear, accurate pH/ORP readings in electrically noisy environments
• With 4-cell and 2-cell electrode options, the
Alpha COND 2000
allows you to measure a broad conductivity range, from ultra-pure water to highly conductive samples
Alpha DO 2000
supports either galvanic or amperometric measurements, allowing a broad dissolved oxygen range of 0 to 20 ppm or 0 to 200 % saturation
The Electrodes:
Thermo Scientific offers a wide selection of process electrodes, buffers, standards and accessories to complement your process requirements.
• High-quality, double-junction
pH and ORP electrodes
with Kynar ® or
Annular PTFE reference junctions operate in environment from
0 °C up to 110 °C. Each electrode comes with integral low-noise semi-conductor cables (unless otherwise stated)
• 2-cell and 4-cell
Conductivity electrodes
that incorporate 3-wire
Pt100 for automatic temperature compensation. Durable, low maintenance electrodes built with
Titanium or SS316 give consistent performances in high temperature of up to 200 °C
•
Dissolved Oxygen electrodes
designed for minimal maintenance and quick, stable readings within short response time. Rugged and long-lasting galvanic electrodes require no warm-up time; low maintenance amperometric electrodes capture DO readings as low as 0.01 ppm
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 3
Main Features:
No Need for Recalibration
After Power-Failure
Built-in non-volatile memory retains calibration and setup information even when power is cut off
Push-Button Calibration
Quick, convenient and easy
Menu-Driven Controls
With intuitive prompts and Electrode offset adjustment from keypad connectors
Advanced Switch Mode
Power Supply (SMPS)
Auto-detection of power supply input from 80 V to
250 VAC/DC
Three Control Mode Options
Limit control mode for straightforward on/off operations, or proportional control mode and proportional integral control mode for processes that require finer controls
Front Panel
MIN Function
100% Yh
50%
Proportional Integral, Proportional or Limit Control, Operation of Relays
MAX Function
Relay tON
Pulse Length T tOFF
ON
Relay
Pulse Length T tON tOFF
ON
- Xw
0%
Xp
Prop.
Band SP 1 SP 2
Xp
Prop.
Band
Control Characteristic of Controller as Proportional Controller
+ Xw
OFF
Controller Signal of
Pulse Length Control
Time (S)
OFF Time (S)
Controller Signal of
Pulse Frequency Control
Three Layers of
Password Protection
Greater security against unauthorized or accidental tampering of data and critical settings
Minimal Maintenance
Required
Simply wipe occasionally with lint-free cloth to remove dust and dirt
Large UV Light-Protected
LCD Display with Backlight
For easy reading, even in dark places
IP66 (NEMA 4X) Rugged
Housing
Weatherproof and corrosion-resistant
Bi-Colour LEDs
Clearly indicates relay status and mode of operation. Visible even from a distance
Manual Override
Facilitates quick processing with direct control on closing pumps and cleaning system
4 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Liquid Ground
caters for symmetrical mode of operation to prevent measurement error in an electrically noisy environment
12 V DC Output
To power peripheral devices via controller
Two 4-20 mA or 0-20 mA
Current Outputs
Fully scaleable, galvanically-isolated outputs for parameter and temperature measurements. Out-ofrange current at 22 mA
Automatic Temperature
Compensation
Or manual temperature compensation without
ATC probe. 3-wire system compensates for cables line resistance errors. Independent settings for calibration and process temperatures for accurate temperature compensation
Installation and Wiring is
Easy
with pin terminals detachable blocks
Back Panel
Rated to IP66
(Nema 4X), the rugged weather-proof casing simplifies installation outdoors or indoors
Pipe Mount Wall Mount Panel Mount
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 5
Four Fully Programmable Relays
Two Independent Relays
allow combination of high and low settings
Wash Relay
for periodical, automated cleansing of sensors – essential for accurate measurements
Single-Pole-Double-Throw
(SPDT) Alarm Relay
alerts when readings fall outside set points.
Comes with usercustomisable time-delay for minimal false alarms
Hold Function
to tie in a float or flow switch or other control device to lock out control functions if chemical feed levels are low
Prevents “Chattering”
Separately adjustable high and low hystereses prevent relay from switching between on and off during rapid fluctuations around set-points
Multiple Mounting Options
Wall-mount, pipe-mount or panel-mount: Flexible mounting options to suit your environment
Thermo Scientific Alpha pH 2000D
Differential pH/ORP Controller/Transmitter:
pH/ORP:
The Alpha pH 2000D Controller/
Transmitter and combination electrode system employs differential pH measurement technology.
What’s unique about this system is the differential electrode, which uses a pH glass bulb in place of the conventional reference system, making it more resistant to contamination or fouling in harsh wastewater applications. Replaceable salt bridge and reference solution add lifespan to the electrode when junction clogs.
The result: a reliable, long-lasting and cost-saving pH measurement system for demanding environments.
The pH Differential Electrode:
• Cost Savings, Reduced Downtime and Maintenance Costs –
soiled salt bridge and buffer reference solution can easily be replaced at a fraction of the cost of a new combination electrode
• Automatic Temperature Compensation
–
built-in temperature electrode
• Use Any Buffer Standard from 2 to 10 pH as a Reference –
very useful for applications that require adjustable isopotential points
• Built-In Electronic Amplifier
provides a low impedance output from the electrode, and allows analyzers to be located up to 3000 feet away from the electrode
• Ground Rod Minimizes Electrical
Interference
from motors, pumps, transformers and ground currents
• Wide pH range of -2.00 to 16.00 pH at two-decimal accuracy
• ORP mode measures in mV or % concentration, with independent calibration modes
• Control and measure pH and
ORP simultaneously with master-slave operation by placing two controllers side by side
• Wall mount, pipe mount or panel mount options. Compact design of electrode with universal 1.5”
NPT mounting threads enables optimal mounting positions
Easy replacement of salt bridge
Active (process) pH/ORP electrode
Ground rod shields active pH/ORP electrode from electrical noise
Reference electrode
Viton ® reference o-ring offers excellent resistance to aggressive chemicals
Universal 1.5” NPT threads for optimal mounting
Short 6” body with six wrench flats for easy assembly
Smooth surfaces reduce chances of fouling
Larger refillable internal reference chamber minimises effects of dilution and extends electrode life
Replaceable quad junction salt bridge
Better protection of sensing electrode
6 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
About Differential pH Measurement:
The Conventional
Combination Electrode:
The conventional combination electrode consists of two parts: the glass electrode and the reference
(Figure 1)
.
The glass electrode contains a silver wire immersed in conductive solution. During measurement, the glass bulb and stem are the only parts which come in contact with the sample. Hence, contamination of the silver wire and conductive solution does not occur.
The reference electrode, on the other hand, is constructed simply with a porous junction and a silver wire. This porous junction allows the reference electrolyte to flow from its chamber to the sample, establishing a connection between the two. However, the porosity also allows contaminants to flow into the reference chamber, reacting with the electrolyte and/or silver wire.
The reference electrode is also susceptible to clogs. In the case of conventional combination electrodes, the entire electrode must be replaced due to a clogged reference electrode.
When contamination and clogging occurs, performance of the entire electrode is compromised.
The Differential Electrode:
The differential electrode replaces the exposed silver wire with a design built on the benefits of a pH glass electrode
(Figure 2)
.
Quadraple junction salt bridges and an electrolyte-filled chamber act as barriers to prevent contaminants from entering the inner chamber, while at the same time, allowing connection between the reference electrolyte and the sample.
In the event of clogs, the salt bridges and electrolyte are easily replaceable, reducing downtime and cost of maintenance.
An individual liquid ground is also built into the electrode, effectively eliminating noises from ground loops potential
(Figure 3)
:
(E1 – E3) – (E2 – E3) = E1 – E3
With these design improvements, the differential electrodes enjoy a longer lifespan in harsh wastewater environments as compared to conventional electrodes.
Measurement of pH in wastewater poses several challenges, one of which is fouling of the reference electrode system
Pre-Amplifier
pH
Glass
Electrode
(E1) pH
Reference
Electrode
(E2)
Figure 1: The conventional combination electrode is made up of a glass electrode and a reference electrode
Figure 2: Differential electrode replaces porous reference electrode with a glass electrode
Reference
Electrode
(E2)
Solution
Ground
(E3)
Process
Electrode
(E1)
Figure 3: Individual liquid ground loop eliminates noises from ground loop potentials
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 7
Thermo Scientific Alpha pH 2000 pH/ORP Controller/Transmitter:
pH/ORP:
Built for the rugged industrial environment, the Alpha pH 2000 transmitter comes with an option for symmetrical mode of operation, making it ideal for electrically noisy environments. IP65 NEMA 4X casing is weatherproof and corrosionresistant, protecting meter against harsh elements.
The Alpha pH 2000 is user-friendly and intuitive: controller alerts when meter or electrode requires maintenance, and provides troubleshooting prompts in plain language.
• Wide pH range of -2.00 to 16.00 pH at two-decimal accuracy
• ORP mode measures in mV or % concentration, with independent calibration modes
• Quick, easy push-button calibration with auto-buffer recognition.
Meter displays electrode status after each calibration
• Accepts Antimony electrodes – useful in applications involving
Hydrofluoric (HF) Acid
• Control and measure pH and
ORP simultaneously with master-slave operation by placing two controllers side by side
Asymmetrical
PE N L S
3
0 / PA
2 1 22 27
Temp.
pH
BNC
Measuring Cable pH Combination
Electrode
Symmetrical
PE N L S
3 2 1 22
0 / PA
27
Temp.
Potential
Matching Pin (PM) pH
BNC
Measuring Cable pH Combination
Electrode
Asymmetrical mode works well in environments with where there is little or no electrical noise. When there is electrical noise, the noise acts as a common signal and is picked up by both the pH and the reference electrodes. However, since the reference electrode is grounded to the ground potential of the amplifier, electrical noise will be present only on the pH electrode.
This noise is amplified along with the pH signal, which causes reading fluctuations in an electrically noisy atmosphere. Electrical noise from a DC source (as in an electroplating tank) will typically result in stable but incorrect values.
Symmetrical mode avoids grounding the reference electrode by reconfiguring the input to a floating differential mode. The electrical noise appears equally on the pH and reference electrodes, and is therefore rejected by the operational amplifier.
The Alpha pH 2000 transmitter offers an option for Symmetrical Mode of Operation. To take advantage of
Symmetrical operation, you must have an electrode with a solution ground (potential matching) pin.
If your electrode does not have a solution ground, be sure to set the controller to Asymmetrical mode.
8 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Specification Information pH/ORP Controller/Transmitter
Order Code
Part No.
pH:
Range:
Resolution:
Accuracy:
ORP:
Range:
Resolution:
Accuracy:
Temperature:
Range:
Resolution:
Accuracy:
Sensor:
Compensation:
Set point & controller functions:
Set point 1 (SP1) / set point 2 (SP2):
Switching pH hysteresis:
Switching ORP hysteresis:
Function (switchable):
Adjustable period with pulse length controller:
Adjustable period with pulse frequency controller:
Integral action time (IAT):
Pickup/dropout delay:
Wash cycle:
Wash duration:
Contact outputs:
Switching voltage/current/power:
Alarm functions:
Function (switchable):
Pickup delay:
Switching voltage/current/power:
Electrical data & connections:
Transmitter function:
CU 22 function:
Isolated output voltage:
Hold function switch:
Load: pH/ORP input:
Connection terminal:
Display:
LCD:
Backlight:
Power supply:
Input:
Main fuse:
Pollution degree:
Transient overvoltage category:
EMC specifications:
Emitted interference:
Immunity to interference:
Environmental conditions:
Operating temperature range:
Max. relative humidity:
Mechanical specifications:
Dimensions (WxHxD):
Weight:
Ingress protection:
Alpha pH 2000D
(Wall mount)
TSPHCTP2000D
01X275375
Alpha pH 2000W
(Wall mount)
TSPHCTP2000W
01X275373
-2.00 to 16.00 pH or -1000 to 1000 mV or 0 to 100 %
0.1 to 1 pH
10 to 100 mV or 1 to 10.0 %
P/PI control (pulse length/pulse frequency/proportional integral); limit control; off
0.5 to 20 sec
60 to 120 pulse/min
0 to 999.9 min
0 to 2000 sec
0.1 to 200.0 hr
1 to 2000 sec
1 SPDT, 3 SPST relays
Max. 250 VAC / max. 3 A / max. 600 VA
Alpha pH 2000P
(Panel mount)
TSPHCTP2000P
01X275374
Two 0/4 to 20 mA scalable outputs for pH/ORP and temperature, galvanically isolated
22 mA current output
12 V ±0.5 V (max. 50 mA)
To freeze output current and deactivate control relays
2-pin terminal (Differential)
5-pin, 8-pin, 9-pin & 13-pin terminal, detachable blocks
315 mA time delay, 250 V,
Bussmann BK/GDC-315 mA
950 g (unit) / 1100 g (packed)
Max. 600 Ω
BNC (10 12 impedance); asymmetrical/symmetrical
3-pin, 8-pin, 9-pin & 13-pin terminal, detachable blocks
3-pin, 9-pin & 19-pin terminal, detachable blocks
80 to 250 VAC/DC ; 50/60 Hz ; 10 VA
144 x 144 x 110 mm
2
II
250 mA, anti-surge,
S504 Bussmann
745 g (unit) / 1100 g (packed)
IP66 (NEMA 4X)
-2.00 to 16.00 pH
0.01 pH
±0.01 pH
-1000 to 1000 mV / 0 to 100 %
1 mV / 0.1 %
±1 mV / ±0.2 %
-10.0 to 110 °C / 14.0 to 230.0 ºF
NTC 300; 2 wire
-10.0 to 125.0 °C / 14.0 to 257.0 ºF
0.1 ºC / 0.1 ºF
±0.5 ºC / ±1.0 ºF
Pt100 / Pt1000 (jumper selectable); 2 or 3 wire
Auto/manual (independent process/CAL temperature)
Steady or fleet (pulse)
0 to 2000 sec
Max. 250 VAC / max. 3 A / max. 600 VA
UV coat, backlit 14 segments display with symbols for status information
On/off selectable with four levels of brightness control
According to EN 61326
According to EN 61326
0 to 40 ºC
80 % up to 31 ºC decreasing linearly to 50 % at 40 ºC
96 x 96 x 175 mm
550 g (unit) / 950 g (packed)
IP54 (front panel)
* Includes side thread rods/brackets for mounting
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 9
pH/ORP Electrodes
Order Code
Part No.
EC100GTSO20B EC100GTSO10B EC100GTSO05B ECARGTSO05B ECARHTTSO05B ECARTSOHF05B ECARTSO05B ECFP21A1A1
93X417005 93X417006 93X218865 93X218864 93X218860 93X218872 93X218859 93X218986 pH Electrodes
Classification pH range
Reference
Reference electrolyte
Operating temperature
Pressure tolerance
Temperature sensor
Potential matching pin/liquid ground
Material
Thread
Cable
Connector
Dimensions Length
Diameter
Weight
0 to 14 pH
Annular PTFE, double junction
0 to 14,
HF resistant
6 bars (87 psi)
Pt100
Saturated KCl, polymerized gel
0 to 110 ºC /
0 to 80 ºC / 32 to 176 ºF 32 to 230 ºF high temp.
9 bars (130 psi)
–
Platinum
PPS (Ryton ® )
¾” NPT
Integral 20 m
(65.6 ft) low-noise semi-conductor screened
Integral 10 m
(32.8 ft) low-noise semi-conductor screened
0 to 80 ºC / 32 to 176 ºF
–
6 bars (87 psi)
Integral 5 m (16.4 ft) low-noise semi-conductor screened
950 g 850 g 650 g
BNC
151 mm (excludes cable)
26 mm (external)
430 g
Differential pH
0 to 14
Kynar ® , differential pH electrode pH buffer solution
-5 to 95 ºC /
23 to 203 ºF
6.9 bars (100 psi)
NTC 300
SS316
CPVC
1½” NPT
Integral 3 m (9.8 ft) cables, tinned ends
–
152.7 mm
(excludes cable)
48.3 mm (external)
500 g
Order Code
Part No.
ECHTAUTSO05B
93X219128
ECHTPTTSO05B
93X219126
ECFR21A1A1
93X218987
ORP Electrodes
Classification
Sensor
ORP range
Reference
Reference electrolyte
Operating temperature
Pressure tolerance
Temperature sensor
Potential matching pin/liquid ground
Material
Thread
Cable
Connector
Weight
ORP
Gold
Annular PTFE, double junction
Saturated KCl, polymerized gel
± 1000 mV
0 to 80 ºC / 32 to 176 ºF
6 bars (87 psi)
Pt100
Platinum
PPS (Ryton ® )
¾” NPT
Integral 5 m (16.4 ft) low-noise semi-conductor screened
BNC
151 mm (excludes cable)
26 mm (external)
430 g
Differential ORP
Platinium
Kynar ® , differential pH electrode pH buffer solution
-5 to 95 ºC / 23 to 203 ºF
6.9 bars (100 psi)
NTC 300
SS316
CPVC
1½” NPT
Integral 3 m (9.8 ft) cables, tinned ends
–
152.7 mm (excludes cable)
48.3 mm (external)
500 g
10 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Electrode Selection Guide pH/ORP Electrodes
General pH measurement pH measurement with ATC pH measurement in noisy environment eg. electroplating pH measurement at high temperatures
(up to 110 °C/230 °F ; 9 bar/130 psi) pH measurement in the presence of Hydrofluoric Acid (HF)
Replaceable salt junctions & refillable reference electrolyte
General ORP/Redox measurement
ORP measurement in noisy environment
ORP measurement in Cyanide treatment
ORP measurements in oxidising applications (above 500 mV)
ORP measurements in reducing applications (below 500 mV)
Line Diagram (All dimensions are in mm unless specified otherwise)
pH/ORP Electrodes
EC100GTSO20B
EC100GTSO10B
EC100GTSO05B
ECARGTSO05B
ECARHTTSO05B
ECARTSOHF05B
ECARTSO05B
ECHTAUTSO05B
ECHTPTTSO05B
25.5
19 21
pH/ORP Differential
Electrodes
ECFP21A1A1
ECFR21A1A1
1.5” NPT
EC100GTSO20B 93X417005 EC100GTSO10B 93X417006 EC100GTSO05B 93X218865 ECARGTSO05B 93X218864 ECARHTTSO05B 93X218860 ECARTSOHF05B 93X218872 ECARTSO05B 93X218859 ECFP21A1A1 93X218986
•
•
•
•
•
•
•
•
•
•
•
• • • •
•
•
•
•
•
•
•
•
•
47
151
20.5
20.3
ECHTPTTSO05B 93X219126 ECFR21A1A1 93X218987
•
•
•
•
•
•
152.7
Accessories Ordering Information
Order Code Part Number Description
TSPHCTP2000D 01X275375 Alpha pH 2000 wall-mount pH/ORP differential controller/transmitter. Incl. terminal blocks, cable glands, gasket etc
TSPHCTP2000W 01X275373 Alpha pH 2000 wall-mount pH/ORP controller/transmitter (unit only). Incl. elbow BNC connector, terminal blocks, cable glands, gasket, etc
TSPHCTP2000P 01X275374
Alpha pH 2000 panel-mount pH/ORP controller/transmitter (unit only). Incl. elbow BNC connector, terminal blocks, gasket, threaded rods, catch, etc
EC100GTSO20B 93X417005 Ryton
EC100GTSO10B 93X417006 Ryton
EC100GTSO05B 93X218865 Ryton
®
®
®
ECARGTSO05B 93X218864 Ryton ®
ECARHTTSO05B 93X218860 Ryton ®
ECARTSOHF05B 93X218872 Ryton ®
-body pH combi electrode with Pt100 RTD (ATC) & 20 m cable with BNC & PMP
-body pH combi electrode with Pt100 RTD (ATC) & 10 m cable with BNC & PMP
-body pH combi electrode with Pt100 RTD (ATC) & 5 m cable with BNC & PMP
-body pH combi electrode with 5 m cable with BNC & connector for PMP (no ATC)
93X218859 Ryton ®
-body pH combi electrode with 5 m cable with BNC connector (no ATC); measures up to 110 ºC
-body pH combi electrode without ATC & 5 m cable with BNC connector. HF resistant glass
ECARTSO05B
ECFP21A1A1
-body pH combi electrode with 5 m cable with BNC connector (no ATC)
93X218986 PES-body differential pH combi electrode with NTC 300 (ATC) & 5 m tinned open-ended cable (Alpha pH 2000D only)
ECHTAUTSO05B 93X219128 Ryton ®
ECHTPTTSO05B 93X219126 Ryton ®
-body ORP gold electrode with 5 m cable with BNC & PMP (no ATC)
-body ORP platinum electrode with 5 m cable with BNC & PMP (no ATC)
ECFR21A1A1 93X218987 PES-body differential ORP platinum electrode with NTC 300 (ATC) & 20 ft tinned open-ended cable (Alpha pH 2000D only)
ECCBLO5SMK50 01X222801 Low-noise 50 m coaxial SMK cable for pH/ORP electrodes (without ATC), 5 mm, open-ended with no connectors
28X088001
ECCBL030510
28X088001 Male BNC connector for 5 mm extension cable; 1 unit (need BNC crimping tool to connect to extension cable)
01X222802
Low-noise 10 m coaxial cable for pH/ORP electrodes (without ATC; with PMP), 3 mm/5 mm, male-male BNC connectors
(for extending ECARGTSO05, ECHTAUTSO05B & ECHTPTTSO05B)
Low-noise 20 m coaxial cable for pH/ORP electrodes (without ATC; with PMP), 3 mm/5 mm, male-male BNC connectors
ECCBL030520 01X222803
(for extending ECARGTSO05, ECHTAUTSO05B & ECHTPTTSO05B)
ECCONBNCBNC 01X243102 BNC to BNC adapter (for extension of cable connection) – a pack of 10 units
ECAC021011
ECAK061014
81X220801
81X220802
CPVC electrode tee for pH/ORP electrodes with ¾” to 1” adapter
Kynar ® electrode tee for pH/ORP electrodes with ¾” to 1” adapter
ECPREAMP 01X228601 Pre-amplifier (for cable length exceeding 25 m) with female-female BNC connectors at each side of the junction box; batteries included
ECPHSIMULATOR 01X373301 Precision hi-low impedance & multiple buffers pH simulator (with BNC-BNC cable provided)
15X403101
01X211270
01X278701
15X403101 Salt bridge for ECFP21A1A1 & ECFR21A1A1 differential pH or ORP electrode
01X211270 Reference electrolyte for ECFP21A1A1 & ECFR21A1A1 differential pH or ORP electrode (500 ml)
01X278701 Panel mount kit for Alpha 2000 controllers/transmitters
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 11
Thermo Scientific Alpha COND 2000
Conductivity Controller/Transmitter:
Conductivity:
Measure from ultra-pure water to highly conductive samples with the Alpha COND 2000 controller/ transmitter: this conductivity controller accepts 4-cell and
2-cell electrodes, and features programmable temperature coefficients to give you precise temperature compensation.
• Measures seven ranges, from
0 to 2 µS/cm to 0 to 1000 mS/cm
• Readings of up to three-decimal resolution at ±1 % accuracy
• Adjustable temperature coefficients for more precise temperature compensation:
Choose between programmable linear temperature compensation from 0.0 % to 10.0 %, and pure water temperature compensation to correct non-linearity of ultrapure water temperature correction curves
• Meter displays electrode status after each calibration
• User-adjustable cell constant values (k = 0.005 to k = 9.999)
• 4-cell electrode prevents polarizing effects and electrode fouling in samples with high conductivity
• Accepts 2- or 3-wire, Pt100 or
Pt1000 RTD sensors for automatic temperature compensation
• Allows user to input cell constant corresponding to connecting electrode independently during calibration
50
40
30
20
10
0
0
100
90
80
70
60
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Temp ºC
Resistivity Of Pure Water
90 95 100
12 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Specification Information
Conductivity Controller/Transmitter
Order Code
Part No.
Conductivity:
Range:
Resolution:
Accuracy:
Temperature:
Range:
Resolution:
Accuracy:
Sensor:
Compensation:
Set-point & controller functions:
Set point 1 (SP1) / set point 2 (SP2):
Switching Conductivity hysteresis:
Function (switchable):
Adjustable period with pulse length controller:
Adjustable period with pulse frequency controller:
Integral action time (IAT):
Pickup/dropout delay:
Wash cycle:
Wash duration:
Contact outputs:
Switching voltage/current/power:
Alarm functions:
Function (switchable):
Pickup delay:
Switching voltage/current/power:
Electrical data & connections:
Transmitter function:
CU 22 function:
Isolated output voltage:
Hold function switch:
Load:
Conductivity input:
Connection terminal:
Display:
LCD:
Backlight:
Power supply:
Input:
Main fuse:
Pollution degree:
Transient overvoltage category:
EMC specifications:
Emitted interference:
Immunity to interference:
Environmental conditions:
Operating temperature range:
Max. relative humidity:
Mechanical specifications:
Dimensions (WxHxD):
Weight:
Ingress protection:
Alpha COND 2000W
(Wall mount)
TSCONCTP2000W
01X275376
Alpha COND 2000P
(Panel mount)
TSCONCTP2000P
01X275377
... to 2.000 µS/cm ; ... to 20.00 µS/cm ;
... to 200.0 µS/cm ; ... to 2000 µS/cm ;
... to 20.00 mS/cm ; ... to 200.0 mS/cm ;
... to 1000 mS/cm
0.001 µS/cm ; 0.01 µS/cm ;
0.1 µS/cm ; 1 µS/cm ;
0.01 mS/cm ; 0.1 mS/cm ;
1 mS/cm
±1 % of full scale reading (±2 % >500 mS/cm)
-10.0 to 125.0 °C (14.0 to 257.0 °F)
0.1 ºC / 0.1 ºF
±0.5 ºC / ±1.0 ºF
Pt100/Pt1000 (jumper selectable); 2 or 3 wire
Auto/manual (normalized at 25 °C)
... to 2.000 µS/cm or ... to 20.00 µS/cm or
... to 200.0 µS/cm or ... to 2000 µS/cm or
... to 20.00 mS/cm or ... to 200.0 mS/cm or
... to 1000 mS/cm
0 to 10 % of full scale
P/PI control (pulse length/pulse frequency/proportional integral); limit control; off
0.5 to 20 sec
60 to 120 pulse/min
0 to 999.9 min
0 to 2000 sec
0.1 to 200.0 hr
1 to 2000 sec
1 SPDT, 3 SPST relays
Max. 250 VAC / max. 3 A / max. 600 VA
Steady or fleet (pulse)
0 to 2000 sec
Max. 250 VAC / max. 3 A / max. 600 VA
Two 0/4 to 20 mA scalable outputs for pH/ORP and temperature, galvanically isolated
22 mA current output
12 V ±0.5 V (max. 50 mA)
To freeze output current and deactivate control relays
Max. 600 Ω
2-cell/4-cell terminal
5-pin, 8-pin, 9-pin & 13-pin terminal, detachable blocks
5-pin, 9-pin & 19-pin terminal, detachable blocks
UV coat, backlit 14 segments display with symbols for status information
On/off selectable with four level of brightness control
80 to 250 VAC/DC ; 50/60 Hz ; 10 VA
315 mA, anti-surge, 250 V
2
II
According to EN 61326
According to EN 61326
0 to 40 °C
80 % up to 31 °C decreasing linearly to 50 % at 40 °C
144 x 144 x 110 mm
745 g (unit) / 1100 g (packed)
IP66 (NEMA 4X)
96 x 96 x 175 mm
550 g (unit) / 950 g (packed)
IP54 (front panel)
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 13
Conductivity Electrodes
Order Code
Part No.
EC91346S ECCS10-0-01T ECCS10-0-01TS ECCS10-0-01S ECCS10-0-01SS ECCS10-0-1S ECCS10-0-1SSP ECCS10-1-0S ECCS10-1-0SSP
93X219048 93X219019 93X219054 93X219018 93X219053 93X219020 93X219055 93X219021 93X219056
Conductivity
Electrodes
Conductivity range
Cell constant, K
Temperature sensor
Pressure rating at 25 ºC
Material
Fitting material
Thread
Cable
Dimensions
Weight
Length
Diameter
Up to 500 mS/cm
0.3, 4-cell
6 bar
(87 psi)
Ryton ®
SS316
–
,
¾” NPT
Integrated
7.6 m (24.9 ft),
8-wire doubleshielded, tinned ends
150.5 mm
(excludes cable)
22.2 mm
(external)
430 g
3.4 bar
(50 psi)
-5 to 50 ºC /
23 to 122 ºF
0.55 to 20 µS/cm
0.01, 2-cell
5.5 bar
(80 psi)
-5 to 80 ºC /
23 to 176 ºF
Titanium
Nylon plastic
Stainless steel
3.4 bar
(50 psi)
-5 to 50 ºC /
23 to 122 ºF
Pt100, 3-wire
5.5 bar
(80 psi)
-5 to 80 ºC /
23 to 176 ºF
Nylon plastic
Stainless steel
3.4 bar
(50 psi)
-5 to 50 ºC /
23 to 122 ºF
½” NPT
0.5 to 200 µS/cm
0.1, 2-cell
Nylon plastic
-5 to 200 ºC /
23 to 392 ºF
SS316
13.8 bar
(200 psi)
Stainless steel
600 g 680 g
Integrated 7.5 m (24.6 ft), 6-wire double-shielded, tinned ends
680 g
168 mm
(excludes cable)
660 g
12.8 mm
(external)
560 g 660 g
0.01 to 200 mS/cm
1.0, 2-cell
3.4 bar
(50 psi)
-5 to 50 ºC /
23 to 122 ºF
Nylon plastic
590 g
13.8 bar
(200 psi)
-5 to 120 ºC /
23 to 248 ºF
Stainless steel
660 g
Electrode Selection Guide
Conductivity Electrodes
General Conductivity measurements
Low Conductivity & Resistivity measurements
High Conductivity measurements
(4-cell electrodes)
Conductivity measurements with ATC
Conductivity measurements of ultrapure water
Conductivity measurements of pure water
Conductivity measurements of power plant
& condensate water
EC91346S 93X219048
•
•
• •
•
ECCS10-0-01T 93X219019
•
•
•
•
ECCS10-0-01TS 93X219054
•
•
•
•
ECCS10-0-01S 93X219018
•
•
•
•
ECCS10-0-01SS 93X219053
•
•
•
ECCS10-0-1S 93X219020
•
ECCS10-0-1SSP 93X219055
•
•
• •
ECCS10-1-0S 93X219021
•
ECCS10-1-0SSP 93X219056
•
•
•
•
•
14 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Line Diagram (All dimensions are in mm unless specified otherwise)
Conductivity Electrodes
EC91346S
Black Strain
Relief
150.5
Conductivity Electrodes
ECCS10-0-01T
ECCS10-0-01S
Cable Length: 30’
Black Strain
Relief
Ryton
Cap
3/4” NPT
41.5
3/4” NPT
22.9
½” MNPT
Plastic Nylon ø12.7
Titanium Body
110 ±2
Cable Length: 25’ Belden 9536
(6 Conductor Cable)
Conductivity Electrodes
ECCS10-0-1S
Black Strain
Relief
Ryton
Cap
½” MNPT
Plastic Nylon ø12.7
Stainless Steel
0.500”
110 ±2
Cable Length: 25’ Belden 9536
(6 Conductor Cable)
Conductivity Electrodes
ECCS10-1-0S
Black Strain
Relief
Ryton
Cap
½” MNPT
Plastic Nylon ø12.7
Stainless Steel
Roll Tip
316
Stainless Steel
Roll Over
PTFE
110 ±2
Cable Length: 25’ Belden 9536
(6 Conductor Cable)
Accessories Ordering Information
Order Code
TSCONCTP2000W 01X275376
TSCONCTP2000P
Part Number Description
01X275377
Alpha COND 2000 wall-mount Conductivity controller/transmitter. Incl. terminal blocks, cable glands, gasket, etc
Alpha COND 2000 panel-mount Conductivity controller/transmitter. Incl. terminal blocks, gasket, threaded
EC91346S
ECCS10-0-01T
ECCS10-0-01TS
ECCS10-0-01S
93X219048
93X219019
93X219054
93X219018 rods, catch, etc
4-cell Conductivity electrode with 3-wire Pt100, 30 ft tinned open-ended cable
Conductivity/Resistivity electrode with Pt100, cell constant K=0.01, titanium with 25 ft tinned open-ended cable
(with ½ inch nylon plastic cap threading)
Conductivity/Resistivity electrode with Pt100, cell constant K=0.01, titanium with 25 ft tinned open-ended cable
(with ½ inch stainless steel cap threading)
Conductivity/Resistivity electrode with Pt100, cell constant K=0.01, stainless steel with 25 ft tinned open-ended cable
ECCS10-0-01SS
ECCS10-0-1S
ECCS10-0-1SSP
ECCS10-1-0S
ECCS10-1-0SSP
ECAC021022
01X278701
93X219053
93X219020
93X219055
93X219021
93X219056
81X220803
01X278701
Conductivity/Resistivity electrode with Pt100, cell constant K=0.01, stainless steel with 25 ft tinned open-ended cable
Conductivity electrode with Pt100, cell constant K=0.1, stainless steel with 25 ft tinned open-ended cable
(with ½ inch nylon plastic cap threading)
Conductivity electrode with Pt100, cell constant K=0.1, stainless steel with 25 ft tinned open-ended cable
(with ½ inch stainless steel cap threading)
Conductivity electrode with Pt100, cell constant K=1.0, stainless steel with 25 ft tinned open-ended cable
(with ½ inch nylon plastic cap threading)
Conductivity electrode with Pt100, cell constant K=1.0, stainless steel with 25 ft tinned open-ended cable
(with ½ inch stainless steel cap threading)
CPVC electrode tee for Conductivity/Resistivity electrodes with ½” to 1” adapter
Panel mount kit for Alpha 2000 controllers/transmitters
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 15
Thermo Scientific Alpha DO 2000
Dissolved Oxygen Controller/Transmitter:
Dissolved Oxygen:
With a wide measuring range of 0 to 20 ppm or 0 to 200 % saturation, Alpha DO 2000 controller/ transmitter is ideal for use in a variety of applications, ranging from water treatment and monitoring to pharmaceutical and food processing.
Meter comes in both Galvanic and
Amperometric versions.
• Readings values in mg/L or % air saturations, selectable from menu options
• Quick, easy calibration using atmospheric air as calibration media for 100 % air saturation
• Pressure, Salinity and Automatic
Temperature Compensation
The Galvanic Electrode
(ECDOGEN-S & ECDOTPII-S)
The Amperometric Electrode
(EC237150 & EC237450)
Rugged and long-lasting, the galvanic electrode requires no warm-up time and prevents zero drift by recreating H 2 O within the electrode. This prevents change of pH to the electrode and allows it to recycle within the probe. The result: galvanic sensors have long lifespans and require low maintenance costs.
The amperometric dissolved oxygen electrode contains special membranes that are designed to require almost zero maintenance. These unique membranes stay stable even under harsh ambient conditions and high pressure. This enables the sensors to capture accurate
DO readings within short response time at required flow as low as 0.02 m/s.
16 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Specification Information
Dissolved Oxygen
Controller/Transmitter
Order Code
Part No.
Dissolved Oxygen:
Range:
Resolution:
Accuracy:
Temperature:
Range:
Resolution:
Accuracy:
Sensor:
Compensation:
Temperature compensation:
Salinity compensation:
Pressure compensation:
Set point & controller functions:
Set point 1 (SP1) / set point 2 (SP2):
Switching DO hysteresis:
Function (switchable):
Adjustable period with pulse length controller:
Adjustable period with pulse frequency controller:
Integral action time (IAT):
Pickup/dropout delay:
Wash cycle:
Wash duration:
Contact outputs:
Switching voltage/current/power:
Alarm functions:
Function (switchable):
Pickup delay:
Switching voltage/current/power:
Electrical data & connections:
Transmitter function:
CU 22 function:
Isolated output voltage:
Hold function switch:
Load:
DO input:
Connection terminal:
Display:
LCD:
Backlight:
Power supply:
Input:
Main fuse:
Electromagnetic compliance:
Emitted interference:
Immunity to interference:
Environmental conditions:
Operating temperature range:
Max. relative humidity:
Mechanical specifications:
Dimensions (WxHxD):
Weight:
Ingress protection:
Alpha DO 2000W
(Galvanic)
(Wall mount)
TSDOCTP2000W
01X275378
0.00 to 25.00 mg/L or ppm;
0.0 to 300.0 %
±1.5 % of full scale reading
0.00 to 25.00 mg/L or ppm;
0.0 to 300.0 %
0 to 10.0 %
Alpha DO 2000WPG
(Amperometric)
(Wall mount)
TSDOCTP2000WPG
01X275379
0.00 to 20.00 mg/L or ppm;
0.1 to 1.0 mg/L or 1.0 to 10.0 %
P/PI control (pulse length/pulse frequency/proportional integral); limit control; off
0.5 to 20 sec
60 to 120 pulse/min
0.0 to 999.9 min
0 to 1999 sec
0.1 to 199.9 hr
1 to 1999 sec
0.0 to 200.0 %
1 SPDT, 3 SPST relays
Max. 250 VAC / max. 3 A / max. 600 VA
Alpha DO 2000PPG
(Amperometric)
Pt100/Pt1000 (jumper selectable);
2 or 3 wire
-10.0 to 125.0 °C / 14.0 to 257.0 °F
0.1 ºC / 0.1 ºF
±0.5 ºC / ±1.0 ºF
NTC 22 kΩ thermistor
(Panel mount)
TSDOCTP2000PPG
0.0 to 50.0 ppt (manual setting and automatic correction)
10.73 to 43.51 psi (manual setting and automatic correction)
01X275380
Two 0/4 to 20 mA outputs for DO values and temperature, galvanically isolated
22 mA current output –
12 V ±0.5 V (max. 50 mA)
To freeze output current and deactivate control relays
5-pin, 8-pin, 9-pin & 13-pin terminal, detachable blocks
Max. 600 Ω
2-pin terminal
2x 3-pin, 8-pin, 9-pin & 13-pin terminal blocks
3-pin, 9-pin & 19-pin terminal blocks
UV coat, backlit 14 segments display with symbols for status information
On/off selectable with four level of brightness control
315 mA, anti surge, 250 V
80 % up to 31 °C decreasing linearly to 50 % at 40 °C
144 x 144 x 111.5 mm
0.01 mg/L or ppm; 0.1 %
0.740 to 3.000 bar ; 555 to 2250 mmHg ;
Steady or fleet (pulse)
Max. 250 VAC / max. 3 A / max. 600 VA
80 to 250 VAC/DC ; 50/60 Hz ; 10 VA
250 mA, anti surge
According to EN 61326
According to EN 61326
IP66 (NEMA 4X)
0.00 to 20.00 mg/L or ppm;
±1 % of full scale reading
Auto/manual
0 to 1999 sec
0 °C to 50 °C
144 x 144 x 110 mm
745 g (unit) / 1100 g (packed)
0.0 to 200.0 %
175 x 96 x 96 mm
700 g (unit) / 850 g (packed)
IP54 (front panel)
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 17
Dissolved Oxygen Electrodes
Order Code
Part No.
ECDOGEN-S
01X247507
Dissolved Oxygen
Electrodes
ECDOTPII-S
01X247508
EC237150
93X416401
EC237450
93X416402
Dissolved Oxygen range
Type
Flow rate
Response time
Temperature sensor
Pressure rating
Operating temperature
Material
Membrane
Cable
Weight
0.50 to 20 ppm 0.03 to 20 ppm
Galvanic
50 mm/sec (dependent on temperature and O
2
level)
40 to 50 sec to attain 95 % of actual reading
Pt100
6 bar (87 psi)
0 to 50 ºC / 32 to 122 ºF
Delrin housing
HDPE
Integral 3 m (9.8 ft) water-resistant, tinned ends
152.4 mm (excludes cable)
58.4 mm (external)
670 g
Electrode Selection Guide
0.04 ppm to saturation 0.01 ppm to saturation
Amperometric
20 mm/sec
–
22 kΩ NTC
4 bar (58 psi)
0 to 60 ºC / 32 to 140 ºF
Non-replaceable
0 to 130 ºC / 32 to 248 ºF
Stainless steel
FDA membrane
(sold separately)
12 mm shaft diameter (excludes cable)
178 (external)
670 g
Dissolved Oxygen Electrodes
DO measurements at low levels
Waterproof probes
Galvanic DO measurements system for general purposes, eg. wastewater
& aquaculture
Galvanic DO measurements system for low
DO level, eg. power plants, metal corrosion test facilities
Biocompatible electrode materials
Amperometric DO measurements system for biotechnology, steam sterilisation & autoclaving, fermentation applications
Amperometric DO measurements system for general purposes, eg. wastewater, fish farms, composting facilities
ECDOGEN-S 01X247507
•
•
ECDOTPII-S 01X247508
•
•
•
•
EC237150 93X416401
•
•
•
•
•
EC237450 93X416402
•
18 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Line Diagram (All dimensions are in mm unless specified otherwise)
Dissolved Oxygen Electrodes
ECDOGEN-S
ECDOTPII-S
152.4
26.7
58.4
Red Wire (+) Black Wire (-)
Black Cable
Black Nut =
DOGEN-S
Gray Nut =
DOTPII-S
Zinc Anode
DOGEN-S
Lead Anode
DOTPII-S
(Internal)
ø1.05”
(26.7 mm)
Silver
Cathode
(Internal) ø2.30”
(58.4 mm)
6.00”
(152.4 mm)
Galvanic Probe
(Construction)
Membrane
Dissolved Oxygen Electrode
EC237450
178
120
Accessories Ordering Information
Order Code
TSDOCTP2000W
Part Number Description
01X275378
Alpha DO 2000 galvanic wall-mount Dissolved Oxygen controller/transmitter. Incl. terminal blocks, cable
TSDOCTP2000WPG 01X275379
TSDOCTP2000PPG 01X275380
ECDOGEN-S
ECDOTPII-S
EC237150
EC237450
01X241605
01X241606
32X246702
15X241503
01X247507
01X247508
93X416401
93X416402
01X241605
01X241606
32X246702
15X241503
ECDOGENSOLNBT 01X211228
ECDOTPIISOLNBT 01X211229
EC237140
EC237118
EC237137
EC355089
EC355136
01X278701
01X416501
01X416601
15X416701
30X416801
30X416802
01X278701 glands, gasket, etc
Alpha DO 2000 polarographic wall-mount Dissolved Oxygen controller/transmitter. Incl. terminal blocks, cable glands, gasket, etc
Alpha DO 2000 polarographic panel-mount Dissolved Oxygen controller/transmitter. Incl. terminal blocks, gasket, threaded rods, catch, etc.
Delrin housing-body galvanic Dissolved Oxygen electrode with Pt100, 5 m tinned open-ended cable
Delrin housing-body, galvanic Dissolved Oxygen electrode with Pt100, 5 m tinned open-ended cable
Polarographic probe with 22 KOhm NTC, 5 m tinned open-ended cable
Fermentation polarographic probe with 22 KOhm NTC, with extra membrane, without cable
Set of 5 o-rings & membranes (DOGEN-S)
Set of 5 o-rings & membranes (DOTPII-S)
Large o-ring (DOGEN-S/DOTPII-S)
Tool for membrane housing (DOGEN-S/DOTPII-S)
DO refilling electrolyte for ECDOGEN-S (480 ml bottle)
DO refilling electrolyte for ECDOTPII-S (480 ml bottle)
3 FDA membrane bodies, electrolyte, pipette, spare o-ring, polishing strip (for EC237450)
Electrolyte for EC237450, 50 ml
Autoclavation connector cap for EC237450
5 m cable for EC237450
10 m cable for EC237450
Panel mount kit for Alpha 2000 controllers/transmitters
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 19
Wall Mount – ½ DIN (in mm)
144
111.5
27.5
6
80
39
78
PG13.5 (3 pcs)
90
Holes for post mounting (4X)
Holes for wall mounting (2X)
Red plugs for wall mounting holes enclosure
(2X)
24
57.8
For PG13.5 cable glands
Panel Mount – ½ DIN (in mm)
Max. 80 84
1 - 22
29
Seal gasket
175
138 175
Threaded rod for panel mounting
Panel Mount – ¼ DIN (in mm)
138
Cut-out mounting plates for post mounting
Flat gasket
1
92+0.5
Panel cut-out
Max. 180
Max. 45
20 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Sensor Installation Tips
There are two main sensor installation configurations:
1. In-line Installation where electrodes are installed into the piping system
• In-line installation is best in a location which is always flooded.
It is recommended that the electrode be installed in the dead leg of a pipe tee fitting
(Figure 4)
This reduces the velocity of the
. fluid as it flows into and around the electrode before flowing upwards and away
• Take into consideration the amount of cleaning and calibrating your application imposes on the electrode. In-line mounting may mean the process has to be shut down, or that a portion of the pipe must be drained in order to remove the electrode
• Remove cables before unscrewing electrodes from the pipes to avoid twisting and damaging wires or shielding
2. Submersible Installation where electrodes are submerged in tanks
• Use a baffle in submersible installation to avoid air bubbles from being trapped inside or around the electrode, distorting readings
(Figure 5)
. Install your electrode away from mixers, sparges and inlets
• Mount electrodes near outlets of the tank, away from points where reagents are introduced.
This allows time for reagents to mix thoroughly and react with your effluent water. Some applications, such as neutralization processes that require pH control, are best executed with submersible configuration than with in-line configuration, where both pH and flow are variables
• Some sensors must be mounted at a ±30 ° angle
(Figure 6)
. This ensures that the electrolyte remains in contact with sensing tips, and prevents bubble entrapment within the electrode membrane. Some electrodes, however, like our DO Sensor,
EC237450, can be installed even upside-down – very useful for measurements in tanks that are nearly empty
• Keep connection between electrode and preamplifier dry and clean at all times. Moisture in this area may cause permanent damage
Whether you’re considering an in-line or submersible configuration, the principle considerations are to avoid air bubble entrapment, as well as to ensure maximum exposure of the sensor to your process water.
In processes when temperature and pressure of the process liquid exceeds the sensor ratings, a sidestream system may be used, where a portion of the process liquid is constantly directed to the sensor.
Sensor
Tee
Figure 4: In-line installation
Flow
Sensor
30 º Min
Weld Spud at Angle
Figure 5: Submersible installation Figure 6: Angle mounting installation
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 21
Applications
pH Application
The pH neutralization system is crucial in the back-end process of treating effluent water in industries such as pharmaceutical, F&B manufacturing, electroplating and seawater desalination etc.
In a neutralization system, effluent water flows into a tank where a pH electrode picks up the pH level of the process water. When this pH level goes below or above set limits, the electrode sends a signal to the meter, which in turn, adjusts the pH level in the tank by operating two chemical pumps that release acid or alkali into the tank as needed.
Pump
Acid
Alpha pH 2000D
Recorder
Influent
Electrode
Mixer
Valve
Effluent
Base
Pump
Alpha pH 2000 Alpha pH 2000
pH & ORP Application
In applications where pH and ORP must be measured and controlled simultaneously, two Alpha pH/ORP 2000 meters can be placed side by side where the pH meter acts as the primary controller – the ORP controller will only operate its pumps when pH is within set limits.
Pump pH Adjustment
Influent
Electrode
Mixer
Valve
Pump
Effluent
ORP Adjustment
Alpha COND 2000
Conductivity Application
In the back-end process of the electroplating industry, conductivity monitoring systems monitor the conductivity of rinse water in metal finishing facilities, maintaining chemical concentrations at levels that provide adequate rinsing and at the same time, prevent excessive dragin to subsequent process tanks. When rinse water conductivity exceeds set limits, the meter activates a valve that introduces more water into the rinse tank, reducing conductivity of the rinse water.
Valve
Rinse
Tank Electrode
Mixer
Valve
Effluent
Recorders
Alpha DO 2000 /
Alpha DO 2000PG
pH & DO Application
In biological wastewater treatment, both dissolved oxygen level and pH level are vital in ensuring efficient breakdown of biological waste in the effluent water.
A dissolved oxygen sensor picks up the temperature and
DO level of the process water in the biological wastewater tank. It then relates this information to the DO meter, which controls an air pump to increase or reduce the amount of oxygen level that goes into the effluent water.
Pump
Acid
Alpha pH 2000
Influent
Electrodes
Mixer
Valve
To
Secondary
Treatment
Base
Pump
22 Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process
Trademarks Used:
Viton ® is a registered trademark of DuPont
Performance Elastomers.
Kynar ® is a registered trademark of Arkema Inc.
Ryton ® is a registered trademark of Chevron
Philips Chemical Company LLC.
Warranty:
Thermo Fisher Scientific provides one year of warranty against manufacturing defects for meters, and six months for electrodes.
Disclaimers:
Specifications and terms are subject to change.
Not all products are available in all countries.
Please consult your local sales representative for details.
All drawings and diagrams are for illustration purposes only and are not drawn to scale.
About Thermo Fisher Scientific
Thermo Fisher Scientific (NYSE: TMO) is the world leader in serving science, enabling our customers to make the world healthier, cleaner and safer. With annual sales of more than $9 billion, we employ 30,000 people and serve over 350,000 customers within pharmaceutical and biotech companies, hospitals and clinical diagnostic labs, universities, research institutions, government agencies as well as environmental and industrial process control settings. Serving customers through two premier brands, Thermo
Scientific and Fisher Scientific, we help solve analytical challenges from routine testing to complex research and discovery. Thermo
Scientific offers customers a complete range of high-end analytical instruments as well as laboratory equipment, software, services, consumables and reagents to enable integrated laboratory workflow solutions. Fisher Scientific provides a complete portfolio of laboratory equipment, chemicals, supplies and services used in healthcare, scientific research, safety and education. Together, we offer the most convenient purchasing options to customers and continuously advance our technologies to accelerate the pace of scientific discovery, enhance value for customers and fuel growth for shareholders and employees alike.
Thermo Scientific / Alpha Process Products / 2000 Series Controllers / www.thermo.com/process 23
Environmental Instruments
Water Analysis Instruments
North America
166 Cummings Center
Beverly, MA 01915 USA
Toll Free: 1-800-225-1480
Tel: 1-978-232-6000
Dom. Fax: 1-978-232-6015
Int’l Fax: 978-232-6031 www.thermo.com/process
Europe
Denmark House, Angel Drove
Ely, Cambridgeshire
CB7 4ET, UK
Tel: 44-1353-666111
Fax: 44-1353-666001
Asia Pacific
Blk 55, Ayer Rajah Crescent
#04-16/24, Singapore 139949
Tel: 65-6778-6876
Fax: 65-6773-0836
© 2007 Thermo Fisher Scientific Inc.
All rights reserved.
www.thermo.com/process
CON 08X233408 05/08 Rev 0
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project