The PQube

.

Simply the best power monitor. Ever.

Power Standards Lab

PQube

®

AC Power Monitor

Embedded power quality and energy/carbon monitoring

Highlights

An entirely new idea: combine a hyper-accurate energy monitor with a world-class power quality monitor. Then squeeze it into a compact, low-cost package that doesn’t require any software at all.

Captures disruptive voltage disturbances every time they occur. Time-stamped pictures of the waveforms, and Excel ® -compatible CSV spreadsheet files.

Energy and peak metering, including kilowatt-hours, kVA, kVA-hours, true Power

Factor, peak amps, peak kVA, peak watts, unbalance, and a Carbon footprint meter that uses a patent-pending algorithm.

Tiny. Perfect for embedding in sensitive equipment – quickly reduces service costs and provides critical data for improving energy efficiency.

As easy to use as a digital camera – everything you need is stored on a standard plug-in SD card.

Made in USA. No software required. Very low cost.

Features

General: o Three-phase/single-phase voltage monitoring – standard worldwide voltage configurations up to 690V L-L (400V L-N), 50/60/400Hz nominal. o Auto power configuration (patent pending) – detects single-phase, phase-tophase, delta, wye, corner ground, and many others. Also auto-detects nominal voltage and nominal frequency. o One digital input, two additional ±60V analog input channels, one relay contact output, and two temperature-humidity channels. o 256 samples-per-cycle recording standard. o 4 gigabyte SD-card standard (can use up to 8GB cards). Typically records about

2 GB per year. o Full color organic LED display: 30+ languages, date/time setup, most recent events, meters, etc o DIN-rail or optional panel mount bracket o Power from 24-48VDC/24 VAC, or optional 100~240 VAC power supply. Built-in

Li-Ion UPS o Free individual NIST calibration certificate for every PQube. Download from www.PowerStandards.com

Power Quality monitoring: o Voltage dips, swells, and interruptions – waveforms and RMS graphs o Over-frequency and under-frequency events o 1-microsecond high-frequency impulse detection o Time-triggered snapshots o THD, TDD, Voltage unbalance, and current unbalance o Harmonics and Interharmonics – up to the 63 rd order for voltage and current o RMS Flicker – P inst

, P

ST

, P

LT o Detailed event recording, plus daily, weekly, monthly trends. Cumulative probability, histograms, and more

Energy monitoring: Just snap on a plug-in current module o Watts, VA, VAR’s, true Power Factor, Watt-hours, VA-hours o Carbon footprint meter. You can specify carbon values for various types of electric power, and the ratio of each type supplied by your electric company. Your PQube then measures the carbon footprint directly in kilograms! It even distinguishes between “generated” and

“avoided” CO

2.

o Peaks: single-cycle peak, 1-minute, and 15-minute averages o CT ratios support up to 50,000 amps. PT ratios support up to 6,900,000 volts. o Daily, weekly, monthly trends, Load duration curves and more.

No software required: o Spreadsheets: CSV Excel®-compatible files; events, trends, statistics o Pictures: Event and trend/statistics – dual-language graphs output directly from your

PQube in universal GIF format o PQDIF: the IEEE’s standard for power quality data files o Text, XML, and HTML summaries: perfect for interfacing with other programs

Easy data retrieval: o Easy access to all PQube graphs, spreadsheets, and PQDIF files - simply pop out SD card from front slot. No communications required. No restrictions from your IT department. o Open file formats: o Graphs in GIF format with dual language labels o Spreadsheets in CSV format o PQDIF format for events, trends, and statistics o Summaries in text, html (web), and XML (computer readable) formats o HTML (web browser) indexes make it easy to find files o With optional Ethernet plug-in module, you add: o Email – trends and statistics and events, straight from your PQube to your PC. Email is a great choice for locations where firewalls are an issue. Your PQube supports encrypted e-mail passwords, too, for greater compatibility with servers that require

MD5. o Web server built-in – easy viewing and downloading from anywhere in the world. o FTP server built-in – easy file transfer from anywhere in the world. o Modbus-TCP – meters can be read by thousands of programs o Connect to a cellular modem for wireless Ethernet access

Easy installation o Snap-together modules for Ethernet, current, optional power supply, and more o Direct connection to any world-wide voltage: 100V, 120V, 200V, 208V, 230V, 240V, 277V,

400V, 480V, 600V. 690V. o o

Direct connection to any world-wide frequency: 50 Hz, 60 Hz, 400 Hz, plus DC

DIN-rail mount or panel mount. Can snap into standard DIN circuit-breaker box with standard 45mm cutout, or use with optional panel-mount bracket. o Built-in UPS with automatically charged Li-Ion battery. Battery can be easily replaced without interrupting PQube monitoring

Complies with world-wide standards: o Safety: UL, TUV, ISA-82.02.01 (IEC 61010-1 MOD), CAN/CSA-C22.2 NO.61010-1, Japan Smark, GS o Immunity: IEC 61000-4-5 (6kV peak 100kHz surge), IEC 61000-4-4 (4kV peak EFT bursts),

IEC 61000-4-2 Level 1 and MIL-STD-883 (electrostatic discharges), IEC 61000-4-3 (radio frequency fields), IEC 61000-4-8 (magnetic fields) o Emissions: EN 55022 and CISPR 22, radiated and conducted RF emissions. o Accuracy: Full NIST-trace Certificate for every individual PQube.

www.PowerStandards.com

Applications

Industrial equipment o

Size and price are perfect for embedding in automated machinery o

Quickly pay for PQube with avoided service calls o

Track energy trends over time – detect developing leaks, failing motors, and more

Medical o

Perfect for embedding in MRI and CAT scanners. o

Detect power quality events that cause intermittent errors, imaging malfunctions. o

Provide energy monitoring: the first step in improving energy efficiency in medical facilities

Security scanning at airports o

World-wide necessity – must function perfectly with bad power o

Scanning errors can be catastrophic - embedded power quality monitoring is critical.

Power companies o

Monitor key accounts at the meter, and at the critical loads: was it your problem, or a facility problem? o

Lowest-cost system-wide monitoring – including PQDIF output files

Facility management companies o

Add value with power quality and energy monitoring o

PQube is the only monitoring system that doesn’t require network infrastructure – just install and get useful data right away

Military bases, government campuses, large facilities o

Allocate energy costs, and detect energy leaks o

Full carbon monitoring for green initiatives o

Start with no network; add e-mail later; then add full network support when needed

Data centers o

AC and DC monitoring, plus temperature and humidity o

Monitor input and output of power conditioning – demonstrate your improvements

Telecom o

3-phase and 1-phase AC monitoring, with simultaneous capture of disturbances on -48Vdc o

Trigger on AC disturbances, -48Vdc disturbances, or both o

Full daily, weekly, and monthly trends and statistics for proof of service

Researchers o

All data stored in open-format files (Excel®-compatible CSV files) – easy to write your own programs for analysis o

Voltage, current, and DC oscilloscope waveforms, with sophisticated triggering o

Daily, weekly, and monthly trends and statistics: voltage, current, frequency, power, temperature, humidity, and more

Green initiatives o

Direct reading of carbon emissions, using patent-pending algorithms o

Ultimate precision: 0.05% accuracy for sensitive energy savings measurements

Distributed generation - wind and solar o

Ultra-precise 3-phase AC measurements, including net power flow o

Ultra-precise frequency recording and disturbances for stability analysis o

Detect LVRT (voltage dip) faults – speeds up acceptance tests and payment o

Available 1500 Vdc and 600-amp DC sensors, simultaneous with builtin AC sensors, for inverter efficiency measurements, recording DC bus disturbances

Energy audits and Power Quality consulting o

Direct graph outputs (GIF format) that copy/paste into your reports – no software required o

Accumulated energy, peak energy, and daily/weekly/monthly trends and statistics for full understanding o

The most accurate, most flexible, easiest-to-use power recorder ever made for energy and power quality

Sample Files

www.PowerStandards.com

Optional Plug-in Modules

Current Sensing modules

• Up to five channels of current monitoring.

• Simple to set CT ratios in your PQube (up to 50 kiloAmps), with crest factor of

350%.

• Current waveforms, inrush current, and power flow (kW, kWh, kVA, kVAh, kVAR, kVARh, tPF)

• Measure unbalance, harmonics, and interharmonics for current

• Peak meters – peak amps, peak kVA, and peak watts. Single-cycle, 1-minute, and

15-minute peaks. Useful for sizing circuit breakers, UPS, and transformers.

• Carbon footprint meter – input your local electric power source information, and your PQube automatically measures your CO

2

footprint directly in kilograms

CT4 Current Sense module

• Just pass wires through openings in module (0.34in (8.6mm) maximum diameter)

• Part Number CT4-20A-00 for 20-amp nominal rating

• Part Number CT4-50A-00 for 50-amp nominal rating.

XCT4 Current Transformer Interface module

Connects directly to current transformer secondary wires – 1 or 5 amp

• Part Number XCT4-01A-00 for 1-amp nominal rating

• Part Number XCT4-05A-00 for 5-amp nominal rating

XCT5 Current Transformer Interface module

• Connects directly to voltage secondary wires of your CTs – 1, 5, or 10 volt.

• Part Number XCT5-0.333V-00 for 0.333-volt nominal rating (can be used with PSL current sensors – see web site for available models).

• Part Number XCT5-01V-00 for 1-volt nominal rating

• Part Number XCT5-05V-00 for 5-volt nominal rating

• Part Number XCT5-10V-00 for 10-volt nominal rating

ETH1 - Ethernet module

• Automatically sends you an e-mail whenever a disturbance occurs, complete with picture and Excel

®

compatible attachments

• Built in web server – see status of your PQube and look at event and trend recordings

• Update your firmware and reset your PQube via email

• Use SNTP for synchronizing (2 second absolute) to UTC time standard

• DHCP/Fixed IP, POP, SMTP, FTP, Modbus-over-TCP

• Part Number ETH1-10T-00

CTE1 – Combine network connectivity and current monitoring

• Combined ETH1 ethernet module and XCT5 current module in one small package

• Smaller footprint – ideal for panel mounting with limited space available

• Part Number CTE1-10T-0.333V-00 for 0.333V nominal rating

• Part Number CTE1-10T-1 V-00 for 1V nominal rating

• Part Number CTE1-10T-5V-00 for 5V nominal rating

• Part Number CTE1-10T-10V-00 for 10V nominal rating

PS1 - Power Supply module

• PS1 Power Supply Module lets your PQube take power from 100V~240V, 50/60

Hz. (Your PQube takes power from 24VAC, 24Vdc - 48Vdc without any optional modules.)

• Snap multiple PS1 modules together for redundant power from different feeders

• Part Number PS1-100~240-00

PS2 - Power Supply module

• PS2 Power Supply Module lets your PQube take power from 100V~240V, 50/60

Hz

• 24VDC output to power external accessories

• Part Number PS2-100~240-00

TH1 – Temperature-Humidity probe

• Monitors ambient temperature and humidity

• Every PQube accepts two electrically-isolated probes

• Use one probe for local ambient temperature-humidity, and put the other on an optional extension cable for monitoring remote conditions

• Temperature accuracy- Typical: ± 0.5ºC

• Humidity accuracy: Typical: ± 4.5%RH (20~80% R.H)

• Part Number TH1-80C-00

ATT1 – DC Voltage Monitoring

• For High Voltage DC monitoring

• Measure 1 differential voltage or 2 voltages relative to earth available

• Part Number ATT1-0600V-00 for 600V nominal rating

• Part Number ATT1-1200V-00 for 1200V nominal rating

ATT2 – DC Power and Energy

• For DC power and energy monitoring

• Measures DC voltage (up to 600V) and current

• Part Number ATT2-0600V-00

PQube front terminals – actual size

Actual

Size

PQube back terminals – actual size

PQube Brochure Version 1.4.0

Abbreviated PQube Specifications Version 1.4.0 -- Full specification available at www.PowerStandards.com

Reference conditions for factory tests: 19~25°C, 15%~50% RH, steady-state 10/12 cycle signals. ±1/2 display count on all accuracies.

Inputs

Mains Voltage Measuring Channels

Connection L1, L2, L3, N PQube screw terminals [9], [11], [13], [15]

Frequency Range

Mains Configuration

40 Hz ~ 70 Hz and 320 Hz ~ 560 Hz. Nominal 50 Hz, 60 Hz, or 400 Hz. Specifications below apply at 50/60 Hz.

Single-phase, delta, wye or star. User selected or auto-selected.

Range of Nominal Input Voltage 100 VAC ~ 690 VAC L-L (69 VAC ~ 400 VAC L-N). User selected or auto-selected.

Measurement Channels Line-to-Neutral, Line-to-Line, Neutral-to-Earth

Sampling Rate

Measurement Range

Accuracy

RMS Measurement Method

HF Impulse Detection

Unbalance – Voltage

256 samples per cycle, phase-locked to input frequency

0 VAC ~ 900 VAC L-L (520 VAC L-N)

±0.05% rdg ±0.05% FS typical (10% ~ 150% of nominal). Factory tested at better than ±0.04% rdg ±0.04% FS.

True single-cycle RMS, phase-locked to each channel, updated every 1/2 cycle. URMS½ per IEC 61000-4-30

Class A. Also 10/12 cycle true-RMS per IEC 61000-4-30 Class A.

L1-E, L2-E, L3-E. ±450 Vpk nominal threshold detected through 2-pole high-pass 4.8 kHz nominal filter.

Measurement method ANSI C84.1. Range: 0.0% ~ 100.0%. Accuracy equivalent to rms voltage specification applied to measurement method.

THD – Voltage

RMS Flicker

Measurement method: DFT of phase-locked 256 samples-per-cycle. Range: 0.0% ~ 100.0%. Accuracy:

±0.2% at 60-Hz test waveform having typical harmonic content (5% 5th, 2.5% 7th, 1.5% 9th, and 1% 11th)

Pinst – average absolute difference between URMS½ and 1-second RMS, in percent of nominal, multiplied by scaling factor for improved compatibility with Incandescent Flicker in IEC 61000-4-15.

Harmonics and Interharmonics Range: 0% ~ 100% of fundamental, measured up to the 63rd order (harmonics displayed up to the 50th order). Harmonic accuracy: IEC 61000-4-7:2002 Class II, typical, up to the 50th order, for units manufactured after February 2010. (Preliminary specification, subject to further evaluation)

Installation Category CAT IV UL/IEC 61010 for voltages up to 300 VAC L-N (equivalent to 480 VAC L-L), CAT III for higher voltages

Analog Input Channels

Nominal Input

Full Scale

Measurement Channels

Accuracy

Digital Input

Rating

Threshold

0 ~ 30 VAC or ±60 VDC to Earth max, input impedance: 800 kΩ to Earth

70 VAC, ±100 VDC

AN1-Earth, AN2-Earth, AN1-AN2

±0.2% rdg ±0.2% FS typical (10% ~ 100% FS) to Earth. Factory tested at better than ±0.1% rdg ±0.1% FS AC

60 VDC to Earth

1.5 V ±0.2 V with respect to PQube's Earth terminal, with 0.3 V hysteresis typical

Optional Current Measuring Modules

CT4-20A-00, CT4-50A-00

Measurement Type Pass-through (built-in current transformers)

Nominal Input 20 amps RMS for CT4-20A, 100 amps RMS for CT4-50A

Crest Factor

Accuracy

3.5 (±70 amps instantaneous for CT4-20A, ±350 amps instantaneous for CT4-100A)

±0.2% rdg ±0.2% FS typical (10% ~ 120% FS). Factory tested at better than ±0.15% rdg ±0.15% FS

XCT4-1A-00, XCT4-5A-00

Measurement Type External current transformer

Nominal Input

Crest Factor

Accuracy - excluding CT's

1 amp RMS for XCT4-1A, 5 amps RMS for XCT4-5A, CT Input Ratio Range 1:1 to 10000:1

3.5 (±3.5 amps instantaneous for XCT4-1A, ±17.5 amps instantaneous for XCT4-5A)

±0.2% rdg ±0.2% FS typical (10% ~ 120% FS). factory tested at better than ±0.15% rdg ±0.15% FS

XCT5-0.333V-00, XCT5-1V-00, XCT5-5V-00, XCT5-10V-00, CTE1

Measurement Type External current transformer

Nominal Input

Crest Factor

Accuracy - excluding CTs

0.333 V RMS, 1 V RMS, 5 V RMS, or 10 V RMS, CT Input Ratio Range 1:1 to 10000:1

3.5 (±1.17 Vpk, ±3.5 Vpk, ±17.5 Vpk, or ±35 Vpk)

±0.2% rdg ±0.2% FS typical (10% ~ 120% FS). Every PQube factory tested at better than ±0.1% rdg ±0.1% FS

Instrument Power

Screw Terminals

AC Input

DC Input

Optional PS1 Plug-in Module

AC Input

Power Required

(AC or DC) PQube POWER screw terminals [23], [31]

24VAC ± 20% 50/60 Hz

24-48VDC ± 20% (polarity independent)

100~240VAC ± 10%. 50/60 Hz

25VA max

Power Measurements

Inputs

Voltages

Currents

L-N, or L-Nm for delta configurations. Nm defined as measurement neutral, the instantaneous average L-E voltage. All voltages scaled up to 10000:1 for potential transformers.

L1, L2, L3, N, E currents. Optional user-selected calculated current on one channel for installations with N-1 current transformers. All voltages scaled up to 10000:1 for current transformers.

Measurement interval Phase-locked, 10-cycles (50 Hz nominal) or 12-cycles (60 Hz nominal). Approximately 5 readings per second.

Accuracy excluding external CTs

Watts (power) ±0.2% typical at unity power factor, nominal voltage, 20% ~ 100% FS current. Better than ±0.25% rdg ±0.25%

FS plus error due to phase angle uncertainty (<1.5° typical) for Θfundamental < ±30°, nominal voltage, 10% ~

120% FS current. Θfundamental = angle between fundamental voltage and fundamental current

Volt-Amps (apparent power) Better than ±0.25% rdg ±0.25% FS typical (10% ~ 120% FS)

Agency Approvals and Listings

UL

RoHS

CE

EMC

UL-recognized, cULus – File Number E220936

Certified – PSL Construction File PQube-001

Certified - PSL Construction File PQube-001, TUV CB Test Certificate US-TUVR-4368-A2

Certified - 20080102-01-CE, 20080326-01-RI

TUV Bauart-mark

ABS Shipyard

Certified – TUV Report 30880881.009

Certified – 2009 Steel Vessels Rules 1-1-4/7.7, 4-8-3/Table 2, 2008 MODU Rules: 43-3-3/Table 1

© 2010 Power Standards Lab Revision 1.4.0

Power Standards Lab ● 2020 Challenger Drive, Ste. 100 ● Alameda ● California ● 94501 ● USA www.PowerStandards.com

TEL ++1-510-522-4400

FAX ++1-510-522-4455