Winco HPS9000VE E Tri-Fuel Generator Installation and Operators Manual
Below you will find brief information for Tri-Fuel Generator HPS9000VE E. It is a high-quality, precision engineered generator set designed and tested to give you years of satisfactory service. This portable unit requires large quantities of fresh air for cooling the engine and generator. This unit is capable of producing 8,000 watts of continuous power and 9,000 watts of surge power, providing you with reliable backup power for your home or business. It can be fueled by gasoline, natural gas, or LP vapor, giving you flexibility and convenience. You can start it manually or electrically, and the unit is equipped with a low oil shutdown system to prevent engine damage.
Advertisement
Advertisement
HPS9000VE/E
INSTALLATION AND
OPERATORS MANUAL
TRI-FUEL GENERATOR
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the generator and battery. Read and understand all instructions in the manual before starting and operating the generator set.
USING THE MANUAL
PROPER USE AND INSTALLATION
You must be sure your new engine generator set is:
* Properly serviced before starting.
* Operated in a well ventilated area.
* Properly exhausted and gases safely
dispersed.
* Operated only for its designed purposes.
* Used only by operators who understand
its operation.
* Properly maintained.
Congratulations on your choice of a Winco generator set. You have selected a high-quality, precision engineered generator set designed and tested to give you years of satisfactory service.
To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
COPY YOUR MODEL AND
SERIAL NUMBER HERE
No other WINCO generator has the same serial number as yours. It is important that you record the number and other vital information here. If you should ever need to contact us on this unit it will help us to respond to your needs faster.
Should you experience a problem please follow the “Troubleshooting Tables” near the end of this manual. The warranty listed in the manual describes what you can expect from WINCO should you need service assistance in the future.
MODEL
HPS9000VE/E
SERIAL NUMBER_________________________
TABLE OF CONTENTS
INTRODUCTION 2
BASIC INFORMATION
SAFETY INFORMATION 3
PURCHASE DATE_________________________
DEALER_________________________________
DEALER PHONE # ________________________
UNIT SPECIFICATIONS
GENERATOR MODEL HPS9000VE
Surge Watts 9,000
Continuous Watts 8,000
INITIAL START UP
Manual Starting (Gasoline only)
Electric Starting (Gasoline)
Electric Starting (LP/NG)
10
10
11
305447-0003-G1
S20W-110/
CONNECTING THE LOADS 12
ENGINE 14
CONTROL PANEL WIRING DIAGRAM
WARRANTY INFORMATION
17
18
3210-10
2
60706-237
SAFETY INFORMATION
This engine generator set has been designed and manufactured to allow safe, reliable performance.
Poor maintenance, improper or careless use can result in potentially deadly hazards; from electrical shock, exhaust gas asphyxiation, or fi re. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
b. Keep fuel containers out of reach of children.
c. Do not smoke or use open fl ame near the generator set or fuel tank.
Keep fi re extinguisher nearby and know its proper use. Fire extinguishers rated ABC by
NFPA are appropriate.
e. Store fuel only in an approved container, and only in a well ventilated area.
f. Follow local codes for closeness to
combustible material.
ANSI SAFETY DEFINITIONS
***********************************************************
DANGER:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations.
***********************************************************
3. DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain carbon monoxide, an invisible, odorless and deadly gas that must be mixed with fresh air.
a. Operate only in well ventilated areas.
b. Never operate indoors including attached
garages c. Never operate the unit in such a way as to allow exhaust gases to seep back into closed rooms (i.e. through windows, walls, fl oors).
***********************************************************
WARNING:
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
***********************************************************
4. NOISE HAZARD Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
a. Use hearing protection when working around this equipment for long periods of time.
b. Keep your neighbors in mind when using this
equipment.
***********************************************************
CAUTION:
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
***********************************************************
5. CLEANLINESS Keep the generator and surrounding area clean.
a. Remove all grease, ice, snow or materials that create slippery conditions around the unit.
b. Remove any rags or other materials that could create a potential fi re hazard.
c. Carefully clean up any gas or oil spills before starting the unit.
1. ELECTRICAL SHOCK The output voltage present in this equipment can cause fatal electric shock.
This equipment must be operated by a responsible person.
a. Do not allow anyone to operate the generator without proper instruction.
b. Guard against electric shock.
c Avoid contact with live terminals or
receptacles.
d Use extreme care if operating this unit in rain
6. SERVICING EQUIPMENT All service, including the installation or replacement of service parts, should be performed only by a qualifi ed technician.
a. Use only factory approved repair parts.
b. Do not work on this equipment when fatigued.
c. Never remove the protective guards, covers, or receptacle panels while the engine is
running.
d. Use extreme caution when working on electrical components. High output voltage from this equipment can cause serious injury e. Use only three-pronged grounded receptacles and extension cords.
f. Be sure the unit is properly grounded to an external ground rod driven into the earth.
e. Always avoid hot muffl ers, exhaust manifolds, and engine parts. They can cause severe
2. FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and/or fi re.
a. Do not refuel when the engine is running or
hot.
f. The use of the engine-generator set must comply with all national, state, and local
codes.
3210-10 3 60706-237
TESTING POLICY
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current and frequency are carefully checked.
Rated output of generator is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specifi ed by the manufacturer of the applicable engines.
INTENDED USES
This engine generator set has been designed primarily for portable heavy duty commercial use. Both
120 volt and 240 volt receptacles are provided in the control panel to plug in your loads (lights, portable tools, and small appliances). These units are dual wound generators, therefore the 120 volt loads must be equally split with 1/2 of the rated capacity available on each of the two 120 volt circuits.
This portable unit requires large quantities of fresh air for cooling the engine and generator. For safety, long life and adequate performance, these units should never be run in small compartments without positive fresh air fl ow.
UNIT CAPABILITIES
GENERATOR CONNECTIONS
HPS9000VE: 120 volt and 240 volt receptacles are provided for connection to various loads. The diagram below represents this 8,000 watt (rated output) generator. A & B represent the 120 volt output legs of this generator. Up to 4000 watts at 120 volts (33 Amps) can be drawn from the receptacles attached to either A or B output legs. This generator is capable of producing 33 Amps of 240 volt current at C.Check the appliance or tool nameplates for the current and voltage to insure compatibility. Remember that power taken from C reduces the power available at equally both A and B and vice versa.
RESTRICTED USES
DO NOT remove from the cradle assembly. Removal of the generator from the cradle assembly may cause excessive vibration and damage to the engine-generator set.
DO NOT install and operate this generator in a small compartment., i.e. generator compartments of vehicles, motor homes or travel trailers. These compartments will not allow enough free fl ow of fresh air to reach the engine generator set for cooling and will cause the unit to overheat, damaging both the engine and generator. Small compartments will also develop hot spots where there is very little air fl ow and may cause a fi re.
PLEASE NOTE There are 3rd party companies making enclosures for generators that have been properly engineered. The use of these 3rd party enclosures is acceptable as long as they have been certifi ed and meet current code.
DO NOT attempt to operate at 50 cycles. These units are designed and governed to operate at 60 cycles only.
STARTING ELECTRIC MOTORS
Electric motors require much more current (amps) to start them than to run them. Some motors, particularly low cost split-phase motors, are very hard to start and require 5 to 7 times as much starting current as running current. Capacitor motors are easier to start and usually require 2 to 4 times as much starting current as running current. Repulsion
Induction motors are the easiest to start and require only 1 1/2 to 2 1/2 times as much starting as running current.
Most fractional horsepower motors take about the same amount of current to run them whether they are Repulsion Induction (RI), Capacitor (Cap), or
Split-Phase (SP) type.
If the electric motor is connected to a hard starting load such as an air compressor, it will require more starting current. If it is connected to a light load, or no load such as a power saw, it will require less starting current. The exact requirement will also vary with the brand or design of the motor.
3210-10
4
60706-237
Self-exciting generators respond to severe overloading differently than utility power. When overloaded, the engine is not able to supply enough power to bring the electric motor up to operating speed. The generator responds with high initial starting current, but the engine speed drops sharply. The overload may stall the engine. If allowed to operate at very low speeds, the electric motor starting winding will burn out in a short time. The generator winding might also be damaged.
CAUTION: EQUIPMENT DAMAGE
RUNNING THE GENERATOR SET UNDER
THESE CONDITIONS MAY RESULT IN DAMAGE
TO THE GENERATOR STATOR AS WELL AS THE
MOTOR WINDING.
The heavy surge of current required for starting motors is required for only an instant. The generator will not be damaged if it can bring the motor up to speed in a few seconds of time. If diffi culty is experienced in starting motors, turn all other electrical loads off and if possible reduce the load on the electric motor.
LUBRICATION
Before starting the engine, fi ll the crankcase to the proper level with a good quality oil. The recommended grade of oil and quantity of oil required is listed in the engine operator’s manual and under the service tab in this manual. This unit was shipped with most of the oil removed. The engine normally holds 46 to 48 ounces of oil. Since there is some trapped oil in the engine, when fi lling the crankcase the fi rst time use the dipstick (ref “A”) to ensure that you do not over fi ll the crankcase. Reference “B” shows the full oil level mark on the dipstick.
A
C
B
A
PREPARING THE UNIT
UNPACKING
CAUTION: EQUIPMENT DAMAGE
THIS UNIT HAS BEEN SHIPPED WITHOUT OIL.
Failure to maintain the engine oil at the proper level will result in serious engine damage.
When you unpack your new engine-generator set be sure to remove all the information sheets and manuals from the carton.
1. This generator-set was in good order when shipped. Inspect the generator-set promptly after receiving it. If any damage is noted, notify the transportation company immediately; request proper procedures for fi ling a “concealed damage” claim. Title to the equipment and responsibility for fi ling a claim rests with you when a generator-set is sent F.O.B. shipping point. Only you can legally fi le a claim.
2. Before proceeding with the preparations of your new generator-set for operation, take a couple of minutes to insure the unit you have received is the correct model and review the specifi cation pages in this manual to insure that this unit meets your job requirements.
Oil is added to the engine by removing the oil fi ll cap
(ref “C”) and adding oil at this point. After fi lling the crankcase to the proper level, be sure you properly tighten the oil fi ll cap. NOTE: This engine generator must be on a level surface before you check or add oil to the system.
The necessity of using the correct oil, and keeping the crankcase full cannot be overemphasized. Engine failures resulting from inadequate or improper lubricant are considered abuse and not covered by the generator or engine manufacturer’s warranty.
Oil Recommendations
Outdoor temperatures determine the proper oil viscosity for the engines. Use the chart to select the best viscosity for the outdoor temperature range expected.
° F ° C
3210-10 5 60706-237
Oil Recommendations Con’t
LP/NG FUEL INSTALLATION
* Below 40 O F (4 O C) the use of SAE30 will result in hard starting.
** Above 80 O F (27 O C) the use of 10W-30 may cause increased oil consumption. Check oil level more frequently.
The information in this instruction is offered to assist you in providing the proper vapor fuel supply for your engine. This information is only provided to advise you of the engine’s requirements and the decisions you must make. In no case should this information be interpreted to confl ict with any local, state or national code. If in doubt, always follow local codes.
Briggs & Stratton recommends the use of their warranty certifi ed oils for best performance. Other highquality detergent oils are acceptable if classifi ed for service SF, SG, SH SJ or higher. Do not use special additives.
DANGER: FIRE - PERSONAL INJURY -
All fuel lines must be installed by a qualifi ed fuel
supplier.
GASOLINE
When using gasoline, always use fresh, clean, unleaded fuel. This engine is certifi ed to operate on unleaded gasoline with a minimum octane rating of
87 or higher. Gasoline containing no more than 10% ethanol is acceptable.
CAUTION: EQUIPMENT DAMAGE
Do not use unapproved gasolines, such as E15 or
E85. Do not mix oil in the gasoline. Use of unapproved fuels will damage the engine components and void the engine warranty.
The fuel source should be as close as possible to the outdoor operating location. This will reduce the installation cost of fuel runs. Connect the fuel supply line to the inlet of the fuel demand regulator on the unit using a locally approved fl exible fuel line (see table for recommended line size). The pressure supplied to the demand regulator must be FOUR
TO SIX OUNCES or 7 to 11 INCHES W.C. (water
column). The primary regulator at the fuel supply must be capable of delivering the proper volume of fuel at this pressure.
Use of fuels with content of ethanol greater than shown above may cause starting and/or performance problems. Always insure that the fuel is clean and free of all impurities.
Have your local fuel supplier install a protected fuel connection at the outside operating location. He should also install a lockable fuel shut off valve at the connection point. Have your fuel supplier permanently install a fl exible fuel line to the demand regulator on the engine generator set.
WARNING: FIRE DANGER
DANGER: FIRE - PERSONAL INJURY -
Gasoline and its fumes are VERY explosive when proper precautions are not taken.
The LP/NG fuel supply line must always be shut off when the engine is not running. Failure to do so may allow fuel to leak at the unit.
Never use gasoline that has been stored for an extended period of time as the fuel will lose its volatile properties and you will be left with varnish residue.
The varnish like substance will clog the carburetor and will not burn properly.
INSTALLING THE FUEL LINE
DANGER: PERSONAL INJURY
The use of fuel additives, such as STA-BIL, or an equivalent will minimize the formation of fuel gum deposits. If a unit has been out of operation for an extended period of time, it is best to drain old fuel from the engine and replace with fresh fuel before attempting to start.
Units that are intended to be run unattended
MUST have an electric fuel solenoid installed. This solenoid MUST be wired to AUTOMATICALLY turn off
the fuel whenever the engine stops.
See the engine manual for special instruction for operating this unit at over 5000 feet
Unit location will determine the size of fuel line that is required to supply the engine with a constant fuel pressure. Refer to the tables below for fuel line size, and recommended tank size. For distances of 100 feet and over, a two regulator fuel system is recommended. This system consisting of a primary 10-15# regulator at the tank and a 6 ounce secondary regulator installed about 10 feet from the generator.
3210-10
6
60706-237
You need to run a 3/4 inch line or larger from the secondary regulator to the engine-generator set. When a two (2) regulator fuel system is used, a fuel line size of 3/8 inch is generally adequate for distances up to 300 feet. The line size from the table below applies to the distance from the second regulator to the demand regulator. A positive fuel shut-off de- vice must be installed in the fuel line close to the
engine generator set. This may be either a lockable manual shut-off valve available from your local fuel installer, or a 12 volt DC fuel solenoid valve. This optional 12 volt DC valve is available through your local Winco dealer.
FUEL PRESSURE
Correct fuel pressure cannot be stressed enough.
The most common cause for inoperative systems is an inadequate or incorrect fuel pressure. Power and performance of the engine is in direct relation to the correctness of the fuel system. Shown below is a block diagram of a typical L.P. or N.G. installation.
The fuel line used to connect the supply line to the demand regulator must be a locally approved fl exible fuel line. Products used will vary in different regions depending on availability and local codes. Consult with your local fuel supplier to insure complete compliance with ALL codes.
1. Remove the pipe plug from the demand regulator.
2. Connect the fl ex fuel line to the demand regulator to the optional fuel solenoid..
Reference numbers 1 through 3 in the block diagrams above are system parts supplied by customer.
DANGER: PERSONAL INJURY
Do not use galvanized pipe in the fuel line runs.
The galvanized coating will become eroded and fl ake off, causing possible obstruction or damage to the regulator or fuel valve. The obstruction could cause an inoperative engine or an explosive fuel leak.
Reference number 4 is the engine generator set.
Below is a table of the fuel pressure reading at each reference in the system.
Fuel Pressure Table
Size of pipe required for generators operating on natural gas/LP gas.
Length of Fuel Line* Fuel Line Size
less than 25 feet
25 to 100 feet
over 100 feet
3/4 inch black pipe
1 inch black pipe
not recommended**
*allow an additional 3 feet for each standard elbow.
Do not use ‘street ells’ (restrictive)
** Consult factory for fuel runs over 100 feet.
DANGER! - FIRE - PERSONAL INJURY -
Be careful when sealing gas joints. Excessive sealing compound can be drawn into the solenoid, regulator or carburetor causing an engine malfunction
or dangerous fuel leak.
Single Regulator (L.P. Vapor only)
1 3
UNIT OFF
STARTING
NO LOAD
FULL LOAD
TANKPSI 7-11 in
4-6 oz
TANK PSI 7-11 in
4-6 oz
TANK PSI 7-11 in
4-6 oz
TANK PSI 7-11 in
4-6 oz
4
7-11 in
4-6 oz
7-11 in
4-6 oz
7-11 in
4-6 oz
7-11 in
4-6 oz
FUEL CONSUMPTION (Full Load)
Gasoline
LP Vapor
Natural Gas
1.63Gal/HR
1.9 Gal/HR
180 cu ft/hr
173,850 BTU
180,000 BTU
3210-10 7 60706-237
Two (2) Regulator System (L.P. Vapor only)
UNIT
OFF
1
TANK
PSI
2
10-15 lbs
STARTING TANK 10-15 lbs
PSI
NO LOAD TANK 10-15 lbs
FULL
LOAD
PSI
TANK 10-15 lbs
PSI
3
7-11 in
4-6 oz
7-11 in
4-6 oz
4
7-11 in
4-6 oz
7-11 in
4-6 oz
7-11 in 7-11 in
4-6 oz 4-6 oz
7-11 in 7-11 in
4-6 oz 4-6 oz
Natural Gas
UNIT OFF
STARTING
NO LOAD
FULL LOAD
1 3
LINE PSI 7-11 in
4
7-11 in
4-6 oz 4-6 oz
LINE PSI 7-11 in 7-11 in
4-6 oz
LINE PSI 7-11 in
4-6 oz
LINE PSI 7-11 in
4-6 oz
4-6 oz
7-11 in
4-6 oz
7-11 in
4-6 oz
Remember that whichever fuel delivery system or type of vapor fuel used, the fuel pressure at the demand regulator installed on the engine generator must be between 4 and 6 oz. (7-11 inches of water column). Any lower pressure and the unit will starve for fuel under load. Any higher and the unit will ‘fl ood’ when attempting to start.
LP TANK SIZING
Once above the minimum acceptable size, the size of L.P. tank used will generally depend on how long you want the unit to run without refi lling. The tank sizes shown below are the smallest recommended tank sizes based on the outside temperature. Keep in mind the colder it gets the slower L.P. will vaporize.
This is the reason for the larger tanks at low temperature. Minimum sizing is not based on running time.
Temp f.
60 deg 30 deg 0 deg -20 deg
150 gal 250 gal 500 gal 1000 gal
CHANGING FUEL TYPES
These engine generator sets are designed to run on three different fuels; gasoline, natural gas or LP vapor. They may be easily changed from one fuel to another.
FROM GASOLINE TO LP/NG
1. With the engine running turn off the gasoline
fuel valve.
2. Run the engine until it runs out of fuel.
3. Remove the pipe plug from the demand regulator.
4. Install locally approved fl exible fuel line.
5. Connect the LP/NG vapor fuel line.
6. This unit have two different hose fi ttings on the top of the demand requlator. One is for
LP and one is for Natural Gas. Make sure the hose is attached to the proper fi tting.
7. Turn on the vapor fuel.
8. Start the engine.
9 . Apply the load to the generator.
3210-10
8
60706-237
FROM LP/NG TO GASOLINE
1. With the engine running turn off the LP/NG fuel supply.
2. Run the engine until it runs out of fuel.
Amp Hours: 15AH or greater. Follow the battery manufacturers recommendations for servicing and charging prior to use. Connect the battery to the electric start system using the cables provided.
mand regulator.
4. Reinstall the plastic plug in the regulator.
5. Check to be sure the gasoline fuel valve is off.
6. Fill the gasoline fuel tank.
7. Turn on the gasoline fuel valve.
8. Start the engine.
CAUTION: EQUIPMENT DAMAGE
These electric start engines are NEGATIVE
GROUND. Use extreme caution when connecting the battery. Connect the NEGATIVE battery terminal to
GROUND.
BATTERY INSTALLATION
This engine generator set is shipped with a battery tie down kit for customer installation. This kit consists of a battery tie down and hardware for installation of the customer supplied battery on the unit. If you intend to use the power plant’s electric start system, you will need to purchase and install a battery to operate it.
Units equipped with a recoil or rope start will operate satisfactorily on gasoline without a battery but stating on LP/NG requires electric start be used.
For your safety always connect the positive battery cable to the “bat+” terminal fi rst. Then connect the negative battery cable to the “bat-” terminal. Make sure all connections are clean and tight. Reverse the sequence when disconnecting, disconnect the negative cable fi rst. These engines produce enough direct current to keep a battery charged under normal operating conditions, but were not intended to be used as a battery charger.
WARNING: PERSONAL INJURY
Lead acid batteries produce explosive hydrogen gas when charging. Keep sparks, fl ames, and burning cigarettes away from the battery. Ventilate the area when charging or using the battery in an enclosed space. Lead acid batteries contain sulfuric acid, which causes severe burns. If acid contacts eyes, skin or clothing, fl ush well with water. For contact with eyes, get immediate medical attention.
BATTERY CHARGING
Units equipped with electric start have a small fl ywheel charger built into the engine fl ywheel assembly for recharging the starting battery. This fl ywheel charger generates a small AC current that passes through a diode assembly to produce a DC charging current of about 1 to 3 AMPS. This circuit is not designed to be used as a battery charging circuit to recharge dead batteries.
WARNING: EQUIPMENT DAMAGE
The battery positive (+) cable is shipped with a plastic protective cap. When starting manually, this protective cap must remain in place to avoid possible damage to the engine electrical system and/or generator end.
A 12-volt powersports (motorcycle/atv/snowmo-
bile) battery, BCI group 20 or 24HL rated at 300
CCA or larger is recommended for this electric start engine generator set. Maximum length: 8 1/8”,
Maximum width: 3 9/16”, Height range: 5 3/4” - 7”.
OPTIONAL DOLLY KIT
An optional dolly kit is available for this generator.
The dolly kit comes with instructions and parts list.
After installing the dolly kit, fi le the instructions and parts list in the back of this manual for future reference.
3210-10 9 60706-237
OIL ALERT SYSTEM
C
B
This WINCO generator is equipped standard with low oil shutdown systems. The Briggs and Stratton engine uses an oil pressure switch system. This low oil warning system will automatically stop the engine before the oil level reaches a critical danger point.
This feature is designed to prevent costly repairs and downtime.
CAUTION: EQUIPMENT DAMAGE
Allowing the engine to shutdown repeatedly on low oil level may cause excessive wear which can be cumulative.
INITIAL START UP
3. Pull out the choke (Ref “B”) to the full “on”
position.
4 Turn the key to the run position, Ref “C”
5. Pull the starter grip lightly until resistance is felt, then pull briskly.
6. When the engine starts, open the choke
gradually.
7. The engine should promptly come up to
The throttle control on these generators is preset and locked to operate at 3600 RPM (nominal) with no load speed set at 3690 RPM. Only a trained service technician should be allowed to adjust this speed setting.
NOTICE: ENGINE START LOCKOUT
NOTICE:
Do not allow the starter grip to snap back against the engine. Return it gently to prevent damage to the starter.
This unit will not start if it is low on oil. The lu- bricating oil level must be at the full mark before the engine will start and run.
ELECTRIC STARTING (Gasoline only)
BASIC OPERATION
MANUAL STARTING (Gasoline only)
Refer to the engine manual for additional starting, operating, and stopping instructions.
1. Check oil level. Refi ll as needed
If the engine is cold and stiff or if the battery is not fully charged, starting can be made easier by slowly hand cranking the engine through the compression stroke before pushing the starter switch. This permits the starter to gain momentum before the heavy load of the compression stroke occurs. This minimizes the drain on the battery and improves the possibility of starting under such adverse conditions. Always keep the battery charged, especially during cold weather operation.
2. Turn on the fuel supply, Ref “A
A
NOTE - There is a second fuel valve under the fuel tank that is used when removing the tank. This valve is normally left on.
1. Check oil level, refi ll as needed
2. Turn on the fuel supply. Ref “A”
3. Move the choke to the full “on” position. A warm engine will require less choking than a cold engine. Ref “B”
4. Rotate the key switch (Ref “C”) briefl y to the
START position. The starter life is improved by using shorter starting cycles with time to cool off between cranking cycles. Do not operate the starter more than 15 seconds during each minute. Repeat if necessary.
5. When the engine starts, open the choke
gradually.
6. The engine should promptly come up to
3210-10
10
60706-237
CAUTION: EQUIPMENT DAMAGE
STARTING HINTS
Never permit the choke to remain on after the engine has run for a short time. It is not necessary to choke the engine when it is warm. Avoid overchoking.
1. Cold weather a. Use the proper oil for the temperature expected.
b. Use fresh winter grade fuel. Winter grade
gasoline is blended to improve starting. Do not
use summer grade gasoline.
ELECTRIC STARTING LP/NG only)
When operating on LP or NG, you will have to always use the electric start to get the unit running.
Because of the engine vacuum need to activate the fuel system it is almost impossible to manual start the unit using LP or NG.
2. Hot weather a. Use the proper oil for the temperature expected.
b. Use only summer blended gasoline. Using gaso-
line left over from winter may cause the unit to
vapor lock.
STOPPING AND STORAGE
1. Check oil level, refi ll as needed.
2. Turn on the LP/NG fuel supply
3. NEVER USE THE CHOKE WHEN OPERATING
ON LP or NG.
B
C
4. Rotate the key switch (Ref “C”) briefl y to the
START position. The starter life is improved by using shorter starting cycles with time to cool off between cranking cycles. Do not operate the starter more than 15 seconds during each minute. Repeat if necessary.
5. When the engine starts, release the key switch, allowing it to return to the “on” position.
6. The engine should promptly come up to
1. Move the on/off switch to the “OFF” position.
2. Before extended storage (over 30 days) certain precautions must be taken to ensure the fuel doesn’t deteriorate and clog the fuel system.
Note: The use of a fuel additive, such as Briggs &
Stratton Advanced Fuel Treatment & Stabilizer or an equivalent will minimize the formation of gum deposits during storage. The additive may be added to gasoline in the engines fuel tank or to gasoline in a storage container.
a. Add the fuel stabilizer to the fuel in the tank and run the unit for 2 minutes to circulate the stabilizer throughout the fuel system. b. If you choose to remove the remaining fuel from the fuel tank, it must be drained into an approved
container.
c. Start the engine and allow it to run until all the fuel in the carburetor and the fuel lines has been used up and the engine stops.
Note: Running the engine to use up the fuel in the lines and carburetor will still leave a small amount of fuel in the carburetor. It is best for extended storage to treat the fuel before draining.
d. While the engine is warm, drain the oil and refi ll with fresh oil.
e Clean dirt and chaff from cylinder, cylinder head fi ns, blower housing, screen and muffl er areas.
f. Store in a clean and dry area.
3210-10 11 60706-237
OPERATING SPEED
The engine-generator must be run at the correct speed in order to produce the proper electrical voltage and frequency.
CAUTION: EQUIPMENT DAMAGE
D
The output voltage should be checked to insure the generator is working properly prior to connecting a load to the generator. Failure to do so could result in damage to equipment plugged into the unit and possible injury to the individual.
All engines have a tendency to slow down when a load is applied. When the electrical load is connected to the generator, the engine is more heavily loaded, and as a result the speed drops slightly. This slight decrease in speed, together with the voltage drop within the generator itself, results in a slightly lower voltage when the generator is loaded to its full capacity than when running no load. The slight variation in speed also affects the frequency of the output current. This frequency variation has no appreciable effect in the operation of motors, lights and most appliances. However, electronic equipment and clocks will be affected if correct RPM is not maintained. See
Load vs. Output chart.
Although individual units and models vary slightly, the normal voltage and frequency of the engine-generator described in this manual are approximately as follows, under varying loads:
CAUTION: EQUIPMENT DAMAGE
SPEED ADJUSTMENTS SHOULD ONLY BE
MADE BY A QUALIFIED SERVICE TECH.
Whenever making any speed adjustments, check the unit with a voltmeter and a frequency meter or tachometer and be sure the voltage and speed are correct.
Lower voltage may damage both the generator and any load connected to it. Running the engine at excessively high speeds results in high voltage, which may signifi cantly shorten the life of appliances being used.
Output voltage should be checked periodically to ensure continued proper operation of the generating plant and appliances. If the generator is not equipped with a voltmeter, it can be checked with a portable meter.
Generator
Load
None
Half
Full
LOAD VS. OUTPUT
Speed
(RPM)
Frequency
(Hz)
3690
3600
3510
61.5
60.0
58.5
Voltage
125V
120V
115V
The speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency. For normal usage, the speed setting should not be changed. If the generator is being run continuously on a very light load, it is often advisable to lower the operating speed slightly.
Reference “D” below is the speed adjustment for this engine.
CONNECTING THE LOADS
APPLYING THE LOADS
Allow the engine to warm up for two or three minutes before applying any load. This will allow the engine to reach normal operating temperature and oil to circulate throughout the engine. A short warm-up time will permit the engine to work more effi ciently when the load is applied and will reduce the wear in the engine, extending its life.
Receptacles have been provided to allow loads to be connected to the generator. The loads should be added one at a time. If a large motor is being started; or multiple motors are being started, they should be started individually and the largest should be started fi rst.
3210-10
12
60706-237
CAUTION: EQUIPMENT OVERLOAD
Keep the generator load within the generator and receptacle nameplate rating. Overloading may cause damage to the generator and/or the loads .
Most electric tools and appliances will have the voltage and amperage requirements on their individual nameplates. When in doubt, consult the manufacturer or a local electrician. The nameplate amperage rating for electric motors can be misleading. See “Starting
Electric Motors” in Unit Capabilities (page 4).
WIRING
Plug your tools such as drills, saws, blowers, sump pump and other items to be powered directly into the generator receptacles. Before plugging in all the tools and cord sets, recheck the rating of the generator set. Be sure it can handle the intended load and is compatible with the voltage, phase, and current ratings. ‘Hard Wiring’ this unit directly into a home or a temporary construction site electrical system is NOT A SIMPLE DO-IT-YOURSELF JOB.
For your safety, all wiring must be done by a qualifi ed electrician and conform to the National Electric
Code and comply with all state and local codes and regulations. Check with local authorities before proceeding.
These engine-generator sets are inherently self regulating based on engine speed. The engine governor will automatically adjust itself to the load. No harm to the generator will result if it is operated with no load connected. Proper utilization of the receptacles located on the control panel is necessary to prevent damage to either the receptacles or the generator.
The generator is a limited source of electrical power, therefore, pay special attention to the receptacle and generator ratings. The nameplate rating can be obtained through a single receptacle as long as the receptacle amperage rating is not exceeded.
GROUNDING
WARNING: PERSONAL DANGER
A fully isolated, double pole double throw manual transfer switch must be installed any time a generator is being connected to an existing distribution system.
1. These engine generator sets are designed for portable use. Receptacles are provided on the control panel to permit 120 volt portable appliances and tools to be plugged directly into them. Please note that the 4-wire 120/240 volt receptacle on these units are designed to power both 120 or 240 volt loads. The plug for this receptacle can be wired for either 120 volt, 240 volt, or a combination of 120 and
240 volt loads depending on how the plug is wired.
All units must be grounded. Drive a 3/4 or 1” copper pipe or rod into the ground close to the engine-generator set. The pipe must penetrate moist earth. Connect an approved ground clamp to the pipe. Run a no. 10 Awg wire from clamp to the generator ground lug on the receptacle panel. Do not connect to a water pipe or to a ground used by a radio system.
The engine-generators covered in this manual were designed primarily for portable use. If you are connecting into a building wiring system that is already grounded using the 14-60 4 wire plug, you do not have to ground the unit.
WARNING: PERSONAL DANGER
A 4-wire receptacle (two hot, one ground, and one neutral) has been provided on the control panel for use in temporary power applications requiring
120/240 volt power. Consult a licensed electrician for wiring the TemPower plug and connecting it as temporary service. To connect these units directly to an un-powered, isolated construction site TemPower panel, have your electrician connect to the control panel using a 120/240 volt, 4-wire twist-lock plug
(L14-30P).
DO NOT OPERATE THIS GENERATOR INDOORS.
The unit should be stored in a warm dry location.
During a power outage, move the unit outdoors to a
fl at dry location such as a driveway or sidewalk.
2. If the generator set is be connected to an existing distribution system, a fully isolated manual transfer switch must be installed. The transfer switch prevents damage to the generator and other circuit components if main line power is restored while the generator is connected. Installing a transfer switch also permits the use of normal fusing.
3210-10 13 60706-237
3. Many homes and construction sites are wired for at least 60 to 100 Amp entrance service, much greater than the capacity of this portable generator. When installing the generator at these sites, a secondary emergency distribution panel may have to be installed, such as the Emergency Transfer/Service (ET/S) system available through your
WINCO dealer. The emergency distribution panel must be installed by a licensed electrician according to all applicable codes. The electrician will move the critical circuits to be powered during the outage to the emergency panel. Keep in mind only a limited amount of amperage is available from the generator set. Some circuit breakers may still have to be turned off to prevent an overload on the generator during the initial start up. See the nameplate on your generator for the amperage capabilities of your unit.
If major engine service or repair is required, contact an authorized engine service center. The manufacturer of these engines has established an excellent world-wide engine service organization. Engine service is very likely available from a nearby authorized dealer or distributor. Check the yellow pages of your local telephone directory under “Engines-Gasoline” for the closest engine repair center or ask the dealer from whom you purchased the power plant.
1. Change the oil after the fi rst 5 hours of operation
C
B
C
CAUTION: EQUIPMENT DAMAGE
Failure to properly limit and balance the load applied to the generator will cause the generator to produce low voltage and may damage the engine generator set. It may also cause severe damage to the loads connected to the generator at that time.
Improper loading of the generator set constitutes abuse and will not be covered by warranty.
and yearly or 100 hours thereafter under normal operating conditions. Change engine oil every 50 hours of operation if the engine is operated under heavy load, or in high ambient temperatures.
a. Start the engine and warm it up, stop the engine and remove the spark plug wire to prevent it from accidently being started.
b. Remove oil drain plug at base of the engine
(Ref “B”) and drain the oil into an approved container. Use a 3/8” drive socket extension.
ENGINE CARE
Maintenance Chart
First 5 Hours x Change oil
Every 8 Hours or Daily x
Check engine oil level x Clean area around muffler and controls
Every 100 Hours or Annually x Clean or change air filter * x
Clean pre-cleaner (if equipped) * x Change engine oil and filter x Replace spark plug x Check muffler and spark arrester
Every 250 Hours or Annually x Check valve clearance. Adjust if necessary.
Every 400 Hours or Annually x Change air filter x
Replace fuel filter x Clean air cooling system * x Clean oil cooler fins *
* In dusty conditions or when airborne debris is present, clean more often.
properly.
d. Before you install the new oil fi lter, lightly lubri- cate the oil fi lter gasket with fresh clean oil.
e. Install the oil fi lter by hand until the gasket contacts the oil fi lter adapter, then tighten the oil fi lter 1/2 to 3/4 turns.
f. Replace oil drain plug.
Refer to the table on page 5 for the proper grade of oil based on your operating
temperature.
NOTE: This engine requires 46 to 48 ounces of oil if it is completely drained. Use caution when refi lling the engine as some residual oil may have remained in the engine. Always use the dipstick when fi lling the engine with oil to prevent overfi lling.
I. Start the engine up and warm it up.
J. After warming up the engine, recheck the oil level and refi ll as necessary to bring it to the proper level. See page 5 for proper oil level.
3210-10
14
60706-237
2. Checking the Oil Level: The oil level must always be checked before the engine is started. Take care to remove any dirt or debris from around the oil fi ll plug before removing. Be sure the oil level is maintained. Fill to the “FULL” mark on the dipstick.
3. Dual Element Air Filter: Clean and or replace foam pre-cleaner and air fi lter annually or every 100 hours. Service more often under dusty conditions.
WARNING: EQUIPMENT DAMAGE
Never start or run the engine with the air fi lter removed
4. Spark Plug: Replace annually or every 100 hours of operation. Always replace with the same spark plug that came in the engine and check gap before installing. Spark plug gap is 0.030”. Poor spark will also occur if spark plug wire does not fi t fi rmly on spark plug. If this happens, reform the terminal to fi t fi rmly on spark plug tip.
5. Carbon Canister: Designed to collect, store, and dispose of fuel vapors created in the fuel tank / fuel system. The canister should last the life of the unit as long as it stays dry.
B
GENERATOR CARE
Proper care and maintenance of the generator is necessary to ensure a long trouble free life.
F
E
D
G
A 1. Exercising The Generator - The generator should be operated every three to four weeks. It should be operated for a period of time suffi cient to warm the unit up and to dry out any moisture that has accumulated in the windings. If left, this moisture can cause corrosion in the winding. Frequent operation of the engine generator set will also insure that the set is operating properly should it be needed in an emergency.
2. Generator Maintenance - Any major generator service, including the installation or replacement of parts, should be performed only by a qualifi ed electrical service technician. USE ONLY FACTORY
APPROVED REPAIR PARTS.
a. Loosen snaps (Ref “A”) and remove cover. b. Remove the nut (Ref “D”) and the retainer. c. Remove the air fi lter. (Ref “F”) d. Remove the pre-cleaner (Ref “G”) from the air fi lter.
e. To loosen debris, gently tap the air fi lter on a hard surface. If the air fi lter is excessively dirty, replace with a new fi lter.
Notice: Do not use pressurized air or solvents to clean the fi lter. Pressurized air can damage the fi lter and solvents will dissolve the fi lter.
f. Wash the pre-cleaner in liquid detergent and water. Then allow it to thoroughly air dry.
DO NOT oil the pre-cleaner.
g. Install foam pre-cleaner to the air fi lter.
h. Install the air fi lter and secure with retainer and
nut
I Install and secure the cover.
a. Bearing - The bearing used in these generators is a heavy duty double sealed ball bearing.
They require no maintenance or lubrication.
b. Receptacles - Quality receptacles have been utilized. If a receptacle should become cracked or otherwise damaged, replace it. Using dam- aged or cracked receptacles can be both dan- gerous to the operator and destructive to the
equipment.
3210-10 15 60706-237
CLEANING
Remove dirt and debris with a cloth or brush. DO
NOT use high pressure spray to clean either the engine or the generator. This high pressure spray could contaminate the fuel system and the generator components.
1. Keep the air inlet screen on both the engine and generator free of any dirt or debris to insure proper cooling. At least yearly, remove the blower housing on the engine and clean the chaff and dirt out of the engine cooling fi ns and fl ywheel. Clean more often if necessary. Failure to keep these areas clean may cause overheating and permanent damage to the unit.
No output voltage *Short in load (disconnect).
*Tripped or defective circuit
breaker.
*Broken or loose wire.
receptacle.
*No generator).
stator.
*Defective capacitor.
*Shorted diodes on rotor.
*GFCI
———————————————————————
GENERATOR SPECIFICATIONS
2. Periodically clean muffl er area to remove all grass, dirt and combustible debris to prevent a fi re.
3. On engine muffl ers equipped with spark arresters, the spark arrester must be removed every 50 hours for cleaning and inspection. Replace if damaged
Generator manufacturer
Generator model number
Part number
Rotor resistance
Stator resistance
Cap winding resistance
Capacitors
Capacitor part number
MECC Alte Spa
S20W-110
16346-006
5.22 Ohms
0.210 Ohms
0.87 Ohms
16346-312
TROUBLESHOOTING
ENGINE SPECIFICATIONS
PROBLEM (SYMPTOMS) POSSIBLE
CAUSES
———————————————————————
Won’t Start *Low Oil Level.
*Fouled
*Out
*Start switch in Off position.
*Fuel valve turn off.
*Plugged
———————————————————————
Voltage too low *Engine speed is too low.
overloaded.
stator.
*Defective
Capacitor.
———————————————————————
Circuit Breaker *Defective load.
Load.
———————————————————————
Voltage too high *Engine speed is too high.
———————————————————————
Generator *Overloaded.
overheating *Insuffi cient ventilation.
———————————————————————
Engine manufacturer
Engine model number
Type & Code
Briggs & Stratton
305447
0003-G1
491055
394018
272490
492932
491056
Spark plug gap
Armature air gap
0.030 in
0.008 - 0.012 in
Intake valve clearance 0.004 - 0.006 in
Exhaust valve clearance 0.004 - 0.006 in
Oil capacity 46 - 48 oz.
3210-10
16
60706-237
3210-10 17 60706-237
24 MONTH LIMITED WARRANTY
WINCO, Inc. warrants to the original purchaser for 24 months that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO’s written instructions.
* NOTE: Units used in prime power are warranted for 120 day Units that are resold are not covered under this warranty. Any further warranty whether expressed or implied, rest solely with the reseller.
WINCO, Inc. warrants to the ultimate purchaser and each subsequent purchaser that the evaporative emission control system is designed, built, and equipped so as to conform at the time of original sale to the then current evaporative emission requirements. In addition it is free from defects in materials and workmanship that may keep it from meeting these requirements. This evaporative emission control system is warranted for two years. If an evaporative emission related part on your equipment is defective, the part will be repaired or replaced by WINCO Inc.
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO’s option, material found to be defective in material or workmanship under normal use and service will be repaired or replaced. For warranty service, return the product within 24 months from the date of purchase, transportation charges prepaid, to your nearest WINCO
Authorized Service Center or to WINCO Inc. at Le Center, Minnesota.
THERE IS NO OTHER EXPRESS WARRANTY.
To the extent permitted by law, any and all warranties, including those of merchantability and fi tness for a particular purpose, are limited to 24 months from date of purchase. In no event is WINCO liable for incidental or consequential damages.
Note: Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply in every instance. This warranty gives you specifi c legal rights which may vary from state to state.
WINCO reserves the right to change or improve it products without incurring any obligations to make such changes or improvements on products purchased previously.
EXCLUSIONS:
WINCO does not warrant Engines. Engines are covered exclusively by the warranties of their respective manufacturers.
WINCO does not warrant Batteries, or Other Component Parts that are warranted by their respective manufacturers.
WINCO does not warrant modifi cations or alterations which were not made by WINCO Inc.
WINCO does not warrant products which have been subjected to misuse and/or negligence or have been involved in an accident.
This warranty does not include travel time, mileage or labor for removal or reinstallation of a WINCO product from its application.
3210-10 60706-237
18
CALIFORNIA EVAPORATIVE EMISSION CONTROL
WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board is pleased to explain the evaporative emission control system’s warranty on your model 2013 or later generator. In California, new equipment that uses small off-road engines must be designed, built, and equipped to meet the State’s stringent anti-smog standards. WINCO must warrant the evaporative emission control system on your generator for the period listed below provided there has been no abuse, neglect or improper maintenance of your equipment.
Your evaporative emission control system may include parts such as: carburetor, fuel tanks, fuel lines, fuel caps, valves, canisters, fi lters, vapor hoses, clamps, connectors and other associated components.
MANUFACTURER’S WARRANTY COVERAGE
The evaporative emission control system is warranted for two years. If any evaporative emission related parts on your equipment are defective, the parts will be repaired or replaced by WINCO.
OWNER’S WARRANTY RESPONSIBILITIES:
As the generator owner, you are responsible for performance of the required maintenance listed in your owner’s manuals. WINCO recommends that you retain all receipts covering maintenance on your generator, but WINCO cannot deny warranty solely for lack of receipts.
As the generator owner, you should be aware that WINCO may deny you warranty coverage if your generator or a part has failed due to abuse, neglect, or improper maintenance or unapproved modifi cations.
You are responsible for presenting your generator to a WINCO service center as soon as the problem exists. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days. If you have a question regarding your warranty coverage, you should contact WINCO at 507-357-6831.
3210-10 19 60706-237
3210-10
20
WINCO INC.
225 S. CORDOVA AVE.
LE CENTER, MN 56057
507-357-6821
SERVICE DEPT.
507-357-6831 www.wincogen.com
60706-237