Datasheet | Viessmann SCU224 Technical information

Add to my manuals
18 Pages

advertisement

Datasheet | Viessmann SCU224 Technical information | Manualzz
Versatronik® 532 & 532D Solar
Communication Gateway for solar controls
Modbus
Communication
Document Applicable to:
Versatronik 532 Solar/Modbus P/N 704089
Versatronik 532D Solar/Modbus P/N 704090
Applicable Controls
Resol Deltasol M
Resol Deltasol BS Plus
Resol Deltasol BS1/2/3/4
Resol Deltasol BX/BXL
Resol Deltasol E/ES/BX/MX/SKSC3
Viessmann Vitosolic 200
Viessmann SCU 124
Viessmann SCU 224
Viessmann SCU 345
Technical, Installation and Configuration Information
Cautionary Statement
The information presented in this document is
only to be used by those familiar with its
application and use.
IMPORTANT
Read and save these instructions for
future reference
About these instructions
!
Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include “WARNING”, “CAUTION” and “IMPORTANT”. See below.
!
WARNING
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
Indicates an imminently hazardous
situation which, if not avoided,
could result in death, serious injury
or substantial product/property
damage.
!
CAUTION
Indicates an imminently hazardous
situation which, if not avoided,
may result in minor injury or
product/property damage.
 Warnings draw your attention to
the presence of potential
hazards or important product
information.
 Cautions draw your attention to
the presence of potential
hazards or important product
information
CAUTION
Static sensitive components may
be damaged by improper handling
or work within the control. Ensure
all possible measures are taken to
eliminate build-up of static
electricity.
IMPORTANT
Trademark Information
RESOL® and DeltaSol® M are
trademarks of RESOL.
For more information please visit
www.resol-gmbh.de
Viessmann® and Vitotronic® are
trademarks of Viessmann Werke
GmbH & Co KG registered in the
United States and other
countries.
Please visit:
www.viessmann.ca
www.viessmann.us
2
 Helpful hints for installation,
operation or maintenance which
pertains to the product.
Important Regulatory and Installation Requirements
Codes
The installation of this unit must
be in accordance with local
codes.
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
All electrical wiring is to be done
in accordance with the latest
edition of CSA C22,1 Part 1 and/
or local codes. In the U.S. use
the National Electrical Code
ANSI/NFPA 70.
The installing contractor must
comply with the Standard of
Controls and Safety Devices for
Automatically fired Boilers, ANSI/
ASME CSD-1 where required by
the authority having jurisdiction.
Working on the equipment
The installation, adjustment,
service and maintenance of this
unit must be done by a licensed
professional heating contractor
or persons who are qualified and
experienced in the installation,
service, and maintenance of
similar products. There are no
user serviceable parts on this
control.
Power supply
Install power supply in
accordance with the regulation of
the authorities having jurisdiction
or in absence of such
requirements, in accordance with
National Codes.
Purpose of Device and Operation
The Versatronik 532 Solar
gateway provides a
communication translation
between applicable controls and
DDC systems which are capable
of Modbus RS485
communications.
The Versatronik gateway may be
either part of a control panel or
stand-alone control device.
3
 Please carefully read this manual
prior to attempting installation.
Any warranty is null and void if
these instructions are not
followed.
 The completeness and
functionality of field supplied
electrical controls and
components must be verified by
those installing the device
!
WARNING
More than one live circuit. See
wiring diagram in this manual.
Turn off power supply to control
and damper/blower before
servicing. Contact with live
electrical components can result in
serious injury or death
Installation
Mounting Versatronik Gateway—120VAC Unit
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
2
1
4
1
3
Mounting Steps
1. Mount Versatronik 532 Gateway in a
convenient location near the solar control.
Remove cover by loosening the two screws on
either side of base to release the cover.
2. Fasten base to wall using field-supplied
screws/fasteners.
3. Remove knockout and installed wire strain
relief or box connector. Removal of remaining
knockouts is required to make further
connections.
4. Once all of the 120VAC and low voltage
connections are complete and verified, reinstall
the cover from Step 1.
!
WARNING
When extending wire there is the possibility of
exposure to electromagnetic interference. Avoid
running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage
conductors cannot be avoided, use stranded, twisted
pair of shield design wire. Ensure that only one end of
the shielding is grounded.
4
Installation
Mounting Versatronik Gateway—24VAC DIN Rail Unit
Mounting Steps
1
2
" !
! "
#
BACnet IP connection.
Solar Control Connection RJ45
Paralleled BUS connection
LON connection terminals A and B
24VAC Power Connection
1.
2.
3.
4.
5.
Connection Overview
4
3
1
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
1. Mount Versatronik 532d Gateway onto
DIN rail within an enclosure in a
convenient location near the solar
control.
2. Make all the necessary connections
including the 24VAC power connection.
!
!
5
WARNING
When extending wire there is the possibility of
exposure to electromagnetic interference. Avoid
running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage
conductors cannot be avoided, use stranded, twisted
pair of shield design wire. Ensure that only one end of
the shielding is grounded.
5
Connection Overview
RJ45 Communication Cable Supplied
Connection Overview
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
1. Cut UTP cable to 2m length.
2. Strip insulation and crimp plug on
one end.
3. Strip other end, cut all wires but
wire 1 and 2.
4. Strip wire 1 and 2.
5. Wires 1 and 2 used to make
connections to the solar control.
6
Versatronik 532 Dial Setting Overview
Rotary Dial Setting
Setting Overview
1. The rotary dial setting on the Versatronik
Gateways provides addressing information for
systems that may utilize a number of
Versatronik Gateways.
Applications with the Versatronik 532 Solar
with RESOL controls, it is not required to
make adjustments to the rotary dial setting. It
should be left in the factory default position
setting of 0.
+
#$
%
%
(
(
(
)
*
(
+ & &
!"
&
' KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
1
7
Connection Overview—120VAC Unit
MODBUS Communication connections to BMS:
Example: Resol Deltasol BS Plus
Connection Overview
1 Control sensor portion of control.
1
2 A CAT-5 cable is supplied with the
Versatronik Solar Gateway. The
RJ45 is plugged into the gateway
and terminates into the control.
4 Standard plug-in power
connection supply for the
gateway. It requires 120VAC for
its operation.
2
BMS Connection
3
+
#$
%
%
)
(
(
(
*
(
+ & &
!"
&
' KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
3 BMS connection.
4
120VAC
8
Connection Overview—120VAC Unit
MODBUS Communication Connections to BMS:
Example: Resol Deltasol M
Connection Overview
1 Control sensor portion of control.
V Bus
1
2 A CAT-5 cable is supplied with the
Versatronik Solar Gateway. The
RJ45 is plugged into the gateway
and terminates into the control.
4 Standard plug-in power
connection supply for the
gateway. It requires 120VAC for
its operation.
BMS Connection
2
3
+
#$
%
%
)
(
(
(
*
(
+ & &
!"
&
' KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
3 BMS connection.
4
120VAC
9
Connection Overview—24VAC DIN Rail Unit
MODBUS Communication Connections to BMS:
Example: Resol Deltasol BS Plus
Connection Overview
1 Control sensor portion of control.
1
2 A CAT-5 cable is supplied with the
Versatronik Solar Gateway. The
RJ45 is plugged into the gateway
and terminates into the control.
4 Standard plug-in power
connection supply for the
gateway. It requires 24VAC for its
operation.
2
BMS Connection
3
" ! "
#
!
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
3 BMS connection.
!
4
24VAC
10
Connection Overview—24VAC DIN Rail Unit
MODBUS Communication Connections to BMS:
Example: Resol Deltasol M
Connection Overview
1 Control sensor portion of control.
2 A CAT-5 cable is supplied with the
Versatronik Solar Gateway. The
RJ45 is plugged into the gateway
and terminates into the control.
V Bus
1
4 Standard plug-in power
connection supply for the
gateway. It requires 24VAC for its
operation.
2
BMS
Connection
3
" !
#
!
"
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
3 BMS connection.
4
24VAC
11
! Modbus Information
Overview:
Wiring
RS-485 Network
COM1 terminals A and B are used.
The A and B naming convention may differ across
manufacturers.
Refer to individual wiring/installation pages in this
manual.
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
A=(+) non-inverting
B=(—) inverting
Termination and Bias

This device does not have a termination
resistor installed

There are two 4.7kohm pull up/down
resistors located on the lines to maintain
bias.
LED Operation
LED2 will blink every time a Modbus request is
seen on the network
Modbus Communication
Configuration Settings
The gateway is a Modbus slave and all
communication has to be initiated by a master.
To set up successful communication with the
gateway all connection parameters have to be
set correctly to the following: 9600 8-N-1 RTU.
Mode
RTU
Baud Rate
9600bps
Data Bits/Length
8
Parity
None
Stop bits
1
Address/Device ID
88, 1-9
Trouble-Shooting
Problem: Not getting a response from the
gateway device



12
Ensure the connection is set to 9600 8-N-1
Check the rotary dial switch for the device
addressing and it not in between dial
settings
Ensure the communication cables match
their polarity
Deltasol BS1/2/3/4
Deltasol-E
Deltasol-ES
Controls temperature
units1
-
X
X
X
X
X
X
Discrete Inputs 10001-10016
Sensor 1-16 Open Error
Binary
X
-
-
-
-
-
Discrete Inputs 10017-10032
Sensor 1-16 Shorted Error
Binary
X
-
-
-
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
-
X
X
X
-
X
-
-
X
Discrete Inputs 10033-10048
Sensor 1-16 Connected
Binary
X
-
X
-
-
-
-
Discrete Inputs 10049-10064
Relay Flags 1-16
Binary
X
X
-
-
X
-
-
-
Discrete Inputs 10065-10080
Error Flags 1-16
Binary
X
X
X
X
-
X
X
X
X6
Discrete Inputs 10080-10096
Warning Flags 1-16
Binary
X
-
-
-
-
-
-
-
-
Input Register 30001
Temperature Sensor 1
C or F
X
X
X
X
X
X
X
X
X
Input Register 30002
Temperature Sensor 2
C or F
X
X
X
X
X
X
X
X
X
Input Register 30003
Temperature Sensor 3
C or F
X
X
X
X
X
X
X
X
X
Input Register 30004
Temperature Sensor 4
C or F
X
X
X
X
X
X
X
X
X
Input Register 30005
Temperature Sensor 5
C or F
X
-
-
X
X
X
X
X
X
Input Register 30006
Temperature Sensor 6
C or F
X
-
-
X
X
-
X
X
X
Input Register 30007
Temperature Sensor 7
C or F
X
-
-
X
X
-
X
X
X
Input Register 30008
Temperature Sensor 8
C or F
X
-
-
X
X
-
X
X
X
Input Register 30009
Temperature Sensor 9
C or F
X
-
-
X
-
-
X
X
-
Input Register 30010
Temperature Sensor 10
C or F
X
-
-
X
-
-
X
X
-
Input Register 30011
Temperature Sensor 11
C or F
X
-
-
-
-
-
X
X
-
Input Register 30012
Temperature Sensor 12
C or F
X
-
-
-
-
-
X
X
-
Input Register 30013
Irradiation
W/m2,
W/ft2
X
-
-
X
X
-
X
X
Input Register 30014
Pulse Counter 1
-
X
-
-
X
-
-
-
-
Input Register 30015
Pulse Counter 2
-
X
-
-
-
-
-
-
-
Input Register 30016
Speed Relay 1
%
X
X
X
X
X
X
X
X
X
Input Register 30017
Speed Relay 2
%
X
X
X
X
X
X
X
X
X
Input Register 30018
Speed Relay 3
%
X
-
-
X
X
X
X
X
X
Input Register 30019
Speed Relay 4
%
X
-
-
X
-
X
X
X
X
Input Register 30020
Speed Relay 5
%
X
-
-
X
-
-
X
X
-
Input Register 30021
Speed Relay 6
%
X
-
-
X
-
-
X
-
Input Register 30022
Speed Relay 7
%
X
-
-
X
-
-
X
-
Input Register 30023
Speed Relay 8
%
X
-
-
-
-
-
X
-
Input Register 30024
Speed Relay 9
%
X
-
-
-
-
-
X
-
Input Register 30025
Speed Relay 10
%
X
-
-
-
-
-
X
-
7
X
-
7
X
-
Input Register 30026
Input Register 30027
Speed Relay 11
Speed Relay 12
%
%
-
Superscript references please refer to following page
13
-
-
Deltasol-SKSC3
SCU224, SCU124,
Deltasol BS Plus
Coil Register 97
Deltasol-MX
Units
See following page for configuration notes
Deltasol BX Plus
Description
VBus Modbus Objects
Deltasol-BX
Deltasol-BXL/SCU345
Object
Deltasol-M, Vitosolic 200
Modbus Information
-
-
-
X
X
Modbus Information
SCU224, SCU124,
Deltasol BS Plus
Deltasol BS1/2/3/4
Deltasol-E
Deltasol-MX
Deltasol-SKSC3
Binary or Dec.
-
X3
-
X5
X3
-
-
-
Input Register 30029
Heat Quantity in Wh4
Wh
-
X
X
-
X
X
-
X
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
Deltasol BX Plus
Units
Option Mask / Schema
Deltasol-BX
Deltasol-BXL/SCU345
Description
Input Register 30028
See below for configuration notes
Deltasol-ES
Object
Deltasol-M, Vitosolic 200
VBus Modbus Objects Continued
Input Register 30030
Heat Quantity in kWh4
kWh
-
X
X
-
X
X
-
X
Input Register 30031
Heat Quantity in MWh4
MWh
-
X
X
-
X
X
-
X
Input Register 30032
Operating Hours 1
Hours
-
X
X
-
X
X
-
-
Input Register 30033
Operating Hours 2
Hours
-
X
X
-
X
X
-
-
Input Register 30034
Operating Hours 3
Hours
-
-
-
-
X
X
-
-
Input Register 30035
Operating Hours 4
Hours
-
-
-
-
X
X
-
-
Input Register 30036
Operating Hours 5
Hours
-
-
-
-
X
-
-
-
Input Register 30037
Operating Hours 6
Hours
-
-
-
-
X
-
-
-
Input Register 30038
Zone Supply 1
C or F
-
-
-
X
-
-
-
-
Input Register 30039
Zone Supply 2
C or F
-
-
-
X
-
-
-
-
Input Register 30040
Zone Supply 3
C or F
-
-
-
X
-
-
-
-
Input Register 30041
Zone Supply 4
C or F
-
-
-
X
-
-
-
-
Input Register 30042
Zone Status 1
-
-
-
X
-
-
-
-
Input Register 30043
Zone Status 2
-
-
-
X
-
-
-
-
Input Register 30044
Zone Status 3
-
-
-
X
-
-
-
-
Input Register 30045
Zone Status 4
-
-
-
X
-
-
-
-
Input Register 30046
Flow Volume (VFS)
-
-
-
X
X
-
X
l/h or gpm
X
Configuration Notes
Note 1: All input/holding registers are signed 16-bit integers with a multiplier of 1
Note 2: Depending on your unit, and the unit settings, it will transmit the values in Celsius or Fahrenheit.
2
Convert to binary
Bit 0: Sensor/Relay 1 (least significant bit, furthest to the right)
Bit 1: Sensor/Relay 2
3
Convert to binary:
Bit 0: Collector cooling, collector 1 (OCX)
Bit 1: Minimum limitation, collector 1 (OCN)
Bit 2: Antifreeze, collector 1 (OCF)
Bit 3: Tube collector special function (OTC)
Bit 4: Re-cooling function (OREC)
Bit 5: Heat quantity measurement (OHQM)
4
Values roll over when reaching the next base-1000 magnitude (i.e. 999 Wh becomes 0 Wh + 1 KWh.)
5
System Arrangement
6
Warning Flags:
Flag 1: Broken sensor
Flag 2: Short circuit sensor
Flag 3: DT high
Flag 4: Warning circulation at night
7
Speed Pulse Width Modulation (PWM) 1,2
14
Technical Information
3
7
8
+ +
#$
9
%
%
)
(
(
(
*
(
6
& &
&
' KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
5
!"
10
4
2
1
PCB Identifiers
Specifications
1
120VAC Power Supply Connections
Voltage Requirements
120VAC
2
Fuse
Fuse Rating
160mA Time Delay
3
Service Button
Power
4VA
4
LON Connections to BMS
5
RJ45 Connection to BMS BACnet
Communication
Connections
Supplied cable
between devices
6
Addressing selector for multiple modules
7
COM3 for multiple BUS connections
8
COM4 RJ45 Connection to control
9
Power LED indicator
CAUTION
Static sensitive components may
be damaged by improper handling
or work within the control. Ensure
all possible measures are taken to
eliminate build-up of static
electricity.
10 Service LED
15
Technical Information
4
6
7
" ! #
!
"
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
9
8
2
5
3
!
1
PCB Identifiers
Specifications
1
24VAC Power Supply Connections
Voltage Requirements
24VAC
2
Power LED indicator
Fuse Rating
N/A
3
BACnet RJ45 BMS Connection
Power
4VA
4
Addressing dial for multiple units
5
COM4 RJ45 Connection to control
Communication
Connections
Supplied cable
between devices
6
COM3 for multiple BUS connections
7
Service button
8
Service LED
9
LON Connections to BMS
CAUTION
Static sensitive components may
be damaged by improper handling
or work within the control. Ensure
all possible measures are taken to
eliminate build-up of static
electricity.
16
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
Notes:
17
KWE P/N 394047 Versatronik 532 Solar/Modbus Gateway V1.0 09/2013 Technical information subject to change without notice
KWE Technologies Group
750 McMurray Road
Waterloo, Ontario, Canada
N2V 2G5
Tel: (519) 747-5042
Fax: (519) 747-4448
www.kwe-tech.com
[email protected]
18