3 Nexus 1000V Switch for Microsoft Hyper-V Configuration

3 Nexus 1000V Switch for Microsoft Hyper-V Configuration
CH A P T E R
3
Nexus 1000V Switch for Microsoft Hyper-V
Configuration
This section describes how to configure the Nexus 1000V Switch for Microsoft Hyper-V in a VMDC
solution.
•
VSM CLI Configuration
•
SCVMM Configuration
Figure 3-1 compares the SCVMM and Nexus 1000V Switch for Microsoft Hyper-V terminology that
will be referenced in each section.
The reader should be familiar with these terms to better understand the role of each object as it pertains
to the entire configuration and how each relates to SCVMM and the Nexus 1000V Switch for Microsoft
Hyper-V.
Figure 3-1
SCVMM and Nexus 1000V Switch for Microsoft Hyper-V Terminology
Network and Tenants Under Test
Three private tenants and one public tenant logical networks were created.
Six network segment pools were created, three public (T1, T2, T3) and three private (PT1, PT2, PT3).
The three public network segment pools were configured as members of the public tenant logical
network; the three private network segment pools were each configured as an individual member of a
the three private tenant logical networks.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-1
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Switch for Microsoft Hyper-V VSM CLI Configuration
Only one network segment per public network segment pool was created. Two network segments per
private network segment pool were created.
The IP pool templates and port-profiles are described in the IP Pool templates and Port-profiles
sections later in the doc.
The configuration looks like this:
logical network PublicTenants
network segment pool T1
network segment T1-NetworkSegment101
network segment pool T2
network segment T2-NetworkSegment102
network segment pool T3
network segment T3-NetworkSegment103
logical network PrivateTenant1
network segment pool PT1
network segment PT1-NetworkSegment2013
network segment PT1-NetworkSegment2014
logical network PrivateTenant3
network segment pool PT2
network segment PT2-NetworkSegment2023
network segment PT2-NetworkSegment2024
logical network PrivateTenant3
network segment pool PT3
network segment PT3-NetworkSegment2033
network segment PT3-NetworkSegment2034
Refer to Cisco Nexus 1000V for Microsoft Hyper-V Network Segmentation Manager Configuration
Guide for more information about Microsoft networking concepts, command details, and
implementation.
Refer to Cisco Nexus 1000V for Microsoft Hyper-V Release Notes, Release 5.2(1)SM1(5.1) for new
features and caveats.
Nexus 1000V Switch for Microsoft Hyper-V VSM CLI
Configuration
This section describes how to configure the Nexus 1000V with Hyper-V using the Network
Segmentation Manager (NSM) CLI on the VSM.
Step 1
Create Logical Networks.
A logical network (for example, internet, intranet, DMZ) is a connectivity abstraction that models
separate networks managed by an enterprise. Logical network abstraction hides VLANs and IP subnets
from users (VM network administrators, the tenant administrators, and the server administrators), except
for the fabric administrator managing the physical fabric.
In other words, a logical network is composed of one or more network segment pools and each network
segment pool is a group of VLANS, IP subnets, or VLAN/IP subnet pairs.
The following logical networks configuration shows three private tenants and one public tenant.
nsm logical network PublicTenants
nsm logical network PrivateTentant1
nsm logical network PrivateTentant2
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-2
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Switch for Microsoft Hyper-V VSM CLI Configuration
nsm logical network PrivateTentant3
Step 2
Create Network Segments Pools.
A network segment is associated with a unique broadcast domain and facilitates the availability of the
network resources to a VM. SCVMM uses the VM networks and the VM subnets to provide the isolated
virtual machine networks.
When a Nexus 1000V manages the virtual network, the VMM administrator creates the VM networks
that use external isolation. To create external isolation, the network administrator creates network
segments on the Nexus 1000V and provisions the isolated networks using VLANs and private VLANs.
Note
In Nexus 1000V for Microsoft Hyper-V, a VLAN is not created to define a bridge domain. Instead, a
network segment is created on the VSM. Creating a network segment triggers VLAN auto-creation.
The following configuration shows network segment pools.
nsm
nsm
nsm
nsm
nsm
nsm
Step 3
network
network
network
network
network
network
segment
segment
segment
segment
segment
segment
pool
pool
pool
pool
pool
pool
T1
T2
T3
PT1
PT2
PT3
Add each Network Segment Pool to the Logical Network.
The T1, T2, and T3 segment pools are members of the same public tenant logical network. The PT1, PT2,
and PT3 segment pools are members of unique logical networks.
The following configuration shows mapping for network segment pools into logical networks.
nsm network
member-of
nsm network
member-of
nsm network
member-of
nsm network
member-of
nsm network
member-of
nsm network
member-of
Step 4
segment
logical
segment
logical
segment
logical
segment
logical
segment
logical
segment
logical
pool T1
network PublicTenants
pool T2
network PublicTenants
pool T3
network PublicTenants
pool PT1
network PrivateTentant1
pool PT2
network PrivateTentant2
pool PT3
network PrivateTentant3
Create IP Pool Templates.
Server administrators can manage IP addresses for the virtual environment using IP pool templates. You
can use the IP pool templates to assign a range of IP addresses to hosts and VMs in the Microsoft
SCVMM-managed environment. When creating an IP pool template for a VM network, you can define
a range of IP addresses for VMs managed by SCVMM.
The following configurations shows IP pool templates that were created.
nsm ip pool template PT1-VL2013-IP-Pool
ip address 200.1.3.2 200.1.3.250
network 200.1.3.0 255.255.255.0
default-router 200.1.3.253
nsm ip pool template PT1-VL2014-IP-Pool
ip address 200.1.4.2 200.1.4.250
network 200.1.4.0 255.255.255.0
default-router 200.1.4.253
nsm ip pool template PT2-VL2023-IP-Pool
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-3
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Switch for Microsoft Hyper-V VSM CLI Configuration
ip address 200.2.3.2 200.2.3.250
network 200.2.3.0 255.255.255.0
default-router 200.2.3.253
nsm ip pool template PT2-VL2024-IP-Pool
ip address 200.2.4.2 200.2.4.250
network 200.2.4.0 255.255.255.0
default-router 200.2.4.253
nsm ip pool template PT3-VL2033-IP-Pool
ip address 200.3.3.2 200.3.3.250
network 200.3.3.0 255.255.255.0
default-router 200.3.3.253
nsm ip pool template PT3-VL2034-IP-Pool
ip address 200.3.4.2 200.3.4.250
network 200.3.4.0 255.255.255.0
default-router 200.3.4.253
nsm ip pool template T1-VL101-IP-Pool
ip address 10.101.1.2 10.101.1.250
network 10.101.1.0 255.255.255.0
default-router 10.101.1.253
nsm ip pool template T2-VL102-IP-Pool
ip address 10.102.1.2 10.102.1.250
network 10.102.1.0 255.255.255.0
default-router 10.102.1.253
nsm ip pool template T3-VL103-IP-Pool
ip address 10.103.1.2 10.103.1.250
network 10.103.1.0 255.255.255.0
default-router 10.103.1.253
Step 5
Create Network Segments.
Configure each network segment to be a member of the previously configured network segment pools.
Configure each network segment as an access port with an access VLAN. Import the previously
configured IP pool for each network segment. Publish each network segment.
The Step 9VM Network Creation., page 3-36 commands are added automatically and appear later in this
section when configuring VM networks in SCVMM.
VM networks enable the SCVMM administrator to create an isolated virtual Layer 3 (L3) network. Each
VM network can have multiple VM subnets (virtual L2 domain). Microsoft SCVMM 2012 supports
VLAN-backed and network virtualization (NVGRE)-backed VM networks. The Nexus 1000V supports
VLAN-backed VM networks only.
The following configuration shows network segments that were created.
nsm network segment T1-NetworkSegment101
member-of network segment pool T1
switchport access vlan 101
ip pool import template T1-VL101-IP-Pool
publish network segment
switchport mode access
nsm network segment T2-NetworkSegment102
member-of network segment pool T2
switchport access vlan 102
ip pool import template T2-VL102-IP-Pool
publish network segment
switchport mode access
nsm network segment T3-NetworkSegment103
member-of network segment pool T3
switchport access vlan 103
ip pool import template T3-VL103-IP-Pool
publish network segment
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-4
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Switch for Microsoft Hyper-V VSM CLI Configuration
switchport mode access
nsm network segment PT1-NetworkSegment2013
member-of vmnetwork PT1-NetworkSegment2013
member-of network segment pool PT1
switchport access vlan 2013
ip pool import template PT1-VL2013-IP-Pool
publish network segment
switchport mode access
nsm network segment PT1-NetworkSegment2014
member-of network segment pool PT1
switchport access vlan 2014
ip pool import template PT1-VL2014-IP-Pool
publish network segment
switchport mode access
nsm network segment PT2-NetworkSegment2023
member-of network segment pool PT2
switchport access vlan 2023
ip pool import template PT2-VL2023-IP-Pool
publish network segment
switchport mode access
nsm network segment PT2-NetworkSegment2024
member-of network segment pool PT2
switchport access vlan 2024
ip pool import template PT2-VL2024-IP-Pool
publish network segment
switchport mode access
nsm network segment PT3-NetworkSegment2033
member-of network segment pool PT3
switchport access vlan 2033
ip pool import template PT3-VL2033-IP-Pool
publish network segment
switchport mode access
nsm network segment PT3-NetworkSegment2034
member-of network segment pool PT3
switchport access vlan 2034
ip pool import template PT3-VL2034-IP-Pool
publish network segment
switchport mode access
Step 6
Create Port profiles.
Unlike the Nexus 1000V for ESX, in which a port profile identifies both network policy and network
isolation (VLAN), SCVMM networking decouples this information into a VM network and the port
classification. When the Nexus 1000V is used with Hyper-V, the network administrator creates network
segments to isolate networks. The SCVMM server administrator uses network segments in the resulting
VM networks. The network administrator defines creates port profiles to define port policy. The server
administrator uses port profiles to create a port classification.
To deploy a VM to the virtual access layer, choose the port classification, VM network, and the VM
subnet. When a VM is deployed, a port profile is dynamically created on the Nexus 1000V for each
unique combination of port classification, VM network, and VM subnet. All other VMs deployed with
the same policy to this network reuse the dynamic port profile, which is a combination of network
isolation and network policy.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-5
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Switch for Microsoft Hyper-V VSM CLI Configuration
Note
The generated profile should be neither modified nor inherited in other port profiles.
When a port-attach notification is received, the port profile globally unique identifier (GUID) and
network segment GUID are generated. A GUID provides a unique reference for the port profile and the
network segment.
When a GUID is generated, a new port profile, combining the port profile and the VLAN, is created on
the VSM. This auto-created port-profile is inherited on the interface. If more than one port uses the same
combination of port profile and network segment, the port profile is shared. Port profiles are dynamically
created during the interface attach process.
The following configuration shows port-profiles that were created.
port-profile type vethernet
no shutdown
state enabled
publish port-profile
port-profile type vethernet
no shutdown
state enabled
publish port-profile
port-profile type vethernet
no shutdown
state enabled
publish port-profile
port-profile type vethernet
no shutdown
state enabled
publish port-profile
port-profile type vethernet
no shutdown
state enabled
publish port-profile
port-profile type vethernet
no shutdown
state enabled
publish port-profile
Step 7
T1-PortProfile
T2-PortProfile
T3-PortProfile
PT1-PortProfile
PT2-PortProfile
PT3-PortProfile
Create Uplink Port Profile and Network Uplink.
An uplink port profile is essentially a template that defines a list of network segment pools to be
associated with any (physical) network adapters to which the uplink port profile is applied. An uplink
port profile enables you to specify protocols and port policy for the uplink adapter, using an Ethernet
port profile to be specified.
The following configuration shows uplink port-profiles.
port-profile type ethernet UplinkPortProfile
channel-group auto mode on mac-pinning
no shutdown
max-ports 512
state enabled
nsm network uplink UCS-Uplink
import port-profile UplinkPortProfile
allow network segment pool T1
allow network segment pool T2
allow network segment pool T3
allow network segment pool PT1
allow network segment pool PT2
allow network segment pool PT3
publish network uplink
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-6
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Note
When a new segment is created and tied to an existing network segment pool in the list under the network
uplink, VLANs are inherited in the NSM created profile as shown.
The following configuration shows an Ethernet UCS-Uplink port-profile.
port-profile type ethernet UCS-Uplink
inherit port-profile UplinkPortProfile
switchport mode trunk
switchport trunk allowed vlan 101-103,2013-2014,2023-2024,2033-2034
no shutdown
max-ports 512
description NSM created profile. Do not delete.
state enabled
Note
The Switchport allow vlan add command is not needed.
Nexus 1000V Part 2: SCVMM Configuration
This section provides guidance on how to create the N1000V logical switch (VSM and VEMs) in
Hyper-V through SCVMM.
Step 1
Download Cisco Nexus 1000V Package.
The Nexus 1000V for Hyper-V package (zip file) is available at the download URL location provided
with the software. Complete the following steps to download the package.
Download the Cisco Nexus 1000V for Microsoft Hyper-V package for Microsoft System Center Virtual
Machine Manager (SCVMM) 2012. The package contains the following files:
Step 2
•
Virtual Supervisor Module (VSM) ISO (n1000vh-dk9.5.2.1.SM1.5.1.iso)
•
Virtual Ethernet Module (VEM) MSI package (Nexus1000V-VEM-5.2.1.SM1.5.1.msi)
•
Cisco VSEM Provider MSI package (Nexus1000V-VSEMProvider-5.2.1.SM1.5.1.msi)
•
Cisco SCVMM VM Template (Cisco Nexus1000V VSM Template)
•
Cisco Installer App (Cisco.Nexus1000VInstaller.UI.exe)
Install the Virtual Switch Extension Manager Provider.
To establish communication between SCVMM and the Nexus 1000V VSM, the Virtual Switch Extension
Manager (VSEM) provider must be installed on the SCVMM server.
a. Run the Cisco VSEM Provider MSI package (Nexus1000V-VSEMProvider-5.2.1.SM1.5.1.msi)
that comes with the Nexus 1000V Package.
Follow the link to where the MSI was downloaded and double-click MSI to run it.
b. Follow the prompts as shown in Figure 3-2, Figure 3-3, and Figure 3-4 until the install is
complete.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-7
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-2
Run the MSI Installer
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-8
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-3
Read and Accept the License Agreement
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-9
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-4
Step 3
Select Finish when the Installer completes
Verify that VSEM Provider is installed properly.
Go to Settings > Configuration Providers. Confirm that Cisco Systems Nexus 1000V is listed as a
Configuration Provider.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-10
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-5
Step 4
Cisco VSEM Provider installed
Copy VEM MSI to SCVMM repository.
The VEM is an MSI file that must be placed in the following location on the SCVMM server:
ALLUSERSPROFILE%\Switch Extension Drivers, for example, C:\ProgramData\Switch
Extension Drivers. SCVMM uses the MSI file during the Add host operation to install VEM code on
the host.
Note
Step 5
Do not install VEM code on the SCVMM server; only copy the file to the specified location.
Add VSEM (Connect SCVMM to VSM).
The following procedures add the VSEM that was just installed. This step is required to connect
SCVMM to the VSM in Hyper-V.
In these steps, the login account and the MGMT IP address configured in the VSM are needed to
establish the communication between SCVMM and the VSM. Once the VSEM is added, the
configuration that was created in the CLI of the VSM can be pulled in the SCVMM.
a. Right-click Switch Extension Manager and select Virtual Switch Extension Manager..
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-11
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-6
Add VSEM
b. Add the Connection string and select Run As Account.
10.0.72.101 is the IP address of the VSM created on the Nexus 1110x.
The created account uses the login credentials required to log in to VSM.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-12
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-7
Add VSEM Wizard
Refer to Installing Cisco Nexus 1000v for Microsoft Hyper-V for more information about
creating a Run As Account.
c. Verify that no additional configuration, such as proxy, is required.
Open a browser and test the connection to the VSM. Browse to http://<VSM IP Address>.
Output similar to Figure 3-5 should be seen:
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-13
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-8
Browse to VSM
d. Select the host group to which the VSEM is available.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-14
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-9
Add VSEM Wizard All Hosts
e. Confirm the VSEM settings and click Finish.
Figure 3-10
Add VSEM Wizard Confirm Settings
f. Verify that Virtual Switch Extension Manager is installed.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-15
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-11
Step 6
Verify VSEM is installed
Create Logical Switch in SCVMM.
After VSEM is added (Step 5), do the following:
1.
Create a logical switch on VMM using VSEM.
2.
Define extensions and port profiles for the logical switch.
3.
Create classifications containing the native port profile and a port profile for each extension.
a. Right-click Logical Switch and select Create Logical Switch.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-16
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-12
Create Logical Switch
b. Read the text and click Next.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-17
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-13
Create Logical Switch Getting Started
c. Name the logical switch.
In this case, the hostname of the VSM was used. Use defaults for SR-IOV.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-18
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-14
Create Logical Switch Name
d. Check the previously configured VSEM (V2-HyperV-VSM-P1) and click Next.
The VSEM has the following attributes:
Extension type: Forwarding
Extension Manager: Cisco Nexus 1000V Chassis
Only one virtual switch extension can be selected.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-19
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-15
Create Logical Switch Select VSEM
e. Select Team in the uplink mode field and click Add to add the uplink port profile.
Note
The mode should always be Team, whether using a single uplink or multiple uplinks.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-20
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-16
Create Logical Switch Select Add Uplink
f. Select the uplink port profile and click OK.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-21
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-17
Add Uplink Port Profile
g. Confirm the uplink port profile settings and click Next.
By default, the host group All Hosts is created in Hyper-V. The network sites PT1, PT2, PT3,
T1, T2 and T3 were created during Nexus 1000V CLI configuration.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-22
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-18
Create Logical Switch Note Host Groups and the Network site
h. Specify the Port Classifications and click Next.
Port Classifications must be created in SCVMM and linked to port-profiles created in the VSM.
The port-profiles were created previously in the “Nexus 1000V Switch for Microsoft Hyper-V
VSM CLI Configuration” section on page 3-2; one port classification per port profile was
created. When adding VMs to the logical switch, the port classification and VM network are
selected when configuring network adapters (see VM Deployment).
Refer to Creating Logical Switch in SCVMM in Installing Cisco Nexus 1000V for Microsoft
Hyper-V for additional guidance for creating port classifications.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-23
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-19
Create Logical Switch Specify the Port Classifications
i. In the Summary panel, confirm the settings and click Finish to create the logical switch.
Figure 3-20
Create Logical Switch Specify Confirm Settings
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-24
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
j. Manually refresh the VSEM.
After the Nexus 1000V logical switch is created, manually refresh VSEM to force the updates
to appear in SCVMM.
Figure 3-21
Step 7
Manual Refresh of the VSEM
Add VEMs (Hosts) to the Nexus 1000V.
a. Right-click All Hosts and select Add Hyper-V Hosts and Clusters..
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-25
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-22
Add Hyper-V Hosts
b. Select the appropriate computer location and click Next.
All hosts in the test bed were in a trusted Active Directory domain.
Figure 3-23
Add Hyper-V Hosts Windows Computer Location
c. Click Browse to see a list of Run As Accounts.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-26
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-24
Add Hyper-V Hosts Specify Credentials
d. Select the Run As account created during the Hyper-V install.
The account is different than the Run As account used to install VSEM. The scvmmadmin
account was created in Active Directory and is a domain administrator account for the local
domain.
See the “Microsoft Windows Server 2012 Installation” section on page 2-6 for more
information about the scvmmadmin account.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-27
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-25
Add Hyper-V Hosts Select Run As Account
e. Enter the hostname of each host to add as a VEM and click Next.
Figure 3-26
Add Hyper-V Hosts Enter Hostnames
f. After hosts are discovered, select each host to add and click Next.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-28
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-27
Add Hyper-V Hosts Select the Hosts
g. Assign hosts to a host groups.
Leave Reassociate this host with the VMM environment unchecked and click Next.
Figure 3-28
Add Hyper-V Hosts Assign the Host Group
h. Enable Live Migration and click Next.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-29
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-29
Add Hyper-V Hosts Enable Live Migration
i. Confirm the Settings and click Finish.
Figure 3-30
Add Hyper-V Hosts Confirm Settings
j. Verify All Hosts are seen in the All Hosts group.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-30
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-31
Step 8
Add Hyper-V Hosts Verify All Hosts
Add Each Host to Logical switch.
a. Right-click the host to be added and select Properties.
Figure 3-32
Host Properties
b. Add New Logical Switch.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-31
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
In the Host Properties > Virtual Switches window, select New Virtual Switch and New
Logical Switch to add the host to the Nexus 1000V.
As seen in Figure 3-33, a standard External switch was already created for management. In
Hyper-V, multiple switches can exist on the host.
Figure 3-33
Host Properties New Logical Switch
c. Add physical adapters to the logical switch team.
There are two adapters, VIC Ethernet interface 3 and VIC Ethernet interface 4 that will be used
on each host. Add these to the logical switch.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-32
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-34
Host Properties Add Physical Adapter 1
Add the second physical adapter 2 and hit OK.
Figure 3-35
Host Properties Add Physical Adapter 2
d. Click OK to continue to add host to the logical switch.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-33
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-36
Host Properties Continue to Add Host to Logical Switch
e. Verify that the VEM is installed on the VSM.
Figure 3-37 shows the output seen on the VSM when the VEM is added to the Logical switch.
Figure 3-37
Host added as a VEM
f. After all hosts were added to the logical switch, they are seen as VEMs in the VSM. Execute
show module on the VSM to verify these hosts are seen as VEMs.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-34
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-38
All Host Added as a VEM
g. Verify interfaces are added to Logical Switch.
Because each host has two Cisco VIC Ethernet interfaces, two Ethernet interfaces per host are
seen, along the port-channel interfaces.
These are:
Eth3/1
Eth3/2
Eth4/1
Eth4/2
Eth5/1
Eth5/2
Eth6/1
Eth6/2
Po1
Po2
Po3
Po4
These interfaces and port-channels can get verified by executing show interface brief on the
VSM:
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-35
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-39
Step 9
Show Interface Brief
VM Network Creation .
After the Nexus 1000V Switch for Microsoft Hyper-V Logical switch has been installed, the VM
Networks can get created.
a. Verify the Logical Networks created on the N1000V are seen in Hyper-V.
Figure 3-40
Logical Networks
b. Right-click VM Network and select Create VM Network.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-36
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-41
Create VM Network
c. Create the VM network name and select the logical network.
Figure 3-42
Create VM Network Name
d. Select the network segment.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-37
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
Figure 3-43
e.
Select Network Segment
Confirm the VM network settings.
Figure 3-44
Confirm VM Network Settings
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-38
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Nexus 1000V Part 2: SCVMM Configuration
f. Follow the same steps to create the remaining VM Networks.
Figure 3-45
All VM Networks
g. Verify the network segment are now a “member-of” the correct VM Networks. This line of the
configuration is automatically added to the CLI as noted Step 5Create Network Segments.,
page 3-4.
nsm network segment T1-NetworkSegment101
member-of vmnetwork T1-NetworkSegment101
member-of network segment pool T1
switchport access vlan 101
ip pool import template T1-VL101-IP-Pool
publish network segment
switchport mode access
At this point, the logical switch, including VSM and VEMs, is installed. VMs can now be added to the
logical switch.
Deployment Guidelines
1.
Manually refresh the VSEM. Hyper-V performs a periodic refresh every 30 minutes; changes in
the Nexus 1000V are not automatically updated in Hyper-V. Manually refresh the VSEM to force
updates to show up in SCVMM.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-39
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Adding VMs to Nexus V Switch for Hyper-V Logical Switch
2.
Manually remove NetSwitchTeam. If a host is deleted from SCVMM, NetSwitchTeam is not
removed from the host.
If hosts are removed and added again, the hosts is not added to the logical switch because
NetSwitchTeam still exists on the hosts.
This error is seen in the Jobs section:
Error (25238)
Creating the adapter team failed with error An internal error has occurred trying to contact the
v2-c1b4-p1.vmdc.net server.
WinRM: URL: [http://v2-c1b4-p1.vmdc.net:5985], Verb: [GET], Resource:
[http://schemas.microsoft.com/wbem/wsman/1/wmi/root/scvmm/ErrorInfo?ID=1001]
Check that WS-Management service is installed and running on server v2-c1b4-p1.vmdc.net.
For more information use the command "winrm helpmsg hresult". If v2-c1b4-p1.vmdc.net is a
host/library/update server or a PXE server role then ensure that VMM agent is installed and
running. Recommended Action
ensure the team is functioning correctly and retry the operation
To clear this condition, open Windows PowerShell and do the following:
PS C:\Users\Administrator.VMDC> Get-NetSwitchTeam *
Name
: V2-HyperV-VSM-P12b352411-1eff-4e95-bc84-9f0fb5a339a4
Members : {Ethernet 5, Ethernet 4}
PS C:\Users\Administrator.VMDC> Get-NetSwitchTeam | Remove-NetSwitchTeam
After the obsolete NetSwitchTeam is removed, the host can be added to the Logical switch.
3.
Verify that hosts ports show up in VSM. In UCSM, each host had two MGMT and two DATA
vNICs. The DATA vNICs were used for NetSwitchTeam. On one or two occasions, when a host was
added to the Nexus 1000V logical switch, only one interface showed up in the VSM for that VEM,
even though both interfaces were selected. The procedure to add the host to the Nexus 1000V had
to be repeated, and the interface that did not show up had to be added to the newly created Nexus
1000V connection.
This can be verified by logging into the VSM and looking at the output from show interface brief.
Look for the VEM and the ports. A show port-channel summary should shows those ports added
to the port-channel.
4.
Close and reopen SCVMM. On occasion, odd behavior was seen, such as hosts not responding to
messages. Connecting to hosts using Remote Desktop Protocol (RDP) showed that the hosts were
in the correct state. Closing and reopening the SCVMM app cleared this state. This is most likely a
winrm issue that needs further investigation when it happens again.
5.
Create a Gold Template for SCVMM. After three to four weeks, SCVMM became unstable. A
new SCVMM was created, and a Gold Template was generated from that VM, in case the instability
recurs.
6.
Refer to Cisco Nexus 1000V for Microsoft Hyper-V Installation Guide, Release 5.2(1)SM1(5.1) for
information about creating the Nexus 1000V logical switch in Hyper-V SCVMM.
Adding VMs to Nexus V Switch for Hyper-V Logical Switch
This section shows the process for adding Virtual Machines to the Nexus 1000V Switch for Microsoft
Hyper-V Logical switch.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-40
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Adding VMs to Nexus V Switch for Hyper-V Logical Switch
Step 1
Go to the VM Properties page.
Right-click the VM and select Properties.
Step 2
Select Hardware Configuration and select the adapter to add to the logical switch.
There are two adapters in the test VMs. One connects to the Microsoft external switch for Management
and the other connects to the Nexus 1000V.
Step 3
Select the VM network.
On the network adapter properties page, click Browse to see a list of available VM networks.
Figure 3-46
Step 4
Select a VM Network
Select the classification.
After selecting the VM network, click the Classification drop-down and select the classification profile.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-41
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Adding VMs to Nexus V Switch for Hyper-V Logical Switch
Figure 3-47
Select Classification
Step 5
After selecting the classification, click OK.
Step 6
Verify the Virtual Machine has been deployed by issuing a “show interface virtual” from the CLI of the
VSM:
V2-HyperV-VSM-P1# show interface virtual
------------------------------------------------------------------------------Port
Adapter
Owner
Mod Host
------------------------------------------------------------------------------Veth1
Net Adapter
PT1-vSTC1-VL2013
3
V2-C1B3-P1
Veth2
Net Adapter
PT1-vSTC1-VL2014
3
V2-C1B3-P1
Veth3
Net Adapter
PT3-vSTC1-VL2033
3
V2-C1B3-P1
Veth4
Net Adapter
T1-vSTC1-VL101
3
V2-C1B3-P1
Veth5
Net Adapter
PT2-vSTC1-VL2023
4
V2-C1B4-P1
Veth6
Net Adapter
PT2-vSTC1-VL2024
4
V2-C1B4-P1
Veth7
Net Adapter
PT3-vSTC1-VL2034
4
V2-C1B4-P1
Veth8
Net Adapter
T2-vSTC1-VL102
4
V2-C1B4-P1
Veth9
Net Adapter
PT1-vSTC2-VL2013
5
V2-C2B1-P1
Veth10
Net Adapter
PT1-vSTC2-VL2014
5
V2-C2B1-P1
Veth11
Net Adapter
PT3-vSTC2-VL2033
5
V2-C2B1-P1
Veth12
Net Adapter
T3-vSTC1-VL103
5
V2-C2B1-P1
Veth13
Net Adapter
PT2-vSTC2-VL2023
6
V2-C2B2-P1
Veth14
Net Adapter
PT2-vSTC2-VL2024
6
V2-C2B2-P1
Veth15
Net Adapter
PT3-vSTC2-VL2034
6
V2-C2B2-P1
Veth16
Net Adapter
LM-Windows Server 2012 -01
4
V2-C1B4-P1
Veth17
Net Adapter
LM-Win2008-02
4
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-42
V2-C1B4-P1
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Adding VMs to Nexus V Switch for Hyper-V Logical Switch
Deployment Guidelines
1.
Select the correct interfaces when adding network adapters. In UCSM, each host has two
MGMT and two DATA vNICs. From the Windows OS perspective, four VIC interfaces are
presented. Ensure that the correct interfaces are selected when adding the hosts to virtual switches.
Check the MAC addresses.
2.
Refer to Connecting VMs to Logical Switch in Cisco Nexus 1000v for Microsoft Hyper-V
Installation Guide, Release 5.2(1)SM1(5.1) for more information.
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-43
Chapter 3
Nexus 1000V Switch for Microsoft Hyper-V Configuration
Adding VMs to Nexus V Switch for Hyper-V Logical Switch
Microsoft Hyper-V and Nexus 1000V Switch for Microsoft Hyper-V within a VMDC Architecture
3-44