PERFORMANCE IMPROVEMENT OF AC-DC POWER FACTOR CORRECTION CONVERTERS FOR DISTRIBUTED POWER SYSTEM

PERFORMANCE IMPROVEMENT OF AC-DC POWER FACTOR CORRECTION CONVERTERS FOR DISTRIBUTED POWER SYSTEM
PERFORMANCE IMPROVEMENT OF AC-DC POWER
FACTOR CORRECTION CONVERTERS FOR
DISTRIBUTED POWER SYSTEM
MATADA MAHESH
Dissertation submitted in partial fulfillment of the requirements for the
degree of
Doctor of Philosophy
In
Electrical Engineering
Under the supervision of
Prof. Anup Kumar Panda
Department of Electrical Engineering
National Institute of Technology, Rourkela
October 2011
PERFORMANCE IMPROVEMENT OF AC-DC POWER
FACTOR CORRECTION CONVERTERS FOR DISTRIBUTED
POWER SYSTEM
Matada Mahesh
Department of Electrical Engineering
National Institute of Technology, Rourkela
PERFORMANCE IMPROVEMENT OF AC-DC POWER
FACTOR CORRECTION CONVERTERS FOR
DISTRIBUTED POWER SYSTEM
MATADA MAHESH
Dissertation submitted in partial fulfillment of the requirements for the
degree of
Doctor of Philosophy
In
Electrical Engineering
Under the supervision of
Prof. Anup Kumar Panda
Department of Electrical Engineering
National Institute of Technology, Rourkela
October 2011
Declaration
I hereby declare that the work which is being presented in the thesis entitled
“Performance Improvement of AC-DC Power Factor Correction Converters For
Distributed Power System” in partial fulfillment of the requirements for the award of the
degree of DOCTOR OF PHILOSOPHY, submitted to the Department of Electrical
Engineering of National Institute of Technology, Rourkela, Orissa is an authentic record of
my own work under the supervision of Prof. A. K. Panda, Electrical Engineering
Department. I have not submitted the matter embodied in this thesis for the award of any
other degree or diploma of the university or any other institute.
Date: 19th October, 2011
Matada Mahesh
DEPARTMENT OF ELECTRICAL ENGINEERING
NATIONAL INSTITUTE OF TECHNOLOGY, ROURKELA
ORISSA, INDIA – 769008
CERTIFICATE
This is to certify that the thesis entitled “Performance
Performance Improvement of AC-DC
Power Factor Correction Converters For Distributed Power System”,
System
being
submitted to the National Institute of Technology, Rourkela by Mr. Matada Mahesh,
Mahesh Roll
No. 507EE006 for the award of Doctor of Philosophy in Electrical Engineering, is a bona fide
record of research work carried out by him under my supervision and guidance.
The candidate has fulfilled all the prescribed requirements
The Thesis which is based on candidate’s own work, has not submitted elsewhere for a
degree/diploma.
In my opinion, the thesis is of standard required for the aw
award
ard of a Doctor of Philosophy
degree in Electrical Engineering.
Prof. A. K. Panda
Supervisor
Department of Electrical Engineering
Engineering, National Institute of Technology
Rourkela – 769008
Email: [email protected]
BIO-DATA OF THE CANDIDATE
Name
: Matada Mahesh
Date of Birth
: 24th June, 1974
Permanent Address
: “Pancha Peeta”, S M V Nagar,
III Cross (Right), Kappagal Road,
Bellary, Karnataka – 583103.
Email
: [email protected]
ACADEMIC QUALIFICATION
•
Pursuing Ph. D in Electrical Engineering, National Institute of Technology, Rourkela.
•
M. Tech in Power Electronics Engineering, B M S College of Engineering, Bangalore.
•
B. E. in Electrical and Electronics Engineering at Vijayanagar Engineering College,
Bellary, Karnataka.
RESEARCH PUBLICATIONS
JOURNAL
1. Matada Mahesh, and A. K. Panda, “Improved dynamic response of single-phase AC-DC
power factor correction converter,” International Journal in Power System Optimization and
Control (IJPSOC-09), vol. 1, no. 1, pp. 43-48, Jan. 2009.
2. Matada Mahesh, and A. K. Panda, “High-power factor three-phase AC-DC soft-switched
converter incorporating zero-voltage transition topology in modular systems for high-power
industry applications,” IET - Power Electron., vol. 4, no. 9, pp. 1032-1042, Nov. 2011.
3. Matada Mahesh, and A. K. Panda, “Increase of efficiency of a AC-DC PFC boost converter
by a novel soft-switching technique”, Intl. Journal of Electric Power Components and
Systems, Taylor and Francis Publication, accepted for future publication.
CONFERENCE
1. Matada Mahesh, and A. K. Panda, “Two sided PWM control of switching power factor
correction AC-DC converter”, IEEE-International Conf. on Industrial Technology, (IEEEICIT’09), pp. 1-6, Monash University – Gippsland, Australia, Feb. 2009.
2. Matada Mahesh, and A. K. Panda, “Simulation of Improved Dynamic Response in Active
Power Factor Correction Converters” 13th IEEE VSI / VLSI Design and Test Symposium,
VDAT’09, VLSI Society of India. pp. 231-236, Wipro Campus, Bangalore, India, 2009.
3. Matada Mahesh, A. K. Panda, and H. N. Pratihari, “A novel soft-switching boost power
factor correction converter with an active snubber”, International Conf. Power Electronics
Machines and Drives( IET – PEMD’10), pp. 1-6, Brighton, UK, 2010.
4. Matada Mahesh, A. K. Panda “Implementation of a ZVT based Power Factor Correction
Converter”, IEEE-International Power and Energy Conf., (IPEC’10), pp. 693-698,
Singapore, 2010.
ACKNOWLEDGEMENTS
I express my sincere gratitude to my academic and research advisor Prof. Anup Kumar
Panda for his excellent guidance, research attitude, encouragement, and kind co-operation
throughout the course of my research work. I consider myself fortunate to have worked under his
guidance. My family and I are greatly indebted to him.
I am grateful to my Doctoral Scrutiny Members, Prof. B. D. Subudhi, Prof. K. B.
Mohanty, and Prof. G. S. Rath, for their valuable suggestions and numerous help towards my
research work.
I am especially indebted to my past teammates in my Power Electronics research group,
Mr. Swapnajit Pattnaik and Mr. K. Aroul with their meaning-full discussions and moral
support. I would like to thank my present research friends Mr. Y. Suresh, Mr. M. Suresh,
and Mr. T. Ramesh for extending their technical and personal support. It has been a great
pleasure to work with such a helpful, hard working, and creative group.
It has been a great pleaser to work in the Center for Power Electronics and Drives (PED)
Laboratory of the Electrical Department. I would like to acknowledge the PED Laboratory staff,
technician Mr. Rabindra Nayak and Mr. Chotilal, without them the work would not have
been progressed.
I am grateful to the concerned authorities of my parent Institution, Manipal Institute of
Technology, Manipal for sanctioning of leave for my PhD studies.
Without my family’s sacrifice and support, this research work would not have been
possible. I would like to express my greatest admiration to my mother for her sacrifice and positive
encouragement that she showered on me throughout this research work. I shall also always remain
indebted to my parent in-laws for the continuous support they gave me and especially for taking
care of my son and supporting my wife (in her busy schedule) during my absence which helped me
to complete this thesis in time. I also thank my brother, Mr. M Bharatish, sister in-laws for
extending support and encouragement given during my difficult times of my research work.
My son Master Nenad suffered a lot in my absence from home and I thank him profusely
for his sense of understanding and unwavering faith in me.
Finally, I would end this note by placing my wife Mridula J at the bottom of my heart for
the moral and emotional support she gave along with the tolerant effort she put to make this
research work complete.
I dedicate this work to all my family members and relatives.
Above all, I salute the divine powers, the Almighty for their abundant blessings
for giving me strength and energy to complete this study successfully.
Matada Mahesh
Dedicated with reverence to memories of my Father,
Late M. M. Jagadeeshaiah
A Great Philosopher, Humanist and Educationist.
Table of Contents
Title
Page
No.
Abbreviations……………………………………................. v
Nomenclature……………………………………................. vi
Abstract……………………………………………………..
ix
List of Figures…………………………………....................
xi
List of Tables……………………………………………….. xvii
Chapter 1
Introduction………………………………………………...
1
1.1
Research background………………………………………..
2
1.2
Effects of non-linear loads in the power grid………………..
5
1.2.1
Definition of power factor…………………………………... 7
1.2.2
Compliance and regulations of line current harmonics……... 9
1.3
Power factor correction techniques………………………….
9
PFC control methods………………………………………...
11
Performance parameters of PFC converter………………….
12
1.4.1
Low bandwidth and its effect on the active PFC converter…
12
1.4.2
Losses in PFC converter…………………………………….. 16
1.3.1
1.4
1.4.2.1 MOSFET and diode loss calculation………………………... 18
1.5
Soft switching converter topologies……………………........
23
1.6
Modular system……………………………………………...
30
1.7
Motivation…………………………………………………...
32
1.8
Objectives…………………………………………………… 34
1.9
Dissertation structure………………………………………... 34
Chapter 2
2.1
2.1.1
Dynamic Performance Improvement of PFC Converter
by Enhancement in PWM Technique…………………….. 37
Introduction………………………………………………….
38
Design analysis for PFC feedback control system…………..
39
Current Loop Compensator………………………………….
39
i
2.1.2
Voltage feedforward loop compensation……………………
42
2.1.3
Voltage loop compensation………………………………….
44
PWM control………………………………………………...
46
2.2.1
Issues surrounding PWM control……………………………
47
2.2.2
Comparison of PWM and two sided PWM techniques……... 48
2.2
Operation of proposed two sided PWM control ……………. 49
2.3
2.3.1
Time domain analysis……………………………………….. 51
2.3.2
Design procedure of 1-phase AC-DC PFC boost converter..
53
2.3.2.1
Boost Inductor……………………………………………….
54
2.3.2.2
Output capacitor……………………………………………..
55
2.3.2.3
Output voltage ripple limit…………………………………..
55
2.3.2.4
Holdup time requirement……………………………………
56
Simulation and Experimental Results……………………….
56
2.4.1
Single phase PFC AC-DC boost converter………………….
56
2.4.2
Three-phase PFC AC-DC converter in Modular system……
62
Summary…………………………………………………….
66
Application of ZVT to PFC Boost Converter with
Passive Auxiliary Circuit…………………………………..
67
Introduction………………………………………………….
68
2.4
2.5
Chapter 3
Circuit description and PFC feedback system………………. 70
3.1
3.2
3.1.1
Circuit description …………………………………………..
70
3.1.2
PFC feedback system………………………………………..
71
Operating principle of proposed converter………………….. 73
ii
Design procedure……………………………………………. 84
3.3
3.3.1
Snubber inductor Lsn………………………………………… 84
3.3.2
Snubber and storage capacitors CSn and CSt…………………
84
3.3.3
Storage inductor Lst………………………………………….
85
3.4
Simulation and Experimental results………………………... 85
3.5
Comparison of efficiency curves……………………………. 93
3.6
Summary…………………………………………………….
Chapter 4
94
Application of novel ZVT to PFC Boost Converter with
Active Auxiliary Circuit…………………………………… 95
Introduction………………………………………………….
96
4.1
Topology description………………………………………..
98
4.2
Operating principle and analysis…………………………….
99
4.3
Design procedure……………………………………………. 108
Boost converter components………………………………...
109
4.3.1.1 Boost inductor Lb……………………………………………
109
Output Capacitor C0…………………………………………
110
4.3.1.3 Active snubber circuit components………………………….
110
4.3.1
4.3.1.2
4.4
Special features of the proposed converter………………….. 113
4.5
Simulation and experimental results………………………...
114
4.5.1
Response of resonant elements………………………….......
115
4.5.2
Main switch SW1…………………………………………….
115
4.5.3
Auxiliary switch SW2 and boost diode DB………………….
116
Performance of proposed converter…………………………
119
4.6
iii
4.7
Summary…………………………………………………….
122
Chapter 5
High Power Factor Three-Phase Soft-Switched AC-DC
PFC Converters in Modular System……………………...
123
Introduction………………………………………………….
124
A 1.5 kW three-phase AC-DC PFC boost converter with
126
passive snubber circuit in modular system…………………..
5.1
5.1.1
Converter block schematic and functionality……………….. 126
5.1.2
Schematic design and component selection…………………
129
5.2
Simulation and experimental results………………………...
131
5.3
A 1.5 kW three-phase AC-DC PFC boost converter with an
active snubber circuit in modular system……………………
140
5.4
Simulation and experimental results………………………...
142
5.5
Performance characteristics…………………………………. 144
5.6
Summary…………………………………………………….
Chapter 6
Summary and future scope………………………………... 150
6.1
Summary…………………………………………………….
6.2
Future Scope………………………………………………… 155
149
151
6.2.1
Dynamic response in low power applications………………. 155
6.2.2
Design of PFC converter at very high switching frequency
156
6.2.3
Unbalanced input voltage in modular approach………..
156
References…………………………………………………..
157
Research publications……………………………………...
176
iv
ABBREVIATIONS
AC
Alternating Current
ACMC
Average Current Mode Control
CCM
Continuous Conduction Mode
DC
Direct Current
DCM
Discontinuous Conduction Mode
DPS
Distributed Power System
EMI
Electro Magnetic Interference
ESR
Equivalent Series Resistance
IC
Integrated Circuit
IEEE
Institute of Electrical And Electronics Engineers
MOSFET
Metal Oxide Semiconductor Field Effect Transistor
NIT
National Institute of Technology
PF
Power Factor
PFC
Power Factor Correction
PSIM
POWER-SIM (Power Electronics And Drives Simulator)
PWM
Pulse Width Modulation
RMS
Root Mean Square
SC
Semiconductor
THD
Total Harmonic Distortion
ZCS
Zero Current Switching
ZCT
Zero Current Transition
ZVS
Zero Voltage Switching
ZVT
Zero Voltage Transition
Note: Abbreviations are used and mentioned as and when it is required in the theses.
v
NOMENCLATURE
∆IL
Inductor ripple current
A
Scaled down sine signal input to multiplier of ACMC
B
Output signal of voltage compensator in ACMC
C
Output singal of low-pass-filter in ACMC
Cin1
Line input filter capacitor
Cin2
High frequency bypass capacitor after bridge rectifier
Co
Output capacitor of boost converter
cos ø
Cosine of the angle between input voltage and fundamental current
Cr
Resonance capacitor in soft switching converters
Csn
Snubber capacitor
Cst
Storage capacitor
Cvf
Capacitor in voltage loop of ACMC
D
Duty cycle
D1-D4
Diodes in bridge rectifier and/or auxiliary diodes in proposed converters
DB
Boost diode
dnom
Nominal duty ratio of semiconductor switch
Dpeak
Maximum value of transistor duty cycle
Dr
Resonant diode
Eon_M
Turn-on energy losses of MOSFET
fs
Switching frequency of converter
I1_RMS
RMS value of the fundamental input line current
IB_RMS
RMS value of the body diode current of MOSFET
ID
Drain current of MOSFET
iDB
Boost diode current
IF_avg
Average value of forward current of diode
vi
IF_B
forward current through body diode of MOSFET
IF_RMS
RMS value of forward current diode
Iin
Input line current
Iin__peak(max)
Maximum value of input current to converter
Io
Output load current
IRMS
RMS value of the input line current
Irr
reverse recovery current of the boost diode
iSW
current through the MOSFET switch
Kd
Distortion factor lies between zero and one
Kθ
Displacement factor lies between zero and one
Lb
Boost indcuor of boost converter
Lin
Input line filter inductor
Lmin
Minimum value of boost inductor
Lr
Resonant inductor in soft-switching converters
Lsn
Snubber inductor
Lst
Storage inductor
PAPP
Apparent power
PC_DM
Condcution losses of body diode of MOSFET
PCM
Conduction losses of controlled device MOSFET
Pout
Output power of boost converter
PReal
Real Power
RDson
On-state resistance of MOSFET
Rin
Resistance of source impedance
RLoad
Load resistance
SW
Controlled switch MOSFET of converter with passive snubber circuit
vii
SW1
Controlled main switch in proposed PFC converter with active snubber
SW1_D
Body diode of main switch of boost converter
SW2
Controlled auxiliary switch in PFC converter with active snubber
SW2_D
Body diode of auxiliary swich in soft-switched boost converter
T
Time period of a switching cycle
tfv
Fall time of voltage across MOSFET during turn-on
tri
Rise time of current in MOSFET during turn-on
Vac
AC line input voltage
Vcsn
Voltage across snubber capacitor
Vcst
Voltage across storage capacitor
VD_DB
Voltage across the body-diode of MOSFET
VD0
Diode on-stage voltage
VDS
Drain-source voltage of MOSFET
VDrr
Voltage across boost diode during reverse recovery interval
Vin
Input of boost converter or output of bridge rectifier
Vin_peak(min)
Minimum value of input peak voltage
Vo
Output voltage
VRMS
RMS value of voltage
Vsw1
Voltage across main switch in boost converter
Vsw2
Voltage across auxiliary switch in boost converter
X
Voltage compensator block in ACMC
Y
Current controller block in ACMC
Z
Feed-forward or low pass filter block in ACMC
Zs
Input source line impedance
Note: Notations are used and mentioned as and when it is required in the theses.
viii
ABSTRACT
In present situation, the increase in the utilization of computers, laptops,
uninterruptable power supplies, telecom and bio-medical equipments has become
uncontrollable as its growth is rising exponentially. Hence, increase in functionality of such
equipments leads to the higher power consumption and low power density which provided a
large market to distributed power systems (DPS). The development of these DPS posed
challenges to power engineers for an efficient power delivery with stringent regulating
standards; this is the motivation and driving force of this research work. The objective is to
minimize the switching losses of front-end converters employed in DPS, with the primary
aim of achieving nearly unity power factor operation of converters.
Single-phase and three-phase rectifiers are increasingly used in the field of alternating
current – direct current (AC-DC) power converters as front-end converters in DPS. For
power factor correction (PFC) stage, conventional single-phase AC-DC PFC boost converter
is the most suitable topology because of its inherent advantages. These PFC boost converters
exhibit poor dynamic regulation of output voltage owing to low pass filter in the voltage
feedback loop. Research effort has been made to mitigate this problem of AC-DC PFC boost
converters. An extended pulse width modulation switching technique has been investigated
and proposed especially for single-phase and three-phase AC-DC PFC boost converters to
improve the dynamic response of output voltage during transient periods.
Current trends demand the miniaturization of front-end converters in DPS. One of the
several methods to achieve the same is operation of PFC converter at higher switching
frequency; this in turn increases the switching losses of a PFC converter. Suitable soft
switching techniques are generally employed to minimize these switching losses. Also these
techniques alleviate the semiconductor switches of PFC converters from extra voltage and/or
current stresses. In this research work, two types of zero voltage transition (ZVT) techniques
ix
in PFC boost converters for medium as well as for high power converters are proposed: (1)
Boost converter with passive auxiliary circuit and (2) Boost converter with active auxiliary
circuit. These PFC converters are designed to operate for 400 V, 100 kHz, 500 W and/or
1500 W specifications. The operation principles and a detailed steady-state analysis of each
ZVT based AC-DC PFC boost converters are described and presented.
The proposed
converters are more reliable and achieve high efficiency with low total harmonic distortion.
Besides improving circuit topology and efficiency, effort is made to achieve power
expandability and higher power density for the front-end converters in DPS by modular
approach. In addition, this approach also provides higher reliability, easier thermal
management, and maintainability.
The proposed converters presented in this research work are well defined by their
mathematical modeling and its modes of operations. The prototypes of all the proposed
converters are developed in the Power Electronics and Drives laboratory, National Institute of
Technology, Rourkela.
Their feasibility are verified and confirmed by simulation and
experimental results.
x
List of Figures
Fig. 1.1
Structure of basic distributed power system………………………………….
3
Fig. 1.2
Image of DPS for telecom server system…………………………………….. 4
Fig. 1.3
Single-phase AC-DC bridge rectifier with bulk capacitor………………........ 6
(a) Schematic diagram, (b) Experimentally obtained input voltage and
current waveforms, and (c) Measurement of harmonics on bridge
rectifier + filter capacitor………………………………………………...
Fig. 1.4
6
Methods of power factor correction techniques………………………............ 11
(a) Passive power factor correction technique, and (b) Active power factor
correction technique……………………………………………………...
11
Fig. 1.5
Block diagram of ACMC PFC boost…………………………………………
13
Fig. 1.6
Graph showing all possible dynamic operation of PFC boost converter……..
14
Fig. 1.7
Two-stages in cascaded approach to improve dynamic response of PFC
converter………………………………………………………………...........
15
Fig. 1.8
switching characteristics of MOSFET………………………………………..
Fig. 1.9
Unavoidable switching losses in converters………………………………….. 23
(a) Conventional hard switching, and (b) Resonant converter switching..….
21
23
Fig. 1.10
Conventional boost converter PWM switch cell………………………........... 24
Fig. 1.11
Resonant switch configurations………………………………………………. 25
(a) General topology, (b) Half-wave configuration, and (c) Full –wave
configuration…………………………………………………..................
Fig. 1.12
Basic topologies of soft switching resonant converters………………………
25
26
(a) Full-wave ZCS quasi-resonant boost converter, (b) Half-wave ZCS
quasi-resonant boost converter, (c) Full-wave ZVS quasi-resonant boost
converter, and (d) ZVS Multi-resonant boost converter…………………
xi
26
Fig. 1.13
Basic topologies of ZVT and ZCT PWM converters…………………............ 29
(a) ZVT PWM switching cell, (b) Boost ZVT PWM switching cell, (c)
ZCT PWM switching cell, (d) Boost ZCT PWM switching cell, and
(e) Boost ZVT-ZCT PWM switching cell………………………………......
29
Fig. 1.14
Block diagram of three identical PFC converters in modular approach...........
31
Fig. 2.1
Model of boost PFC converter using PWM switch model……………...........
40
(a) Exact model, and (b) Simplified equivalent model at high frequency......
40
Fig. 2.2
Magnitude and phase response of exact model and simplified model of boost
PWM switch……………………………………………………….................. 41
Fig. 2.3
Circuit diagram of current loop error……………………………………........
42
Fig. 2.4
Second order low-pass filter in feedforward loop……………………………. 43
Fig. 2.5
Voltage loop error amplifier configuration in PFC feedback system…….......
45
Fig. 2.6
Small signal model of outer voltage loop for constant power loads………….
45
Fig. 2.7
Gain of pulse width modulator…………………………………….................. 46
Fig. 2.8
Comparison of two sided and single sided PWM techniques………………...
Fig. 2.9
Two sided latched PWM schematic for PFC AC-DC boost converter………. 50
Fig. 2.10
Theoretical timing diagram for proposed two sided latched PWM…………..
Fig. 2.11
Comparison of dynamic response of output voltage for a step change in
49
51
input voltage (a) 150 VRMS to 220 VRMS, (b) 220 VRMS to 150 VRMS……........... 58
Fig. 2.12
Experimentally obtained dynamic response of conventional and two sided
PWM techniques for an input change from (a) and (b) 150 VRMS to 220 VRMS,
(c) and (d) 220 VRMS to 150 VRMS…………………………………..................
Fig. 2.13
Comparison of dynamic response of output voltage for step change in load
from (a) 50% to full load
Fig. 2.14
60
(b) Full load to 50% load……………………
61
Output voltage comparison of two sided PWM technique and conventional
PWM technique for a load current change from 50% of full load to full-load. 61
xii
Fig. 2.15
Hardware prototype of single-phase PFC AC-DC converter with two sided
PWM technique…………………………………………………....................
Fig. 2.16
Dynamic response of output voltage for step change in load for three-phase
modular system………………………………………………….....................
(a) Conventional PWM technique in modular system, and (b) Two sided
PWM technique in modular system………………...……………………
Fig. 2.17
Proposed single-phase AC-DC PFC boost converter with passive snubber
70
Inductor current averaging block diagram in PFC AC-DC converter with
passive snubber……………………………………………………………….
Fig. 3.3
64
(b) % THD and (c) % efficiency………………. 65
circuit…………………………………………………………………………
Fig. 3.2
64
Experimental performance characteristics of proposed three-phase modular
system (a) Power factor
Fig. 3.1
62
72
Key waveforms of the proposed soft switching PFC AC-DC boost converter
with passive snubber circuit………………………………………………….. 74
Fig. 3.4
(a) Converter operation in interval (t0-t2)……………………………………..
75
(b) Converter operation in interval (t2-t3)…………………………………….. 76
(c) Converter operation in interval (t3-t4)……………………………………..
77
(d) Converter operation in interval (t4-t5)…………………………………….. 78
(e) Converter operation in interval (t5-t6)………………………………..........
79
(f) Converter operation in interval (t6-t7)………………………………..........
80
(g) Converter operation in interval (t7-t8)…………………………………….. 81
(h) Converter operation in interval (t8-t9)…………………………………….. 82
(i) Converter operation in interval (t9-t10)…………………………………….
Fig. 3.5
Simulation results of resonant elements of proposed passive snubber
circuit…………………………………………………………………………
Fig. 3.6
82
87
Experimental results of resonant elements of proposed passive snubber
circuit…………………………………………………………………………
xiii
88
Fig. 3.7
Simulation results of switching characteristics of switch SW of
proposed converter………………………………………………………........
Fig. 3.8
88
Experimental results of switching characteristics of switch SW of proposed
converter………………………………………………………........................ 89
Fig. 3.9
Simulation results of soft switching of boost diode in proposed passive
snubber converter……………………………………………………………..
Fig. 3.10
Experimental result of soft switching of boost diode in proposed passive
snubber converter……………………………………………………………..
Fig. 3.11
89
90
(a) Simulated voltage and current switching waveforms of auxiliary diode
D1 and Experimental voltage and current switching waveforms of
auxiliary diode D1………………………………………………………… 91
Fig. 3.12
(a) Simulated voltage and current waveforms of auxiliary diode D3, and (b)
Experimental voltage and current waveforms of auxiliary diode D3……..
Fig. 3.13
Experimental input voltage input current waveforms of proposed 1-phase
PFC AC-DC converter with passive snubber circuit……………………........
Fig. 3.14
92
Prototype of proposed 1-phase AC-DC PFC converter with passive snubber
circuit…………………………………………………………………………
Fig. 3.15
91
92
Comparison of efficiency curves of single-phase conventional hard switched
PFC converter and proposed single-phase soft switched PFC converter…….
93
Fig. 4.1
Proposed 1-phase PFC AC-DC boost converter with active snubber circuit...
99
Fig. 4.2
Key waveforms of the proposed soft-switch PFC AC-DC boost converter
with active snubber circuit……………………………………........................
Fig. 4.3
100
(a) Equivalent circuit of converter operation during interval (t0-t1).............. 101
(b) Equivalent circuit of converter operation during interval
(t1-t2)………. 101
(c) Equivalent circuit of converter operation during interval (t2-t3)………… 102
(d) Equivalent circuit of converter operation during interval (t3-t4)………… 104
(e) Equivalent circuit of converter operation during interval (t4-t5)………… 104
(f) Equivalent circuit of converter operation during interval (t5-t6)………… 106
xiv
(g) Equivalent circuit of converter operation during interval (t6-t7)………… 106
(h) Equivalent circuit of converter operation during interval (t7-t8)………… 107
Fig. 4.4
(a) Simulation result waveforms and (b) Experimental result waveforms….
115
Fig. 4.5
Simulation and experimental switching characteristics of a main switch SW1
116
Fig. 4.6
Simulation and experimental switching waveforms of auxiliary switch SW2
and boost diode DB…………………………………………………...............
Fig. 4.7
Simulation results of input voltage and magnified input current waveforms
of proposed converter with active snubber for an input voltage of 215 VRMS
Fig. 4.8
117
118
Experimental input voltage and input current waveforms of proposed singlephase PFC AC-DC converter with active snubber circuit for an input voltage
of 215 VRMS…………………………………………………………………...
Fig. 4.9
119
Comparison of efficiency curves of conventional hard switched PFC
converter, soft switched PFC converter with passive snubber and proposed
soft switched converter with active snubber circuit…………………………..
Fig. 4.10
120
Hardware prototype of single-phase PFC boot converter with an active
snubber circuit………………………………………………………………... 121
Fig. 5.1
Block schematic of proposed 1.5 kW soft-switched PFC boost converter in
modular system……………………………………………………………….
Fig. 5.2
Simulation layout of proposed three-phase AC-DC PFC boost converter
with passive snubber circuit in modular system ……………………………..
Fig. 5.3
134
Experimental input currents (iA, iB, iC) at (a) full-load (b) 75% of full-load
(c) 50% of full-load and (d) 25% of full-load for an input voltage of 245 VRMS
Fig. 5.6
134
Experimental input voltage and current waveforms of a proposed 3-phase
AC-DC PFC converter with passive snubber circuit in modular approach......
Fig. 5.5
133
Simulated input voltage and current waveforms of a proposed three-phase
AC-DC PFC converter with passive snubber circuit in modular approach…..
Fig. 5.4
127
136
Output voltage response of a proposed converter under change in load
(a) From full-load to half load (b) From half load to full-load………………
xv
137
Fig. 5.7
Comparison of efficiency curves of proposed three-phase soft-switched
converter with three-phase hard-switched converter…………………………
Fig. 5.8
138
Photograph of proposed 3-phase AC-DC PFC boost converter with passive
snubber circuit………………………………………………………………... 139
Fig. 5.9
Block schematic of proposed 1.5 kW soft-switched PFC boost converter
with active snubber circuit in modular system……………………………….. 141
Fig. 5.10
Simulation layout of proposed three-phase AC-DC PFC boost converter
with active snubber circuit in modular system ………………………………. 143
Fig. 5.11
Simulated input current (magnified) iA, iB, iC and input A-phase voltage VA
waveforms at 25% of full load for an input voltage of 215 VRMS……............. 144
Fig. 5.12
Experimental input voltage and current waveforms. Input currents iA, iB and
iC at (a) full load (b) at 75% of full load (c) 50% of full load (e) 25% of full
load and input phase voltage VA. …………………………………………….. 145
Fig. 5.13
Comparisons of variation of THD as a function of load power of three-phase
AC-DC PFC boost converters………………………………………………... 145
Fig. 5.14
Comparisons of variation of PF as a function of load power of three-phase
AC-DC PFC boost converters………………………………………
Fig. 5.15
146
Comparison of efficiency curves of proposed three-phase soft-switched
converters with hard switched three-phase AC-DC converter as a function of 147
load power…………………………………………………………………….
Fig. 5.16
Output voltage response under change in load (a) From full load to half load
(b) from half load to full load………………………………………................ 148
Fig. 5.17
Photograph of proposed 3-phase AC-DC PFC boost converter with active
snubber circuit………………………………………………………………... 148
xvi
List of Tables
Table 1.1
Specification and components used in the test circuit of Fig. 1.3……….....
5
Table 2.1
Specification of PFC AC-DC boost converter……………………………..
54
Table 2.2
Components employed in the proposed…………………………………....
57
Table 2.3
Specifications of three-phase AC-DC PFC converter in modular
approach…………………………………………………………………….
63
Table 3.1
Conduction state of auxiliary diodes D1-D4 in a proposed…………………
Table 3.2
Components used in the Proposed 1-phase PFC with passive snubber……. 86
Table 4.1
Specification of proposed single phase soft switched and hard switched
PFC AC-DC boost converter……………………………………………….
Table 4.2
108
Parameter set employed in the evaluation tests of the soft switched active
PFC converter………………………………………………………………
Table 5.1
Specifications of 1500 W Three-phase AC-DC PFC proposed converter…
Table 5.2
Parameter set employed in the evaluation tests of the proposed PFC ACDC boost with passive snubber circuit……………………………………..
Table 5.3
73
111
130
131
Parameter set employed in the evaluation tests of the 3-ph AC-DC PFC
boost converter with an active snubber…………………………………….
xvii
142
Chapter 1
Introduction
o Research background
o Effects of non-linear loads in the power grid
o Power factor correction (PFC) techniques
o Performance parameters of PFC converter
o Soft switching of converter topologies
o Modular system
o Motivation
o Objectives
o Dissertation structure
1
Introduction
1.1 Research Background
In present situation, the increase in the utilization of computers, laptops, telecom, biomedical equipments, and uninterruptable power supplies is uncontrollable as its growth is
rising exponentially. Hence, increase in functionality of such equipments leads to the higher
power consumption and low power density. On the other hand, today’s industry/market
demands the miniaturization of power sources with higher power density at reasonable price.
Therefore, the power supplies for the telecom and computer applications are required to
provide more power with less cost and small size.
To achieve these requirements, distributed power system (DPS) is widely adopted.
Hence, DPS has evolved from a conventional approach (such as centralized system) by
employing isolated DC-DC converters to intermediate bus architecture using non-isolated
converters [1, 2].
The requirements aimed by DPSs continue to expand beyond its initial goal of dealing
with power distribution problems associated with computer and telecom applications. While
centralized power system continues to be a cost effective solution for some applications,
additional important factors such as the easier thermal management, higher reliability, need
of tight regulation during load current transients, reduced current ripple and the increased
quantity of voltages required on a board, have spawned a multitude of distributed power
solutions. The basic configuration of a typical DPS is shown in Fig. 1.1. In this system, the
front end converters used in DPS applications adopt a two stage approach. In the first stage,
the front-end converters connected in parallel provide the power factor correction (PFC) and
the second stage provides isolation and highest regulation of the required output DC voltage.
As a result, the overall performance of the entire system strongly depends on the choice and
2
design of individual stages [2-4]. Because of this modular approach, DPS system has many
advantages over centralized power system. It is widely adopted for telecom and computer
server applications because of its inherent advantages such as higher reliability, modularity,
high power density, easier thermal management and easy maintainability [5-10]. Because of
these benefits of DPS over the centralized power system, installations of DPSs are rising up
especially for power sources to telecom and computer applications.
Front -end ac - dc converter
AC Line
On board
Converter
DC / DC
Converter
High Volt
VRM
Low Volt
VRM
DC / DC
Converter
POL
Converter
POL
Converter
DC / DC
Converter
400 V DC
48V DC
Fig. 1.1 Structure of basic distributed power system
Now a day, high compact, flexible DPS servers for telecom, data networks and
computer applications are available in market. A typical image of DPS for telecom server is
Buy SmartDraw!copies
print this are
shown in Fig. 1.2. At the bottom of the server, front-end
(AC/DC)purchased
converter
modules
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
placed. It can be seen that several modules are placed side by side to provide the energy
demanded by the load. After the front-end converter modules, the following stage converters,
which are known as load converters on the circuit boards on the equipment modules are
located on the upper berth of the rack. Therefore, these load converters are also called on3
board converters. As the size of the racks is fixed for a given DPS, it is desired to have more
space for the equipments such as telecom boards or computer servers. Thus, the size and
volume of the power supply has to be minimized.
Fig. 1.2 Image of DPS for telecom server system
On the other hand, increase in number of equipments
in apurchased
system
more power
Buy SmartDraw!copies implies
print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
consumption. Hence, more power is to be supplied from power sources within less volume,
which means higher power density. Moreover, DPS for server system has a fixed rack width,
such as 19’’, 23’’ or 26’’, 7ft frame work, and the power modules are vertically slide inside
the rack, as shown in the bottom part of the Fig. 1.2 . By reducing the profile of power
modules, more modules could fit into the rack and provide more power. Therefore, 1.75’’
width of module becomes a standard size in a rack, as shown in the bottom part of the Fig.
1.2. By reducing the profile of power modules, more modules could fit into the rack and
4
provide more power. Therefore, 1.75’’ width of module becomes a standard profile from
presently existing power modules.
1.2 Effects of non-linear loads in the power grid
Obtaining power from the utility power grid can be done in different ways. Most of
the electronic equipments connected to the electricity power grid draw high peak
discontinuous non-sinusoidal line current rather than smooth sine wave current. This current
is composed of number of harmonic currents, which flow through electricity power grid as
well as in the equipment itself. Fig. 1.3 shows the illustration of experimental set-up of
single-phase alternating current-direct current (AC-DC) bridge rectifier followed by bulk
capacitor. The schematic of single-phase bridge rectifier shown in Fig. 1.3(a) has been tested
in the laboratory. The converter of such arrangement draws a discontinuous non-sinusoidal
peak current and hence the presence of harmonic currents in the AC-DC rectifier circuit as
well as in the power grid to which this converter is connected. The narrow peak input current
occurs due to the short on-time duration of bridge rectifier diodes as the diodes conduct only
when instantaneous input voltage is greater than the output voltage. Table 1.1 shows the
specification and component values of the AC-DC rectifier circuit under test. The results
obtained from the test circuit are shown in Fig. 1.3(b), which shows the input line voltage and
line current waveforms of supply frequency 50 Hz. Fig. 1.3(c) represents the harmonic
spectrum of the line current.
Table 1.1: Specification and components used in the test circuit of Fig. 1.3
Sl. No
1
2
3
4
5
6
7
Parameter
Vac
Source impedance, Zs
Output voltage, Vo
Output power, Pout
Load
Co
Diodes (in bridge rectifier)
5
Value
230 V(rms)
Rin = 0.4 Ω, Lin = 800 μH
320 V (5% ripple)
300 W
Constant power load
450 μF/600 V, ESR = 150 mΩ
25NSR120 SQ, Rd=20 mΩ
(a) Schematic diagram
(b) Experimentally obtained input voltage and
current waveforms
(c) Measurement of harmonics on bridge rectifier + filter capacitor
Fig. 1.3 Single-phase AC-DC bridge rectifier with bulk capacitor
drawing peak current
The distortion in the input voltage signal is due to the impedance drop across the
source impedance caused by this peak current. In general, the power factor (PF) of a bridge
rectifier configuration is dependent on the parasitic resistance of the components, type of the
load connected and the size of the capacitor. In the circuit shown above, output capacitor of
value 1.3 μF/W is used. This is selected based on a thumb rule, 1 μF-2 μF / Watt for power
supplies [11]. For the illustration shown in Fig. 1.3, the resulting PF is equal to 0.35. This
low PF and hence, the degradation of the power quality is not only due to the phasedifference between the fundamentals of the voltage and current but also due to the presence
of high harmonic current. Thus, a bridge rectifier followed by a bulk capacitor is an
6
inefficient process, which produces a large spectrum of harmonic signals that may interfere
with other equipments connected to the same power grid.
Summarizing, a conventional AC-DC bridge rectifier with bulk capacitor has following main
drawbacks:
o It generates harmonics and electromagnetic interference (EMI) in the power grid.
o It has low PF which results in reduced efficiency of the system.
o It increases the operating temperature in the transmission lines as well as in the other
equipments connected to the grid.
o It reduces the capacity of line to provide a maximum power to the load.
Thus, in order to overcome the above mentioned drawbacks of a converter, it is essential
to improve the power factor of a system.
1.2.1 Definition of power factor
The concept of power factor is a measure of how well the power from the utility grid is
utilized. Its value lies in the range between 0 and 1, and it is computed as the ratio of the real
power to the apparent power.
PF =
Real power
Apparent power
(1.1)
Real power is measured in watts and is the power required to do real work. Assuming
that the line voltage is a perfect sinusoidal, the real power (PReal) is defined as the product of
the fundamental of the voltage (VRMS), the fundamental of the current (I1_RMS) and the phase
displacement (cos ø) between these two fundamentals:
P
=V
I
cos(  )
Real
RMS 1_RMS
(1.2)
Apparent power (Papp.), is measured in volt-amps, is the real power plus the reactive power,
7
which makes up the power required to produce the magnetic fields needed to produce real
work. It is the product of the RMS voltage (VRMS) and RMS current (IRMS):
(1.3)
P
=V
I
App.
RMS RMS
by definition (1.1), and from (1.2) and (1.3), the PF can be expressed as:
I
PF =
1_RMS
I
PF = K
cos(  )
(1.4)
RMS
cos(  )
d
(1.5)
where K is the distortion factor given by,
d
I
1_RMS
K =
=
d
I
RMS
I
1_RMS
(1.6)
2
2
2
I
+I
+....+ I
1_RMS 2_RMS
n_RMS
where ‘n’ is the order of the nth harmonic current.
The displacement power factor K is the cosine of the displacement angle between the
θ
fundamental input current and the input voltage,
K = cos(  )
θ
hence, (1.5)
(1.7)
=>
(1.8)
PF = K d K 
A measure of harmonic content in a circuit is total harmonic distortion (THD) defined
as the square root of the ratio of the sum of all of the squared higher-order harmonics to the
amplitude of the fundamental harmonic. THD is defined as:
I
THD =
2
2
2
+I
+....+ I
2_RMS 3_RMS
n_RMS
I
(1.9)
1_RMS
From equations (1.5), (1.6) and (1.9), we get the relationship between the THD and the PF:
8
PF =
1
1+ THD
2
cos(  )
(1.10)
Therefore, the objective of a power factor correction circuit is to maintain a negligible
phase angle between the input voltage and current and to keep the harmonics content to a
minimum level.
1.2.2 Compliance and regulations of line current harmonics
As early as 1980, the efforts made in the various power quality surveys by various
utilities research organizations, corporate industrial campus, and commercial building
installations [12,13] revealed that for better understanding of various power quality problems
and to provide cost effective solution to specific problems, monitoring of power quality is the
first important step.
Considering the various effects of harmonics and its problems, discussed in the
previous section, Electricity regulatory commissions and utilities, all over the world have
started imposing penalty for harmonics dumping by the user into the supply lines. In India,
Central Electricity Authority through its statutory body Central Electricity Regulatory
Commission has notified Institute of Electrical and Electronics Engineers (IEEE) Std. 51992--(revised version of IEEE Std 519-1981) through legislature [14], about the allowable
limits for harmonics in the electrical system. It is essential for both the utility and user
industry to understand the related standard and to know the limits specified therein. The
IEEE Standard 519 imposes limits on particular harmonics as well as on the THD of the
current waveform. The detailed recommended practices of harmonic voltage and current
limits have well reported in reference [14].
1.3 Power factor correction techniques
As mentioned earlier, due to the proliferation of non-linear loads in the distribution
9
systems, current and voltage harmonics are generated in the power grid. Therefore, there is a
need to compensate these undesired distortions in order to minimize their effects on the
distribution system and hence to improve its efficiency. Broadly, two methods have been
come across to eliminate the harmonic related problems and to enhance the overall
performance of the grid or distribution systems, namely passive method, and active method.
These two harmonic filtering methods are presented and briefly discussed in the following
sections.
In passive PFC approach, an L-C filter is inserted between the AC line and the input
port of the diode rectifier of AC-DC converter [15-16] as shown in Fig. 1.4(a).
This
technique is simple and rugged but has bulky size and heavy weight components. One filter
is to be connected to eliminate one particular harmonic and hence system becomes bulky and
expensive in order to eliminate significant amount of harmonics. Moreover, the power factor
cannot be very high in this technique.
In active PFC converter techniques, power electronics DC-DC converter is employed
and operated at high frequency to shape the input line current as sinusoidal as possible. The
simplified basic block diagram of active PFC technique is shown in Fig. 1.4(b).
The
commonly used topologies as DC-DC converter in active PFC converter are boost, buck,
buck-boost, flyback, cuk, or sepic topologies [16-20]. In active PFC technique, the input
power factor can reach nearly unity and the AC-DC interface of power converter emulates a
pure resistor [15-23]. The boost converter is widely used as a DC-DC converter for PFC
applications and is most suitable topology for PFC pre-regulator in telecom applications
because of its inherent properties [16, 23, 24]. Hence the DC-DC converter of boost topology
is the basic interest of our research and our significance of novel techniques are applied to
boost converter in PFC pre-regulator system.
10
The active PFC methods have many
advantages over the passive PFC techniques high power factor, reduced harmonics, smaller
size and weight. Hence our research is focused in the area of active PFC converter to achieve
near unity input power factor and hence to increase quality of power in the grid.

Passive power factor correction technique
Input voltage and input current response of passive
PFC technique
(a)

Active power factor correction technique
Input voltage and input current response of active
PFC technique
(b)
Fig. 1.4 Methods of power factor correction techniques
1.3.1 PFC control methods
The PFC control methods are broadly classified into two groups [16, 24-25]. 1)
Active control and 2) Automatic control of line current. Active control method is associated
with continuous conduction mode (CCM) of the inductor current and hence it is referred as
CCM shaping techniques. On the other hand, the automatic control is used when converter
operates in discontinuous conduction mode (DCM).
For medium and high power
applications, CCM is suitable because of low EMI and better input current waveform [16,
11
24]. The DCM method is employed for low power applications, i.e. 300 W or less.
Furthermore, the active control method is classified as follows:
(a) Charge control, (b) Hysteresis mode control,
(c) Average current mode control
(ACMC), (d) Peak current mode control and e) Non-linear carrier control.
Each control strategy has its own merits and demerits based on the topology of the
DC-DC converter employed in PFC converter. ACMC is the fact of standard technique used
in industry today for the boost AC-DC PFC converter because of its advantage of less THD,
improved noise and easy to shape input current waveform [16, 24, 26-31].
Fig. 1.5 shows the block diagram of ACMC based single-phase PFC boost converter.
The feedback system has two control loops. Namely, voltage control loop and current control
loop. In Fig. 1.5, block ‘X’ represents the voltage loop, which is also referred as outer loop
and regulates the output voltage that is higher than the peak value of input voltage. Block ‘Y’
is the inner current loop which is much faster loop. In current control loop, current tracking
forces the average value of boost inductor current to track the reference current so that it has
the same shape as that of rectified input voltage [32, 33]. This task gives the input a nearly
unity power factor. Block ‘Z’ is basically a low pass filter, which provides the voltage feedforward signal to the multiplier. This block causes power input of the AC-DC PFC converter
to remain constant at a specified level (determined by the load) irrespective of the changes in
the line voltage. The magnitude of feedforward signal is proportional to the RMS value of
the input voltage.
1.4 Performance parameters of PFC converter
1.4.1 Low bandwidth and its effect on the active PFC converter
In the approach to meet international standard regulations and recommendations, such
as IEC 100-3-2, IEE-519, in high quality rectifiers, the main effort is devoted to the quality of
12
AB
C2
Fig. 1.5 Block diagram of ACMC PFC boost
converter
the input current waveform. But the dynamic response of the output voltage in such
converters is sacrificed. This is due to the fact that a low-pass filter has to be placed in the
output voltage feedback loop when the bulk capacitor is used at the output terminals of PFC
converter [30, 32, 33]. This low pass filter in the voltage feedback loop is needed to reduce
the THD of the input line current and hence the improved input power factor of overall
system.
This makes the poor dynamic response of a converter. For the applications,
especially power supplies to air-craft, bio-medical equipments and defense etc, the dynamic
response of power supplies cannot be neglected. The most possible operating modes within
the PFC boost converter are discussed in this section. The trade-off between output capacitor
Co and voltage loop feedback capacitor Cvf, pointed in Fig. 1.5 has been reported in reference
[29]. This is essentially based on the effect of output capacitor Co and voltage loop feedback
13
capacitor Cvf employed in ACMC PFC boost converter, and which can be analyzed on two
dimensional graph as presented in Fig. 1.6.
In the linear design region, a very high output capacitor valued along with lower
feedback capacitor is used to have the advantage of fast dynamic operation with low ripple on
the output voltage. This is the commonly used mode in PFC converters. Hence, earlier
design has been stated on this linear region to avoid any undesirable, unknown phenomena
inside PFC converter due to the shortage in other operating modes information and analysis.
Fig. 1.6 Graph showing all possible dynamic operation of PFC boost converter
Based on the nonlinear design models, new stable and unstable operation regions have
been identified by authors reported in references [29, 35-37]. The progressed research in
improving the power density, a new stable design regions are identified for a medium output
capacitor values and slightly higher feedback capacitors than that used in linear region
design. A good performance has been noticed with improvement in dynamic response.
However, this leads to the use of a second stage DC-DC converter to obtain regulated output
14
voltage as this approach has higher output ripple voltage.
Unstable region and highly
distorted regions also have been detected which result in asymmetrical input current
waveform and increased amplitude in the output voltage ripple.
In some worst case
conditions, input current is seen to be non-sinusoidal current, this is due to the saturation of
feedback amplifier in voltage control loop.
The concept of improvement in the dynamic regulation and to decrease the bulk
capacitor size can be expressed from the simple example. A second DC-DC converter is
cascaded with the first converter, with the bulk capacitor placed in between as shown in Fig.
1.7. Due to the two stage power processing, system efficiency depends on the efficiencies of
both stages and obviously efficiency of entire system will be much lower than that of each
stage also the controlling of the complicated power circuit cannot be neglected.
Fig. 1.7 Two-stages in cascaded approach to improve dynamic response
of PFC converter
Practically speaking, the dynamic response of PFC converter is mainly restricted by
low bandwidth of voltage loop control in the feedback system. Several other methods have
been proposed to improve the dynamic response of PFC converters. The extension method of
two stage approach discussed above is proposed in reference [34], in which first stage is
having dual output voltage of equal magnitude and same is fed to the second stage converter.
The main idea in this method is to reduce the value of output capacitor and hence exhibits
increased power density and improved dynamic response with no penalty in the efficiency of
15
converter. This method can be applied to all other possible topologies of DC-DC converter in
PFC AC-DC rectifiers.
In reference [38], authors have proposed novel dynamic
improvement based on dual controller method. In this technique, the voltage control block
has two loops. One loop is having low bandwidth which is active during steady state
operation and other loop is having high bandwidth which is active during transient response
of a system. Only one loop will be operating at any instant of time. The better dynamic
performance can be achieved with this method but the additional auxiliary circuit is
incorporated to drive either of two voltage loops to transit from steady state to transient or
vice versa lead to the complexity in the control circuit.
The simple novel idea is introduced in reference [39], in which the PFC boost
converter is of soft switching. In this proposed method, voltage loop has a variable gain, with
small steady state error and to achieve wide bandwidth with sufficient phase margin. The
compensation network is optimized dynamically to achieve a satisfactory result during
transient period. It has been noticed that, the transient response from full-load to low load is
improved by 31% when compared with the conventional pulse width modulation (PWM)
control.
The novel two sided PWM control is proposed in our research and is discussed in
chapter 2 of this thesis to improve the dynamic response of PFC boost converter.
1.4.2 Losses in PFC converter
For application like DPS, high power density and low profile begin to be the standard
approach.
Since, the volume of passive components of the converter reduce with the
increasing of the switching frequency, the converters are operating at higher switching
frequencies. It is still questionable that PFC is able to operate at such a high switching
frequency.
In a conventional PFC boost converter, because of the CCM operation, large
16
diode’s reverse recovery current flows. Therefore PFC converter has large switching loss and
is not able to work at high switching frequency. Furthermore, especially at low input line
voltage condition, a large conduction loss is caused by input diode bridge and MOSFET onstate resistance due to high line current level.
One of the major issues in operating the PFC converter at high switching frequency is
the occurrence of switching loss during switching transient period. Although conduction loss
approximately remains same for all different switching frequencies, switching loss increases
proportionally to the switching frequency. Hence, to enable the converter to operate at higher
switching frequency and to improve the efficiency, switching loss must be eliminated or
minimized. In the past years, much research and efforts have been done to minimize the PFC
converter switching loss as well as conduction loss.
The active power switch used in the PFC converter is one of the most eminent sources
for power loss. The device losses are broadly classified into three categories: conduction
losses, switching losses and blocking losses. The blocking losses are also referred as leakage
losses and are normally being neglected. Metal oxide semiconductor field effect transistor
(MOSFET) is the active switching device used in the boost converter of our proposed
research work; hence, hereafter the discussion on losses is applicable to MOSFET in boost
converter unless it is specified in the thesis. The conduction loss of the MOSFET is the
current square times the on-state resistance of the device. On the other hand, switching loss
is due to the overlapping of the voltage and current waveforms during switching transition.
This switching loss is approximated as the half the drain voltage times the inductor current
over the switching time [40-43]. The switching loss of MOSFET also includes the loss due
to output (drain-source) capacitance.
The charge is stored in the output capacitor of
MOSFET device. This stored charge is dissipated during turn on transition of MOSFET and
17
this is calculated as half the output capacitance times the square of drain-source voltage times
the switching frequency. The other losses also exist in the converter due to MOSFET body
diode conduction loss, control circuit and gate drive loss.
A new concept based on energy balance condition is reported to calculate the
switching loss due to the output capacitance of MOSFET [44-47]. The relationship between
output capacitance and switching loss of MOSFET is found as a combined ratio which can’t
be separated into two terms; The result obtained from this method shows that switching
energy loss can remain same and is given by 0.5 (ID)(VDS) (tfall+trise), as the total of switching
and output capacitance losses [43]. On the other-hand, the effect of output capacitance of
MOSFET affects the rise and fall times over the switching period. The switching losses in
each semiconductor device of the converter are calculated and the converter is to be designed
to eliminate or to minimize the losses to improve the overall efficiency of the converter.
1.4.2.1 MOSFET and Diode loss calculation
1.4.2.1.1 Conduction losses
Conduction losses in power MOSFET are calculated using an MOSFET
approximation with the drain-source on-state resistance RDSon.
vDs (iD)=RDSon (iD) (iD)
(1.11)
vDs and iD are drain-source voltage and the drain current respectively. The typical value of
RDSon can be read from the device data-sheet diagram.
Therefore, the instantaneous value of MOSFET conduction losses is:
pCM(t) = vDs (iD) = [RDSon] iD2(t)
(1.12)
By integrating the above equation, over the period of cycle, the average value of the
MOSFET conduction losses can be obtained as,
18
1 T
1 T
2
2
PCM   0 pCM (t ) dt   0 RDSon iD (t ) dt  RDSon I DRMS
T
T
(1.13)
where IDRMS is the RMS value of the MOSFET on-state current.
The conduction losses of the anti-parallel diode of MOSFET are also considered as it
conducts for short duration of operation of the PFC converter topology proposed and
described in chapter 4. The conduction losses of body diode of MOSFET can be calculated
using a diode approximate equivalent circuit which is a series connection of voltage source
VD0 representing diode on-state voltage and a diode on-state resistance RDSon, VD_DB being the
voltage across the diode and iF_B the current through the body diode:
vD_DB = vD0 + RDSon (iF_B)
(1.14)
The instantaneous value of power loss due to body diode conduction is given by,
2
pC_DB (t) = vD_DB (t) iF_B (t) = (vD0 ) iF _B (t) + RD iF_B
(t)
(1.15)
If IB_RMS is the RMS value of body diode current, the average value of body diode conduction
losses over a period of switching cycle T is
PC_DB =
1 T
1 T
pC _ DB (t ) dt   [vD 0 iF _ B (t )  RD iF2 _ B (t ) ] dt  vD 0 I F _ Bavg  RD I F2 _ BRMS

T 0
T 0
(1.16)
In the same way, the conduction loss of the main or boost diode of converter can be
calculated and is given by,
PCD =
1 T
pCD (t ) dt  vD I F _ avg  RD I F2 _ RMS
T 0
(1.17)
where, PCD is the total conduction losses of boost diode.
IF_avg and IF_RMS are average and RMS values of forward current flowing through diode under
consideration respectively.
1.4.2.1.2
Switching losses and gate drive losses
19
The switching loss is the sum of the switching losses during turn-on and turn-off
processes of the MOSFET. Whenever the boost diode in PFC boost converter switches off,
the reverse recovery current of that diode flows through the MOSFET as soon as MOSFET
turns on. Hence the turn-on losses of MOSFET is the sum of switch–on energy loss without
considering the boost diode reverse recovery effect and switch on energy dissipation caused
by reverse recovery current of boost diode in the MOSFET. To have clarity in the calculation
of total switching losses within the MOSFET device, a switching characteristics of a
MOSFET shown in Fig. 1.8 is considered. Fig. 1.8(a) presents the drain-source voltage VDS
and drain current iD waveforms without considering the reverse recovery current of boost
diode in a converter.
The qualitative overview of the instantaneous power loss of a
MOSFET, which is a product of device voltage and current waveforms, is shown in Fig.
1.8(b), while Fig 1.8(c) shows the reverse recovery current switching effects of the boost
diode on the switching losses of the MOSFET during turn-on process. The total turn-on
energy losses, Eon of the MOSFET is approximately equal to the sum of total energy enclosed
by the triangle during turn-on process of Fig. 1.8(b) and the total energy stored in the boost
diode shown in Fig. 1.8(c).
 tri  t fv 
  Qrr (VDS )
Therefore, Eon _ M  VDS ( I D _ on ) 
 2 


(1.18)
where, tfv is the voltage VDS fall time and tri is the current ID rise time of MOSFET during
turn-on process.
The turn-off energy losses in the MOSFET can be calculated in the similar manner.
From Fig. 1.8(b), considering the turn-off transition of MOSFET,
 trv  t fi 

Eoff _ M  VDS ( I Doff ) 
 2 


(1.19)
20
where trv is the rise time of the MOSFET drain-source voltage and tfi is the fall time of the
MOSFET drain current iD.
Turn-on energy in the boost diode consists of mostly of reverse recovery energy, denoted by
EonD: Hence, It can be calculated as follows,
Eon _ D  
tri tfv
0
vD (t ) iF (t ) dt  Eon _ Drr 
1
Qrr VDrr
4
(1.20)
VDrr is the voltage across the boost diode during reverse recovery (not shown in Fig. 1.8).
Fig. 1.8 switching characteristics of MOSFET
semiconductor device
21
For the worst case condition, this voltage is approximated as the output voltage
(higher) level of boost converter.
The switch off losses within the diode is normally
neglected. Hence, the switching losses in the MOSFET and the boost diode are the product of
switching energies and the switching frequency of the converter. Therefore,
PSW _ M  ( Eon _ M  Eoff _ M ) f s
(1.21)
PSW _ D  ( Eon _ D  Eoff _ D ) f s  Eon _ D ( f s )
(1.22)
Gate drive losses of the parameters of the MOSFET are defined by the gate charge Qg, the
gate driving voltage Vg and switching frequency fs as,
Pg = Qg Vg fs
(1.23)
hence, the total loss in the converter can be expressed as,
Ptotal_loss= PCM + PC_DB + PCD + PSW_M + PSW_D+Pg
(1.24)
Ptotal _loss= PC + PSW+Pg
(1.25)
where, PC = PCM+PC_DB+PCD and PSW = PSW_M+PSW_D
The overall efficiency of a converter is determined by a ratio of output power delivered to the
load to the input power of the converter. Hence,
converter 
(1.26)
Pout
Pin
where, Pout is the power consumed by the load and Pin is the power input to the
converter. Overall efficiency η can be improved by reducing the losses in a converter. The
approximate switching losses of conventional hard switched converter and that of resonant
converter switching losses are shown in Fig. 1.9.
By the application of suitable soft
switching technique in a converter, the unavoidable switching losses can be minimized.
However, the stress and strain of a switching device during turn-on and turn-off processes
22
shown in Fig. 1.9(a) and Fig. 1.9(b) can also be eliminated by employing suitable soft
switching techniques such as ZVT, ZCT and active clamp topologies. When switching
frequency becomes very high, a significant compromise has to be made between conduction
loss and frequency related losses such as, switching loss and gate drive loss. Several soft
switching driver circuits for converters are proposed in the past for improvement in the
efficiency of a converter [48-52].
(a) Conventional hard switching
characteristics
(b) Resonant converter switching
characteristics
Fig. 1.9 Unavoidable switching losses in converters
1.5
Soft switching converter topologies
In 1980s, lots of research efforts were established towards the use of resonant
converters. The basic circuit diagram of conventional boost PWM switch is shown in Fig.
1.10. A fundamental deviation from the conventional forced turn-off approach is the ‘zero
current’ switching technique reported in references [53, 54]. In probing for a general zero
23
current switching (ZCS) technique, authors have proposed the ‘resonant switch’ in reference
[55]. By simply replacing the power switches in conventional PWM converters by resonant
switches, new families of converters called ‘quasi-resonant’ converters were introduced.
This new family of converters can be viewed as hybrid converters between PWM converters
and resonant converters. Diverse forms of quasi-resonant concepts in PWM converters have
been reported in literature [56-78]. These quasi-resonant converters utilize the principle of
inductive or capacitive energy storage and transfer in a similar fashion as PWM converters
and the circuit topologies also resemble those of PWM converters. It is to be noted that, in
Fig. 1.10 Conventional boost converter PWM switch cell
these converters, an LC tank circuit always present near the power switch and is used not
only to obtain the sinusoidal voltage or current waveforms of the power switch but also to
store and transfer energy from input to output in a manner similar to the conventional
resonant converters. A resonant inductor Lr is connected in series with active switch SW to
achieve ZCS operation and resonant capacitor Cr in parallel with active switch SW provides
ZVS operation. In general, the actual implementation of the resonant switch can be either a
‘half-wave’ configuration or a full-wave configuration.
The basic resonant switch
configurations for ZCS operation of a switch SW are shown in Fig. 1.11 (a)-(c). The resonant
diode Dr in series with the active switch SW creates ZCS half wave configuration as this
24
arrangement provides unidirectional current and on the other hand, the resonant diode Dr
connected in anti-parallel with switch SW provides ZCS full-wave configuration. Similarly,
the half-wave and full-wave configuration of ZVS resonant converters can be obtained and
have been reported in reference [79].
It has been found that, the resonant converters
employing half-wave resonant switches have DC voltage conversion ratios sensitive to load
Fig. 1.11 Resonant switch configurations (a) General topology (b) Half-wave
configuration and (c) Full-wave configurations
variation. However, the DC voltage conversion ratios can be made load independent by
simply modifying the resonant switch into a full-wave configuration [66]. Fig. 1.12 shows
the basic topologies of soft switching resonant converters. In the ZCS quasi-resonant switch
converter shown in Fig. 1.12(a) and Fig 1.12(b), the boost diode DB operates with ZVS and
the active switch SW and resonant diode Dr operate with ZCS. On the other hand, the active
switch SW and resonant diode Dr operate in ZVS and boost diode DB operate with ZCS in
full-wave ZVS quasi-resonant converter shown in Fig 1.12(c).
There are some drawbacks in quasi-resonant converters which are discussed above,
such as, the limitation of maximum switching frequency in ZCS quasi-resonant converters.
This is because of the capacitive turn-on switching loss caused by the discharge of the output
capacitance of the switch in ZCS quasi-resonant converters. Since, this loss is proportional to
the switch output capacitance, switching frequency and proportional to the square of the input
voltage. It has a particularly significant effect on the performance of the ZCS quasi-resonant
25
(d) Full-wave ZCS quasi-resonant boost
converter
(c) Half-wave ZCS quasi-resonant boost
converter
(b) ZVS Multi-resonant boost
converter
(a) Full-wave ZVS quasi-resonant boost
converter
Fig. 1.12 Basic topologies of soft switching resonant converters
converters. In addition to this, the current level flowing through the circuit components will
be higher than the required values of input current and load current. ZVS quasi-resonant
converters do not suffer from turn-on switching loss, and therefore can operate at higher
frequencies than ZCS quasi-resonant converters. Since, they do not circulate a significant
amount of energy; they can achieve extremely high efficiencies. However, their applications
are very limited because of design constraints imposed by the characteristics of today’s
semiconductor devices that limit their input voltage and load range [80]. The multi-resonant
converters are the resonant converters which overcome the above mentioned drawbacks of
ZVS and ZCS quasi-resonant converters. In multi-resonant converters, soft switching is
achieved by unique arrangement of a multi-element network that absorbs all major parasitic
in the resonant circuit, including the active switch output capacitance, diode junction
26
capacitance and transformer leakage inductance. The ZVS based multi-resonant converter is
shown in Fig. 1.12(d). This unique arrangement of parasitic element in the converter allows
these converters to operate at high switching frequencies with favorable soft switching
conditions for all the semiconductor devices in a converter, i.e. with zero voltage turn-on of
the switch(es) and zero voltage turn-off of the diode(s). Like any other ZVS converters, ZVS
multi resonant converters require constant off-time, variable-frequency control, but they can
also be modified to operate at a constant frequency [56, 81,82]. But the major drawback of
multi-resonant converters is the increased circulating energy which is caused by a continuous
resonance of the multi-element resonant circuit. The effect of this circulating energy is
particularly significant for applications with wide input voltage range. Also, since multiresonant converters regulate the output voltage with constant off-time, their frequency
increases as the load decreases and the input voltage increases.
Therefore, frequency
dependent losses increase. This increased conduction losses (due to the increased circulating
energy) and increased frequency-dependent losses significantly affect the partial-load
efficiency. However, for properly designed converters that reduce the circulating energy,
high partial-load efficiency can be maintained down to 30% - 40% of full load [56].
Apart from these resonant converters, other soft switching techniques known as active
clamp converters for AC-DC PFC converters as well as for DC-DC converters have been
reported in the literature [83-87]. These techniques achieve soft switching to main switch as
well as to other switching devices in a converter, but the soft switching process under zero
voltage switching is load dependent. Hence, the voltage and current ratings of the switches
employed in these active-clamped converters are higher than the source voltage and load
current levels [88-89].
To reduce the semiconductor device switching losses and to overcome some of the
27
drawbacks of a converter discussed above, passive snubber techniques came into the research
[71, 90-96]. The soft switching by adding auxiliary passive circuit (which consists of only
passive switches and passive elements) in association with conventional DC-DC PWM
converter achieves ZVS or/and ZCS of active switch as well as other passive semiconductor
devices employed in auxiliary circuit. These soft switching techniques with passive snubber
circuits are popular and still rolling in the industrial research because of their simplicity in
design and increased efficiency of converters. However, some of the lossless passive snubber
circuits proposed in references [71, 92,94, 96] suffer from increased device stress and hard
switching of boost switch and boost diode at higher frequency operation of a boost converter.
The succeeding and most attractive soft switching techniques in these days are zero
voltage transition (ZVT) and zero current transition (ZCT) PWM techniques which are most
commendable ones among other existing soft switching techniques [47, 79, 97-98] and
considerable research effort has been come across in this ZVT and ZCT soft switching
technique [47, 72, 79, 97-117]. In ZVT and ZCT soft-switching techniques, one auxiliary
active switch, passive devices and elements forming an auxiliary circuit is connected in
parallel with the conventional boost active switch. The basic ZVT and ZCT topologies are
shown in Fig. 1.13. This arrangement provides a partial resonance period created by a shunt
auxiliary circuit to achieve ZCS or ZVS during the switching transition. This technique
retains the advantages of a conventional PWM converter and quasi-resonant converter
because once the switching transition is over, the converter operation reverts to the regular
PWM operation mode. Hence, the features of the ZCT PWM and ZVT PWM soft switching
converters are summarized as follows:

Zero voltage/current turn-on/off for the active power switch over the wide line and
load range.
28

Low voltage/current stresses of the power switch and rectifier diode.

Constant switching frequency operation in the converter.

Minimal circulating energy within the converter.
(a) ZVT PWM switching cell
(c) ZCT PWM switching
cell
(b) Boost ZVT PWM switching cell
(d) Boost ZCT PWM switching cell
Fig. 1.13 Basic topologies of ZVT and ZCT PWM converters
As discussed earlier, the proliferation of utilization of laptops, biomedical equipments
and portable equipments applicable to all applications, claim for power sources of high power
29
density and high efficiency. Power density in PFC pre-regulator power sources can be
improved by reduction of losses and size of components.
Size reduction of magnetic
components and other passive elements can be done up to certain extent depending upon the
operating switching frequency of the converter. Thus, the recent demands for high efficiency,
high power density, and reasonable cost power supply for telecom and computer applications
in DPS motivates to design pre-regulator PFC boost converters with active or passive
auxiliary circuits at different load conditions.
The proposed converters of our research work can achieve high efficiency and high
power density by reducing losses and operating at high switching frequency. Also, these
topologies reduce the voltage or/and current stresses, which lead to the low power rating
components at reasonable cost of an overall system.
1.6 Modular system
The use of three-phase AC-DC rectifiers with high quality input currents with
excellent output voltage regulation to meet telecommunication standards have been reported
in references [10, 84, 118-122]. The main intension of this approach is to achieve higher
power expandability and low volume occupancy of distributed power system sources. In this
modular approach, three identical single-phase AC-DC converter modules are connected in
parallel to form a three-phase converter system with or without using the neutral line of the
three phase power supply (which may not be available in some applications or installations).
With this approach, the single output filter capacitor is enough at the output of the
three-phase converter whose volume and weight are reduced drastically owing to the
fact that, like the three-phase rectifier, the dominant ripple frequency is six times the
input source frequency. This approach of three-phase AC-DC converter has its own vantage
of providing 48 V or 24 V DC voltage output from three-phase AC supply with a direct
30
single stage power converter with automatic PFC, electrical isolation and simple DC-DC
control characteristics. Fig. 1.14 shows basic block diagram three identical AC-DC PFC
converters in modular system. Besides the above mentioned merits, the modular approach
has the following advantages [10, 84, 120, and 121].
 Improved reliability and performance of converters.
 Flexibility in expanding the power rating of converters.
 Low periodic maintenance and repair of power converters because of the use of standard
single-phase converter units.
 Avoids the use of expensive components of larger rating which may occur in single high
power converter.
 Calibration of components directing to reduction in manufacturing cost and time.
Fig. 1.14 Block diagram of three identical PFC converters in modular approach
31
Modular approach presented in [121] for three – phase applications suffers from
problem of phase current interactions between different modules, this phase current
interaction affects the slope of the boost inductor current during the off period of the main
switch. In the proposed converters of our research work, no such interaction takes place
between modules as such systems have been developed and is well presented in [84, 120].
1.7 Motivation
The tremendous requirements of power sources for almost all electronic products
under different power ratings pose stiff challenges to power supply designer. Regulated
voltage at DC bus bar, increased current requirements and the dynamic characteristics of ACDC active PFC converters create new demands on power distribution and management. The
issues such as high efficiency, high power density, and fast dynamic response etc, became
critical for specific applications such as power sources to telecom and computer servers, biomedical equipments, and aeronautical engineering. The transfer of electrical power from
power grid to customer end with low cost and increased efficiency has been made possible
due to advances in Power Electronic converter design with sophisticated control methods.
But compromise is to be done in some extends with size, weight and cost etc. in today’s
Power Electronic apparatus.
The cost, size and performance advantages have promoted Power Electronics
applications extensively in industrial, commercial, residential, aerospace and military
environments in recent years.
Today, a market demands the miniaturization of power
sources. This compels to go for high switching operations of power converters which reduce
the size of magnetic components employed in converters. High switching operation of
converters leads to the increased switching losses which reduce the efficiency of converters.
Another basic requirement for electronic loads in DPS is to provide galvanic isolation to
32
satisfy safety standards and to achieve flexible system configuration. These requirements can
be fulfilled by employing active PFC converters is DPS. The research is still progressing to
achieve fast dynamic response, better efficiency, and high power expansion with stringent
regulatory standards, which motivates to develop improved performance of active PFC
converters employed in DPS.
A simple extended PWM switching technique has been
investigated in our research work and employed in AC-DC PFC converter to improve the
dynamic response during step change in load current and line voltage. The same concept is
extended to three-phase system in modular approach to expand the power rating of
converters.
Increased popularity of DPS claims for high power density and efficiency of AC-DC
PFC converters. Power density will be improved by reduction of losses and size of
components. Size reduction can be done up to certain extent depending upon the operating
switching frequency of the converter. Several topologies were proposed in past few years
such as: quasi-resonant converter, resonant converter and ZVT-PWM converter; to reduce
losses. But resonant converters suffer from the disadvantage of high voltage and current
peaks. This in-turn causes the device ratings to be much higher than the hard-switched
counterparts. ZVT techniques become popular as it provides reduced voltage and current
stresses with much reduced switching losses. Recent demands of high efficiency, high power
density, low cost power supply in DPS motivates to design ZVT based AC-DC PFC
converter with active and passive auxiliary circuits. The proposed converters can achieve
high efficiency by reducing switching losses. It reduces voltage and current stresses, which
leads to low cost and low power ratings components.
Besides increased efficiency, power expansion and reliability of AC-DC PFC
converters employed in DPS are quite significant. These requirements can be accomplished
33
with the modularity approach.
In addition, this approach also provides easier thermal
management and maintainability. These requirements motivate to implement soft switching
technique in modular system of ZVT based PFC converters to achieve high power density
with improved efficiency.
1.8 Objectives
From the preceding discussion, the dissertation objectives may be streamlined as follows:

To develop efficient PWM control technique for single-phase as well as for threephase AC-DC PFC boost converters. A simple extended PWM technique overcomes
the sluggish response of PFC converters and also reduces the voltage stress of PFC
boost converter components during transient periods.

To implement soft switching techniques in single-phase AC-DC PFC boost converter
topology employing active auxiliary circuit and passive snubber circuit.
This
proposed technique will improve power density and efficiency for medium power
applications. Another main objective is to eliminate the voltage and/or currents
stresses of boost semiconductor switches as well as semiconductor switches of
auxiliary circuit itself. The proposed converters can achieve better efficiency at side
load range.

To develop three-phase modular system of power rating 1.5 kW, 400 V, 100 kHz with
reduced switching losses, reduced voltage and current stresses of semiconductor
devices.
1.9 Dissertation structure
From the introduction, it can be observed that, several fundamental factors have been
considered for the improvement of performance of front-end AC-DC PFC pre-regulator. To
meet certain factors with respect to performance improvement requirement of PFC converter,
34
in this dissertation, different proficiencies have been investigated, which include dynamic
response, different converter topologies to meet high power efficiency and modular approach
solution to achieve power expandability for front end converters in distributed power system.
In chapter 2, issues of PWM control in PFC converter have been discussed. For PFC stage, it
is desirable to have better dynamic response for change in input voltage or load current. Due
to the presence of low bandwidth filter in the voltage control loop, the system has slow
response. Therefore, it is essential to find out the extended PWM switching technique to
achieve fast dynamic response in PFC converters. A simple extended version of PWM
technique is proposed for front-end AC-DC PFC converter for dynamic improvement. From
the theoretical analysis, simulation and experimental verification, it is demonstrated that by
applying two sided PWM technique for single-phase and three-phase PFC converters, a faster
dynamic response can be obtained with primary achievement of nearly unity input power
factor of converter.
High switching frequency of PFC circuit can result in smaller EMI filter size and
boost inductor size. With higher switching frequency, switching loss is the major concern.
To allow PFC circuit operating with switching frequency of 100 kHz, in chapter 3, PFC boost
converter with passive snubber circuit has been discussed. Firstly, the boost converter with
passive snubber circuit is discussed and its optimistic design is described. This topology can
achieve higher efficiency by minimizing switching loss with voltage and current levels within
the permissible limits. The performance evaluation of a single-phase PFC boost converter
prototype developed in a laboratory has been analyzed and verified with a simulation results.
Furthermore, to overcome the drawbacks of PFC converter with passive snubber circuit, a
simple active snubber ZVT based PFC boost converter is proposed in chapter 4. An optimal
design methodology for PFC boost converter with active snubber circuit has been presented.
35
Through the analysis and practical verification of single-phase circuit operation at full load
condition and soft switching process of all semiconductor devices show that successful
auxiliary resonant converter design relies on proper design of boost inductor and selection of
snubber capacitor components. Furthermore, PFC boost converter with auxiliary snubber
circuit exhibits small switching loss due to its soft switching capability and soft turn-off of
boost diode. Therefore, it is able to operate at high switching frequency to achieve high
efficiency while maintaining nearly sinusoidal input line current.
In chapter 5, a modular approach solution for front-end AC-DC PFC converter is
proposed to gain the inherent advantages of modularity for DPS. To obtain the benefits of
modular approach, three identical single-phase AC-DC PFC converters with soft-switching
topologies have been demonstrated. Here, the single-phase converter circuits proposed in
chapter 3 and chapter 4 are developed in modular approach and corresponding results have
been presented. The experimental result show that, the modular approach is able to achieve
the power expandability of 1.5 times the power developed by single-phase converters
proposed in chapter 3 and chapter 4.
Last chapter 6 is dedicated to summary of overall thesis and future work on
performance analysis and its improvement of front-end AC-DC PFC converters.
36
Chapter 2p
Chapter 1
Chapter 1
Dynamic Performance Improvement
ter
1
of PFC Converter by Enhancement in
PWM Technique
o Introduction
o Design analysis of PFC feedback control system
o PWM control
o Operation of proposed two sided PWM technique
o Simulation and Experimental results
o Summary
37
Introduction
Chapter 1 explained in detail the dynamic response problems occurring in PFC AC-DC
converters. Due to input power variation in PFC converters, output load voltage contains a
ripple voltage, whose frequency is twice the line frequency, which affects the input current
waveform unless the voltage loop bandwidth is held below the half of the line frequency. This
low bandwidth in voltage loop makes the active PFC converters to have sluggish transient
response. This sluggish transient response problem is further compounded by large voltage
overshoots and voltage drops enforcing additional stress on the PFC components, as well as on
its downstream switch mode power supply load. It was pointed out that, simple way of obtaining
good transient response is possible only by sacrificing the efficiency of the overall system by
cascading the PFC pre-regulator with second DC-DC converter [29, 34].
In chapter 1, it is also discussed about the various methods proposed to ameliorate the
dynamic response without permitting propagation of the ripple through voltage loop. Even
though effective methods have been proposed for improvement of the voltage loop dynamics, the
conventional low bandwidth design of the voltage loop is still predominant. This is mainly due to
unresolved controller design and PWM technique issues. This motivated us to focus on the
research of dynamic improvement of converters employed for PFC applications.
Following above discussion, in this chapter investigation of improvement in the dynamic
response of a AC-DC PFC boost converter with novel PWM strategy is carried out. This novel
PWM control strategy for PFC applications has been published in our publications [123, 124].
The advantages of the proposed scheme are:
(a) The bandwidth of voltage loop can be still maintained small to avoid ripple frequency
38
propagation through the voltage loop and hence eliminates the distortion in input current.
(b) This novel PWM strategy can be applied to three-phase PFC converter in modular system,
hence exhibiting the higher power expandability.
(c) Improves the audio susceptibility of the converter system.
The high quality of input current in AC-DC PFC converter is often achieved by a current
mode PFC controller Integrated Chip’s (IC) such as UC3854, UC3853, AN-1077, IR1150, etc.
As described in section 1.3.1 of chapter 1, these PFC controllers essentially have current loop,
voltage loop and feed-forward loop to achieve unity input PF in PFC pre-regulator system. The
important conception of each loop is discussed in detail and this outlines the importance and
significance of this study.
2.1
Design analysis for PFC feedback control system
2.1.1
Current Loop Compensator
Excellent references exist on current loop design [32, 125-128]. The objective of this
loop is to track a reference sine waveform whose frequency is twice the line frequency.
This
reference signal has a high dv/dt around the zero crossings of the line. Therefore the loop needs
gain at frequencies corresponding to the higher order Fourier coefficients needed to recreate the
reference waveform. This implies high bandwidth for the current loop. A bandwidth of 10 kHz
can be considered for this type of PFC application which is usually adequate for 50 Hz or 60 Hz
line frequency [32, 128]. In order to design a proper current loop compensator, the equivalent
model of the boost converter is analyzed. By applying three terminals PWM switch model [32,
128] to the boost converter, the small signal equivalent circuit of the boost converter shown in
Fig. 2.1 is obtained. The power stage small signal duty to current transfer function of the exact
model of boost PFC converter shown in Fig. 2.1(a) is
39
Gid (s) =
2 V0 RSENSE
R (1- D)2
1+
s
ωz
s
s
1+
+
ω0 Q ω0
(2.1)
2
where D is the duty cycle and
ωz =
2
(1- D)
, ω0 =
, Q = R(1- D)
RC
LC
Vout ^
d
D
C
L.
Vout ^
d
D
I ^
Ld
I ^
Ld
(a) Exact model
(b) Simplified equivalent model at high frequency
Fig. 2.1 Model of boost PFC converter using PWM switch model
The ‘RSENSE’ term is not seen directly from the Fig. 2.1(a) and (b) but is included here
since it relates the actual inductor current to the signal at the current loop error amplifier. In the
equation (2.1), it can be observed that, the power converter stage DC gain, poles and zeroes are
moving as the instantaneous line voltage changes (D changes with the line voltage). It is well
known that, the output capacitor in a PFC converter is large enough in order to meet the hold-up
time requirement and to minimize the 100 or 120 Hz ripple. Fig. 2.1(b) shows the simplified
form of the small signal equivalent circuit of the boost converter, which is obtained by assuming
the large output capacitor to meet holdup-time requirement and less switching frequency ripple
(high switching frequency) [32]. This is essentially a reasonable approximation for realistic
circuit design. The simplified form of current loop transfer function for the equivalent circuit
shown in Fig. 2.1(b) is given by,
40
Gids (s) =
V0 RSENSE
s L VSE
(2.2)
where VSE is the triangular voltage peak to peak.
The bode plots of exact model of equation (2.1) and simplified model of equation (2.2)
are plotted in Fig. 2.2 for selected instantaneous line voltages (including high line and low line
voltages). It can be observed that although the power-stage DC gain, poles and zero are changing
with the line, the high-frequency portions of the responses are converging to the response of
simplified model as shown in Fig. 2.2. Hence, the simplified model approach is used for
designing current control loop as it is easier and details obtained from high frequency equivalent
Magnitude (dB)
circuit is adequate to design the current loop.
Low line voltage : 85 V
Line voltage
: 180 V
High line voltage : 240 V
Simplified model : (HF approx.)
100
50
0
Phase (deg)
90
45
0
-45
-90
-135
0
10
10
1
10
2
3
10
Frequency (Hz)
10
4
10
5
10
6
Fig. 2.2 Magnitude and phase response of exact model and simplified model of
boost PWM switch
In ACMC method, current control loop is essentially a current amplifier with a two pole,
single zero compensation network and this is shown in Fig. 2.3. The zero is placed to achieve
the desired phase margin and the pole is placed at or after one-half of the switching frequency to
reduce the switching noise of the sensed inductor current [129].
41
Fig. 2.3 Circuit diagram of current loop error
amplifier
The transfer function of current loop error amplifier shown in Fig. 2.3 is given by,
Av =
1+ s R f Cz
s Ri (C p +Cz ) (1+ s R f )
here,
(2.3)
C p Cz
C p +Cz
Ri and Rf are input and feedback resistors of current loop amplifier.
Cp and Cz capacitances to have pole and zero of transfer function.
Cout is the output of current loop error amplifier.
iL and iref are measured inductor and derived sinusoidal currents respectively.
2.1.2 Voltage feedforward loop compensation
The RMS voltage feedforward control is performed in many PFC IC controller circuits in
order to achieve a constant gain in voltage loop over varying input voltages and to provide input
voltage correction to the line current [32, 102, 130]. It can be observed in Fig. 1.5 of chapter 1,
that the required average value of the rectified AC input is obtained by a two pole low pass
filtering circuit, i.e. the output of block ‘C’ is squared before being used as a divider term in
deriving the reference current signal iref. The addition of this term in the multiplier does not
warrant a change in output of a voltage compensator for change in the input voltage for a given
load. In fact, the output of a voltage compensator becomes proportional to the output power for
42
normal operating range [126, 130]. A broad sense of two pole feedforward low-pass filter
suitable for PFC circuit is shown in Fig. 2.4. The key advantage of this feeforward technique is
constant loop gain and constant peak power over the specified input range of voltage. In a PFC
feedback system of Fig. 1.5, of chapter 1, the output of a multiplier is the reference current signal
and it is given by,
iref =
( A) ( B)
where
(2.4)
(C )2
A= Kv vin, (Kv: Input voltage gain),
B= vvc, (vvc: Output voltage signal of voltage compensator), and
C=Kff Vin_rms, (Kff : gain of input voltage feedforward signal)
Fig. 2.4 Second order low-pass filter in feedforward loop
Since both the rectified output voltage and boost converter output voltage contain 2 nd
harmonic component [130], there exists a ripple in B and C components of Fig. 1.5 of chapter 1.
Hence, ripples in components B and C are injected into the current reference iref. From equation
(2.4), it can be derived that,
iref
iref
B
B
2
C
C
(2.4a)
43
here, ∆B and ΔC are unknown, the worst case occurs when they have a phase shift of 180 0.
Considering absolute value of equation (2.4a), we obtain,
iref
iref
worst
B
B
2
C
C
(2.4b)
From the above equation (2.4b), it can be concluded that, for a system looking to achieve
1.5% THD, it is typical to allow the feedforward circuit ‘C’ to contribute less than 0.5%
distortion and the total distortion of ‘B’ should be smaller than 0.5% [131]. The selection of cutoff frequency of the feedforward low-pass filter and voltage compensator gain should be based
on this criterion.
2.1.3 Voltage loop compensation
The voltage control loop is very essential in feedback system of PFC converters to
achieve a proper stability of the system. But there are some trade-offs in designing voltage
control loop that are particular to AC-DC PFC converter application. The key requirement of
power balance, on the line frequency time scale, necessitates that the feedback voltage loop’s
bandwidth must be less than the half of the line frequency. If not, the voltage loop will distort the
input line current in order to regulate the output voltage [32, 130]. This makes a trade-off
between input PF and transient response.
Generally, a transconductance type amplifier is employed in voltage loop compensator
which is compensated by connecting impedance between the amplifier’s output and ground.
Usually, the output current of amplifier is not sufficient to drive a resistive load unless the
desired DC gain is very high [130]. This implies capacitive loading and hence the integral gain.
In such cases, the integral compensation can be used. The transconductance amplifier of voltage
loop compensator (voltage error amplifier) is shown in Fig. 2.5. Its transfer function is given by,
44
AV
1 s R C1
gm
s(C1
(2.5)
C C
C2 ) 1 s R 1 2
C1 C2
where, gm is the transconductance of the voltage error amplifier. R, R1, R2, C1 and C2 are the
elements of transconductance amplifier circuit.
Fig.
2.5 Voltage loop error amplifier configuration in PFC feedback system
In order to analyze voltage control loop in PFC applications, the basic low frequency
model of the output of the power stage and the current feedback loop have to be considered. The
power stage and the current feedback loop compose the voltage controlled current source driving
the output capacitor connected in parallel with load resistor. This arrangement essentially forms
an integrator and it has gain characteristics which rolls off at a constant 20dB per decade rate
with increase in frequency. The low frequency small signal equivalent circuit for the power
stage with the current loop closed [128, 130] is shown in Fig. 2.6.
Fig. 2.6 Small signal model of outer voltage loop for constant power
loads, r0=RL
45
In above Fig. 2.6, gc
case, RL
K
Vin2 _ RMS
V0
, gi
K2
Vin _ RMS Vc
V0
, and r0
V0
,
I out
for the constant power load
Vo
. From the small signal model, the control to output voltage transfer function
I out
can be obtained as:
~
GV
V0
~
Vc
gc
C0 s
(2.6)
For constant power applications, a phase margin of 450 [131] for voltage compensation is
employed.
2.2
PWM control
PWM control plays a vital role in high switching operation of converters. The output of
the feedback controller (output of current controller) is applied to one of the inputs of the PWM
modulator comparator. On the other input of this comparator, a saw-tooth voltage ramp of
specified frequency is applied. Since the feedback signal is connected to the inverting input of
the error-amplifier, if the output is below the set regulation value, the output of error amplifier
goes high.
ΔD
Pulse Width Modulator Gain
(Unit - V -1 )
PWM output
Control voltage
ΔVCONT
D=
VRAMP
VCONT
VRAMP
ΔD =
VCONT
ΔVCONT
VRAMP
G PWM =
ΔD
1
=
VCONT
VRAMP
Fig. 2.7 Gain of pulse width modulator
This causes the PWM to increase pulse width (hence duty cycle) and thus makes the
output voltage to rise. Similarly, if the output of the converter whose value is to be regulated
46
goes above its set value, the error amplifier output goes low, causing the duty cycle to decrease.
The generation of pulse from this PWM to drive the switch in converters is shown in Fig. 2.7.
As mentioned previously, the output of the PWM modulator stage is a duty cycle and its input is
the control voltage or the output of the error amplifier. So, the gain of this PWM stage is not a
dimensionless quantity, but has units of 1/V. From Fig. 2.7, it can be obtained that; the gain of
PWM modulator is equal to 1/VRAMP. Where VRAMP is peak to peak amplitude of ramp saw tooth
signal.
2.2.1 Issues surrounding PWM control
As described in previous section 2.1, it is well known that, active PFC AC-DC converters
always use closed-loop negative feedback systems with PWM technique to achieve objectives of
line and load regulation. Most PWM controllers use a clock-edge to set one edge of the PWM
signal and feed-back to set the other edge of the PWM signal. But, one edge available for control
remains unused. This direct duty cycle control has disadvantages like slow response to sudden
input changes, poor audio susceptibility and poor open loop line regulation [132-134]. In both
current mode and voltage mode control of PWM is restricted and it uses one of two edges
available for control [15, 133, 134]. Controller with hysteresis based on power converters makes
use of both edges but the switching frequency is allowed to vary and control scheme is sensitive
to commutation noises [24, 135-137]. Variation in the switching frequency makes it difficult to
filter the ripple components in the input and output waveforms of the converters [138].
Therefore, it is essential to have constant switching frequency for easy design of input EMI filter
and magnetic components with primary objective to obtain unity power factor in power supplies.
Saw-tooth ramp generator is required in PFC converters to stabilize fixed frequency PWM
control. Many commercial PWM controller ICs are available with/without saw-tooth generator.
47
ICs with a saw-tooth generator are limited in switching frequency and ICs that do not include the
saw-tooth ramp generator are available that operate at much higher switching frequency. Still
there exists a challenging task for power supply design engineers in generation of the high
frequency saw-tooth ramp with the fast reset. Employing two sided PWM technique improves
the dynamic response of the power factor correction converter and it is most suitable for high
frequency applications [133, 134].
2.2.2 Comparison of PWM and two sided PWM techniques
In broad sense, PWM-scheme is classified by whether one or both edges are modulated.
The latter requires a double-sided or triangular carrier signal (with equal slope) to generate PWM
pulses. Fig. 2.8 shows the difference between single-sided (conventional PWM) and two sided
latch PWM modulation techniques. In double sided modulation technique, the pulse transition
from high to low is occurring at ‘t1’ which is intersection of positive ramp of triangle signal and
control signal, pulse transition from low to high is happening at intersection of negative ramp of
triangle signal and control signal. In case of conventional PWM technique, pulse transition from
high to low is occurring at ‘t2’ the intersection of positive ramp of saw-tooth signal and control
signal, transition from low to high is taking place at the instant of end period of saw-tooth signal.
It can be observed that, the same number of output transitions occurs per period T in two sided
PWM technique and that of single sided PWM technique, but the signal is sampled twice in two
sided PWM technique. Also, the carrier slew-rate is doubled in two sided PWM technique so the
requirement for fc/f is halved. In Fig 2.8, it can be observed that, over a period of cycle from nT
to (n+1) T, the transition of pulse from high to low for two sided PWM technique is occurring at
instant t1, and transition from high to low for single sided PWM technique is happening at t=t2,
here t1<t2, hence the quick response is achieved by the two sided PWM technique rather than
48
single sided PWM technique. This response is mainly depending on the slope, i,e peak value of
carrier signal. In two sided PWM technique, the ramp amplitude is chosen to meet the equal
ramp slope criteria for optimal current mode to achieve better dynamic performance of the
system. Thus the two sided PWM method stabilizes any transient responses on the load or input
line quicker than conventional PWM method for properly designed control loops [134]. This
novel approach motivated us to employ two sided PWM scheme to AC-DC PFC boost converter.
Triangular signal
Sawtooth signal
Control signal
Single sided PWM
Two sided PWM
nT
(n +1)T
(n + 2)T
Fig. 2.8 Comparison of two sided and single sided PWM techniques
2.3 Operation of proposed two sided PWM control
Fig. 2.9 shows a sensor-less current mode control implementation in inner current mode
control of two sided active PFC AC-DC boost converter. This scheme achieves modulation of
both edges while maintaining fully latched operation. In this PWM scheme two comparators are
used instead of one to set and to reset the switch. One comparator is used for the comparison
between the feedback signal sign and ramp to set the switch while another comparison between
an offset feedback signal and ramp to reset the switch. The ramp is not a saw-tooth, which is
hard to generate at high frequencies [134], but a triangular ramp wave with equal rising and
49
50
Fig. 2.9 Two sided latched PWM schematic for PFC AC-DC boost converter
falling slopes is used to stabilize the duty ratio of the switch and to set the switching frequency.
The ramp amplitude is chosen to meet the equal ramp slope criteria for optimal current mode
control.
1
sign + 0.5
Ramp
0
sign - 0.5
Dl(n)T
Dr(n)T
Time
tsw
(2n - 1)T
(2n)T
(2n +1)T (2n + 2)T
2T
Fig. 2.10 Theoretical timing diagram for proposed two sided latched PWM technique
Fig. 2.10 shows the timing diagram of the signals in the proposed two sided PWM
scheme for active PFC AC-DC converter. There is a triangular ramp with equal rising and falling
slopes. This ramp is compared to the feedback signal with two appropriate offsets. The resulting
PWM signal is shown at the bottom of the Fig. 2.10. Note that the delay between consecutive
rising and falling edges is T. The ramp slope is chosen to be equal to the feedback signal at duty
ratio of half. This is a design choice and depends on the nominal duty ratio.
2.3.1 Time domain analysis
By applying the switch set and reset criteria for a current mode control of two sided
PWM technique shown in Fig. 2.9 and assuming that the converter is operating in the CCM of
51
operation, the following equations can be obtained. The mathematical analysis is similar to the
method used in [133, 134].
sign((2n dl (n))T )
1
sign((2n dr (n))T )
1
2
2
dl (n)
(2.7)
dr (n)
(2.8)
The signal ‘Sign’ is control signal which is output of a current controller. In other words,
the signal ‘Sign’ is obtained as the integral of the difference of the reference signal and the
switching signal waveform. However, the gain of the integral is obtained using the equal slope
criteria when the reference signal is half the input voltage.
Vin
2
Ti
1
T
Ti
Vin
T
2
(2.9)
where, 1/T is the ramp slope for a ramp signal of unit amplitude and Vin is the input voltage to
boost converter. Let us define, the nominal duty ratio of the converter in steady state be ‘dnom’.
This term is essentially used to eliminate ‘Vin’ and ‘Vref’ from the duty ratio equations.
sign((2n
dr (n))T )
sign((2n dl (n))T )
dr (n))T )
sign((2n dl (n))T )
(Vr Vin )
[dl (n) _ dr (n)]T
Vin
T
2
(2.10)
also,
sign((2n
2(dnom 1)[dl (n)
dr (n)]
(2.11)
The relationship of signal ‘sign’ between present time step and the next time step is as follows,
sign((2n 1) dl (n 1))T )
sign((2n
dr (n))T )
sign((2n 1) dl (n 1))T )
sign((2n
dr (n))T )
Vr
[2 dr (n) dl (n 1)]T
Vin
T
2
2 dnom[2 dr (n) dl (n 1)]
(2.12)
(2.13)
By substituting the nominal duty ratio in the above two equations, we get,
dr (n) 1/ 2
dl (n) 1/ 2 2(1 dnom)(dl (n)
dl (n 1) 1/ 2
dr (n) 1/ 2
(2.14)
dr(n))
2 dnom (2 (dr (n) dl (n 1)))
52
(2.15)
By simplifying equations (2.14) and (2.15) and by considering reference and input voltage
quantities, right duty ratio ‘dr’ and left duty ratio ‘dl’ can be obtained as [134],
dr
1
(1 2 dnom)2
2
dnom
(2.16)
and
dl
dnom
1
(1 2 dnom)2
2
(2.17)
From the previous analysis and simplified expressions of ‘dl’ and ‘dr’, it can be
summarized that, the nominal duty ratio ‘dnom’ is always equal to the average of the left and
right duty ratios. The nominal duty ratio dnom = 0.5, when both left and right duty ratios are
equal. At all points except at dnom=0.5, the right duty ratio is greater than the left duty ratio.
This causes problem at extreme values when the left duty ratio approaches zero and the right
duty ratio approaches unity.
The value of nominal duty ratio for the two extreme cases is computed as follows.
dr
1
or
1
(1 2 dnom)2
2
dnom
1
dnom
5
4
(2.18)
0.809
(2.19)
dl
0
dnom
or
dnom
1
(1 2 dnom)2
2
3
5
4
(2.20)
0.191
(2.21)
It is to be noted that, this stability bound is not fundamental to this approach, however it is the
result of meeting the equal slope criteria at dnom=0.5.
2.3.2 Design procedure of single-phase AC-DC PFC boost converter
As noted in section 1.4.1 of chapter 1, the boost converter topology operating in CCM is
most popular for medium and high power AC-DC PFC applications. Hence, the conventional
53
boost converter operating in CCM is considered to employ two sided PWM technique to improve
the transient response of the AC-DC PFC converter.
Table 2.1 shows the design basic
specifications that will govern the main attributes of the circuit components. However, the
design procedure for the PFC boost converter elements is same for both the single sided PWM
and two sided PWM control techniques.
Table 2.1 Specification of PFC AC-DC boost converter
Rated Output Power
Universal Input Voltage Range
Line Frequency
Nominal Regulated Output Voltage
Switching Frequency
Target Efficiency
Hold-Up Time
Pout =500 W
Vin= 85 V to 265 V (rms)
fline = 47 – 63 Hz
Vo = 400 V
fs = 100 kHz
η 95%
thold_up = 20 ms
Following are the standard design equations of the main components of the PFC AC-DC
boost converter; the procedure is reported in [130, 139-141]. There are many other factors
involved in the design process of PFC boost converter. However, the following equations are
intended to provide a frame work for the design.
Pin(max)
Pout (max)
min
Iin _ RMS (max)
Iin _ peak (max)
500
0.95
526.32 W
(5.22)
Pin(max)
Vin _ RMS (min)
2 Iin _ RMS (max)
526.32
85
6.2 A
(2.23)
2 (6.2)
8.77 A
(2.24)
2.3.2.1 Boost Inductor
Typically the boost inductor to be operated in CCM is designed with the ripple current
20% of the peak current [130, 140, 142].
54
Vin _ peak (min)
2 Vin _ RMS (min)
2 (85) 120.21V
(2.25)
Maximum value of transistor duty cycle,
Dpeak
1
Vin _ peak (min)
120.21
400
1
Vo
Inductor ripple current,
I L _ peak (max)
IL
IL
2
Iin _ peak (max)
0.7
(2.26)
(0.20) Iin _ peak (max)
8.77
1.75
2
(0.20)8.77
1.75 A
(2.27)
9.64 A
(2.28)
Lmin
Vin _ peak (min) Dpeak
fs ( I L )
120.21(0.7)
100000(1.75)
480 H (min imum)
(2.29)
2.3.2.2 Output capacitor
In power supply design, the value of the output capacitor is computed based on the
following [102, 130]; 1) Amount of the tolerable output ripple voltage by the capacitor and 2)
Holdup time of the power supply. Hence, the determination of output capacitor value is mainly
depending on the output voltage ripple allowed and on the holdup time in brownout conditions.
2.3.2.3 Output voltage ripple limit
The criterion for selection of output capacitor is the amount of tolerable ripple in the out voltage,
Pout
hence, C0
V0
2 ( fline ) (% V0 _ ripplie )
500
400
2 (50) (0.03) (400)
331.57 F
(2.30)
where ∆V0_ripple is the desired peak to peak output voltage ripple and 30% is considered in this
design.
De-rating the output capacitor value by 20% for tolerance in order to guarantee
minimum capacitance requirement is satisfied.
C0
C0(min)
(1
Ctol )
331.57
(1 0.2)
(2.31)
55
C0
414.46 F
2.3.2.4 Holdup time requirement
Typical power supplies in distributed power system employ a PWM stage after PFC stage
to provide isolated DC output for end user. Hence, some applications, especially computing,
have the holdup time requirement. This means that, the power supply must be able to sustain its
load output for short duration. 20 ms of holdup time is an accepted standard in the industry.
Hence, the minimum capacitance required for a 20 ms holdup time can be calculated as,
C0
C0
2( Pout ) tholup
(Vo2
V02_ min )
2(500) 20(10
(400
2
03
)
2
250 )
(2.32)
205.12 F
where the tholdup is the minimum holdup time and Vo_min is the minimum output voltage
that the load will operate. The calculations of equations (2.31) and (2.32) yield an output
capacitor C0 to a minimum value of 414.46 μF. To meet minimum holdup time and output
voltage ripple requirements, the higher standard capacitance value of 450 μF, 600 V is selected.
2.4
Simulation and Experimental Results
2.4.1 Single phase AC-DC PFC boost converter
Based on the theoretical analysis described in above sections, the two sided PWM
technique for improvement in dynamic response of AC-DC PFC converter is evaluated. A 500
W, 400 V and 100 kHz switching frequency, universal input single-phase AC-DC PFC boost
converter prototype is designed and implemented with a feedback PFC controller IC-UC3854. A
separate auxiliary circuit is developed to generate triangular waveform to achieve two sided
PWM technique successfully. Besides, the conventional AC-DC PFC converter circuit using
56
identical devices and ACMC was built with same PFC controller IC with single sided (regular)
PWM technique as the benchmark. All the converter circuit parameters are listed in Table. 2.2.
The configuration of the proposed AC-DC PFC converter is developed in association
with its sophisticated feedback system and simulated in Power-Sim (PSIM) Power Electronics
and Drives simulation package.
The purpose of this simulation is to verify the control
algorithms, design the controller parameters, and to verify static and dynamic performances of
the proposed system with conventional system.
Table 2.2 Components employed in the proposed
converter
Value/Model
Component
Bridge rectifier
MOSFET
Fast-recovery Diode
Output capacitor
Simulation
Ideal
Ideal
Ideal
450 μF, 600 V
Boost inductor
1 mH
Low line filter inductor (Lin)
5.6 μH
Experimental
DFB2060 (Fairchild SC)
IRFP460 (International Rectifier)
RHRP3060 (Fairchild SC)
UNLYTIC make– (UL30-series)
Sendust toroid, part No. CS468125 and
32 single layer turns of 16 AWG
5.6 μH
Fig. 2.11 shows the steady-state and transient response of simulation results of proposed
two sided PWM AC-DC PFC converter as well as conventional PWM AC-DC PFC converter.
Fig. 2.11(a) and Fig. 2.11(b) show simulated input voltage, input current and output voltage
waveforms of proposed converter and conventional converter for a step change in voltage from
150 VRMS to 220 VRMS and 220 VRMS to 150 VRMS respectively. The step change in input voltage
from 150 VRMS to 220 VRMS and vice versa is occurring at instant 0.7 sec. In both cases (change
in voltage from high to low and low to high, Fig. 2.11(a) and Fig. 2.11(b)), the two sided PWM
PFC converter recovers its steady state at around 0.765 sec and that of conventional PWM PFC
57
(a)
Fig. 2.11 Comparison of dynamic response
(b) of output voltage for a step change in
input voltage
(a) 150 VRMS to 220 VRMS (b) 220 VRMS to 150 VRMS
58
converter is recovering at 0.805 sec. However, the overshoot and under shoot voltage stresses
on devices and output capacitor are more in case of conventional PWM PFC converter and these
limits are noted and marked in Fig. 2.11. It can be seen from these figures that, the proposed two
sided PWM technique increases the dynamic response at least by 5% under worst case condition
for a large change in input voltage.
The experimental results of dynamic response due to step change in input voltage from
150 VRMS to 220 VRMS and vice versa have been observed, recorded by Digital Storage
Oscilloscope and are shown in Fig. 2.12. The identical response with respect to simulation
results are verified during step change in the input voltage. In experimental results, as soon as
there is change in the input voltage, the peak voltage (surge) spike appears on input voltage in
both cases where same response has not occurred in simulation results. This is because the
discrete transition simulators like ‘PSIM’ are incapable of showing parasitic effect processes
such as surge current or voltage. It can also be observed that, the two sided PWM technique
provides quick response in comparison with conventional PWM technique employed in singlephase AC-DC PFC converter.
The performance of transient response for load change is also obtained by simulation of
both the converters. The output voltage waveform in transient state, in which load is changed
from full load to 50% of full load and vice versa for both the converters are shown in Fig. 2.13.
When the load is changed at time t = 0.8 sec, in both cases, (a) 50% to full load and (b) full load
to 50% load change, the output voltage overshoots to 388 V and 410 V respectively. After about
20 ms, the output voltage recovers to its stable state in case of two sided PWM technique.
However, the overshoot and undershoot of output voltage just after the load change are almost
same but the output voltage is in two sided technique recovers back to its stable state quickly.
59
(a) Two sided PWM response
(b) Standard conventional PWM
response
(c) Two sided PWM response
(d) Standard conventional PWM response
Fig. 2.12 Experimentally obtained dynamic response of conventional and two sided PWM
techniques for an input change from (a) and (b) 150 VRMS to 220 VRMS
(c) and (d) 220 VRMS to 150 VRMS Scale: Ch1: 100 V/div, Ch2:3: 200 V/div, Ch2: 2 A/div.
The percentage of improvement with respect to load change transient output voltage is
verified by experimental results shown in Fig. 2.14. Fig. 2.14 shows the comparison of output
voltage dynamic response to a load step from 0.625 A to 1.25 A for both control schemes. It is
found by experimental result that the half load to full load response is improved by 25% in two
sided PWM technique when compared with the conventional PWM control technique. The
photograph of the prototype of single-phase AC-DC PFC boost converter with proposed
technique is shown in Fig. 2.15.
60
(b)
(a)
Fig. 2.13 Comparison of dynamic response of output voltage for step change in load
(a) From 50% to full load (b) Full load to 50% load
(a) Two sided PWM technique
(b) Conventional PWM technique
Fig. 2.14 Output voltage comparison of two sided PWM technique and conventional
PWM technique for a load current change from 50% of full load to full load
Scale: 100 V/div, 5 ms /div.
61
Fig. 2.15 Hardware prototype of single-phase PFC AC-DC converter with two sided
PWM technique
2.4.2 Three-phase AC-DC PFC converter in Modular system
Prototypes of modular three-phase AC-DC converter with two sided PWM technique and
modular three-phase system with conventional PWM technique have been built and tested in the
Power Electronics and Drives Laboratory, National Institute of Technology (NIT), Rourkela,
with component values as shown in Table 2.3. The components employed in each module of
proposed three-phase modular system are mentioned in Table 2.2 of section 2.4.1. The complete
explanation of three-phase AC-DC PFC converter with sophisticated feedback control in
modular approach is described in chapter 5.
62
Table 2.3 Specifications of three-phase AC-DC PFC converter
in modular approach
Rated Output Power (Each module)
500 W
Rated output power (Complete module 3*500 = 1500 W
Input Voltage
215 VRMS
Line Frequency
fline = 50 Hz
Nominal Regulated Output Voltage
Vo = 400 V
Switching Frequency
fs = 100 kHz
Target Efficiency
η
Hold-Up Time
thold_up = 20 ms
95%
The experimental results of the proposed two sided PWM technique as well as
conventional PWM technique in modular approach are shown in Fig. 2.16. Fig. 2.16 (a) shows
the transient response of output voltage when load changes from 50% to full load and vice versa
for conventional PWM three phase AC-DC PFC converter. On the other hand, Fig. 2.16 (b)
shows the transient response of three-phase modular system of two sided PWM technique. It can
be observed from Fig. 2.16 (b) that, the output voltage recovered to its steady state within 1.2 ms,
which is around 30% improvement in comparison to three-phase modular system with
conventional PWM technique. In specific, DC output voltage is barely disturbed in spite of low
bandwidth of the DC voltage loop due to the load feedforward. It is indicated that good dynamic
performance can be achieved with two sided PWM technique.
In comparison of transient
response of output voltage of single-phase two sided PWM technique shown earlier in Fig. 2.14
(a), and that of three-phase modular system shown in Fig. 2.16 (b), the three-phase modular
system provides improved transient response at least by 20% over the single-phase PFC system.
63
This is due to the fact of high value of output capacitor connected across the output terminals in
three-phase modular system, which improves the stability of output voltage.
50% of full-load to full-load
Full-load to 50% of full-load
(a)
Conventional PWM technique in modular system
50% of full-load to full-load
Full-load to 50% of full-load
(b) Two sided PWM technique in modular system
Fig. 2.16 Dynamic response of output voltage for step change in load for three-phase
modular system. Scale: 200 V/div, 5ms/div.
64
The performance characteristics of the three-phase system operation in modular approach
with two sided PWM technique under variable load condition are presented in Fig. 2.17. Over
the wide range of output power, it can be observed that, the PF varies from 0.999 to 0.995 from
full-load to 25% of full load and total THD varies from 4.5% to nearly 10% from full-load to
25% of full-load and it is less than 5% at maximum load.
1
0.998
(a)
0.996
0.994
0.992
450
600
750
900
1050
1200
1350
1500
12
10
8
(b)
6
4
2
0
450
600
750
900
1050
1200
1350
1500
90
88
(c)
86
84
82
80
450
600
750
900
1050
1200
1350
1500
Fig. 2.17 Experimental performance characteristics of proposed three-phase
modular system
(a) Power factor (b) % THD and (c) % efficiency
65
The proposed three-phase converter in modular approach exhibits maximum efficiency
nearly 89% and at lower load conditions, the efficiency of system is lower as the converter is
designed for full load condition.
2.5 Summary
The basic and main idea of incorporation of two sided PWM technique in AC-DC PFC
boost converter is to improve the dynamic response of the single-phase and three-phase AC-DC
PFC boost converters over the conventional PWM PFC boost converters. The comparison of
two sided PWM technique and conventional PWM technique is described. The single-phase and
three-phase AC-DC PFC boost converters are implemented with the proposed new two sided
technique. The predicted transient response, theoretical analysis and simulation results of the
proposed converters are being confirmed by the comparison of experimental results obtained
from corresponding single-phase PFC and three-phase PFC converters. In addition to this,
experimental results have also shown that, the proposed technique in PFC converter is capable of
operating over a wide range of load without any problem. These AC-DC PFC converters
controlled by two sided PWM technique have achieved nearly unity input power factor even at
light load condition with low THD.
66
Chapter 3
Application of ZVT to PFC Boost
Converter with Passive Auxiliary
Circuit
o Introduction
o Circuit description and PFC feedback system
o Operating principle of proposed converter
o Design procedure
o Simulation and Experimental results
o Comparison of efficiency curves
o Summary
67
Introduction
The miniaturization of telecom and computer server equipments together with
growing requirements for on-board power processing in DPS have spurred significant
research and development efforts in the area of high power density and low profile power
supplies. To accomplish high power density, it is required to operate PWM converters at
higher switching frequencies, since the size of the reactive components (especially inductors)
will reduce with the increase of switching frequency. Although, high power density can be
achieved by operating PWM converters at higher switching frequencies, it is still
questionable that, is PFC converter is capable of operating at such a high switching
frequency? This question arises because AC-DC PFC converter circuit operating in CCM
exhibits large diode reverse recovery current which results in the increased conduction loss of
active switches used in the converter. In addition to this, at low line input voltage range,
large amount of conduction loss is caused by diode bridge rectifier, large MOSFET on-state
resistance, and diode drop, which results in low efficiency of PFC pre-regulator circuit.
The PFC converter operating at high switching frequency has two major issues; (1)
Emission of EMI into utility grid and (2) generation of switching losses during switching
transient period.
However, passive filtering method is employed to reduce the EMI
emissions into the utility. On the other hand, conduction losses remain almost constant for
different switching frequencies but switching loss increases proportionally with the switching
frequency.
Thus it is essential to reduce the switching losses of AC-DC PFC converter
operating at high switching frequency. In the last couple of decades, significant effort has
been performed to minimize or to eliminate the PWM converter switching losses by
employing soft switching techniques in PWM DC-DC as well as in AC-DC PFC converters
[55-101, 107, 143-155].
The soft switching technique not only minimizes the switching loss but also provides
68
normal and safe operation of semiconductor switches in PWM converters [15, 84]. The soft
switching is achieved in association with auxiliary circuit called snubber circuit. Hence
snubbers are used to reduce switching losses, stresses and noise in semiconductor switch
during its turn-off and turn-on processes. These stresses, strains and noise are due to parasitic
capacitance, stray inductance and other imperfections in practical circuit and devices.
Generally, passive snubbers are more desirable due to their inherent reliability, simple design,
higher performance/cost ratio and independence [70, 94-96, 100, and 143]. These auxiliary
passive circuits essentially minimize the switching losses of PWM converters to which they
employed.
In this chapter, a novel passive snubber circuit is investigated and proposed to achieve
soft switching in PFC boost converter with the primary objective of achieving near unity
input power factor of PFC pre-regulator. The application of this novel passive snubber
topology in AC-DC PFC boost converter applications is not yet reported in the literature.
However, this passive snubber circuit is employed in the soft switching of DC-DC buck
converter, which is reported in reference [92] for low power applications. The proposed
passive snubber circuit provides ZCS and ZVS conditions for turn ON and OFF of MOSFET
switch respectively in boost converter, and it does not introduce extra voltage and current
stress on the semiconductor controlled MOSFET switch. In the proposed technique, by
considering the magnitude of ripple current flowing in the switch, the peak switch current
during the resonance interval is designed to be less than the designed switch current without
the snubber. Hence, the proposed passive snubber technique does not introduce over current
stress on the controlled semiconductor active switch.
This chapter is organized as follows: Section 3.1 presents description of the proposed
passive snubber circuit and feedback system of AC-DC PFC boost converter. The operating
principle, steady state analysis and equivalent modes of operations are described in section
69
3.2. Design procedure for practicability of the proposed topology is illustrated in section 3.3.
In section 3.4, the simulated and experimental results are shown to prove the theoretical and
mathematical analysis. Section 3.5 presents the comparison of efficiency curves of hard
switched AC-DC PFC boost converter with that of the proposed single-phase AC-DC PFC
boost converter. Finally important features are summarized in section 3.6.
3.1
Circuit description and PFC feedback system
3.1.1 Circuit description
The proposed single-phase AC-DC PFC boost converter with passive snubber circuit
is shown in Fig. 3.1. The single-phase module of the proposed converter is composed of a
Lb
Lin
Cin1
iDB
I0
iLb
iin
Vac
DB
Cin 2
iLsn
Lsn
Vin
D3
Cst
Lst
D2
SW
iSW
D4
D1
C0
V0
Csn
Fig. 3.1 Proposed single-phase AC-DC PFC boost converter with passive snubber circuit
small EMI filter (Lin and Cin1) followed by single-phase bridge rectifier, a low value of high
frequency bypass capacitor filter Cin2 and a DC-DC boost converter incorporated with
auxiliary passive circuit. Lb is the boost inductor, DB is the boost diode. Co is the output
filter capacitor. The passive snubber circuit is composed of a snubber inductor Lsn, storage
inductor Lst, storage capacitor Cst, snubber capacitor Csn and auxiliary diodes D1, D2, D3 and
D4. The concept of operation involves the transfer of snubber capacitor (Csn) energy to a
storage capacitor Cst via a resonance process and then delivers it to the output in the
70
successive switching action. In this passive snubber circuit, snubber elements Csn and Lsn are
fully discharged within a switching period, and hence provides zero current turn-on and zero
voltage turn-off to the active switch of boost converter. The auxiliary diodes D1, D2, D3, and
D4 are also turned ON and turned OFF under ZVS or/and ZCS.
The DC output voltage Vo and boost inductor current iLb of a proposed single-phase
AC-DC PFC soft switched converter are sensed accurately and fed to the feedback system. A
CCM PFC controller eight pin IC ICE2PCS01 is employed in feedback system which uses
ACMC to achieve nearly unity input power factor in addition to obtaining the regulated
output voltage. The detailed description of this ACMC is method reported in reference [156].
In this method, the inductor current is continuously monitored and the current loop is
designed to regulate the average inductor current such that it is proportional to the off duty
cycle of switch SW and thus inductor current follows rectified input voltage. Hence, the input
line current is as sinusoidal as possible and in this PFC control IC ICE2PCS01, it is not
required to sense the input voltage in the proposed PFC converter as that was required in PFC
UC3854 controller described in section 2.1.2 of chapter 2. The triggering pulses generated
from PFC controller IC ICE2PCS01 are fed to active switch SW of the proposed converter.
3.1.2
PFC feedback system
The simplified block diagram of current averaging circuit which is inbuilt in the PFC
controller IC ICE2PCS01 is shown in Fig. 3.2. The boost inductor current iLb is sensed by a
shunt resistor Rsense of the power converter circuit. As this sensed signal is of negative
polarity together with switching ripple, the controller need to do signal averaging and convert
the polarity to positive in order to apply to the following PWM block. The transfer function
of averaging circuit block shown in Fig. 3.2 is given by,
K ave (S) =
Vcomp
iLb
K RSENSE
V0_EA
=
1+ s
(3.1)
K Ccomp
V0_EA (gOTA )
71
Power converter
RSENSE
Full - wave
rectifier
i
Lb
R1
Offset_low load
To PWM comparator
Vcomp
OTA
OTA
Current averaging Current Mirror
Ccomp
1: 1
circuit
R2
I =
1
Vcomp
R
2
Multiplier
V0_EA
Fig. 3.2 Inductor current averaging block diagram in PFC AC-DC converter with
passive snubber
where K = R2/R1, and gOTA is the trans-conductance of the error amplifier OTA for
current averaging circuit and V0_EA is the variable controlled by voltage loop. Ccomp is the
capacitor at output terminal of the averaging circuit which filters out the switching current
ripple. So the corner frequency of the averaging circuit fave must be lower than the switching
frequency fs of the converter. hence,
Ccomp =
gOTA (V0 _ EA )
(3.2)
K (2π f ave )
Under normal mode of operation, the signal Vcomp is proportional to the averaged
inductor current and is applied to PWM comparator block to generate required triggering
pulses. To regulate the output voltage, a multiplier in the feedback system controls the
amplitude of the sinusoidal reference signal in accordance with the voltage error signal
generated from output voltage of the proposed converter. When the load decreases, the output
voltage increases. To maintain constant load voltage, the control circuit senses the load
voltage and the pulse width is automatically reduced in the switching cycle and the output
voltage is regulated and maintained almost constant.
72
3.2 Operating principle of proposed converter
To simplify the steady state analysis and operating intervals of the circuit, the
following conditions are assumed during one switching cycle.
o Semiconductor switches, inductors, and capacitors are ideal.
o The bridge rectifier output voltage Vin is constant over a switching period, as
switching frequency is quite high compared to AC input frequency.
o Output filter capacitor Co is large enough to maintain a constant output voltage Vo.
o The reverse recovery time of diodes D1, D2, D3 and D4 are ignored.
The circuit behavior during one switching cycle can be explained in nine intervals
with the help of key waveforms shown in Fig. 3.3. The operating states of the proposed
converter shown in Fig. 3.4 are analyzed under steady state condition and Table 3.1 shows
the conduction state of auxiliary diodes in various intervals of operation.
Table 3.1: Conduction state of auxiliary diodes D1-D4 in a proposed
snubber circuit
Intervals
Diodes t0<t<t1 t1<t<t2 t2<t<t3 t3<t<t4 t4<t<t5 t5<t<t6 t6<t<t7 t7<t<t8 t8<t<t9 t9<t<t10
D1


D2



None
None
D3

D4



The equivalent circuits are described below.
Mode 1 (t0<t<t1): Prior to t=t0, only boost diode DB is under conduction, switch SW
and all auxiliary diodes are in OFF state. This interval is shown in Fig. 3.4(a). At instant
t=t0, the switch SW is turned ON by applying triggering pulses, hence it turns-on with ZCS.
The rate of rise of switch current iSW during turn-on transition is limited by snubber inductor
Lsn. During this interval, current in snubber inductor Lsn ramps up linearly while the boost
diode current iDB ramps down in a complimentary manner.
73
T
VGSW
DSW T
i Lb
i
SW
VSW
i
Lsn
iDB
i
Lst
V
Cst
x
V
Csn
t0
t1
t4
t2
t3
t5
t6 t
7
t9
t10
t
t8
Fig. 3.3 Key waveforms of the proposed soft switching PFC AC-DC boost converter
with passive snubber circuit
The following equations can be obtained for the interval 1,
iLb (t )  iLb (t0 ) 
(Vin V0 )
(t  t0 )
Lb
iSW (t )  iLsn (t )  iLsn (t0 ) 
iDB (t )  iDB (t0 ) 
(3.3)
V0
(t  t0 )
LSn
`
(3.4)
V0
(t  t0 )
Lsn
(3.5)
VSW (t )  VCsn (t )  0
(3.6)
At the instant t=t1, switch current iSW reaches Iin (iLb(t1)) and boost diode current iDB
falls to zero. Then, the switch current iSW continues to rise and iDB current continues to fall
in reverse direction. As a result, at t=t2, the reverse recovery current of DB falls to –Irr,
74
Lb
DB
iDB
I0
iLb
iLsn
Vin
Lsn
C0
V0
SW
iSW
Fig. 3.4(a) Converter operation in interval (t0-t2)
thus the boost diode DB turn-off under ZVS and this mode ends at t=t2. During this stage,
iDB (t )  
V0
(t  t1 )
Lsn
(3.7)
iSW (t2 )  iLsn (t2 )  Iin  I rr
(3.8)
iDB (t2 )  I rr
t12  trr 
(3.9)
Lsn
I rr
V0
(3.10)
here, Irr and trr are the reverse recovery current and reverse recovery time of the boost diode
DB respectively, for the given forward current values of IF=Iin and –di/dt=-V0/Lsn.
Mode 2 (t2<t<t3): The equivalent circuit during this mode is as shown in Fig. 3.4(b).
As soon as boost diode DB turns off, the auxiliary diode D1 becomes forward biased and
hence the resonant circuit is formed along the path Csn-Lst-D1-Cst-Lsn. During this interval, the
snubber capacitor Csn and storage capacitor Cst starts charging by output voltage V0. Hence,
the following equations can be obtained during this interval,
iLb (t )  iLb (t2 ) 
iLsn (t )  iLb (t ) 
Vin
(t  t2 )
Lb  Lsn
(3.11)
V0
sin 1 (t  t2 )
Z1
iLst (t )  iLsn (t )  iLb (t ) 
(3.12)
V0
sin 1 (t  t2 )
Z1
(3.13)
75
VCsn (t )  V0
1
[1 cos 1 (t  t2 )]
(1  x)
(3.14)
VCst (t )  xVCsn (t )
(3.15)
where
Z1 
Leqt
Ceqt
C
and x  sn
,  1
1
(C C )
, Leqt  Lsn  Lst , Ceqt  sn st
(Csn  Cst )
Leqt Ceqt
is the raio between C
Cst
sn
and C .
st
Lb
iLb
Vin
I0
Cst
Lsn
iLsn
D1
C0
V0
Csn
SW
Fig 3.4(b) Converter operation in interval (t2-t3)
This mode continues until the snubber capacitor Csn charges to a level of output
voltage V0. Hence at t=t3,
VCst(t3) = V0,
thus by using (3.14),
we have,
cosω1(t3-t2) = -x
(3.16)
By substituting (3.16) into (3.15), we have
Vcst(t3) = xV0
(3.17)
hence, in order to ensure the existence of t2 for charging snubber capacitor Csn completely,
the value of x in (3.16) should be less than or equal to 1. Therefore, CSt ≥ CSn.
by using (3.16 ), we have,
(t3  t2 ) 

1 
 sin1 x
1 2

(3.18)
Mode 3 (t3<t<t4): Fig. 3.4(c) shows the equivalent circuit during mode 3. At t3, as
soon as snubber capacitor Csn reaches to a level of output voltage V0, the auxiliary diode D2
76
becomes forward biased, hence D2 turns-on with ZCS. During this interval, the energy stored
in storage inductor Lst is transferred to the storage capacitor via the resonance path Lsn-D2-LstD1-Cst. The following equations are valid during this interval,
iLb (t )  iLb (t3 ) 
Vin
(t  t4 )
( Lb  Lsn )
(3.19)
Lb
iLb
Lsn
iLsn
Vin
I0
Cst
D1
SW
C0
V0
D2
iSW
Fig. 3.4(c) Converter operation in interval (t3-t4)
iLsn (t )  iLb (t ) 
iLst (t ) 
V0
cos [2 (t  t3 )  2 ]
Z2
(3.20)
V0
cos [2 (t  t3 )  2 ]
Z2
(3.21)
VCsn (t ) V0
(3.22)
(3.23)
VCst (t )  x V0 sin[2 (t  t3 )  2 ]
where
Z2 
Leqt
Cst
,  2

x 
, and 2  tan1 
.
 1 x 
Leqt Cst
1
This mode ends when the energy from Lst is transferred to storage capacitor Cst
completely. Hence the current through storage inductor gradually ceases to zero at t4, and
hence both diodes D1 and D2 are turned OFF at near zero current.
77
Mode 4 (t4<t<t5): As shown in Fig. 3.4(d), the switch current iSW continues to conduct.
A load is supplied by the output capacitor C0 and the input power continues to store in the
boost inductor Lb. This interval defines the duty cycle of the switch SW and is equivalent to
switch ON period of conventional hard switch PWM boost converter. In this interval, the
passive snubber circuit is completely inactive.
Lb
I0
iLb
Vin
iLsn
Lsn
C0
V0
SW
iSW
Fig. 3.4(d) Converter operation in interval (t4-t5)
During this interval,
iLb (t )  iLsn (t )  iLb (t4 ) 
Vin
(t  t4 )
( Lb  Lsn )
(3.24)
iLst (t )  0
(3.25)
VCsn (t ) V0
VCst (t ) 
(3.26)
 x V0
(3.27)
Mode 5 (t5<t<t6): This interval is shown in Fig. 3.4(e). The triggering pulse to switch
SW is removed at t5, thus the switch is turned-off near ZVS and its rate of change of voltage
is limited by snubber capacitor Csn. During this interval, the current in snubber inductor Lsn
keeps flowing and it acts as a current source and hence the current flows through the auxiliary
diode D2 and auxiliary diode D1 will not be conducted as it is reverse biased by a storage
78
capacitor voltage VCst. During this interval the capacitor Csn is discharged to load through Iin
(input current iLb(t)). During this mode,
iLb (t )  iLsn (t )  iLb (t5 ) 
Vin VCsn (t ) V0
(t  t5 )  I in
( Lb  Lsn )
(3.28)
iLst (t )  0
(3.29)
VCsn (t )  V0 
VCst (t ) 
Iin
(t  t5 )
CS n
(3.30)
 x V0
 VCst (t6 ) 
(3.31)
 x V0 
VCst (t5 )
(3.32)
Lb
I0
iLb
Vin
iLsn
Lsn D
2
C0
V0
Csn
SW
Fig. 3.4(e) Converter operation in interval (t5-t6)
This mode ends when the snubber capacitor voltage Vcsn drops to a level of
x Vo.
From (3.30), we have,
(t6  t5 )  (1 x)
Csn
V0
Iin
(3.33)
Mode 6 (t6<t<t7): The equivalent circuit during this mode is shown in Fig. 3.4(f).
During this interval, the energy stored in the capacitors Cst and Csn is discharged to output
load. The diodes D1 and D3 are reverse biased hence the snubber capacitor Csn is discharged
through D2 and the storage capacitor Cst discharges through D4.During this interval,
79
iLb (t )  iLsn (t )  iLb (t6 ) 
(Vin VCsn (t ) V0 )
(t  t6 )
( Lb  Lsn )
(3.34)
iLst (t )  0
(3.35)
VCsn (t ) 
 x V0  C
Iin
Iin
(t  t6 ) 
sin3 (t  t6 )
x 3 Cst (1  x)
st (1  x)
(3.36)
VCst (t ) 
 x V0  C
Iin
(t  t6 )
(1
 x)
st
(3.37)
here,
 3
1
.
Lsn Ceqt
Lb
I0
iLb
iLsn
Vin
Lsn
Cst
D2
D4
C0
V0
Csn
SW
Fig. 3.4(f) Converter operation in interval (t6-t7)
At the end of this mode, the snubber inductor current iLsn gradually ceases to zero,
hence the diode D2 is turned OFF at ZCS. At t=t7, the following equations are valid,
iLsn (t7 )  0
 x V0  1in x
Lsn
Cst

x  
1 x 2
1
  sin x 
1  x  2
x



(3.39)
 x V0  1in x
Lsn
Cst

x  
1 x 2
1
  sin x 
1  x  2
x




(3.40)
vCsn (t7 ) 
vCst (t7 ) 
(3.38)
I
I
Mode 7 (t7<t<t8): This interval of operation is shown in Fig. 3.4(g). The discharge of
storage capacitor Cst continues to discharge by Iin during this interval. The path D3-Lst-D1
80
will not conduct as D1 is reverse biased by storage capacitor voltage vCst. During this mode,
following equations are valid.
iLb (t )  iLsn (t )  iLb (t7 ) 
(Vin  VCst (t ) V0 )
(t  t7 )
Lb
(3.41)
iLsn (t )  iLst (t )  0
(3.42)
VCst (t ) VCst (t7 )
(3.43)
Lb
I0
iLb
Cst
Vin
D4
C0
V0
Fig. 3.4(g) Converter operation in interval (t7-t8)
VCst (t ) VCst (t7 ) 
Iin
(t  t7 )
Cst
(3.44)
This interval ends at t8, at this instant the voltage level of storage capacitor vcst is given by
VCst (t8 ) VCsn (t7 )
(3.45)
Mode 8 (t8<t<t9): Fig. 3.4(h) shows the equivalent circuit during this interval. At
instant t=t8, the diode D3 becomes forward biased and hence the earlier remained energy in
the snubber capacitor Csn is discharged to output load. Simultaneously, the stored capacitor
Cst continues to discharge through D4. This mode ends when both the capacitors Csn and Cst
are completely discharged and hence both the diodes D3 and D4 are turned OFF at near zero
voltage. During this mode,
81
Lb
I0
iLb
D3 Cst
Vin
D4
C0
V0
Csn
Fig. 3.4(h) Converter operation in interval (t8-t9)
iLb (t )  iLb (t8 ) 
(Vin  VCst (t ) V0 )
(t  t8 )
Lb
(3.46)
iLsn (t )  iLst (t )  0
(3.47)
VCsn (t )  VCsn (t8 ) 
VCst (t ) VCst (t8 ) 
Iin
(t  t8 )
Cst (1  x)
(3.48)
Iin
(t  t8 )
Cst (1  x)
(3.49)
Mode 9 (t9<t<t10): The equivalent circuit for this interval is as shown in Fig. 3.4(i).
This interval is essentially a boost diode conduction mode which connects the load to supply
line through boost inductor Lb. The passive snubber circuit is not active and the response of
this stage is similar to that of the switch OFF period of conventional hard switched PWM
boost converter.
Lb
DB
I0
iLb
Vin
C0
Fig. 3.4(i) Converter operation in interval (t9-t10)
82
V0
During this interval, the following equations are valid,
iLb (t )  iLb (t9 ) 
(Vin V0 )
(t  t9 )
Lb
(3.50)
iLsn (t )  iLst (t )  0
(3.51)
VCsn (t )  VCst (t )  0
(3.52)
VSW (t ) V0
(3.53)
At the instant t=t10, one complete cycle is completed and the next switching cycle is repeated
from that instant onwards.
From the key waveforms of the analysis shown in the Fig. 3.3, the minimum on-time ‘ton,MIN’
and minimum off-time ‘tof,MIN’ of the active switch can be obtained as follows,
ton, MIN 
Lsn Iin
1  
1
1
1 

tan1
1
  sin x 
 1
V0
12
x
(3.54)
toff , MIN 
Csn V0 
1 

1 
I in 
x 
(3.55)
here, the minimum on-time ‘ton,MIN’ in the minimum time required to transfer the complete
stored energy from snubber capacitor Csn to the reset circuit. This time is measured from t0 to
t4. While the ‘toff,MIN’ is the total time measured from ‘t5’ to ‘t9’.
If the actual on time of the switch is shorter than ton,MIN, the complete energy would
not be transferred to the storage capacitor Cst before the turn-off of the switch SW. Hence, the
switch has to be turned off with some non-zero voltage of snubber capacitor Csn, which may
result in nonzero voltage switching of the switch. On the other hand, if the actual turn-off
time of the switch SW is shorter than toff,MIN, then Cst cannot be completely discharged before
the switch SW is turned ON. Then, when the switch is turned ON, Cst cannot be completely
discharged. Then the snubber capacitor voltage vCsn is nonzero before the switch is turned
OFF. Hence, the switch will be turned OFF with nonzero voltage. In both of the cases, as
83
described in Fig. 2 and Fig. 3, the switch can still be turned ON with zero current from ‘mode
9’ to ‘mode 1’ (next successive switching cycle), due to the presence of snubber inductor Lsn,
even if the main switch cannot be turned OFF with zero voltage.
3.3 Design procedure
The procedure of selecting boost converter components Lb, and Co is the same as that
for a conventional PWM boost converter as described in section 2.3.2, chapter 2, hence, in
this chapter, the more focus is given on the designing of the passive auxiliary circuit, where
the snubber, storage inductors and snubber, storage capacitors are most important
components for proposed soft switching.
3.3.1 Snubber inductor Lsn
It was mentioned in the introduction of this chapter that, one of the main problems of
the boost converter is reverse recovery current of the boost diode. This is a function of the
diode’s turn-off di/dt and can be improved by diverting the flow of current through it
eventually. Hence, the precise value of Lsn is computed by considering the rate of rise of
switch current during turn-on period of MOSFET switch, hence,
Lsn 
t12 V0
I in _ max
(3.56)
where t12 is the reverse recovery time which is a part of interval 1 described in section 3.2.
Iin_max is the peak value of input current Iin.
3.3.2 Snubber and storage capacitors CSn and CSt
The values of Csn and Cst are designed by the following standard iterative procedure.
In the initial step, x  [0,1] is arbitrarily selected. In the second step, it is to be ensured that the
MOSFET switch voltage stress during mode 5 must be less than V0. Based on this, by
substituting ‘x’ into (3.39) and assuming VCs is less than V0, it can be found that,
84
2
x  I in 

CSn 


1  x V0 (1  x) 


1 x 2
1
 2  sin x 
x

2



(3.57)
The minimum value of input current Iin, Iin_min which ensures the soft switch is
calculated by substituting ‘x’ into (3.55) with the designed minimum OFF time toff,MIN_d.
Thus,
Iin _ min 
Csn V0 
1 

1 
toff , MIN _ d 
x 
(3.58)
here, toff,MIN_d is the designed minimum off time value of toff_MIN.
The arbitrarily selected value of ‘x’ is accepted if above calculated value of Iin_min is below the
designed minimum input current for PFC boost converter (procedure described in section
2.3.2, chapter 2). Otherwise, another value of ‘x’ is selected and the same steps are repeated.
With the proper selection of ‘x’, Cst is obtained from the value of Csn, i.e. Cst=Csn/x.
3.3.3 Storage inductor Lst
One of the important factors considered in soft-switching is the reduction of current
stress on the MOSFET device. Hence, the suitable value of storage inductor Lst is calculated
based on the current stress on the switch which is not higher than the designed input line
current ripple ∆Iin. Thus, based on (3.13), we have
 V 2 Csn
Lst   0 
 Lsn
 I  1  x
(3.59)
Note: It is required to compare the calculated value of ton_MIN in (3.54) with the
minimum duty cycle ratio duration required for the boost converter to achieve soft switching
and to obtain nearly unity input power factor of the proposed converter. i.e. DMin T > ton_MIN.
If this condition is satisfied, above calculated set of components will be taken. Otherwise, the
new set of values will be chosen again.
3.4
Simulation and Experimental results
A prototype of the proposed single-phase AC-DC PFC boost converter with passive
snubber circuit has been built and fabricated in the Power Electronics and Drives
85
laboratory, NIT, Rourkela. The proposed converter operates with an input voltage of 215
Vrms, output voltage V0=400 V, 500 W and a switching frequency of 100 kHz.
The
schematic of the proposed converter is simulated in PSIM simulator package to verify the
theoretical and design analysis of the proposed converter. The major parameters and
components employed in the prototype are tabulated in Table 3.2.
Table 3.2: Components used in the Proposed 1-phase PFC with passive
snubber converter
Component
Value/Model
Simulation
Experiment
Bridge Rectifier IC
Ideal
GBJ 2506-BP
Switch, SW
Ideal
IRFP 460
Auxiliary Diodes (D1 – D4)
Ideal
RHRP 3060
Boost Diode, DB
Ideal
DSEI 30-12A
Low line filter inductor (Lin)
5.6μH
5.6μH
0.47μF, 275V
Input filter (Cin1)
1μF, 630V
Input HF bypass capacitor (Cin2)
0.47μF, 275V
1μF, 630V
Boost inductor (Lb)
1.5 mH
1.5 mH
Snubber inductor (Lsn)
2.5 μH
2.5 μH
Storage inductor (Lst)
62.5 μH
62.5 μH
Snubber capacitor (Csn)
0.68 μF
0.68 μF
Storage capacitor (Cst)
1.2 μF
1.2 μF
450μF, 600V
output capacitor (C0)
450μF, 600V
The simulation and experimental results of snubber inductor current iLsn, storage
inductor current iLst, snubber capacitor voltage VCsn, and storage capacitor voltage VCst
waveforms are shown in Fig. 3.5 and Fig. 3.6 respectively. From Fig. 3.5 and Fig. 3.6, it
86
can be verified that, the experimentally obtained waveforms presented in Fig. 3.6 are closer
to that obtained in simulation response shown in Fig. 3.5. This is a proof of evidence that,
the simulation and experimental results are strongly agree with the theoretical designed
analysis of the operating principle of the proposed PFC converter with passive snubber
circuit.
Fig. 3.5 Simulation results of resonant elements of proposed passive snubber circuit
Top: Snubber inductor (Lsn) and storage inductor (Lst) currents
Bottom: Snubber capacitor (Csn) and storage capacitor (Cst) voltages
Fig. 3.7 and Fig. 3.8 show the simulation and experimental switching waveforms
respectively of MOSFET switch SW at full load condition. Comparing simulated results
shown in Fig. 3.7 with experimentally obtained results presented in Fig. 3.8, the
experimentally obtained results are nearly identical to simulation results, except that the
87
iLsn
iLst
VCsn
VCst
Fig. 3.6 Experimental results of resonant elements of proposed passive snubber circuit
Top:
Snubber inductor (Lsn) and storage inductor (Lst) currents
Bottom: Snubber capacitor (Csn) and storage capacitor (Cst) voltages
Scale: Ch1, Ch2: 2 A/div, Ch3, Ch4: 200 V/div, 1 μsec/div
presence of di/dt effect in Fig. 3.8 across the MOSFET switch, which is due to stray
inductance of the circuit. However, the voltage across the MOSFET switch SW is equal or
within the output voltage level. In both the cases, the switch turns on with zero current and
turns off with zero voltage.
Fig. 3.7 Simulation results of switching characteristics of switch SW of
proposed converter
88
Overshot due to stray inductance
of the circuit
VSW
iSW
Zero voltage turn OFF
Zero current turn ON
Fig. 3.8 Experimental results of switching characteristics of switch SW of proposed converter
Scale: Ch1: 100 V/div, Ch2: 1 A/div, 1μs/div
The simulation and experimental results of soft switching characteristics of boost
diode DB are shown in Fig. 3.9 and Fig. 3.10 respectively. The boost diode DB exhibits zero
voltage turn-off and zero current turn-on processes.
Fig. 3.9 Simulation results of soft switching of boost diode in proposed passive snubber converter
Top: Boost diode current iDB waveform. Bottom: Boost diode voltage VDB waveform.
89
VDB
Zero voltage turn OFF
iDB
iDB
(Vcst + VD4)
Zero current turn ON
Reverse recovery
current
Fig. 3.10 Experimental result of soft switching of boost diode in proposed passive
snubber converter
Scale: Ch1: 200 V/div, Ch2: 1 A/div, 1μs.
The experimentally obtained result shown in Fig. 3.10 almost resembles the simulated
switching results of boost diode DB presented in Fig. 3.9, except that the absence of reverse
recovery current of boost diode DB in the Fig. 3.9. This is because, the discrete transition
simulators like PSIM do not apply full physical model of device and as a result such
simulators are not capable of showing parasitic processes such as reverse recovery process.
In the proposed converter, the boost diode DB turns off with ZVS and turns on with ZCS.
Fig. 3.11 shows the simulated and experimental results of voltage and current
waveforms of auxiliary diode D1. This diode starts conducting at the beginning of the ‘mode
2’ (t2-t3) and terminates its conduction at the end of the ‘mode 3’ (t3-t4). This diode exhibits
zero voltage turn-on and turn-off processes.
The simulated and experimentally obtained switching voltage and current waveforms
of auxiliary diode D3 are presented in Fig. 3.12. This device conducts only during ‘interval
8’ (t8-t9) and experiences zero current turn-on and zero voltage turn-off. From Fig. 3.11 and
Fig. 3.12, it can be observed that, the voltage across and current through these diodes D1 and
D3 are well below the load voltage and load current, hence there are no voltage and current
stresses on these devices.
90
Volts / Amps
VD1
Zero voltage
Turn on
Zero voltage
Turn off
iD1
(a)
Volts / Amps
(b)
Fig. 3.11
(a) Simulated voltage and current switching waveforms of auxiliary diode D1
(Current signal is magnified by a factor 20)
(b) Experimental voltage and current switching waveforms of auxiliary diode D1.
(c) Scale: 100 V/div, 2 A/div, 1μs/div
Zero current
Turn on
VD3
iD3
Zero voltage
Turn off
(b)
Fig. 3.12
(a) Simulated voltage and current waveforms of auxiliary diode D3
(Current signal is magnified by factor 20)
(b) Experimental voltage and current waveforms of auxiliary diode D3.
Scale: 100 V/div, 1 A/div, 1 μs/div
(a)
The other auxiliary diodes D2 and D4 conduct for very short duration over a period of
switching cycle and it is noticed that these also experience soft switching with the permissible
voltage and current ratings in the principle of operation of a proposed converter.
The experimental input voltage and input current waveforms of a proposed soft
switched PFC AC-DC converter for an input voltage of 215 V at full load condition are
91
presented in Fig. 3.13. It is ascertained that, the input current is in phase with input line
voltage and the measured value of the THD of input current is found to be 7.7% and its
corresponding input PF is 0.997. The Fig. 3.14 shows the experimental set-up of proposed
single-phase PFC with passive snubber converter.
Fig. 3.13 Experimental input voltage input current waveforms of proposed 1phase PFC AC-DC converter with passive snubber circuit
Scale: Ch1: 100 V/div, Ch2: 2 A/div, 2.2m s.
Fig. 3.14 Prototype of proposed 1-phase AC-DC PFC converter with passive snubber circuit
92
Buy SmartDraw !- purchased copies print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
3.5
Comparison of efficiency curves
The comparison of efficiency curves of proposed soft switched PFC boost converter
with that of hard switched PFC converter for a nominal input voltage of 215 V is presented in
Fig. 3.15. It is observed that the efficiency curve of the proposed soft switched converter is
relatively higher than that obtained in the hard switched converter. It can also be observed
that, the efficiency of the proposed single-phase soft switched converter varies from 89.5 %
to 97.3%. The highest efficiency of the proposed soft switched converter is obtained at full
load power of 500 W which is around 6% higher than that of the conventional hard switched
PFC converter. It is noted that, the performance of the proposed converter is superior to the
converters reported in references [71, 72, 84, 97, 102] with respect to the efficiency
parameter. The high efficiency of the proposed converter concludes the correctness of the
designed value of components.
100
98
96
94
92

90
88
86
84
Soft-switched with passive snubber
Hard-switched converter
82
80
0
100 150 200 250 300 350 400 450 500
Fig. 3.15 Comparison of efficiency curves of single-phase conventional hard switched
PFC converter and proposed single-phase soft switched PFC converter
93
Buy SmartDraw!- purchased copies print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
3.6
Summary
A high power quality single-phase AC-DC PFC boost converter with passive
auxiliary circuit for medium and high power applications is proposed in this chapter. The
auxiliary passive snubber circuit employed in AC-DC PFC boost converter has been
explained with the emphasis on the mathematical and theoretical analysis. The predicted
operating modes and simulation results of the proposed converter are confirmed by the
comparison of experimental results obtained from a realized prototype of 500 W, 400 V and
100 kHz AC-DC PFC boost converter. All measurement results are carried out briefly on this
proposed soft switched PFC boost converter. The maximum efficiency of 97.3% is achieved
at full load condition. In the proposed, both the active switch and boost diode are turned on
with zero current and turned off exactly at zero voltage. On the other hand, all other
semiconductor switches are turned on and off under exact ZVS and/or ZCS. The proposed
soft switching PFC converter has achieved nearly unity power factor at full load condition
and even at light load condition with low THD.
94
Chapter 4
Application of novel ZVT to PFC
Boost Converter with Active
Auxiliary Circuit
o Introduction
o Topology description and PFC feedback system
o Operating principle and analysis
o Design procedure
o Simulation and Experimental results
o Performance of proposed converter
o Summary
95
Introduction
In the previous chapter, soft switching of PFC boost converter with passive auxiliary
circuit was discussed. Although this soft switching technique performs well with respect to
reliability of the system and efficiency, passive snubber circuits (dissipative circuit consisting
of diodes and passive components) shift the switching power loss from the switch to the
snubber circuit and therefore may not provide a reduction in the overall switching power loss
[15, 76].
The recent soft switching technique with passive snubber proposed in reference
[92] however reduces the switching losses but exhibits voltage stress on boost diode of boost
converter. This is because; the boost diode voltage is sum of voltages of storage capacitor
and one of the auxiliary diodes. Although, some of the soft switching techniques proposed in
reference [71, 95, 157, 159-162] can help to minimize switching losses at switching
frequencies, they typically experience at least two of the following limitations;
1)
Extra voltage stress across the active switch, due to the variation of the voltage
across the snubber capacitor during resonance interval. This leads to the additional
off-state stress on the active switch.
2)
Current stress on the switch, this is because the switch current includes the
discharging current of the snubber capacitor and main current flow for energy
conversion.
3)
Soft switching cannot be ensured at heavy load conditions because the snubber
circuit cannot completely reset before the next energy absorbing process.
A relatively simple active snubber circuit consisting of auxiliary switch, resonant
elements inductor, capacitor, and auxiliary diodes can overcome the drawbacks of the passive
circuit discussed above. With the aim of achieving an improvement in overall performance of
PWM DC-DC as well as AC-DC PFC converters, soft switching with active snubber circuits
have been subject of intensive research from a couple of decades [73, 97-100, 103, 107, 144,
96
147].
In addition, it has been reported that soft switching with active snubber circuit
techniques provide improved performance with respect to efficiency and EMI of the
converter when compared with soft switching techniques with passive snubber circuit [73, 88,
97, 107, 144, 147, 157, 158].
These soft switching techniques with active snubber circuits allow the power
converters to operate with higher switching frequencies without penalizing the trade-off
between converter efficiency and switching losses. Among all soft switching techniques, the
switch commutation under zero voltage transition (ZVT) is better among the best soft
switching techniques [113]. A systematic approach to study the synthesis and properties of
the generalized form of soft switching with active snubber category of circuits has been
presented in [88, 110, 112, 113]. In ZVT technique, a resonant circuit is employed in parallel
with the power switch and hence the partial resonance is created by the shunt resonant circuit
to achieve ZCS or ZVS during the switching transition only [79].
In this chapter, a novel active snubber circuit is employed in a boost converter of a
single-phase AC-DC PFC boost converter to achieve ZVT of an active switch. This proposed
circuit not only provides soft switching to main switch, but also provides exact or near zero
voltage/zero current switching to auxiliary switch and as well as to other semiconductor
diodes. The proposed circuit also provides zero voltage turn off condition to the active
switch with extended operating range of load power.
This chapter is organized as follows: Section 4.1 describes the description of the
topology of the proposed single-phase AC-DC PFC converter with auxiliary circuit. The
mode of operation of each interval and steady state analysis are discussed in section 4.2.
Design considerations for practicability of the proposed topology are illustrated in section
4.3. In section 4.4, the special features of the proposed converter are summarized. In Section
4.5 simulation and experimental results are presented to prove the theoretical analysis.
97
Section 4.6 shows the comparison of efficiency curves of proposed soft switched AC-DC
PFC converter with hard switched AC-DC PFC converter for a wide range of output power.
Finally important features are summarized in the section 4.7.
4.1 Topology description
Fig. 4.1 shows the proposed single-phase AC-DC PFC soft switched boost converter.
This proposed converter is composed of a small EMI filter (Lin and Cin1) followed by single –
phase bridge rectifier, a low value of high frequency bypass capacitor filter Cin2 and a DC-DC
boost converter. SW1 is the main switch of the boost converter.
The active snubber is
composed of a snubber capacitor CB, a resonant inductor Lr, auxiliary switch SW2 and
auxiliary diodes D1, D2 and D3. The active snubber circuit when switched properly ensures
lossless switching. The DC output voltage and boost inductor current of proposed converter
are sensed accurately and fed to the corresponding feedback system. A continuous
conduction mode PFC controller IC ICE2PCS01 is employed which uses ACMC to achieve
nearly unity input power factor and to obtain a regulated output voltage [156]. The complete
description of PFC feedback system described in section 3.1.2 of chapter 3 is applicable for
this proposed AC-DC PFC converter with active snubber. This is because the objective of
the feedback system is same for both the converters proposed in chapter 3 and as well as in
chapter 4. However, in this proposed soft-switched PFC converter, the generated gating
pulses of IC ICE2PCS01 controller are fed to dual driver IC UC3706. This dual driver IC
UC3706 provides required alternative gate pulses with adequate dead band to both switches
SW1 and SW2 of the proposed single-phase AC-DC boost converter. Whereas, in the proposed
soft-switched converter presented in chapter 3, does not have IC UC3706 arrangement as that
converter has only one active switch, hence, gating pulses of IC ICE2PCS01 are applied to
switch SW.
98
iDB
Lb
iin
D11
iLb
D13
iLr
Cr
Vac
Lin
Cin 2
Cin1
Vin
D14
D12
SW1
SW2
Lr
D3
CB
D1
I0
DB
D2
V0
C0
iSW 1
iSW 2
Fig. 4.1 Proposed 1-phase PFC AC-DC boost converter with active snubber circuit
4.2 Operating principle and analysis
To simplify the steady state analysis and operating intervals of the proposed
converter, the following conditions are assumed during one switching cycle.
o
Semiconductor switches, inductors, and capacitors are ideal.
o
The bridge rectifier output voltage Vin is constant over a switching period as switching
frequency is quite high compared to AC input frequency.
o
Output filter capacitor Co is large enough to maintain a constant output voltage Vo.
o
The reverse recovery time of diodes D1, D2 and D3 are ignored.
The circuit behavior during one switching cycle can be explained in eight intervals with the
help of key/theoretical waveforms shown in Fig. 4.2. The equivalent operating states of the
proposed converter shown in Fig. 4.3 are analyzed under steady state condition. The
equivalent circuits are described in the following intervals.
Interval 1 (t0 - t1): Fig. 4.3(a) shows the operating state of the circuit during this
interval. During the time prior to t0, the switches SW1 and SW2 are in off state and the boost
diode DB is conducting the boost inductor current. At t=t0, the auxiliary switch SW2 is turned
on by applying a gate pulse. The auxiliary switch SW2 and auxiliary diode D3 are turned on
at ZCS and the resonant inductor Lr limits the rapid rate of rise of current through auxiliary
switch SW2. During this interval, the current in resonant inductor Lr ramps up linearly
99
VGSW2
DSW2
VGSW1
DSW1
i
SW1
DA1
Iin_max
DA 2
iLb
Iin_max
i DB
VLr
V0
i
Lr
V
SW1
ILr_max
V0
VDB
V0
VCB
V0
VD1
V0
VD2
V0
VSW2
V0
t
t0
t1 t 2
t3 t 4 t5
t6 t7
t 8 =t 0
Fig. 4.2 Key waveforms
of the proposed soft-switch PFC AC-DC boost
converter with active snubber circuit
While the boost diode current iDB ramps down in a complimentary manner. This interval
completes when the boost diode current iDB reaches to zero.
During this interval,
iLb (t)=iLb (t0 )+
(Vin -V0 )
(t-t0 )
Lb
(4.1)
100
Lb
i
DB
I
i
Lb
i
Lr
i
SW 2
Vin
DB
Lr
0
C
0
D
3
V0
SW
2
Fig. 4.3(a) Equivalent circuit of converter operation during interval (t0-t1)
iLr (t)=isw2 (t)=
V0
(t-t )
Lr 0
iDB (t)=iLb (t0 )-iLr (t) = iLb (t0 )-
(4.2)
V0
(t-t0 )
Lr
(4.3)
(4.4)
Vcr (t)=Vsw1(t)=V0
Interval 2 (t1 – t2): Fig. 4.3(b) shows the operating state of the circuit during this
interval. In this interval, the boost diode current iDB continues to fall in the reverse direction
and the resonant inductor current iLr continues to rise linearly. This can also be referred as
reverse recovery interval of boost diode. This interval ends, when the boost diode current iDB
reaches its maximum reverse recovery current –Irr. Thus the boost diode DB turns off under
ZVS.
Lb
irr
I
i
Lb
Vin
i
Lr
i
SW 2
Lr
D
3
0
DB
C
0
V0
SW
2
Fig. 4.3(b) Equivalent circuit of converter operation during interval (t1-t2)
101
During this interval,
iLb (t)=iLb (t1 )+
(Vin -V0 )
(t-t1 )
Lb
iLr (t)=isw2 (t)=iLb (t1 )+
(4.5)
V0
(t-t1 )
Lr
(4.6)
Vcr (t)=VSW1(t)=V0
(4.7)
iDB (t2 )=-I rr
(4.8)
t12 =trr =
Lr
I
V0 rr
(4.9)
here Irr and trr are the reverse recovery current and the reverse recovery time of the boost
diode DB respectively, for the given value of input current of iLb and –di/dt = –V0/Lr.
Interval 3 (t2 - t3): During this interval, the parallel resonance occurs between Lr and
Cr as shown in Fig. 4.3(c).
A load is supplied by the output capacitor Co. The energy
already stored in the capacitor Cr is transferred to resonant inductor Lr through the resonant
path Cr- Lr- D3-SW2. Hence, the resonant inductor current rises in sinusoidal fashion from the
instant ‘t2’ and reaches its maximum at ‘t3’. During this interval,
iLb (t)= iLb (t2 )+
(Vin - vcr )
(t - t2 )
Lb
(4.10)
Lb
I
i
Lb
Lr
Cr
Vin
0
i
Lr
i
Cr
D
3
SW
2
C
0
i
SW 2
V0
Fig. 4.3(c) Equivalent circuit of converter operation during interval (t2-t3)
102
iLr (t)= isw2 (t)=iLb (t2 )+I rr cosω1 (t - t2 )+
V0
sinω1(t - t2 )
Z1
(4.11)
(4.12)
Vcr (t)=Vsw1(t)=V0 cosω1(t - t2 )- Z1 I rr sinω1(t - t2 )
where
ω1 = 1 / Lr Cr and Z1 = Lr / Cr .
This interval ends when the total energy stored in capacitor Cr is transferred to
resonant inductor Lr and hence the voltage across main switch SW1 becomes zero at instant
‘t3’. At this instant, the resonant current and energy levels of resonant inductor Lr reach their
maximum values and hence following equations can be obtained.
iLr (t3 )=I Lr-max =iLb (t2 )+
V02 +Z12 I rr2
(4.13)
Z1
1
1
1
2
ELr-max = Lr I Lr-max
= Lr [iLb (t2 )+I rr ] 2 + Cr V02
2
2
2
(4.14)
During this interval, the parasitic capacitors of switch SW1 and diode D1 are
discharged from V0 to zero and the boost diode DB and auxiliary diode D2 are charged from
zero to V0.
Interval 4 (t3 - t4): As shown in Fig. 4.3(d), the resonant current which was flowing
through Cr, is diverted to body diode of the main switch SW1 and this body diode SW1_D
conducts the excess current of the resonant inductor Lr provided by the input boost inductor
current iLb(t). During this interval,
iLb (t)=iLb (t3 )+
Vin
(t-t3 )
Lb+Lr
(4.15)
iLr (t)=isw2 (t)=I Lr-max
(4.16)
isw1_D (t)=I Lr_max -i Lb (t)
(4.17)
Vcr (t)=VSW1(t)=0
(4.18)
103
Lb
I
i
Lb
Lr
SW
1_ D
i
Lr
i
SW 1_ D
D
3
SW
2
Vin
0
C
0
V0
i
SW 2
Fig. 4.3(d) Equivalent circuit of converter operation during interval (t3-t4)
The conduction of body diode SW1_D of main switch SW1 maintains a zero voltage
across the main switch SW1 and hence provides ZVT for the main switch SW1. This interval
continues until the triggering gate pulse VGSW1 is applied to gate of the SW1.
Interval 5 (t4 - t5): Fig. 4.3(e) shows operating state of series resonance interval. The
triggering pulse is applied to the main switch SW1 at instant ‘t4’ and the gate signal of
auxiliary switch SW2 is removed simultaneously. Hence, the main switch SW1 is turned on
with ZVT and the current in boost inductor Lb rises linearly and the auxiliary switch SW2
turned off with near ZVS and its growth of rapid change of drain to source voltage is limited
by snubber capacitor CB. During this resonance period, the energy stored in the resonance
inductor Lr is transferred to the snubber capacitor CB.
Lb
i
CB
I
i
Lb
i
Lr
C
SW
1
Vin
D
1
i
SW1
0
B
C
0
V0
Fig. 4.3(e) Equivalent circuit of converter operation during interval (t4-t5)
104
During this interval,
V
iLb (t)=iLb (t4 )+ in (t-t4 )
Lb
(4.19)
iLr (t)= iD1(t)= I Lr-max cosω2 (t - t4 )
(4.20)
VCB (t)= VSW2 (t)= Z 2 I Lr-max sinω2 (t - t4 )
(4.21)
(4.22)
Vcr (t)=VSW1(t)=0
where
ω2 = 1 / Lr CB and Z2 = Lr / CB .
At the end of this interval, the total energy from resonant inductor Lr is transferred to
the snubber capacitor CB. The energy balance equation is given by,
1
1
2
Lr I Lr_max
= CB V0 2
2
2
(4.23)
This interval ends when the snubber capacitor voltage VCB reaches V0 and the resonant
inductor current iLr ceases to zero. As the resonant inductor current iLr ceases to zero at ‘t5’,
the auxiliary diode D1 is turned off near ZCS. At the same instant, voltage across switch
SW2 drops abruptly down to zero and may produce oscillations between resonant inductor Lr
and output capacitance of the auxiliary switch SW2 and such oscillations are prevented by
auxiliary diode D3 .
Interval 6: (t5 - t6): During this interval, the main switch SW1 continues to conduct as
shown in Fig. 4.3(f). A load is supplied by the output filter capacitor C0 and the input power
is stored in boost inductor Lb. This interval is equivalent to switch-on period of conventional
PWM boost converter. In this interval, the active snubber circuit is completely inactive.
During this stage,
iLb (t) = isw1 (t) = iLb (t5 )+
Vin
(t - t5 )
Lb
(4.24)
(4.25)
iLr (t)=0
105
Lb
I
i
Lb
SW
1
0
C
0
Vin
V0
i
SW1
Fig. 4.3(f) Equivalent circuit of converter operation during interval (t5-t6)
(4.26)
Vcr (t)= VSW1(t)= 0
Interval 7 (t6 - t7): This interval is shown in Fig. 4.3(g). The triggering pulse to the
main switch SW1 is removed at ‘t6’. Thus, near ZVS turn off of main switch SW1 is achieved,
at the same instant, the auxiliary diode D2 becomes forward bias due to the boost inductor
current iLb and turns on with ZVS. As the auxiliary diode D2 is turned on, the snubber
capacitor CB limits the rapid change of drain to source voltage of main switch SW1. During
this interval, the capacitor Cr is charged to output voltage V0 and the energy stored in the
snubber capacitor CB is released to output capacitor C0 and hence CB voltage discharges from
V0 to zero.
Lb
I
i
Lb
i
CB
Vin
C D
B 2
C
0
Cr
i
Cr
0
V0
Fig. 4.3(g) Equivalent circuit of converter operation during interval (t6-t7)
106
During this interval,
iLb (t)=iLb (t6 )+
(Vin -V0 -VCB )
(t-t6 )
Lb
(4.27)
iLr (t)=0
(4.28)
Vcr (t)=VSW1 (t)=V0 -vCB (t)
(4.29)
Interval 8 (t7 – t8): Fig. 4.3(h) shows the operating state of the circuit during this
interval. In this interval, the boost diode DB starts conducting the load current and the boost
inductor current starts decreasing. The snubber circuit is not active during this interval. The
response of this stage is similar to that of the switch-off period of conventional PWM boost
converter.
During this interval,
iLb (t)=iDB (t)=iLb (t7 )+
(Vin -V0 )
(1-DSW1 -DSW2 )
Lb
(4.30)
iLr (t)=0
(4.31)
Vcr (t)=VSW1(t)=V0
(4.32)
Lb
DB
I
i
Lb
i
DB
0
Vin
V0
C
0
Fig. 4.3(h) Equivalent circuit of converter operation during interval (t7-t8)
where DSW1 is the duty cycle of the main switch SW1 and DSW2 is the duty cycle of the
auxiliary switch SW2. From Fig. 4.2, DSW2 is given by,
107
DSW2=DA1+DA2
(4.33)
here, DA1 is the duty cycle for the interval (t0-t2) and DA2 is the duty cycle for the interval (t2t4). At the instant t=t8, one complete cycle is completed and the next switching cycle is
repeated.
4.3 Design procedure
Since, the design example of the conventional hard switched PWM boost converters
has been presented in earlier literature and text books; hence, in this thesis the significant
importance is given on design example of active snubber circuit components. However, the
necessary condition for the output voltage of the proposed PFC boost converter is derived
and is same as that of the output voltage equation of the conventional PWM converter. This
is because, the ZVT boost converter operates as same as that of a conventional boost
converter throughout its switching cycle except during the switch turn-on and turn-off
processes. The prototypes of proposed soft-switched PFC converter and as well as hardswitched PFC converter are developed and tested in the Power Electronics and Drvies
laboratory, at NIT, Rourkela. Their specifications are identical and are tabulated in the Table
4.1.
Table 4.1 Specification of proposed single phase soft switched and hard switched
PFC AC-DC boost converter
Input voltage (Vac)
215 VRMS, 50 Hz
Output voltage (V0)
400 V
Output Power (P0) (each module)
500 W
Switching frequency (fs)
100 kHz
Input current peak ripple (ΔILb)
20 %
5%
Output voltage ripple (ΔV0)
108
4.3.1 Boost converter components
4.3.1.1 Boost inductor Lb
From Fig. 4.2, Neglecting the turn off transition (t6 - t7) of switch SW1, writing
voltage-second balance equation of the boost inductor Lb from equations (4.1), (4.5), (4.10),
(4.15), (4.19), (4.24) and (4.30); we obtain,
(Vin -V0 )
V
V
(V -V )
DA1+ in DA2 + in DSW1 + in 0 (1-DSW1 -DSW2 )=0
Lb
Lb +Lr
Lb
Lb
(4.34)
We have, DA1 + DA2 = DSW2, if Lb >> Lr, on Simplification of (4.34), we get,
V0 =
Vin
[1- DSW1 - DSW2 + DA1 ]
(4.35)
if DA2 << DA1,
(4.35) =>
V0 
Vin
(1- DSW1 )
(4.36)
The above equation (4.36) is identical to the output voltage expression of conventional hardswitched boost converter.
If peak-to-peak ripple current of the boost inductor Lb=ΔILb,
Then ΔILb ≈ iLb(t6)-iLb(t2)
(4.37)
Neglecting duty cycle DA2, we obtain,
∆ILb≈(Vin/Lb) DSW1 T
(4.38)
From (4.36) and (4.38),
∆ILb ≈ (V0/Lb) (1-DSW1) DSW1 T

(4.39)

Vo
 (1 D ) D
Lb  

SW 1
SW 1
 (I Lb ) ( f s ) 
(4.40)
Where fs = 1/T, switching frequency of the converter.
Lb will be maximum for DSW1 = 0.5. Hence, Lb should be greater than the value calculated in
(4.40) at DSW1=0.5; therefore, minimum value of boost inductor (Lbmin) is
109
Lbmin 
V0
4(I Lb ) ( f s )
(4.41)
From the specification of the soft-switched proposed converter, the computation of value of
boost inductor ‘Lb’ is found to be 1.5 mH. This boost inductor is fabricated from a sendust
toroidal core (part number – CS468125, CWS make) having 38 single layer turns of 13 AWG
is used.
4.3.1.2 Output Capacitor C0
The converter hold-up time and ripple of output voltage are influenced by the value of output
capacitor. In this design, the criterion for selection of this capacitor is based on the amount of
tolerable ripple in the output voltage V0 is considered and is given by,
Co(min) 
Pout V0
(2 ) f r (V0 )
(4.42)
where fr is the frequency of the rectified sine wave and V0 is the output voltage ripple in
terms of percentage. Considering the all above factors, the output capacitor of value 450 μF,
600 V is selected.
4.3.1.3 Active snubber circuit components
A widely used method presented in [99, 100, 102] is applied to design active snubber
components to achieve proper ZVT and soft-switching to other semiconductor devices. The
component values and devices of the proposed soft-switched single-phase PFC AC-DC
converter are tabulated in Table 4.2.
The base values were selected as
Base Voltage V0 = 400 V
(4.43)
Base Current Ib = ILb_max – (ΔILb)/2
(4.44)
P 
 500 
2 o

2

  
 0.99   7.93 A
Where I Lb _ max 
Vin_RMS (min)
90
(4.45)
I Lb  I Lb _ max (20%)  (7.93) (0.20) 1.6 A
(4.46)
110
Ib  I Lb _ max 
(I Lb )
1.6
 7.93
 7.13 A
2
2
(4.47)
Table 4.2 Parameter set employed in the evaluation tests of the soft switched active
PFC converter
Parameter
Device number/Value
Four Rectifier diodes (to form bridge) 25NSFL
MOSFETs (SW1, SW2)
IRFP 460
Hyper fast diode (DB)
DSEI 30-12A
Auxiliary diodes, (D1, D2 & D3)
RHRP 3060
Low line filter inductor (Lin)
5.6 μH
Input filter (Cin1)
0.47 μF, 275 V
Input HF bypass capacitor (Cin2)
1 μF, 630 V
Boost inductor (Lb)
1.5 mH
Resonant inductor (Lr)
10 μH
Snubber capacitor (CB)
5.6 nF, 400 V
Output capacitor (C0)
450 μF, 600 V
4.3.1.3.1 Resonant inductor Lr
The value of Lr mainly depends on how fast the reverse recovery current of boost
diode DB reaches its zero value. Due to production spread of the diodes and the circuit
conditions, the reverse recovery characteristics may vary for different diodes. For this, a
beneficial characterization is to set the time it takes for the resonant inductor current iLr to
slew from zero to the maximum boost diode current equal to three times the diode’s specified
(by manufacturer) reverse recovery time. Assuming the maximum value of reverse-recovery
time (trr) of selected boost diode DB to be 60n sec,
Lr 
V0
I Lb _ max
3 trr 
(400)
(3) (60) (1009 )
7.93
(4.48)
Therefore, minimum value of Lr required is,
111
Lr  9.08 H
(4.49)
Resonant inductor ‘Lr’ is fabricated by a sendust toroidal core (part number –
CS234125, CWS make) having 12 single layer turns of 14 AWG. Both the cores (Lb and Lr)
employed in the proposed soft switching converter exhibit low loss, high flux density as well
as relatively high saturation level.
4.3.1.3.2 Snubber Capacitor CB
The snubber capacitor CB is selected based on the complete energy transfer from
resonant inductor Lr to snubber capacitor CB. It is also essential to have a selected snubber
capacitor CB to be larger than that of resonant capacitor Cr to ensure complete discharge of
the resonant capacitor during resonant interval. Otherwise, the larger value of the resonant
capacitor increases the minimum duty cycle and hence the increased conduction losses in the
converter. Based on energy transfer balanced equation, from (4.14) and (4.23), we obtain,
1
1
1
Lr [iLb (t2 )+ I rr ] 2 + Cr V02  CB V02
2
2
2
(4.50)
1
1
1
(9.08)(106 ) [7.13  2]2  (480) (1012 ) (400)2  CB (400)2
2
2
2
(4.51)
 CB  5.21 nF
(4.52)
here iLb(t2) = Ib base current value calculated in equation (4.47) and the peak reverse recovery
current Irr is found from the manufacturer’s data sheet of employed boost diode DB for a
given maximum forward current of the converter. The other advantage of this proposed ACDC PFC boost converter is that, it is not required to have extra component of resonance
capacitor Cr across the main switch SW1 of the boost converter, however, the output
capacitance of main switch SW1 will serve the purpose of resonant capacitor and its value is
considered from the manufacturer’s data sheet of the switch SW1.
112
4.3.1.3.3 Verification of selected auxiliary components
In interval 5, according to (4.21), if the value of CB is decreased, voltage stress across
SW2 will increase. Hence to limit the dv/dt of the switch SW2, the following condition is to be
satisfied,
t45   2



t45   2
( Lr ) (CB )  t f 2

(4.53)

(9.08 ) (5.25 n)  342.9 ns  t f 2
(4.54)
In interval 7, the rate of rise of voltage across the main switch SW1 is limited by snubber
capacitor CB, hence the discharge time of snubber capacitor during this interval should satisfy
the following condition,
t67 

Cr  CB
(V0 )  t f 1
I Lb _ max
t67 
(4.55)
[ (480) (1012 )  (5.21) (1009 )]
(400)  287 ns t f 1
7.93
(4.56)
here, tf1and tf2 are fall time ratings of the main switch SW1 and auxiliary switch SW2
respectively, whose worst case maximum value is found to be 98n sec of the switching
devices employed in the proposed converter.
4.4 Special features of the proposed converter
The proposed single-phase AC-DC PFC boost converter is incorporated with ZVT
based active snubber circuit which achieves advantages over other soft switching converters.
The features of the proposed soft switched AC-DC converter are briefly summarized as
follows:
1)
All semiconductor devices operate with soft switching in the proposed converter. The
main switch SW1 is turned on with exact ZVT and is turned off near ZVS, the auxiliary
switch SW2 is turned on with ZCS and is turned off near ZVS. Other semiconductor
devices of the proposed converter also operate with soft switching.
113
2)
There is a little extra voltage stress on the boost diode of DB of single-phase AC-DC
PFC boost converter with passive snubber circuit proposed in chapter 3 of this thesis.
This extra voltage stress on the boost diode DB is eliminated in this proposed AC-DC
PFC converter with active snubber circuit.
3)
There is no extra voltage stress on the auxiliary switch SW2 of this converter. Based on
the energy balance condition, resonant current flows through auxiliary switch. So, there
is less current stress on the auxiliary switch with acceptable levels. The voltage and
current levels of auxiliary diodes D1, D2 and D3 are within the permissible limits.
4)
There is no current stress in the main switch SW1 and its body diode of the proposed soft
switched PFC boost converter. But the main switch of similar topology of DC-DC
converter described in [112] is subjected to undergo additional current stress and strain.
This extra current stress of main switch in [112] occurs as the body diode of main switch
conducts twice in each switching cycle with abrupt change in current.
5)
No input voltage sensing is required as it is needed in other active PFC converters
presented in [33, 84, 91, 95, 99, 121, 126, 127].
6)
The efficiency is higher even at lighter loads when compared to DC-DC converter
proposed in [97] as there is no energy loss (due to absence of resonant diode) during
resonance intervals.
7)
At light load conditions, the on state time of the main switch’s body diode is increased
when the input current is decreased. However, turn off process of main switch with ZVT
will not be affected under these conditions.
4.5 Simulation and experimental results
In simulation, a feedback system has been developed in SIMULINK environment and
is linked with a power converter which is developed in Power-Sim (PSIM) Power electronics
and Drives simulation package. The two models (boost converter and feedback system) built
114
in different environment are coupled by SIMCOUPLER. The single-phase AC-DC soft
switched PFC boost converter shown in Fig. 4.1 is tested with the implementation of an
experimental prototype on the electronic load DLP-400-5-750 (From ALLTEST
Instruments), and the performance efficiency of the proposed converter is compared with that
of the conventional hard-switched single-phase AC-DC PFC converter.
4.5.1 Response of resonant elements
Fig. 4.4 shows the comparison of simulated and experimental waveforms of resonant
inductor current iLr, boost inductor current iLb, and snubber capacitor voltage VCB at full load
condition. It can be observed that, the experimentally obtained waveforms shown in Fig.
4.4(b) are closer to that obtained in simulation.
This is a proof of evidence that, the
simulation and experimental results are strongly agreed with the theoretical designed analysis
of the operating principle of the proposed converter.
i
Lb
i
Lr
VCB

(a) Simulation waveforms
(b) Experimental result waveforms
Top: Resonant inductor current (iLr), and boost inductor current (iLb)
Bottom: Snubber capacitor voltage (VCB)
Scale: 2A/div, 200 V/div, 1 μsec/div
Fig. 4.4
4.5.2 Main switch SW1
Fig. 4.5 shows the simulation and experimental switching waveforms of main switch
SW1 of the proposed soft-switched converter at full load condition. The main switch SW1 is
115
turned on under exact ZVT when voltage across Cr is zero and it can be observed that the
switch has not exceeded its voltage and current limits.
The main switch SW1 also turns off under near ZVS.
The current and voltage
waveforms obtained through simulation and experimental investigations are in close
agreement with theoretical analysis.
(b)
(a)
Fig. 4.5 Simulation and experimental switching characteristics of a main switch SW1
a) Simulated results: voltage and magnified current waveforms of SW1.
b) Experimental results: voltage and current waveforms of SW1. Scale: 200 V/div, 2 A/div, 1 μs/div.
4.5.3 Auxiliary switch SW2 and boost diode DB
The simulation and experimental switching waveforms of auxiliary switch SW2 and
boost diode DB at full load condition are presented in Fig. 4.6. It can be observed that, from
Fig. 4.6 (a) and Fig. 4.6 (b), the auxiliary switch SW2 is turned on with ZCS because of
resonant inductor Lr and turns off under ZVS when the resonant current flowing through Lr
and Cr ceases to zero. The auxiliary switch SW2 is active only for a short period of time,
which is verified by its conduction period and is too small. It is also noted that, there is no
voltage oscillations across the switch SW2 just after the turn-off process of an auxiliary switch
SW2. But, such oscillations across auxiliary switch are occurring in the converter topology
depicted in the reference [97]. This is due to the relationship between resonant inductor Lr and
output capacitance Coss of an auxiliary switch SW2. This oscillation is prevented by an
116
(a)
(b)
(c)
(d)
Fig. 4.6 Simulation and experimental switching waveforms of auxiliary switch SW2 and boost diode DB
Simulation waveforms:
Experimental waveforms:
(a) Voltage and magnified current waveforms of auxiliary switch SW2. (b) Voltage and current waveforms of SW2
(c) Voltage and magnified current waveforms of boost diode DB.
(d) Voltage and current waveforms of DB.
Scale: 200V/div, 2 A/div, 1 μs/div.
auxiliary diode D3 connected in series with auxiliary switch SW2 of a proposed converter.
Also the current and voltage stresses of an auxiliary switch SW2 are well within in the
permissible limits. The switching waveforms of boost diode DB are presented Fig. 4.6 (c) and
(d). The boost diode BD also turns-on and off under ZVS. The experimentally obtained
results are almost closer to simulation results of the boost diode DB, except that in Fig. 4.6(c)
absence of reverse recovery current in boost diode DB as discrete transition simulators like
PSIM don’t apply full physical model of device and as a result such simulators are incapable
of showing parasitic processes such as reverse recovery.
A high frequency hyper-fast
recovery diode is used as a boost diode in the proposed converter. The reverse recovery
current which exists for shorter period may lead to substantial increase in conduction losses
117
of main switch SW1. However such losses due to reverse-recovery current can be eliminated
in future of similar projects by employing silicon carbide diodes which are now available in
the market. The all auxiliary diodes D1, D2 and D3 conduct for very short intervals over a
period of switching cycle and it is also noticed that these also experience soft switching
processes with the permissible voltage and current ratings in the principle of operation of a
proposed PFC converter with active snubber circuit.
The simulation and experimentally obtained input voltage and current waveforms of a
proposed PFC converter with active snubber for an input voltage of 215 V at full load
condition are presented in Fig. 4.7 and Fig. 4.8 respectively. The experimentally obtained
input voltage and current waveforms are measured and recorded by CW240 Clamp-on Power
Meter in the laboratory. The screen (LCD-liquid crystal display) of this meter displays only
horizontal grid lines. From both the figures (Fig. 4.7 and Fig. 4.8), it is ascertained that, the
input current signal is in phase with the input line voltage. This confirms the quality of input
line current which is almost sinusoidal and correctness of derived equation (4.36) which is
essential for boost converter of proposed active snubber topology.
Fig. 4.7 Simulation results of input voltage and magnified input current waveforms of
proposed converter with active snubber for an input voltage of 215 VRMS
118
This proof affirms that the proposed active snubber topology provides near unity
power factor operation and is perfectly suitable for PFC applications. The value of the THD
of input current is found to be 4.2% and its corresponding input PF is 0.999.
Fig. 4.8 Experimental input voltage and input current waveforms of proposed
single-phase PFC AC-DC converter with active snubber circuit for an input
voltage of 215 VRMS .
4.6 Performance of proposed converter
The performance of a proposed converter can be analyzed by comparing the
efficiency curve with that of the other converter efficiency curves.
Fig. 4.9 shows the
comparison of efficiency curves with respect to the output load of all the three converters
namely, (1) soft switching with auxiliary snubber circuit, (2) soft switching with passive
snubber circuit and (3) hard switching of conventional PFC converters. Among all the three
methods, the converter proposed with active snubber circuit achieves a maximum efficiency
of 98.3% which is around 1.02% more than that of a soft switching converter with passive
auxiliary circuit and 7.08% higher than the conventional hard switched PFC converter at fullload condition. The improvement of efficiency of proposed PFC AC-DC converter with
other converters at low load condition (15% of full-load) is also expressed in Fig. 4.9. The
119
proposed converter has a higher efficiency compare to the converters proposed in references
[71, 73, 74, 76, 92, 97, 178].
The higher efficiency in PFC converter with active snubber circuit is because of the perfect
soft-switching processes of semiconductor devices in comparison with PFC converter with
passive snubber circuit. In addition to this, the PFC AC-DC converter with passive snubber
circuit has more number of resonant elements (almost twice that of resonant elements in
active snubber circuit), which leads to the substantial increase in conduction losses and
significant effect of parasitic elements.
On the other hand, PFC AC-DC converter with
passive snubber circuit with its higher component count and design simplicity still make it
competitive, when compared to the ZVT PFC AC-DC converter with an active snubber
circuit. The variation of PF and THD with respect to output load for all the converters
discussed so far will be elaborated in three-phase systems (chapter 5) of this thesis. The Fig.
4.10 shows the experimental set-up of proposed single-phase PFC AC-DC converter with an
active snubber circuit.
100
98
96
94
92
90

88
86
Soft-switched with active snubber
Soft-switched with passive snubber
Hard-switched converter
84
82
80
0
100 150 200 250 300 350 400 450 500
Fig. 4.9 Comparison of efficiency curves of conventional hard switched PFC converter, soft
switched PFC converter with passive snubber and proposed soft switched converter with
active snubber circuit
120 Buy SmartDraw!- purchased copies print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
Fig. 4.10 Hardware prototype of single-phase PFC boot converter with an active snubber
circuit
4.7
Summary
A novel auxiliary snubber circuit is incorporated in the boost converter of single-
phase PFC AC-DC converter to improve the performance with respect to the efficiency of the
converter. The main idea is to reduce the switching losses by achieving a process of soft
switching in a main switch of boost converter and as well as in other semiconductor devices
in the converter. In this technique, the snubber energy is recuperated to the load without
using the main switch path; hence the conduction loss of the system is reduced. In the
proposed topology, the main switch is turned on with exact ZVT and is turned off near ZVS.
The boost diode turns on and off with ZVS. There are no extra voltage stress and current
strain on the main switch and as well as on the boost diode. An auxiliary switch SW2 is
121
turned on with ZCS and is turned off near ZVS due to the resonant elements resonant
inductor Lr, resonant capacitor Cr and snubber capacitor CB. The excess voltage on an
auxiliary switch does not take place, but based on the energy balance condition, resonant
current flows through auxiliary switch. Hence, there is less current stress on the auxiliary
switch which is within the acceptable levels. All other auxiliary diodes are turned on and
turned off under/near ZVS and/or ZCS. The voltage and current stress and strain on all other
auxiliary diodes are within the permissible limits. A prototype suitable for input voltage of
215 VRMS with a specification of 400 V, 500 W and 100 kHz converter is developed and
tested in the Power Electronics and Drives laboratory to verify with the simulation result.
122
Chapter 5
High Power Factor Three-Phase SoftSwitched AC-DC PFC Converters in
Modular System
o Introduction
o 1.5 kW 3-phase PFC boost converter with passive snubber in modular
system
o Simulation and experimental results
o 1.5 kW Three-phase PFC boost with active snubber in modular system
o Simulation and experimental results
o Performance characteristics
o Summary
123
Introduction
With the development of telecom and information technology sector, the power supply
industries are under constant pressure of developing front-end AC-DC PFC converter with low
volume, higher efficiency, lower profile, less cost. In addition to these factors, expandability of
power range for a given high power specification of converter is also a challenging task. This
chapter finds a suitable solution for high power rating converter that expands power range of a
converter system in modular approach. A systematic modular approach also provides higher
power density, easier thermal management and high reliability of a system. The research effort is
focused on the development of the university level prototypes of three-phase AC-DC softswitched PFC converters each of power rating 1.5 kW.
In the previous chapters of this thesis, importance was given to the improvement of
dynamic response and efficiency of single-phase AC-DC PFC boost converters for medium
power (500 W) applications. Two different soft switching techniques were proposed and
described to improve the efficiency of single-phase AC-DC PFC boost converters.
For high power AC-DC applications, three-phase power supplies are widely employed in
various applications including power sources to telecom and computer server systems. In case of
three-phase AC-DC converters, there are typically two configurations: (1) A group of three
single-phase PFC rectifiers (referred as three-phase AC-DC modular system) and (2) A threephase PFC rectifiers. The latter rectifiers have distinctive features over the former, such as
constant power flow which allows use of smaller capacitors, fewer switches and higher
efficiency due to reduced switching and conduction losses [163]. However, the modular system
(parallel operation of two or more modules) of three-phase PFC rectifiers can expand the power
range to a much higher level and permits to use (n+1) modules (n is required number of
124
modules) for the redundancy purpose in order to improve the system reliability. Added to this,
modular system is superior with respect to thermal management, maintainability, cost,
requirement for maintenance and repair of power converter modules because of the use of
standard single-phase converters [7, 12, 163]. Hence, active PFC AC-DC front-end converters
of DPS have been attracting increased attention due to continuously growing power quality
concerns. Therefore, single-phase parallel configurations with AC-DC PFC boost, SEPIC and
CUK converters have been developed and reported in the references [84, 164, 165, 166]. A great
amount of work has been reported concerning the three-phase PWM boost [84, 121, 167-169],
buck [170, 171], buck-boost [172] converters for various power supply applications. Either of
these converters often requires either input voltage and/or output safety isolation transformations
and also provides a unity input power factor, limited input harmonic currents fed-back to AC
power grid, high efficiency and high power density. One of the main drawbacks found in earlier
years of the three-phase modular approach is the interference of the phase currents between two
phases, this is instanced by the authors in the reference [121], however, in the proposed converter
of this chapter, this draw back has been overcome by employing individual control loop to each
module and such modular systems have been well presented in [84, 120, 167].
The main objective of this chapter is to achieve power range expandability of PFC frontend converter in modular approach and the aim of this chapter is to show the improvement in the
performance characteristics of three-phase AC-DC PFC converter in modular system. The
significance importance is given to improve the efficiency by minimizing the switching losses of
the PFC boost converter by employing passive snubber circuit and active snubber circuit
separately.
In this chapter, two different soft-switching techniques in three-phase PFC boost
converters in modular approach are presented and described separately. The two soft-switching
125
techniques; PFC with passive snubber and PFC with active snubber circuits already applied in
single-phase AC-DC PFC boost converters in chapter 3 and chapter 4 respectively of this thesis
are now applied to three-phase AC-DC PFC boost converters in modular system. Hence, this
chapter mainly has two parts: ‘Section 5.1’ deals with the application of soft-switching technique
with passive snubber circuit in three-phase AC-DC PFC boost converter and ‘Section 5.3’ deals
describes about the application of soft-switching technique with active snubber circuit employed
in three-phase AC-DC PFC boost converter in modular approach.
5.1
A 1.5 kW three-phase AC-DC PFC boost converter with passive snubber circuit in
modular system
Fig. 5.1 shows the three-phase AC-DC PFC boost converter with passive snubber circuit
schematic with simplified feedback block diagram in modular approach. The output voltage and
all three inductor currents of power converter are accurately sensed and are fed to the feedback
system. The complete feedback system consists of a group of three identical feedback systems
and it is connected in such a manner that, one boost converter is connected to its corresponding
feedback module.
5.1.1 Converter block schematic and functionality
The converter design is described in brief with reference to the detailed block schematic
shown in Fig. 5.1. The complete block schematic represents functionality of a proposed threephase soft-switched converter. An identical single-phase AC-DC PFC boost converter with
passive snubber circuit is connected in each line of a three-phase AC supply input filter circuit
consisting of Lin and Cin1. The outputs of all the three converter modules are connected in parallel
126
DSSA
LbA
iLbA
iinA
Lin
Cin 2
Cin1
iLsn
D3
LsnA
Vin
iDB1
DB1
D4
Cst
Lst
D1
Cn
D2
SWA
Csn
iSWA
DSSB
LbB
VAN
VBN
iDB2
iLbB
iinB
Lin
DB2
iLsn
Cin 2
Cin1
D3
LsnB
Vin
I0
D4
Cst
Lst
D1
Cn C
0
D2
SWB
V0
Csn
iSWB
VCN
DSSC
LbC
iLbC
iinC
Lin
Cin1
Cin 2
DB3
iLsn
D3
LsnC
Vin
Cst
Lst
iDB3
D4
D1
Cn
D2
SWC
iSWC
Csn
Fig. 5.1 Block schematic of proposed 1.5 kW soft-switched PFC boost converter in modular
system
127
to raise the power level of the total converter system. The capacitor Cin2 in all the three
converters is to filter out the noise and its value is not too large to distort the input wave shape
signal even at low output power and high line input conditions. The circuit topology and
feedback system of each module of proposed three-phase AC-DC PFC converter is same as that
of the single-phase AC-DC PFC converter with passive snubber circuit described in section 3.1.1
and 3.1.2 respectively of chapter 3. The working principle of each converter module shown in
Fig. 5.1 is same as that described in section 3.2 of chapter 3 of single phase soft-switched PFC
converter. However, it is understood that, the input voltage to all the three single-phase AC-DC
PFC converters is displaced by 1200 from one another.
As described earlier in sections 3.1.1 and 3.1.2 of chapter 3, the latest PFC IC
ICE2PCS01 from Infineon Technologies [156, 174, 175] is used in each feedback system. The
triggering pulses generated from PFC controller IC of each module are fed to their corresponding
MOSFET switch of power boost converters arranged in modular system.
In the proposed
converter system, it is not required to sense and feed the input voltage signal to feedback system
to keep the input power almost constant, this is the special feature of PFC IC used in this
proposed three-phase converter, but such arrangement (sensing input voltage and feeding to
feedback system) is essentially required in other AC-DC PFC converters presented in [84, 91,
95, 99, 102, 121, 124].
To regulate the output voltage, multipliers in the feedback system control the amplitude
of the corresponding sinusoidal reference signal in accordance with the voltage error signal
generated from output voltage of each module of the proposed converter. When the load
decreases, the output voltage increases. To maintain constant load voltage, the control circuit
senses the load voltage and feeds back to the feedback system. The pulse width is automatically
128
reduced in the switching cycle and the output voltage is regulated and maintained almost
constant.
5.1.2 Schematic design and component selection
The design procedure, which is developed by standard method of design procedures
presented in references [97, 99, 102, 152, 160] has been followed which is based not only on the
soft switching turn-on and turn-off requirements of the MOSFET switch in each module and
other semiconductor switches on the proposed converter, but also the transfer of the snubber
energy to the load. The complete design procedure for resonant elements of each module of the
proposed converter is described in section 3.3 of chapter 3 and the same concords with the
proposed each module of three-phase AC-DC PFC modular system.
The MOSFETs employed are selected by their capacity to carry the peak inductor
current, support the flyback (reflected) boost voltage and their ability to generate low conduction
losses for achieving higher efficiency. In this design, three SPA20N65C3 (650 V/20.7 A/0.19
Ω) MOSFETs from Infineon Technologies were used. The boost rectifier diodes must also have
a nearer voltage and current ratings as the MOSFET’s. The boost DB diode in each module must
also be very fast to reduce the MOSFET’s turn-on losses. Three boost diodes RHRP 3060 (600
V/30 A) from Fairchild Semiconductor are used in the proposed system. The Fast recovery
epitaxial diodes DSEI30-12A from IXYS Corporation (auxiliary diodes D1 – D4 in each module)
which assist in auxiliary circuits are used in the proposed modular converter. Standard axial
rectifier diodes 1N5408 from Vishay Electronics (DSSA, DSSB, DSSC) provide soft-start function
which limit the start up inrush current thus reducing the stress on the corresponding boost diode
of each module. Just after start-up, when output capacitor becomes equal to regulated voltage of
400 V, these protective diodes (DSSA, DSSB, and DSSC) become reverse biased.
129
To develop a better understanding about the performance of a three-phase modular
system of a continuous boost PFC circuit, a 1500 W prototype PFC boost circuit model was
built. To meet the requirements of EMI, power quality standards of IEEE-519 and having a
smaller input EMI filter, with switching frequency below 150 kHz was preferred. Thus for all
the different measurements made, the switching frequency was always kept to about 100 kHz
and the boost inductor ripple current was considered to be less than 20% of its maximum peak
value. Table 5.1 shows the brief specifications of the proposed AC-DC PFC boost converter.
The component values and devices of the proposed three-phase AC-DC PFC converter with
passive snubber circuit are tabulated in Table. 5.2
Table 5.1 Specifications of 1500 W Three-phase AC-DC PFC proposed converter
Product
Operating ambient
General
Universal input 1500 W PFC AC-DC boost converter with
passive snubber circuit.
Full operation: -100 C to +400 C.
Input range
Hold-up time
Input power factor
Input circuit
Inrush current
Efficiency
Input
85V to 265 V AC/50 Hz (Nominal: 215 V AC/ per phase).
Better than 20 mS at 215 V AC input, measured at full load.
Greater than 0.99 at full load condition.
Three wire system with safety ground.
< 40 Amps for less than 5 cycles at 215 V AC input
Typically 96.5% at full-load, 215 V input and nominal output
voltage.
Nominal output
Max. Load current
Voltage regulation
Output
Nominal value of +400 V DC with ripple less than 5 V pk-pk.
About 3.8 Amps.
Output to be within 400 V 5 V at specified ambient, specified
input line and specified output current conditions.
130
Table 5.2 Parameter set employed in the evaluation tests of the proposed
AC-DC PFC boost with passive snubber circuit
Component
Value/model
Simulation
Experimental
Bridge Rectifier IC with heat sink (In each module)
Ideal
GBJ 2506-BP
MOSFETs ( SWA, SWB, SWC )
Ideal
SPA20N65C3
Auxiliary Diodes (D1 – D4), (In each module)
Ideal
DSEI 30-12A
Boost Diode (DB1, DB2,DB3)
Ideal
RHRP 3060
Low line filter inductor (Lin), (In each module)
5.6 μH
0.47μF, 275 V
Input filter (Cin1), (In each module)
Input HF bypass capacitor (Cin2), (In each module)
1 μF, 630 V
5.6 μH
0.4 μF, 275 V
1 μF, 630 V
Boost inductor (LbA, LbB, LbC)
1.5 mH
1.5 mH
Snubber inductor (LsnA, LsnB, LsnC)
2.5 μH
2.5 μH
Storage inductor (In each module)
62.5 μH
62.5 μH
Snubber capacitor (Csn), (In each module)
0.68 μF
0.68 μF
Storage capacitor (Cst), (In each module)
1.2 μF
1.2 μF
Output HF bypass capacitor (Cn), (In each module)
1 μF, 600 V
1 μF, 600 V
The proposed three-phase soft-switched converter was designed to operate in the CCM of
operation for the whole line period and for wide range of output power levels.
The hardware
layout was developed with great care, so as to minimize the effects of EMI. DC electronic load
model No. DLR-400-15-2500 from “Alltest Instruments Inc.,” has been used for technical
evaluation of the proposed converter.
Overall converter performance was tested with an
electronic load to ascertain that the design meets the required specifications.
5.2
Simulation and experimental results
In simulation, three individual feedback systems are developed in SIMULINK
environment and are linked with a power converter which is developed in PSIM package through
Sim-Coupler module. Fig. 5.2 shows the complete simulation schematic layout of a proposed
three-phase AC-DC PFC converter in modular approach. The advantage of Sim-Coupler module
131
is to make use of PSIM’s capability in power simulation and MATLAB/SIMULINK capability
in control simulation, thus greatly shortening the time to set-up and simulate a power electronic
system. In this simulation, the sensed inductor currents and output voltage are fed to feedback
system which is developed in SIMULINK environment through a Sim-Coupler.
After
processing of a feedback system the triggering pulses obtained from control system are applied
to MOSFETs of a power boost converter in Power-Sim environment via Sim-Coupler.
Fig. 5.3 shows the input voltage, input currents and output voltage waveforms of a
proposed converter for an input voltage of 245 VRMS. This is tested for beyond the nominal input
voltage to check for the higher range of input voltage level (As proposed converter is designed
for universal input voltage). In the upper graph of Fig. 5.3, three phase input voltages, output
voltage waveforms along with magnified input current waveform of phase A are shown, both
input voltage and current of phase A are almost sinusoidal and are in phase. This ascertains that
each AC line input current is in phase with its corresponding sinusoidal input voltage; this is the
evidence of theoretical analysis that, proposed three-phase converter operates at nearly unity
power factor.
In the lower graph of Fig. 5.3, it can be observed that, three input currents are
displaced by 1200. This confirms that, there is no phase displacement between the each input
line current with its corresponding input voltage.
132
133
Fig. 5.2 Simulation layout of proposed three-phase AC-DC PFC boost converter with passive snubber circuit in modular system
(Power converter in PowerSim (PSIM) and feedback system in SIMULINK)
Fig. 5.3 Simulated input voltage and current waveforms of a proposed three-phase ACDC PFC converter with passive snubber circuit in modular approach
Fig. 5.4 Experimental input voltage and current waveforms of a proposed
three-phase AC-DC PFC converter with passive snubber circuit in modular approach
Scale: 100 V/div, 2 A/div, 5 ms/div.
134
The oscillogram of Fig. 5.4 shows the input voltage and current measurements of the 1.5
kW prototype of the proposed three-phase AC-DC soft-switched PFC converter. All the three
current waveforms and input voltage of phase A are almost sinusoidal to that shown in simulated
results of Fig. 5.3.
This justifies that the mathematically designed converter components
strongly agree with the predicted waveforms of a proposed PFC converter.
The experimental results measured and recorded by oscillogram are shown in Fig. 5.5. The
three-phase input current waveforms at a variable load conditions from full-load to 25% of fullload for an input voltage of 215 VRMS are shown in Fig. 5.5 (a) - (d). It is evident that the
proposed three-phase soft-switched converter with passive snubber circuit operates at nearer to
unity power factor over a wide range of load variation and input current decreases with decrease
in load level.
The transient response of the proposed three-phase AC-DC PFC boost converter with
passive snubber circuit at load step from 1.5 kW (full-load) to 0.75 kW (half load) and vice versa
are shown in Fig. 5.6 (a) and Fig. 5.6(b) respectively. It can be seen that, during transition from
full-load to half load step change of Fig. 5.6 (a), the output voltage rises from the nominal output
voltage V0=400 V to the maximum value of 425 V, on the other hand, during transition from half
load to full-load, (see Fig 5.6 (b)), the output voltage undershoots to a level of 385 V and
recovers to its nominal output voltage level without disturbance. It is observed that the proposed
three-phase soft-switched converter maintains almost constant load voltage at all output power
levels starting from 25% of full-load to full-load.
135
(a)
(b)
(c)
(d)
Fig. 5.5 Experimental input currents (iA, iB, iC) at (a) full-load (b) 75% of full-load (c)
50% of full-load and (d) 25% of full-load for an input voltage of 245 VRMS.
Scale: 1 A/div, 3 ms/div.
136
(a)
(b)
Fig. 5.6 Output voltage response of a proposed converter under change in load
(a) From full-load to half load (b) From half load to full-load.
Scale: 100 V/div, 5 ms/div.
137
The comparison of efficiency curves of proposed soft-switched converter and that of
three-phase hard-switched converter are shown in Fig. 5.7. From Fig. 5.7 it can be seen that the
efficiency of proposed soft-switched converter is higher than that of hard-switched converter,
especially at high output power levels. At full-load power level, it is found that, the proposed
three-phase soft-switched converter has total losses of around 39% of the total losses of the
three-phase hard-switched converter, and so the overall efficiency, which is at about 90.8% in
the hard-switched case, increases to 96.2% . Even under, light load condition (25% of fullload), the minimum increase in the efficiency is found to be 3.5%. The developed prototype of
proposed three-phase AC-DC PFC soft-switched boost converter with passive snubber circuit is
shown in Fig. 5.8.
100
98
96
94
92
90
88
86
Three phase hard-switched converter
Proposed three-phaseconverter with passive snubber
84
82
450
600
750
900
1050
1200
1350
1500
Fig. 5.7 Comparison of efficiency curves of proposed three-phase softswitched converter with three-phase hard-switched converter
138
Fig. 5.8 Photograph of proposed 3-phase AC-DC PFC boost converter with passive snubber
circuit
Buy SmartDraw!- purchased copies print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
139
5.3
A 1.5 kW three-phase AC-DC PFC boost converter with an active snubber circuit in
modular system
A prototype of a proposed three-phase AC-DC PFC boost converter with an active
snubber circuit has been developed in the Power Electronics and Drives Laboratory, at NIT,
Rourkela. Three identical single-phase AC-DC PFC boost converter with an active snubber
proposed in chapter 4 of thesis are connected in modular approach. Regarding the feedback
system, as described earlier, PFC IC ICE2PCS01 controller has been employed to each module
of the proposed three-phase system.
Fig. 5.9 shows the three-phase AC-DC PFC boost converter with an active snubber
circuit schematic with simplified feedback block diagram in modular approach. The output
voltage and all three boost inductor currents of power converter are accurately sensed and are fed
to the feedback system. The complete feedback system consists of a group of three identical
feedback systems and it is connected in such a manner that, one boost converter is connected to
one corresponding feedback module.
The technical specifications of the prototype of the proposed three-phase AC-DC
PFC converter with an active snubber circuit are identical to that three-phase AC-DC PFC
converter with passive snubber circuit described in Table 5.1 of section 5.1.2. This is because;
the aim of both prototypes (three-phase AC-DC PFC with passive snubber and three-phase ACDC PFC with active snubber converters) is to achieve higher efficiency of a converter with the
primary objective of accomplishing nearly unity input power factor. The component values and
devices of the proposed three-phase AC-DC PFC converter with active snubber circuit are
tabulated in Table. 5.3.
140
DSSA
LbA
iLbA
iinA
iLrA
Cr
Cin 2
Lin
D3
Vin SW1A
Cin1
DB1
CB
Lr
D1
D2
Cn
SW2 A
iSW 2 A
iSW 1
DSSB
LbB
I0
iLbB
iinB
iLrB
Cr
Lin
VAN
Cin 2
Cin1
VBN
Vin
SW1B
LbC
Lin
D1
C0
D2
V0
Cn
DSSC
iLbC
iinC
D3
DB2
SW2B
iSW 2B
iSW 1B
VCN
Lr
CB
iLrC
Lr
CB
D3
D1
DB3
Cr
Cin 2
Vin SW
1C
Cin1
D2
Cn
SW2C
iSW 2C
iSW1C
Lb
iDB
D
D
i
Fig. 5.9 Block schematic of proposed 1.5 kW soft-switched
PFC boosti converter
with
i
CB
L
iLb
DB
C
iLr
C
Lr
B
L
active
snubber
circuit
in
modular
system
C
C
V
in
11
13
Lb
Lr
r
r
SW1
iSW 1
ac
SW2
D3
D1
D2
in 2
Cin1
Vin
D14
C0
iSW 2
in
141
D12Buy
SW1
SW2
I0
DB
r
D3
D1
D2
V0
C0
print
SmartDraw!purchased copies
this
iSW 1
i 2
document without a SWwatermark
.
Visit www.smartdraw.com or call 1-800-768-3729.
Table 5.3 Parameter set employed in the evaluation tests of the 3-ph AC-DC PFC boost
converter with an active snubber
Parameter
5.4
Simulation
Experimental
Bridge Rectifier IC with heat sink (In each module)
Ideal
GBJ 2506-BP
MOSFETs (SW1A, SW2A, SW1B, SW2B, SW1C, SW2C,)
Ideal
IRFP 460
Hyper fast boost diodes (DB1, DB2 & DB3)
Ideal
DSEI 30-12A
Auxiliary diodes, (D1, D2 & D3), (In each module)
Ideal
RHRP 3060
Low line filter inductor,(Lin), (In each module)
5.6 μH
5.6 μH
Input filter (Cin1), (In each module)
0.47 μF, 275 V
0.47 μF, 275 V
Input HF bypass capacitor (Cin2), (In each module)
1 μF, 630 V
1 μF, 630 V
Boost inductor (LbA, LbB & LbC), (In each module)
1.5 mH
1.5 mH
Resonant inductor (Lr), (In each module)
10 μH
10 μH
Snubber capacitor (CB), (In each module)
5.6 nF, 400 V
5.6 nF, 400 V
Output bypass capacitor Cn, (In each module)
1 μF
1 μF
Output capacitor (C0)
450 μF, 600 V
450 μF, 600 V
Simulation and experimental results
In simulation, as described in previous section 5.2 the power converter (developed in
PSIM) of each phase is linked with its corresponding feedback system (developed in SIMULINK
environment) via Sim-coupler. The simulation schematic of proposed three-phase AC-DC PFC
boost with an active snubber circuit is shown in Fig. 5.10. The feedback system generates the
complementary gate drive pulses with sufficient dead band to both active switches of the
proposed PFC boost soft-switched converter.
The simulated three-phase input voltage waveform of A-phase and input currents at low
load (25% of full load) are shown in Fig. 5.11 for an input voltage of 215 Vrms. It is ascertained
that each AC input line current is in phase with its corresponding sinusoidal input voltage; thus,
input power factor of a proposed three-phase converter is nearly unity.
142
143
5
Ref Sine Wave C
Voltage PI Controller2
0.002s
0.0006s+0.3
Ref Sine Wave B
Voltage PI Controller1
0.002s
0.0006s+0.3
Ref Sine Wave A
Abs2
|u|
Limiter5
Abs1
|u|
Limiter3
Abs
|u|
Limiter1
Product2
Product1
Product
Divn 2
Divn1
Divn
2e-5s+0.2
1e-5s+0.5
1-Phase zvt-fb 3
VinLINKO1
VoLINKO2 PulseinLINK
ILINKO3
Limiter6
Zero-Order
Hold1
Zero-Order
Hold2
Saw-tooth -Switching frequency2
Current PI Controller2
2e-5s+0.2
1e-5s+0.5
1-Phase zvt-fb 2
VinLINKO1
VoLINKO2 PulseinLINK
ILINKO3
Limiter4
Zero-Order
Hold
Saw-tooth -Switching frequency1
Current PI Controller1
2e-5s+0.2
1e-5s+0.5
1-Phase zvt-fb
VinLINKO1
VoLINKO2 PulseinLINK
ILINKO3
Limiter2
Saw-tooth -Switching frequency
Current PI Controller
Relay2
Relay1
Relay
Fig. 5.10 Simulation layout of proposed three-phase AC-DC PFC boost converter with active snubber circuit in modular system
(Power converter in PowerSim (PSIM) and feedback system in SIMULINK)
Ref - O/p voltage
0.002s
0.0006s+0.3
Voltage PI Controller
VA
(I A * 85)
(IB * 85)
(IC * 85)
Fig. 5.11 Simulated input current (magnified) iA, iB, iC and input A-phase voltage VA
waveforms at 25% of full load for an input voltage of 215 VRMS.
The experimental results shown in Fig. 5.12 are measured and recorded by CW240
Clamp-on Power Meter. The three-phase input current waveforms at a variable load conditions
from full load to 25% of full load for an input phase voltage of 215 Vrms are shown in Fig. 5.12
(a) – (d). Fig. 5.12(d) represents the input phase voltage VA as well as three input current
waveforms at low load condition. It is observed that, this response is almost closer to that
obtained in simulated results shown in Fig. 5.11. From this, it is evident that, the proposed ACDC soft switched converter operates nearer to the unity power factor even under low load
condition.
5.5
Performance characteristics
The THDi and PF were calculated from the measured data of the experimental results of
the proposed AC-DC soft-switched converter. The variation of THDi as a function of the load
power of the proposed boost converter with active snubber, PFC converter with passive snubber
and the conventional hard switched converter are shown in Fig. 5.13. The THDi at full load of
the proposed converter is obtained to be around 2.8% and the corresponding PF is equal to
0.9996.
144
iA
iC
i
i
C
A
i
ii A
A
ii
CC
B
iB
(a)
i i
BB
(b)
V
i
C
iC
i
i
A
iA
i
i
C
B
iB
A
i
A
B
(d)
(c)
Fig. 5.12 Experimental input voltage and current waveforms. Input currents iA, iB and iC at (a) full load
(b) at 75% of full load (c) 50% of full load (e) 25% of full load and input phase voltage VA.
Ph Hard switched converter
Ph Soft-switched with passive snubber
Ph Soft-switched with active snubber
900
1050
1200
1350
1500
Scale: on screen.
10
Buy SmartDraw!- purchased copies print this
document without a watermark .
3-Ph hard-switched converter
Visit
www.smartdraw.com
or call 1-800-768-3729.
Fig. 7 Experimental input voltage andcurrent waveforms (a)input currentsi ,i andi at fullload (b)input currentsi ,i andi at 75% of fullload
B
A B
C snubber
C
3-Ph soft-switched withA passive
(c) phase voltage V andinput currents at 50% of fullload(e)input phase voltage V andin put currentsi ,i andi at 25% of fullload (light load).
A
A
A
B
C
3-Ph soft-switched with active snubber
8
6
4
2
450
600
750
900
1050
1200
1350
1500
Fig. 5.13 Comparison of variation of THD as a function of load power of
three-phase AC-DC PFC boost converters.
145
The PF variation as a function of load power of the proposed soft-switched boost
converter with active snubber, PFC boost converter with passive snubber and conventional hard
switched PFC boost converters are shown in Fig. 5.14. It can be seen that, the power factor of
the proposed converter is higher than that of the PFC with passive snubber and hard switched
converter at higher power levels. At lower power levels, its value is slightly lower than that of
conventional PFC converter due to considerable effect of lower order harmonics and higher than
the PFC converter with passive snubber circuit. The total THDi is well below 10%, hence the
proposed soft switched converter exhibits lowest outcome of THDi.
10
1
0.999
8
0.998
6
0.997
0.996
4
0.995
0.994
450
600
750
3-Ph Hard switched converter
3-Ph Soft-switched with passive snubber
3-Ph Soft-switched with active snubber
900
1050 1200 1350 1500
2
450
600
750
Fig. 5.14 Comparison of variation of PF as a function of load power of
three-phase AC-DC PFC boost converters.
The efficiency curves of the proposed three-phase AC-DC soft switched PFC boost
converters (both with active snubber and passive snubber) and the conventional three-phase ACDC hard-switched PFC boost converter with the nominal input voltage 215 Vrms are presented in
146
Buy SmartDraw!document w
Visit www.smartdraw
Fig. 5.15. It is observed that the efficiency of the proposed converter varies from 97.3% to
91.3%. The highest efficiency of the proposed AC-DC PFC converter is obtained at full load
power of 1500 W which is around 7.25% higher than that of the conventional hard switched PFC
converter. The proposed soft-switched PFC converter with active snubber has higher efficiency
of 1.35% with respect to that of PFC converter with passive snubber. The corresponding
improvement at the low power level of proposed soft-switching converters (PFC with active and
passive snubbers) are also shown in Fig. 5.15.
The Fig. 5.16 shows the variation of output
voltage under step-change condition of the output load.
It is observed that the converter
maintains almost constant load voltage.
100
98
96
94
92
90
88
86
84
Three-phase hard-switched converter
Three-phase soft-switched with passive snubber
Three-phase soft-switched with active snubber
82
80
300
450
600
750
900
1050 1200 1350 1500
Fig. 5.15 Comparison of efficiency curves of proposed three-phase soft-switched
converters with hard switched three-phase AC-DC converter as a function of load power
Buy SmartDraw!- purchased copies print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
147
Fig.5.16 Output voltage response under change in load
(a) From full load to half load (b) from half load to full load.
Scale: 100 V/div, 5 ms/div.
The developed prototype of proposed three-phase AC-DC PFC soft-switched boost
converter with an active snubber circuit is shown in Fig. 5.17.
Fig. 5.17 Photograph of proposed 3-phase AC-DC PFC boost converter with active snubber
circuit
148
Buy SmartDraw!- purchased copies print this
document without a watermark .
Visit www.smartdraw.com or call 1-800-768-3729.
5.6 Summary
A three-phase modular approach has been proposed for high power expansion of AC-DC
PFC converters. Higher efficiency is obtained in these proposed three-phase converters by
incorporating soft-switching techniques. Soft switching techniques proposed for single-phase
AC-DC PFC boost converters in chapter 3 and chapter 4 are employed for the proposed threephase AC-DC PFC converters in modular system; to minimize the switching losses with the
primary objective of achieving near unity input power factor. For simulation, special features of
PSIM and SIMULINK are utilized by interfacing both the environments via Sim-Coupler. The
prototypes for all the three converters (hard-switched, soft-switched with passive snubber, and
soft-switched with active snubber) are developed in the laboratory for the converter specification
of 400 V, 1.5 kW, 100 kHz frequency operation. The performance improvement with respect to
efficiency, THD and PF is successfully obtained in the proposed three-phase AC-DC PFC boost
soft-switched converters.
Through the performance characteristics and graphs of all the three
converters presented in section 5.5, it is revealed that, three-phase AC-DC PFC boost converter
with active snubber circuit is found to be the superior among the converters with respect to
efficiency, THD and power factor.
149
Chapter 6
Summary and Future Scope
o Summary
o Future scope
150
Because of high performance, easy maintainability, and high reliability, DPS systems
are widely employed for telecom and computer server applications. In present situation, the
exponential increase in the functionality of these applications demands the power
management, which provides a large market to DPS systems. Hence, the emergence of frontend AC-DC converters (PFC + DC/DC converter) in these DPS poses many challenges and
attracts large research efforts to investigate different solutions such as: high efficiency, fast
dynamic response, and high power density. Improved performance of these front-end ACDC converters in DPS systems must meet these requirements.
6.1
Summary
This dissertation is engaged in researching solutions for PFC boost converters
operating at high switching frequency. For PFC stage, conventional single switch PFC boost
converter is most suitable topology because of its inherent advantages. However, to meet
EMI standards, as well as small filter size, switching frequency of PFC boost converter
circuit is usually chosen below 150 kHz. The conventional PFC boost converter with singlesided PWM switching sacrifices the dynamic response of output voltage during load or line
voltage change, owing to the fact of low bandwidth filter in the voltage feedback loop. This
sluggish transient response problem is further compounded by large voltage overshoots and
voltage drops enforcing additional stress on the PFC boost components, as well as on its
downstream switch mode power supply load.
On the other hand, operating AC-DC PFC
boost converter in CCM, with high switching frequency reduces the size of converter
(especially magnetic components) and hence the reduction in the overall cost; but this leads
to the large switching loss (owing to hard switching) which precludes the circuit operation at
higher switching frequency. Hence, the loss minimization in these front-end converters has
become a prime issue and can be accomplished by employing soft-switching techniques.
151
Thus it is important to investigate a suitable soft switching topology that allows the high
switching frequency operation of PFC AC-DC boost converter. In addition to these, the DPS
demands high power expandability, higher power density and less weight for front-end
converters employed for telecom and computer server applications. A systematic modular
approach of three-phase system will support the design engineers to achieve these needs of
DPSs system. This dissertation brings out some of the solutions to these problems by
employing suitable methods and auxiliary soft switching circuits to AC-DC PFC boost
converter.
This research presents different topologies with improved performance of PFC ACDC converters for DPS applications. The specific contributions of this study, based on
chapter two to five are summarized as below:
1.
For front-end single-phase AC-DC PFC converters, an extended PWM method
is proposed to improve the dynamic response during load change or line voltage change.
Improved dynamic response is achieved by employing two sided PWM technique by using
equal slope triangular signal instead of saw-tooth signal. For PWM switching, the control
signal from the feedback system is derived into two signals (of opposite off-sets) which are
compared with triangular signal to generate required triggering pulses to drive MOSFET
switch of boost converter. To achieve this, two comparators are used in the PWM switching
module. However, the increase in the complexity of the PWM switching does not affect the
overall performance of the converter.
This method essentially improves the dynamic
response of the system and reduces the voltage stress on PFC components in comparison with
single-sided PWM switching method.
Along with the improved dynamic response, the higher power density can be
accomplished with power expandability of three-phase system in modular approach. These
single-phase as well as three-phase PFC converters have achieved nearly unity input power
152
factor even at light load conditions with low THD. The discussed features of the method are
authenticated with simulation as well as experimental results.
2.
For medium power applications at higher switching frequency, a single-phase
AC-DC PFC soft-switched boost converter with a passive snubber circuit has been
investigated. The aim is to increase the efficiency of the converter with the primary objective
of operating proposed converter at nearly unity power factor. The proposed passive snubber
circuit in boost converter serves as an energy recovery turn-on snubber, which greatly
reduces the reverse-recovery peak current of the boost diode and turn-on losses of the
controlled switch.
In addition, this auxiliary passive circuit provides ZVS and/or ZCS
condition for all semiconductor switches of the converter.
The special feature of this
converter is that, the snubber energy is recuperated to the load without the use of main path
(through PFC boost diode), hence the reduction in the conduction losses of the boost diode.
In the proposed converter, all the semiconductor switches except the boost diode do not have
extra voltage or current stress. However, the voltage stress on the boost diode is slightly
higher than the output voltage because of the presence of the storage capacitor in the
auxiliary passive circuit, but the current in the boost diode is well within the limit.
Comparing with the single-phase conventional AC-DC PFC boost converter, this proposed
converter achieves higher efficiency for a wide range of output power.
The prototype
developed in the laboratory of the proposed converter operates at almost unity power factor
and provides low THD. The experimental results measured and recorded are authenticated
with the simulation results of the proposed converter.
3.
For medium power applications, a single-phase AC-DC PFC boost converter
with a suitable active auxiliary snubber circuit has been investigated and proposed. This
topology with an active auxiliary circuit is designed to achieve ZVT for main switch; its
feasibility is tested and verified with prototype developed in the laboratory. The auxiliary
153
active circuit components require lower ratings than that of the main power circuit
components.
The proposed auxiliary circuit contributes less power loss because it is
connected in parallel to main switch and is active only for very short duration over a
switching period. The auxiliary circuit is designed such that main switch turns-on exactly at
zero voltage and auxiliary switch turns-on at ZCS; and both the switches are turned off at
near ZVS. All the other semiconductor uncontrolled switches are turned on and off at
exactly/ ZVS and/or ZCS.
In this manner, the proposed ZVT topology minimizes the
switching losses of a proposed AC-DC PFC boost converter. There are no extra voltage and
current stresses on all semiconductor switches and the drawback of the extra voltage stress of
boost diode in the previously proposed passive snubber circuit (chapter 3) has been overcome
in this topology.
The proposed ZVT topology is highly efficient as compared with conventional
hard-switched and soft-switched passive snubber (proposed in chapter 3) and this is
authenticated from efficiency graph.
Efficiency graph also shows the wide load range
applicability of the operation of the converter. Moreover, the proposed PFC converter with
active auxiliary circuit has a simple structure and ease of control because of lesser number of
components in comparison to the proposed PFC converter with auxiliary passive circuit
presented in chapter 3 of this thesis. A prototype of specification 400 V, 500 W and 100 kHz
converter is developed and tested in the Power Electronics and Drives laboratory to verify
with the simulation result. The prototype operates at nearly unity input power factor with low
THD over a wide range of load power.
4.
Besides improving circuit topology and performance for improvement in
efficiency, a high power expandability and higher power density could be realized by
connecting three identical single-phase PFC boost converters in modular approach.
154
In
addition, this approach also provides higher power density and less weight of PFC converter
system.
The topologies of soft-switched converters proposed in chapter 3 and chapter 4 are
used to develop prototypes of three-phase system in modular approach. The performance
improvement of these three-phase converters (soft-switched with passive snubber and softswitched with active snubber) is described in chapter 5 of this thesis separately. The features
of soft-switching and its performance improvements described in single-phase soft-switched
converters (chapter 3 and chapter 4) are retained in the three-phase modular systems (part I
and part II respectively) and hence provide higher efficiency with primary objective of
operating converters at nearly unity power factor.
This modular approach for a given specification of higher output power can reduce
the count of passive components such as output capacitors (bulk in size), size and
interconnections. Therefore, three-phase modular system in DPS could result in higher
power density, better electrical performance, and easier thermal management. Moreover, due
to the modular approach, entire front-end converter could be assembled by placing different
integrated power electronics module together.
Therefore, automatic manufacturing is
possible, which can result in lower cost of the system.
6.2
Future Scope
This dissertation has tried out to break-through some technology barriers for future
power management in the field of DPS. It has explored some good ideas and suitable
solutions, but further investigation is necessary either for telecom and computer server
applications or in related field of power management, which are suggested as follows:
6.2.1 Dynamic response in low power applications
155
In the chapter 2 of this thesis, it is revealed that faster dynamic response can be
achieved for PFC boost converter with two sided PWM technique. This two sided PWM
technique can be applied to fly-back (derived from buck-boost) and forward (derived from
buck) converters operating as AC-DC PFC converters. These converters are preferred
because they provide proper isolation between input and output; moreover any output voltage
can be obtained by changing the transformer turns ratio of these converters for low power
(<250 W) applications such as power sources to aeronautical and bio-medical equipments.
6.2.2 Design of PFC converter at very high switching frequency
In this thesis, PFC boost converters with auxiliary circuits are designed for switching
frequency of 100 kHz in a university/laboratory level of engineering research. A very high
power density PFC converters operating at very high switching frequency (hence reduction in
size of passive components) has become important in these years.
The high output power density of the PFC converters is experiencing an adverse
effect resulted from the applied switching frequency. Thus further improvement on the
circuit analysis and printed circuit board (PCB) layout design could help in the improvement
of high switching operating frequency.
In spite of issues resulted from the very high
switching frequency (> 400 kHz) converter design, selection of recently developed
semiconductor devices (CoolMOSTM MOSFETs, Silicon Carbide diodes) and PCB layout
circuit design are among the important factors to consider, to maximize the capability of
frequency-output power product in the very high switching frequency converter applications.
6.2.3 Unbalanced input voltage in modular approach
Continuation of the work described in chapter 5 of this dissertation could be focused
on the unbalanced three-phase input voltages and output load conditions. The schemes
presented in sections 5.1 and 5.3 of chapter 5 are based on balanced input voltages. Further
investigation would also be required during grid disturbance such as voltage sag or swell.
156
References
[1]
M. Mankinkar, “Power supplies’ energy business/revenue models,” in Proc. IEEE
Applied Power Electron., Conf. (APEC’06), pp. 3-5, 2006.
[2]
F. C. Lee, P. Barbosa, Peng xu, J. Zhang, B. Yang and F. Canales, “Topologies and
design considerations for distributed power system applications”, in Proc IEEE, vol. 89,
no. 6, June 2001, pp. 939-950.
[3]
F. C. Lee, M. Xu, S. Wang, and B. Lu, “Design challenges for distributed power
systems,” in Proc. IEEE Power Electron., and motion control, (IPEMC’06), 2006, pp. 115.
[4]
W. A. Tabisz, M. M. Jovanovic, and F. C. Lee, “Present and future of distributed power
systems”, in Proc. IEEE Applied Power Electron., Conf. (APEC’92), 1992, pp. 11-18.
[5]
R. Ayyanar, R. Giri, and N. Mohan, “Active input voltage and load current sharing in
input-series and output parallel connected modular dc-dc converter using dynamic inputvoltage reference scheme”, IEEE Trans. Power Electron., vol. 19, no. 6, pp. 1462-1473,
Nov. 2004.
[6]
S. Moo, H. L. Cheng, and P. H. Lin, “Parallel operation of modular power factor
correction circuits”, IEEE Trans. Power Electron., vol. 17, no. 3, pp. 398-404, May 2002.
[7]
M. L. Heldwein, A. Ferrari De Souza, and I. Barbi, “A simple control strategy applied to
three-phase rectifier units for telecommunication applications using single-phase rectifier
modules”, in Proc. Power Electron. Spec. Conf. (PESC’99), vol. 2, 1999, pp. 795-800.
[8]
B. Lu, “Investigation of high-density integrated solution for AC/DC conversion of a
distributed power system,” PhD – Dissertation, Virginia polytechnic Inst. and State
University, May 2006.
[9]
M. Ilic, D Maksimovic, “Interleaved zero-current-transition buck converter,” IEEE Trans.
Ind. Applications., vol. 43, no. 6, pp. 1619-1627, Nov. 2007.
157
[10]
J. Perreault, “Design and evaluation of cellular power converter architectures”, Ph.D dissertation, Massachusetts Institute of Technology, June 1997.
[11]
Pressman, “Switching power supply design,” Second Edn., McGraw-Hill Publications,
1998.
[12]
R. A. Adams, R. C. Catoe Jr, J. G. Dalton, and S. G. Whisenant, “Power quality issues
within modern industrial facility,” in Proc. IEEE-Fiber and Film Industry Technical
Conf., May 1990, pp. 1-6.
[13]
R. G. Coney, “The impact of power quality on industry in Africa,” in Proc. IEEEAFRICON, vol. 1, Sept. 1996, pp. 21 - 27.
[14]
“IEEE 519 Recommended Practices and Requirements for Harmonic Control in Electric
Power Systems,” Tech. Rep., IEEE Industry Applications Soc./Power Engineering Soc.,
1993.
[15]
N. Mohan, T. M. Undeland, and W. P. Robbins, “Power electronics, converters,
applications, and design,” John Wiley & Son, Inc., New York, 1995.
[16]
Y. Zaohong, and P. C. Sen, “Recent developments in high power factor switch-mode
converters,” in Proc. IEEE-Elect. & Computer Engg., Conf., vol. 2, 1998, pp. 477-480.
[17]
W. Huai, I. Batarseh, “Comparison of basic converter topologies for power factor
correction,” in Proc. IEEE- Secon’98, 1998, pp. 348-353.
[18]
K. Rustom, and I. Batarseh, “Recent advances in single-stage power factor correction,” in
Proc. Intl. Conf. on Indl. Technology (ICIT’03), vol. 2, 2003, pp. 1089-1095.
[19]
C. Qiao, and K. M. Smedley, “A topology survey on single-stage power factor corrector
with a boost type input-current-shaper,” IEEE Trans. Power Electron., vol. 16, no. 3, pp.
360-368, May 2001.
158
[20]
O. Garcia, J. A. Cobos, R. Prieto, P. Alou, and J. Uceda, “Single phase power factor
correction: A survey,” IEEE Trans. Power electron., vol. 18, no. 3, pp. 749-755, May
2003.
[21]
R. J. King, “Analysis and design of an unusual unity power factor rectifier,” IEEE Trans.
Indl. Electron., vol. 38, no. 2, pp. 126-134, April 1991.
[22]
R. Mrtinez, and P. N. Enjeti, “A high performance single phase rectifier with input power
factor correction,” IEEE Trans. on Power Electron., vol. 11, no. 2, pp. 311-317, Mar.
1996.
[23]
K. Liu, and Y. Lin, “Current waveform distortion in power factor correction circuits
employing discontinuous-mode boost converters,” in Proc. Power Electron. Spec. Conf.
(PESC’89), 1989, pp. 533-540.
[24]
L. Rossetto, G. Spiazzi, and P. Tenti, “Control techniques for power factor correction
converters” in Proc. Intrl. Conf. on Power Electron., and Motion Control, Warswaw,
Sept. 1994, pp. 1310-1318.
[25]
J. Klein, M. K. Nalbant, "Power Factor Correction - Incentives, Standards and
Techniques," in Proc. Power Conversion and Intelligent Motion (PCIM’90), 1990, pp.
27-31.
[26]
G. Spiazzi, and J. A. Pomilio, “Interaction between EMI filter and power factor
preregulators with average current control: analysis and design considerations,” IEEE
Trans. Industrial Electron., vol. 46, no. 3, pp. 577-584, June 1999.
[27]
J. Rajagopalan, and F. C. Lee, “A general technique for derivation of average current
mode control laws for single-phase power-factor-correction circuits without input voltage
sensing,” IEEE Trans. Power Electron., vol. 14, no. 4, pp. 663-672, July 1999.
159
[28]
H. H. C. Iu, Y. Zhou, and C. K. Tse, “Fast-scale instability in a PFC boost converter
under average current-mode control,” Int. J. Circ. Theory and Appl., vol. 31, John Wiley
& Sons, pp. 611-624, 2003.
[29]
M. Orabi, and T. Ninomiya, “Review of pre-regulator CCM boost PFC converter
dynamics limits,” in Proc. Power Electron. Spec. Conf. (PESC), 2004, pp. 2314-2319.
[30]
Fernandez, J. Sebastian, P. Villegas, M. M. Hernando, and D. G. Lamar, “Dynamic limits
of a power-factor preregulators,” IEEE Trans. Industrial Electron., vol. 52, no. 1, pp. 7787, Feb. 2005.
[31]
C. Zhou and M. M. Jovanovic, “Design trade-offs in continuous current-mode controlled
boost power-factor correction circuits," in Proc. International High Frequency Power
Conversion Conf. (HFPC’92), 1992, pp. 209-220.
[32]
J. P. Noon, “Designing high-power factor off-line power supplies,” Proc. Unitrode power
Supply Des. Sem., 2003, pp. 2.1–2.35.
[33]
L. H. Dixon, “High power factor preregulators for off-line power supplies,” Unitrode
Power Supply Design Manual, SEM600, 1988.
[34]
J. Sebastian, P. J. Villegas, F. Nuno, O. Garcia, and J. Arau, “Improving dynamic
response of power-factor preregulators by using two-input high-efficient postregulators,”
IEEE Trans. Power Electron., vol. 12, no. 6, pp. 1007-1016, Nov. 1997.
[35]
M. Orabi, T. Ninomiya, C. Jin, “New practical issue for power factor correction converter
stability,” in Proc. Euro. Power and Energy Systems, (PES’02), 2002, pp. 340-345.
[36]
M. Orabi, T. Ninomiya, C. Jin, “New formulation for the stability analysis of power
factor correction converters,” in Proc. IEEE-Power Electron., Congress, (CIEP’02),
2002, pp. 33-38.
160
[37]
M. Orabi, T. Ninomiya, C. Jin, “Novel developments in the study of nonlinear
phenomena in power –factor-correction circuits,” in Proc. IEEE- Indl. Electron., Conf.
(IECON’02), vol. 1, 2002, pp. 209-215.
[38]
M. Rathi, N. Bhiwapurkar, and N. Mohan, “Dual voltage controller based power factor
correction circuit for faster dynamics and zero steady state error,” in Proc. IEEE-Indl.
Electron., Conf. (IECON’03), vol. 1, 2003, pp. 238-242.
[39]
Y. M. Lai, S. C. Tan, and S. N. Chan, “A fast response zero-voltage- pulse-width
modulation boost converter using a variable gain control technique,” in Proc. IEEE-Intl.
Conf. on Indl. Technology, (ICIT’08), 2008, pp. 1-6.
[40]
P. Maimo-uni, H. Tranduc, P. Rossel, D. Allain, and M. Napieralska, “Spice model for
TMOS power MOSFETs,” in Application Note AN1043, 2005, Motorola Semiconductor.
[41]
L. Spaziani, “A study of MOSFET performance in processor targeted buck and
synchronous rectifier buck converters,” in proc. High Freq. Power. Conv. Conf.
(HFPC’96), Sept. 1996, pp. 123-137.
[42]
Y. Qiu, M. Xu, F. C. Lee, Y. Bai, and A. Q. Huang, “Investigation of synchronous
MOSFET body diode reverse body diode recovery loss in voltage regulator modules,” in
proc. CPES’03, 2003, pp. 229-233.
[43]
M. Brown, “Power supply cookbook”, Second Edition, Woburn, USA, ButterworthHeinemann Publications, 2001.
[44]
J. Klein, “Synchronous buck MOSFET loss calculations,” in Fairchild Semiconductor,
Power Management Applications, AN-6005, 2006.
[45]
V. Barkhordarian, “Power MOSFET basics,” in international rectifier, Application Note.
[46]
M. Oabi, A. Abou-Alfotouh, and A. Lotfi, “Coss capacitance contribution to synchronous
buck converter losses,” in Proc. Power Electron., Spec. Conf. (PESC’08), June 2008, pp.
666-672.
161
[47]
G. Hua, E. X. Yang, Y. Jiang, and F. C. Lee, “Novel zero-current transition PWM
converters,” in Proc. Power Electron., Spec. Conf. (PESC’93), 1993, pp. 538-544.
[48]
T. Lopez, G. Sauerlaender, T. Duerbaum and T. Tolle, “A detailed analysis of a resonant
gate driver for PWM applications,” in Proc. Appl. Power Electr., Conf (APEC’03), 2003,
pp. 873-878.
[49]
R. L. Steigerwald, “Lossless gate driver circuit for a high frequency converter,” in U.S.
Patent 5010261, April 1991.
[50]
S. H. Weinberg, “A novel lossless resonant MOSFET driver,” in Proc. Power Electron.,
Spec. Conf. (PESC’92), 1992, pp. 1003–1010.
[51]
Z. Yang, S. Ye, and Y. Liu, “A new resonant gate drive circuit for synchronous buck
converter,” IEEE Trans. Power Electron., vol. 22, no.4, pp. 1311-1320, 2007.
[52]
K. Yao, and F. C. Lee, “A novel resonant gate driver for high frequency synchronous
buck converters,” IEEE Trans. on Power Electron., vol. 17, no.2, pp. 180-187, 2002.
[53]
E. E. Buchanan and E. J. Miller, “Resonant switching power conversion technique,” in
Proc. Power Electron. Spec. Conf. (PESC’75), 1975 Rec., pp. 188-193.
[54]
E. J. Miller, “Resonant switching power conversions,” in Proc. Power Electron. Spec.
Conf. (PESC’76), 1976, pp. 194-204.
[55]
K. H. Liu and F. C. Lee, “Resonant switches-A unified approach to improve performance
of switching converters,” in Proc. IEEE Int. Telecomm., Energy Conf. 1984, pp. 344-351.
[56]
M. M. Jovanovic, “Resonant, quasi-resonant, multi-resonant and soft-switching
techniques-merits and limitations,” International journal of Electronics, vol. 77, no. 5, pp.
537-554, 1994.
[57]
S. J. Jeon, and C. G. Hyeong, “A primary-side-assisted zero-voltage and zero-current
switching DC-DC converter,” International Journal of Electronics, Taylor and Francis,
vol. 89, no. 1, pp. 77-89, 2002.
162
[58]
H. Guichao, and F. C. Lee, “Soft-switching techniques in PWM converters,” in Proc.
Indl. Electron., Control and Instrumentation Conf. (IECON’93), 1993, pp. 637-643.
[59]
M. K. Kazimierczuk, W. D Morse, “State-plane analysis of zero-voltage-switching
resonant DC/DC converters,” IEEE Tran. Aerospace and Electronic Systems, vol. 25, no.
2, pp. 232-240, Mar. 1989.
[60]
M. K. Kazimierczuk, “Analysis and design of buck/boost zero-voltage-switching resonant
DC/DC converter,” Proc. IEE, Circuits devices and Systems, vol. 136, no. 4, pp. 157-166,
Aug. 1989.
[61]
M. M. Jovanovic, K. H. Liu, O. Ramesh, F. C. Lee, “State-plane analysis of quasiresonant converters,” IEEE Trans. Power Electron., vol. PE-2, no. 1, pp. 36-44, 1987.
[62]
J. A. Correa Pinto, A. A. Pereira, V. J. Farias, L. C. Freitas, and J. B. Vieira Jr, “A power
factor correction pre-regulator AC-DC interleaved boost with soft-commutation,” in
Proc. Power Electron. Spec. Conf. (PESC’97), vol. 1, 1997, pp. 121-125.
[63]
M. A. Chaudhari and H. M. Suryawanshi, “High-power-factor operation of three-phase
AC-to-DC resonant converter,” Proc. IEE, Electr. Power Appln., vol. 153, no. 6, pp. 873882, Nov. 2006.
[64]
G. Hua, and F. C. Lee, “Soft-switching techniques in PWM converters,” IEEE Trans. Ind.
Electron., vol. 42, no. 6, pp. 595-603, Dec. 1995.
[65]
W. H. Wolfle, and W. G. Hurley, “Quasi-active power factor correction with a variable
inductive filter: Theory, design and practice,” IEEE Trans. Power Electron., vol. 18, no.
1, pp. 248-255, Jan. 2003.
[66]
K. H. Liu, O. Ramesh, and F. C. Lee, “Quasi-resonant converters-topologies and
characteristics,” IEEE Trans. Power Electron., vol. PE-2, no. 1, pp. 62-71, Jan. 1987.
[67]
Y. Jang, M. M. Jovanovic, “A new PWM ZVS full-bridge converter,” IEEE Trans. Power
Electron., vol. 22, no. 3, pp. 987-994, May 2007.
163
[68]
F. L. Tofoli, E. A. A. Coelho, L. C. Freitas, V. J. Farias, and J. B. Vieira, “Proposal of a
soft-switching single-phase three-level rectifier,” IEEE Trans. Ind. Electron., vol. 55, no.
1, pp. 107-113, Jan. 2008.
[69]
E. Kim, and B. H. Kwon, “Zero-voltage-and zero-current-switching full-bridge converter
with secondary resonance,” IEEE Trans. Indl. Electron., vol. 57, no. 3, pp. 1017-1025,
Mar. 2010.
[70]
K. M. Smith, K. M. Smedley, “A comparison of voltage-mode soft-switching methods for
PWM converters,” IEEE Trans. Power Electron., vol. 12, no. 2, pp. 376-386, Mar. 1997.
[71]
K. I. Hwu, C. Tsai, K. F. Lin, “A simple passive ZCS circuit for PFC converter,” in Proc.
Applied Power Electronics Conf. Expo., (APEC’08), 2008, pp. 1022-1026.
[72]
G. Yao, A. Chen, and X. He, “Soft switching circuit for interleaved boost converter,”
IEEE Trans. Power Electron., vol. 22, no. 1, pp. 80-86, Jan. 2007.
[73]
P. F. Melo, R. Gules, E. F. R. Romaneli, and R. C. Annunziato, “A modified SEPIC
converter for high-power-factor rectifier and universal input voltage applications,” IEEE
Trans. Power Electron., vol. 25, no. 2, pp. 310-321, Feb 2010.
[74]
G. Moschopoulos, P. K Jain, Y. Liu, and G. Joos, “A zero-voltage-switched PWM boost
converter with an energy feedforward auxiliary circuit,” IEEE Trans. Power Electron.,
vol. 14, no. 4, pp. 653-661, July 1999.
[75]
K. Liu, and F. C. Lee, “Zero-voltage switching technique in DC/DC converters,” IEEE
Trans. Power Electron., vol. 5, no. 3, pp. 293-304, July 1990.
[76]
Y. Jang, M. M. Jovanovic, K. Fang, and Y. Chang, “High-power-factor soft-switched
boost converter,” IEEE Trans. Power Electron., vol. 21, no. 1, pp. 98-104, Jan. 2006.
[77]
Y. Jang, M. M. Jovanovic, and D. L. Dillman, “Soft-switched PFC boost rectifier with
integrated ZVS two-switch forward converter,” IEEE Trans. Power Electron., vol. 21,
no. 6, pp. 1600-1606, Nov 2006.
164
[78]
H. Mao, F. C. Lee, D. Boroyevich, and S. Hiti, “Review of high-performance three-phase
power-factor correction circuits,” IEEE Trans. Ind. Electron., vol. 44, no. 4, pp. 437-446,
Aug. 1997.
[79]
I. Batarseh, “Power electronic circuits,” John Wiley and Sons, Inc., Hoboken, NJ, 2004.
[80]
M. M. Jovanovic, W. A. Tabisz, and F. C. Lee, “Zero-voltage-switching technique in high
frequency off-line converters,” in Proc. Applied Power Electronics Conf. (APEC’88),
1988, pp. 23-32.
[81]
D. Maksimovic, and S. Cuk, “Ageneral approach to synthesis and analysis of quasiresonant converters,” in Proc. IEEE- Power Electron. Spec. Conf. (PESC’89), 1989, pp.
713-727.
[82]
R. Farrington, M. M. Jovanovic, and F. C. Lee, “Constant-frequency zero-voltageswitched multi-resonant converters: topologies, analysis, and experimental results,” in
Proc. IEEE-Power Electron. Spec. Conf. Rec. (PESC’90), 1990, pp. 33-40.
[83]
L. Ge, M. Shoyama, T. Ninomiya, “Noise reduction mechanism in common-source type
active-clamped DC-DC converters,” in Proc. IEEE – Tele-commn., Energy Conf., 2003,
pp. 505-509.
[84]
H. M. Suryawanshi, M. R. Ramteke, K. L. Thakre, and V. B. Borghate, “Unity-PowerFactor operation of three-phase AC-DC soft switched converter based on boost active
clamp topology in modular approach,” IEEE Trans. Power Electron.,, vol. 23, no. 1, pp.
229-236, Jan. 2008.
[85]
C. Gang, X. Dehong, F. Bo, W. Yousheng, “Minimum-voltage active-clamping DC-DC
converters,” in Proc. Power Electron. Spec. Conf. (PESC’02), 2002, pp. 403-408.
[86]
S. Lee, J. Park, and S. Choi, “A three-phase current-fed push-pull DC-DC converter with
active clamp for fuel cell applications,” in Proc. IEEE-Applied Power Electron., conf.
(APEC’10), 2010, pp. 1934-1941.
165
[87]
J. P. Rodrigues, S. A. Mussa, I. Barbi, A. J. Perin, “Three-level zero-voltage switching
pulse-width modulation DC-DC boost converter with active clamping,” Proc. IET-Power
Electronics, pp. 345-354, 2010.
[88]
N. Lakshminarasamma, and V. Ramanarayana, “A family of auxiliary switch ZVS-PWM
DC-DC converters with couple inductor,” IEEE Trans. Power Electron., vol. 22, no. 5,
pp. 2008-2017, Sept. 2007.
[89]
N. Lakshminarasamma, B. Swaminathan, and V. Ramanarayana, “A unified model for
ZVS dc to dc converters with active clamp,” in Proc. Power Electron. Spec. Conf.
(PESC’04), 2004, pp. 2441-2447.
[90]
C. J. Tseng, and C. L. Chen, “A passive lossless snubber cell for non-isolated PWM
DC/DC converters”, IEEE Trans. Ind. Electron., vol. 45, no. 4, pp. 593-601, 1998.
[91]
C. A. Gallo, F. L. Tofoli, and J. A. C. Pinto, “A passive lossless snubber applied to the
AC-DC interleaved boost converter,” IEEE Trans. Power Electron., vol. 25, no. 3, pp.
775-785, 2010.
[92]
R. T. H. Li, C. H. Shu-hung, “A passive lossless snubber cell with minimum stress and
wide soft-switching range,” IEEE Trans. Power Electron., vol. 25, no. 7, pp. 1725-1738,
July 2010.
[93]
W. Y. Choi, J. M. Kwon, E. H. Kim, J. J. Lee, B. H. Kwon, “Bridgeless boost rectifier
with low conduction losses and reduced diode reverse-recovery problems,” IEEE Trans.
Ind. Electron., vol. 54, no. 2, pp. 769-780, 2007.
[94]
F. Z. Peng, G. J Su, and L. M. Tolbert, “A passive soft-switching snubber for PWM
inverters,” IEEE Trans. Power electron., vol. 19, no. 2, pp. 363-370, 2004.
[95]
H. Wu, and X. He, “Single phase three-level power factor correction circuit with passive
lossless snubber,” IEEE Trans. Power Electron., vol. 17, no. 6, pp. 946-953, 2002.
166
[96]
X. He, A. Chen, W. Hongyang, D. Yan, and Z. Rongxiang, “Simple passive lossless
snubber for high-power multilevel inverters,” IEEE Trans. Ind. Electron., vol. 53, no. 3,
pp. 727-735, June 2006.
[97]
H. Bodur, A. F. Bakan, “A new ZVT-PWM DC-DC converter,” IEEE Trans. Power
Electron., vol. 17, no. 1, pp. 40-47, Jan. 2002,
[98]
C. J. Tseng, C. L. Chen, “A novel ZVT PWM cuk power-factor corrector,” IEEE Trans.
Ind. Electron., vol. 46, no. 4, pp. 780-787, Aug. 1999.
[99]
J. Bazinet, J. A. O’Connor, “Analysis and design of a zero voltage transition power factor
correction circuit,”
in Proc. IEEE-Applied Power Electron., Conf. (APEC’94), Feb.
1994, pp. 591-597.
[100] C. J. Tseng, and C. L. Chen, “Novel ZVT-PWM converters with active snubbers,” IEEE
Trans. Power Electron., vol 13, no. 5, pp. 861-869, Sept. 1998.
[101] S. Kaewarsa, C. Prapanavarat, U. Yangyuen, “An improved zero voltage-transition
technique in a single-phase power factor correction circuit,” in Proc. International
conference on power system technology – (POERCON’04), vol. 1, Nov. 2004, pp. 678 –
683.
[102] J. P. Noon, “A 250 kHz, 500W power factor correction circuit employing zero voltage
transitions,” Switching Regulated Power Supply Design Manual, Unitrode, 1995.
[103] S. Wen, C. Renjie, and C. L. Yung, “A ZVT quasi-resonant PWM converter for unity
power factor application,” Intl. Journal of Electronics, Taylor and Francis Ltd, vol. 84,
no. 4, pp. 421-428, 1998.
[104] C. J. Tseng, and C. L. Chen, “Comparisons of zero-voltage-transition cuk converters,”
Proc. IEE-Electr. Power Appl., vol 146, no. 4, pp. 433-440, July 1999.
167
[105] C. S. Yun, B. C. Kim, K. H. Kim, Y. C. Lim and P. Freere, “Reducing the high frequency
transformer losses in an FB ZVT PWM converter,” Proc. IEE-Electr. Power Appl., vol.
149, no. 2, pp. 161-164, Mar. 2002.
[106] J. L. Lin, C. H. Chang, “Small-signal modeling and control of ZVT-PWM boost
converters,” IEEE Trans. Power Electron., vol. 18, no.1, pp. 2-10, Jan. 2003.
[107] N. Jain, K. J. Praveen, and J. Geza, “A zero voltage transition boost converter employing
a soft switching auxiliary circuit with reduced conduction losses,” IEEE Trans. Power
Electron., vol. 19, no. 1, pp. 130-139, Jan. 2004.
[108] B. R. Lin, S. J. Huang, and C. H. Huang, “Implementation of a switching mode power
supply with ZVT power factor correction,” in Proc. IEEE-Power Electron., and Drive
Systems, (PEDS’03), vol. 2, 2003, pp. 1402-1406.
[109] P. J. M. Menegaz, J. L. F. Vieira, D. S. L. Simonetti, “A ZVT DC-DC self resonant boost
converter with improved features,” in Proc. Power Electron. Spec. Conf. (PESC’04),
2004, pp. 1631-1635.
[110] M. L. Martins, J. L. Russi, H. Pinheiro, J. R. Pinheiro, H. A. Grundling, and H. L. Hey,
“Unified design of ZVT PWM converters with resonant auxiliary circuit,” Proc. IEEElectr. Power Appl., vol. 151, no. 3, pp. 303-312, May 2004.
[111] M. Ilic, D. Maksimovic, “Interleaved zero current transition buck converter,” in Proc.
Applied Power Electron., Conf. (APEC’05), vol. 2, pp. 1265-1271, 2005.
[112] J. Russi, M. L. Martins, H. A. Grundling, H. Pinheiro, J. R. Pinheiro, and H. L. Hey, “An
improved design for ZVT DC-DC PWM converters with snubber assisted auxiliary
switch,” Journal of Revista Controle and Automacao, vol. 16, no. 1, pp. 25-33, Jan.
2005.
[113] M. L. Martins, J. L. Russi, and H. L. Hey, “A classification methodology for zero-voltage
transition PWM converters,” Journal of Revista Controle and Automacao, vol. 16, no. 1,
168
pp. 44-55, Jan. 2005.
[114] M. Ilic, D Maksimovic, “Interleaved zero-current transition buck converter,” IEEE-Trans.
Industry Applns., vol. 43, no. 6, pp. 1619-1627, Nov/Dec 2007.
[115] C. M. de Oliveira Stein, J. R. Pinheiro, and H. L. Hey, “A ZCT auxiliary commutation
circuit for interleaved boost converters operating in critical conduction mode,” IEEE
Trans. Power electron., vol. 17, no. 6, pp. 954-962, Nov. 2002.
[116] M. Mahesh, A. K. Panda and H. N. Pratihari, “A novel soft-switching boost power factor
correction converter with an active snubber,” in Proc. IET- Power Electron., Machines
and Drives, (PEMD’10), April 2010, pp. 1-6.
[117] I. Aksoy, H. Bodur, and A. F. Bakan, “A new ZVT-ZCT-PWM DC-DC converter,” IEEE
Trans. Power Electron., vol. 25, no. 8, pp. 2093-2105, Aug. 2010.
[118] J. Hahn, P. N. Enjeti, I. J. Pitel, “A new three-phase power-factor correction (PFC)
scheme using two single-phase PFC modules,” IEEE Trans. Industry Applns., vol. 38,
no. 1, pp. 123-130, Jan/Feb 2002.
[119] S. Kim, and P. N. Enjeti, “A modular single-phase power-factor-correction scheme with a
harmonic filtering function,” IEEE Trans. Indl., Electron., vol. 50, no. 2, pp. 328-335,
April 2003.
[120] U. Kamnarn, and V. Chunkag, “Analysis and design of a modular three-phase AC-to-DC
converter using CUK rectifier module with nearly unity power factor and fast dynamic
response,” IEEE Trans. Power electron., vol. 24, no. 8, pp. 2000-2012, Aug. 2009.
[121] G. Spiazzi, and F. C. Lee, “Implementation of a single-phase boost power-factorcorrection circuits in three-phase applications,” IEEE Trans. Indl. Electron., vol. 44, no.
3, pp. 365-371, June 1997.
[122] W. B. Lawrance, and W. Mielczarski, “Harmonic current reduction in a three-phase diode
bridge rectifier,” IEEE Trans. Indl. Electron., vol. 39, no. 6, pp. 571-576, Dec. 1992.
169
[123] M. Mahesh, A. K. Panda, “Two sided PWM control of switching power factor correction
AC-DC converter,” in Proc. Intl. Conf. on Industrial Technology, (IEEE-ICIT’09), pp. 16, Feb. 2009.
[124] M. Mahesh, A. K. Panda, “Improved dynamic response of 1-phase AC-DC power factor
correction converter,” International journal of Power System Optimization and control,
vol. 1, no. 1, pp. 43-48, Jan. 2009.
[125] A. Abramovitch , S Ben-Yaakov, “Analysis and design of the feedback and feedforward
paths of active power factor correction systems for minimum input current distortion”, in
Proc. Power Electron. Spec. Conf. (PESC’95), vol.2, 1995, pp. 1009-1014.
[126] J. P. Noon and D Dhaval, “Practical Design Issues for PFC Circuits”, in Proc. Applied
Power Electronics Conf. (APEC’97), vol. 1, 1997, pp. 51-58.
[127] C. K. Tse, "Circuit theory of power factor correction in switching converters,” Intl. J.
Theor. Appln., John Wiley, vol. 31, pp. 157-198, 2003.
[128] V. Vorperian, “Simplified analysis of PWM converters using model of PWM switch
continuous conduction mode,” IEEE Trans. Aerospace and Electronic Systems, vol. 26,
no. 3, pp. 497-505, 1990.
[129] W. Tang, F. C. Lee, and R. B. Ridley, “Small-signal modeling of average current mode
control,” in Proc. Applied Power Electronics Conf. (APEC’92), 1992, pp. 747-755.
[130] P. N. Ekemezie “Design of a power factor correction AC-DC converter,” in proc. IEEEAFRICON’07, 2007, pp. 1 – 7.
[131] M. Xie, “Digital control for power factor correction,” M.Sc. Dissertation, Virginia
polytechnic Inst. and State University, June 2003.
[132] P. Midya, and P. T. Krein, “Noise properties of pulse-width modulatedpower converters:
open-loop effects,” IEEE Tran. Power Electron., vol. 15, no. 6, pp. 1134-1143, Nov.
2000.
170
[133] P. Midya, and P. T. Krein, “Closed-loop noise properties of pulse-width modulated
power converters,” in Proc. Power Electron. Spec. Conf. (PESC’95), vol. 1, 1995, pp. 1521.
[134] P. Midya, K. Haddad “Two sided Latched Pulse Width Modulation Control”, in Proc.
Power Electronics Specialists Conference (PESC’00), vol. 2, 2000, pp. 628–633.
[135] R. B. Ridley, “A new, continuous-time model for current- mode control with constant
frequency, constant on-time, and constant off-time, in CCM and DCM,” in Proc. Power
Electron. Spec. Conf. (PESC’90), 1990, pp. 382–389.
[136] C. Zhou, R. B. Ridley and F. C. Lee, “Design and analysis of a hysteretic boost power
factor correction circuit”, in Proc. Power Electronics Specialists Conference (PESC’90),
1990, pp. 800-807.
[137] C. A. Canesin, I. Barbi, “A unity power factor multiple isolated outputs switching mode
power supply using a single switch”, in Proc. Applied Power Electron., Conf. (APEC’91),
1991, pp. 430–436.
[138] X. Yang and Z. Wang, “research on quasi-constant frequency hysteresis pwm current
mode control”, in Proc. Intl. Conf. on Power Electronics and Drive Systems, (PEDS’99),
vol. 2, 1999, pp. 1124–1127.
[139] K. Raggl, T. Nussbaumer, G. Doering, J. Biela, and J. W. Kolar, “Comprehensive design
and optimization of a high-power-density single-phase boost PFC,” IEEE Trans. Ind.
Electron., vol. 56, no. 7, pp. 2574-2587, 2009.
[140] P. C. Todd, “Boost power factor correction design with the UC3853,” Unitrode
Corporation, Application note, U-159.
[141] - Power Factor Correction Handbook, - On Semiconductor: Rev. 2, Aug-2004.
http://onsemi.com
171
[142] J. R. R. Zientarski, R. C. Beltrame, D. B. Candido, M. L. Martins, H. L. Hey, “Design
methodology for universal line input boost power factor correction magnetics,” IET
Power Electron., Journal, vol. 4, no. 6, pp. 715-724, 2011.
[143] N. Jain N, P. Jain, and Joos G, “Analysis of a zero voltage transition boost converter
using a soft switching auxiliary circuit with reduced conduction losses,” in Proc. Power
Electronics Specialists Conference (PESC’01), 2001, pp.1799-1804.
[144] G. Hua, X. Yang, Y. Jiang, and F. C. Lee, “Novel zero-current-transition PWM
converters,” in Proc. Power Electronics Specialists Conference (PESC’93), 1993, pp.
538-544.
[145] M. M. Jovanovic, “A technique for reducing rectifier reverse-recovery related losses in
high-voltage, high-power boost converters,” in Proc. Applied Power Electron., Conf.
(IEEE-APEC’97),1997, pp. 1000-1007.
[146] E. S. Silva, L. R. Barbosa, and J. B. Vieira, “An improved boost PWM soft-singleswitched converter with low voltage and current stresses,” IEEE Trans. on Industrial
Electronics, vol. 48, no. 6, pp. 1174-1179, Dec. 2001.
[147] H. Mao, F. C. Lee, X. Zhou, H. Dai, M. Cosan, and D. Boroyevich, “Improved zerocurrent transition converters for high-power applications,” IEEE Trans. on Industrial
Applications, vol. 33, no. 5, pp. 1220-1232, Sept. 1997.
[148] C. M. C. Duarte and I. Barbi, “A new family of ZVS-PWM active clamping dc-to-dc
converters: analysis, design and experimentation,” in Proc. INTELEC, 1996, pp. 305312.
[149] W. Dong, Q. Zhao, J. Liu, and F. C. Lee, “A boost converter with lossless snubber under
minimum voltage stress,” in Proc. Applied Power Electron., Conf. (IEEE-APEC’02),
Rec., 2002, pp. 509-515.
172
[150] L. Lorenz, G. Deboy and I. Zverev, “Matched pair of CoolMosTM transistor with SiCSchottky diode-advantages in applications,” in Proc. IEEE IAS, Rec., 2000, pp. 376-383.
[151] B. Lu, W. dong, Q. Zhao, and F. C. Lee, “Performance evaluation of CoolMOSTM and
SiC diode for single-phase power factor correction applications,” in Proc. Applied Power
Electron., Conf. (IEEE-APEC’03), 2003, pp. 651-657, 2003.
[152] R. T. H. Li, H. S. H. Chung, and A. K. T Sung, “Passive lossless snubber for boost PFC
with minimum voltage and current stress,” IEEE Trans. Power Electron., vol. 25, no. 3,
pp. 602-613, 2010.
[153] C. Y. Inaba, Y. Konishi, and M. Nakaoka, “High-frequency flyback-type soft-switching
PWM DC-DC power converter with energy recovery transformer and auxiliary passive
lossless snubbers,” IEE Proc. Elect. Power Applns., vol. 151, no. 1, pp. 32-37, 2004.
[154] S. Pattnaik, A. K. Panda, and K. Mahapatra, “Efficiency improvement of synchronous
buck converter by passive auxiliary circuit,” IEEE Trans. Industry Appln., vol. 46, no. 6,
pp. 2511-2517, Dec. 2010.
[155] C. Y. Inaba, Y. Konishi, H. Tanimatsu, Y. Ishigami, and M. Nakaoka, “Passive resonant
snubber-assisted two-switch flyback converter with auxiliary pulse transformer for energy
recovery,” in Proc. IEEE-Indl. Electron., Society, (IECON’03), vol. 1, 2003, pp. 55-59.
[156] L. Junyang, L. Jianwei, and J. M. Kiat, “ICE1PCS01 based boost type CCM PFC design
guide – control loop modeling,” Infineon Technologies-application note, vol. 1.3, pp. 127, 2007.
[157] K. M. Smith, K. M. Smedley, “Properties and synthesis of passive lossless soft-switching
PWM converters,” IEEE Trans. on Power Electronics, vol.14, no. 5, pp. 890-899, 1999.
[158] J. Y. Zhu, D. Ding, “Zero-voltage and zero-current switched PWM DC-DC converters
using active snubbers,”, IEEE Trans. Industry Applns., vol. 35, no. 6, pp. 1406-1412,
1999.
173
[159] N. Machin, and T. Vescovi, “Very high efficiency techniques and their selective
application to the design of a 70 A rectifier,” in Proc. 15th Int. Telecommun. Energy Conf.
(INTELEC’93). Sept. 1993, vol. 1, pp. 126-133.
[160] B. Irving, and M. Jovanovic, “Analysis, design, and performance evaluation of flyingcapacitor passive lossless snubber applied to PFC boost converter,” in Proc. Appl. Power
electron., Conf. Expo. (APEC’02), Mar. 2002, vol. 1, pp. 503-508.
[161] G. Ivensky, I. Zeltser, and S. Ben-Yaakov, “New snubbers with energy recovery into a
local power supply,” in Proc. 34th IEEE Power Electron., Spec. Conf. (PESC’03), Jun.
2003, vol. 2, pp. 1327-1332.
[162] K. Smith, and K. M. Smedly, “Lossless passive soft-switching methods for inverters and
amplifiers,” IEEE Trans. Power Electron., vol. 15, no.1, pp. 164-173, Jan. 2000.
[163] Y. Chen, K. M. Smedley, “Parallel operation of one-cycle controlled three-phase PFC
rectifiers,” IEEE Trans. Indl. Electron., vol. 54, no. 6, pp. 3217-3224, 2007.
[164] A. Newton, T. C. Green, and D. Andrew, “AC-DC power factor correction using
interleaved boost and CUK converters,” in Proc. Inst. Electr. Eng. PEVSD Conf. 2000,
pp. 293-298.
[165] S. Kim, and P. N. Enjeti, “Control of multiple single-phase PFC modules with a single
low-cost DSP,” IEEE Trans. Indl., Appln., vol. 39, no. 5, pp. 1379-1385, Oct. 2003.
[166] S. Kim, and P. N. Enjeti, “A parallel-connected single phase power factor correction
approach with improved efficiency,” IEEE Trans. Power Electron., vol. 19, no. 1, pp. 8793, Jan. 2004.
[167] L. C. G. Freitas, M. G. Simoes, C. A. Canesin, and L C. D. Freitas, “Programmable PFC
based hybrid multipulse power rectifier for ultra clean power applications,” IEEE Trans.
Power Electron., vol. 21, no. 4, pp. 959-966, Jul. 2006.
174
[168] X. H. Wu, S. K. Panda, and J. X. Xu, “Analysis of the instantaneous power flow for
three-phase PWM boost rectifier under unbalanced supply voltage conditions,” IEEE
Trans. Power Electron., vol. 23, no. 4, pp. 1679-1691, Jul. 2008.
[169] P. Xiao, K. A. Corzine, and G. K. Venayagamoorthy, “Multiple reference frame-based
control of three-phase PWM boost rectifiers under unbalanced and distorted input
conditions,” IEEE Trans. Power Electron., vol. 23, no. 4, pp. 2006-2017, Jul. 2008.
[170] T. Nussbaumer and J. W. Kolar, “Improving mains current quality for three-phase threeswitch buck-type PWM rectifiers,” IEEE Trans. Power Electron., vol. 21, no. 4, pp. 967973, Jul. 2006.
[171] T. Nussbaumer, M. Baumann, and J. W. Kolar, “Comprehensive design of a three-phase
three-switch buck-type PWM rectifier,” IEEE Trans. Power Electron., vol. 22, no. 2, pp.
551-562, Mar. 2007.
[172] L. –S. Yang, T. -J. Liang, and J. F. Chen, “Analysis and design of a novel three-phase
AC-DC buck-boost converter,” IEEE Trans. Power Electron., vol. 23, no. 2, pp. 707714, Mar. 2008.
[173] E. Jayashree, G. Uma, “Analysis, design and implementation of a quasi-resonant DC-DC
converter,” IET Power Electron., Journal, vol. 4, no. 7, pp. 785-792, 2011.
[174] L. Junyang, L. Jianwei, and J. M. Kiat, “ICE1PCS01 based boost type CCM PFC design
guide – Control Loop Modeling”, Appln. Note, Vol. 3, May 2007.
[175] _______, Standalone power factor correction controller in continuous conduction mode,
Appln. Note, Version 2.2, Oct. 2007.
175
RESEARCH PUBLICATIONS
JOURNAL
1. Matada Mahesh, and A. K. Panda, “Improved dynamic response of single-phase AC-DC
power factor correction converter,” International Journal in Power System Optimization and
Control (IJPSOC-09), vol. 1, no. 1, pp. 43-48, Jan. 2009.
2. Matada Mahesh, and A. K. Panda, “High-power factor three-phase AC-DC soft-switched
converter incorporating zero-voltage transition topology in modular systems for high-power
industry applications,” IET Power Electron., vol. 4, no. 9, pp. 1032-1042, Nov. 2011.
3. Matada Mahesh, and A. K. Panda, “Increase of efficiency of a ac-dc PFC boost converter by
a novel soft-switching technique”, Intl. Journal of Electric Power Components and Systems,
Taylor and Francis Publication, accepted for future publication.
CONFERENCE
1. Matada Mahesh, and A. K. Panda, “Two sided PWM control of switching power factor
correction AC-DC converter”, IEEE-International Conference on Industrial Technology,
(ICIT’09), pp. 1-6, Monash University – Gippsland, Australia,, Feb. 2009.
2. Matada Mahesh, and A. K. Panda, “Simulation of Improved Dynamic Response in Active
Power Factor Correction Converters” 13th IEEE VSI / VLSI Design and Test Symposium,
VDAT-‘09, VLSI Society of India. pp. 231-236, Wipro Campus, Bangalore, India, 2009.
3. Matada Mahesh, A. K. Panda, and H. N. Pratihari, “A novel soft-switching boost power
factor correction converter with an active snubber”, IET – PEMD’10, International Conf.
Power Electronics Machines and Drives, pp. 1-6, Brighton, UK, 2010.
4. Matada Mahesh, A. K. Panda “Implementation of a ZVT based Power Factor Correction
Converter”, IEEE-International Power and Energy Conference, IPEC’10, pp. 693-698,
Singapore, 2010.
176