6201-WA-ASCII to 6201-WA-DFNT
ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Setup Guide
9/6/2007
Please Read This Notice
Successful application of this module requires a reasonable working knowledge of the ProLinx
Module, its connected devices, and the application in which the combination is to be used. For this reason, it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions.
This manual is provided to assist the user. Every attempt has been made to assure that the information provided is accurate and a true reflection of the product's installation requirements. In order to assure a complete understanding of the operation of the product, the user should read all applicable documentation on the operation of the connected devices.
Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product.
Reproduction of the contents of this manual, in whole or in part, without written permission from
ProSoft Technology is prohibited.
Information in this manual is subject to change without notice and does not represent a commitment on the part of ProSoft Technology Improvements and/or changes in this manual or the product may be made at any time. These changes will be made periodically to correct technical inaccuracies or typographical errors.
Important Installation Instructions
Power, input and output wiring must be in accordance with Class I, Division 2 wiring methods – Article 501-4 (b) of the National Electrical Code, NFPA 70 and in accordance with the authority having jurisdiction. The following warnings must be heeded:
A
B
C
D
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIV. 2;
WARNING – EXPLOSION HAZARD – WHEN IN HAZARDOUS
LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING
MODULES, and
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE
AREA IS KNOWN TO BE NONHAZARDOUS.
"THIS DEVICE SHALL BE POWERED BY CLASS 2 OUTPUTS ONLY."
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about the product, documentation or support, please write or call us.
ProSoft Technology
1675 Chester Avenue, Fourth Floor
Bakersfield, CA 93301
+1 (661) 716-5100
+1 (661) 716-5101 (Fax) http://www.prosoft-technology.com
Copyright © ProSoft Technology, Inc. 2000 - 2007. All Rights Reserved.
6201-WA-ASCII Setup Guide
9/6/2007
PSFT.ASCII.PLX.UM.Thursday, September 06, 2007
ProSoft Technology ®, ProLinx ®, inRAx ®, ProTalk® and RadioLinx ® are Registered Trademarks of ProSoft Technology, Inc.
High Speed Wireless ASCII Generic Serial Gateway
Contents
PLEASE READ THIS NOTICE .............................................................................................................................. 2
Important Installation Instructions ...................................................................................................................... 2
Your Feedback Please ...................................................................................................................................... 3
CONTENTS ........................................................................................................................................................... 5
1 INTRODUCTION........................................................................................................................................... 7
1.1
Before You Begin..................................................................................................................................... 7
1.2
Using the Sample ProSoft Configuration Builder Files............................................................................. 8
1.3
About Transmission Casts ......................................................................................................................10
2 LOAD THE REQUIRED SOFTWARE..........................................................................................................11
2.1
Install ProSoft Configuration Builder (PCB) ............................................................................................11
2.2
Copy the Sample Application File ...........................................................................................................12
3 CONFIGURE THE ASCII MODULE.............................................................................................................13
3.1
Complete the ProSoft Configuration Builder Sections ............................................................................14
3.1.1
Radio Ethernet Configuration ........................................................................................................14
3.1.2
Radio Configuration.......................................................................................................................15
3.1.3
Radio SNTP Client ........................................................................................................................16
3.1.4
Radio PWP Exchanges .................................................................................................................17
3.1.5
Radio PWP Multicast Group List ...................................................................................................20
3.1.6
ASCII Port 0 ..................................................................................................................................20
3.1.7
Common........................................................................................................................................21
3.2
Save and Download the Configuration File to the 6201-WA-ASCII ........................................................21
4 CONFIGURE THE DFNT MODULE.............................................................................................................23
4.1
Complete the ProSoft Configuration Builder Sections ............................................................................24
4.1.1
Radio Ethernet Configuration ........................................................................................................24
4.1.2
Radio Configuration.......................................................................................................................25
4.1.3
Radio SNTP Client ........................................................................................................................26
4.1.4
Radio PWP Exchanges .................................................................................................................27
4.1.5
Radio PWP Multicast Group List ...................................................................................................29
4.1.6
DFNT Client 0................................................................................................................................29
4.1.7
DFNT Client 0 Commands SLC5002 Address Fields....................................................................30
4.1.8
CommonNet ..................................................................................................................................31
4.2
Save and Download the Configuration File to the 6201-WA-DFNT ........................................................32
5 VERIFY DATA EXCHANGE ........................................................................................................................35
6 DEFAULT MODULE CONFIGURATION ASSIGNMENTS..........................................................................37
6.1
IP Addresses ..........................................................................................................................................37
6.2
WATTCP Parameters .............................................................................................................................37
7 PROSOFT TECHNOLOGY, INC., SUPPORT, SERVICE & WARRANTY ..................................................39
7.1
How to Contact Us: Sales and Support...................................................................................................40
7.2
Return Material Authorization (RMA) Policies and Conditions ................................................................41
7.2.1
All Product Returns .......................................................................................................................41
7.3
Procedures for Return of Units Under Warranty .....................................................................................41
7.4
Procedures for Return of Units Out of Warranty .....................................................................................42
7.4.1
Un-repairable Units .......................................................................................................................42
7.5
LIMITED WARRANTY ............................................................................................................................43
7.5.1
What Is Covered By This Warranty ...............................................................................................43
7.5.2
What Is Not Covered By This Warranty.........................................................................................44
7.5.3
DISCLAIMER REGARDING HIGH RISK ACTIVITIES ..................................................................45
7.5.4
DISCLAIMER OF ALL OTHER WARRANTIES.............................................................................45
7.5.5
LIMITATION OF REMEDIES**......................................................................................................45
ProSoft Technology, Inc.
September 6, 2007
Page 5 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Contents
7.5.6
Time Limit for Bringing Suit ...........................................................................................................45
7.5.7
No Other Warranties .....................................................................................................................46
7.5.8
Intellectual Property ......................................................................................................................46
7.5.9
Additional Restrictions Relating To Software And Other Intellectual Property ..............................46
7.5.10
Allocation of risks ..........................................................................................................................47
7.5.11
Controlling Law and Severability ...................................................................................................47
INDEX ...................................................................................................................................................................49
Page 6 of 50 ProSoft Technology, Inc.
September 6, 2007
High Speed Wireless ASCII Generic Serial Gateway
1 Introduction
In This Chapter
¾ Before
¾ Using the Sample ProSoft Configuration Builder Files ............. 8
¾ About
This manual is intended to guide you through the setup and configuration of your
ProLinx Wireless ASCII and DFNT devices.
Important: This Setup Guide shows you how to set up a simple wireless network between a 6201-WA-ASCII module and a 6201-WA-DFNT module. This guide should be used as a starting point only.
In all likelihood, the requirements of your particular application will involve additional configuration and development. For detailed information on the ASCII, DFNT, and
ProLinx Wireless protocols, please refer to the following Driver Manuals, on your
ProSoft Solutions CD-ROM:
ASCII Manual
DFNT Manual
PWP Driver Manual
For general information on installing and configuring ProLinx modules, please refer to the ProLinx Reference Guide, also on your ProSoft Solutions CD-ROM.
1.1 Before You Begin
The insert included with your modules describes a sample SINGLE-REMOTE SITE SAMPLE application.
It is important that you read through the insert and perform any required steps.
Setting up the ASCII and DFNT network is relatively simple using the sample files included on the ProLinx
Solutions CD. The flow diagram illustrates the highlevel steps used to configure each module.
The default configuration file contains separate configurations for each module. You can use the sample files to get started or you can create the configuration files from scratch. The easiest way to begin is to use the sample configurations. Once you understand how they are created, setting up your network is easy.
Load Required Software to
Your PC or Laptop
Configure the local
6201-WA-ASCII
Configure the remote
6201-WA-DFNT
ProSoft Technology, Inc.
September 6, 2007
Page 7 of 50
6201-WA-ASCII module ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
1.2 Using the Sample ProSoft Configuration Builder Files
Introduction
The sample application uses one 6201-WA-ASCII module and one 6201-WA-
DFNT module to establish wireless communications between an ASCII
Communication Device (Terminal, Scanner, Printer) at a local site and a PLC located at a remote site. The WA-DFNT module is configured as a Client. The following diagram illustrates this application.
Remote Site
Local Site
12
00 W or ds ord s
12
00 W
24
00
Ch ar ac te rs ac te rs
24
00
Char
6201- WA- DFNT
( Client)
EtherNet/IP
Ethernet
ControlLogix
( Server)
ASCII
CommunicationsDevice
Local
6201- WA- ASCII
In this example, the following is assumed:
That the ASCII Device and the Remote PLC are located far enough from each other that a wired connection would be impractical
The application uses one 6201-WA-ASCII module and one 6201-WA-DFNT module to establish communication between the ASCII Device such as a data terminal with modifications to the ASCII module configuration file. Scanners and printers may also be connected.
The module's radio communication parameters are preset and configured to pass up to 1200 words/2400 characters in either direction
You can use this guide in one of two ways. First, you can use it as a learning tool to see how the PCB files make the sample application work. You can also follow along with the example and modify the configuration files as you go along.
The logic in the following flow chart needs to be implemented in the processor to which the 6201-WA-DFNT is wired. This will enable the 6201-WA-ASCII module to properly exchange data with the Serial Port connected ASCII Device.
In the example below, the 6201-WA-6201 Module has been configured to transmit and receive data using "Intercharacter Delay Timeout". This means that when the users set amount of milliseconds expires without arrival of additional characters into serial port buffer, the module will transfer the arrived data from the serial port buffer into the module's main memory. The data in the main memory is available to the radio section of the module for wireless exchange.
Page 8 of 50 ProSoft Technology, Inc.
September 6, 2007
High Speed Wireless ASCII Generic Serial Gateway
The gray boxes to the left of the chart give an explanation of logical events in each of the chart symbols.
Legend: (For details refer to Generic ASCII Serial Communications
Module Driver Manual. Sections 2.1.1 and 2.1.2)
RW[X]=V; Received(PLC Input) Word offset position in the array. V is Value.
TW[X]=V; Transmit(PLC Output) Word offset position in the array. V is Value.
RA[0]; Received ASCII data array with 0 as starting position. 127 Words max.
TA[0]; Transmit ASCII data array with 0 as starting position. 127 words max.
START
Monitor for change in the value of the
Received Word array at index 0.
NO
Transfer ASCII data from Received Word array starting at index 3 to ASCII data array starting at index 0. Maximum data array size is 127 words (255 bytes).
Transmit Word outputs at Index:
[0] New incremented integer value.
[1] Character count from last Received Word .
[2] Inter Character spacing in Milliseconds .
[3] Byte quantity of data to transmit.
Transfer ASCII data from Transmit ASCII data array starting at index 0 to transmit Word array starting at index 4. Maximum data array size is
127 words (255 bytes).
TW[0]=V( new)
TW[1]=V(RW[2])
TW[2]=V( mSec)
TW[3]=V( Byte Qty)
YES
ProSoft Technology, Inc.
September 6, 2007
Page 9 of 50
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
1.3 About Transmission Casts
Introduction
The sample uses a UNICAST transmission type. UNICAST means that you set up Produce and Consume Commands that transfer or receive data between two individual modules. For example, a Produce command can specify that this data is only produced to one particular consuming module based on the consuming modules IP address.
In addition to UNICAST, you also have the flexibility of using MULTICAST (data sent to multiple modules in a MULTICAST Group List but only picked up by the module within that list with a Consume command that has the matching
Exchange ID and the IP address of the module multicasting the command), and
BROADCAST which sends data out to all modules. With BROADCAST, each module receives the transmission whether it be two modules or 50 modules.
Each module receiving the BROADCAST has to check every message to determine if it is intended for the module or not. This can decrease performance times since the module may be checking hundreds of messages that are not intended for it.
Use MULTICAST to limit the modules that should receive the message. For example, five modules may be part of a MULTICAST Group, yet there may be 15 modules on the network. Only five of the 15 modules on the network will be configured to handle certain types of commands while the remaining 10 that are not in the MULTICAST group will ignore the messages not intended for them.
Page 10 of 50 ProSoft Technology, Inc.
September 6, 2007
Load the Required Software 6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
2 Load the Required Software
In This Chapter
¾ Install ProSoft Configuration Builder (PCB)............................ 11
¾ Copy the Sample Application File .......................................... 12
There is one application (ProSoft Configuration Builder) and one file (PPF) that you must download from the ProLinx Solutions CD to your PC or LAPTOP whether you are using the sample configuration or are modifying the configuration to suit the needs of your application. This section describes how to get everything you need loaded to your PC. You must perform these steps regardless of whether you are configuring your modules now or just reading about the sample applications.
2.1 Install ProSoft Configuration Builder (PCB)
ProSoft Configuration Builder helps you configure the module for your application.
1 Insert the ProLinx Solutions CD into the CD-ROM drive on your PC or
LAPTOP. The ProLinx Solutions splash page appears:
2 Select Install Configuration Tool.
3 Follow the prompts to install ProSoft Configuration Builder to your hard disk.
ProSoft Technology, Inc.
September 6, 2007
Page 11 of 50
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
2.2 Copy the Sample Application File
Load the Required Software
4 From the ProLinx Solutions splash screen, click Product
Documentation .
5 Choose Samples → Wireless.
6 Copy the PROLINX WIRELESS SAMPLE.PPF file to a location on your PC or LAPTOP.
Page 12 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the ASCII Module 6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
In This Chapter
¾ Complete the ProSoft Configuration Builder Sections............ 14
¾ Save and Download the Configuration File to the 6201-WA-ASCII
............................................................................................... 21
Based on the sample application, the remote Server is connected to a 6201-WA-
DFNT configured as a Client. The goal here is to begin to establish communications between the 6201-WA-ASCII and the 6201-WA-DFNT modules. The default configuration is designed to pass 1200 words between each module. Each module is configured separately.
Configuration is accomplished using ProSoft Configuration Builder (PCB). The default configuration file is PROLINX WIRELESS SAMPLE.PPF.
1 Start PCB.
2
Select File → Open.
3
Navigate to the location where you copied the PROLINX WIRELESS
SAMPLE.PPF
file and select this file.
4
Expand the ASCII Serial to EtherNetIP folder.
5 Expand the 6201-WA-ASCII module selection.
ProSoft Technology, Inc.
September 6, 2007
Page 13 of 50
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the ASCII Module
3.1 Complete the ProSoft Configuration Builder Sections
3.1.1 Radio Ethernet Configuration
Double-click the icon.
Every ASCII module is set up with the defaults shown in the example. You may have to modify values such as the Radio Default Gateway, the Network Name
(SSID), and the Station Name to suit the needs of your network. The Station
Name may be modified when using more than one ASCII module.
Note: All modules must have the same Subnet Mask, Default Gateway, and Network
Name (SSID) if they are all located on the same network. Only the fourth octet in the
Radio_IP address must be different for each module. Please refer to Default Module
Configuration Assignments for a list of pre-assigned ProSoft product IP addresses.
The PWP Driver Manual located on the ProLinx Solutions CD contains a description of the remaining parameters. If you are making changes, be sure to save your changes before moving on to the next step.
Page 14 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the ASCII Module
Expand the Wireless Configuration section
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway and double-click on the icon.
The default Signal LED 1 through 4 parameter values are fixed and cannot be modified. If you need to change the values for the remaining parameters in this dialog box, make sure to save your changes before moving on to the next step.
As you select each parameter, the help text area in the lower right area of the dialog box displays information to help you make your selections.
RTS Threshold
60 to 2347
RTS/CTS handshake threshold byte count. Less than 60 will interfere with control packets.
ProSoft Technology, Inc.
September 6, 2007
Page 15 of 50
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the ASCII Module
Transmit Rate
This parameter defines the data rate(s) for transmission of directed messages.
Possible values are outlined in the following table.
4
5
6
7
Value Definition
1
2
3
Fixed 1 Mbit (1)
Fixed 2 Mbit (2)
Auto fallback high (11, 5.5, 2, 1)
Fixed medium rate (5.5)
Fixed high rate (11)
Auto fallback standard (2, 1)
Auto fallback medium (5.5, 2, 1)
Important: For Multicast mode, use transmit rates of 1 or 2 for best results.
WEP Key Rollover
Yes or No
WEP (Wireless Encryption Protocol) is an encryption method that allows devices on a wireless network to transmit data securely.
This parameter interacts with the WATTCP file parameter "Enable Encryption" and the values for WEP Keys 1 through 4. When the WEP Key Rollover parameter is enabled, the module will randomly change the WEP key.
3.1.3 Radio SNTP Client
Double-click on the icon.
Page 16 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the ASCII Module 6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
This section is used to synchronize the time using a centralized atomic clock.
This feature is only usable if your modules are communicating through an access point such as a RadioLinx Industrial Hotspot. The values in this window should be left with the default values. As you select each parameter, the help window on the screen displays information to help you make your selections. The PWP
Driver Manual located on the ProLinx Solutions CD describes each parameter in detail.
3.1.4 Radio PWP Exchanges
Double-click on the icon.
This is the area where you set up data exchange between the modules.
Communication is accomplished using Producer and Consumer commands.
Using these commands, you specify the IP address of the receiving (Consumer) and sending (Producer) module as well as the database locations to produce data and receive data.
In the sample application, the modules are set up to send 1200 words back and forth between the 6201-WA-ASCII and the 6201-WA-DFNT modules. Each module contains a database and both modules are capable of producing or consuming data. This is accomplished using ProSoft Wireless Protocol (PWP) commands. In the sample, we are sending all 1200 words and receiving 1200 words back. We are actually sending only 50 words of data from and to the user's main and remote sites.
Two Produce commands and two Consume commands are used to make this happen. Each command sends (or receives) 600 words of data. The following example shows both produce commands from the sample application.
1 3 4 5 2 6
ProSoft Technology, Inc.
September 6, 2007
Page 17 of 50
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Producer Command Narrative for the First Command (line 1):
1 Send data using Unicast Mode
2
Send the data to IP Address 172.16.10.150.
3
Send 600 registers beginning at DB Register 0.
4
Do not set a Swap Code.
5 Send the data every 100 milliseconds.
6
Use an Exchange ID of 1000.
Producer Command Narrative for the Second Command (line 2):
1 Send data using Unicast Mode
2 Send the data to IP Address 172.16.10.150.
3 Send 600 registers beginning at DB Register 600.
4 Do not set a Swap Code.
5 Send the data every 100 milliseconds.
6 Use an Exchange ID of 1001.
Configure the ASCII Module
Note: IP Address 172.16.10.150 is the 6201-WA-DFNT module.
The Consume commands perform the same function for data coming into the module from the DFNT once configured.
1 3 4 5 2 6
Consumer Command Narrative for the First Command (line 3):
1 Consume data using Unicast Mode.
2 Consume this data only from IP Address 172.16.10.150.
3 Consume 600 words and store them beginning at DB register 1200.
4 Do not use a Swap Code.
5 Consume data within 400 milliseconds.
6 Only consume data with an Exchange ID of 1002.
Consumer Command Narrative for the Second Command (line 4):
1 Consume data using Unicast Mode.
2 Consume this data only from IP Address 172.16.10.150.
3 Consume 600 words and store them beginning at DB register 1800.
4 Do not use a Swap Code.
5 Consume data within 400 milliseconds.
6 Only consume data with an Exchange ID of 1003.
Note: The sample configuration file also shows an additional Produce and Consume command. These commands are designed to pass a time value from the DFNT to the
ACSII module and then loop back from the ASCII to the DFNT. These commands are included for testing and radio communication verification purposes only and are not necessarily required for your application.
Page 18 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the ASCII Module 6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
How it's Done
1 Double-click on the icon.
2 Click the Add button. ProSoft Configuration Builder adds a default row.
3 Click the Edit button. The Edit window appears.
Define each element of the command by selecting the element, then select or enter the desired values.
4 Click OK when done.
Note : In addition to the help on the dialog, the PWP Driver Manual located on the
ProLinx Solutions CD provides descriptions of each parameter.
ProSoft Technology, Inc.
September 6, 2007
Page 19 of 50
6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the ASCII Module
This section does not contain any data for the sample application. The sample application uses UNICAST transmission and therefore there is no need to enter
IPs of other devices in this section. The ProLinx PWP Driver Manual describes this section in detail.
3.1.6 ASCII Port 0
The sample configuration file requires that this module be configured for matching serial port communication with the ASCII Communication Device.
Expand the ASCII Port 0 section.
Double-click on the icon.
The remaining parameters are set to ensure that the ASCII module can communicate with the PLC. Refer to the ASCII Driver Manual located on the
ProLinx solutions CD for detailed information on each of these parameters.
Page 20 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the ASCII Module
3.1.7 Common
Expand the Common section.
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Double-click on the icon.
This section does not require any editing for the sample application. Refer to the
Modbus Plus Driver Manual located on the ProLinx Solutions CD for information on setting up data mapping for your application
3.2 Save and Download the Configuration File to the 6201-WA-ASCII
1
Connect your PC or LAPTOP to the DEBUG port of the 6201-WA-ASCII module. Apply power to the module if you have not already done so.
2 Choose File → Save As… and save the .PPF file to a location on your hard drive.
ProSoft Technology, Inc.
September 6, 2007
Page 21 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the ASCII Module
3 Right-click on 6201-WA-ASCII and select Download from PC to Device.
4 Select the appropriate COM port and click the Download button.
The download is complete when the OK button becomes active. When the download is completed, click the OK button.
Page 22 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the DFNT Module 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
4 Configure the DFNT Module
In This Chapter
¾ Complete the ProSoft Configuration Builder Sections............ 24
¾ Save and Download the Configuration File to the 6201-WA-DFNT
............................................................................................... 32
Based on the sample application, the remote Server is connected to a 6201-WA-
DFNT configured as a Client. The goal here is to begin to establish communications between the 6201-WA-ASCII and 6201-WA-DFNT modules.
The default configuration is designed to pass 1200 words between each module.
Each module is configured separately.
Configuration is accomplished using ProSoft Configuration Builder (PCB). The default configuration file is PROLINX WIRELESS SAMPLE.PPF.
1 Start PCB.
2
Select File → Open.
3
Navigate to the location where you copied the PROLINX WIRELESS
SAMPLE.PPF
file and select this file.
4
Expand the ASCII Serial to EtherNetIP folder.
5 Expand the 6201-WA-DFNT module selection.
ProSoft Technology, Inc.
September 6, 2007
Page 23 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the DFNT Module
4.1 Complete the ProSoft Configuration Builder Sections
4.1.1 Radio Ethernet Configuration
Double click on the selection.
Every EtherNet/IP module is set up with the defaults shown in the example. You may have to modify values such as the Radio Default Gateway, the Network
Name (SSID), and the Station Name to suit the needs of your network. The
Station Name may be modified when using more than one EtherNet/IP module.
Note: All modules must have the same Subnet Mask, Default Gateway, and Network
Name (SSID) if they are all located on the same network. Only the fourth octet in the
Radio_IP address must be different for each module. Please refer to Default Module
Configuration Assignments for a list of pre-assigned ProSoft product IP addresses.
The PWP Driver Manual located on the ProLinx Solutions CD contains a description of the remaining parameters. If you are making changes, be sure to save your changes before moving on to the next step.
Page 24 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the DFNT Module
Expand the Wireless Configuration section
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway and double-click on the icon.
The default Signal LED 1 through 4 parameter values are fixed and cannot be modified. If you need to change the values for the remaining parameters in this dialog box, make sure to save your changes before moving on to the next step.
As you select each parameter, the help text area in the lower right area of the dialog box displays information to help you make your selections.
Transmit Rate
This parameter defines the data rate(s) for transmission of directed messages.
Possible values are outlined in the following table.
Value Definition
1 Fixed 1 Mbit (1)
4
5
2
3
Fixed 2 Mbit (2)
Auto fallback high (11, 5.5, 2, 1)
Fixed medium rate (5.5)
Fixed high rate (11)
ProSoft Technology, Inc.
September 6, 2007
Page 25 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Value Definition
6
7
Auto fallback standard (2, 1)
Auto fallback medium (5.5, 2, 1)
Configure the DFNT Module
Important: For Multicast mode, use transmit rates of 1 or 2 for best results.
RTS Threshold
60 to 2347
RTS/CTS handshake threshold byte count. Less than 60 will interfere with control packets.
WEP Key Rollover
Yes or No
WEP (Wireless Encryption Protocol) is an encryption method that allows devices on a wireless network to transmit data securely.
This parameter interacts with the WATTCP file parameter "Enable Encryption" and the values for WEP Keys 1 through 4. When the WEP Key Rollover parameter is enabled, the module will randomly change the WEP key.
4.1.3 Radio SNTP Client
Double-click on the icon.
Page 26 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the DFNT Module 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
This section is used to synchronize the time using a centralized atomic clock.
This feature is only usable if your modules are communicating through an access point such as a RadioLinx Industrial Hotspot. The values in this window should be left with the default values. As you select each parameter, the help window on the screen displays information to help you make your selections. The PWP
Driver Manual located on the ProLinx Solutions CD describes each parameter in detail.
4.1.4 Radio PWP Exchanges
Double-click on the icon.
This is the area where you set up data exchange between the ASCII and the
DFNT modules. Communication is accomplished using Producer and Consumer commands. Using these commands, you specify the IP address of the receiving
(Consumer) and sending (Producer) module as well as the database locations to produce data and receive data.
In the sample application, the modules are set up to send 1200 words back and forth between the 6201-WA-ASCII and the 6201-WA-DFNT module. Each module contains a database and both modules are capable of producing or consuming data. This is accomplished using ProSoft Wireless Protocol (PWP) commands. In the sample, we are sending all 1200 words and receiving 1200 words back. We are actually sending only 50 words of data from and to the user's main and remote sites.
Two Produce commands and two Consume commands are used to make this happen. Each command sends (or receives) 600 words of data. The following example shows both produce commands from the sample application.
1 3 4 5 2 6
ProSoft Technology, Inc.
September 6, 2007
Page 27 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the DFNT Module
1 Producer Command Narrative for the First Command (line 3):
2 Send data using Unicast Mode
3 Send the data to IP Address 172.16.10.160.
4 Send 600 registers beginning at DB Register 1200.
5 Do not set a Swap Code.
6 Send the data every 100 milliseconds.
7 Use an Exchange ID of 1002.
Producer Command Narrative for the Second Command (line 4):
1 Send data using Unicast Mode
2 Send the data to IP Address 172.16.10.160.
3 Send 600 registers beginning at DB Register 1800.
4 Do not set a Swap Code.
5 Send the data every 100 milliseconds.
6 Use an Exchange ID of 1003.
Note: IP Address 172.16.10.160 is the 6201-WA-ASCII module.
The Consume commands receive data coming into the module from the DFNT once configured.
1 3 4 5 2 6
Consumer Command Narrative for the First Command (line 1):
1 Consume data using Unicast Mode.
2
Consume this data only from IP Address 172.16.10.160.
3
Consume 600 words and store them beginning at DB register 0.
4
Do not use a Swap Code.
5
Consume data within 400 milliseconds.
6 Only consume data with an Exchange ID of 1000.
Consumer Command Narrative for the Second Command (line 2):
1 Consume data using Unicast Mode.
2 Consume this data only from IP Address 172.16.10.160.
3 Consume 600 words and store them beginning at DB register 600.
4 Do not use a Swap Code.
5 Consume data within 400 milliseconds.
6 Only consume data with an Exchange ID of 1001.
Page 28 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the DFNT Module 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Both the ASCII and the DFNT have corresponding Produce and Consume commands. The following diagram illustrates the sample application:
6201-WA-ASCII (Primary Client) PWP Exchanges
6201-WA-DFNT (Remote Client)
Note: The sample configuration file also shows an additional Produce and Consume command. These commands are designed to pass a time value from the DFNT to the
ASCII module and then loop back from the ASCII to the DFNT. These commands are included for testing and radio communication verification purposes only and are not necessarily required for your application.
This section does not contain any data for the sample application. The sample application uses UNICAST transmission and therefore there is no need to enter
IPs of other devices in this section. The ProLinx PWP Driver Manual describes this section in detail.
4.1.6 DFNT Client 0
The sample configuration file requires that the module currently being configured be configured as a Client. This is done in the DFNT Client 0 section.
1 Double-click on the icon.
ProSoft Technology, Inc.
September 6, 2007
Page 29 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
2 Double-click on the icon.
Configure the DFNT Module
The remaining parameters are set to ensure that the DFNT module can communicate with the PLC. Refer to the DFNT Driver Manual located on the
ProLinx solutions CD for detailed information on each of these parameters.
4.1.7 DFNT Client 0 Commands SLC5002 Address Fields
Double-click on the icon.
Note: For command lines 1 and 2 to function properly with the ControlLogix processor, the menu item "Logic/Map PLC/SLC Messages…" in the RSLogix 5000 application, must have the "File Number" field in the "PLC 2, 3, 5/SLC Mapping" dialog box linked/associated with a user specified "Tag Name" Field Tag.
Page 30 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the DFNT Module 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Line 1
In this command line, the DFNT continuously writes 50 words as fast as possible from the DFNT internal address 0 into the PLC slot 0, IP address 105.102.0.224.
Line 2
In this command line, the DFNT continuously reads 50 words as fast as possible from PCL slot location 0, IP address 105.102.0.224 using the function code Prot
Typed Read, and stores the data into the DFNT internal address 0.
4.1.8 CommonNet
Expand the CommonNet section.
Double-click on the icon.
This section does not require any editing for the sample application. Refer to the
DFNT Driver Manual located on the ProLinx Solutions CD for information on setting up data mapping for your application.
ProSoft Technology, Inc.
September 6, 2007
Page 31 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Double-click on the icon.
Configure the DFNT Module
This section does not require any editing for the sample application. Refer to the
DFNT Driver Manual located on the ProLinx Solutions CD for information on setting up data mapping for your application.
4.2 Save and Download the Configuration File to the 6201-WA-DFNT
1
Ensure that your PC or LAPTOP is still connected to the DEBUG port of the
6201-WA-DFNT module. Apply power to the module if you have not already done so.
2 Choose File → Save As… and save the .PPF file to a location on your hard drive.
Page 32 of 50 ProSoft Technology, Inc.
September 6, 2007
Configure the DFNT Module 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
3 Right-click on 6201-WA-DFCM_slc and select Download from PC to
Device .
4 Select the appropriate COM port and click the Download button.
The download is complete when the OK button becomes active. When the download is complete, click OK.
ProSoft Technology, Inc.
September 6, 2007
Page 33 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Configure the DFNT Module
Page 34 of 50 ProSoft Technology, Inc.
September 6, 2007
Verify Data Exchange 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Run Diagnostics Using ProSoft Configuration Builder
1 Move the connector from the Debug Port on the DFNT module and plug it into the Debug Port of the ASCII module. Ensure that power is applied to both modules.
2
Right-click on 6201-WA-ASCII and select Diagnostics.
ProSoft Technology, Inc.
September 6, 2007
Page 35 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
3 Select the appropriate Com port
Verify Data Exchange
4 Press "?" to display the Diagnostic menu.
5 Press "D" to display the Database menu.
6 Press "3" to show database registers beginning at 3000.
7 Press the "S" key to refresh the database values. The circled values in the example should change each time you press the "S" key indicating that data is being passed between modules. If these values do not change, contact
ProSoft Technical Support.
The data shown represents clock values originating from the 6201-WA-ASCII module. The values are stored in 5 registers beginning with register 3000. The clock values are being passed wirelessly to the 6201-WA-DFNT. The 6201-WA-
DFNT module is taking this data and passing it back to the 6201-WA-ASCII module and placing it into 5 registers beginning at register 3005.
Page 36 of 50 ProSoft Technology, Inc.
September 6, 2007
Default Module Configuration Assignments 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
6 Default Module Configuration Assignments
In This Chapter
¾ IP
¾ WATTCP
IP Address are assigned in ranges to each of the WA modules. This information is used in the Radio Ethernet Configuration section of the configuration file. The following table shows the range assignments and the default value preconfigured in the module:
Module IP Address Range Address Set in the Module (Default)
The purpose for reserving up to 10 IP addresses per module is for addressing and establishing radio communications between modules of the same model number (for example 6201-WA-ASCII to 6201-WA-ASCII).
The following default parameters are applicable to all WA modules:
Radio_Subnet_Mask : 255.255.255.0
Radio_Default_Gateway: 172.16.10.1
ProSoft Technology, Inc.
September 6, 2007
Page 37 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Default Module Configuration Assignments
Page 38 of 50 ProSoft Technology, Inc.
September 6, 2007
ProSoft Technology, Inc., Support, Service & Warranty 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
7 ProSoft Technology, Inc., Support, Service &
Warranty
In This Chapter
¾ How to Contact Us: Sales and Support.................................. 40
¾ Return Material Authorization (RMA) Policies and Conditions41
¾ Procedures for Return of Units Under Warranty..................... 41
¾ Procedures for Return of Units Out of Warranty..................... 42
¾ LIMITED
Be sure and read the full Warranty that can be found on our web site at www.prosoft-technology.com
for details and other terms and conditions. The content in this summary is subject to change without notice. The content is current at date of publication.
ProSoft Technology, Inc. strives to provide meaningful support to its customers.
Should any questions or problems arise, please feel free to contact us at:
Internet
Web Site: http://www.prosoft-technology.com/support
E-mail address: [email protected]
Those of us at ProSoft Technology, Inc. want to provide the best and quickest support possible, so before calling please have the following information available. You may wish to fax this information to us prior to calling.
1 Product Version Number
2 System architecture
3 Network details
In the case of hardware, we will also need the following information:
1 Module configuration and contents of file
2 Module Operation
3 Configuration/Debug status information
4 LED patterns
5 Information about the processor and user data files as viewed through the development software and LED patterns on the processor
6 Details about the networked devices interfaced, if any
For technical support calls within the United States, an after-hours answering system allows pager access to one of our qualified technical and/or application support engineers at any time to answer your questions.
ProSoft Technology, Inc.
September 6, 2007
Page 39 of 50
6201-WA-ASCII ♦ ProLinx Wireless ProSoft Technology, Inc., Support, Service & Warranty
High Speed Wireless ASCII Generic Serial Gateway
7.1 How to Contact Us: Sales and Support
All ProSoft Technology Products are backed with full technical support. Contact our worldwide Technical Support team and Customer Service representatives directly by phone or email:
USA / Latin America (excluding Brasil) (Office in California)
+1(661) 716-5100
+1(661) 716-5101 (Fax)
1675 Chester Avenue, 4th Floor
Bakersfield, California 93301
U.S.A.
+1.661.716.5100, [email protected]
Languages spoken include: English, Spanish
Asia Pacific (office in Malaysia)
+603.7724.2080
+603.7724.2090 (Fax)
C210, Damansara Intan,
1 Jalan SS20/27, 47400 Petaling Jaya
Selangor, Malaysia
+603.7724.2080, [email protected]
Languages spoken include: Chinese, Japanese, English
China Pacific (office in China)
+86.21.64518356 x 8011
+86.21.64756957 (Fax)
4/F, No. 16 Hongcao Road
Shanghai, China 200233
China
+86.21.64518356 x 8011, [email protected]
Languages spoken include: Chinese, English
Europe / Middle East / Africa (office in Toulouse, France)
+33 (0) 5.34.36.87.20
+33 (0) 5.61.78.40.52 (Fax)
Zone d'activité de Font Grasse
17, rue des Briquetiers
F-31700 Blagnac
France
+33 (0) 5.34.36.87.20. support. [email protected]
Languages spoken include: French, English
Brasil (office in Sao Paulo)
+55-11-5084-5178
+55-11-5083-3776 (Fax)
Rua Vergueiro, 2949 - sala 182 - Edifício Vergueiro Work Center
Vila Mariana - São Paulo
Cep: 04101-300 – Brasil
+55-11-5084-5178, [email protected]
Languages spoken include: Portuguese, English
Page 40 of 50 ProSoft Technology, Inc.
September 6, 2007
ProSoft Technology, Inc., Support, Service & Warranty 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
7.2 Return Material Authorization (RMA) Policies and Conditions
The following RMA Policies and Conditions apply to any returned product. These
RMA Policies are subject to change by ProSoft without notice. For warranty information, see Section C below entitled "Limited Warranty". In the event of any inconsistency between the RMA Policies and the Warranty, the Warranty shall govern.
7.2.1 All Product Returns
1 In order to return a Product for repair, exchange or otherwise, the Customer must obtain a Returned Material Authorization (RMA) number from ProSoft and comply with ProSoft shipping instructions.
2 In the event that the Customer experiences a problem with the Product for any reason, Customer should contact ProSoft Technical Support at one of the telephone numbers listed above in Section A. A Technical Support Engineer will request several tests in an attempt to isolate the problem. If after these tests are completed, the Product is found to be the source of the problem,
ProSoft will issue an RMA.
3 All returned Products must be shipped freight prepaid, in the original shipping container or equivalent, to the location specified by ProSoft, and be accompanied by proof of purchase. The RMA number is to be prominently marked on the outside of the shipping box. Customer agrees to insure the
Product or assume the risk of loss or damage in transit. Products shipped to
ProSoft without an RMA number will be returned to the Customer, freight collect. Contact ProSoft Technical Support for further information.
4 Out of warranty returns are not allowed on RadioLinx accessories such as antennas, cables, and brackets.
The following policy applies for Non-Warranty Credit Returns:
A
B
10% Restocking Fee if Factory Seal is not broken
20% Restocking Fee if Factory Seal is broken
ProSoft retains the right, in its absolute and sole discretion, to reject any nonwarranty returns for credit if the return is not requested within three (3) months after shipment of the Product to Customer, if the Customer fails to comply with
ProSoft's shipping instructions, or if the Customer fails to return the Product to
ProSoft within six (6) months after Product was originally shipped.
7.3 Procedures for Return of Units Under Warranty
1 A Technical Support Engineer must pre-approve all product returns.
2 Module is repaired or replaced after a Return Material Authorization Number is entered and a replacement order is generated.
3 Credit for the warranted item is issued within 10 business days after receipt of product and evaluation of the defect has been performed by ProSoft. The credit will only be issued provided the product is returned with a valid Return
Material Authorization Number and in accordance with ProSoft's shipping instructions.
ProSoft Technology, Inc.
September 6, 2007
Page 41 of 50
6201-WA-ASCII ♦ ProLinx Wireless ProSoft Technology, Inc., Support, Service & Warranty
High Speed Wireless ASCII Generic Serial Gateway a) If no defect is found, a credit is issued. b) If a defect is found and is determined to be customer generated or if the defect is otherwise not covered by ProSoft's Warranty, or if the module is not repairable, a credit is not issued and payment of the replacement module is due.
7.4 Procedures for Return of Units Out of Warranty
1 Customer sends unit in for evaluation.
2 If no defect is found, Customer will be charged the equivalent of US $100 plus shipping, duties and taxes that may apply. A new Purchase Order will be required for this evaluation fee.
If the unit is repaired the charge to the Customer will be 30%* of the list price plus any shipping, duties and taxes that may apply. A new Purchase Order will be required for a product repair.
3 For an immediate exchange, a new module may be purchased and sent to
Customer while repair work is being performed. Credit for purchase of the new module will be issued when the new module is returned in accordance with ProSoft's shipping instructions and subject to ProSoft's policy on nonwarranty returns. This is in addition to charges for repair of the old module and any associated charges to Customer.
4 If, upon contacting ProSoft Customer Service, the Customer is informed that unit is believed to be unrepairable, the Customer may choose to send unit in for evaluation to determine if the repair can be made. Customer will pay shipping, duties and taxes that may apply. If unit cannot be repaired, the
Customer may purchase a new unit.
3150-All
3750
3600-All
3700
3170-All
3250
1560 can be repaired, if defect is the power supply
1550 can be repaired, if defect is the power supply
3350
3300
1500-All
* 30% of list price is an estimated repair cost only. The actual cost of repairs will be determined when the module is received by ProSoft and evaluated for needed repairs.
Page 42 of 50 ProSoft Technology, Inc.
September 6, 2007
ProSoft Technology, Inc., Support, Service & Warranty 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
Purchasing Warranty Extension
As detailed below in ProSoft's Warranty, the standard Warranty Period is one year (or in the case of RadioLinx modules, three years) from the date of delivery.
The Warranty Period may be extended for an additional charge, as follows:
Additional 1 year = 10% of list price
Additional 2 years = 20% of list price
Additional 3 years = 30% of list price
This Limited Warranty ("Warranty") governs all sales of hardware, software and other products (collectively, "Product") manufactured and/or offered for sale by
ProSoft, and all related services provided by ProSoft, including maintenance, repair, warranty exchange, and service programs (collectively, "Services"). By purchasing or using the Product or Services, the individual or entity purchasing or using the Product or Services ("Customer") agrees to all of the terms and provisions (collectively, the "Terms") of this Limited Warranty. All sales of software or other intellectual property are, in addition, subject to any license agreement accompanying such software or other intellectual property.
7.5.1 What Is Covered By This Warranty
A
B
Warranty On New Products : ProSoft warrants, to the original purchaser only, that the Product that is the subject of the sale will (1) conform to and perform in accordance with published specifications prepared, approved, and issued by ProSoft, and (2) will be free from defects in material or workmanship; provided these warranties only cover Product that is sold as new. This Warranty expires one year (or in the case of RadioLinx modules, three years) from the date of shipment (the "Warranty Period").
If the Customer discovers within the Warranty Period a failure of the
Product to conform to specifications, or a defect in material or workmanship of the Product, the Customer must promptly notify ProSoft by fax, email or telephone. In no event may that notification be received by
ProSoft later than 15 months (or in the case of RadioLinx modules, 39 months) from the date of delivery. Within a reasonable time after notification, ProSoft will correct any failure of the Product to conform to specifications or any defect in material or workmanship of the Product, with either new or used replacement parts. Such repair, including both parts and labor, will be performed at ProSoft's expense. All warranty service will be performed at service centers designated by ProSoft. If
ProSoft is unable to repair the Product to conform to this Warranty after a reasonable number of attempts, ProSoft will provide, at its option, one of the following: a replacement product, a full refund of the purchase price or a credit in the amount of the purchase price. All replaced product and parts become the property of ProSoft. These remedies are the Customer's only remedies for breach of warranty.
Warranty On Services : Material and labor used by ProSoft to repair a verified malfunction or defect are warranted on the terms specified above
ProSoft Technology, Inc.
September 6, 2007
Page 43 of 50
6201-WA-ASCII ♦ ProLinx Wireless ProSoft Technology, Inc., Support, Service & Warranty
High Speed Wireless ASCII Generic Serial Gateway
C for new Product, provided said warranty will be for the period remaining on the original new equipment warranty or, if the original warranty is no longer in effect, for a period of 90 days from the date of repair.
The Warranty Period for RadioLinx accessories (such as antennas, cables, brackets, etc.) are the same as for RadioLinx modules, that is, three years from the date of shipment.
7.5.2 What Is Not Covered By This Warranty
A
B
C
D
ProSoft makes no representation or warranty, expressed or implied, that the operation of software purchased from ProSoft will be uninterrupted or error free or that the functions contained in the software will meet or satisfy the purchaser's intended use or requirements; the Customer assumes complete responsibility for decisions made or actions taken based on information obtained using ProSoft software.
With the exception of RadioLinx accessories referenced in paragraph 1(c) this Warranty does not cover any product, components, or parts not manufactured by ProSoft.
This Warranty also does not cover the failure of the Product to perform specified functions, or any other non-conformance, defects, losses or damages caused by or attributable to any of the following: (i) shipping; (ii) improper installation or other failure of Customer to adhere to ProSoft's specifications or instructions; (iii) unauthorized repair or maintenance; (iv) attachments, equipment, options, parts, software, or user-created programming (including, but not limited to, programs developed with any
IEC 61131-3 programming languages, or "C") not furnished by ProSoft; (v) use of the Product for purposes other than those for which it was designed; (vi) any other abuse, misapplication, neglect or misuse by the
Customer; (vii) accident, improper testing or causes external to the
Product such as, but not limited to, exposure to extremes of temperature or humidity, power failure or power surges outside of the limits indicated on the product specifications; or (viii) disasters such as fire, flood, earthquake, wind or lightning.
The information in this Agreement is subject to change without notice.
ProSoft shall not be liable for technical or editorial errors or omissions made herein; nor for incidental or consequential damages resulting from the furnishing, performance or use of this material. The user guides included with your original product purchased by you from ProSoft, contains information protected by copyright. No part of the guide may be duplicated or reproduced in any form without prior written consent from
ProSoft.
Page 44 of 50 ProSoft Technology, Inc.
September 6, 2007
ProSoft Technology, Inc., Support, Service & Warranty 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
7.5.3 DISCLAIMER REGARDING HIGH RISK ACTIVITIES
PRODUCT MANUFACTURED OR SUPPLIED BY PROSOFT IS NOT FAULT
TOLERANT AND IS NOT DESIGNED, MANUFACTURED OR INTENDED FOR
USE IN HAZARDOUS ENVIRONMENTS REQUIRING FAIL-SAFE
PERFORMANCE (INCLUDING, WITHOUT LIMITATION, THE OPERATION OF
NUCLEAR FACILITIES, AIRCRAFT NAVIGATION OF COMMUNICATION
SYSTEMS, AIR TRAFFIC CONTROL, DIRECT LIFE SUPPORT MACHINES
OR WEAPONS SYSTEMS), IN WHICH THE FAILURE OF THE PRODUCT
COULD LEAD DIRECTLY OR INDIRECTLY TO DEATH, PERSONAL INJURY,
OR SEVERE PHYSICAL OR ENVIRONMENTAL DAMAGE (COLLECTIVELY,
"HIGH RISK ACTIVITIES"). PROSOFT SPECIFICALLY DISCLAIMS ANY
EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR HIGH RISK
ACTIVITIES.
7.5.4 DISCLAIMER OF ALL OTHER WARRANTIES
THE WARRANTIES SET FORTH IN PARAGRAPH 1 ABOVE ARE IN LIEU OF
ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT
LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE.
7.5.5 LIMITATION OF REMEDIES**
IN NO EVENT WILL PROSOFT (OR ITS DEALER) BE LIABLE FOR ANY
SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES BASED ON
BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE, STRICT
TORT, OR ANY OTHER LEGAL THEORY. DAMAGES THAT PROSOFT AND
ITS DEALER WILL NOT BE RESPONSIBLE FOR INCLUDE, BUT ARE NOT
LIMITED TO: LOSS OF PROFITS; LOSS OF SAVINGS OR REVENUE; LOSS
OF USE OF THE PRODUCT OR ANY ASSOCIATED EQUIPMENT; LOSS OF
DATA; COST OF CAPITAL; COST OF ANY SUBSTITUTE EQUIPMENT,
FACILITIES, OR SERVICES; DOWNTIME; THE CLAIMS OF THIRD PARTIES,
INCLUDING CUSTOMERS OF THE PURCHASER; AND INJURY TO
PROPERTY.
** Some areas do not allow time limitations on an implied warranty, or allow the exclusion or limitation of incidental or consequential damages. In such areas the above limitations may not apply. This Warranty gives you specific legal rights, and you may also have other rights which vary from place to place.
7.5.6 Time Limit for Bringing Suit
Any action for breach of warranty must be commenced within 15 months (or in the case of RadioLinx modules, 39 months) following shipment of the Product.
ProSoft Technology, Inc.
September 6, 2007
Page 45 of 50
6201-WA-ASCII ♦ ProLinx Wireless ProSoft Technology, Inc., Support, Service & Warranty
High Speed Wireless ASCII Generic Serial Gateway
Unless modified in writing and signed by both parties, this Warranty is understood to be the complete and exclusive agreement between the parties, suspending all oral or written prior agreements and all other communications between the parties relating to the subject matter of this Warranty, including statements made by salesperson. No employee of ProSoft or any other party is authorized to make any warranty in addition to those made in this Warranty. The
Customer is warned, therefore, to check this Warranty carefully to see that it correctly reflects those terms that are important to the Customer.
B
C
D
A
E
Any documentation included with Product purchased from ProSoft is protected by copyright and may not be photocopied or reproduced in any form without prior written consent from ProSoft.
ProSoft's technical specifications and documentation that are included with the Product are subject to editing and modification without notice.
Transfer of title shall not operate to convey to Customer any right to make, or have made, any Product supplied by ProSoft.
Customer is granted no right or license to use any software or other intellectual property in any manner or for any purpose not expressly permitted by any license agreement accompanying such software or other intellectual property.
Customer agrees that it shall not, and shall not authorize others to, copy software provided by ProSoft (except as expressly permitted in any license agreement accompanying such software); transfer software to a third party separately from the Product; modify, alter, translate, decode, decompile, disassemble, reverse-engineer or otherwise attempt to derive the source code of the software or create derivative works based on the software; export the software or underlying technology in contravention of applicable US and international export laws and regulations; or use the software other than as authorized in connection with use of Product.
Intellectual Property
In addition to complying with the Terms of this Warranty, Customers purchasing software or other intellectual property shall comply with any license agreement accompanying such software or other intellectual property. Failure to do so may void this Warranty with respect to such software and/or other intellectual property.
Page 46 of 50 ProSoft Technology, Inc.
September 6, 2007
ProSoft Technology, Inc., Support, Service & Warranty 6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
7.5.10 Allocation of risks
This Warranty allocates the risk of product failure between ProSoft and the
Customer. This allocation is recognized by both parties and is reflected in the price of the goods. The Customer acknowledges that it has read this Warranty, understands it, and is bound by its Terms.
7.5.11 Controlling Law and Severability
This Warranty shall be governed by and construed in accordance with the laws of the United States and the domestic laws of the State of California, without reference to its conflicts of law provisions. If for any reason a court of competent jurisdiction finds any provisions of this Warranty, or a portion thereof, to be unenforceable, that provision shall be enforced to the maximum extent permissible and the remainder of this Warranty shall remain in full force and effect. Any cause of action with respect to the Product or Services must be instituted in a court of competent jurisdiction in the State of California.
ProSoft Technology, Inc.
September 6, 2007
Page 47 of 50
6201-WA-ASCII ♦ ProLinx Wireless ProSoft Technology, Inc., Support, Service & Warranty
High Speed Wireless ASCII Generic Serial Gateway
Page 48 of 50 ProSoft Technology, Inc.
September 6, 2007
Index
A
About Transmission Casts • 10
Additional Restrictions Relating To Software
And Other Intellectual Property • 46
All Product Returns • 41
Allocation of risks • 47
ASCII Port 0 • 20
Before You Begin • 7
B
C
Common • 21
CommonNet • 31
Complete the ProSoft Configuration Builder
Sections • 14, 24
Configure the ASCII Module • 13
Configure the DFNT Module • 23
Controlling Law and Severability • 47
Copy the Sample Application File • 12
D
Default Module Configuration Assignments •
37
DFNT Client 0 • 29
DFNT Client 0 Commands SLC5002
Address Fields • 30
DISCLAIMER OF ALL OTHER
WARRANTIES • 45
DISCLAIMER REGARDING HIGH RISK
ACTIVITIES • 45
H
How it's Done • 19
How to Contact Us
Sales and Support • 40
I
Important Installation Instructions • 2
Install ProSoft Configuration Builder (PCB) •
11
Intellectual Property • 46
Introduction • 7
IP Addresses • 37
ProSoft Technology, Inc.
September 6, 2007
High Speed Wireless ASCII Generic Serial Gateway
L
LIMITATION OF REMEDIES** • 45
LIMITED WARRANTY • 43
Line 1 • 31
Line 2 • 31
Load the Required Software • 11
N
No Other Warranties • 46
P
Please Read This Notice • 2
Procedures for Return of Units Out of
Warranty • 42
Procedures for Return of Units Under
Warranty • 41
ProSoft Technology, Inc., Support, Service &
Warranty • 39
Purchasing Warranty Extension • 43
R
Radio Configuration • 15, 25
Radio Ethernet Configuration • 14, 24
Radio PWP Exchanges • 17, 27
Radio PWP Multicast Group List • 20, 29
Radio SNTP Client • 16, 26
Return Material Authorization (RMA) Policies and Conditions • 41
RTS Threshold • 15, 26
S
Save and Download the Configuration File to the 6201-WA-ASCII • 21
Save and Download the Configuration File to the 6201-WA-DFNT • 32
T
Time Limit for Bringing Suit • 45
Transmit Rate • 16, 25
U
Un-repairable Units • 42
Using the Sample ProSoft Configuration
Builder Files • 8
V
Verify Data Exchange • 35
Page 49 of 50
6201-WA-ASCII ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
W
WATTCP Parameters • 37
WEP Key Rollover • 16, 26
What Is Covered By This Warranty • 43
What Is Not Covered By This Warranty • 44
Y
Your Feedback Please • 3
Index
Page 50 of 50 ProSoft Technology, Inc.
September 6, 2007
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 PLEASE READ THIS NOTICE
- 2 Important Installation Instructions
- 3 Your Feedback Please
- 5 CONTENTS
- 7 INTRODUCTION
- 7 Before You Begin
- 8 Using the Sample ProSoft Configuration Builder Files
- 10 About Transmission Casts
- 11 LOAD THE REQUIRED SOFTWARE
- 11 Install ProSoft Configuration Builder (PCB)
- 12 Copy the Sample Application File
- 13 CONFIGURE THE ASCII MODULE
- 14 Complete the ProSoft Configuration Builder Sections
- 14 Radio Ethernet Configuration
- 15 Radio Configuration
- 16 Radio SNTP Client
- 17 Radio PWP Exchanges
- 20 Radio PWP Multicast Group List
- 20 ASCII Port
- 21 Common
- 21 Save and Download the Configuration File to the 6201-WA-ASCII
- 23 CONFIGURE THE DFNT MODULE
- 24 Complete the ProSoft Configuration Builder Sections
- 24 Radio Ethernet Configuration
- 25 Radio Configuration
- 26 Radio SNTP Client
- 27 Radio PWP Exchanges
- 29 Radio PWP Multicast Group List
- 29 DFNT Client
- 30 DFNT Client 0 Commands SLC5002 Address Fields
- 31 CommonNet
- 32 Save and Download the Configuration File to the 6201-WA-DFNT
- 35 VERIFY DATA EXCHANGE
- 37 DEFAULT MODULE CONFIGURATION ASSIGNMENTS
- 37 IP Addresses
- 37 WATTCP Parameters
- 39 PROSOFT TECHNOLOGY, INC., SUPPORT, SERVICE & WARRANTY
- 40 How to Contact Us: Sales and Support
- 41 Return Material Authorization (RMA) Policies and Conditions
- 41 All Product Returns
- 41 Procedures for Return of Units Under Warranty
- 42 Procedures for Return of Units Out of Warranty
- 42 Un-repairable Units
- 43 LIMITED WARRANTY
- 43 What Is Covered By This Warranty
- 44 What Is Not Covered By This Warranty
- 45 DISCLAIMER REGARDING HIGH RISK ACTIVITIES
- 45 DISCLAIMER OF ALL OTHER WARRANTIES
- 45 LIMITATION OF REMEDIES
- 45 Time Limit for Bringing Suit
- 46 No Other Warranties
- 46 Intellectual Property
- 46 Additional Restrictions Relating To Software And Other Intellectual Property
- 47 Allocation of risks
- 47 Controlling Law and Severability
- 49 INDEX