Complete Specifications

Complete Specifications
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Rosemount 2051
Specifications
PERFORMANCE SPECIFICATIONS
For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange (2051C) or 1/2 in. - 14 NPT (2051T) process connections,
digital trim values set to equal range points. Applicable to 4-20 mA HART output only unless otherwise noted.
Conformance To Specification (±3σ (Sigma))
Technology leadership, advanced manufacturing techniques and statistical process control ensure specification conformance to at least ±3σ.
Reference Accuracy(1)
Models(1)
Standard
Performance Option, P8
±0.075% of span
For spans less than 10:1, accuracy =
Ranges 2-5
2051C
Ranges 2-5
URL
± 0.025 + 0.005 ⎛ ---------------⎞ % of Span
⎝ Span⎠
Range 1
High Accuracy Option, P8
±0.065% of span
For spans less than 10:1, accuracy =
URL
± 0.015 + 0.005 ⎛ ---------------⎞ % of Span
⎝ Span⎠
±0.10% of span
For spans less than 15:1, accuracy =
URL
± 0.025 + 0.005 ⎛ ---------------⎞ % of Span
⎝ Span⎠
2051T
Ranges 1-4
±0.075% of span
For spans less than 10:1, accuracy =
Ranges 1-4
URL
± 0.0075 ⎛ ---------------⎞ % of Span
⎝ Span⎠
Range 5
±0.075% of span for spans greater than 5:1
2051L
Ranges 2-4
±0.075% of span
For spans less than 10:1, accuracy =
URL
± 0.025 + 0.005 ⎛ ---------------⎞ % of Span
⎝ Span⎠
(1) For FOUNDATION fieldbus transmitters, use calibrated range in place of span.
4
High Accuracy Option, P8
±0.065% of span
For spans less than 10:1, accuracy =
URL
± 0.0075 ⎛ ---------------⎞ % of Span
⎝ Span⎠
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Rosemount 2051
Long Term Stability
Models
Standard
Performance Option, P8
Range 1 (CD)
Ranges 2-5
±0.2% of URL for 1 year, Reference Stability
±0.1% of URL for 2 years, Operating Stability
±0.125% of URL for 5 years, Operating Stability
Ranges 1-5
±0.1% of URL for 2 years, Operating Stability
±0.125% of URL for 5 years, Operating Stability
Ranges 2-4
Not Specified
2051CD, CG
2051T
2051L
Dynamic Performance
4-20 mA HART(1)
1-5 Vdc HART Low Power
Fieldbus(3)
Typical HART Transmitter Response Time
(2)
Total Response Time (Td + Tc)
2051C, Range 3-5:
Range 1:
Range 2:
2051T:
2051L:
Dead Time (Td)
Update Rate
:
115 milliseconds
270 milliseconds
130 milliseconds
100 milliseconds
See Instrument Toolkit®
60 milliseconds (nominal)
22 times per second
152 milliseconds
307 milliseconds
152 milliseconds
152 milliseconds
See Instrument Toolkit
97 milliseconds
22 times per second
Transmitter Output vs. Time
Pressure Released
Td
100%
Tc
Td = Dead Time
Tc = Time Constant
Response Time = Td +Tc
63.2% of Total
Step Change
36.8%
(1) Dead time and update rate apply to all models and ranges; analog output only
(2) Nominal total response time at 75 °F (24 °C) reference conditions.
(3) Transmitter fieldbus output only, segment macro-cycle not included.
0%
Time
Line Pressure Effect per 1000 psi (6,9 MPa)
For line pressures above 2000 psi (13,7 MPa) and Ranges 4-5, see user manual (Rosemount publication number 00809-0100-4101).
Models
2051CD
Line Pressure Effect
Zero Error(1)
Ranges 2-3 ±0.1% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)
Range 1 ±0.5% of URL/1000 psi (68,9 bar)
Span Error
Ranges 2-3 ±0.1% of reading/1000 psi (68,9 bar)
Range 1 ±0.4% of reading/1000 psi (68,9 bar)
(1) Can be calibrated out at line pressure.
5
Product Data Sheet
Rosemount 2051
00813-0100-4101, Rev BA
February 2009
Ambient Temperature Effect per 50°F (28°C)
Models
Ambient Temperature Effect
2051C
Ranges 2-5 ±(0.025% URL + 0.125% span) from 1:1 to 5:1
±(0.05% URL + 0.25% span) from 5:1 to 100:1
Range 1 ±(0.2% URL + 0.5% span) from 1:1 to 50:1
2051T
Range 2-4
Range 1
Range 5
2051L
±(0.05% URL + 0.25% span) from 1:1 to 30:1
±(0.07% URL + 0.25% span) from 30:1 to 100:1
±(0.05% URL + 0.25% span) from 1:1 to 10:1
±(0.10% URL + 0.25% span) from 10:1 to 100:1
±(0.2% URL + 0.3% span)
See Instrument Toolkit
Mounting Position Effects
Models
Mounting Position Effects
2051C
2051T
2051L
Zero shifts up to ±1.25 inH2O (3,1 mbar), which can be calibrated out. No span effect.
Zero shifts up to ±2.5 inH2O (6,2 mbar), which can be calibrated out. No span effect.
With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (2,49 mbar). With diaphragm in
horizontal plane, zero shift of up to 5 inH2O (12,43 mbar) plus extension length on extended units. Zero
shifts can be calibrated out. No span effect.
Vibration Effect
Less than ±0.1% of URL when tested per the requirements of
IEC60770-1 field or pipeline with high vibration level (10-60 Hz
0.21mm displacement peak amplitude / 60-2000 Hz 3g).
Power Supply Effect
Less than ±0.005% of calibrated span per volt.
Electromagnetic Compatibility (EMC)
Meets all relevant requirements of EN 61326 and NAMUR NE-21.
Transient Protection (Option Code T1)
Meets IEEE C62.41, Category Location B
6 kV crest (0.5 μs - 100 kHz)
3 kV crest (8 × 20 microseconds)
6 kV crest (1.2 × 50 microseconds)
6
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Rosemount 2051
FUNCTIONAL SPECIFICATIONS
Range and Sensor Limits
Range
2051CD, 2051CG, 2051L
1
2
3
4
5
Range and Sensor Limits
Lower (LRL)
Minimum Span
Upper (URL)
2051C Differential
2051C Gage(1)
2051L Differential
2051L Gage(1)
0.5 inH2O
(1,2 mbar)
2.5 inH2O
(6,2 mbar)
10 inH2O
(24,9 mbar)
3 psi
(0,207 bar)
20 psi
(1,38 bar)
25 inH2O
(62,3 mbar)
250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,6 bar)
2000 psi
(137,9 bar)
–25 inH2O
(–62,1 mbar)
–250 inH2O
(–0,62 bar)
-1000 inH2O
(-2,49 bar)
-300 psi
(-20,6 bar)
-2000 psi
(-137,9 bar)
–25 inH2O
(–62,1 mbar)
–250 inH2O
(–0,62 bar)
–393 inH2O
(–979 mbar)
–14.2 psig
(–979 mbar)
–14.2 psig
(–979 mbar)
N/A
N/A
–250 inH2O
(–0,62 bar)
–1000 inH2O
(–2,49 bar)
–300 psi
(–20,7 bar)
N/A
–250 inH2O
(–0,62 bar)
–393 inH2O
(–979 mbar)
–14.2 psig
(–979 mbar)
N/A
(1) Assumes atmospheric pressure of 14.7 psig.
Range
2051T
1
2
3
4
5
Range and Sensor Limits
Minimum
Span
Upper
(URL)
Lower
(LRL) (Abs)
Lower(1)
(LRL) (Gage)
0.3 psi
(20,6 mbar)
1.5 psi
(0,103 bar)
8 psi
(0,55 bar)
40 psi
(2,76 bar)
2000 psi
(137,9 bar)
30 psi
(2,06 bar)
150 psi
(10,3 bar)
800 psi
(55,2 bar)
4000 psi
(275,8 bar)
10000 psi
(689,4 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
(1) Assumes atmospheric pressure of 14.7 psig.
7
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Rosemount 2051
Service
FOUNDATION fieldbus Parameters
Schedule Entries
Links
Virtual Communications Relationships (VCR)
Liquid, gas, and vapor applications
Protocols
7 (max.)
20 (max.)
12 (max.)
Standard Function Blocks
4–20 mA HART (Output Code A)
Resource Block
Output
• Contains hardware, electronics, and diagnostic information.
Two-wire 4–20 mA, user-selectable for linear or square root
output. Digital process variable superimposed on 4–20 mA
signal, available to any host that conforms to the HART
protocol.
Transducer Block
Power Supply
LCD Block
External power supply required. Standard transmitter operates
on 10.5 to 42.4 V dc with no load.
• Configures the local display.
Turn-On Time
• Processes the measurements for input into other function
blocks. The output value is in engineering units or custom
and contains a status indicating measurement quality.
Performance within specifications less than 2.0 seconds after
power is applied to the transmitter.
• Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure
sensor or recall factory defaults.
2 Analog Input Blocks
PID Block
Load Limitations
Maximum loop resistance is determined by the voltage level of
the external power supply, as described by:
• Contains all logic to perform PID control in the field including
cascade and feedforward.
Backup Link Active Scheduler (LAS)
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
Load (Ohms)
1387
The transmitter can function as a Link Active Scheduler if the
current link master device fails or is removed from the
segment.
1000
1-5 Vdc HART Low Power (Output Code M)
500
Operating
Region
Output
0
10.5
20
30
Voltage (V dc)
42.4
The HART communicator requires a minimum
loop resistance of 250Ω for communication.
FOUNDATION fieldbus (Output Code F)
Three wire 1–5 Vdc output, user-selectable for linear or
square root output. Digital process variable superimposed on
voltage signal, available to any host conforming to the HART
protocol.
Power Supply
External power supply required. Standard transmitter operates
on 9 to 28 Vdc with no load.
Power Consumption
Power Supply
3.0 mA, 27–84 mW
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
100 kΩ or greater
Current Draw
17.5 mA for all configurations (including LCD display option)
Turn-On Time
Turn-On Time
Performance within specifications less than 2.0 seconds after
power is applied to the transmitter.
Performance within specifications less than 20.0 seconds after
power is applied to the transmitter.
FOUNDATION fieldbus Function Block Execution Times
Block
Execution Time
Resource
Transducer
LCD Block
Analog Input 1, 2
PID
8
Output Load
30 milliseconds
45 milliseconds
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Rosemount 2051
Overpressure Limits
Temperature Limits
Transmitters withstand the following limits without damage:
Ambient(1)
–40 to 185 °F (–40 to 85 °C)
2051C
With LCD display(2): –40 to 175 °F (–40 to 80 °C)
• Ranges 2–5: 3626 psig (250 bar)
4500 psig (310,3 bar) for option code P9
Storage(1)
• Range 1: 2000 psig (137,9 bar)
–50 to 230 °F (–46 to 110 °C)
With LCD display: –40 to 185 °F (–40 to 85 °C)
2051T
(1) Limits for silicone fill fluid only.
• Range 1: 750 psi (51,7 bar)
(2) LCD display may not be readable and LCD updates will be slower
at temperatures below -4 °F (-20 °C).
• Range 2: 1500 psi (103,4 bar)
• Range 3: 1600 psi (110,3 bar)
• Range 4: 6000 psi (413,7 bar)
Process Temperature Limits
• Range 5: 15000 psi (1034,2 bar)
At atmospheric pressures and above.
TABLE 2. 2051 Process Temperature Limits
2051L
Limit is flange rating or sensor rating, whichever is lower (see
Table 1).
TABLE 1. 2051L Flange Rating
Standard
Type
CS Rating SST Rating
ANSI/ASME
Class 150
285 psig
275 psig
ANSI/ASME
Class 300
740 psig
720 psig
At 100 °F (38 °C), the rating decreases with
increasing temperature.
DIN
PN 10–40
40 bar
40 bar
DIN
PN 10/16
16 bar
16 bar
At 248 °F (120 °C), the rating decreases
with increasing temperature.
Static Pressure Limit
2051CD
• Operates within specifications between static line pressures of
-14.2 psig (0.034 bar) and 3626 psig (250 bar)
•
For Option Code P9, 4500 psig (310,3 bar)
• Range 1: 0.5 psia to 2000 psig (34 mbar and 137,9 bar)
Burst Pressure Limits
2051C Coplanar or traditional process flange
• 10000 psig (689,5 bar)
2051T
• Ranges 1–4: 11000 psi (758,4 bar)
• Range 5: 26000 psi (1792,64 bar)
2051C
Silicone Fill Sensor(1)
with Coplanar Flange
–40 to 250 °F (–40 to 121 °C)(2)
with Traditional Flange
–40 to 300 °F (–40 to 149 °C)(2)
with Level Flange
–40 to 300 °F (–40 to 149 °C)(2)
with 305 Integral Manifold –40 to 300 °F (–40 to 149 °C)(2)
Inert Fill Sensor(1)
0 to 185 °F (–18 to 85 °C)(3)
2051T (Process Fill Fluid)
Silicone Fill Sensor(1)
–40 to 250 °F (–40 to 121 °C)(2)
Inert Fill Sensor(1)
–22 to 250 °F (–30 to 121 °C)(2)
2051L Low-Side Temperature Limits
Silicone Fill Sensor(1)
–40 to 250 °F (–40 to 121 °C)(2)
Inert Fill Sensor(1)
0 to 185 °F (–18 to 85 °C) (2)
2051L High-Side Temperature Limits (Process Fill Fluid)
Syltherm® XLT
D.C. Silicone 704®
D.C. Silicone 200
Inert
Glycerin and Water
Neobee M-20
Propylene Glycol and
Water
–100 to 300 °F (–73 to 149 °C)
32 to 400 °F (0 to 205 °C)
–40 to 400 °F (–40 to 205 °C)
–50 to 350 °F (–45 to 177 °C)
0 to 200 °F (–18 to 93 °C)
0 to 400 °F (–18 to 205 °C)
0 to 200 °F (–18 to 93 °C)
(1) Process temperatures above 185 °F (85 °C) require derating
the ambient limits by a 1.5:1 ratio.
(2) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for
pressures below 0.5 psia.
(3) 160 °F (71 °C) limit in vacuum service.
Humidity Limits
0–100% relative humidity
Volumetric Displacement
Less than 0.005 in3 (0,08 cm3)
Damping
Analog output response to a step input change is user-selectable
from 0 to 25.6 seconds for one time constant. This software
damping is in addition to sensor module response time.
9
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Rosemount 2051
Failure Mode Alarm
2051C Process Wetted Parts
If self-diagnostics detect a sensor or microprocessor failure, the
analog signal is driven either high or low to alert the user. High or
low failure mode is user-selectable with a jumper on the
transmitter. The values to which the transmitter drives its output in
failure mode depend on whether it is factory-configured to
standard or NAMUR-compliant operation. The values for each are
as follows:
Standard Operation
Drain/Vent Valves
Output Code
Linear Output
3.9 ≤ I ≤ 20.8
0.97 ≤ V ≤ 5.2
A
M
Fail High
Fail Low
I ≥ 21.75 mA
V ≥ 5.4 V
I ≤ 3.75 mA
V ≤ 0.95V
316 SST or Alloy C-276
Process Flanges and Adapters
Plated carbon steel, SST CF-8M (cast version of 316 SST,
material per ASTM-A743), or CW12MW (cast version of Alloy
C-276)
Wetted O-rings
Glass-filled PTFE or Graphite-filled PTFE
Process Isolating Diaphragms
NAMUR-Compliant Operation
Output Code
Linear Output
3.8 ≤ I ≤ 20.5
A
316L SST or Alloy C-276
Fail High
Fail Low
I ≥ 22.5 mA
I ≤ 3.6 mA
2051T Process Wetted Parts
Process Connections
Output Code F
If self-diagnostics detect a gross transmitter failure, that
information gets passed as a status along with the process
variable.
• 316L SST or Alloy C-276
Process Isolating Diaphragms
• 316L SST or Alloy C-276
PHYSICAL SPECIFICATIONS
2051L Process Wetted Parts
Electrical Connections
1
/2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit.
Flanged Process Connection (Transmitter High Side)
Process Diaphragms, Including Process Gasket Surface
Process Connections
•
2051C
Extension
• 1/4–18 NPT on 21/8-in. centers
•
• 1/2–14 NPT and RC 1/2 on 2-in.(50.8mm), 21/8-in. (54.0 mm),
or 21/4-in. (57.2mm) centers (process adapters)
•
CF-3M (Cast version of 316L SST, material per
ASTM-A743), or Cast C-276. Fits schedule 40 and 80
pipe.
Mounting Flange
2051T
1/2–14
316L SST or Alloy C-276
•
NPT female
Zinc-cobalt plated CS or SST
1
• G /2 A DIN 16288 Male (available in SST for Range 1–4
transmitters only)
9/16–18
gland
• Autoclave type F-250-C (Pressure relieved
thread; 1/4 OD high pressure tube 60° cone; available in SST
for Range 5 transmitters only)
Reference Process Connection (Transmitter Low Side)
Isolating Diaphragms
•
316L SST or Alloy C-276
Reference Flange and Adapter
2051L
• High pressure side: 2-in.(50.8mm), 3-in. (72 mm), or 4-in.
(102mm), ASME B 16.5 (ANSI) Class 150 or 300 flange;
50, 80 or 100 mm, DIN 2501 PN 40 or 10/16 flange
• Low pressure side: 1/4–18 NPT on flange, 1/2–14 NPT on
process adapter
10
•
CF-8M (Cast version of 316 SST, material per
ASTM-A743)
Product Data Sheet
00813-0100-4101, Rev BA
February 2009
Non-Wetted Parts for 2051C/T/L
Electronics Housing
Low-copper aluminum or CF-8M (Cast version of 316 SST).
Enclosure Type 4X, IP 65, IP 66, IP68
Coplanar Sensor Module Housing
Rosemount 2051
Shipping Weights
TABLE 3. Transmitter Weights without Options
Transmitter
lb. (kg)
2051C
2051L
2051T
4.9 (2,2)
Table 4 below
3.1 (1,4)
CF-3M (Cast version of 316L SST)
Bolts
ASTM A449, Type 1 (zinc-cobalt plated carbon steel)
ASTM F593G, Condition CW1 (Austenitic 316 SST)
ASTM A193, Grade B7M (zinc plated alloy steel)
Sensor Module Fill Fluid
Silicone oil (D.C. 200) or Fluorocarbon oil (Halocarbon or
Fluorinert® FC-43 for 2051T)
Process Fill Fluid (2051L only)
Syltherm XLT, D.C. Silicone 704,
D.C. Silicone 200, inert, glycerin and water, Neobee M-20 or
propylene glycol and water
Paint
Polyurethane
TABLE 4. 2051L Weights without Options
Flange
2-in., 150
3-in., 150
4-in., 150
2-in., 300
3-in., 300
4-in., 300
DN 50/PN 40
DN 80/PN 40
DN 100/
PN 10/16
DN 100/
PN 40
Flush
lb. (kg)
2-in. Ext.
lb (kg)
4-in. Ext.
lb (kg)
6-in. Ext.
lb (kg)
12.5 (5,7)
17.5 (7,9)
23.5 (10,7)
17.5 (7,9)
22.5 (10,2)
32.5 (14,7)
13.8 (6,2)
19.5 (8,8)
17.8 (8,1)
—
19.5 (8,8)
26.5 (12,0)
—
24.5 (11,1)
35.5 (16,1)
—
21.5 (9,7)
19.8 (9,0)
—
20.5 (9,3)
28.5 (12,9)
—
25.5 (11,6)
37.5 (17,0)
—
22.5 (10,2)
20.8 (9,5)
—
21.5 (9,7)
30.5 (13,8)
—
26.5 (12,0)
39.5 (17,9)
—
23.5 (10,6)
21.8 (9,9)
23.2 (10,5)
25.2 (11,5)
26.2 (11,9)
27.2 (12,3)
Cover O-rings
Buna-N
TABLE 5. Transmitter Options Weights
Code
J, K, L, M
M5
B4
B1 B2 B3
B7 B8 B9
BA, BC
H2
H3
H4
H7
FC
FD
FA
FB
FP
FQ
Option
Add
lb (kg)
Stainless Steel Housing
3.9 (1,8)
LCD display for Aluminum Housing
0.5 (0,2)
SST Mounting Bracket for Coplanar Flange 1.0 (0,5)
Mounting Bracket for Traditional Flange
2.3 (1,0)
Mounting Bracket for Traditional Flange
2.3 (1,0)
SST Bracket for Traditional Flange
2.3 (1,0)
Traditional Flange
2.6 (1,2)
Traditional Flange
3.0 (1,4)
Traditional Flange
3.0 (1,4)
Traditional Flange
2.7 (1,2)
Level Flange—3 in., 150
12.7 (5,8)
Level Flange—3 in., 300
15.9 (7,2)
Level Flange—2 in., 150
8.0 (3,6)
Level Flange—2 in., 300
8.4 (3,3)
DIN Level Flange, SST, DN 50, PN 40
7.8 (3,5)
DIN Level Flange, SST, DN 80, PN 40
12.7 (5,8)
11