Dacor Renaissance ERV48, PRV30, PRV36, PRV46 Downdraft Raised Vent Installation Instructions
Below you will find brief information for Renaissance ERV48, Renaissance PRV30, Renaissance PRV36, Renaissance PRV46. These downdraft raised vents allow for efficient and effective ventilation from your cooking area. The vent system includes the raised vent itself and a single Dacor approved remote or in-line blower. The vent can be configured to exhaust through the back, the bottom or either side. This unit must be installed with an approved Dacor remote or in-line blower. Read the use and care manual completely before operating the raised vent.
Advertisement
Advertisement
Installation Instructions
Renaissance
®
Downdraft Raised Vent
Models: ERV48, PRV30, PRV36, PRV46
Part No. 65335 Rev. P
Use these downdraft raised vents only with approved Dacor appliances.
See the installation instructions for the particular appliance model being installed to determine suitability.
®
Table of Contents
Important Safety Instructions .......................................... 1
Important Information About Safety Instructions .............. 1
Safety Symbols and Labels ............................................. 1
General Safety Precautions ............................................. 2
Product Specifications ..................................................... 3
Product Dimensions ......................................................... 3
Installation Specifications ................................................ 4
Electrical Specifications ................................................... 4
Planning the Installation ................................................... 4
Planning the Duct Work ................................................... 6
Installation Instructions .................................................... 8
Installation Preparation .................................................... 8
Installation ........................................................................ 8
Verifying Proper Operation ............................................. 12
Installation Checklist ...................................................... 12
Wiring Diagram ................................................................ 13
Before You Begin...
Important:
• Installer: In the interest of safety and to minimize problems, read these installation instructions completely and carefully before you begin the installation process. Leave these installation instructions with the customer.
• Customer: Keep these installation instructions for future reference and the local electrical inspector’s use.
Customer Service Information
If You Need Help...
Model Identification:
If you have questions or problems with installation, contact your Dacor ® dealer or the Dacor Customer Service Team.
For repairs to Dacor appliances under warranty call the Dacor
Distinctive Service line. Whenever you call, have the model and serial number of the appliance ready. The model and serial number are printed on the product data label on the front of the unit. The product data label also specifies the power supply requirements.
Dacor Customer Service
Phone: (800) 793-0093 ex. 2813 (U.S.A. and Canada)
Monday - Friday 6:00 a
.
m
.
to 5:00 p
.
m
.
Pacific Time
Web site: www.dacor.com
Dacor Distinctive Service (for repairs under warranty only)
Phone: (800) 793-0093 ex. 2822 (U.S.A. and Canada)
Monday - Friday 6:00 a
.
m
.
to 5:00 p
.
m
.
Pacific Time
ERV48 = 48-inch wide raised vent, ERV style top cap
PRV30 = 30-inch wide raised vent, PRV style top cap
PRV36 = 36-inch wide raised vent, PRV style top cap
PRV46 = 46-inch wide raised vent, PRV style top cap
See page 3 for top cap style descriptions.
Tested in accordance with the latest edition of ANSI Z 21.1 standard for household gas cooking appliances, ANSI/UL 858 household electrical ranges, CAN/CSA-C22.2 NO. 64 Standard for Household
Electric Cooking and Liquid Heating Appliances, and UL 507 electric fans.
All specifications subject to change without notice. Dacor assumes no liability for changes to specifications.
© 2007 Dacor, all rights reserved.
Important Safety Instructions
Important Information About
Safety Instructions
• The Important Safety Instructions and warnings in these instructions are not meant to cover all possible problems and conditions that can occur. Use common sense and caution when installing, maintaining or operating this or any other appliance.
• Always contact the Dacor Customer Service Team about problems and conditions that you don’t understand. See Customer Service Information.
Safety Symbols and Labels
DANGER
Immediate hazards that WILL result in severe personal injury or death.
WARNING
Hazards or unsafe practices that COULD result in severe personal injury or death.
CAUTION
Hazards or unsafe practices that COULD result in minor personal injury or property damage.
DANGER
IMPORTANT: Do not store or use combustible, flammable or explosive vapors and liquids (such as gasoline) inside or in the vicinity of this or any other appliance. Also keep items that could explode, such as aerosol cans, away from the range or cooktop. Do not store flammable or explosive materials in adjacent cabinets or areas.
WARNING
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a) Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
b) Sufficient air is needed for proper combustion and exhausting of gases through the flue(chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American
Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
d) Ducted fans must always be vented to the outdoors.
READ AND SAVE THESE INSTRUCTIONS
1
2
Important Safety Instructions
General Safety Precautions
To reduce the risk of fire, electric shock, serious injury or death when using your appliance, follow basic safety precautions, including the following:
WARNING
• Do not install or operate a damaged appliance. If you receive a damaged appliance, contact your dealer or builder.
• Observe all governing codes and ordinances during planning and installation. Contact your local building department for further information.
• For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
• Use this raised vent only for its intended purpose as outlined in the use and care manual. This appliance is not intended for commercial use.
• The customer should not install, repair or replace any part of this unit unless specifically recommended in the literature accompanying it. A qualified service technician should perform all other service. Contact the Dacor Customer Service Team for examination, repair or adjustment.
• Keep all packaging materials away from children.
Plastic bags can cause suffocation.
• For proper operation, this unit must be installed with a remote or in-line blower. Use only one of the models specified. Only one blower shall be installed.
• Install or locate this appliance only in accordance with these installation instructions, the Dacor range/ cooktop installation instructions and the remote or in-line blower installation instructions. Improper installation, adjustment, alteration, service or maintenance can cause serious personal injury or property damage.
• Before installing or servicing the raised vent, disconnect the power plug from the electrical outlet.
• The installer must show the customer the location of the electrical outlet so that the customer knows where and how to disconnect power.
• Read the use and care manual completely before operating this appliance.
• Do not tamper with the controls.
• Never allow the filters or vent openings to become blocked or clogged. Do not allow foreign objects, such as cigarettes or napkins, to be sucked into the vent holes.
• Clean the filters and all grease-laden surfaces often to prevent grease fires and maintain performance.
Clean this appliance only as specified in the use and care manual.
WARNING
• Do not leave children or pets alone or unattended in the area around the range or cooktop when it is in use. Never allow children to sit or stand on an appliance. Do not let children play with a range, cooktop or the raised vent. Do not store items of interest to children above or around the appliance.
• This appliance is equipped with a three prong grounding plug for your protection against possible electric shock hazards. It must be plugged into a dedicated, grounded electrical outlet. Where a standard two prong electrical outlet is encountered, it is the personal responsibility and obligation of the customer to have it replaced with a dedicated, properly grounded three prong electrical outlet.
Do not under any circumstances:
♦ Cut or remove the third (ground) prong from the power cord.
♦ Use an adapter plug.
♦ Use an extension cord.
♦ Use a power cord that is frayed or damaged.
♦ Use of a ground fault interrupter (GFI) is not recommended.
Three prong grounding plug
Grounding type electrical outlet
Product Dimensions
Product Specifications
Tolerances: ±1/16” (±1.6 mm) unless otherwise stated
5/16” (8 mm) thick stiffener across back
2 3/16"
(5.6 cm)
2 1/8"
(5.4 cm)
2 1/2"
(6.4 cm)
3/16"
(5 mm)
Top cap with vent down
9/16"
(1.4 cm)
Model
Number
ERV48
PRV30
PRV36
PRV46
A - Top Cap
Width
48” (121.9 cm)
30” (76.2 cm)
36” (91.4 cm)
46” (116.8 cm)
B - Chassis
Width
43 3/8” (110.2 cm)
27 3/8” (69.5 cm)
33 3/8” (84.8 cm)
43 3/8” (110.2 cm)
1 15/16"
(4.9 cm)
2 9/16"
(6.5 cm)
Vent shown in raised position
10"
(25.4 cm)
A
2 1/8" (5.4 cm)
ERV top cap - side view
3/8"
(1.0 cm)
2 1/8" (5.4 cm)
PRV top cap - side view
7/16"
(1.1 cm)
18 5/8”
(47.3 cm)
3 3/4"
(9.5 cm)
1"
(2.5 cm)
30 1/4"
(76.8 cm) to
37 1/4"
(94.6 cm)
*
30"
(76.2 cm)
B
6"
(15.2 cm)
Motor cover
Front of unit
Product data label
28" 3-prong grounded power cord
See page 6 for exhaust locations and dimensions.
* Maximum height of raised vent must not exceed maximum specified counter height for cooking appliance. See installation instructions for cooking appliance.
Adjustable anchor legs
3
Installation Specifications
Electrical Specifications
WARNING
The electric outlet for the raised vent should be installed only by a licensed electrician.
The raised vent is supplied with a 28” (71.1 cm) power cord with a three prong plug. Plug it directly into a three prong electrical outlet meeting the requirements below. Do not use an extension cord.
The correct voltage, frequency and amperage must be supplied as specified below. The circuit must be protected by a properly sized circuit breaker or time-delay fuse.
Electrical Supply Requirements
A three prong electrical outlet connected to a 120 Vac,
60 Hz, 15 Amp. grounded, dedicated, single phase circuit is required.
• The above specifications are for reference only. If the power supply requirements shown above do not agree with those listed on the product data label, use the ratings on the label.
• The customer must supply 3 conductor wiring/conduit with minimum current carrying capacity of 8 Amps. to supply power to the remote or in-line blower from the raised vent. See General System Layout and
Planning the Duct Work for further details.
• It is the owner’s responsibility to ensure that electrical outlet is installed by a licensed electrician. The electrical installation must comply with the latest revision of the National Electric Code ANSI/NFPA 70* (latest revision) and local codes and ordinances.
*A copy of this standard may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02269-9101
• Locate the electrical outlet in an accessible location, so that the power plug can be disconnected for service without removing the range/cooktop or raised vent from the cabinet.
4
Planning the Installation
General System Layout
The vent system consists of the raised vent itself and a single
Dacor approved remote or in-line blower (see page 6).
WARNING
• Failure to install an approved remote or in-line blower or proper duct work will result in a back draft and/or the insufficient venting of smoke and fumes.
• To reduce the risk of personal injury caused by reaching over a hot appliance, cabinet storage space located directly above the range/cooktop should be avoided.
• Follow the instructions and diagrams for minimum safe clearances and installation location in these instructions, the appliance installation instructions and the remote or in-line blower installation instructions.
Failure to do so may result in a fire or safety hazard.
• Install the raised vent and range/cooktop so that they can be removed if service is required.
• Refer to the range/cooktop installation instructions for the minimum cutout dimensions specific to the particular raised vent model being installed.
• Plan the installation so that all minimum dimensions are met or exceeded. All contact surfaces between the raised vent and any cabinets or walls must be solid and at right angles.
• The raised vent exhaust may be configured to vent through the back, the bottom or through one of the sides. Allow room for the exhaust duct coming out of the unit. See Planning the Duct Work for further details.
• The maximum allowable duct run must be taken into consideration when determining the layout. See
Planning the Duct Work for further details.
• The raised vent is equipped with adjustable anchor legs to accommodate various cabinet heights.
• Wire the remote or in-line blower to turn on when the raised vent is turned on. Run the blower wiring/conduit parallel to the duct work, connecting it to the raised vent on one end and the blower on the other. There are
7/8” access holes in the bottom and side of the raised vent for connecting the conduit/strain relief.
Front of unit
Blower wiring access hole in side
Blower wiring access hole in bottom
Electrical Access Hole Locations
Installation Specifications
Backsplash Backsplash
Countertop overhang
Vertical non-combustible surface rear wall
Vertical non-combustible surface rear wall
Countertop overhang
Notches required for some rasied vent installations, see cooktop installation instructions
See the cooktop installation instructions for exact countertop and cabinet dimensions
Flush with back side of cabinet front
Notches required for some raised vent installations, see range installation instructions
Notches for self-rimming style installations, see range installation instructions
Cooktop Cabinet/Countertop Cutout - Top View
See the range installation instructions for exact countertop and cabinet dimensions
Range Cabinet/Countertop Cutout - Top View
REMP series remote blower
3 ¼ x 10 to
round transition and 45° adjustable elbow
Wall board Duct work between raised vent and remote blower
Backsplash
Cabinet back
Outside wall
Raised vent
Cooktop
Raised vent
Range
Raised vent configured for bottom exhaust
3 ¼ x 10 to round transition
Wall cap on outside wall
Raised vent configured for rear exhaust
Wiring/conduit from raised vent to remote blower
Floor
Example of Layout with Cooktop
and Rear Exhaust
Wiring/conduit from raised vent to in-line blower
Floor
Duct work Duct work
ILHSF series in-line blower
Example of Layout with Range and Bottom Exhaust
5
6
Installation Specifications
Planning the Duct Work
WARNING
• To reduce the risk of fire and to properly exhaust air, be sure to duct air outside the house or building. Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces or garages.
• TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCT WORK.
• DO NOT install more than one blower to increase the length of the duct run. Even small differences between blower air flow rates can greatly reduce the air draw by the raised vent.
Local building codes may require the use of makeup air systems with ventilation systems that move air greater than the specified movement rate ( CFM). The specified rate varies based on locale. Consult a qualified HVAC specialist when designing the system for the requirements in your area and to assure optimal performance.
You must install one of the Dacor remote or in-line blower models listed below for the raised vent to operate properly.
See the blower installation instructions for directions.
• When connecting the duct work to the back of the unit, the customer must supply a 3 ¼ x 10 rectangular transition to make the connection.
• For side and bottom exhaust connections, use the supplied 1
5
/
8
x 16 duct transition to connect the duct work to the unit. It transitions between the 1
5
/
8
x 16 exhaust outlet on the unit and a 3 ¼ x 10 rectangular duct connection. On bottom exhaust installations cut a hole in the floor to allow the transition and/or duct work to pass through the floor (see page 8).
APPROVED DACOR BLOWERS FOR USE WITH
MODEL ERV AND PRV SERIES RAISED VENTS
Model
Number
REMP3 REMP16 ILHSF8 ILHSF10
Rating* 600 CFM 1000 CFM 600 CFM 1100 CFM
* Nominal rating at zero inches static pressure. See blower installation instructions for actual ratings.
The raised vent can be configured to exhaust through the back, the bottom or either side by removing the appropriate exhaust knock out shown below.
5"
(12.7 cm)
1"
(2.5 cm)
2 x 16, connects to side or bottom exhaust on raised vent
1 1/8"
(2.9 cm)
CL
6 1/4"
(15.9 cm)
Front of unit
Motor cover
CL
3”
CL
Rear Exhaust Knock Out (3 ¼ x 10)
Vertical center line of rear exhaust knock out lines up with vertical
center line of chassis
Bottom Exhaust Knock Out (1
5
/
8
x 16)
On 46” and 48” wide models, the vertical center line of bottom knock-
out lines up with vertical center line of chassis
On 30” and 36” wide models, the vertical center line of bottom knock-
out is offset 3”
Side Exhaust Knock Outs (1
5
/
8
x 16)
3 ¼ x 10 to duct work
1
5
/
8
x 16 Duct Transition
• All duct work materials (including screws and duct tape) must be purchased separately by the customer.
• When planning new duct work, always look for the shortest, most direct route to the outside. See page
5 for examples.
• You can increase the duct size over the duct run if desired. To prevent a back draft, never decrease the duct size over the run.
• Do not rely on duct tape alone to seal duct joints.
Fasten all connections with sheet metal screws and tape all joints with certified silver tape or duct tape.
• Use sheet metal screws as required to support the duct weight.
• To prevent back-drafts, a damper at the duct outlet may also be required.
• When determining the exhaust location, take into account that drifting snow (in colder climates) can obstruct the air flow. Allow additional clearance than the stated minimums under these conditions.
Installation Specifications
• On side exhaust installations, allow five inches of space on the side for the 1
5
/
8
x 16 duct transition plus additional space for the duct attached to it (X).
• Make sure duct work does not interfere with floor joists or wall studs.
• With concrete slab construction, “box-in” the duct work and blower wiring to prevent collapsing or other damage when the wet concrete is poured.
• Cross-drafts or air currents from adjacent open windows or doors, heating/air conditioning outlets, ceiling fans and recessed ceiling lights reduce vent efficiency.
1 5 /
8
x 16 duct transistion
5”
X
Duct Work Design Tips
• Wherever possible, reduce the number of transitions and turns to as few sharp angles as possible. Two staggered 45° angles are better than one 90°. Keep turns as far away from the hood exhaust as possible, with as much space between each bend as possible.
• For best performance, use round duct instead of rectangular when possible, especially when elbows are required.
• If multiple elbows are used, try to keep a minimum of
24” of straight duct between them. Avoid “S” or “back to back” configurations of adjacent elbows.
• Do not use flexible metal duct.
Calculating the Maximum Duct Run Length
• Do not use duct work that is smaller in cross-sectional area than the required duct sizes in the table to the right.
• For best performance, keep the duct run as short as possible and never exceed the maximums stated at the right.
• The maximum straight duct length for the raised vent system depends on the model of remote or in-line blower used with the vent system and the number of elbows and transitions used. The Equivalent Number
of Feet for each elbow and transition (see table) must be subtracted from the maximum straight length to compensate for wind resistance. To determine the maximum allowable length of the duct work, subtract all of the equivalent lengths of the elbows and transitions listed at the right from the Blower Maximum Duct
Straight Length.
For example, for a raised vent system using 3 ¼ x 10 rectangular duct, two (2) 3 ¼ x 10 90° elbows, a 3 ¼ x
10 rectangular to 10” round transition, and a REMP16 remote blower:
• From the Blower Maximum Duct Straight Length table below, the maximum length without transitions and elbows is 60 feet.
• The equivalent length of each 90 ° elbow is 15 feet.
• The equivalent length of 45 ° elbow is 2 feet.
• The equivalent length of the transition is 4 feet.
• The total equivalent length of the above components is:
15 feet + 15 feet + 4 feet + 2 feet = 36 feet.
• The maximum amount of straight duct that can be used with a REMP16 and the above components is: 60 feet -
34 feet = 24 feet.
45° elbow
8 inch
Equivalent Number of Feet -
Duct Elbows and Transitions
3 feet
3 ¼” x 10
45° elbow
45° elbow
10 inch
2 feet
3 ¼ x 10
90° elbow
90° elbow
8 inch
90° elbow
10 inch
7 feet
5 feet
3 ¼ x 10
90° flat elbow
3 ¼ x 10 to 8” round transition
90° 3 ¼ x 10 to
8” round transition
Roof cap
25 feet
*
3 ¼ x 10 to 10” round transition
Wall cap
7 feet
15 feet
20 feet
4 feet
4 feet
*
* The equivalent lengths of roof and wall caps vary with model and configuration. For equivalent length, contact the manufacturer or a qualified HVAC specialist.
Duct Size
Used
8 Inch
10 Inch
3 ¼ x 10”
Blower Maximum Duct Straight Length
REMP3 Remote Blower REMP16 Remote Blower ILHSF8 In-line Blower ILHSF10 In-line Blower
50 feet (15.2 meters) 60 feet (18.3 meters) 50 feet (15.2 meters) 60 feet (18.3 meters)
40 feet (12.2 meters)
40 feet (12.2 meters)
70 feet (21.3 meters)
60 feet (18.3 meters)
40 feet (12.2 meters)
40 feet (12.2 meters)
70 feet (21.3 meters)
60 feet (18.3 meters)
7
8
Installation Instructions
Installation Preparation
Verify Package Contents
• Product literature
• Anchoring legs (left - PN 36861, right - PN 36862)
• 2 wood screws, #14 x 2 ½ (PN 83047)
• 3 wire nuts
• 1
5
/
8
x 16 duct transition (PN 13768)
• 2 sheet metal screws, #10 x ½ (PN 83022)
• 2 keps nuts, ¼-20 (PN 83049)
• 2 flat washers, ¼-20 (PN 83203)
• Insulation foam
Installation
WARNING
• If the electrical service (electrical outlet) does not meet the Electrical Specifications on page 4, do not proceed with the installation. Call a licensed electrician and have an electrical outlet installed that meets the specifications.
• Install the vent only in a vertical orientation. Do not mount the vent on a slant or angle.
• Do not enlarge or modify the exhaust knock outs or cut an exhaust hole in a location on the chassis other than those shown. Doing so may cause an increase in noise and decrease performance.
NOTE: The raised vent installs in the back of the cutout, separate from the range or cooktop. Install the raised vent before installing the range or cooktop.
Installing the Raised Vent
1. Remove the appropriate side, back or bottom exhaust knockout, depending on the desired exhaust configuration, from the raised vent chassis by cutting the metal cross overs and removing the insert.
2. Cut and remove the foil material inside the knock-out hole. If you fail to remove the foil, the vent will not work.
3. If the unit will vent through the bottom or side:
• Attach the supplied duct transition to exhaust location with the provided sheet metal screws.
Bottom installation
Side installation
Attach sealing foam
1
5
/
8
x 16
Duct Transition Installation
• For bottom installations cut a hole in the cabinet floor to allow the exhaust transition and/or the duct to pass through the floor.
Top of vent resting on countertop
Cut hole in floor to allow duct to pass through on bottom venting installations
Back of unit
Side knock-out
Side knock-out
Floor
Rear knock-out with metal cross overs shown
4. If the unit will exhaust air from the back, attach a
3 ¼ x 10 duct to the vent hole created by removing the knock-out on the back of the unit.
Bottom knock-out
Vent Knock-out Locations - Rear View
Installation Instructions
5. Gently slide the vent into the rear of the countertop cutout with the electrical access panel toward the front.
Anchor leg
Top of vent resting on countertop
Front of raised vent
Electrical access panel
WARNING
Tape all duct joints securely to prevent combustion by-products, smoke or odors from entering the home.
Doing so will also improve system efficiency.
Installing the Blower and Ducts
1. Install the remote or in-line blower according to the blower installation instructions.
2. Install the duct work according to the Installation
Specifications section. Use sheet metal screws and duct tape to connect and seal all of the pieces. Support the duct weight as necessary to ensure sealed joints.
Put nuts/ washers on studs
REMP series remote blower
Floor
6. Loosely attach the anchoring legs to the studs on the left and right sides of the raised vent using the provided keps nuts and washers.
7. Adjust the anchoring leg height so that the end caps are gently resting on the counter, then tighten the hex nuts.
8. Secure the anchoring legs to the cabinet floor with the provided wood screws.
3 ¼ x 10 to 10” round transition and
45 adjustable elbow
°
Wall board
Backsplash
Raised vent
Range
Duct work between raised vent and remote blower
Raised vent configured for rear exhaust
Floor
Wiring/conduit that supplies power to remote blower (see Electrical
Installation, page 10)
Example of Installation with Rear Exhaust
(Side View)
9
Installation Instructions
Electrical Installation
WARNING
• ELECTRIC SHOCK HAZARD - Do not connect the raised vent power plug to the electrical outlet until installation is complete.
• Failure to complete electrical connections properly may result in an electric shock hazard or a damaged or non-functional system. Follow the wiring diagrams carefully to ensure a proper installation. Do not change the factory wired terminal connections inside the electrical access panel for the raised vent or the blower.
• To avoid an electric shock hazard and to prevent damage route all wiring away from hot surfaces.
1. Run the wiring/conduit line used to supply power from the raised vent to the blower parallel to the duct work.
2. Make sure the raised vent power plug is disconnected from the electrical outlet.
3. Remove the cover from the raised vent electrical access panel.
4. Connect the wiring/conduit to the blower according to the wiring diagrams on this page, the facing page and local codes and ordinances. Make sure all terminal connections, including the factory wired connections, are tight.
5. Replace the electrical access panel.
Match wire colors to terminals as shown.
Wires to power plug.
Pre-wired at factory.
Do not modify.
BLACK
WHITE
Blower Output
Power Input
Electrical access panel
Raised Vent
Front View
GREEN
Attach ground wire as shown
To power wiring/conduit.
Connect other end of wires to blower terminal block.
Raised Vent
Electrical Access Panel
10
Raised vent
Installation Instructions
REMP16 remote blower
Connect wires/conduit according to remote blower installation instructions
Range
See Raised Vent
Electrical Access
Panel on facing page
Floor
Wiring/conduit from raised vent to remote blower
Example of Installation with Bottom Exhaust
(Side View)
Range/Cooktop Installation
Install the range or cooktop according to its installation instructions.
11
Installation Instructions
Verifying Proper Operation
WARNING
• Read the raised vent use and care manual completely before operation.
• Install all of the front filters prior to operating the raised vent. Refer to the use and care manual for filter installation instructions.
CAUTION
To prevent damage to the raised vent power cord, route it away from the surfaces of the range or cooktop before connecting it.
1. Make sure the power switch on the top of the raised vent is in the up position.
2. Plug the raised vent power plug into the electrical outlet.
3. Press the power switch once to raise the vent to its operating position.
4. Once in the up position the vent should begin to draw air. Turn the variable speed control switch in both directions to verify that the system is operating correctly.
5. Press the top cap up/down switch once to lower the vent.
6. Make sure that the top cap on the raised vent intake does not catch on the back edge of the cooktop or range when the intake is lowered. If interference occurs, adjust the position of the cooktop or range.
Failure to eliminate any interference may result in permanent damage to the vent.
If the raised vent is not operational after installation:
• Make sure that power is being supplied to the unit.
• Make sure that power is being supplied to the blower from the raised vent.
• If the vent will not raise properly or makes a scraping sound check for obstructions interfering with the raising of the unit.
If the raised vent still does not function after performing the above checks, do not attempt to repair it yourself. Contact
Dacor Distinctive Service at (800) 793-0093 ex. 2822. Be sure to have all model and serial numbers from the product data labels for the raised vent and the blower available when you call.
Dacor is not responsible for the cost of correcting problems caused by a faulty installation.
Installation Checklist
□
Are the anchor legs extended down to make contact with the floor and tightened into place? Are the anchor legs fastened to the floor? Is the unit level?
□
Is the duct work completely installed? Are all joints attached with sheet metal screws and wrapped with duct tape?
□
Are both ends of the remote or in-line blower power cable connected (to the raised vent and to the blower itself)?
□
Are the vent filters installed according to the use and care manual instructions?
□
Is the power cord routed away from the hot surfaces of the range or cooktop.
□
Is the unit connected to an electrical outlet that meets the electrical specifications in these instructions?
□
Has proper operation been verified?
□
Has the warranty been activated on-line or the warranty card been filled out completely and mailed?
12
DOWN
LIMIT SWITCH
COM
NO NC
UP
LIMIT SWITCH
COM
NC NO
RED
Wiring Diagram
SNORKEL SWITCH
RED
BLUE
COM NO NC
WHT
CHASSIS
GROUND
STUD
BLUE
WHT
REMOTE POT
RELAY
N
COM
L
NO
ORNG
SPEED CONTROL
RED
BLK
L2 N2 L1 N1 GND GND
BLOWER
OUTPUT
POWER
INPUT
GROUND
13
Dacor ● 14425 Clark Avenue, City of Industry, CA 91745 ● Phone: (800) 793-0093 ● Fax: (626) 403-3130 ● www.dacor.com
Advertisement
Key Features
- Can be configured to exhaust through various locations
- Requires Dacor approved blower for proper operation
- Comes with a variable speed control switch