PRE Series Plugs and Sockets

PRE Series Plugs and Sockets
Plugs and Receptacles
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 16 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK09/10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Applications
• Plugs and receptacles are used with portable or stationery
electrical equipment such as:
— Lighting systems
— Conveyors
— Heaters
— Motor generators
— Air conditioning equipment
— Compressors
— Pumps
• For use in corrosive atmospheres and installations in Zone 1
and 2 and 21 and 22 of the oil and gas industry; such as:
— Refineries
— Chemical and petrochemical plants
— Pipelines
— Loading docks
— Onshore and offshore drilling platforms
Plug
Wall Mounting Socket
Mobile Socket
Flush Socket
Features
• Plug and socket system is designed with a safe disconnect
mechanism to insure maximum hazardous location protection:
— The contact separation is in a flameproof chamber
— The automatic electrical disconnection of each phase is
contained in a second flameproof chamber
• Short circuit protection is 20 kA, while normal reference is 10
kA.
• Different voltages are color coded for easy identification.
• The receptacles are keyed to accept only ATX plugs (other plugs
can not be inserted).
• ATX plugs can be used in non-hazardous IEC 309 sockets.
• Operating temperature of -40 ºC to +55 ºC (-40 ºF to +131 ºF)
Standard Materials
Technical Data
Breaking Capacity
• Wall Socket for 2P - 2P+E - 3P: high impact resistance
polycarbonate
• Wall Socket for 3P+E - 3P+N+E: high impact resistance
fiberglass reinforced polyester
• Plug, mobile socket and flush socket: polyamide
4 kW – 220 V
4.3 kW – 240 V
AC 3
7.5 kW – 380 V
ATEX/IECEx Certifications and Compliances
• Certification Type PCX, PCX/EN
• Gas: Zones 1 and 2
— Conforming to ATEX 94/9/CE: CE 0081
II 2 G
— ATEX/IEC Protection: Ex de IIC
— T6 for Ta  +40 °C (+104 °F) and T5 for Ta  +55 °C (+131 °F)
— Ambient Temperature: -40 °C  Ta  +55 °C (-40 °F  Ta 
+131 °F)
• Dust: Zones 21 and 22
— Conforming to ATEX 94/9/CE: CE 0081
II 2 D
— ATEX/IEC Protection: Ex tD A21
— Surface Temperature: T68 °C (T154 °F)
— Ambient Temperature: -40 °C  Ta  +55 °C (-40 °F  Ta 
+131 °F)
• CE Declaration of Conformity: 50228, 5C214
• ATEX Certificate: LCIE 02 ATEX 6068, LCIE 02 ATEX 0001U
• IECEx Certificate: IECEx LCI 04.0014, IECEx LCI 04.0012
• Other Certifications: GOST
• Ingress Protection (solid and liquid): IP66
• Impact Resistance (shock): IK10 (Polyester) and IK09
(Polyamide)
• Ex Standards: EN/IEC 60079-0; 60079-1; 60079-7; 61241-0;
61241-1
• Product Standards: EN/IEC 60309-1, 60309-2
• Other Standards: EN/IEC 60529 (IP), 62262 (IK)
1298
8.2 kW – 415 V
ICC
20 kA
NBR IEC Brazilian Certifications and Compliances
•
•
•
•
•
•
•
•
•
Certification Type PCX, PCX/EN
Gas: Zones 1 and 2
Dust: Zones 21 and 22
IEC Protection: Ex de IIC Gb; T6 for Ta  +40 °C (+104 °F) and
T5 for Ta  +55 °C (+131 °F)
Ambient Temperature: -40 °C  Ta  +55 °C (-40 °F  Ta 
+131 °F)
Inmetro Certificate: BR230639, BR230598-U
Ingress Protection (solid and liquid): IP66
Ex Standards: NBR IEC 60079-0; 60079-1; 60079-7
Other Standards: NBR IEC 60529 (IP)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 16 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK09/10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Wall Mounting Socket
Plug
Mobile Socket
• Three M20 threaded entries
• One PG16 integrated cable
•
(one on the top and two on the
gland – Ø 6.5 to Ø 14.5 mm
bottom).
(Ø 0.26 to Ø 0.57”).
• Supplied with one M20 cable
• Terminal capacity 2.5 mm (0.004 •
gland – Ø 6.5 to Ø 14.5 mm
in2).
(Ø 0.26 to Ø 0.57”) and two M20
blanking plugs.
• Terminal capacity 2 x 4 mm
(0.003 x 0.006 in ). Can be
through-wired.
• Fitted with three linked earth
terminals.
2
Flush Socket
One PG16 integrated cable
gland – Ø 6.5 to Ø 14.5 mm (Ø
0.26 to Ø 0.57”).
Terminal capacity 2 x 4 mm
(0.003 x 0.006 in ).
• Terminal capacity 2 x 4 mm
(0.003 x 0.006 in ).
2
2
2
2
2
2
PRE
2
IECEx Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
ATEX / IEC
16
R
Amps:
16 - 16A
Pin Configuration:
2 - 2P
3 - 2P+E
4 - 3P+E
5 - 3P+N+E
6 - 3P
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
M - Mobile Socket
F - Flush Socket
Catalog Numbering Guide - NBR IEC Brazilian Certified Plugs and Receptacles
N PRE
2
16
NBR IEC Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
NBR IEC Certified
P
R
P
Amps:
16 - 16A
Pin Configuration:
2 - 2P
3 - 2P+E
4 - 3P+E
5 - 3P+N+E
6 - 3P
Voltage:
P - 20 - 25 Vac 50/60 Hz
W1 - 20 - 50 Vdc
W - 40 - 50 Vac 50/60 Hz
Y - 100 - 130 Vac 50/60 Hz
B - 200 - 250 Vac 50/60 Hz
R - 380 - 415 Vac 50/60 Hz
N - 480 - 500 Vac 50/60 Hz
G - 50 - 500 Vac 300 to 500 Hz
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
M - Mobile Socket
F - Flush Socket
Voltage:
P - 20 - 25 Vac 50/60 Hz
W1 - 20 - 50 Vdc
W - 40 - 50 Vac 50/60 Hz
Y - 100 - 130 Vac 50/60 Hz
B - 200 - 250 Vac 50/60 Hz
R - 380 - 415 Vac 50/60 Hz
N - 480 - 500 Vac 50/60 Hz
G - 50 - 500 Vac 300 to 500 Hz
ELV: Extra Low Voltage
Purple
20/25 Vac
White
20/50 Vdc
White
40/50 Vac
LV: Low Voltage
Yellow
Blue
Red
Black
100/130 Vac
200/250 Vac
380/415 Vac
480/500 Vac
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
Green
50/500 Vac
(300 to 500 Hz)
1299
Plugs and Receptacles
Catalog Numbering Guide - IECEx Internationally Certified Plugs and Receptacles
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 16 Amp Extra Low Voltage and Low Voltage Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK09/10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Catalog Number
Description
Pin Configuration
NBR
Volume dm3 (in3)
Wall Socket
0.6 (1.3)
3.8 (231.89)
PRE216RP
NPRE216RP
Plug
0.2 (0.4)
0.6 (361.6)
PRE216PP
NPRE216PP
0.4 (0.9)
1.3 (79.33)
PRE216MP
NPRE216MP
Extra Low Voltage: ELV
20/25 Vac 50/60 Hz — Purple
Mobile Socket
polarization
tab
2P
Flush Socket
Wall Socket
10h
0.2 (0.4)
1.3 (79.33)
PRE216FP
NPRE216FP
0.6 (1.3)
3.8 (231.89)
PRE316RP
NPRE316RP
0.2 (0.4)
0.6 (36.61)
PRE316PP
NPRE316PP
0.4 (0.9)
1.3 (79.33)
PRE316MP
NPRE316MP
0.2 (0.4)
1.3 (79.33)
PRE316FP
NPRE316FP
Wall Socket
0.6 (1.3)
3.8 (231.89)
PRE616RP
NPRE616RP
Plug
0.2 (0.4)
0.6 (36.61)
PRE616PP
NPRE616PP
0.4 (0.9)
1.3 (79.33)
PRE616MP
NPRE616MP
0.2 (0.4)
1.3 (79.33)
PRE616FP
NPRE616FP
0.6 (1.3)
3.8 (231.89)
PRE216RW1
NPRE216RW1
Plug
10h
Mobile Socket
2P+E
Flush Socket
Mobile Socket
3P
Flush Socket
Plugs and Receptacles
IECEx
Weight kg (lb)
polarization
tab
20/50 Vdc — White
Wall Socket
0.2 (0.4)
0.6 (36.61)
PRE216PW1
NPRE216PW1
0.4 (0.9)
1.3 (79.33)
PRE216MW1
NPRE216MW1
0.2 (0.4)
1.3 (79.33)
PRE216FW1
NPRE216FW1
Wall Socket
0.6 (1.3)
3.8 (231.89)
PRE216RW
NPRE216RW
Plug
0.2 (0.4)
0.6 (36.61)
PRE216PW
NPRE216PW
0.4 (0.9)
1.3 (79.33)
PRE216MW
NPRE216MW
0.2 (0.4)
1.3 (79.33)
PRE216FW
NPRE216FW
auxiliary
pin 12h
0.6 (1.3)
3.8 (231.89)
PRE616RW
NPRE616RW
0.2 (0.4)
0.6 (36.61)
PRE616PW
NPRE616PW
polarization
tab
0.4 (0.9)
1.3 (79.33)
PRE616MW
NPRE616MW
0.2 (0.4)
1.3 (79.33)
PRE616FW
NPRE616FW
0.6 (1.3)
3.8 (231.89)
PRE316RY
NPRE316RY
Plug
Mobile Socket
Flush Socket
auxiliary
tab 10h
2P
polarization
tab
40/50 Vac 50/60 Hz — White
Mobile Socket
2P
Flush Socket
Wall Socket
Plug
Mobile Socket
3P
Flush Socket
polarization
tab
Low Voltage: LV
100/130 Vac 50/60 Hz — Yellow
Wall Socket
4h
Plug
Mobile Socket
L/+
Flush Socket
2P+E
0.2 (0.4)
0.6 (36.61)
PRE316PY
NPRE316PY
0.4 (0.9)
1.3 (79.33)
PRE316MY
NPRE316MY
0.2 (0.4)
1.3 (79.33)
PRE316FY
NPRE316FY
0.6 (1.3)
3.8 (231.89)
PRE316RB
NPRE316RB
0.2 (0.4)
0.6 (36.61)
PRE316PB
NPRE316PB
0.4 (0.9)
1.3 (79.33)
PRE316MB
NPRE316MB
0.2 (0.4)
1.3 (79.33)
PRE316FB
NPRE316FB
200/250 Vac 50/60 Hz — Blue
Wall Socket
Plug
L/+
6h
Mobile Socket
Flush Socket
1300
2P+E
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 16 Amp Low Voltage Plugs and Sockets and Accessories
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK09/10
Description
Pin Configuration
IECEx
Catalog Number
NBR
Weight kg (lb)
Volume dm3 (in3)
1.5 (3.3)
4.7 (286.81)
PRE416RB
0.6 (1.3)
0.6 (361.6)
PRE416PB
NPRE416PB
0.6 (1.3)
4.0 (244.09)
PRE416MB
NPRE416MB
0.2 (0.4)
1.3 (79.33)
PRE416FB
NPRE416FB
Low Voltage: LV
200/250 Vac 50/60 Hz — Blue
Wall Socket
L1
Plug
9h
Mobile Socket
L3
3P+E
Flush Socket
key way
NPRE416RB
4.7 (286.81)
PRE516RB
NPRE516RB
0.3 (0.7)
1.3 (79.33)
L3
3P+N+E (1)
PRE516PB
NPRE516PB
0.6 (1.3)
4.0 (244.09)
PRE516MB
NPRE516MB
(1) 120/208 V - 144/250 Vac 50/60 Hz
0.2 (0.4)
1.3 (79.33)
PRE516FB
NPRE516FB
1.5 (3.3)
4.7 (286.81)
PRE416RR
NPRE416RR
0.2 (0.4)
0.6 (361.6)
PRE416PR
NPRE416PR
0.6 (1.3)
4.0 (244.09)
PRE416MR
NPRE416MR
0.3 (0.7)
1.3 (79.33)
PRE416FR
NPRE416FR
1.6 (3.5)
4.7 (286.81)
PRE516RR
NPRE516RR
0.3 (0.7)
1.3 (79.33)
PRE516PR
NPRE516PR
Plug
N
Mobile Socket
L2
380/415 Vac 50/60 Hz — Red
Wall Socket
L2
L1
Plug
6h
L3
Mobile Socket
3P+E
Flush Socket
L2
L1
Wall Socket
6h
Plug
N
L3
0.6 (1.3)
4.0 (244.09)
PRE516MR
NPRE516MR
0.3 (0.7)
1.3 (79.33)
PRE516FR
NPRE516FR
Wall Socket
1.5 (3.3)
4.7 (286.81)
PRE416RN
NPRE416RN
Plug
0.2 (0.4)
0.6 (361.6)
PRE416PN
NPRE416PN
0.6 (1.3)
4.0 (244.09)
PRE416MN
NPRE416MN
0.3 (0.7)
1.3 (79.33)
PRE416FN
NPRE416FN
1.6 (3.5)
4.7 (286.81)
PRE516RG
NPRE516RG
0.2 (0.4)
0.6 (361.6)
PRE516PG
NPRE516PG
0.6 (1.3)
4.0 (244.09)
PRE516MG
NPRE516MG
0.3 (0.7)
1.3 (79.33)
PRE516FG
NPRE516FG
Mobile Socket
Flush Socket
3P+N+E (2)
(2) 200/346 V - 240/415 Vac 50/60 Hz
480/500 Vac 50/60 Hz — Black
7h
Mobile Socket
3P+E
Flush Socket
50/500 Vac 300/500 Hz — Green
Wall Socket
Plug
Mobile Socket
Flush Socket
L3
L2
2h
N
L1
3P+N+E
Accessories
Description
IECEx
Catalog Number
NBR
M5 earth stud with black neoprene sealing washer and green/yellow earth
conductor, length 300 mm (11.8”)
PREESTM20
NPREESTM20
M20 earth continuity adaptor with black neoprene sealing washer and green/
yellow earth conductor, length 300 mm (11.8”)
PREECAM20
NPREECAM20
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
1301
Plugs and Receptacles
1.6 (3.5)
9h
L1
Wall Socket
Flush Socket
L2
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
Increased Safety
Dimensions
16A — 2P — 2P+E — 3P Versions
Wall Mounting Sockets
82.5 mm
(3.25”)
63.0 mm
(2.48”)
Plugs
120.0 mm
(4.72”)
5.5 mm
(0.22”)
5.5 mm
(0.22”)
133.0 mm
(5.24”)
65.0 mm
(2.56”)
Mobile Sockets
Flush Sockets
Ø
39.0 mm
(1.54”)
54.0 mm
(2.13”)
42.0 mm
(1.65”)
Ø
39.0 mm
(1.54”)
Ø
4.2 mm
(0.17”)
Ø
4.2 mm
(0.17”)
160.0 mm (6.30”)
3.15”/
80.0 mm
3.0 mm
(0.12”)
76.0 mm maximum
(3.00”)
210 mm (8.27”)
42.0 mm
(1.65”)
46.0 mm
(1.81”)
54 mm
(2.13”)
46.0 mm
(1.81”)
130.0 mm
(5.12”)
80.0 mm
(3.15”)
Plugs and Receptacles
Can be mounted on panel - 0.12"/3.0 mm thickness maximum
160.0 mm
(6.30”)
49.5 mm
(1.95”)
58.0 mm
(2.28”)
152.0 mm (5.98”)
202.0 mm (7.95”)
125.0 mm
(4.92”)
272.0 mm (10.71”)
76.0 mm
56.0 mm (3.00”)
(2.20”)
16A — 3P+E — 3P+N+E Versions
Wall Mounting Sockets
97.0 mm
(3.82”)
Plugs
145.0 mm
(5.71”)
140.0 mm
(5.51”)
B
A C
310.0 mm (12.20”)
Fix. 105.0 mm
(4.13”)
240.0 mm (9.45”)
Fix.
80.0 mm
(3.15”)
Ø
6.0 mm
(0.24”)
Dimensions in Millimeters (Inches)
A
B
C
3P+E
66.0 (2.60)
154.0 (6.06)
55.5 (2.19)
3P+N+E
73.0 (2.87)
166.0 (6.54)
62.0 (2.44)
Mobile Sockets
Flush Sockets
150.0 mm
(5.91”)
68.0 mm
(2.68”)
56.0 mm
(2.20”)
90.0 mm
(3.54”)
160.0 mm
(6.30”)
3.0 mm
(0.12”)
maximum
76.0 mm
(3.00”)
230.0 mm (9.06”)
1302
Ø
49.5 mm
(1.95”)
Ø
4.2 mm
(0.17”)
60.0 mm
(2.36”)
Can be mounted on panel - 3.0 mm (0.12”) thickness maximum
56.0 mm
(2.20”)
Ø
4.2 mm
0.17”
Ø
49.5 mm
(1.95”)
68.0 mm
(2.68”)
160.0 mm (6.30”)
90.0 mm
(3.54”)
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 16 Amp Plug and Socket Dimensions
76.0 mm
56.0 mm (3.00”)
(2.20”)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 32 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Applications
LV: Low Voltage
• Plugs and sockets are used with portable or stationery
electrical equipment such as:
— Lighting systems
— Conveyors
— Heaters
— Motor generators
— Air conditioning equipment
— Compressors
— Pumps
• For use in corrosive atmospheres and installations in Zone 1
and 2 and 21 and 22 of the oil and gas industry, such as:
— Refineries
— Chemical and petrochemical plants
— Pipelines
— Loading docks
— Onshore and offshore drilling platforms
Plug
Wall Mounting Socket
Mobile Socket
Flush Socket
Features
Standard Materials
• Wall Socket: high impact resistance fiberglass reinforced
polyester
• Plug, mobile socket and flush socket: polyamide
Technical Data
Breaking Capacity
AC 1
ATEX/IECEx Certifications and Compliances
• Certification Type PCX, PCX/EN
• Gas: Zones 1 and 2
— Conforming to ATEX 94/9/CE: CE 0081
II 2 G
— ATEX/IEC Protection: Ex de IIC
— T-Rating: T6 for Ta  +40 °C (+104 °F) and T5 for Ta  +55 °C
(+131 °F)
— Ambient Temperature: -40 °C  Ta  +55 °C (-40 °F  Ta 
+131 °F)
— Impact Resistance (shock): IK10 (Polyester) and IK09
(Polyamide)
• Dust: Zones 21 and 22
— Conforming to ATEX 94/9/CE: CE 0081
II 2 D
— ATEX/IEC Protection: Ex tD A21
— Surface Temperature: T154 °F/T68 °C
— Ambient Temperature: -40 °C  Ta  +55 °C (-40 °F  Ta 
+131 °F)
— Impact Resistance (shock): IK10
• CE Declaration of Conformity: 50228, 5C214
• ATEX Certificate: LCIE 02 ATEX 6068, LCIE 02 ATEX 0001U
• IECEx Certificate: IECEx LCI 04.0014, IECEx LCI 04.0012
• Other Certifications: GOST
• Ingress Protection (solid and liquid): IP66
• Ex Standards: EN/IEC 60079-0; 60079-1; 60079-7; 61241-0;
61241-1
• Product Standards: EN/IEC 60309-1, 60309-2
• Other Standards: EN/IEC 60529 (IP), 62262 (IK)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
Plugs and Receptacles
• Plug and socket system is designed with a safe disconnect
mechanism to insure maximum hazardous location protection:
— The contact separation is in a flameproof chamber
— The automatic electrical disconnection of each phase is
contained in a second flameproof chamber
• Short circuit protection is 20 kA, while normal reference is 10
kA.
• Different voltages are color coded for easy identification.
• The sockets are keyed to accept only ATX plugs (other plugs
can not be inserted).
• ATX plugs can be used in non-hazardous sockets.
32 A – 500 V
11 kW – 220 V
12 kW – 240 V
AC 22
19 kW – 380 V
20.7 kW – 415 V
ICC
20 kA
NBR IEC Brazilian Certifications and Compliances
•
•
•
•
•
•
•
•
•
Certification Type PCX, PCX/EN
Gas: Zones 1 and 2
Dust: Zones 21 and 22
IEC Protection: Ex de IIC Gb; T6 for Ta  +40 °C (+104 °F) and
T5 for Ta  +55 °C (+131 °F)
Ambient Temperature: -40 °C  Ta  +55 °C (-40 °F  Ta  +131 °F)
Inmetro Certificate: BR230639, BR230598-U
Ingress Protection (solid and liquid): IP66
Ex Standards: NBR IEC 60079-0; 60079-1; 60079-7
Other Standards: NBR IEC 60529 (IP)
1303
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 32 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Wall Mounting Socket
• Three M25 threaded entries
(one on the top and two on the
bottom).
• Supplied with one M25 cable
gland – Ø 8 to Ø 18.5 mm (Ø
0.31 to Ø 0.73”) and two M25
blanking plugs.
• Terminal capacity 2 x 6 mm
(0.003 x 0.009 in ).
• Fitted with three linked earth
terminals.
Plug
Mobile Socket
Flush Socket
• One PG21 integrated cable
gland – Ø 8 to Ø 18.5 mm (Ø
0.31 to Ø 0.73”) for 3P+N+E
versions.
• Terminal capacity 6 mm
(0.009 in ).
• One PG21 integrated cable
gland – Ø 8 to Ø 18.5 mm (Ø
0.31 to Ø 0.73”) for 2P+E and
3P+E versions.
• One PG29 integrated cable
gland – Ø 18 to Ø 25 mm (Ø
0.70 to Ø 0.98”) for 3P+N+E
versions.
• Terminal capacity 2 x 6 mm
0.003 x 0.009 in )
• Terminal capacity 2 x 6 mm
0.003 x 0.009 in )
2
2
2
Plugs and Receptacles
2
2
2
2
2
Catalog Numbering Guide — IECEx Internationally Certified Plugs and Receptacles
PRE
3
32
IECEx Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
ATEX / IEC Certified
R
Amps:
32 - 32A
Pin Configuration:
3 - 2P+E
4 - 3P+E
5 - 3P+N+E
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
M - Mobile Socket
F - Flush Socket
P
Voltage:
Y - 100 - 130 Vac
50/60 Hz
B - 200 - 250 Vac
50/60 Hz
R - 380 - 415 Vac
50/60 Hz
N - 480 - 500 Vac
50/60 Hz
Catalog Numbering Guide — NBR IEC Brazilian Certified Plugs and Receptacles
N PRE
3
32
NBR IEC Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
NBR IEC Certified
R
Amps:
32 - 32A
Pin Configuration:
3 - 2P+E
4 - 3P+E
5 - 3P+N+E
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
M - Mobile Socket
F - Flush Socket
P
Voltage:
Y - 100 - 130 Vac
50/60 Hz
B - 200 - 250 Vac
50/60 Hz
R - 380 - 415 Vac
50/60 Hz
N - 480 - 500 Vac
50/60 Hz
LV: Low Voltage
1304
Yellow
Blue
Red
Black
100/130 Vac
200/250 Vac
380/415 Vac
480/500 Vac
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 32 Amp Low Voltage Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Catalog Number
Description
Pin Configuration
Volume dm3 (in3)
IECEx
NBR
1.9 (4.19)
7.0 (427.17)
PRE332RY
NPRE332RY
0.5 (1.10)
4.0 (244.09)
PRE332PY
NPRE332PY
0.8 (1.76)
3.2 (195.28)
PRE332MY
NPRE332MY
0.6 (1.32)
2.7 (164.76)
PRE332FY
NPRE332FY
1.9 (4.19)
7.0 (427.17)
PRE332RB
NPRE332RB
0.5 (1.10)
4.0 (244.09)
PRE332PB
NPRE332PB
0.8 (1.76)
3.2 (195.28)
PRE332MB
NPRE332MB
0.6 (1.32)
2.7 (164.76)
PRE332FB
NPRE332FB
1.9 (4.19)
7.0 (427.17)
PRE432RB
NPRE432RB
0.5 (1.10)
4.0 (244.09)
PRE432PB
NPRE432PB
0.8 (1.76)
3.2 (195.28)
PRE432MB
NPRE432MB
0.6 (1.32)
2.7 (164.76)
PRE432FB
NPRE432FB
L2
1.9 (4.19)
7.0 (427.17)
PRE532RB
NPRE532RB
L3
3P+N+E (1)
0.5 (1.10)
4.0 (244.09)
PRE532PB
NPRE532PB
1.0 (2.20)
4.0 (244.09)
PRE532MB
NPRE532MB
0.6 (1.32)
2.7 (164.76)
PRE532FB
NPRE532FB
2.0 (4.41)
7.0 (427.17)
PRE432RR
NPRE432RR
0.4 (0.88)
4.0 (244.09)
PRE432PR
NPRE432PR
0.8 (1.76)
3.2 (195.28)
PRE432MR
NPRE432MR
0.6 (1.32)
2.7 (164.76)
PRE432FR
NPRE432FR
2.0 (4.41)
7.0 (427.17)
PRE532RR
NPRE532RR
0.5 (1.10)
4.0 (244.09)
PRE532PR
NPRE532PR
100/130 Vac 50/60 Hz — Yellow
Wall Socket
4h
Plug
L/+
Mobile Socket
2P+E
Flush Socket
200/250 Vac 50/60 Hz — Blue
Wall Socket
L/+
Plug
6h
Mobile Socket
2P+E
Flush Socket
Wall Socket
L1
Plug
9h
Mobile Socket
L3
Flush Socket
L1
Wall Socket
key way
9h
Plug
N
Mobile Socket
Flush Socket
3P+E
L2
(1) 120/208 V - 144/250 Vac
50/60 Hz
380/415 Vac 50/60 Hz — Red
Wall Socket
L2
L1
Plug
6h
Mobile Socket
3P+E
Flush Socket
L2
L1
Wall Socket
Plug
N
L3
6h
L3
Mobile Socket
3P+N+E (2)
1.0 (2.20)
4.0 (244.09)
PRE532MR
NPRE532MR
Flush Socket
(2) 200/346 V - 240/415 Vac
50/60 Hz
0.6 (1.32)
2.7 (164.76)
PRE532FR
NPRE532FR
2.0 (4.41)
7.0 (427.17)
PRE432RN
NPRE432RN
0.4 (0.88)
4.0 (244.09)
PRE432PN
NPRE432PN
1.0 (2.20)
4.0 (244.09)
PRE432MN
NPRE432MN
0.6 (1.32)
2.7 (164.76)
PRE432FN
NPRE432FN
480/500 Vac 50/60 Hz — Black
Wall Socket
Plug
Mobile Socket
7h
3P+E
Flush Socket
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
1305
Plugs and Receptacles
Weight kg (lb)
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 32 Amp Low Voltage Plug and Socket Accessories and
Dimensions
Increased Safety
Accessories
Catalog Number
Description
IECEx
NBR
M5 earth stud with black neoprene sealing washer and green/yellow earth
conductor, length 300 mm (11.8”)
PREESTM25
NPREESTM25
M20 earth continuity adaptor with black neoprene sealing washer and
green/yellow earth conductor, length 300 mm (11.8”)
PREECAM25
NPREECAM25
Dimensions
32A — 2P+E — 3P+E — 3P+N+E Versions
Wall Mounting Sockets
Plugs
Plugs and Receptacles
97.0 mm
(3.82”)
Fix.
80.0 mm
(3.15”)
Ø
6.0 mm
(0.24”)
B
Fix. 105.0 mm
(4.13”)
Fix. 105.0 mm
(4.13”)
C
A
D
B
A C
Dimensions in Millimeters (Inches)
A
B
C
Dimensions in Millimeters (Inches)
D
A
B
C
2P+E
140.0 (5.51) 275.0 (10.83) 155.0 (6.10) 370.0 (14.67)
2P+T
80.0 (3.15)
170.0 (6.69)
67.0 (2.64)
3P+E
140.0 (5.51) 275.0 (10.83) 155.0 (6.10) 370.0 (14.67)
3P+T
80.0 (3.15)
170.0 (6.69)
67.0 (2.64)
3P+N+T
80.0 (3.15)
195.0 (7.68)
74.0 (2.91)
Mobile Sockets
Flush Sockets
Can be mounted on panel - 3.0 mm (0.12”) thickness maximum
3.0 mm
(0.12”)
maximum
110.0 mm
(4.33”)
260.0 mm (10.24”)
1306
56.0 mm
(2.20”)
Ø
4.2 mm
(0.17”)
Ø
56.0 mm
(2.20”)
74.0 mm
(2.91”)
56.0 mm
(2.20”)
60.0 mm
(2.36”)
74.0 mm
(2.91”)
60.0 mm
(2.36”)
150.0 mm
(5.91”)
103.0 mm
(4.06”)
210.0 mm
(8.27”)
Ø
4.2 mm
(0.17”)
Ø
56.0 mm
(2.20”)
210.0 mm (8.27”)
103.0 mm
(4.06”)
3 P + N + E 140.0 (5.51) 275.0 (10.83) 165.0 (6.50) 375.0 (14.76)
60.0 mm
(2.36”)
110.0 mm
(4.33”)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 63 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Applications
• Plugs and sockets are used with stationary or portable
electrically operated devices such as:
— Welding devices
— Lighting systems
— Conveyors
— Heaters
— Motor generator sets
— Air conditionings
— Compressors
— Pumps
• For use in corrosive atmospheres and installations in Zones 1,
and 2 and 21 and 22 of oil and gas industry, such as
— Refineries
— Chemical and petrochemical plants
— Pipelines
— Onshore and offshore drilling platforms
Plug
Wall Mounting Socket
Features
Plugs and Receptacles
• Positive polarization: only ATX plugs of same style, number of
poles and ampere rating may be used with these sockets.
• Interlocked 3-pole or 4-pole Ex de disconnecting on-load
switch, with auxiliary early break contact (capacity 2.5 mm2 /
0.004 in2 max).
• Plug is mechanically locked in socket when switch is ON.
• Switch operating handle can be padlocked in OFF position (max
4 padlocks ).
• Plug cannot be inserted or removed unless switch is in OFF
position.
Wall Mounting Socket Through-Wired
Standard Materials
• Socket: high impact resistance fiberglass reinforced polyester.
• Flap cover and plug: polyamide
ATEX/IECEx Certifications and Compliances
• Certification Type PC63X
• Gas: Zones 1 and 2
— Conforming to ATEX 94/9/CE: CE 0081
II 2 G
— ATEX/IEC Protection: Ex de IIC
— T-Rating: T6 for Ta  +40 °C (+104 °F) and T5 for +40 °C  Ta
 +55 °C (+104 °F  Ta  +131 °F)
• Dust: Zones 21 and 22
— Conforming to ATEX 94/9/CE: CE 0081
II 2 D
— ATEX/IEC Protection: Ex tD A21
— Surface Temperature: T90 °C (T194 °F)
• Ambient Temperature: -30 °C to +55 °C (-22 °F to +131 °F)
• CE Declaration of Conformity: 50208
• ATEX Certificate: LCIE 02 ATEX 6004
• IEC Certificate: LCIE Ex 99.004
• Other Certifications: GOST
• Ingress Protection (solid and liquid): IP66
• Impact Resistance (shock): IK10
• Ex Standards: EN/IEC 60079-0; 60079-1; 60079-7; 61241-0;
61241-1
• Product Standards: EN/IEC 60309-1, 60309-2
• Other Standards: EN/IEC 60529 (IP), 62262 (IK)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
NBR IEC Brazilian Certifications and Compliances
•
•
•
•
•
•
•
•
•
Certification Type PC63X
Gas: Zones 1 and 2
Dust: Zones 21 and 22
IEC Protection: Ex ed IIC Gb; T6 for Ta  +40 °C (+104 °F) and
T5 for +40 °C  Ta  +55 °C (+104 °F  Ta  +131 °F)
Ambient Temperature: -30 °C to +55 °C (-22 °F to +131 °F)
Inmetro Certificate: BR230595
Ingress Protection (solid and liquid): IP66
Ex Standards: NBR IEC 60079-0; 60079-1; 60079-7
Other Standards: NBR IEC 60529 (IP)
1307
Plugs and Receptacles
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 63 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Wall Mounting Socket
• Standard versions:
— Supplied with one M50 cable gland for
unarmored cable – Ø 28 to Ø 42 mm (Ø
1.10 to Ø 1.65”) and one M25 blanking
plug.
— Terminal capacity 1 x 35 mm2 (0.002 x
0.054 in2).
Plug
• Through-wired versions:
— Supplied with two M50 cable glands for
unarmored cable – Ø 28 to Ø 42 mm
(Ø 1.10 to Ø 1.65”) and one M25
blanking plug.
— Terminal capacity 2 x 35 mm2 (0.003 x
0.054 in2).
• One integrated cable entry for unarmored
flexible cable – Ø 17.5 to Ø 29 mm
(Ø 0.69 to Ø 1.14”) for 3P + E versions;
Ø 17.5 to Ø 32 mm (Ø 0.69 to Ø 1.26”) for
3P + N + E versions.
• Terminals capacity 16 mm2 (0.025 in2).
63 Amps
Main Contacts
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Rated Surge Voltage
Switching Capacity
AC 21 A / AC 22 A
AC 23 A
AC 3
690 Vac
690 Vac
63 Amp
6 KV
63 Amp
15 kW
22 kW
30 kW
18.5 kW
11 kW
18.5 kW
22 kW
15 KW
DC 21
DC 22
DC 23
Auxiliary Contacts
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Switching Capacity: AC 15
230 Volt to 690 Volt
230 Volt
400 Volt
500 Volt
690 Volt
230 Volt
400 Volt
500 Volt
690 Volt
–
–
–
400 Volt
400 Volt
10 Amp
6 Amp
4 Amp
230 Volt
400 Volt
Others
Termination (flexible/solid)
1308
35 mm2 (0.002 in2)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 63 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Catalog Numbering Guide — IECEx Internationally Certified Plugs and Receptacles
PRE
4
63
IECEx Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
ATEX / IEC Certified
R
Amps:
63 - 63A
Pin Configuration:
4 - 3P+E
5 - 3P+N+E
B
A
S
Cable Entry Size: 
3 - M32
4 - M40
5 - M50
6 - M63
Voltage:
B - 200 - 250 Vac
50/60 Hz
R - 380 - 415 Vac
50/60 Hz
N - 480 - 500 Vac
50/60 Hz
R1 - 440 - 460 Vac
60 Hz
N1 - 600 - 690 Vac
50/60 Hz
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
3
Cable Type:
A - Armored
U - Unarmored
Options:
S - 316L Stainless
Steel
T - Through-wired
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
Catalog Numbering Guide — NBR IEC Brazilian Certified Plugs and Receptacles
N PRE
4
63
Amps:
63 - 63A
Pin Configuration:
4 - 3P+E
5 - 3P+N+E
B
A
S
Cable Entry Size: 
3 - M32
4 - M40
5 - M50
6 - M63
Voltage:
B - 200 - 250 Vac
50/60 Hz
R - 380 - 415 Vac
50/60 Hz
N - 480 - 500 Vac
50/60 Hz
R1 - 440 - 460 Vac
60 Hz
N1 - 600 - 690 Vac
50/60 Hz
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
3
Plugs and Receptacles
NBR IEC Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
NBR IEC Certified
R
Cable Type:
A - Armored
U - Unarmored
Options:
S - 316L Stainless
Steel
T - Through-wired
LV: Low Voltage
Blue
Red
Black
Red 1
Black 1
200/250 Vac
380/415 Vac
480/500 Vac
440/460 Vac
600/690 Vac
 With one M5 plugged entry.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
1309
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 63 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
Standard Versions
Description
Pin Configuration
Weight kg (lb)
Volume dm3 (in3)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
8.0 (17.64)
26.0 (1586.62)
1.0 (2.20)
7.0 (427.17)
Catalog Number
IECEx
NBR
200/250 Vac 50/60 Hz — Blue
Wall Socket
Plug
3P+E
PRE463RBU5
NPRE463RBU5
PRE463PB
NPRE463PB
PRE463RRU5
NPRE463RRU5
PRE463PR
NPRE463PR
PRE563RRU5
NPRE563RRU5
PRE563PR
NPRE563PR
380/415 Vac 50/60 Hz — Red
Wall Socket
Plug
3P+E
Wall Socket
Plug
Plugs and Receptacles
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
3P+N+E (1)
(1) 200/346 V – 240/415 Vac 50/60 Hz
440/460 Vac 60 Hz — Red
Wall Socket
Plug
3P+E
Wall Socket
Plug
3P+N+E (2)
PRE463RR1U5 NPRE463RR1U5
PRE463PR1
NPRE463PR1
PRE563RR1U5 NPRE563RR1U5
PRE563PR1
NPRE563PR1
PRE463RNU5
NPRE463RNU5
PRE463PN
NPRE463PN
PRE563RNU5
NPRE563RNU5
PRE563PN
NPRE563PN
(2) 250/440 V – 265/460 Vac 60 Hz
480/500 Vac 50/60 Hz — Black
Wall Socket
Plug
3P+E
Wall Socket
Plug
3P+N+E (3)
(3) 277/480 V – 288/500 Vac 50/60 Hz
600/690 Vac 50/60 Hz — Black
Wall Socket
Plug
PRE463RN1U5 NPRE463RN1U5
PRE463PN1
NPRE463PN1
3P+E
Wall Socket
Plug
3P+N+E (4)
PRE563RN1U5 NPRE563RN1U5
PRE563PN1
NPRE563PN1
(4) 347/600 V – 400/690 Vac 50/60 Hz
1310
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 63 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Through-wired Versions
Description
Pin Configuration
Catalog Number
IECEx
NBR
Weight kg (lb)
Volume dm3 (in3)
16.0 (35.27)
110.0 (6712.61)
PRE463RRU5T NPRE463RRU5T
16.0 (35.27)
110.0 (6712.61)
PRE563RRU5T NPRE563RRU5T
380/415 Vac 50/60 Hz — Red
Wall Socket
3P+E
Wall Socket
3P+N+E (1)
(1) 200/346 V – 240/415 Vac 50/60 Hz
Dimensions
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
Standard Version
380 mm (14.96”)
420.0 mm (16.54”)
with cable gland
320.0 mm (12.60”)
187.0 mm
(7.36”)
Plugs and Receptacles
6.5 mm
(0.26”)
215.0 mm
(8.46”)
255.0 mm (10.04”)
188.5 mm (7.42”)
133.5 mm 102.0 mm
(4.67”)
(4.02”)
235.0 mm
(9.25”)
Through-Wired Version
7.0 mm (0.28”)
(4) Mtg Holes
235.0 mm (9.25”)
147.0 mm (5.79”)
2 Cable Entries
M8
Fix.
146.0 mm (5.75”)
Fix.
187.0 mm (7.36”)
M25 Blanking
Plug Fitted
16.73”/425.0 mm
8.46”/215.0 mm
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
380.0 mm (14.96”)
6.5 mm (0.26”0
(4) Mtg Holes
Fix. 320.0 mm (12.60”)
7.87”/200.0 mm
1311
Plugs and Receptacles
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 125 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Applications
• Plugs and sockets are used with stationary or portable
electrically operated devices such as:
— Welding devices
— Lighting systems
— Conveyors
— Heaters
— Motor generator sets
— Air conditioning
— Compressors
— Pumps
• For use in corrosive atmospheres and installations in Zones 1,
and 2 and 21 and 22 of oil and gas industry, such as
— Refineries
— Chemical and petrochemical plants
— Pipelines
— Onshore and offshore drilling platforms
Plug
Wall Mounting Socket
Features
• Positive polarization: only ATX plugs of same style, number of
poles and ampere rating may be used with these sockets.
• Interlocked 3-pole or 4-pole Ex de disconnecting on-load
switch, with auxiliary early break contact – capacity 2.5 mm2
(0.004 in2) maximum.
• Plug is mechanically locked in socket when switch is ON.
• Switch operating handle can be padlocked in OFF position (max
4 padlocks).
• Plug cannot be inserted or removed unless switch is in OFF
position.
Standard Materials
• Socket: 316L stainless steel
• Flap cover and plug: polyamide
ATEX/IECEx Certifications and Compliances
• Certification Type PC125X
• Gas: Zones 1 and 2
— Conforming to ATEX 94/9/CE: CE 0081
II 2 G
— ATEX/IEC Protection: Ex de IIC
— T-Rating: T6 for Ta  +40 °C (+104 °F) and 5 for  Ta 
55 °C (+131 °F)
• Dust: Zones 21 and 22
— Conforming to ATEX 94/9/CE: CE 0081
II 2 D
— ATEX/IEC Protection: Ex tD A21
— Surface Temperature: T90 °C (T194 °F)
• Ambient Temperature: -30 °C to +55 °C (-22 °F to +131 °F)
• CE Declaration of Conformity: 50218
• ATEX Certificate: LCIE 99 ATEX 6031
• IEC Certificate: LCIE Ex 99.017
• Other Cetifications: GOST
• Ingress Protection (solid and liquid): IP66
• Impact Resistance (shock): IK10
• Ex Standards: EN/IEC 60079-0; 60079-1; 60079-7; 61241-0;
61241-1
• Product Standards: EN/IEC 60309-1, 60309-2
• Other Standards: EN/IEC 60529 (IP), 62262 (IK)
1312
NBR IEC Brazilian Certifications and Compliances
•
•
•
•
•
•
•
•
•
Certification Type PC125X
Gas: Zones 1 and 2
Dust: Zones 21 and 22
IEC Protection: Ex de IIC Gb; T6 for -30 °C  Ta  +40 °C
(-22 °F  Ta  +104 °F) and T5 for +40 °C  Ta  +55 °C
(+104 °F  Ta  +131 °F)
Ambient Temperature: -40 °C to +55 °C (-40 °F to +131 °F)
Inmetro Certificate: BR230596
Ingress Protection (solid and liquid): IP66
Ex Standards: NBR IEC 60079-0; 60079-1; 60079-7
Other Standards: NBR IEC 60529 (IP)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 125 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Wall Mounting Socket
Plug
• One M63 cable gland for unarmored cable – Ø 36 to Ø 44 mm
(Ø 1.42 to Ø 1.73”) and one M25 blanking plug.
• Terminal capacity 120 mm2 (0.186in2).
• One integrated cable entry for unarmored flexible cable – Ø 30 to
Ø 48 mm (Ø 1.18 to Ø 1.89”).
• Terminals capacity 50 mm2 (0.078in2).
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
160 Amps
AC 23 A
AC 3
DC 21
DC 22
DC 23
Auxiliary Contacts
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Switching Capacity: AC 15
Others
Termination (flexible/solid)
Plugs and Receptacles
Main Contacts
Rated Insulation Voltage
Rated Operating Voltage
Rated Operating Current
Rated Surge Voltage
Switching Capacity
AC 21 A / AC 22 A
690 Vac
690 Vac
125 Amp
8 KV
125 Amp
400 Volt to 690 Volt
80 kW
110 kW
55 kW
400 Volt
500 Volt
690 Volt
90 kW
70 kW
400 Volt
500 Volt
125 Amp
220 Volt 
125 Amp
440 Volt 
125 Amp
220 Volt 
100 Amp
440 Volt 
125 Amp
220 Volt 
63 Amp
440 Volt 
230 Volt
230 Volt
10 Amp
6 Amp
230 Volt
120 mm2 (0.007 in2)
 2 contacts connected in series per pole.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
1313
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 125 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
Catalog Numbering Guide — IECEx Internationally Certified Plugs and Receptacles
PRE
4
Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
ATEX / IEC Certified
12
R
Amps:
12 - 125A
Pin Configuration:
4 - 3P+E
5 - 3P+N+E
R
A
T
Cable Entry Size: 
3 - M32
4 - M40
5 - M50
6 - M63
Voltage:
R - 380 - 415 Vac
50/60 Hz
N - 480 - 500 Vac
50/60 Hz
R1 - 440 - 460 Vac
60 Hz
N1 - 600 - 690 Vac
50/60 Hz
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
3
Cable Type:
A - Armored
U - Unarmored
Options:
T - Through-wired
Catalog Numbering Guide — NBR IEC Brazilian Certified Plugs and Receptacles
N PRE
Plugs and Receptacles
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
4
NBR IEC Series:
PRE - PRE Series
Zone 1, 2, 21 and 22
NBR IEC Certified
Pin Configuration:
4 - 3P+E
5 - 3P+N+E
12
R
Amps:
12 - 125A
R
A
Voltage:
R - 380 - 415 Vac
50/60 Hz
N - 480 - 500 Vac
50/60 Hz
R1 - 440 - 460 Vac
60 Hz
N1 - 600 - 690 Vac
50/60 Hz
Equipment:
P - Plug
R - Receptacle
(Wall Mounting)
3
T
Cable Entry Size: 
3 - M32
4 - M40
5 - M50
6 - M63
Cable Type:
A - Armored
U - Unarmored
Options:
T - Through-wired
LV: Low Voltage
Red
Black
Red 1
Black 1
380/415 Vac
480/500 Vac
440/460 Vac
600/690 Vac
 With one M25 plugged entry.
1314
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
PRE Series 125 Amp Plugs and Sockets
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
NBR IEC:
Zone 1 and 2 - 21 and 22
Ex de IIC Gb
Inmetro (Portaria no 179)
IP66
Description
Pin Configuration
IECEx
Catalog Number
Volume dm3 (in3)
NBR
16.0 (0.63)
70.0 (4271.66)
PRE412RRU6
NPRE412RRU6
1.1 (0.04)
13.0 (793.31)
PRE412PR
NPRE412PR
16.0 (0.63)
70.0 (4271.66)
PRE512RRU6
NPRE512RRU6
1.1 (0.04)
13.0 (793.31)
PRE512PR
NPRE512PR
16.0 (0.63)
70.0 (4271.66)
PRE412RR1U6
NPRE412RR1U6
1.1 (0.04)
13.0 (793.31)
PRE412PR1
NPRE412PR1
16.0 (0.63)
70.0 (4271.66)
PRE512RR1U6
NPRE512RR1U6
1.1 (0.04)
13.0 (793.31)
PRE512PR1
NPRE512PR1
16.0 (0.63)
70.0 (4271.66)
PRE412RNU6
NPRE412RNU6
1.1 (0.04)
13.0 (793.31)
PRE412PN
NPRE412PN
16.0 (0.63)
70.0 (4271.66)
PRE512RNU6
NPRE512RNU6
1.1 (0.04)
13.0 (793.31)
PRE512PN
NPRE512PN
16.0 (0.63)
70.0 (4271.66)
PRE412RN1U6
NPRE412RN1U6
1.1 (0.04)
13.0 (793.31)
PRE412PN1
NPRE412PN1
16.0 (0.63)
70.0 (4271.66)
PRE512RN1U6
NPRE512RN1U6
1.1 (0.04)
13.0 (793.31)
PRE512PN1
NPRE512PN1
380/415 Vac 50/60Hz — Red
Wall Socket
Plug
3P+E
Wall Socket
Plug
3P+N+E (1)
(1) 200/346 V – 240/415 Vac 50/60 Hz
440/460 Vac 60 Hz — Red
Wall Socket
Plug
3P+E
Wall Socket
Plug
3P+N+E (2)
(2) 250/440 V – 265/460 Vac 60 Hz
480/500 Vac 50/60 Hz— Black
Wall Socket
Plug
3P+E
Wall Socket
Plug
3P+N+E (3)
(3) 277/480 V – 288/500 Vac 50/60 Hz
600/690 Vac 50/60 Hz — Black
Wall Socket
Plug
3P+E
Wall Socket
Plug
3P+N+E (4)
(4) 347/600 V – 400/690 Vac 50/60 Hz
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015
1315
Plugs and Receptacles
Weight kg (lb)
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
Increased Safety
Increased Safety
Dimensions
Front
Side
Plug
Ø 131.0 mm
(5.16”)
848.0 mm (33.39”)
225.0 mm (8.86”)
660.0 mm (25.98”)
340.0 mm (13.39”)
407.0 mm
(16.02”)
262.0 mm
(10.31”)
Plugs and Receptacles
ATEX/IECEX/NBR IEC INCREASED SAFETY EX E ZONE 1 RATED PLUGS AND RECEPTACLES
PRE Series 125 Amp Plug and Socket Dimensions
1316
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© April 2015