Appleton's ATX SWE Series 16 and 20 Amp Switches Catalog Pages

Appleton's ATX SWE Series 16 and 20 Amp Switches Catalog Pages
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWE Series: 16 and 20 A Switches – Increased Safety
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK09 or IK10
Applications:
20 Amp version:
• Two M20 threaded entries on the bottom of the box.
• Switch mechanism fixed on the bottom of the box.
• Padlockable handle in position 0 using maximum 4 padlocks
(maximum handle dia. 8 mm and minimum 15 mm length).
• Termination:
2
2
2.5 mm flexible / 4 mm solid
• Internal earth:
2
2 x 4 mm terminals
• Supplied with:
1 x yellow self-adhesive laminated plastic label with black
lettering (65 x 18 mm)
• Designed to prevent operation in explosive atmospheres
during connect and disconnect operation of lighting and
light power loads.
• For use in hazardous areas where ignitable vapors, gases
or highly combustible dusts are present.
• For installation in chemical and petrochemical plants,
refineries and other process industries.
Features:
16 Amp version:
• Two bottom M20 clearance holes.
• Switch mechanism fixed at the bottom of the box.
• Termination:
2
Type 1: 2.5 mm
2
2
Type 2: 2.5 mm flexible/4 mm solid
• Internal earth:
2
2 x 2.5 mm terminals
• Supplied with:
1 x white self-adhesive laminated plastic label
with black lettering (58 x 18 mm)
Standard Material of Fixtures:
16 Amp version:
• Polyamide box.
• A2 stainless steel coarse pitch screws (1 and a half turn).
• Polyamide cable glands.
• Nickel plated brass locknuts.
20 Amp version:
• Polyester box
• A2 stainless steel captive screws.
• Polyamide cable glands.
Catalog Number Logic:
CONTROL STATIONS & SWITCHES
SWE
Series:
SWE = SWE Series
Zone 1, 2 – 21, 22
ATEX / IEC Certified
XX
XXXX
Amperage:
016 = 16 A
X
020 = 20 A
Switch Type:
S = Switch
C = Changeover
Switch
X
Wiring Diagram No.
X
Number of Poles:
1 = 1-Pole
3 = 3-Pole
2 = 2-Pole
4 = 4-Pole
Contact Configuration:
00
01
02
16 A Switch
Padlockable handle.
Two M20 polyamide cable glands (cable dia. 6.5 to 14.5 mm) on the bottom.
Changeover switch
2-pole
Wiring
Diagram No.
C101
S201
Type
Weight
(kg)
Volume
(dm3)
1
1
0.53
0.53
2.00
2.00
Catalog
Number
SWE016C101AG
SWE016S201AG
Old Catalog
Number
098614
098608
16 A Twist Button - Type 2
Changeover switch
2-pole
Wiring
Diagram No.
C100
S200
Type
Weight
(kg)
Volume
(dm3)
2
2
0.50
0.50
2.00
2.00
Catalog
Number
SWE016C100A
SWE016S200A
Old Catalog
Number
098631
098632
Padlockable handle.
Two M20 polyamide cable glands (cable dia. 6.5 to 14.5 mm) on the bottom.
Changeover switch
2-pole
3-pole
4-pole
351
Wiring
Diagram No.
Weight
(kg)
Volume
(dm3)
C100
S202
S301
S401
1.00
1.00
1.00
1.00
2.00
2.00
2.00
2.00
Catalog
Number
SWE020C100AG
SWE020S202AG
SWE020S301AG
SWE020S401AG
ATX Product Catalog
Old Catalog
Number
096250
096251
096260
096261
S201
Contacts
11-12 23-24
X
X
Positions
0
1
Contacts
13-14 23-24
X
X
16 A Twist Button
C100
20 A Switch
Switch
Type
C101
Positions
0
1
Positions
0
1
Non-padlockable handle.
Two M20 clearance holes on the bottom.
Switch
Type
Options:
G = With Polyamide Cable Gland
P = With Brass Earth Continuity Plate
Switching Arrangement:
16 A Switch - Type 1
Switch
Type
Cable Entry:
A = 2 x M20
XX
Ordering Information:
X
S200
Contacts
1-2
3-4
X
X
Positions
0
1
Contacts
3-4
3-4
X
X
20 A Switch
C100
Contacts
1-2
3-4
X
X
S301
Contacts
1-2
3-4
5-6
Positions
0
1
Positions
0
1
S401
Positions
0
1
X
1-2
X
X
S202
Positions
0
1
Contacts
3-4
5-6
X
X
X
X
Contacts
1-2
3-4
X
X
Closed contact
7-8
X
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWE Series: 16 and 20 A Switches – Increased Safety
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IEC
IP66 - IK09 or IK10
Technical Data:
Main Contacts
16 Amps Type 1
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Switching capacity:
AC 1
AC 12
AC 14
AC 15
AC 21
AC 23
AC 3
AC 3
DC 1
DC 1
DC 1
DC 13
DC 13
Termination (flexible/solid)
16 Amps Type 2
20 Amps
750 V
690 Vac 1 / 110 V DC 1
16 A
500 V
500 V
16 A
500 V
500 V
20 A
16 A
690 V
–
–
16 A
415 V
–
–
08 A
500 V
04 A
690 V
10 A
24 V
06 A
60 V
06 A
110 V (*)
–
–
2.5 mm2 / 4 mm2
16 A
500 V
16 A
400 V
10 A
400 V
6A
500 V
–
–
–
–
–
–
–
1A
110 V
2A
24 V
2.5 mm2
–
–
–
–
16A
500V
16A
400V
–
–
–
–
–
–
–
2.5 mm2 / 4 mm2
(*) 2 contacts connected in series
Hazardous Area
Gas
Dust
1–2
Conforming to ATEX 94/9/CE
II 2 G
CE 0081
Ex de IIC
T6
–
Surface Temperature
–
T80°C
CE Declaration of Conformity
ATEX Certificate
IEC Certificate
2 dia 5.5
20 A Version
-20°C to +40°C
50221
LCIE 00 ATEX 60472
LCIE Ex 00.017
Other Certifications
GOST
Index of Protection
(solid and liquid)
IP66
Impact Resistance (shock)
90
II2 D
Ex tD A21
T Rating
Ambient Temperature
80
2 Ø2.5
Symbol of Protection IEC
CE 0081
21–22
55
Zones
Symbol of Protection ATEX
16 A Version
PCe
104
Certified Type
IK10 (Polyester) / IK09 (Polyamide)
Standards:
Ex standards
Product standards
EMC standards
Other standards
EN / IEC 60079-0; 60079-1; 60079-7; 61241-0; 61241-1
EN / IEC 60947-1; 60947-3; 60947-5
EN / IEC 55015; 61547
EN / IEC 60529 (IP); 62262 (IK)
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
ATX Product Catalog
352
CONTROL STATIONS & SWITCHES
Dimensions (mm):
Compliances:
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWE Series: 40, 63 and 160 A Switches – Increased Safety
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IECEx
IP66 - IK10
Applications:
• Designed to prevent operation in explosive atmospheres during
connect and disconnect operation of power loads.
• For use in hazardous areas where ignitable vapors, gases or
highly combustible dusts are present.
• For installation in chemical and petrochemical plants, refineries
and other process industries.
Features:
63 Amp version:
• Padlockable handle in position “O” using max. 4
padlocks (max. handle dia. 8 mm and min. 15 mm length).
• 3 or 4-pole switch mechanism with one ‘NO’ early
break auxiliary contact.
2
• Main contact termination: 35 mm
2
• Auxiliary contact termination: 2.5 mm
• Supplied with:
Cable entries:
1 x M32 clearance on top
1 x M32 and 1 x M20 clearance on bottom
• Supplied with:
2 x M32 polyamide cable glands (cable 10 to 25 mm)
1 x M20 blanking plug
Yellow laminated plastic label with black
lettering (65 x 18 mm)
160 Amp version:
• Hinged door.
• Closed with plastic double bar locks (key supplied).
• Supplied with 4 fixing lugs.
• Padlockable handle in position “O”.
• 3 or 4-pole switch mechanism with one ‘NO’ early
break auxiliary contact.
2
• Main contact termination: 120 mm
2
• Auxiliary contact termination: 2.5 mm
• Supplied with:
Cable entries:
1 x M63 clearance on top
1 x M63 and 1 x M25 clearance on bottom
• Supplied with:
2 x M63 polyamide cable glands (cable 36 to 44 mm)
1 x M25 blanking plug
Standard Materials:
•
•
•
•
•
Polyester (GRP) box.
316L stainless steel box.
A2 stainless steel captive screws.
Polyamide cable glands and blanking plugs.
Nickel plated brass locknut.
Catalog Number Logic:
SWE
XXXX
Amperage:
040 = 40A
063 = 63 A
160 = 160 A
Wiring Diagram No.
X
X
Switch Type:
S = Switch
C = Changer or
Selector Switch
Series:
SWE = SWE Series
Zone 1, 2 – 21, 22
ATEX / IEC Certified
X
Number of Poles:
3 = 3-pole
4 = 4-pole
Options:
G = With Cable Gland and Blanking Plug
P = With Brass Earth Continuity Plate
S = Stainless Steel Box
XX
Cable Entry:
A = 2 x M20
B = 3 x M20
C = 2 x M25
D = 2 x M25 + 1 x M20
E = 2 x M32 + 1 x M20
Contact
Configuration:
00
01
02
Polyester Box:
63 A Switch – 2 x M32 + 1 x M20
3-pole switch
4 Pole Switch
S302
Wiring
Diagram No.
Weight
(kg)
Volume
(dm3)
S302
S402
8
8
14.5
14.5
Catalog
Number
SWE063S302EG
SWE063S402EG
Old Catalog
Number
096269
096270
3-pole switch
4 Pole Switch
Positions
0
1
S402
160 A Switch – 2 x M63 + 1 x M25
Switch
Type
F
G
H
J
=2
=2
=2
=2
x
x
x
x
M40
M50
M63
M63
+
+
+
+
1
1
1
1
x
x
x
x
M20
M20
M20
M25
Switching Arrangements:
Ordering Information:
Switch
Type
X
Wiring
Diagram No.
Weight
(kg)
Volume
(dm3)
S302
S402
16
16
75
75
Wiring
Diagram No.
Weight
(kg)
Volume
(dm3)
S402
25
75
Catalog
Number
SWE160S302JG
SWE160S402JG
Old Catalog
Number
Positions
0
1
Contacts
1
2
3
X
X
X
Aux
1
X
X
Aux
X
Contacts
2
3
X
X
4
X
096271
096272
Stainless Steel Box:
160 A Switch – 2 x M63 + 1 x M25
Switch
Type
4-pole switch
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
Catalog
Number
SWE160S402JS
Old Catalog
Number
–
ATX Product Catalog
354
CONTROL STATIONS & SWITCHES
XX
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWE Series: 40, 63 and 160 A Switches – Increased Safety
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IECEx
IP66 - IK10
Technical Data:
Main Contacts
63 Amps
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Rated Surge Voltage
Switching Capacity
AC 21 A / AC 22 A
63 A
15 kW
22 kW
30 kW
18.5 kW
11 kW
18.5 kW
22 kW
15 KW
AC 23 A
AC 3
CONTROL STATIONS & SWITCHES
160 Amps
690 Vac
690 Vac
63 A
6 KV
690 Vac
690 Vac
160 A
8 KV
230 V to 690 V
230 V
400 V
500 V
690 V
230 V
400 V
500 V
690 V
DC 21
–
DC 22
–
DC 23
–
Auxiliary Contacts
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Switching Capacity:
400 V
400 V
10 A
AC 15
6A
4A
Others
Termination (flexible/solid)
160 A
400 V to 690 V
80 kW
110 kW
55 kW
400 V
500 V
690 V
90 kW
70 kW
400 V
500 V
160 A
160 A
160 A
100 A
160 A
63 A
220 V (*)
440 V (*)
220 V (*)
440 V (*)
220 V (*)
440 V (*)
230 V
230 V
10 A
230 V
400 V
6A
35 mm2
230 V
120 mm2
(*) 2 contacts connected in series per pole
Compliances:
Hazardous Area
Gas
Certified Type
Zones
Conforming to ATEX 94/9/CE
Symbol of Protection ATEX
Symbol of Protection IEC
T Rating
Surface Temperature
Ambient Temperature
CE Declaration of Conformity
Dust
Hazardous Area
CAe (Polyester box)
1–2
CE 0081
21–22
II 2 G
Gas
Certified Type
CE 0081
Zones
II2 D
Ex de IIC
Ex tD A21
T5 at +40°C
T4 at +55°C
–
–
T95°C at +40°C
T130°C at +55°C
-30°C to +55°C, -20ºC to +55ºC (40 A & 63 A)
50235
Conforming to ATEX 94/9/CE
Symbol of Protection ATEX
Symbol of Protection IEC
T Rating
Surface Temperature
Ambient Temperature
CE Declaration of Conformity
Dust
JBe (Stainless steel box)
1–2
CE 0081
21–22
II 2 G
CE 0081
Ex de IIC
Ex tD A21
T5 at +40°C
T4 at +55°C
–
–
T95°C at +40°C
T130°C at +55°C
-30°C to +55°C
50232
ATEX Certificate
LCIE 02 ATEX 6248X
ATEX Certificate
LCIE 02 ATEX 6118X
IECEx Certificate
LCI 04.0016X
IECEx Certificate
LCIE Ex 02.010X
Other Certifications
Index of Protection
(solid and liquid)
GOST
Impact Resistance (shock)
IK10
IP66
II2 D
Other Certifications
Index of Protection
(solid and liquid)
GOST
Impact Resistance (shock)
IK10
IP66
Standards:
Ex standards
Product standards
EMC standards
Other standards
355
EN / IEC 60079-0; 60079-1; 60079-7; 61241-0; 61241-1
EN / IEC 60947-1; 60947-3
EN / IEC 55015; 61547
EN / IEC 60529 (IP); 62262 (IK)
ATX Product Catalog
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
Control Stations & Switches: Switches, Circuit Breakers and "Break Glass" Call Points
SWE Series: 40, 63 and 160 A Switches – Increased Safety
Zone 1 & 2 - 21 & 22
II 2 GD
ATEX / IECEx
IP66 - IK10
Dimensions (mm):
40 A / 63 A Polyester Version
160 A Polyester Version
27.5
CONTROL STATIONS & SWITCHES
160 A Stainless Steel Version
Cable entries as per Cat. No.
270.5
Fix. 525
254.5
Fix. 407
Visit our website at www.egsatx.com or www.appletonelec.com
or contact us at +33.3.22.54.27.54. © September 2009
ATX Product Catalog
356
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising