Appleton's ATX SWD Series Switches Catalog Pages

Appleton's ATX SWD Series Switches Catalog Pages
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWD Series: 16 and 32 A Switches – Flameproof
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK10
Applications:
• Designed to prevent operation in explosive atmospheres
during connect and disconnect operation of lighting and light
power loads.
• For use in hazardous areas where ignitable vapors, gases or
highly combustible dusts are present.
• For installation in chemical and petrochemical plants, refineries
and other process industries.
Features:
•
•
•
•
• Internal earth:
2
2 x 4 mm terminals
• External earth:
M5 for 16 Amps
M6 for 32 Amps
Standard Material of Fixtures:
• Gray painted marine grade aluminum alloy box.
• A2 stainless steel captive screws.
Two threaded entries (one top and one bottom) M20 or M25.
Switch mechanism fixed at the bottom of the box.
Padlockable handle.
Termination:
2
16A 4 mm terminals
2
32A 6 mm terminals
32 A Version
16 A Version
Catalog Number Logic:
SWD
Amperage:
016 = 16 A
032 = 32 A
X
XXXX
X
Wiring Diagram No.
Cable Entry:
A = 2 x M20
C = 2 x M25
X
Switch Type:
S = Switch
C = Changer or
Selector Switch
XX
CONTROL STATIONS & SWITCHES
Series:
SWD = SWD Series
Zone 1, 2 – 21, 22
ATEX / IEC Certified
XXX
Contact Configuration:
00
01
02
Number of Poles:
2 = 2-pole
3 = 3-pole
4 = 4-pole
Ordering Information:
Switching Arrangement:
16 A Switch
Switch
Type
Wiring
Diagram No.
Entries
Weight
(kg)
Volume
(dm3)
Catalog
Number
Old Catalog
Number
1-pole changeover
C100
2 x M20
2 x M25
1.1
3.8
SWD016C100A
SWD016C100C
–
–
2-pole switch
S200
2 x M20
2 x M25
1.1
3.8
SWD016S200A
SWD016S200C
093529
093526
S300
2 x M20
2 x M25
1.1
3.8
SWD016S300A
SWD016S300C
093530
093527
S400
2 x M20
2 x M25
1.1
3.8
SWD016S400A
SWD016S400C
093531
093528
Wiring
Diagram No.
Entries
Weight
(kg)
Volume
(dm3)
2-pole switch
S200
2 x M20
2 x M25
2.7
8
SWD032S200A
SWD032S200C
–
093544
3-pole switch
S300
2 x M20
2 x M25
2.7
8
SWD032S300A
SWD032S300C
–
093545
4-pole switch
S400
2 x M20
2 x M25
2.7
8
SWD032S400A
SWD032S400C
–
093546
3-pole switch
4-pole switch
32 A Switch
Switch
Type
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
Catalog
Number
Old Catalog
Number
ATX Product Catalog
C100
Contacts
1-2
3-4
X
X
S200
Contacts
1-2
3-4
Positions
0
1
Positions
0
1
S300
Positions
0
1
S400
Positions
0
1
X
1-2
X
1-2
X
X
X
Contacts
3-4
5-6
X
X
Contacts
3-4
5-6
X
X
7-8
X
Contact closed
358
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWD Series: 16 and 32 A Switches – Flameproof
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK10
Technical Data:
Standards:
Main Contacts
16 Amps
32 Amps
Rated insulation voltage (Ui)
Thermal rating
AC 21 A
AC 15
AC 23 A
690 V
20 A
16 A
6A
4 KW
7.5 KW
5.5 KW
4 KW
3 KW
4 KW
5.5 KW
3 KW
2.5 mm2/4 mm2
690 V
40 A
32 A
12 A
11 KW
11 KW
11 KW
11 KW
5.5 KW
11 KW
11 KW
11 KW
3 x 230 V
3 x 400 V
3 x 500 V
3 x 690 V
3 x 230 V
3 x 400 V
3 x 500 V
3 x 690 V
AC 3 A
Termination (flexible/solid)
Compliances: 32 A version:
Gas
Dust
Certification Type
Zones
Conforming to ATEX 94/9/CE
Symbol of Protection ATEX
CONTROL STATIONS & SWITCHES
Symbol of Protection IEC
T Rating
Surface Temperature
EN / IEC 60079-0; 60079-1
EN / IEC 60947-1; 60947-3
–
EN / IEC 60529 (IP); 62262 (IK)
6 mm2
Compliances: 16 A version:
Hazardous Area
Ex Standards
Product Standards
EMC Standards
Other Standards
BR1d (16A)
21–22
CE 0081 II 2 G
CE 0081 II 2 D
Ex d IIC
Ex tD A21
T6 for Ta = +40°C
T5 for Ta = +55°C
–
–
T95°C
-40°C to +55°C
CE Declaration of Conformity
50230
ATEX Certificate
LCIE 02 ATEX 6056
IEC Certificate
LCIE Ex 02.005
Other Certifications
Gas
Dust
Certification Type
1–2
Ambient Temperature
Hazardous Area
CF1E (32A)
Zones
Conforming to ATEX 94/9/CE
Symbol of Protection ATEX
Symbol of Protection IEC
T Rating
Surface Temperature
1–2
21–22
CE 0081 II 2 G
CE 0081 II 2 D
Ex d IIC
Ex tD A21
T6 for Ta +40°C
T5 for +40°C Ta +55°C
–
–
T95°C
Ambient Temperature
-40°C to +55°C
CE Declaration of Conformity
ATEX Certificate
50257
LCIE 03 ATEX 6044X
IEC Certificate
LCIE Ex 03.003X
GOST
Other Certifications
GOST
Ingress Protection
(solid and liquid)
IP66
Ingress Protection
(solid and liquid)
IP66
Impact Resistance (shock)
IK10
Impact Resistance (shock)
IK10
Dimensions (mm):
16 A Version
359
32 A Version
ATX Product Catalog
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWD Series: 20, 32, 63, 100, 125, 160 and 250 A Isolator Switches – Flameproof
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK10
Applications:
Catalog Number Logic:
• Designed to prevent operation in
explosive atmospheres during connect
and disconnect operation of power
loads.
• For use in hazardous areas where
ignitable vapors, gases or highly
combustible dusts are present.
• For installation in chemical and
petrochemical plants, refineries and
other process industries.
Features:
•
•
•
•
Padlockable handle in position “O”.
3 or 4-pole switch mechanism.
“NO-NC” early break auxiliary contact.
Main contact termination:
2
Up to 185 mm .
2
• Auxiliary contact termination: 2.5 mm .
• Cable entries:
Threaded entries two at bottom
and one at top – M20 to M63
• Supplied with:
1 x M20 blanking plug
1 x M8 earth stud
CONTROL STATIONS & SWITCHES
Standard Material of Fixtures:
• Gray painted marine grade aluminum
alloy box.
• A2 stainless steel captive screws.
Options:
• Visible break assembly including a
window to view power connection (only
for 100 A to 160 A versions).
63 A Version
SWD
XXX
XXXX
X
Series:
SWD = SWD Series
Zone 1, 2 – 21, 22
ATEX / IEC Certified
Amperage:
020 = 20 A
032 = 32 A
063 = 63 A
100 = 100 A
125 = 125 A
160 = 160 A
250 = 250 A
Wiring Diagram No.
X
X
Switch Type:
S = Switch
C = Changer or
Selector Switch
Cable Entry:
Options:
A = 2 x M20
V = Visible Break (1)
B = 3 x M20
C = 2 x M25
D = 2 x M25 + 1 x M20
E = 2 x M32 + 1 x M20
F = 2 x M40 + 1 x M20
G = 2 x M50 + 1 x M20
H = 2 x M63 + 1 x M20
J = 2 x M63 + 1 x M25
XX
Contact
Configuration:
00
01
02
Number of Poles:
2 = 2-Pole
3 = 3-Pole
4 = 4-Pole
X
(1) only for 100 A to 160 versions
Ordering Information:
SWD Flameproof Isolator Switches
Switch
Type
Wiring
Diagram No.
Certified
Type
Weight
(kg)
Volume
(dm3)
20 A – 3 x M20 threaded entries (1 Top and 2 Bottom)
3-pole switch
S300
CF2D
3.8
11
4-pole switch
S400
CF2D
3.8
11
Catalog
Number
Old Catalog
Number
SWD020S300B
SWD020S400B
093508
093509
32 A – Bottom entries: 1 x M25 + 1 x M20 – Top entries: 1 x M25
3-pole switch
S300
CF2D
3.8
11
SWD032S300D
4-pole switch
S400
CF10B
11
19.6
SWD032S400D
093510
093511
63 A – Bottom entries: 1 x M32 + 1 x M20 – Top entries: 1 x M32
3-pole switch
S300
CF10B
11
19.6
SWD063S300E
4-pole switch
S400
CF10B
11
19.6
SWD063S400E
093548
093512
100 A – Bottom entries: 1 x M40 + 1 x M20 – Top entries: 1 x M40
3-pole switch
S300
CF20B
13
24.5
SWD100S300F
4-pole switch
S400
CF20B
13
24.5
SWD100S400F
093513
093514
125 A – Bottom entries: 1 x M50 + 1 x M20 – Top entries: 1 x M50
3-pole switch
S300
CF20B
13
24.5
SWD125S300G
4-pole switch
S400
CF20B
13
24.5
SWD125S400G
093515
093516
160 A – Bottom entries: 1 x M50 + 1 x M20 – Top entries: 1 x M50
3-pole switch
S300
CF40B 50.5
235.2
SWD160S300G
4-pole switch
S400
CF40B 50.5
235.2
SWD160S400G
093517
093518
250 A – Bottom entries: 1 x M63 + 1 x M20 – Top entries: 1 x M63
3-pole switch
S300
CF60B
112
646.6
SWD250S300H
4-pole switch
S400
CF60B
112
646.6
SWD250S400H
093519
093520
Switching Arrangement:
S300
Positions
0
1
361
ATX Product Catalog
1-2
X
Contacts
3-4
5-6
X
X
S400
Positions
0
1
1-2
X
Contacts
3-4
5-6
X
X
7-8
X
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWD Series: 20, 32, 63, 100, 125, 160 and 250 A Isolator Switches – Flameproof
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK10
Technical Data:
Main Contacts
20 Amps
32 Amps
63 Amps
100 Amps
125 Amps
160 Amps
250 Amps
800 V
415 V / 500 V / 690 V
25 A
8 kV
50 kA (with fuse)
800 V
415 V / 500 V / 690 V
32 A / 32 A / 25 A
8 kV
50 kA (with fuse)
800 V
415 V / 500 V / 690 V
63 A / 63 A / 40 A
8 kV
50 kA (with fuse)
800 V
415 V / 500 V / 690 V
100 A
8 kV
100 kA (with fuse)
800 V
415 V / 500 V / 690 V
125 A
8 kV
63 kA (with fuse)
800 V
415 V / 500 V / 690 V
160 A / 160 A / 125 A
8 kV
80 kA (with fuse)
800 V
415 V / 500 V / 690 V
250 A / 250 A / 200 A
8 kV
50 kA (with fuse)
25 A
25 A
25 A
25 A
25 A
25 A
25 A
25 A
25 A
25 A
32 A
32 A
32 A
32 A
32 A
32 A
63 A
63 A
63 A
63 A
63 A
63 A
100 A
100 A
100 A
100 A
100 A
63 A
125 A
125 A
125 A
125 A
125 A
80 A
160 A
160 A
160 A
160 A
125 A
100 A
250 A
250 A
200 A
250 A
250 A
125 A
–
–
32 A
25 A
25 A
–
–
–
63 A
63 A
40 A
–
–
–
100 A
80 A
63 A
–
125 A
100 A
80 A
–
125 A
100 A
80 A
–
250 A
200 A
100 A
–
–
11 kW
11 kW
15 kW
24/48 V - 25 A (1)
–
–
–
–
–
–
–
–
0.75 to 6 mm2 / 10 mm2
15 kW
15 kW
18.5 kW
30 kW
30 kW
30 kW
45 kW
45 kW
45 kW
55 kW
55 kW
75 kW
75 kW
75 kW
75 kW
–
–
–
–
–
–
–
–
–
16 mm2 / 16 mm2
–
–
–
–
–
–
–
–
–
4 to 35 mm2 / 50 mm2
–
–
–
–
–
–
–
–
–
4 to 50 mm2 / 70 mm2
–
800 V - 125 A (1)
–
–
–
–
–
–
–
4 to 50 mm2 / 70 mm2
–
800 V - 125 A (1)
–
–
–
–
–
–
–
4 to 50 mm2 / 70 mm2
132 kW
140 kW
90 kW
220 V - 250 A (1)
440 V - 200 A (1)
500 V - 200 A (1)
220 V - 250 A (1)
440 V - 200 A (1)
500 V - 200 A (1)
220 V - 250 A (1)
440 V - 200 A (1)
500 V - 200 A (1)
95 mm2 / 150 mm2
230 V / 400 V
6A/4A
250 V
5A
250 V
5A
250 V
5A
250 V
5A
250 V
5A
230 V / 400 V
4A/3A
5 A / 250 V
4 A / 230 V - 3 A / 400 V
1 A / 24 V - 0.2 A / 48 V
2.5 mm2
6 A / 230 V
5 A / 250 V
–
–
2.5 mm2
5 A / 250 V
–
2.5 mm2
5 A / 250 V
–
2.5 mm2
5 A / 250 V
–
2.5 mm2
–
2.5 mm2
2.5 mm2
CONTROL STATIONS & SWITCHES
Rated Insulation Voltage (Ui)
Rated Operating Voltage (Ue)
Rated Operating Current (Ie)
Rated Surge Voltage (Uimp)
Short Circuit Resistance
Switching Capacity
AC 21 A
415 V
500 V
690 V
AC 22 A
415 V
500 V
690 V
AC 23 A
230 V
415 V
500 V
690 V
AC 23 A
230 V
Motor Power
415 V
(kW)
500 V
690 V
DC 21
–
–
DC 22
–
–
DC 23
–
–
Termination (Flexible / Solid)
Auxiliary Contacts
Rated Operating Voltage (Ue)
Rated Operating Current (Ie)
Switching Capacity
AC 15
DC 14
Termination (Flexible)
(1) Two contacts connected in series.
Compliances:
Hazardous Area
Compliances:
Gas
Dust
Certification Type
Zones
Conforming to ATEX 94/9/CE
Symbol of Protection ATEX
Symbol of Protection IEC
T Rating
Surface Temperature
Ambient Temperature
CE Declaration of Conformity
ATEX Certificate
IEC Certificate
CF2D
1–2
21–22
CE 0081 II 2 D
Ex d IIB
Ex tD A21
T6 for Ta +40°C
T5 for +40°C Ta +55°C
–
–
T95°C
-40°C to +55°C
50254
LCIE 03 ATEX 6061X
LCIE Ex 03.006X
GOST
Ingress Protection
(solid and liquid)
IP66
Impact Resistance (shock)
IK10
Internal Volume
Gas
Dust
Certification Type
CE 0081 II 2 G
Other Certifications
Hazardous Area
2dm3
CF
Zones
Conforming to ATEX 94/9/CE
1–2
21–22
CE 0081 II 2 G
CE 0081 II 2 D
Ex d IIB
Ex tD A21
Symbol of Protection ATEX
Symbol of Protection IEC
T Rating
T6
–
Surface Temperature
–
T80°C
Ambient Temperature
CE Declaration of Conformity
-40°C to +55°C
50229
ATEX Certificate
LCIE 02 ATEX 6057X
IECEx Certificate
IECEx LCI 08.0023X
Other Certifications
GOST
Ingress Protection (solid and liquid)
IP66
Impact Resistance (shock)
IK10
Internal Volume
> 2dm3
*CF10B Ambient T° -20°C to +55°C
Standards:
Ex standards
Product standards
EMC standards
Other standards
EN / IEC 60079-0; 60079-1
EN / IEC 60947-1; 60947-3
/
EN / IEC 60529(IP); 62262(IK)
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
ATX Product Catalog
362
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWD Series: 20, 32, 63, 100, 125, 160 and 250 A Isolator Switches – Flameproof
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK10
Dimensions (mm):
CF2D
CF10B
CF20B
Fix. 245
Fix. 245
CONTROL STATIONS & SWITCHES
Fix. 250
Fix. 140
Fix. 208
48.5
CF40B
CF60B
Fix. 376
363
Fix. 616
Fix. 391
Fix. 245
ATX Product Catalog
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009