Bulletin 749 Rev. B

Model DDX

Single Interlock Preaction Systems

2” (50 mm), 2½” (65 mm), 3” (80 mm),

76 mm, 4” (100 mm), 6” (150 mm),

165 mm & 8” (200mm)

Instructions for Installation,

Operation, Care, and Maintenance

Wet Pilot Line,

Dry Pilot Line, and

Electric Actuation Trims

• Electric Release Trim Available with 175 psi

(12,1 bar) or 300 psi (20,7 bar) Rated Solenoid

Valve

• Electric Release Trim and Wet Pilot Trim

Utilize 7 to 10 psi (0,5 to 0,7 bar) Pneumatic

Supervising Pressure

• Dry Pilot Trim Utilize 8 psi to 28 psi (0,6 to 1,9 bar) Pneumatic Supervising Pressure

• Externally Resettable Clapper

• One Main Drain

Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523

General

Single Interlock Preaction Systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler system piping.

At the heart of Reliable’s Single Interlock Preaction Systems is the Model DDX Deluge Valve. This deluge valve is a hydraulically operated, straight-through-design, differential latching clapper-type (see Fig. 1). System maintenance is simplified since the deluge valve can be reset externally without removing its cover plate. This feature provides a significant system-restoration time advantage. The Model DDX

Deluge Valve has an intermediate chamber and thereby does not require an in-line air check valve. Also, for ease of installation, the deluge valve only requires a single drain connection.

The trim sets for the single interlock preaction systems

(see Figs. 3, 4, 5, 6, 7 and 8) provide all of the necessary equipment for connections to the Model DDX Deluge Valve’s pushrod chamber inlet and outlet ports, a 1¼” (30 mm) main drain on 2” (50 mm), 2½” (65 mm), 76 mm and 3” (80 mm) valve sizes or a 2” (50 mm) main drain on 4” (100 mm), 165 mm, 6” (150 mm) and 8” (200 mm) valve sizes, alarm devices, air supply, and required pressure gauges. The trim sets are available in individual (loose) parts, in time-saving, segmented assembled kit forms or fully assembled to the

Model DDX Deluge Valve (with or without a control valve).

The major benefits of a single interlock preaction system, when compared with a wet pipe or deluge system are as follows:

• A fire alarm sounds prior to the operation of a sprinkler head, which may enable extinguishing the fire by handheld means before the actual operation of any sprinklers and subsequent water damage.

• A trouble annunciator signals whenever the integrity of the piping or sprinklers is accidentally or intentionally disturbed; however, no water flow or water damage will occur at that time.

• Speedy detection and an early fire alarm are provided by fire detectors, without the delay associated with water delivery time in the event of a fire. Note that with a wet pipe system, the fire alarm is delayed until after water has begun flowing from an operated sprinkler head.

Sprinkler piping in Wet Pilot and Electric Actuation Single

Interlock Preaction Systems can effectively be supervised by means of a Reliable Model B-SI Air Compressor Panel or

Model C-SI Air Compressor Panel. Loss of 7 psi (0,5 bar) supervising pneumatic pressure, due to a damaged sprinkler or sprinkler pipe will not cause water to flow through the

Model DDX Deluge Valve and into the system piping. A significant loss of pneumatic pressure will activate a troubleannunciating device when the system pressure falls below approximately 4 psi (0,3 bar). Note: Wherever the word “air” is used in this bulletin as a reference to the pneumatic pressure source it shall also mean “air or nitrogen.”

Wet Pilot Line Single Interlock Preaction Systems use a pilot line consisting of a line of closed sprinklers or pilot line detectors (Reliable’s Model F1-FTR), which are located in the area to be protected. These sprinklers/detectors are more sensitive (lower activation temperature) than the sprinkler heads installed in the fire sprinkler system. The wet pi-

2.

lot line is directly installed to the Model DDX Deluge Valve’s pushrod chamber. Wet pilot line sprinklers are detection devices and do not provide any water to aid in the firefighting capability of the fire sprinkler system.

To fully operate a Wet Pilot Line Single Interlock Preaction

System, the heat from a fire must fuse a wet pilot line sprinkler/detector thereby releasing the water pressure from the

Deluge Valve’s pushrod chamber. As this water pressure is lost in this chamber, the main water supply will open the Deluge Valve’s clapper, thereby flowing water into the fire sprinkler piping. Water flowing into the system will flow through the intermediate chamber of the deluge valve to a mechanical sprinkler alarm (optional) and/or will simultaneously produce water pressure that causes the transfer of contacts in the (optional) alarm pressure switch mounted in the trim. If provided, the alarm pressure switch can electrically initiate the shut-down or start up of equipment, such as computer,

HVAC, or other secondary alarm devices (Note: the wiring contacts for the alarm pressure switch are the “Common” and “A” contacts). The flow of water into the sprinkler system piping converts the dry system into a wet system. In the event that the fire subsequently produces enough heat to operate a fire sprinkler head, water will flow from that sprinkler, controlling or suppressing the fire.

The fire sprinkler system piping may be required to be supervised (see NFPA 13) with air pressure. Loss of this supervisory air due to a damaged sprinkler or the sprinkler piping will not cause the Model DDX Deluge Valve to open. The supervisory air supply for the fire sprinkler piping may effectively be supervised by Reliable’s Model B-SI Air

Compressor Panel or Reliable’s Model C-SI Air Compressor

Panel. Other options include the use of the Reliable NS-PaK or Nitrogen Regulator with an approved nitrogen source, the

Reliable Model A-2 Pressure Maintenance Device with a tank-mounted air compressor, or a tank-less air compressor controlled by a pressure switch or the Reliable Model B-1 Air

Maintenance Device. (See Reliable Bulletin 254).

In Electric Actuation Single Interlock Preaction Sys-

tems, when one electrical detector senses the presence of fire, the electrical releasing control panel activates fire alarm devices and operates the normally-closed solenoid valve

(175 psi (12,1 bar) or 300 psi (20,7 bar) Rated) to the open position (Note: Arranging detectors in a cross-zoned pattern will require operation of two detectors before the solenoid valve can open). The solenoid valve, when closed, retains sufficient water pressure in the pushrod chamber of the

Model DDX Deluge Valve to maintain it closed. Energizing the solenoid valve relieves the water pressure, thus opening the Deluge Valve and allowing water to flow into the sprinkler system.

To fully operate a cross-zoned single interlock system, two electrical detectors must activate and a sprinkler head must open. During the early stages of a fire, smoke or heat activates the first detector, which causes the control panel to produce a local alarm and an alarm at the main fire alarm panel. Electrical relays inside the releasing control panel can be used to shut down air moving equipment or activate security doors and other electrical devices when the panel goes into the first alarm condition. Subsequent activation of

a second, nearby or adjacent, detector will cause the panel to energize the solenoid valve open and release water into the sprinkler system piping. Water flowing into the sprinkler system piping will simultaneously produce water pressure that causes the transfer of contacts in the pressure switch mounted in the Reliable Single Interlock Preaction System’s riser assembly. This pressure switch can electrically initiate the shut down or startup of equipment, such as computers or other second alarm devices. The flow of water into the sprinkler system piping effectively converts the dry system into a wet pipe system. In the event that the fire subsequently produces sufficient heat to operate a sprinkler head, water will flow from that sprinkler, controlling or suppressing the fire.

Dry Pilot Single Interlock Preaction Systems are used in areas that may be subjected to freezing conditions. They can also be utilized to obtain installed sprinkler heights and pipe lengths greater than the allowed for wet pilot systems.

A dry pilot line installation consists of an air-pressurized line of closed sprinklers or pilot line detectors (Reliable’s Model F1-FTR), which are located in the area to be protected.

NFPA 72 or the Authority Having Jurisdiction (AHJ) should be consulted for spacing and elevation requirements for the installation of dry pilot sprinklers/detectors.

In the system’s trim, the dry pilot line is connected to a

Model LP Dry Pilot Line Actuator. This actuator functions very much like a miniature dry pipe valve. It requires only 8 to 28 psi (0,6 to 1,9 bar) of air pressure (depending on the water supply pressure) to maintain the Model DDX Deluge

Valve in a closed position. In areas where moisture-laden air could cause a freezing condition, or other problems in the dry pilot line, the use of a dry, compressed gas such as nitrogen is suggested. Approved gas handling regulators (see

Reliable Bulletin 254) and connections are recommended.

When one of the dry pilot line sprinklers/ detectors actuates, the air pressure in the line is reduced, thus opening the Model LP Dry Pilot Line Actuator, which in turn releases the DDX

Deluge Valve and fills the fire sprinkler piping with water.

However, water does not flow from the fire sprinkler system until one of its sprinklers fuses from the heat of the fire.

The fire sprinkler system piping may be required to be supervised (see NFPA 13) with air pressure. Loss of this supervisory air due to a damaged sprinkler or the sprinkler piping will not cause the Model DDX Deluge Valve to open. This is accomplished by the ½” check valve which is located in the valve’s trim. The check valve prevents air pressure (from the dry pilot line) from escaping out of the Model LP Dry Pilot Line

Actuator. A low air pressure switch (System Sensor EPS40-2 or EPSA40-2) is also provided in the trim. The contacts of this switch will close on the loss of air in the sprinkler piping, thereby providing a low air alarm to aid in insuring the integrity of the sprinkler system piping. The pressure switch’s low air alarm should be wired to a supervisory alarm bell or the building’s alarm system (Note: The wiring for closing of contacts on the loss of pressure is made on the “COM” and

“B” terminals of switch 2.)

Damage to a dry pilot line sprinkler/detector or the dry pilot line piping that causes a significant loss of pressure will cause the Model DDX Deluge Valve to open, flowing water

3.

into the fire sprinkler system piping. The supervisory air supply for both the dry pilot line and the fire sprinkler piping can effectively be maintained by means of pressure-switch-operated, tank-mounted air compressor and a Reliable Model

A-2 Pressure Maintenance Device (see Reliable Bulletins

254). The compressor’s tank provides a reserve supply of air, whereas the Model A-2 Pressure Maintenance Device consistently regulates the air pressure of both the dry pilot line and the fire sprinkler piping.

The dry pilot line sprinklers/detectors must be more sensitive to the heat from a fire than the sprinklers in the fire sprinkler system. The Model F1-FTR (Fixed Temperature Release) is specifically designed for use in dry pilot line operated sprinkler systems. Dry pilot line sprinklers are detection devices and do not provide any water to aid in the firefighting capability of the fire sprinkler system.

To fully operate a dry pilot line preaction system, the heat from a fire must fuse a dry pilot line sprinkler/detector thereby releasing the air pressure from the Model LP Dry Pilot Line

Actuator. The water pressure is then able to overcome the pressure differential of the actuator, allowing water to flow from the Model DDX Deluge Valve’s push rod chamber. As this water pressure is lost in the push rod chamber, the supply pressure will then force the valve’s clapper open, flowing water into the fire sprinkler system piping. Water flowing into the system will flow through the intermediate chamber of the deluge valve to a mechanical sprinkler alarm (optional) and/ or will simultaneously produce water pressure that causes the transfer of contacts in the (optional) alarm pressure switch mounted in the trim. If provided, the alarm pressure switch can electrically initiate the shut-down or start up of equipment, such as computer, HVAC, or other secondary alarm devices (Note: the wiring contacts for the alarm pressure switch are the “Common” and “A” contacts). The flow of water into the sprinkler system piping converts the dry system into a wet system. In the event that the fire subsequently produces enough heat to operate a fire sprinkler head, water will flow from that sprinkler, controlling or suppressing the fire.

Listings & Approvals:

(Only when used with Reliable’s Trim Sets.)

1. Reliable’s 2” (50 mm), 2½” (65 mm), 76 mm, 3” (80 mm),

4” (100 mm), 165 mm, 6” (150 mm) and 8” (200 mm) Electric Actuation Single Interlock Preaction Systems, Wet Pilot

Line Single Interlock Preaction Systems and Dry Pilot Line

Single Interlock Preaction Systems are Underwriters Laboratories, Inc. Listed and UL certified for Canada (cULus) in the Special System Water Control Valve-Deluge Type

(VLFT) category.

2. Reliable’s 2” (50 mm), 2½” (65 mm), 76 mm, 3” (80 mm), 4”

(100 mm), 165 mm, 6” (150 mm) and 8” (200 mm) Electric

Actuation Single Interlock Preaction Systems are certified by Factory Mutual Approvals (FM). Factory Mutual does not approve the use of smoke detectors or cross zoned detectors in preaction systems.

4.

System Operation

When set correctly for service, the Model DDX Deluge

Valve is hydraulically established to withhold the supply water from the sprinkler system piping. The Reliable Model DDX

Deluge Valve is shown in both closed and open positions in

Fig. 1. In the closed position, the supply pressure acts on the underside of the clapper and also on the push rod through the push rod chamber’s inlet restriction. The resultant force due to the supply pressure acting on the push rod is multiplied by the mechanical advantage of the lever and is more than sufficient to hold the clapper closed against normal supply pressure surges.

To fully operate (deliver water) a Wet Pilot Line Single Interlock Preaction System, two independent events must coexist before water flow will occur. A wet pilot line sprinkler/detector must fuse along with a fire sprinkler head. Operation of either one of these heads will cause an alarm to annunciate, but will not cause water discharge from the fire sprinkler system piping.

When a fire is detected, the opened wet pilot line sprinkler/ detector vents the push rod chamber to atmosphere through the chamber’s outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented, the push rod chamber pressure falls instantaneously. When the push rod chamber pressure approaches approximately onethird of the supply pressure, the upward force of the supply pressure acting beneath the clapper overcomes the leverapplied force thereby opening the clapper.

To fully operate an Electric Actuation Single Interlock Preaction System, two independent events must coexist before water flow will occur. One electrical detector (two detectors in a cross-zoned system) must activate and a sprinkler head must open. Operation of either one of these items will only cause an alarm to annunciate, but will not cause water to discharge from the sprinkler system piping.

When a fire is detected, the energized solenoid valve vents the push rod chamber to atmosphere through the chamber’s outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented, the pushrod chamber pressure falls instantaneously. When the pushrod chamber pressure approaches approximately one-third of the supply pressure, the upward force of the supply pressure acting beneath the clapper over comes the lever-applied force thereby opening the clapper.

To fully operate (deliver water) a Dry Pilot Line Single Interlock Preaction System, two independent events must coexist before water flow will occur. A dry pilot line sprinkler/detector must fuse along with a fire sprinkler head. Operation of either one of these heads will cause an alarm to annunciate, but will not cause water discharge from the fire sprinkler system piping.

When a fire is detected, the Model LP Dry Pilot Line Actuator vents the push rod chamber to atmosphere through the chamber’s outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented, the push rod chamber pressure falls instantaneously.

When the push rod chamber pressure approaches approximately one-third of the supply pressure, the upward force of the supply pressure acting beneath the clapper overcomes the lever-applied force thereby opening the clapper.

5.

In all Reliable Single Interlock Preaction Systems, once the clapper has opened, the lever acts as a latch, preventing the clapper from returning to the closed position. Water from the supply flows through the Deluge Valve into the system piping. Water also flows through the Deluge Valve alarm outlet to the alarm devices.

After system shutdown, resetting the Model DDX Deluge

Valve is quite simple. Doing so only requires pushing in and turning the reset knob at the rear of the valve (see Fig 1).

The external reset feature of the Model DDX Deluge Valve provides a means for simple, economical system testing, which is one essential facet of a good maintenance program.

The external reset feature does not, however, eliminate another important facet of good maintenance, namely, periodic cleaning and inspection of the internal valve parts.

In the event that water builds up inside the valve due to condensate from the air supply system or water left inside from valve system testing, a drain is available for venting. After closing the main supply valve, a small valve over the drain cup can be opened slightly until the water inside the valve body and the main pipe column has drained. See the section titled “Draining Excess/Condensate Water From System” in this bulletin for the detailed procedure.

The Model B Manual Emergency Station (see Fig. 12) is also included in all Reliable Single Interlock Preaction System trim sets. It consists of an aluminum nameplate mechanically attached to a ball valve. The valve handle in its OFF position is guarded against accidental turning to the ON position (and system discharge) by a nylon cable tie provided with each trim kit. The cable tie is inserted, as shown in Fig. 12, after the system has been restored for operation. The nylon cable tie is designed to allow, in case of an emergency, forceful turning of the valve handle to the ON position. As an alternative to the Model B Hydraulic Manual Emergency Station, the Model

A Hydraulic Manual Emergency Pull Box (see Reliable Bulletin 506) is also available and can be provided as an option.

Whenever ambient temperature conditions are high, the water temperature in the Model DDX Deluge Valve’s pushrod chamber could possibly increase, thereby increasing the pressure in the chamber to values exceeding the rated pressure of the system. In an indoor installation where standard room temperatures are exceeded, a pressure relief kit may be needed. Pressure relief kit, P/N 6503050001, can be installed into the pushrod chamber’s releasing line to limit the pressure to 250 psi (17,2 bar).

Reliable Model DDX Deluge Valve with associated Single

Interlock Preaction Trims sizes 2” (50 mm), 2½” (65 mm), 76 mm, 3” (80 mm), 4” (100 mm), 165 mm, 6” (150 mm) and 8”

(200 mm) are rated for use at a minimum water supply pressure of 20 psi (1,4 bar) and a maximum water supply pressure of 250 psi (17,2 bar) for 2” (50mm), 2½” (65mm), 76mm,

3” (80mm) and 8” (200mm) valve sizes and 300 psi (20,7 bar) for 4” (100mm), 165mm and 6” (150mm) valve sizes.

Water supplied to the inlet of the valve and to the push rod chamber must be maintained between 40˚F (4˚C) and 140˚F

(60˚C).

2

5

0

P

SI

SU

P

PL

Y

P

R

E

S

S

U

R

E

2

2

5

P

SI

2

0

0

P

S

I

1

7

5

P

S

I

1

5

0

P

S

I

1

2

5

P

I

S

10

0

P

S

I

0

8

P

S

I

0

6

S

P

I

0

4

S

P

I

0

2

S

P

I

0

4

S

P

I

0

8

P

S

I

10

0

P

S

I

2

5

0

P

SI

P

SI

2

2

5

P

S

I

2

0

0

1

7

5

P

S

I

I

1

5

0

PS

1

2

5

P

I

S

0

6

S

P

I

MAXIMUM PILOT LINE HEIGHT (ft)

6.

7.

Small DDX Wet Pilot Line SI Trim (Refer to Fig. 3)

Item

No.

Part No.

Galvanized Black Pipe

Description QTY.

1

6103022000 6103022000

6103022500 6103022500

Valve Assembly, 2" (50mm)

- For 2" Assembly Only

Valve Assembly, 2½" (65mm)

- For 2½" Assembly Only

1

Item

No.

Part No.

Galvanized Black Pipe

23 95306270

24 98174404

25 98174401

26 98174402

Description

95306270 Drain Hose Clip

98164402 Elbow, ¼"

98164401 Elbow, ½"

98164400 Elbow, ¾"

6103027600 6103027600

6103030000 6103030000

6990003549 6990003549

Valve Assembly, 76mm

- For 76mm Assembly Only

Valve Assembly, 3" (80mm)

- For 3" Assembly Only

Butterfly Valve, 2"

- For 2" Assembly Only

27 98174403

28 98174414

29 96920912

30 98840172

31 98840171

98164404 Elbow, 1"

98164407 Elbow, 1¼"

96920912 Flex Line, ½"

98840172 Globe Valve, ¼"

98840171 Globe Valve, ½"

2 6215051000 6215051000

6215051200 6215051200

Butterfly Valve, 2½"

- For 2½" Assembly Only

Butterfly Valve, 3"

- For 3" Assembly Only

1

32 98543226

33 98543243

34 98543223

98523213 Nipple ¼" x 1½"

98526522 Nipple ¼" x 4"

98523210 Nipple ½" x 1½"

7G05080800 7G05080800

Rigid Coupling, 2"

- For 2" Assembly Only

35 98543209

36 98543230

98523209 Nipple ½" x 2"

98523230 Nipple ½" x 3"

3 7G05101000 7G05101000

7G05121200 7G05121200

91004002 91004002

Rigid Coupling, 2½"

- For 2½" Assembly Only

Rigid Coupling, 3"

- For 3" Assembly Only

Outlet Spool, 2"

- For 2" Assembly Only

2 37 98543228

38 98543212

39 98543232

40 98543231

41 98543263

98523234 Nipple ½" x 4½"

98523221 Nipple ½" x Close

98523242 Nipple ¾" x 2"

98523240 Nipple ¾" x 3"

98523261 Nipple 1" x 3"

4 91004001

91004003

91004001

Outlet Spool, 2½"

- For 2½" Assembly Only

1 42 98543213

43 98543239

44 98543250

98523222 Nipple 1" x Close

98523256 Nipple 1¼" x 3"

98523264 Nipple 1¼" x 4"

5

6

7

8

78653000

78653004

78653100

99080002

9 98840101

10 98840106

91004003

78653000

Outlet Spool, 3"

- For 3" Assembly Only

Manual Emergency Station

Assembly

78653004

Valve Caution Station

Assembly

78653100 Ball Drip Valve, ½"

99080002 Adhesive Pad

98840101 Angle Valve, ¼"

98840106 Angle Valve, 1¼"

1

1

1

1

1

1

45 98543285

46 98750003

47 96686756

48 98048025

49 98048022

50 98048015

51 89141112

98523274 Nipple 1¼" x Close

98750013 Pipe Cross, ½"

96686756 PVC Tubing, 3 /

8

" ID x 6 ft.

98048011 Reducer Bushing, ¾" x ¼"

98048012 Reducer Bushing, ¾" x ½"

98048015

Reducer Bushing,

2" Spigot x 1" NPTF, PVC

89141112 Retaining Tie

11 98840117

12 98840188

13 98840181

14 98840145

98840117

98840188

98840181

98840145

Ball Valve,

¼" NPTF x ¼" NPTM

Check Valve,

¼" NPTM x ¼" NPTF

Check Valve,

Horizontal Swing, ½" NPT

Check Valve, Horizontal

Swing, 1" NPT

1

1

1

1

52 98614403

53 98604406

54 98614401

55 98727607

56 98174400

57 98761651

58 98761649

98604403 Square Head Plug, ¼"

98604402 Square Head Plug, ½"

98604401 Square Head Plug, ¾"

98727607 Strainer, ¼"

98164409 Street Elbow, ½"

98761603 Tee, ½"

98761604 Tee, ½" x ¼" x ½"

15 98840147

16 92056702

98840147

Check Valve,

Inline Poppet, ¼"

1 59 96606607

60 96606601

61 96606612

98761605 Tee, ½" x ½" x ¼"

98766521 Tee, ¾"

98761614 Tee, ¾" x ½" x ½"

17 92056703

18 92056810

19 92056705

20 96686722

21 94616917

22 98050004

92056702

92056703

92056810

3

Compression Connector,

/

8

" ID Tube x ¼" NPT

Compression Connector,

Elbow 3 /

8

" ID Tube x ¼" NPT

3

Connector,

/

8

" ID Tube x ½" NPT

1

1

1

92056705

3

Connector, Elbow,

/

8

" ID Tube x ¼" NPT

1

96686722 Copper Tubing, 3 /

8

" OD x 2 ft.

1

94616917 Single Interlock Nameplate

98050004 Drain Cup, PVC

1

1

62 96606603

63 98815200

64 98815204

65 98840160

66 98248000

67 98248001

68 95306255

98761621 Tee, 1¼" x 1¼" x 1"

98805200 Union, ½"

98845204 Union, ½", O-ring Seal

98840160 Valve, 3-way, ¼"

98248000

98248001

Air Pressure Gauge

(0-80 psi)

Water Pressure Gauge

(0-300 psi)

95306255 Hose Clamp

QTY.

1

1

1

2

1

1

9

3

2

1

2

1

2

2

1

1

1

1

1

1

1

1

1

1

2

1

4

1

1

2

4

1

6

4

2

1

1

1

1

1

1

1

1

1

2

2

8.

9.

Large DDX Wet Pilot Line SI Trim (Refer to Fig. 4)

Item

No.

1

Part No.

Galvanized Black Pipe

6103060024 6103060024

6103040026 6103040026

Description

Valve Assembly, 4" (100mm)

- For 4" Assembly Only

Valve Assembly, 6" (150mm)

- For 6" Assembly Only

QTY.

1

Item

No.

Part No.

Galvanized Black Pipe

23 98174404

24 98174402

25 98174403

26 98174405 98164405 Elbow, 2"

Description

98164402 Elbow, ¼"

98164400 Elbow, ¾"

98164404 Elbow, 1"

6103060028 6103060028

6103080001 6103080001

6215051600 6215051600

Valve Assembly, 165mm -

For 165mm Assembly Only

Valve Assembly, 8" (200mm)

- For 8" Assembly Only

Butterfly Valve, 4"

- For 4" Assembly Only

27 96920912

28 98840172

29 98840171

30 98543226

31 98543225

96920912 Flex Line, ½"

98840172 Globe Valve, ¼"

98840171 Globe Valve, ½"

98523213 Nipple ¼" x 1½"

98573220 Nipple ¼" x 2½"

2 6215052400 6215052400

6215053200 6215053200

Butterfly Valve, 6"

- For 6" Assembly Only

Butterfly Valve, 8"

- For 8" Assembly Only

1

32 98543220

33 98543217

34 98543223

98523219 Nipple ¼" x 3"

98523217 Nipple ¼" x 6"

98523210 Nipple ½" x 1½"

7G05161600 7G05161600

Rigid Coupling, 4"

- For 4" Assembly Only

35 98543209

36 98543230

98523209 Nipple ½" x 2"

98523230 Nipple ½" x 3"

3 7G05242400 7G05242400

7G05323200 7G05323200

91004004 91004004

Rigid Coupling, 6"

- For 6" Assembly Only

Rigid Coupling, 8"

- For 8" Assembly Only

Outlet Spool, 4"

- For 4" Assembly Only

2 37 98543216

38 98543237

39 98543234

40 98543279

41 98543222

98523216 Nipple ½" x 3½"

98523250 Nipple ½" x 8"

98523247 Nipple ¾" x 3½"

98523241 Nipple ¾" x Close

98523224 Nipple 1" x 3½"

4 91004006

91004008

91004006

Outlet Spool, 6"

- For 6" Assembly Only

1 42 98543266

43 98543213

44 98543262

98523228 Nipple 1" x 6"

98523222 Nipple 1" x Close

98523262 Nipple 2" x 3½"

5

6

7

8

9

78653000

78653004

78653100

99080002

98840100

10 98840117

11 98840188

91004008

78653000

Outlet Spool, 8"

- For 8" Assembly Only

Manual Emergency Station

Assembly

78653004

Valve Caution Station

Assembly

78653100 Ball Drip Valve, ½"

99080002 Adhesive Pad

98840100 Angle Valve, 2"

98840117

98840188

Ball Valve,

¼" NPTF x ¼" NPTM

Check Valve,

¼" NPTM x ¼" NPTF

1

1

1

1

1

1

1

45 98543238

46 98750003

47 96686756

48 98048025

49 98048022

50 98048015

51 89141112

52 98614403

53 98604406

98523254 Nipple 2" x Close

98750013 Pipe Cross, ½"

96686756 PVC Tubing, 3 /

8

" ID x 6 ft.

98048011 Reducer Bushing, ¾" x ¼"

98048012 Reducer Bushing, ¾" x ½"

98048015

Reducer Bushing,

2" Spigot x 1" NPTF, PVC

89141112 Retaining Tie

98604403 Square Head Plug, ¼"

98604402 Square Head Plug, ½"

12 98840181

13 98840145

14 98840147

15 92056702

16 92056703

17 92056810

18 92056705

19 96686722

20 94616917

21 98050004

22 95306270

98840181

Check Valve,

Horizontal Swing, ½" NPT

1

98840145

98840147

92056702

92056703

92056810

92056705

Check Valve,

Horizontal Swing, 1" NPT

Check Valve,

Inline Poppet, ¼"

3

Compression Connector,

/

8

" ID Tube x ¼" NPT

Compression Connector,

Elbow 3 /

8

" ID Tube x ¼" NPT

3

Connector,

/

8

" ID Tube x ½" NPT

Connector, Elbow,

3 /

8

" ID Tube x ¼" NPT

1

1

1

1

1

1

96686722 Copper Tubing, 3 /

8

" OD x 2 ft.

1

94616917 Single Interlock Nameplate

98050004 Drain Cup, PVC

95306270 Drain Hose Clip 1

1

1

54 98614401

55 98727607

56 98761651

57 98761649

58 96606607

59 96606601

60 96606612

61 96606627

62 98815200

63 98815204

64 98840160

65 98248000

66 98248001

67 95306255

98604401 Square Head Plug, ¾"

98727607 Strainer, ¼"

98761603 Tee, ½"

98761604 Tee, ½" x ¼" x ½"

98761605 Tee, ½" x ½" x ¼"

98766521 Tee, ¾"

98761614 Tee, ¾" x ½" x ½"

98761618 Tee, 2" x 2" x 1"

98805200 Union, ½"

98845204 Union, ½", O-ring Seal

98840160 Valve, 3-way, ¼"

98248000

Air Pressure Gauge

(0-80 psi)

98248001

Water Pressure Gauge

(0-300 psi)

95306255 Hose Clamp

QTY.

1

1

1

1

2

1

9

4

2

2

1

3

1

1

1

1

1

1

2

1

1

1

1

2

1

1

1

2

1

1

2

10

3

1

1

1

1

1

2

1

1

1

1

2

2

10.

11.

Small DDX Electric Actuation SI Trim (Refer to Fig. 5)

Item

No.

1

2

Part No.

Galvanized Black Pipe

6103022000 6103022000

6103022500 6103022500

6103027600 6103027600

6103030000 6103030000

6990003549 6990003549

6215051000 6215051000

Description

Valve Assembly, 2" (50mm)

- For 2" Assembly Only

Valve Assembly, 2½" (65mm)

- For 2½" Assembly Only

Valve Assembly, 76mm

- For 76mm Assembly Only

Valve Assembly, 3" (80mm)

- For 3" Assembly Only

Butterfly Valve, 2"

- For 2" Assembly Only

Butterfly Valve, 2½"

- For 2½" Assembly Only

QTY.

1

1

Item

No.

Part No.

Galvanized Black Pipe

23 94616917

24 98050004

Description

94616917 Single Interlock Nameplate

98050004 Drain Cup, PVC

25 95306270

26 98174404

95306270 Drain Hose Clip

98164402 Elbow, ¼"

27 98174401

28 98174402

29 98174403

30 98174414

31 96920912

32 98840172

98164401 Elbow, ½"

98164400 Elbow, ¾"

98164404 Elbow, 1"

98164407 Elbow, 1¼"

96920912 Flex Line, ½"

98840172 Globe Valve, ¼"

3

6215051200 6215051200

7G05080800 7G05080800

7G05101000 7G05101000

7G05121200 7G05121200

Butterfly Valve, 3"

- For 3" Assembly Only

Rigid Coupling, 2"

- For 2" Assembly Only

Rigid Coupling, 2½"

- For 2½" Assembly Only

Rigid Coupling, 3"

- For 3" Assembly Only

2

33 98840171

34 98543226

35 98543243

36 98543223

37 98543209

38 98543230

39 98543228

98840171 Globe Valve, ½"

98523213 Nipple ¼" x 1½"

98526522 Nipple ¼" x 4"

98523210 Nipple ½" x 1½"

98523209 Nipple ½" x 2"

98523230 Nipple ½" x 3"

98523234 Nipple ½" x 4½"

4

91004002

91004001

91004003

91004002

91004001

91004003

Outlet Spool, 2"

- For 2" Assembly Only

Outlet Spool, 2½"

- For 2½" Assembly Only

Outlet Spool, 3"

- For 3" Assembly Only

1

40 98543212

41 98543232

42 98543231

43 98543263

44 98543213

45 98543239

98523221 Nipple ½" x Close

98523242 Nipple ¾" x 2"

98523240 Nipple ¾" x 3"

98523261 Nipple 1" x 3"

98523222 Nipple 1" x Close

98523256 Nipple 1¼" x 3"

5

6

7

6871020000 6871020000 Solenoid Valve, 175 psi Rated

6871020020 6871020020 Solenoid Valve, 300 psi Rated

78653000

78653004

78653000

78653004

Manual Emergency Station

Assembly

Valve Caution Station

Assembly

8

9

78653100

99080002

10 98840101

11 98840106

12 98840117

13 98840188

78653100 Ball Drip Valve, ½"

99080002 Adhesive Pad

98840101 Angle Valve, ¼"

98840106 Angle Valve, 1¼"

98840117

Ball Valve,

¼" NPTF x ¼" NPTM

98840188

1

1

1

1

1

1

1

1

1

46 98543250

47 98543285

48 98750003

49 96686756

50 98048025

51 98048022

52 98048015

53 89141112

54 98614403

55 98604406

56 98614401

57 98727607

98523264 Nipple 1¼" x 4"

98523274 Nipple 1¼" x Close

98761604 Pipe Cross, ½"

96686756 PVC Tubing, 3 /

8

" ID x 6 ft.

98048011 Reducer Bushing, ¾" x ¼"

98048012 Reducer Bushing, ¾" x ½"

98048015

Reducer Bushing,

2" Spigot x 1" NPTF, PVC

89141112 Retaining Tie

98604403 Square Head Plug, ¼"

98604402 Square Head Plug, ½"

98604401 Square Head Plug, ¾"

98727607 Strainer, ¼"

14 98840181

15 98840145

16 98840147

17 92056702

18 92056703

19 92056810

20 92056705

21 92056704

22 96686722

98840181

98840145

98840147

Check Valve,

¼" NPTM x ¼" NPTF

Check Valve,

Horizontal Swing, ½" NPT

Check Valve,

Horizontal Swing, 1" NPT

Check Valve,

Inline Poppet, ¼"

92056702

92056703

92056810

3

Compression Connector,

/

8

" ID Tube x ¼" NPT

Compression Connector,

Elbow 3 /

8

" ID Tube x ¼" NPT

3

Connector,

/

8

" ID Tube x ½" NPT

92056705

92056704

Connector, Elbow,

3 /

8

" ID Tube x ¼" NPT

Connector, Elbow,

3 /

8

" ID Tube x ½" NPT

96686722 Copper Tubing, 3 /

8

" OD x 2 ft.

1

1

1

1

1

1

1

1

1

58 98174400

59 98761651

60 98761649

61 96606607

62 96606601

63 96606612

64 96606630

65 98815200

66 98815204

67 98840160

68 98248000

69 98248001

70 95306255

98164409 Street Elbow, ½"

98761603 Tee, ½"

98761604 Tee, ½" x ¼" x ½"

98761605 Tee, ½" x ½" x ¼"

98766521 Tee, ¾"

98761614 Tee, ¾" x ½" x ½"

98761621 Tee, 1¼" x 1¼" x 1"

98805200 Union, ½"

98845204 Union, ½", O-ring Seal

98840160 Valve, 3-way, ¼"

98248000

98248001

Air Pressure Gauge

(0-80 psi)

Water Pressure Gauge

(0-300 psi)

95306255 Hose Clamp

QTY.

1

2

1

1

2

1

1

1

2

1

2

2

1

1

9

3

1

1

1

2

1

1

1

1

2

4

1

1

2

1

7

4

1

4

1

1

1

1

1

1

1

1

1

1

1

1

2

3

12.

13.

Large DDX Electric Actuation SI Trim (Refer to Fig. 6)

Item

No.

1

Part No.

Galvanized Black Pipe

6103060024 6103060024

6103040026 6103040026

6103060028 6103060028

Description

Valve Assembly, 4" (100mm)

- For 4" Assembly Only

Valve Assembly, 6" (150mm)

- For 6" Assembly Only

Valve Assembly, 165mm

- For 165mm Assembly Only

QTY.

1

Item

No.

Part No.

Galvanized Black Pipe

23 98050004

24 95306270

98050004

95306270

Description

Drain Cup, PVC

Drain Hose Clip

25 98174404

26 98174402

98164402 Elbow, ¼"

98164400 Elbow, ¾"

2

6103080001 6103080001

6215051600 6215051600

6215052400 6215052400

6215053200 6215053200

Valve Assembly, 8" (200mm)

- For 8" Assembly Only

Butterfly Valve, 4"

- For 4" Assembly Only

Butterfly Valve, 6"

- For 6" Assembly Only

1

27 98174403

28 98174405

29 96920912

30 98840172

31 98840171

32 98543226

33 98543225

34 98543220

98164404 Elbow, 1"

98164405 Elbow, 2"

96920912 Flex Line, ½"

98840172 Globe Valve, ¼"

98840171 Globe Valve, ½"

98523213 Nipple ¼" x 1½"

98573220 Nipple ¼" x 2½"

98523219 Nipple ¼" x 3"

3

4

7G05161600 7G05161600

7G05242400 7G05242400

7G05323200 7G05323200

91004004 91004004

Butterfly Valve, 8"

- For 8" Assembly Only

Rigid Coupling, 4"

- For 4" Assembly Only

Rigid Coupling, 6"

- For 6" Assembly Only

Rigid Coupling, 8"

- For 8" Assembly Only

Outlet Spool, 4"

- For 4" Assembly Only

2

1

35 98543217

36 98543223

37 98543209

38 98543230

39 98543216

40 98543237

41 98543234

42 98543279

43 98543222

98523217 Nipple ¼" x 6"

98523210 Nipple ½" x 1½"

98523209 Nipple ½" x 2"

98523230 Nipple ½" x 3"

98523216 Nipple ½" x 3½"

98523250 Nipple ½" x 8"

98523247 Nipple ¾" x 3½"

98523241 Nipple ¾" x Close

98523224 Nipple 1" x 3½"

5

6

7

91004006

91004008

91004006

91004008

Outlet Spool, 6"

- For 6" Assembly Only

Outlet Spool, 8"

- For 8" Assembly Only

6871020000 6871020000 Solenoid Valve, 175 psi Rated

6871020020 6871020020 Solenoid Valve, 300 psi Rated

78653000

78653004

78653000

78653004

Manual Emergency Station

Assembly

Valve Caution Station

Assembly

8

9

78653100

99080002

10 98840100

11 98840117

12 98840188

13 98840181

14 98840145

15 98840147

16 92056702

17 92056703

18 92056810

19 92056705

20 92056704

21 96686722

22 94616917

78653100 Ball Drip Valve, ½"

99080002 Adhesive Pad

98840100 Angle Valve, 2"

98840117

98840188

Ball Valve,

¼" NPTF x ¼" NPTM

Check Valve,

¼" NPTM x ¼" NPTF

98840181

98840145

98840147

Check Valve,

Horizontal Swing, ½" NPT

Check Valve,

Horizontal Swing, 1" NPT

Check Valve,

Inline Poppet, ¼"

92056702

92056703

3

Compression Connector,

/

8

" ID Tube x ¼" NPT

Compression Connector,

Elbow 3 /

8

" ID Tube x ¼" NPT

92056810

92056705

3

Connector,

/

8

" ID Tube x ½" NPT

3

Connector, Elbow,

/

8

" ID Tube x ¼" NPT

92056704

3

Connector, Elbow,

/

8

" ID Tube x ½" NPT

96686722 Copper Tubing, 3 /

8

" OD x 2 ft.

94616917 Single Interlock Nameplate

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

44 98543266

45 98543213

46 98543262

47 98543238

48 98750003

49 96686756

50 98048025

51 98048022

52 98048015

53 89141112

54 98614403

55 98604406

56 98614401

57 98727607

58 98761651

59 98761649

60 96606607

61 96606601

62 96606612

63 96606627

64 98815200

65 98815204

66 98840160

67 98248000

68 98248001

69 95306255

98523228 Nipple 1" x 6"

98523222 Nipple 1" x Close

98523262 Nipple 2" x 3½"

98523254 Nipple 2" x Close

98750013 Pipe Cross, ½"

96686756 PVC Tubing, 3 /

8

" ID x 6 ft.

98048011 Reducer Bushing, ¾" x ¼"

98048012 Reducer Bushing, ¾" x ½"

98048015

Reducer Bushing,

2" Spigot x 1" NPTF, PVC

89141112 Retaining Tie

98604403 Square Head Plug, ¼"

98604402 Square Head Plug, ½"

98604401 Square Head Plug, ¾"

98727607 Strainer, ¼"

98761603 Tee, ½"

98761604 Tee, ½" x ¼" x ½"

98761605 Tee, ½" x ½" x ¼"

98766521 Tee, ¾"

98761614 Tee, ¾" x ½" x ½"

98761618 Tee, 2" x 2" x 1"

98805200 Union, ½"

98845204 Union, ½", O-ring Seal

98840160 Valve, 3-way, ¼"

98248000

Air Pressure Gauge

(0-80 psi)

98248001

Water Pressure Gauge

(0-300 psi)

95306255 Hose Clamp

QTY.

2

1

1

1

2

1

1

1

1

2

1

1

2

11

3

1

1

1

1

1

1

1

1

1

1

1

2

1

1

1

2

1

3

1

1

1

1

1

1

2

1

2

9

4

1

2

3

14.

15.

Small DDX Dry Pilot Line SI (Refer to Fig. 7)

Item

No.

Part No.

Galvanized Black Pipe

Description QTY.

1

6103022000 6103022000

6103022500 6103022500

6103027600 6103027600

Valve Assembly, 2" (50mm)

- For 2" Assembly Only

Valve Assembly, 2½" (65mm)

- For 2½" Assembly Only

Valve Assembly, 76mm

- For 76mm Assembly Only

1

2

3

4

6103030000 6103030000

6990003549 6990003549

6215051000 6215051000

6215051200 6215051200

7G05080800 7G05080800

7G05101000 7G05101000

7G05121200 7G05121200

91004002

91004001

91004003

91004002

91004001

91004003

6999991340 6999991340

Valve Assembly, 3" (80mm)

- For 3" Assembly Only

Butterfly Valve, 2"

- For 2" Assembly Only

Butterfly Valve, 2½"

- For 2½" Assembly Only

Butterfly Valve, 3"

- For 3" Assembly Only

Rigid Coupling, 2"

- For 2" Assembly Only

Rigid Coupling, 2½"

- For 2½" Assembly Only

Rigid Coupling, 3"

- For 3" Assembly Only

Outlet Spool, 2"

- For 2" Assembly Only

Outlet Spool, 2½"

- For 2½" Assembly Only

Outlet Spool, 3"

- For 3" Assembly Only

Pressure Switch (EPS40-2)

(UL/FM)

5

6

7

8

9 78653100

10 99080002

11 98840101

12 98840106

13

14

15

6999992361 6999992361

71030010

Pressure Switch (EPSA40-2)

(ULC)

71030010 Model LP Pilot Line Actuator

78653000

78653004

78653000

78653004

Manual Emergency Station

Assembly

Valve Caution Station

Assembly

98840117

98840188

98840181

78653100 Ball Drip Valve, ½"

99080002 Adhesive Pad

98840101 Angle Valve, ¼"

98840106 Angle Valve, 1¼"

98840117

98840188

98840181

Ball Valve,

¼" NPTF x ¼" NPTM

Check Valve,

¼" NPTM x ¼" NPTF

Check Valve, Horizontal

Swing, ½" NPT

16

17

18

19

20

21

22

23

98840145

98840147

96816904

92056702

92056703

92056810

92056705

92056704

1

2

1

1

1

1

1

1

1

2

98840145

Check Valve, Horizontal

Swing, 1" NPT

1

98840147 Check Valve, Inline Poppet, ¼" 1

96816904 Check Valve, Inline Poppet, ½" 1

92056702

92056703

92056810

92056705

92056704

3

Compression Connector,

/

8

" ID Tube x ¼" NPT

Compression Connector,

Elbow 3 /

8

" ID Tube x ¼" NPT

3

Connector,

/

8

" ID Tube x ½" NPT

3

Connector, Elbow,

/

8

" ID Tube x ¼" NPT

3

Connector, Elbow,

/

8

" ID Tube x ½" NPT

1

1

1

1

1

1

1

1

1

Item

No.

Part No.

24 96686722

Description

Galvanized Black Pipe

96686722 Copper Tubing, 3 /

8

" OD x 2 ft.

25 94616917

26 98050004

27 95306270

94616917 Single Interlock Nameplate

98050004 Drain Cup, PVC

95306270 Drain Hose Clip

28 98174404

29 98174402

30 98174403

31 98174414

98164402 Elbow, ¼"

98164400 Elbow, ¾"

98164404 Elbow, 1"

98164407 Elbow, 1¼"

32 96920912

33 98840172

34 98840171

35 98543226

36 98543220

37 98543243

38 98543223

39 98543209

40 98543230

96920912 Flex Line, ½"

98840172 Globe Valve, ¼"

98840171 Globe Valve, ½"

98523213 Nipple ¼" x 1½"

98523219 Nipple ¼" x 3"

98526522 Nipple ¼" x 4"

98523210 Nipple ½" x 1½"

98523209 Nipple ½" x 2"

98523230 Nipple ½" x 3"

41

42

43

44

45

46

47

48

49

50

51

52

53

98543235

98543212

98543232

98543267

98543263

98543213

98543239

98543250

98543285

98750003

96686756

98048000

98048025

54 98048022

98523235 Nipple ½" x 8½"

98523221 Nipple ½" x Close

98523242 Nipple ¾" x 2"

98523263 Nipple ¾" x 6"

98523261 Nipple 1" x 3"

98523222 Nipple 1" x Close

98523256 Nipple 1¼" x 3"

98523264 Nipple 1¼" x 4"

98523274 Nipple 1¼" x Close

98750013 Pipe Cross, ½"

96686756 PVC Tubing, 3 /

8

" ID x 6 ft.

98048020 Reducer Bushing, ½" x ¼"

98048011 Reducer Bushing, ¾" x ¼"

55

56

57

58

59

60

70

71

72

73

74

98048015

98840195

89141112

98614403

98604406

98614401

61 98727607

62 98174400

63 98761651

64 98761649

65 96606607

66 96606601

67 96606612

68 96606603

69 98815200

98815204

98840160

98248000

98248001

95306255

98048012 Reducer Bushing, ¾" x ½"

98048015

Reducer Bushing,

2" Spigot x 1" NPTF, PVC

98840195 Relief Valve, ½" NPT, 33 psi

89141112 Retaining Tie

98604403 Square Head Plug, ¼"

98604402 Square Head Plug, ½"

98604401 Square Head Plug, ¾"

98727607 Strainer, ¼"

98164409 Street Elbow, ½"

98761603 Tee, ½"

98761604 Tee, ½" x ¼" x ½"

98761605 Tee, ½" x ½" x ¼"

98766521 Tee, ¾"

98761614 Tee, ¾" x ½" x ½"

98761621 Tee, 1¼" x 1¼" x 1"

98805200 Union, ½"

98845204 Union, ½", O-ring Seal

98840160 Valve, 3-way, ¼"

98248000

Air Pressure Gauge

(0-80 psi)

98248001

Water Pressure Gauge

(0-300 psi)

95306255 Hose Clamp

QTY.

1

1

1

3

1

2

1

1

2

1

1

1

1

4

9

7

1

1

1

1

4

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

2

3

2

2

1

3

4

2

1

9

1

2

2

3

16.

17.

Large DDX Dry Pilot Line SI (See Fig. 8)

Item

No.

Part No.

Galvanized Black Pipe

Description

1

6103060024 6103060024

6103040026 6103040026

6103060028 6103060028

Valve Assembly, 4" (100mm)

- For 4" Assembly Only

Valve Assembly, 6" (150mm)

- For 6" Assembly Only

Valve Assembly, 165mm

- For 165mm Assembly Only

QTY.

1

2

3

4

6103080001 6103080001

6215051600 6215051600

6215052400 6215052400

6215053200 6215053200

7G05161600 7G05161600

7G05242400 7G05242400

7G05323200 7G05323200

91004004

91004006

91004008

91004004

91004006

91004008

6999991340 6999991340

Valve Assembly, 8" (200mm)

- For 8" Assembly Only

Butterfly Valve, 4"

- For 4" Assembly Only

Butterfly Valve, 6"

- For 6" Assembly Only

Butterfly Valve, 8"

- For 8" Assembly Only

Rigid Coupling, 4"

- For 4" Assembly Only

Rigid Coupling, 6"

- For 6" Assembly Only

Rigid Coupling, 8"

- For 8" Assembly Only

Outlet Spool, 4"

- For 4" Assembly Only

Outlet Spool, 6"

- For 6" Assembly Only

Outlet Spool, 8"

- For 8" Assembly Only

Pressure Switch (EPS40-2)

(UL/FM)

5

6

7

8

6999992361 6999992361

Pressure Switch (EPSA40-2)

(ULC)

71030010 71030010 Model LP Pilot Line Actuator

78653000

78653004

78653000

78653004

Manual Emergency Station

Assembly

Valve Caution Station

Assembly

9 78653100 78653100 Ball Drip Valve, ½"

10 99080002 99080002 Adhesive Pad

11 98840100 98840100 Angle Valve, 2"

12

13

98840117

98840188

98840117

98840188

Ball Valve,

¼" NPTF x ¼" NPTM

Check Valve,

¼" NPTM x ¼" NPTF

1

2

1

1

1

1

1

1

1

14

15

98840181

98840145

98840181

98840145

Check Valve, Horizontal

Swing, ½" NPT

Check Valve, Horizontal

Swing, 1" NPT

2

1

16 98840147 98840147 Check Valve, Inline Poppet, ¼" 1

17 96816904 96816904 Check Valve, Inline Poppet, ½" 1

18

19

92056702

92056703

92056702

92056703

3

Compression Connector,

/

8

" ID Tube x ¼" NPT

Compression Connector,

Elbow 3 /

8

" ID Tube x ¼" NPT

1

1

20

21

92056810

92056705

92056810

92056705

3

Connector,

/

8

" ID Tube x ½" NPT

3

Connector, Elbow,

/

8

" ID Tube x ¼" NPT

22 92056704 92056704

3

Connector, Elbow,

/

8

" ID Tube x ½" NPT

23 96686722 96686722 Copper Tubing, 3 /

8

" OD x 2 ft.

24 94616917 94616917 Single Interlock Nameplate

1

1

1

1

1

1

1

1

18.

Item

No.

Part No.

Galvanized Black Pipe

Description

25 98050004 98050004 Drain Cup, PVC

26 95306270 95306270 Drain Hose Clip

27 98174404 98164402 Elbow, ¼"

28 98174402 98164400 Elbow, ¾"

29 98174403 98164404 Elbow, 1"

30 98174405 98164405 Elbow, 2"

31 96920912 96920912 Flex Line, ½"

32 98840172 98840172 Globe Valve, ¼"

33 98840171 98840171 Globe Valve, ½"

34 98543226 98523213 Nipple ¼" x 1½"

35 98543225 98573220 Nipple ¼" x 2½"

36 98543220 98523219 Nipple ¼" x 3"

37 98543217 98523217 Nipple ¼" x 6"

38 98543223 98523210 Nipple ½" x 1½"

39 98543209 98523209 Nipple ½" x 2"

40 98543230 98523230 Nipple ½" x 3"

41 98543216 98523216 Nipple ½" x 3½"

42 98543252 98523232 Nipple ½" x 10½"

43

98543234 98523247

Nipple ¾" x 3½"

(6" & 8" Versions)

98543282 98523253 Nipple ¾" x 4" (4" Version)

44 98543279 98523241 Nipple ¾" x Close

45 98543222 98523224 Nipple 1" x 3½"

46 98543266 98523228 Nipple 1" x 6"

47 98543213 98523222 Nipple 1" x Close

48 98543262 98523262 Nipple 2" x 3½"

49 98543238 98523254 Nipple 2" x Close

50 98750003 98750013 Pipe Cross, ½"

51 96686756 96686756 PVC Tubing, 3 /

8

" ID x 6 ft.

52 98048000 98048020 Reducer Bushing, ½" x ¼"

53 98048025 98048011 Reducer Bushing, ¾" x ¼"

54 98048022 98048012 Reducer Bushing, ¾" x ½"

55 98048015 98048015

Reducer Bushing,

2" Spigot x 1" NPTF, PVC

56 98840195 98840195 Relief Valve, ½" NPT, 33 psi

57 89141112 89141112 Retaining Tie

58 98614403 98604403 Square Head Plug, ¼"

59 98604406 98604402 Square Head Plug, ½"

60 98614401 98604401 Square Head Plug, ¾"

61 98727607 98727607 Strainer, ¼"

62 98761651 98761603 Tee, ½"

63 98761649 98761604 Tee, ½" x ¼" x ½"

64 96606607 98761605 Tee, ½" x ½" x ¼"

65 96606601 98766521 Tee, ¾"

66 96606612 98761614 Tee, ¾" x ½" x ½"

67 96606627 98761618 Tee, 2" x 2" x 1"

68 98815200 98805200 Union, ½"

69 98815204 98845204 Union, ½", O-ring Seal

70 98840160 98840160 Valve, 3-way, ¼"

71

72

98248000

98248001

98248000

98248001

Air Pressure Gauge

(0-80 psi)

Water Pressure Gauge

(0-300 psi)

73 95306255 95306255 Hose Clamp

QTY.

2

14

3

2

1

1

2

1

1

1

1

1

1

1

1

2

1

1

1

2

2

4

1

1

2

1

1

1

2

2

1

1

9

5

2

3

1

2

1

1

1

2

1

1

1

2

1

2

3

Pressurizing Line Connection

The water supply for the push-rod chamber must be provided by connection of its inlet pressurizing line to the water supply piping. Pressurizing lines for multiple Model DDX

Deluge Valve push-rod chambers must never be manifolded together, having only a single tap on the water supply piping. Each Model DDX Deluge Valve must have its own push-rod chamber pressurizing line connection.

This connection must be made on the supply side of the water supply control valve (see Fig. 7 or Fig. 8). This can be accomplished by:

• Using a tapped connection directly below or next to the main water supply control valve using a welded outlet or the appropriate mechanical fittings. A grooved-end outlet coupling is one way to achieve this; or

• Using a water supply control valve that has an available threaded (NPT) supply-side tap design to allow for a direct water supply connection to the Model DDX Deluge

Valve’s push-rod chamber.

Caution: Reliable’s DDX valve is designed with an inlet restriction built into the pushrod chamber. It is important not to introduce additional restrictions into the direct water supply connection or the discharge from the pushrod chamber by installing additional valves or improperly installing the copper lines used in the trim of the valve.

Hydrostatic Testing of DDX Valves and DDX

Systems

As required by NFPA 13, fire sprinkler systems with working pressures up to and including 150 psi are to be hydrostatically tested at a water pressure of 200 psi and maintain that pressure without loss for two hours. Fire sprinkler systems with working pressures above 150 psi are required to be hydrostatically tested at 50 psi above the system working pressure and maintain that pressure without loss for two hours. In addition to the hydrostatic tests described above, dry pipe and double interlock preaction systems require an additional low pressure air test.

In some cases, hydrostatic testing (in accordance with the

NFPA 13 requirements noted above) will result in pressures that exceed the working pressure of the valve and trim kit for the two-hour test period. The valve and applicable trim kit have been tested, approved and listed under these conditions and as such, hydrostatic testing in accordance with NFPA 13 is acceptable. In addition, the clapper can remain in the closed position and the trim kit need not be isolated, as each has been designed to withstand hydrostatic testing as required by NFPA 13.

Hydrostatically testing the valve and trim to pressures higher than their rating is limited to the hydrostatic test as referenced by NFPA 13. It does not address the occurrence(s) of a “water hammer” effect, which can indeed damage the valve. A “water hammer” in the water supply piping of the valve can create pressures in excess of the rated pressure and should be avoided by all necessary means. This condition may be created from improper fi re pump settings, underground construction work, or an improper venting of trapped air in the water supply piping.

19.

System Design Considerations

The automatic sprinklers, wet pilot line sprinklers/ detectors, and signaling devices which are utilized with the Wet

Pilot Line Single Interlock Preaction System must be UL or

ULC Listed, as applicable.

The automatic sprinklers, air compressor, releasing devices, electric releasing control equipment, fire detection devices, manual pull stations, and signaling devices which are utilized with the Electric Actuation Single Interlock Preaction System must be UL or ULC Listed or FM Approved, as applicable.

The automatic sprinklers, air compressor, releasing devices, electric releasing control equipment, fire detection devices, manual pull stations, and signaling devices which are utilized with the Dry Pilot Line Single Interlock Preaction

System must be UL or ULC Listed, as applicable.

The Deluge Valve, and all interconnecting piping must be located in a readily visible and accessible location and in an area that can be maintained at a minimum temperature of

40°F (4°C). Note: Heat tracing is not permitted.

Pendent sprinklers, other than dry pendents, used on preaction systems shall be installed on return bends per NFPA

13.

In Electric Actuation Single Interlock Preaction Systems, the solenoid valve is operated and supervised by the electrical releasing/control panel.

In Wet Pilot Line Single Interlock Preaction Systems, the wet pilot line is only a detection system and does not contribute to controlling the fire. Its installation is subject to the following restrictions: a. It is not to be installed in an area subject to freezing.

b. It is not to be installed in an area where temperatures in excess of 150°F (65°C) are anticipated.

c. NFPA 72 or the authority having jurisdiction should be consulted for spacing and elevation requirements.

d. Maximum wet pilot line length and height must comply with data provided in Fig. 2.

System Air Pressure Requirements

For Wet Pilot Single Interlock Preaction Systems and

Electric Actuation Single Interlock Preaction Systems, a

Reliable Model B-SI Air Compressor Panel or Reliable Model C-SI Air Compressor Panel can be used to maintain the system air pressure at approximately 7 psi (0,5 bar). The air compressor panels contain an integral low air pressure warning light.

In some circumstances, such as when dry sprinklers are being used in a preaction system, it may be desirable to supervise the preaction system at air pressures higher than 7 psi (0,5 bar). For such cases, Reliable recommends the use of a tank-mounted compressor and the Reliable Model A-2

Pressure Maintenance Device. Supervising pressure may be between 7 psi and 20 psi (0,5 and 1,4 bar).

For Dry Pilot Line Single Interlock Preaction Systems, a Reliable Model A-2 Pressure Maintenance Device can be used to maintain the pneumatic pressure of both the Dry

Pilot Line of detectors and the fire sprinklers to the values shown in Table A. The values listed in the table represent the necessary ranges of pneumatic pressure required to keep the Model LP Dry Pilot Line Actuator in the closed position for a given water supply pressure.

Table A

Water Pressure psi (bar)

Maximum

20 (1.4)

30 (2.1)

50 (3.4)

75 (5.2)

100 (6.9)

125 (8.6)

150 (10.3)

175 (12.1)

200 (13.8)

225 (15.5)

250 (17.2)

275 (19.0)

300 (20.7)

Pneumatic Pressure to be

Pumped into Sprinkler System psi (bar)

Not Less Than Not More Than

8 (0.6)

10 (0.7)

12 (0.8)

13 (0.9)

15 (1.0)

16 (1.1)

17 (1.2)

18 (1.2)

19 (1.3)

21 (1.4)

22 (1.5)

23 (1.6)

24 (1.7)

10 (.7)

14 (1.0)

16 (1.1)

17 (1.2)

19 (1.3)

20 (1.4)

21 (1.4)

22 (1.5)

23 (1.6)

25 (1.7)

26 (1.8)

27 (1.9)

28 (1.9)

Note: During system set-up, a higher pneumatic pressure may be required in order to properly set the Model

LP Dry Pilot Line Actuator.

Whenever multiple systems area supplied by a common air or nitrogen source, each system must have its own pressure maintenance device for individual maintenance of pressure (NFPA 13, 7.2.6.5).

System Electrical Requirements

When Using the Electric Actuation Single Interlock Preaction System, all releasing, alarm and detection devices in the Single Interlock Preaction System are supervised by the Potter PFC-4410-RC Releasing Control Panel. Connect these devices as shown in Fig. 9. The Releasing/ Control

Panel should be set to use Program #6 (See Potter Instruction Manual #5403550).

The power supply, the standby emergency power supply, battery charger, and the rectifier circuitry are all contained within the Potter PFC-4410-RC Releasing Control Panel. The solenoid valve is operated and supervised by the Potter

PFC-4410-RC Releasing Control Panel. Potter PFC-4410-

RC Releasing Control Panel requires 120 VAC. Batteries that provide ninety hours of standby power are required for Factory Mutual Approved systems.

Note:

In order for the solenoid valve to maintain Reliable’s warranty it must remain sealed as it came from the factory. If there are concerns about the valve’s internal components, immediate replacement is recommended.

Standard Solenoid Valve Specifi cations:

Skinner Model 73218BN4UNLVN0C111C2

Rated working pressure: 175 psi (12,1 bar)

Voltage: 24 VDC

Power: 10 Watts

Current: 0.41 Amps Holding

Enclosure Coil: NEMA 4X

Pipe Size: ½” NPT Female

Cv Factor: 4.0

Alternate Solenoid Valve Specifi cations:

Skinner Model 73212BN4TNLVN0C322C2

Rated working pressure: 300 psi (20,7 bar)

Voltage: 24 VDC

Power: 22 Watts

Current: 0.83 Amps Holding

Enclosure Coil: NEMA 4X

Pipe Size: ½” NPT Female

Cv Factor: 2.8

20.

Single Interlock Preaction Systems Engineering

Specifi cation

2” (50 mm), 2½” (65 mm), 76 mm, 3” (80 mm), 4” (100 mm),

165 mm, 6” (150 mm) and 8” (200 mm)

Model DDX Deluge Valve

Preaction System shall be a Single Interlock Preaction

System utilizing a [2” (50 mm)][2½” (65 mm)][76 mm] [3”

(80 mm)][4” (100 mm)][165 mm][6” (150 mm][8” (200 mm)]

[cULus Listed] [Factory Mutual Approved] hydraulically operated, differential latching clapper type valve. Deluge valve construction shall be of lightweight, ductile iron construction with either a “screw in” stainless steel seat and clapper assembly or drop in bronze seat and clapper assembly. Stainless steel or Bronze seat shall have O-ring seals to resist leakage and corrosion. Clapper facing shall be pressure actuated, providing a limited compression seat for the sealing force between the clapper rubber facing and the valve seat. Deluge valve shall have an external reset knob for resetting the clapper without requiring the removal of the valve face plate. Push-rod chamber design shall consist of a stainless steel piston/ push-rod and spring assembly with diaphragm seal secured to the casting through a push-rod guide constructed of a synthetic engineering plastic to resist corrosion. Casting shall have a bleeder hole located on the pushrod chamber for air/water leakage indication. Trip ratio shall be approximately a 3:1 force differential. Deluge valve shall be of the straight through design to minimize friction

21.

loss. Inlet restriction orifice shall be factory installed into the inlet port of the deluge valve push-rod cover plate and not be a separate part of the deluge valve trim. End connection style to be [2” (50 mm)][2½” (65 mm)][76 mm] [3” (80 mm)]

[4” (100 mm)][165 mm][6” (150 mm][8” (200mm] grooved, per ANSI/AWWA C606 or flanged per ASME B16.5 or ISO

7005. Deluge valve shall have a rated working pressure of

250 psi (17,2 bar) for 2” (50mm), 2½” (65mm), 76mm, 3”

(80mm) and 8” (200mm) valve sizes and 300 psi (20,7 bar) for 4” (100mm), 165mm and 6” (150mm) valve sizes and shall be factory hydrostatic tested at 500 psi (34,5 bar) for

2” (50mm), 2½” (65mm), 76mm, 3” (80mm) and 8” (200mm) valve sizes and 600 psi (41,4 bar) for 4” (100mm), 165mm and 6” (150mm) valve sizes.

Deluge valve to be [2” (50 mm)][2½” (65 mm)][76 mm] [3”

(80 mm)][4” (100 mm)][165 mm][6” (150 mm][8” (200 mm)]

Reliable Model DDX Deluge Valve (Bulletin 519).

Interlock Preaction Trims shall consist of either black pipe or galvanized pipe and brass components specifically listed/approved with the deluge valve.

In addition, the Electric Actuation Single Interlock Preaction Trim shall include a Deluge valve releasing device to be an electrical two-way, normally closed, pilot operated solenoid valve [cULus Listed] [FMApproved] for its intended use. The solenoid valve shall be constructed of a brass body with stainless steel sleeve tube, springs, stop and plunger, and with ½” female NPT end connections. Solenoid valve shall have a maximum working pressure of [175 psi (12,1 bar)] [300 psi (20,7 bar)] and maximum ambient temperature rating of 150°F (66°C). Power consumption of integrated coil shall be limited to [10 watts (175 psi (12,1 bar)) Rated]

[22 watts (300 psi (20,7 bar)) Rated] and require 24 VDC from a releasing/control panel listed for such service. Solenoid valve shall be a Skinner ½” normally-closed solenoid valve, [Model 73218BN4UNLVNOC111C2 (175 psi (12,1 bar)) Rated]. [Model 73212BN4TNLVNOC322C2 (300 PSI

(20,7 bar)) Rated].

Dry Pilot Line Single Interlock Preaction Trim shall include a low pressure pneumatic actuator which is constructed of cast iron utilizing a diaphragm and compression spring design to separate the pushrod chamber water pressure from the system piping’s pneumatic supervisory air pressure.

The low-pressure actuator shall only require between 8 and

28 psi (0,6 and 1,9 bar) supervisory air pressure for proper setting in accordance with the manufacturers instructions.

The Low-pressure actuator shall be Reliable Model LP Dry

Pilot Line Actuator. The Dry Pilot Line Single Interlock Trim shall also include a low air pressure switch to indicate loss of air pressure in the system piping. The switch shall be

[UL Listed/ FM Approved][cULus Listed] and of the bellowsactivated type enclosed in a weatherproof NEMA 4X/ NEMA

4 rated enclosure incorporating tamper resistant screws.

There shall be two sets of SPDT (form C) contacts rated 10.0

A @ 125/250 VAC and 2.5 A @ 6/12/24 VDC. The pressure switch shall have a maximum service pressure rating of 250 psi (17,2bar). Switch shall be provided with a ½” NPT male pressure connection. Low air supervisory switch shall be

System Sensor EPS40-2.

Pneumatic Supervisory Pressure Supply Options

Owner’s Air supply

Supervisory air supply shall be provided by an owner supplied air system in conjunction with a [cULus Listed] automatic pressure maintenance device, capable of maintaining a constant system pressure regardless of pressure fluctuations in the compressed air source. The pressure maintenance device shall consist of galvanized trim and brass parts, including a strainer and a field adjustable air pressure regulator, and have a working pressure rating of 175 psi

(12,1 bar). The pressure regulator shall have an adjustable outlet pressure range of 5 to 100 psi (0,34 to 6,8 bar). Pressure maintenance device shall be Reliable Model A-2 (see

NFPA13).

Low Pressure Air Compressor Panel

Wet Pilot Line Single Interlock Preaction and Electric Actuation Single Interlock Preaction system supervisory air supply shall be a [cULus Listed] [FM Approved] self-contained, low pressure air compressor panel containing a 1/16 hp air compressor, DPDT relay for remote supervisory annunciation, low pressure warning light, pressure gauge, and low pressure alarm switch. Pressure switch shall control the compressor, providing a maximum operating supervisory pressure of approximately 7 psi (0,5 bar), and a low-pressure supervisory alarm at approximately 4 psi (0,3 bar). Power requirements shall be 120 VAC/60 Hz or 220/230 VAC/50 HZ.

Low Pressure Air Compressor Panel shall be Reliable Model

B-SI or C-SI.

Compressed Air Supply

Supervisory air supply shall be provided by an automatic air compressor sized for the capacity (volume) of the single interlock preaction system piping, and be capable of restoring normal air pressure in the system within the time limits specified in NFPA 13.

Dry Pilot Line Single Interlock Preaction systems desiring a higher supervisory air pressure, shall only require between 8 and 28 psi (0,6 to 1,9 bar) supervisory pressure for proper setting of the low pressure pneumatic actuator in accordance with the manufacturer’s instructions. Air supply shall be equipped with an automatic pressure maintenance device capable of maintaining a constant system pressure regardless of pressure fluctuations in the compressed air

(or nitrogen) source, or system piping. The pressure maintenance device shall consist of galvanized trim and brass parts, including a strainer and a field adjustable air pressure regulator, or pressure switch, and have a working pressure rating of 175 psi (12,1 bar). The pressure regulator shall have an adjustable outlet pressure range of 5 to 100 psi (0,34 to

6,8 bar). Pressure maintenance device shall be Reliable

Model A-2 or Reliable Model B-1. (Note: For small systems with air compressors having a capacity less than 5.5 cfm @

10 psi, a pressure maintenance device is not required per

NFPA 13. Consideration should be given, however, to the impact of a direct air supply on the overall performance of the system.)

22.

Nitrogen

Nitrogen cylinders provided by an approved source shall provide the nitrogen supply. Dry Pilot Line Single Interlock

Preaction System and Wet Pilot Ling Single Interlock or Electric Actuation Single Interlock Preaction systems desiring a higher supervisory air pressure, shall only require between

8 and 28 psi (0,6 to 1,9 bar) supervisory pressure for proper setting of the low pressure pneumatic actuator in accordance with the manufacturer’s instructions. The nitrogen cylinder pressure shall be regulated and supervised through the use of nitrogen regulating device and low-pressure trim kit. This device shall consist of a brass, single stage pressure regulator, equipped with high pressure inlet and low pressure outlet gauges, and ¼” copper connection tubing with galvanized ¾” x ¼” reducer bushing. Optional: Lowpressure trim kit shall be included to monitor the regulated nitrogen supply pressure to provide a low-pressure supervisory alarm. This kit shall include a low-pressure switch with associated galvanized connection trim. Assembly shall be a Reliable Nitrogen Regulating Device. This device is to be used in conjunction with the Reliable Model A-2 Pressure

Maintenance Device.

Optional System Accessories

System Control Valve

Preaction system control valve shall be a slow close, [cU-

Lus Listed] indicating butterfly type valve with a pre-wired supervisory tamper switch assembly. The valve shall be rated for a working pressure of [300 psi (20,7 bar)]. System control valve shall be for a [2” (50 mm)] Gruvlock AN7722-

3A Butterfly Valve or [2½” (65 mm)][3” (80 mm)][4” (100 mm)][6” (150 mm][8” (200 mm] - Nibco GD-4765-8N Butterfly Valve.

Waterfl ow Alarm Pressure Switch

Alarm pressure switch shall be provided to indicate water flow and provide a water flow alarm. Pressure switch shall be

[cULus Listed] and of the bellows activated type enclosed in a weatherproof, 4x, NEMA 4-rated enclosure incorporating tamper-resistant screws. There shall be two sets of SPDT

(Form C) contacts rated at 10.0 A @ 125/250 VAC and 2.5 A

@ 6/12/24 VDC. The pressure switch shall have a maximum service pressure rating of 250 psi (17,2 bar) and shall be factory adjusted to operate at a pressure of 4 to 8 psi (0,27 to 0,55 bar) with adjustment up to 20 psi (1,3 bar). Switch shall be provided with a 1/2” NPT male pressure connection. Waterflow alarm pressure switch shall be System Sensor EPS10-2.

Detection System

To operate the solenoid valve on the electric actuation preaction system, a supplemental electric detection system shall be provided [Insert applicable product specification].

Releasing/Control Panel

A releasing/control panel shall be used to operate the preaction system. The releasing/control panel shall be a conventional, microprocessor-controlled panel containing two initiating device circuits, and waterflow and supervisory inputs. Output circuits shall include alarm, waterflow, supervisory, and releasing circuits. The releasing/control panel

23.

shall be capable of providing any of the following desired modes of operation: single hazard, two zone; single hazard, cross-zoned; dual hazard, combined release; and dual hazard, split release (two area). Releasing/control panel shall be equipped with a local tone alarm to annunciate loss of AC power, system trouble, circuit trouble, and low auxiliary DC power supply. Panel shall be [cULus Listed] [FM Approved] and be capable of providing power for compatible detectors and auxiliary devices used. Audible alarms shall be able to be silenced at releasing panel. Auxiliary DC power supply shall consist of (2) 12-volt lead acid batteries of the same ampere-hour rating, providing [60 hours – cULus Listed]

[90 hours – FM Approved]. Dry contacts shall be provided for remote annunciation of alarm, trouble, and supervisory panel signals. Main power supply to be a dedicated a 120

VAC / 60 Hz circuit.

Technical Data

Reliable Single Interlock Preaction Systems, with associated trim, size 2” (50 mm), 2½” (65 mm), 76 mm, 3” (80 mm),

4” (100 mm), 165 mm, 6” (150 mm) & 8” (200 mm) are rated for use at minimum water supply pressure of 20 psi (1,4 bar) and maximum supply pressure of 250 psi (17,2 bar) for 2”

(50mm), 2½” (65mm), 76mm, 3” (80mm) and 8” (200mm) valve sizes and 300 psi (20,7 bar) for 4” (100mm), 165mm and 6” (150mm) valve sizes. Water supplied to the inlet of the valve and to the pushrod chamber must be maintained between 40°F (4°C) and 140°F (60°C).

The following list of technical bulletins pertains to valves and devices that may be used in this preaction system:

Deluge Valve Reliable 518/519

Hydraulic Emergency Station (Model A) Reliable 506

Solenoid Valve

Mechanical Sprinkler Alarm

Reliable 718

Reliable 612/613

Pressure Maintenance Device Reliable 254

Nitrogen Regulating Device Reliable 254

Air Compressor Panel

(Models B-SI & C-SI)

Reliable 254

Releasing/Control Panel Potter #5403550

Pilot Line Detector Reliable 180

Waterflow Pressure Alarm Switch

System Sensor

WFDS51701

Model DDX Deluge Valve Description

1. Rated working pressure:

Valve & System - 250 psi (17.2 bar) for 2” (50mm),

2 1 /

2

” (65mm), 76mm, 3” (80mm) and 8” (200mm) valve sizes and 300 psi (20,7 bar) for 4” (100mm),

165mm and 6” (150mm) valve sizes.

2. Factory tested to a hydrostatic pressure of 500 psi

(34,5 bar) for 2” (50mm), 2½” (65mm), 76mm, 3” (80mm) and 8” (200mm) valve sizes and 300 psi (20,7 bar) for 4”

(100mm), 165mm and 6” (150mm) valve sizes. (Valve only)

3. End and trim connections:

• ANSI/AWWA C606 grooved inlet and outlet

Nominal

Pipe Size

2” (50 mm)

2½” (65 mm)

76 mm

3” (80 mm)

4” (100 mm)

165 mm

6” (150 mm)

8” (200 mm)

Outlet

Diameter

2.375”

(60mm)

2.875”

(73mm)

3.000”

(76mm)

3.500”

(89mm)

4.500”

(114mm)

6.500”

(165mm)

6.625”

(168mm)

8.625”

(219mm)

Groove

Diameter

2.250”

(57mm)

2.720”

(69mm)

2.845”

(72mm)

3.344”

(85mm)

4.334”

(110mm)

6.330”

(161mm)

6.455”

(164mm)

8.441”

(214mm)

Groove

Width

11/32”

(9.0mm)

11/32”

(9.0mm)

11/32”

(9.0mm)

11/32”

(9.0mm)

3/8”

(9.5mm)

3/8”

(9.5mm)

3/8”

(9.5mm)

7/16”

(11mm)

Outlet

Face to

Groove

5/8”

(16mm)

5/8”

(16mm)

5/8”

(16mm)

5/8”

(16mm)

5/8”

(16mm)

5/8”

(16mm)

5/8”

(16mm)

3/4”

(19mm)

• Threaded openings Per ANSI B 2.1

Flange Dimensions

Flange

Type:

AMSE B16.5

Class 150

Nominal

Pipe

Size

4”

(100mm)

Bolt

Circle

Diameter

7½”

(191mm)

Bolt

Hole

Diameter

¾”

(19mm)

Flange

Outside

Diameter

9”

(229mm)

ISO 7005-2

PN16

4”

(100mm)

7 3 /

32

(180mm)

¾”

(19mm)

9”

(229mm)

AMSE B16.5

Class 150

6”

(150mm)

ISO 7005-2

PN16

6”

(150mm)

AMSE B16.5

Class 150

8”

(200mm)

9½”

(241mm)

9 7 /

16

(240mm)

11¾”

(298mm)

ISO 7005-2

PN16

8”

(200mm)

11 5 /

8

(295mm)

4. Valve Exterior’s Color:

7 /

8

(22mm)

29 /

32

(23mm)

7 /

8

(22mm)

29 /

32

(23mm)

11”

(279mm)

11”

(279mm)

13½”

(343mm)

13½”

(343mm)

Flange

Thickness

15 /

15 /

16

16

(24mm)

(24mm)

15 /

16

(24mm)

15 /

16

(24mm)

1”

(25.4mm)

1”

(25.4mm)

Valve Size

2” (50 mm)

2½” (65 mm)

76 mm

3” (80 mm)

4” (100 mm)

165 mm

6” (150 mm)

8” (200 mm)

5. Face to face dimensions:

Valve Size:

2" (50mm), 2½" (65mm),

76mm & 3" (80mm)

4" (100mm)

6" (150mm) & 165mm

8" (200mm)

End

Connection:

Groove/ Groove

Groove/ Groove

Flange/ Groove

Flange/ Flange

Groove/ Groove

Flange/ Groove

Flange/ Flange

Groove/ Groove

Flange/ Flange

Color

Black or Red

Black or Red

Red

Black or Red

Black or Red

Red

Black or Red

Black or Red

Number of

Bolts

8

8

8

8

8

12

End to End:

12½" (318mm)

14" (356mm)

16" (406mm)

16" (406mm)

16" (406mm)

19" (483mm)

19" (483mm)

19 3 /

8

” (492mm)

21¼" (540mm)

6. Valve Shipping Weight:

Valve Size:

2" (50mm), 2½" (65mm),

76mm & 3" (80mm)

End Connection:

Groove/ Groove

4" (100mm)

6" (150mm) & 165mm

8" (200mm)

Groove/ Groove

Flange/ Groove

Flange/ Flange

Groove/ Groove

Flange/ Groove

Flange/ Flange

Groove/ Groove

Flange/ Flange

7. Trim Shipping Weight:

Weight:

34 lbs (15 kg)

64 lbs (29 kg

79 lbs (36 kg)

92 lbs (42 kg)

95 lbs (43 kg)

122 lbs (56 kg)

138 lbs (69 kg)

148 lbs (67 kg)

197 lbs (90 kg)

Trim

Confi guration

Wet Pilot Single Interlock

2" (50 mm),

2½" (65 mm),

3" (80 mm)

& 76 mm

32 lbs (15 kg)

4" (100 mm),

6" (150 mm),

8" (200 mm)

& 165 mm

38 lbs (17 kg)

Dry Pilot Single Interlock 45 lbs (20 kg)

Electric Actuation Single Interlock 35 lbs (16 kg)

52 lbs (24 kg)

40 lbs (18 kg)

8. Friction loss (Expressed in equivalent length of

Schedule 40 pipe, based on Hazen & Williams formula:

Valve Size:

2" (50mm)

2½" (65mm)

76mm

3" (80mm)

4" (100mm)

165mm

6" (150mm)

8" (200mm)

Equivalent Length:

C = 120

4.4 ft (1,3 m)

C = 100

3.1 ft (1,0 m)

6.0 ft (1,8 m)

7.7 ft (2,3 m)

4.3 ft (1,3 m)

5.5 ft (1,7 m)

Cv

101

236

12.6 ft (3,8 m)

14 ft (4,3 m)

29.4 ft (9,0 m)

9.0 ft (2,7 m)

10 ft (3,0 m)

20.9 ft (6,4 m)

241

254

469

886

29.4 ft (9,0 m) 20.9 ft (6,4 m) 886

53.5 ft (16,3 m) 38.1 ft (11,6 m) 1516

9. Installation position: Vertical

24.

Trim Descriptions

The Single Interlock Preaction Trims for the Reliable Model

DDX Deluge Valve are arranged for rapid, easy, and compact attachment, and serve as connection points to Reliable

Model C Mechanical Alarms and other devices.

The available Model DDX Single Interlock Preaction System trim sets are:

• Wet Pilot Line Single Interlock Preaction Trim

• Dry Pilot Line Single Interlock Preaction Trim

• Electric Actuation Single Interlock Preaction Trim

All three trim configurations can be ordered as individual parts, in time-saving segmentally assembled kit forms, or fully assembled to the Model DDX Deluge Valve (with or without a control valve).

The Model B Hydraulic Manual Emergency Station (see

Fig. 12) is a standard item of all Deluge Valve trim sets. It consists of an aluminum nameplate mechanically attached to a ball valve. The valve handle in its OFF position is guarded against accidental turning to the ON position (and system discharge) by a nylon cable tie provided with each trim kit. The cable tie is inserted, as shown in Fig. 12, after the system has been restored for operation. The nylon cable tie is designed to allow, in case of an emergency, forceful turn-

PRESSURE LOSS (BAR)

M)

M)

0M

(20

H

M

)

M

M

5M

16

&

00

(1

M)

CH

IN

4

NC

8I

0M

MM

0M

76

(8

H

&

M)

NC

3I

5M

(6

)

M

M

0

(5

CH

IN

2

(15

H

CH

IN

NC

6I

1/2

2-

PRESSURE LOSS (PSI)

25.

M

5M

16

)&

)

MM

MM

00

(2

H

NC

8I

50

(1

H

NC

6I

MM

76

&

M)

M)

)

M

M

5M

(6

0M

00

(8

(1

H

CH

IN

CH

NC

IN

3I

4

1/2

2-

MM)

H (50

2 INC

ing of the valve handle to the ON position. As an alternative to the Model B Hydraulic Manual Emergency Station, the

Model A Hydraulic Manual Emergency Pull Box (see Bulletin

506) is also available and can be provided as an option.

Model F1-FTR fixed temperature pilot line detectors and spacing requirements are described in Bulletin 180.

Maintenance

Reliable Single Interlock Preaction Systems and associated equipment shall periodically be given a thorough inspection and test. NFPA 25, Inspection, Testing and Maintenance of Water Based Fire Protection Systems, provides minimum maintenance requirements. System components shall be tested, operated, cleaned, and inspected at least annually, and parts replaced as required.

Wet Pilot Line Single Interlock Preaction Trim

Wet pilot line single interlock preaction trim operation is a simple method of Deluge Valve Actuation. The trim contains components such as a one and one quarter main drain on

2” (50 mm), 2½” (65 mm), 76 mm and 3” (80 mm) valve sizes or a two inch main drain on 4” (100 mm), 165 mm,

6” (150 mm) and 8” (200 mm) valve sizes, alarm test, supply and push rod chamber pressure gauges, and push rod chamber connections. The wet pilot line consists of a line of closed detectors (Model F1-FTR) located over the area to be protected. This line contains water under pressure and is connected to the outlet of the push rod chamber of the Deluge Valve. When one of the pilot line detectors actuates, the push rod chamber is vented and the Deluge Valve operates.

The Deluge Valve can also be operated manually by opening the ball valve of the Model B Hydraulic Manual Emergency Station (see Fig. 12) or the optional Model A Hydraulic

Manual Emergency Pull Box (see Reliable Bulletin 506).

The wet pilot line is only a detection system and does not contribute to controlling the fire. Its installation is subject to the following restrictions: a) It is not to be installed in an area subject to freezing.

b) It is not to be installed in an area where temperatures in excess of 150°F (65°C) are anticipated.

c) NFPA 72 or the authority having jurisdiction should be consulted for spacing and elevation requirements.

d) Maximum wet pilot line length and height must comply with data provided in Fig. 2.

Wet Pilot Trim installation on Model DDX Deluge Valves uses eight tapped openings for trim connections. Each opening and its function are indicated on Fig. 3 or Fig. 4.

Using Fig. 3 or Fig. 4 as reference, the recommended trim installation is as follows:

1. Install ½” nipple (#35, Fig. 3 or #37, Fig. 4) in the tapped opening marked “TEST”. Note: If interference occurs between the supply gauge and the control valve, the

1/4” plug (#52, Fig. 3 or #52, Fig. 4) in the opening marked “SUPPLY” may be swapped with: the 1/4” nipple (#33, Fig. 3), angle valve (#9, Fig. 3) and gauge

(#67, Fig. 3) for the 2” (50mm), 2-1/2” (65mm), 76mm and 3” (80mm) valve sizes; 1/4” nipple (#32, Fig. 4),

1/4” elbow (#23, Fig. 4), 1/4” nipple (#33, Fig. 4), 3-way valve (#64, Fig. 4) and the gauge (#66, Fig. 4) for the

4” (100mm), 165mm and 6” (150mm) valve sizes;

1/4” nipple (#33, Fig. 4), 3-way valve (#64, Fig. 4) and the gauge (#66, Fig. 4) for the 8” (200mm) valve size, in the trim installed in the opening marked “TEST”.

2. Install ½” nipple (#38, Fig. 3 or #34, Fig. 4) in the tapped opening marked “ALARM” and connect balance of this trim line.

3. Install ¼” plug (#52, Fig. 3 or #52, Fig. 4) in the tapped opening marked “SUPPLY.” Note: If interference oc- curs between the supply gauge and the control valve, the 1/4” plug (#52, Fig. 3 or #52, Fig. 4) in the opening marked “SUPPLY” may be swapped with: the 1/4” nipple (#33, Fig. 3), angle valve (#9, Fig. 3) and gauge (#67, Fig. 3) for the 2” (50mm), 2-1/2”

(65mm), 76mm and 3” (80mm) valve sizes; 1/4” nipple (#32, Fig. 4), 1/4” elbow (#23, Fig. 4), 1/4” nipple

(#33, Fig. 4), 3-way valve (#64, Fig. 4) and the gauge

(#66, Fig. 4) for the 4” (100mm), 165mm and 6”

(150mm) valve sizes; 1/4” nipple (#33, Fig. 4), 3-way valve (#64, Fig. 4) and the gauge (#66, Fig. 4) for the

8” (200mm) valve size, in the trim installed in the opening marked “TEST”.

4. Install ½” nipple (#34, Fig. 3 or #34, Fig. 4) in the tapped opening marked “OUT” and connect balance of this trim line.

5. Install ¼” inline check valve (#15, Fig. 3 or #14, Fig. 4) in the tapped opening marked “IN” and connect balance of this trim line. Caution: Over tightening check valve can cause a restriction in flow that may prevent the valve from “setting up”.

6. Install 1¼” Nipple (#44, Fig. 3) or 2” nipple (#44, Fig.

4) in the tapped drain opening and connect balance of this trim line.

7. Install ¾ x ¼ reducing coupling (#48, Fig. 3 or #48, Fig.

4) in the lower-most tapped opening at the rear of the

Deluge Valve and connect the balance of this trim line.

8. Install ¾” nipple (#40, Fig. 3 or #39, Fig. 4) in the uppermost tapped opening at the rear of the Deluge Valve and connect the balance of this trim line.

26.

Electric Actuation Single Interlock Preaction

Trim

Electric Actuation trim (see Figures 5 and 6) combines a normally closed/powered-open solenoid valve with the Wet

Pilot Line Single Interlock Preaction Trim for releasing the

Deluge Valve. The solenoid valve used in the assembly is available in either a 175 psi (12,1 bar) or 300 psi (20,7 bar) rating.

Note:

In order for the solenoid valve to maintain Reliable’s warranty it must remain sealed as it came from the factory. If there are concerns about the valve’s internal components, immediate replacement is recommended.

Electric Actuation Trim installation on Model DDX Deluge

Valves uses eight tapped openings for trim connections.

Each opening and its function are indicated on Fig. 5 or Fig.

6. Using Fig. 5 or Fig. 6 as reference, the recommended trim installation is as follows:

1. Install ½” nipple (#37, Fig. 5 or #39, Fig. 6) in tapped opening marked “TEST.” Note: If interference occurs between the supply gauge and the control valve, the 1/4” plug (#54, Fig. 5 or #54, Fig. 6) in the opening marked “SUPPLY” may be swapped with: the

1/4” nipple (#35, Fig. 5), angle valve (#10, Fig. 5) and gauge (#69, Fig. 5) for the 2” (50mm), 2-1/2” (65mm),

76mm and 3” (80mm) valve sizes; 1/4” nipple (#34,

Fig. 6), 1/4” elbow (#25, Fig. 6), 1/4” nipple (#35,

Fig. 6), 3-way valve (#66, Fig. 6) and the gauge (#68,

Fig. 6) for the 4” (100mm), 165mm and 6” (150mm) valve sizes; 1/4” nipple (#35, Fig. 6), 3-way valve

(#66, Fig. 6) and the gauge (#68, Fig. 6) for the 8”

(200mm) valve size, in the trim installed in the opening marked “TEST”.

2. Install ½” nipple (#40, Fig. 5 or #36, Fig. 6) in tapped opening marked “ALARM” and connect balance of this trim line.

3. Install ¼” plug (#54, Fig. 5 or #54, Fig. 6) in tapped opening marked “SUPPLY.” Note: If interference occurs be- tween the supply gauge and the control valve, the

1/4” plug (#54, Fig. 5 or #54, Fig. 6) in the opening marked “SUPPLY” may be swapped with: the 1/4” nipple (#35, Fig. 5), angle valve (#10, Fig. 5) and gauge (#69, Fig. 5) for the 2” (50mm), 2-1/2” (65mm),

76mm and 3” (80mm) valve sizes; 1/4” nipple (#34,

Fig. 6), 1/4” elbow (#25, Fig. 6), 1/4” nipple (#35, Fig.

6), 3-way valve (#66, Fig. 6) and the gauge (#68, Fig.

6) for the 4” (100mm), 165mm and 6” (150mm) valve sizes; 1/4” nipple (#35, Fig. 6), 3-way valve (#66, Fig.

6) and the gauge (#68, Fig. 6) for the 8” (200mm) valve size, in the trim installed in the opening marked.

4. Install ½” nipple (#36, Fig. 5 or #36, Fig. 6) in tapped opening marked “OUT” and connect balance of this trim line.

5. Install ¼” inline check valve (#16, Fig. 5 or #15, Fig. 6) in tapped opening marked “IN” and connect balance of this trim line. Supply line must be connected to the inlet of the control valve for each Deluge Valve as shown.

Caution: Over tightening check valve can cause a restriction in flow that may prevent the valve from “setting up”.

6. Install 1¼” Nipple (#46, Fig. 5) or 2” nipple (#46, Fig. 6) in tapped drain opening and connect balance of this trim line.

7. Install ¾” x ¼” reducing bushing (#50, Fig. 5 or #50, Fig.

6) in the lower-most tapped opening at the rear of the

Deluge Valve and connect the balance of this trim line.

8. Install ¾” nipple (#42, Fig. 5 or #41, Fig. 6) in the uppermost tapped opening at the rear of the Deluge Valve and connect the balance of this trim line.

Dry Pilot Line Single Interlock Preaction Trim

Dry pilot line single interlock preaction trim is used in water sensitive areas which are subject to freezing conditions or to obtain installed sprinkler heights and pipe lengths greater than allowed for wet pilot line trim.

Dry pilot operation uses a pilot line of closed sprinklers

(Model F1-FTR) containing air under pressure located in the

27.

area to be protected. This pressurized line is connected to a

Model LP Dry Pilot Line Actuator. The dry pilot line actuator functions very much like a miniature dry pipe valve. In areas where moisture-laden air could cause freezing or other problems in the dry pilot line, the use of a cylinder of dry compressed gas such as nitrogen is suggested. Approved gas handling regulators and connections are then recommended. When one of the closed sprinklers on the dry pilot line actuates, the air pressure is reduced, thus opening the

Model LP Dry Pilot Line Actuator, which releases the Deluge

Valve. NFPA 72 or the Authority Having Jurisdiction should be consulted for spacing and elevation requirements of the pilot line sprinklers.

The Dry Pilot Line Trim, shown in Figures 7 and 8, includes gauges to read the air and water pressure, a low air pressure switch, a pressure relief valve, a Model LP Dry Pilot Line

Actuator, and connections for the dry pilot line of detectors.

Dry Pilot Line Trim installation on Model DDX Deluge Valves uses eight tapped openings for trim connections. Each opening and its function are indicated on Fig. 7 and Fig. 8.

Using Fig. 7 and Fig. 8 as reference, the recommended trim installation is as follows:

1. Install ½” nipple (#39, Fig. 7 or #41, Fig. 8) in tapped opening marked “TEST”. Note: If interference occurs between the supply gauge and the control valve, the 1/4” plug

(#58, Fig. 7 or #58, Fig. 8) in the opening marked “SUP-

PLY” may be swapped with: the 1/4” nipple (#37, Fig. 7), angle valve (#11, Fig. 7) and gauge (#73, Fig. 7) for the

2” (50mm), 2-1/2” (65mm), 76mm and 3” (80mm) valve sizes; 1/4” nipple (#36, Fig. 8), 1/4” elbow (#27, Fig. 8),

1/4” nipple (#37, Fig. 8), 3-way valve (#70, Fig. 8) and the gauge (#72, Fig. 8) for the 4” (100mm), 165mm and

6” (150mm) valve sizes; 1/4” nipple (#37, Fig. 8), 3-way valve (#70, Fig. 8) and the gauge (#72, Fig. 8) for the 8”

(200mm) valve size, in the trim installed in the opening marked “TEST”.

2. Install ½” nipple (#42, Fig. 7 or #38, Fig. 8) in tapped opening marked “ALARM” and connect balance of this trim line.

3. Install ¼” plug (#58, Fig. 7 or #58, Fig. 8) in tapped opening marked “SUPPLY.” Note: If interference occurs between the supply gauge and the control valve, the 1/4” plug

(#58, Fig. 7 or #58, Fig. 8) in the opening marked “SUP-

PLY” may be swapped with: the 1/4” nipple (#37, Fig. 7), angle valve (#11, Fig. 7) and gauge (#73, Fig. 7) for the

2” (50mm), 2-1/2” (65mm), 76mm and 3” (80mm) valve sizes; 1/4” nipple (#36, Fig. 8), 1/4” elbow (#27, Fig. 8),

1/4” nipple (#37, Fig. 8), 3-way valve (#70, Fig. 8) and the gauge (#72, Fig. 8) for the 4” (100mm), 165mm and

6” (150mm) valve sizes; 1/4” nipple (#37, Fig. 8), 3-way valve (#70, Fig. 8) and the gauge (#72, Fig. 8) for the 8”

(200mm) valve size, in the trim installed in the opening marked “TEST”.

4. Install ½” nipple (#38, Fig. 7 or #38, Fig. 8) in tapped opening marked “OUT” and connect balance of this trim line.

5. Install ¼” inline check valve (#17, Fig. 7 or #16, Fig. 8) in tapped opening marked “IN” and connect balance of this trim line. Caution: Over tightening check valve can cause a restriction in flow that may prevent the valve from “setting up”.

6. Install 1¼” Nipple (#48, Fig. 7) or 2” nipple (#48, Fig. 8) in tapped drain opening and connect balance of this trim line.

7. Install ¾” x ¼” reducing bushing (#53, Fig. 7 or #53, Fig. 8) in the lower-most tapped opening at the rear of the Deluge

Valve and connect the balance of this trim line.

8. Install ¾” nipple (#44, Fig. 7 or #43, Fig. 8) in the uppermost tapped opening at the rear of the Deluge Valve and connect the balance of this trim line.

Connect the air supply to the air inlet side of the Model LP

Dry Pilot Line Actuator as shown in Fig. 7 or Fig. 8. Table

A specifies the air pressure to be used in a dry pilot line.

The level of air pressure is adjusted by removing the cap nut on the end of the Relief Valve (#56, Fig. 7 or #56, Fig. 8) and turning the now exposed slotted adjusting screw clockwise to increase pressure or counterclockwise to reduce it.

Replace the cap nut after the correct pressure setting has been made at 5 psi above the maximum pilot line pressure required by Table A. An appropriate automatic pressure maintenance device must be used to safeguard against the

Deluge Valve tripping due to air pressure leaks in the dry pilot line. See Bulletin 254 for pressure maintenance device information.

Install the dry pilot line as required. Wire the low air pressure switch (#5, Fig. 7 or #5, Fig. 8) to an annunciating device or control panel. This low air pressure switch should be set to open at an air pressure which is slightly lower than the

“Not Less Than” values found in Table A.

Table A

Water Pressure psi (bar)

Maximum

20 (1.4)

30 (2.1)

50 (3.4)

75 (5.2)

100 (6.9)

125 (8.6)

150 (10.3)

175 (12.1)

200 (13.8)

225 (15.5)

250 (17.2)

275 (19.0)

300 (20.7)

Pneumatic Pressure to be

Pumped into Sprinkler System psi (bar)

Not Les Than Not More Than

8 (0.6)

10 (0.7)

12 (0.8)

13 (0.9)

15 (1.0)

16 (1.1)

17 (1.2)

18 (1.2)

19 (1.3)

21 (1.4)

22 (1.5)

23 (1.6)

24 (1.7)

10 (0.7)

14 (1.0)

16 (1.1)

17 (1.2)

19 (1.3)

20 (1.4)

21 (1.4)

22 (1.5)

23 (1.6)

25 (1.7)

26 (1.8)

27 (1.9)

28 (1.9)

Note: During system set-up, a higher pneumatic pressure may be required in order to properly set the Model LP Dry

Pilot Line Actuator.

8

9

10

4

5

6

7

2

3

Model LP Dry Pilot Line Actuator Parts List

P/N 71030010

Item

No.

1

Part No.

Description

94106936 Lower Housing

Qty.

Required

1

94106935 Upper Housing

96006905 Seat

92206311 Diaphragm

95106911 Facing Plate Assembly

96906311 Diaphragm Washer

94906406 Facing Plate Nut

95406901 Seat O-Ring

95606305 Bolt

96406902 Compression Spring

28.

Maintenance – Model LP Dry Pilot Line Actuator

Refer to Figs. 11 & 15

If water constantly flows through the Model LP Dry Pilot

Line Actuator and into the drain, there is a leak in the seal of the Actuator’s seat.

1. Close the main valve controlling water supply (Fig. 15) to the Dry Pipe Valve and close off the air/nitrogen supply to the sprinkler system. Close valve A (Fig. 15).

2. Drop pressure in the system by opening the ¼” globe valve, valve E (Fig. 15), and remove the Actuator from the system.

3. Remove all six bolts (#9, Fig. 11) holding the Actuator together. Clean or replace the facing plate assembly (#5, Fig.

11) and seat (#3, Fig. 11).

4. Reassemble the Actuator, using a torque of 8 ft-lbs on the facing plate nut (#7, Fig. 11) and 12 ft-lbs on the six bolts

(#9, Fig. 11). Use a cross-tightening pattern. Reinstall the

Actuator. Set up the Model DDX Deluge Valve as per the section “Resetting Model DDX Deluge Valve System”.

Resetting Model DDX Deluge Valve Single

Interlock Preaction Systems

Refer to Figs. 7, 8, 13, 14 & 15.

1. Close the valve controlling water supply (Fig. 15) to the

Deluge Valve and close off the air supply to the sprinkler system.

2. Close the pushrod chamber supply valve, valve A (Fig. 15).

3. Open main drain valve B (Fig. 15) and drain system.

4. Open all drain valves and vents at low points throughout the system, closing them when flow of water has stopped.

Open valve D (Fig. 15). Note: The above steps accomplish the relieving of pressure in the pushrod chamber of the Deluge Valve.

5. With valve F (Fig. 15) open, push in the plunger of ball drip valve G (Fig. 15), forcing the ball from its seat, and drain the alarm line.

6. With the Model B Manual Emergency Station, valve D (Fig.

15) open, push in and rotate the Deluge Valve’s external reset knob (#14, Fig. 13 or #38, Fig. 14) clockwise, until you hear a distinct noise indicating that the clapper has reset.

Note: The reset knob can be rotated only while pressure in the pushrod chamber is vented to atmospheric conditions

(0 psig).

1

6

1

1

1

1

1

1

1

Fig. 11

Fig. 12

29.

7. Inspect and replace any portion of the detection system and/or sprinkler system subjected to fire conditions.

8. Open valve A (Fig. 15) and allow water to fill the push rod chamber. Close valve D (Fig. 15).

9. Bleed all air from the actuation piping.

A. Wet Pilot Line Single Interlock Preaction Trim—bleed the entire wet pilot line until all air is removed at the most remote sprinkler.

B. Electric Actuation Single Interlock Preaction Trim— open the solenoid valve by operating a detector or an electric manual emergency station. While water is flowing through the solenoid valve, cause it to close using the release control panel reset.

C. Dry Pilot Line Single Interlock Preaction Trim—open valve D (Fig. 15) allowing water to flow through the pilot line actuator. When all air has been expelled from the release line, and there is a solid flow of water into the drain cup H (Fig. 15), apply compressed air or nitrogen through the pressure maintenance device to close the pilot line actuator. Subsequently, close valve

D (Fig. 15) or (#7, Fig. 7 or #7, Fig. 8) and adjust the air or nitrogen pressure to the appropriate value in

Table A as indicated on air pressure gauge (#72, Fig.

7 or #71, Fig. 8).

10. Close valve F (Fig. 15). Open the valve to restore air pressure in the sprinkler system. Note: To build supervisory air pressure in the sprinkler system, it may be necessary to temporarily close the main drain valve, valve

B until air pressure has built up to the manufacturers recommended levels.

11. Open valve F (Fig. 15). Verify the main drain valve, valve

B is open. Open slightly the main valve controlling water supply (Fig. 15) to the Model DDX Deluge Valve, closing drain valve B (Fig. 15) when water flows. Observe if water leaks through the ball drip valve, valve G (Fig. 15), into the drip cup, H (Fig. 15). If no leak occurs, the Deluge Valve’s clapper is sealed. Open slowly and verify the main valve controlling water supply is fully opened and properly monitored.

12. Verify that valve A (Fig. 15) and valve F (Fig. 15) are open.

Valve A (Fig. 15) must remain open when the Deluge

Valve has been reset, to maintain water pressure in the push rod chamber.

13. Verify that the Model B Manual Emergency Station, valve D

(Fig. 15) is secured in the OFF position with the appropriate nylon tie (#57, Fig. 7 or #57, Fig. 8) see Fig. 12.

Inspection and Testing

Refer to Figs. 13, 14 & 15.

1. Water supply — be sure the valves controlling water supply to the Deluge Valve are opened fully and properly monitored.

2. Alarm line — be sure that valve F (Fig. 15) is opened and remains in this position.

3. Other trimming valves — check that valve A (Fig. 15) is open, as well as all of the pressure gauge’s ¼“ 3-way valves. Valves D, E & J (Fig. 15) should be closed.

4. Ball drip valve G (Fig. 15) — Make sure valve F (Fig. 15) is open. Push in on the plunger to be sure ball check is off its seat. If no water appears, the Deluge Valve’s water seat is tight. Inspect the bleed hole (see Fig. 13 or Fig. 14) on the underside of the push rod chamber for leakage.

5. Dry pilot trim — check air gauge pressure for conformance to Table A.

6. Wet pilot and Electric Actuation trim — check that system air pressure is approximately 7 psi (0,5 bar). Check the pressure maintenance device for leakage and proper pressure.

7. Releasing device — check outlet of the releasing device

(i.e., the dry pilot line actuator, solenoid valve, or the hydraulic manual emergency station) for leakage. Also verify that tubing drain lines from releasing devices are not pinched or crushed which could prevent proper releasing of the Deluge Valve.

8. Testing alarms — Make sure valve F (Fig. 15) is open.

Open valve J (Fig. 15) permitting water from the supply to flow to the electric sprinkler alarm switch and to the mechanical sprinkler alarm (water motor). After testing, close this valve securely. Push in on the plunger of ball drip valve

G (Fig. 15) until all of the water has drained from the alarm line.

9. Operation test — Open the Model B Manual Emergency

Station, valve D (Fig. 15).

Note: An operational test will cause the Deluge Valve to open and flow water into the sprinkler system.

10. Secure the Model B Manual Emergency Station, valve D

(Fig. 15), in the OFF position with nylon tie after Deluge

Valve is reset (see Fig. 12).

Testing Detection System Without Operating

Deluge Valve

Refer to Figs. 7, 8 & 15.

1. Close the valve controlling water supply to Deluge Valve and open the main drain valve B (Fig. 15).

2. Verify that valve A (Fig. 15) is open, allowing water to enter the push rod chamber.

3. Operate detection system —

A. Wet Pilot Line Single Interlock Preaction Trim—open

Model B Manual Emergency Station, valve D (Fig.

15).

B. Dry Pilot Line Single Interlock Preaction Trim—directly above the Model LP Dry Pilot Line Actuator, remove the ¼” pipe plug (#58, Fig. 7 or #58, Fig. 8) and open the ¼” three-way valve (#71, Fig. 7 or #70, Fig. 8) until the Model LP actuator operates. This will be indicated by a sudden drop in water pressure on the Deluge

Valve’s pushrod chamber gauge. The operation of the actuator will vent the pushrod chamber of the Deluge Valve and cause the valve’s clapper to open.

C. Electric Actuation— energize the solenoid valve by operating a detector (or detectors if cross-zoned).

4. Operation of the detection system must result in a sudden drop of water pressure in the push rod chamber.

30.

31.

Model DDX (Screw-In Seat Confi guration) Deluge Valves Parts List (Refer to Fig. 13)

11

12

13

14

15

16

17

18

Item

No.

2"

(50mm)

2½"

(65mm)

76mm

3"

Part No.

(80mm)

4”

(100mm)

165mm

6”

(150mm)

8"

(200mm)

Part Description

91006011 91006012 91006023 91006013 91006005 91006027 91006007 91006028 Valve Body Groove/Groove

1

2

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A 91006045 N/A 91006067 N/A Valve Body Flange/Groove

N/A 91006035 N/A 91006037 91006039 Valve Body Flange/Flange

N/A N/A N/A 95406414 O-ring (Mounting Ring)

3

4

10

19

20

21

22

23

24

25

26

7

8

5

6

9

27

28

29

30

31

32

91106123

N/A

N/A

N/A

91306013

91916013

92116063

93416003

93706003

93722000

N/A

N/A

94506003

95006414

95306267

N/A

N/A

N/A

95306267

N/A

N/A

95406410

95406411

95606133

N/A

96016003

96206003

N/A

96216003

N/A

QTY.

1

Material

Ductile Iron 65-45-12

71040416 Pushrod Cover Assembly

N/A

95606107

N/A

N/A

N/A

N/A

91106006

N/A

N/A

N/A

N/A

95606110

91306014

91916014

91306016

91916016

91306018

91916008

92116064 92116065 92116066 92116068

93416014 93416016 93416008

93706004

93722000

N/A

93706006

N/A

93722000

93706008

N/A

N/A

Hex Bolt ½”-13 x 1¼”

Hex Bolt ½”-13 x 1½”

Hex Bolt 5 /

8

”-11 x 1¾”

Hex Bolt 5 /

8

”-11 x 2”

Mounting Ring

Clapper

Access Cover

Seal Assembly

Access Cover Gasket

Bumpstop Assembly

N/A 93722000 N/A

93916006

93916066

94106066

94356006

94506004

94006412

94506016

95006410

94506008

95006410

Pushrod Guide

Reset Shaft

Reset Housing

Reset Knob

Lever

Striker

95106006

95276006

N/A

95306267

N/A

N/A

N/A

95306267

N/A

95406007

95406024

95406407

95406409

95406420

95506006

95606114

95606127

N/A

95606130

96016014

N/A

96216086

N/A

96216044

N/A

N/A

95306269

N/A

N/A

95306267

N/A

95436126

95446226

N/A

95606130

96016016

N/A

96216068

N/A

96216047

N/A

N/A

N/A

95316408

N/A

N/A

95316408

95406413

95406412

N/A

95606130

96016008

N/A

96206008

N/A

96216008

1

1

6

8

6

6

Buna-N

Ductile Iron 65-45-12

& Brass C360000

Zinc Plated Steel

1 Stainless Steel CF8 or CF8M

1 Stainless Steel CF8 or CF8M

1 Ductile Iron 65-45-12

1 Stainless Steel 304 & EPDM

1

1

Buna-N or Neoprene

2

Stainless Steel UNS S31600

& EPDM

3

1

1

1

Acetal

Brass UNS C36000

1

Brass UNS C36000

Aluminum 6061

1 Stainless Steel UNS S17400

1 Aluminum Bronze C95400

Piston 1 Stainless Steel CF8M

Diaphragm

Retaining Ring, 3 /

8

Lever Pin

" Shaft,

Retaining Ring, ½” Shaft,

Lever Pin

Retaining Ring, 5 /

8

Lever Pin

” Shaft,

Retaining Ring, ¾” Shaft,

Lever Pin

1

2

Retaining Ring, 3 /

8

Hinge Pin

” Shaft,

Retaining Ring, ½” Shaft,

Hinge Pin

2

Retaining Ring, 3 /

4

Hinge Pin

” Shaft,

O-Ring, Reset Housing ID 1

Stainless Steel 15-7 or 17-7

Buna-N

O-Ring, Reset Housing &

Pushrod Guide OD

2

O-Ring, Pushrod Guide ID 1

EPDM & Polyester

Stainless Steel 15-7 or 17-7

Buna-N

Buna-N

O-Ring, Upper Seat

O-Ring, Lower Seat

1

1

Buna-N

Buna-N

Pushrod

Socket Head Screw, ¼”-20 x 5 /

8

Flat Head Socket Cap Screw

3 /

8

"-16 x ¾"

Socket Head Screw #6-32 x ½"

Socket Head Screw #10-32 x 1"

Seat

1 Stainless Steel UNS S30300

6

1

1

1

Steel

Steel

Stainless Steel 18-8

Stainless Steel UNS S31600

Hinge Pin

Lever Pin

1

1

Stainless Steel CF8M

Stainless Steel UNS S30400

Stainless Steel UNS S21800

Stainless Steel UNS S17400

Stainless Steel UNS S21800

32.

Model DDX (Screw-In Seat Confi guration) Deluge Valves Parts List (Refer to Fig. 13)

(Continued)

Item

No.

2"

(50mm)

33

34

35

36

37

2½"

(65mm)

76mm

96310003

96406003

N/A

96906112

N/A

95606140

N/A

N/A

3"

Part No.

4”

(80mm) (100mm)

96906904

N/A

96406004

96406906

N/A

96906111

N/A

95606139

N/A

165mm

6”

(150mm)

96906904

N/A

96406005

N/A

96906111

N/A

N/A

N/A

8"

(200mm)

96310008

N/A

96406008

Part Description

Clapper Spacer

Lever Spring

Piston/ Reset Spring

N/A Spring Lock Washer, #6

96906111 Spring Lock Washer, #10

N/A

N/A

Flat Head Socket Cap Screw

¼”-20 x ½”

95606135

Flat Head Socket Cap Screw

½"-13 x ¾"

QTY.

Material

2

1

Teflon or Acetal

Stainless Steel UNS S30400

Stainless Steel UNS S31600

2 Stainless Steel UNS S31600

1

2

Stainless Steel 18-8

Stainless Steel UNS S31600

Stainless Steel 18-8

Stainless Steel UNS S31600

Stainless Steel UNS S31600

38 98604402 Steel

39

40

41

42

94616921

91556922

91556923

699993406

Plug, ½” NPT

Knob Caution Label (Not

Shown)

Ball Chain, 1/8" (Not Shown)

(Length is in Inches)

Clamping Link, Ball Chain

(Not Shown)

O-Ring Grease, Dupont tm

Krytox ® GPL-205

1

1

6

1

A/R

Polystyrene

Nickel Plated Brass

Krytox ®

Fig. 14

33.

37

38

39

34

35

36

40

41

29

30

31

32

33

26

27

28

20

21

22

17

18

19

23

24

12

13 93706001

14

15

16

25

95606107

N/A

Model DDX (Drop-In Seat Confi guration) Deluge Valves Parts List (Refer to Fig. 14)

Item

No.

6

7

4

5

1

2

3

8

9

10

Part No.

4"

(100mm)

165mm

6"

(150mm)

91006005 91006027

96016004

91006007

96016006

Valve Body

Seat

91916004 91916006 Clapper

92116064 92116065

93416004

92116066

93416006

Access Cover

Seal Assembly

93706004

94506004

93706006

94506006

Access Cover Gasket

Lever

11 95406006

71040416

95406407

95406007

95406016

95406024

93706002

96216086

96216046

95606131

96216066

95106006

95200038

95506006

93916006

95306267

95606128

95606129

N/A

91106006

96906111

95606127

95606130

95606136

93916066

96406004

96406906

96906904

95276006

92306006

94106066

94356006

6999993406

94616921

91556922

91556923

Part Description

Pushrod Cover Assembly

O-Ring, Pushrod Guide ID

O-Ring, Reset Housing ID

O-Ring, Upper Seat

O-Ring, Lower Seat

O-Ring, Reset Housing OD

Clapper Gasket

Hinge Pin

Lever Pin

Threaded Stud, #10-32 x ¾"

Locking Pin (not shown)

Piston

Socket Plug 3 /

8

” - 18 NPT (not shown)

Pushrod

Pushrod Guide

Retaining Ring, 1/2" Shaft

Button Head Screw #10-32 x 3 /

8

"

Hex Washer Head Screw #10-32 x 3 /

8

"

Hex Cap Screw ½"-13 x 1½"

Hex Cap Screw 5 /

8

"-11 x 1¾"

Spring Lock Washer, #10

Flat Head Socket Cap Screw 3 /

8

"-16 x ¾"

Socket Head Screw #10-32 x 1"

Socket Head Screw, ¼"-20 x 5 /

8

"

Reset Shaft

Lever Spring

Piston/ Reset Spring

Clapper Spacer

Diaphragm

Bumper Disc

Reset Housing

Reset Knob

O-Ring Grease, Dupont tm Krytox ® GPL-205

Knob Caution Label (Not Shown)

Ball Chain, 1/8" (Not Shown) (Length is in Inches)

Clamping Link, Ball Chain (Not Shown)

QTY.

1

1

1

2

6

6

1

1

2

3

1

1

1

1

A/R

1

6

1

1

1

1

1

1

1

1

1

1

1

1

1

3

1

4

2

1

2

2

1

1

1

1

Material

Ductile Iron 65-45-12

Brass UNS C86300

Brass UNS C86300

Ductile Iron 65-45-12

Stainless Steel 304 & EPDM

Buna-N or Neoprene

Stainless Steel UNS S17400

Ductile Iron 65-45-12 & Brass

UNS C36000

Buna-N

Buna-N

Buna-N

Buna-N

Buna-N

Buna-N or Neoprene

Stainless Steel UNS S21800

Stainless Steel UNS S44000

Stainless Steel 18-8

Stainless Steel UNS S44000

Stainless Steel CF8M

Steel

Stainless Steel UNS S30300

Acetal

Stainless Steel 15-7 or 17-7

Stainless Steel 18-8

Zinc Plated Steel

Stainless Steel UNS S31600

Steel

Stainless Steel UNS S31600

Steel

Brass UNS C36000

Stainless Steel UNS S30400

Stainless Steel UNS S31600

Teflon

EPDM & Polyester

SBR Rubber

Brass UNS C36000

Aluminum 6061

Krytox ®

Polystyrene

Nickel Plated Brass

34.

5. Reset detection system — reverse operations performed in step three above and then proceed according to the directions listed in the “Resetting Model DDX Deluge Valve

Single Interlock Preaction Systems” section of this bulletin for resetting the Deluge Valve.

Draining Excess/Condensate Water From

System

Refer to Fig. 15

1. Close the main valve controlling water supply to Deluge

Valve. Also close valve A and open main drain valve B.

2. Open condensate drain valve E until all water has drained.

Close valve E. Note: Be sure not to keep valve E open for an extended period of time because that will cause enough system air to bleed off thereby causing an undesirable activation of a trouble-annunciating device.

3. Close main drain valve B. If system contains pressurized air, allow air pressure to come back up to specification.

Open valve A first, and then open the main valve controlling the water supply to the Deluge Valve.

Maintenance Procedures - Model DDX Deluge

Valve

Refer to Figs. 7, 8, 13, 14 & 15.

5. Mechanical sprinkler alarm (water motor–not shown)

not operating: This is most likely caused by a clogged screen in the strainer of the water motor. Proceed as follows: Remove plug from the strainer. Remove and clean the screen. Replace the screen and the plug, and then tighten securely (Ref. Bulletin 613).

6. Leakage out of the ball drip valve G (Fig. 15).

a. Water leakage due to water column in deluge systems:

This condition can be caused by leakage past the system side of the Model DDX Deluge Valve’s seal assembly

(#8, Fig. 13 or #5, Fig. 14). Be sure that this surface is free of any type of debris. To eliminate leakage due to water column in a deluge system, refer to the section in this bulletin marked “Draining Excess/Condensate Water

From System”. If the problem continues proceed to the following section.

b. Leakage, air or water from the ball drip valve,

G (Fig. 15):

If system air is leaking out the ball drip valve, the problem is either damage to the airside of the Model DDX Deluge

Valve’s seal assembly (#8, Fig. 13 or #5, Fig. 14), seat

(#29, Fig. 13 or #2, Fig. 14), the upper seat o-ring (#23,

Fig. 13 or #11, Fig. 14) or, on the 8” (200 mm) valve size only, the mounting ring o-ring (#2, Fig. 13). If supply water is leaking out the ball drip valve, the problem could be caused by damage to the Model DDX Deluge Valve’s seal assembly (#8, Fig. 13 or #5, Fig. 14), seat (#29, Fig.

13 or #2, Fig. 14), or lower seat O-ring (#24, Fig. 13 or

#11, Fig. 14). The following section provides instructions to correct both conditions:

A) Shut down the valve controlling the water supply to the Deluge Valve and open the

1¼” main drain valve on the 2” (50mm), 2½”

(65mm), 76mm and 3” (80mm) valve sizes or the 2” main drain valve on the 4” (100mm),

165mm, 6” (150mm) and 8” (200mm) valve sizes, valve B (Fig. 15). Open the water column drain valve E (Fig. 15). Close the pushrod chamber supply valve A (Fig. 15) and open the Model B Manual Emergency Station, valve D (Fig. 15).

B) Remove the Deluge Valve’s front (handhold) cover (#7, Fig. 13 or #4, Fig. 14) and inspect the seat (#29, Fig. 13 or #2, Fig. 14), clapper

(#6, Fig. 13 or #3, Fig. 14), and seal assembly (#8, Fig. 13 or #5, Fig. 14) for damage. If inspection indicates damage to the seal assembly (#8, Fig. 13 or #5, Fig. 14), replace as follows:

For Valve Sizes: 2” (50mm), 2½” (65mm),

76mm, 3” (80mm), 8” (200mm) and 4”

(100mm), 6” (150mm) & 165mm with Screw-In

Seat only, Refer to Fig. 7, Fig. 8 & Fig. 13:

Remove the bumpstop nuts (#10, Fig. 13) and remove the seal assembly (#8, Fig. 13). Install a new seal assembly (#8, Fig. 13) and thread the bumpstop nuts (#10, Fig. 13) onto the threaded studs of the seal assembly (#8, Fig. 13) and tighten finger tight plus ¼ to ½ turn. If inspection indicates damage to the clapper (#6, Fig. 13) only, then the clapper subassembly can be removed as follows:

At the rear of the valve, disconnect the water column drain trim section starting with the elbow connector (#22, Fig. 7 or #21, Fig. 8). Then remove the ¼” globe valve (#33, Fig. 7 or #32,

Fig. 8), followed by the ¾”x¼” reducing bushing

(#53, Fig. 7 or #53, Fig. 8). Remove the retaining ring (condensate drain side for 2” (50mm),

2½” (65mm), 3” (80mm), 76mm and 8” (200mm) valve sizes or hand hole cover side for 4”

(100mm), 6” (150mm) and 165mm valve sizes) from the clapper hinge pin (#30, Fig. 13) and push this pin through the hand hole opening for

2” (50mm), 2½” (65mm), 3” (80mm), 76mm and

8” (200mm) valve sizes or condensate drain side for 4” (100mm), 6” (150mm) and 165mm valve sizes and remove the clapper subassembly. Replace the seal assembly as described previously.

Inspect the clapper (#6, Fig. 13) visually before reinstalling. Reinstall in the reverse order making sure the clapper spacers are in their proper position. If the seat (#29, Fig. 13) is damaged or it is suspected that the leakage is through the lower

O-ring (#24, Fig. 13), the seat-clapper subassembly is easily removed as a unit as follows:

35.

Using Reliable P/N 6881603000 Seat Wrench for

2” (50mm), 2½” (65mm), 76mm and 3” (80mm) valve sizes, Reliable P/N 6881604000 for 4”

(100mm) valve size, Reliable P/N 6881606000 for the 6” (150mm) and 165mm valve sizes or

Reliable P/N 6881608000 Seat Wrench for 8”

(200mm) valve size, remove the seat by unscrewing. This will loosen the seat-clappermounting ring subassembly. Reach into the valve and grasp the seat and remove it from the valve. Then remove the clapper-mounting ring subassembly from the valve. Visually examine all components of the seat-clapper-mounting ring subassembly replacing any component that appears damaged. New O-rings (#23 & #24, Fig.

13 and #2, Fig. 13 (8” (200mm) valve size only)) should always be used for reassembly.

For Valve Sizes: 4” (100mm), 165mm, 6”

(150mm) with Drop-In Seat Confi guration only, Refer to Fig. 8 and Fig. 14:

At the rear of the valve, disconnect the water column drain trim section starting with the elbow connector (#21, Fig. 8). Then remove the

¼” globe valve (#32, Fig. 8), followed by the

¾”x¼” reducing bushing (#53, Fig. 8). Remove the retaining ring (hand hole cover side) from the clapper hinge pin (#14, Fig. 14) and push this pin through the condensate drain port and remove the clapper subassembly. Remove the four retaining screws (#24, Fig. 14) holding the seal faceplate assembly (#5, Fig. 14). Inspect the clapper (#3, Fig. 14) visually before installing.

Apply a small amount of silicone based lubricant to the four retaining screws. Install a new seal faceplate assembly. Torque the retaining screws to approximately 40 inch-pounds and reassemble. If the seat (#2, Fig. 14) is damaged or it is suspected that the leakage is through the lower o-ring (#11, Fig. 14), the seat-clapper subassembly is easily removed as a unit as follows:

Using a 5/16” Allen wrench, remove the two 3/8”

NPT pipe plugs (#19, (not shown) Fig. 14) located on the side chamber side of the Model DDX deluge valve. The seat-clapper subassembly is retained by two locking pins (#17, (not shown)

Fig. 14). The centers of these pins have a ¼”-20 threaded hole. Remove the two locking pins by engaging them with a ¼”-20 screw and pulling them out (the two locking pins are not externally threaded, so turning them with the attached ¼”-

20 screw or threaded rod is not recommended. A proven method is to use ¼”-20 threaded rod with a locknut on the unassembled end. Grab hold of the locknut with a pliers or vise-grips and tap the pliers or vise-grips in the direction away from the

Deluge Valve. Doing so should pull the locking pins out of the Deluge Valve. With the clapper

(#3, Fig. 14) in the closed position (not latched), dislodge the clapper-seat subassembly from the

36.

valve body by inserting two slotted screwdrivers under the lever and clapper mounting ears and pry up until the clapper-seat subassembly is free from its bore. Reach into the valve and grasp the clapper-seat subassembly from the sides.

Making sure the clapper is in the closed position

(see Fig. 1), lift up and rotate the clapper-seat sub assembly clockwise 90 degrees so that the lever side of the assembly is facing up towards the outlet of the deluge valve. Next, rotate the clapper-seat sub assembly 90 degrees about the centerline of the valve so that the clapper is facing the hand hole opening and the lever is still facing the outlet of the deluge valve. Then rotate the clapper-seat sub assembly 90 degrees, so that the clapper is now facing the outlet of the deluge valve and the lever is now facing the back of the valve. Pull the clapper-seat sub assembly out through the hand hole opening by the hinge pin side. Rotating the seat-clapper subassembly up as it is being removed will help it slide out more easily since the lever will prohibit it from sliding straight out. Visually examine all components of the clapper-seat subassembly replacing any component that appears damaged. New orings (#11, Fig. 14) should always be used for reassembly.

Reassembly

:

For Valve Sizes: 2” (50mm), 2½” (65mm),

76mm, 3” (80mm), 8” (200mm) and 4”

(100mm), 6” (150mm) & 165mm with Screw-In

Seat Confi guration only, Refer to Fig. 13:

Clean the bore of the valve body. Lubricate the bore with O-ring grease. Lubricate and install the

O-rings (#23 & #24, Fig. 13) onto the seat. Lubricate and install the mounting ring o-ring (#2, Fig.

13) into the body (8” (200mm) valve size only). Insert the clapper-mounting ring subassembly into the handhold opening of the Deluge Valve using caution to not damage or dislodge the mounting ring o-ring (#2, Fig. 13)(8” (200mm) valve size only). Align the mounting ring so that the Lever

(#15, Fig. 13) is near the pushrod (#25, Fig. 13) and the mounting ring (#5, Fig. 13) “ears” are between the tabs of the valve body (#1, Fig. 13). Insert the seat (#29, Fig. 13) into the valve body (#1,

Fig. 13) and through the clapper-mounting ring subassembly. Start to tread the seat (#29, Fig.

13) into the body by hand, then tighten the seat

(#29, Fig. 12) with Reliable P/N 6881603000 Seat

Wrench for 2” (50mm), 2½” (65mm), 76mm and

3” (80mm) valve sizes, Reliable P/N 6881604000

Seat Wrench for 4” (100mm) valve size, Reliable

P/N 688106000 Seat Wrench for 6” (150mm and

165mm valve sizes or Reliable P/N 6881608000

Seat Wrench for 8” (200mm) valve size until it bottoms out on the mounting ring (#5, Fig. 13).

Verify that the seat-clapper-mounting ring subassembly is in the fully down position between the

tabs of the body, and check to see that the lever

(#15, Fig. 13) lines up with the push rod (#25, Fig.

13). Loosen and reassemble if necessary. Reassemble the handhold cover (#7, Fig. 13) and set up the Model DDX Deluge Valve as per the section “Resetting Model DDX Deluge Valve Single

Interlock Preaction Systems”.

For Valve Sizes: 4” (100mm), 165mm, 6”

(150mm) with Drop-In Seat Confi guration only, Refer to Fig. 14:

It is likely that the lower seat o-ring (#11, Fig. 14) has remained at the bottom of the Deluge Valve body’s bore. Discard this o-ring and clean the bore. Lubricate the bore with o-ring grease and place the lower o-ring on the step at the bottom of the bore, verifying that it is in full contact with the bore. Lubricate the bottom step and upper oring (#11, Fig. 14) of the refurbished clapper-seat subassembly. Insert the clapper-seat sub assembly into the hand hole opening, lever (#7, Fig.

14) first and rotating the clapper-seat subassembly until the lever faces the outlet of the deluge valve. Next rotate the clapper-seat subassembly

90 degrees about the center axis of the valve until the bottom of the clapper-seat sub assembly faces the pushrod (#20, Fig. 14). Then rotate the clapper-seat subassembly 90 degrees counterclockwise so that the clapper (#3, Fig. 14) is facing the outlet of the deluge valve and the lever

(#7, Fig. 14) is facing the pushrod (#20, Fig. 14).

Once the clapper seat subassembly is in this position simply slide the assembly into the bore of the valve, making sure it is straight to avoid binding of the seat in the bore. Slightly twisting the assembly will assist in getting the clapperseat subassembly properly seated. Once it is verified that the clapper-seat sub assembly is in the fully down position and the lever (#7, Fig.

14) is aligned with the pushrod (#20, Fig. 14), clean and lubricate the two locking pins (#17,

(not shown) Fig. 14) with o-ring lubricant. Slide the two locking pins into the deluge valve body to lock the seat in place. Slightly twisting and pressing down on the clapper-seat subassembly will help the pins to slide in more easily. Then reinstall the 3/8” NPT pipe plugs (#19, (not shown)

Fig. 14). Reassemble the hand hole cover (#4,

Fig. 14) and set up the Model DDX Deluge Valve as per the section “Resetting Model DDX Deluge

Valve Single Interlock Preaction Systems”.

7. Leakage out of the push rod chamber vent hole:

A small bleed hole is located on the underside of the push rod chamber (see Fig. 13 or Fig. 14). If there is air or water leakage coming out of this hole, do the following: a) Shut down the valve controlling water supply to the Deluge Valve. Relieve the inlet pressure by opening the 1¼” main drain valve on the 2”

(50mm), 2½” (65mm), 76mm and 3” (80mm) valve sizes or the 2” main drain valve on the 4”

37.

(100mm), 165mm, 6” (150mm) and 8” (200mm) valve sizes, valve B (Fig. 15). Close the valve

A (Fig. 15) that supplies water to the push rod chamber, and open the Model B Manual Emergency Station, valve D (Fig. 15).

b) Remove the trim at the unions nearest to the push rod chamber cover (#3, Fig. 13 or #8 Fig. 14).

c) Take the push rod chamber cover (#3, Fig. 13 or #8, Fig. 14) off by removing the six retaining screws (#26, Fig. 13 or #29, Fig. 14).

CONDITION ONE (Water coming out of the bleed hole):

Water coming out of the bleed hole is caused by a leaking diaphragm (#18, Fig. 13 or #34, Fig. 14). Visually inspect the push rod chamber cover (#3, Fig. 13 or #8,

Fig. 14) and piston (#17, Fig. 13 or #18, Fig. 14) to determine what could have damaged the diaphragm and correct. Install a new diaphragm. NOTE: The diaphragm has two different surfaces; it is not bi-directional. It will fail if installed backwards! Roll the diaphragm so that the smooth surface (the pressure side) conforms to the inside of the push rod chamber cover and reassemble the six retaining screws (#26, Fig. 13 or #29, Fig. 14) with an installation torque of 15 foot-pounds. Set up the Model

DDX Deluge Valve as per the section “Resetting Model

DDX Deluge Valve Single Interlock Preaction Systems”.

CONDITION TWO (System Air coming out of the bleed hole):

System air coming out of the bleed hole is caused by a defective O-ring assembled to the push rod guide (#11,

Fig. 13 or #9, Fig. 14). Remove the piston-push rod subassembly, push rod spring (#34, Fig. 13 or #32, Fig. 14), and push rod guide (#11, Fig. 13 or #21, Fig. 14). Verify by hand turning, that the push rod cannot be unscrewed from the piston. Replace all O-rings and the push rod guide (#21, #22 & #11, Fig. 13 or #9, #12 & #21, Fig. 14).

The correct installation torque for the pushrod guide is 35 inch-pounds. CAUTION: Do not over tighten the push rod guide. Reassemble the components that were initially removed. Re-install the diaphragm (#18, Fig. 13 or

#34, Fig. 14) if it appears to be in good shape, otherwise, replace it also. NOTE: The diaphragm has two different surfaces; it is not bi-directional. It will fail if installed backwards! Roll the diaphragm so that the smooth surface

(the pressure side) conforms to the inside of the push rod chamber cover and reassemble the six retaining screws

(#26, Fig. 13 or #29, Fig. 14) with an installation torque of 15 foot-pounds. Set up the Model DDX Deluge Valve as per the section “Resetting Model DDX Deluge Valve

Single Interlock Preaction Systems”.

Fig. 15

38.

39.

40.

Ordering Information

Specify:

Valve Model & Size

Valve Part Numbers

Valve Size

&

End Connection

2” (50mm) Grv/Grv

2½” (65mm) Grv/Grv

3” (80mm) Grv/Grv

76mm Grv/Grv

4” (100mm) Grv/Grv

4” (100mm) Flg/Grv

4” (100mm) Flg/Flg

6” (168mm) Grv/Grv

6” (168mm) Flg/Grv

6” (168mm) Flg/Flg

165mm Grv/Grv

165mm Flg/Grv

8” (200mm) Grv/Grv

8” (200mm) Flg/Flg

Flange Type

N/A

N/A

Color

Red

Black

Red

Black

Red

Red

Red

Black

Red

Red

Black

Red

Red

Red

Red

Black

Red

Black

Red

Red

Black

Red

Red

Black

Black

Red

Black

Red

Black

Red

Red

N/A

N/A

N/A

ASME Class 150

ASME Class 150

ISO PN16

ASME Class 150

ASME Class 150

ISO PN16

N/A

ASME Class 150

ASME Class 150

ISO PN16

ASME Class 150

ASME Class 150

ISO PN16

N/A

ASME Class 150

ISO PN16

N/A

ASME Class 150

ASME Class 150

ISO PN16

Reliable Part Number

6103060030

6103060045

6103060048

6103060049

6103060046

6103060047

6103060050

6103060028

6103060051

6103060052

6103080001

6103080003

6103080016

6103080018

6103080020

6103022000

6103022001

6103022500

6103022501

6103030000

6103030001

6103027600

6103040026

6103040030

6103040044

6103040046

6103040048

6103040045

6103040047

6103040049

6103060024

Trim — Wet Pilot Line Single Interlock Preaction Trim, Dry Pilot Line Single Interlock Preaction Trim, or Electric Actuation

Single Interlock Preaction Trim. Each trim set is available in individual parts, in time-saving, segmentally assembled kit forms, or fully assembled to the Model DDX Deluge Valve with or without a control valve). The Electric Actuation trim is available with a 175 psi (12,1 bar) or 300 psi (20,7 bar) rated solenoid valve.

41.

Wet Pilot Line Single Interlock Preaction Systems

Valve Size & End

Connection

Flange Type Color

Trim Part Numbers

Trim Confi gurations

Individual Parts

(Model DDX Valve

Sold Seperately)

Segmentally Assembled

(Model DDX Valve Sold

Seperately)

2" (50mm) Grv/Grv N/A

Black

Red

Black

2½" (50mm) Grv/Grv N/A

3" (50mm) Grv/Grv

76mm Grv/Grv

4" (100mm) Grv/Grv

4" (100mm) Flg/Grv

4" (100mm) Flg/Flg

N/A

N/A

N/A

ASME Class 150

ASME Class 150

ISO PN16

ASME Class 150

ASME Class 150

Red

Black

Red

Red

Black

Red

Black

Red

Red

Black

Red

6503002752 6503002753

ISO PN16

6" (168mm) Grv/Grv

6" (168mm) Flg/Grv

6" (168mm) Flg/Flg

165mm Grv/Grv

165mm Flg/Grv

8" (200mm) Grv/Grv

8" (200mm) Flg/Flg

N/A

ASME Class 150

ASME Class 150

ISO PN16

ASME Class 150

ASME Class 150

ISO PN16

N/A

ASME Class 150

ISO PN16

N/A

ASME Class 150

ASME Class 150

ISO PN16

Red

Black

Red

Black

Red

Red

Black

Red

Red

Red

Red

Red

Black

Red

Black

Red

Red

6503001710 6503001711

6505A48275

6505060275

6505A60275

6505063275

6505A63275

6505A64275

6505067275

6505A67275

6505A68275

6505A65274

6505A66275

6505A69275

6505080275

6505A80275

6505087275

6505A87275

6505A88275

Fully Assembled to

Model DDX Valve w/o

Control Valve

6505020076

6505A20076

6505022576

6505A22576

6505030076

6505A30076

6505A27676

6505040275

6505A40275

6505043275

6505A43275

6505A44275

6505047275

6505A47275

Fully Assembled to

Model DDX Valve w/

Control Valve

6505020075

6505A20075

6505022575

6505A22575

6505030075

6505A30075

N/A

6505040276

6505A40276

N/A

N/A

6505060276

6505A60276

N/A

N/A

N/A

N/A

6505080276

6505A80276

N/A

42.

6" (168mm) Flg/Flg

165mm Grv/Grv

165mm Flg/Grv

8" (200mm) Grv/Grv

8" (200mm) Flg/Flg

2" (50mm) Grv/Grv

2½" (50mm) Grv/Grv

3" (50mm) Grv/Grv

76mm Grv/Grv

4" (100mm) Grv/Grv

4" (100mm) Flg/Grv

4" (100mm) Flg/Flg

6" (168mm) Grv/Grv

6" (168mm) Flg/Grv

300 psi

(20,7 bar)

{

Rated

Solenoid

Valve

Valve Size & End

Connection

2" (50mm) Grv/Grv

2½" (50mm) Grv/Grv

3" (50mm) Grv/Grv

76mm Grv/Grv

4" (100mm) Grv/Grv

4" (100mm) Flg/Grv

4" (100mm) Flg/Flg

6" (168mm) Grv/Grv

6" (168mm) Flg/Grv

6" (168mm) Flg/Flg

165mm Grv/Grv

165mm Flg/Grv

8" (200mm) Grv/Grv

8" (200mm) Flg/Flg

Flange Type

N/A

N/A

N/A

N/A

N/A

ISO PN16

ISO PN16

N/A

ISO PN16

ISO PN16

N/A

ISO PN16

N/A

ISO PN16

Color

Black

Red

Black

Red

Black

Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Red

ASME Class 150 Black

ASME Class 150 Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Red

ASME Class 150 Black

ASME Class 150 Red

Red

Red

ASME Class 150 Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Red

Trim Part Numbers

Individual Parts

(Model DDX Valve

Sold Separately)

Segmentally Assembled

(Model DDX Valve Sold

Separately)

6503002222

6503001706

Trim Confi gurations {

175 psi

(12,1 bar)

Rated

Solenoid

Valve

Electric Actuation Deluge (Explosion Proof Solenoid Available Upon Request)

6503002223

6503001707

Fully Assembled to

Model DDX Valve w/o Control Valve

6505020031

6505A20031

6505022531

6505A22531

6505030031

6505A30031

6505A27631

6505040231

6505A40231

6505043231

6505A43231

6505A44231

6505047231

6505A47231

6505A48231

6505060231

6505A60231

6505063231

6505A63231

6505A64231

6505067231

6505A67231

6505A68231

6505A65231

6505A66231

6505A69231

6505080231

6505A80231

6505087231

6505A87231

6505A88231

N/A

N/A

N/A

N/A

N/A

ASME Class 150 Black

ASME Class 150 Red

ISO PN16

ASME Class 150 Black

ASME Class 150 Red

ISO PN16

N/A

Black

Red

Black

Red

Black

Red

Red

Black

Red

Red

Red

Black

Red

ASME Class 150 Black

6503002226

6503001708

6503002227

6503001709

6505020041

6505A20041

6505022541

6505A22541

6505030041

6505A30041

6505A27641

6505040241

6505A40241

6505043241

6505A43241

6505A44241

6505047241

6505A47241

6505A48241

6505060241

6505A60241

ASME Class 150 Red

ISO PN16

ISO PN16

N/A

ISO PN16

N/A

ISO PN16

Red

ASME Class 150 Black

ASME Class 150 Red

Red

Red

ASME Class 150 Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Red

6505063241

6505A63241

6505A64241

6505067241

6505A67241

6505A68241

6505A65241

6505A66241

6505A69241

6505080241

6505A80241

6505087241

6505A87241

6505A88241

43.

Fully Assembled to

Model DDX Valve w/ Control Valve

6505020030

6505A20030

6505022530

6505A22530

6505030030

6505A30030

N/A

6505040230

6505A40230

N/A

N/A

6505060230

6505A60230

N/A

N/A

N/A

N/A

6505080230

6505A80230

N/A

6505020040

6505A20040

6505022540

6505A22540

6505030040

6505A30040

N/A

6505040240

6505A40240

N/A

N/A

6505060240

6505A60240

N/A

N/A

N/A

N/A

6505080240

6505A80240

N/A

ISO PN16

Valve Size & End

Connection

2" (50mm) Grv/Grv

2½" (50mm) Grv/Grv

3" (50mm) Grv/Grv

76mm Grv/Grv

4" (100mm) Grv/Grv

4" (100mm) Flg/Grv

4" (100mm) Flg/Flg

6" (168mm) Grv/Grv

6" (168mm) Flg/Grv

6" (168mm) Flg/Flg

165mm Grv/Grv

165mm Flg/Grv

8" (200mm) Grv/Grv

8" (200mm) Flg/Flg

{

Approved

Pressure

UL/FM

Switch

Dry Pilot Line Single Interlock Preaction Systems

Flange Type

N/A

N/A

N/A

N/A

N/A

ISO PN16

ISO PN16

N/A

ISO PN16

ISO PN16

N/A

ISO PN16

N/A

Color

Black

Red

Black

Red

Black

Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Red

ASME Class 150 Black

ASME Class 150 Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Red

ASME Class 150 Black

ASME Class 150 Red

Red

Red

ASME Class 150 Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Trim Part Numbers

6503002708

6503001712

Trim Confi gurations

Individual Parts

(Model DDX Valve

Sold Separately)

Segmentally Assembled

(Model DDX Valve Sold

Separately)

6503002709

6503001713

Red

Fully Assembled to Fully Assembled to

Model DDX Valve w/o Control Valve

Model DDX Valve w/ Control Valve

6505020081

6505A20081

6505022581

6505A22581

6505030081

6505A30081

6505A27681

6505040280

6505A40280

6505043280

6505A43280

6505A44280

6505047280

6505A47280

6505A48280

6505060280

6505A60280

6505063280

6505A63280

6505A64280

6505067280

6505A67280

6505A68280

6505A65277

6505A66280

6505A69280

6505080280

6505A80280

6505087280

6505A87280

6505A88280

6505020080

6505A20080

6505022580

6505A22580

6505030080

6505A30080

N/A

6505040281

6505A40281

N/A

N/A

6505060281

6505A60281

N/A

N/A

N/A

N/A

6505080281

6505A80281

N/A

44

ISO PN16

4" (100mm) Flg/Flg

6" (168mm) Grv/Grv

6" (168mm) Flg/Grv

6" (168mm) Flg/Flg

165mm Grv/Grv

165mm Flg/Grv

8" (200mm) Grv/Grv

8" (200mm) Flg/Flg

ISO PN16

N/A

N/A

N/A

{

Approved

Pressure

ULC

Switch

Dry Pilot Line Single Interlock Preaction Systems (Continued)

Valve Size & End

Connection

2" (50mm) Grv/Grv

2½" (50mm) Grv/Grv

3" (50mm) Grv/Grv

76mm Grv/Grv

4" (100mm) Grv/Grv

4" (100mm) Flg/Grv

Flange Type

N/A

N/A

N/A

N/A

N/A

Color

Black

Red

Black

Red

Black

Red

Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Trim Part Numbers

6503002712

6503001714

Trim Confi gurations

Individual Parts

(Model DDX Valve

Sold Separately)

Segmentally Assembled

(Model DDX Valve Sold

Separately)

6503002713

6503001715

Red

ASME Class 150 Black

ASME Class 150 Red

ISO PN16 Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

ISO PN16 Red

ASME Class 150 Black

ASME Class 150 Red

ISO PN16 Red

Red

ASME Class 150 Red

ISO PN16 Red

Black

Red

ASME Class 150 Black

ASME Class 150 Red

Fully Assembled to Fully Assembled to

Model DDX Valve Model DDX Valve w/o Control Valve w/ Control Valve

6505020086

6505A20086

6505022586

6505A22586

6505030086

6505A30086

6505A27686

6505040282

6505A40282

6505043282

6505A43282

6505A44282

6505047282

6505A47282

6505A48282

6505060282

6505A60282

6505063282

6505A63282

6505A64282

6505067282

6505A67282

6505A68282

6505A65280

6505A66282

6505A69282

6505080282

6505A80282

6505087282

6505A87282

6505020085

6505A20085

6505022585

6505A22585

6505030085

6505A30085

N/A

6505040283

6505A40283

N/A

N/A

6505060283

6505A60283

N/A

N/A

N/A

N/A

6505080283

6505A80283

N/A

Red 6505A88282

Note: For metric installations, a 1¼” NPT x R1¼. ISO 7/1 x Close Nipple (Reliable P/N 98543403) or a 2”

NPT x R2. ISO 7/1 x Close Nipple (Reliable P/N 98543401) is sold separately as an adapter for the single drain outlet of the trims.

45.

1

4

5

6

7

8

9

10

11

12

13

14

15

16

Item

No.

Additional equipment—(Refer to Fig. 16 & Fig. 17).

Component Part Mfgr.

Water Supply Control Valve Select

2

3

Tamper Switch (Optional) for OS&Y Valve

(Optional) for Butterfly Valve

Deluge Valve

Single Interlock Preaction Trim Kit

Waterflow Alarm Pressure Switch

Mechanical Alarm (Optional)

Releasing / Control Panel

Batteries

Optional Accessories

Alarm Annunciator

Trouble Annunciator

Manual Emergency Station (Elec.)

Pilot Line Detectors

Sprinklers

Air Compressor

Pressure Maintenance Device

-

Nitrogen Regulating Device

Air Compressor Panel

D

A

B

B

E

B

-

B

B

B

B

D

B

C

A

A

Description

OS&Y

Butterfly

Model OS&Y2

Model P1BV2

Model DDX

Refer to Parts List in this Bulletin

Model EPS10-2 (DPDT, UL, FM)

Model EPSA10-2 (DPDT, ULC)

Model C

Model PFC-4410-RC

12 VDC, 12 AMP Hours (90 Hours Backup) FM

12 VDC, 7 AMP Hours (60 Hours Backup)

CA2Z (Class A Wiring Module for Initiating Circuits)

CAM (Class A Wiring Module for Indicating Circuits)

ARM-1 / ARM-2 (Auxiliary Relay Module)

RA-4410-RC (Remote Annunciator)

Model SSM24-8 24 VDC / Polarized Bell

Model SSM24-10 24 VDC / Polarized Bell

Model MA24-D 24 VDC / Polarized Sounder

Model MASS24LO 24 VDC / Polarized Sounder Strobe

Model SSM24-6 24 VDC / Polarized Bell

Model MA24-D 24 VDC / Polarized Sounder

Model BNG-1 (SPDT) 1 & 2 Area Detection

Model BNG-1F (DPDT) Cross Zoned Detection

Model F1-FTR Pilot Line Detectors

Closed Type

Per NFPA 13 requirements

Model A-2 or B-1

Model B1

-

Model B-SI or C-SI Air Compressor Panel

Technical Bulletin

-

-

System Sensor

A05-0196

System Sensor

A05-0197

Reliable 518/519

Reliable 749

System Sensor

WFDS51701

Reliable 612 / 613

Potter #5403550

-

-

-

Reliable 180

Reliable 110, 117, 131,

136, etc.

Gast F-30

Reliable 254

Reliable 323

-

Reliable 254

System Equipment Manufacturers

(A) Notifier

(B) Reliable Automatic Sprinkler Co., Inc.

(C) Potter Electric Signal Company

(D) System Sensor

(E) Gast Mfg, Inc.

46.

Nominal

Pipe Size

A B

2” (50 mm)

8

(203)

7

(178)

2½” (65 mm), 3” (80 mm) & 76 mm

8

(203)

7

(178)

4” (100 mm)

(184)

(191)

C

(241)

(241)

D*

12½

(318)

12½

(318)

10

(254)

14

(356)

21¼

(540)

22

(559)

24¼

(616)

N/A

N/A

16

(406)

16

Installation Dimensions in Inches (mm)

D** D*** D****

N/A

N/A

(406)

E

19

(283)

19

(283)

19¾

(502)

F

26¾

(679)

26¾

(679)

24¾

(629)

G

6

(152)

6

(152)

(191)

H

(133)

(133)

(32)

J

(108)

(108)

(140)

K

(140)

(140)

(210)

6” (150 mm)

& 165 mm

(184)

(215)

11

(280)

16

(406)

27½

(699)

19

(483)

19

(483)

21½

(546)

26½

(673)

8

(203)

(32)

(140)

(210)

8” (200 mm)

(184)

(235)

11½

(292)

19 3 /

8

(492)

30¼

(768)

N/A

21¼

(540)

28¼

(718)

33¼

(845)

9

(229)

(32)

(140)

(210)

D* is total takeout for Fully Assembled to Grv/Grv DDX Valve w/o Control Valve Configurations

D** is total takeout for Fully Assembled to Grv/Grv DDX Valve w/ Control Valve Configurations

D*** is total takeout for Fully Assembled to Flg/Grv DDX Valve w/o Control

D**** is total takeout for Fully Assembled to Flg/Flg DDX Valve w/o Control Valve Configurations

L

11

(279)

11

(279)

M

3

(76)

3

(76)

N

(114)

(114)

P

9

(229)

Q

(235)

9

(229)

(235)

13½

(343)

13¾

(349)

14½

(368)

5

(127)

(171)

(121)

(89)

8

(203)

(165)

(222)

(133)

(216)

11¾

(298)

12

(305)

12¾

(324)

47.

SOLENOID VALVE INSPECTIONS, TESTS AND MAINTENANCE

WARNING: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM IN PROPER

OPERATING CONDITION. ANY SYSTEM MAINTENANCE OR TESTING THAT INVOLVES PLACING A CONTROL

VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION OF THAT SYS-

TEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES HAVING JURISDICTION. CONSIDERATION SHOULD

BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREA.

WARNING: PRIOR TO OPERATING THE SOLENOID VALVE, BE SURE TO CLOSE THE SYSTEM CONTROL

VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE

1. Inspections: It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular basis. The frequency of the inspections may vary due to contaminated water supplies, corrosive water supplies, or corrosive atmospheres.

In addition, the alarm devices, detection systems, or other connected trim may require a more frequent schedule. Refer to the system description and applicable codes for minimum requirements.

2. The valve must be inspected at least monthly for cracks, corrosion, leakage, etc., cleaned and replaced as necessary.

3. If leakage is suspected through the solenoid valve, it should be replaced.

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.

Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

Manufactured by

Reliable Automatic Sprinkler Co., Inc.

(800) 431-1588

(800) 848-6051

(914) 829-2042

Sales Offices

Sales Fax

Corporate Offices www.reliablesprinkler.com Internet Address

Recycled

Paper

Revision lines indicate updated or new data.

EG. Printed in U.S.A. 03/15 P/N 9999970440