IX Series Data Sheet - La Marche Manufacturing

IX Series Data Sheet - La Marche Manufacturing
IX SERIES
High Frequency / Hot-Swap Inverter Systems
IX Series
This IX Inverter Series offered by La Marche Manufacturing is designed to operate from a 48VDC (40.5-58V
range) input and produce either 120VAC or 230VAC
nominal output at up to 6kVA total capacity. The low
distortion 50 or 60 Hz sine wave is produced using an
advanced DSP controlled architecture which achieves
better than 89% efficiency and 10.5VA per cubic inch
power density.
Fully Equipped 3KVA System with Optional SNMP Module
UNIPOWER Product
The IX Series pre-configured inverter systems include a
Controller, Static Transfer Switch, Power distribution
and Maintenance by-pass facilities. Remote communications to a PC is provided via USB, RS232 or RS485
serial connections. SNMP alarm traps delivered over an
Ethernet TCP/IP connection are also availalbe as an
option.
Inverter Modules
2006/95/EC
Output
Power
Output
Voltage
1500VA @ 0.8PF
1200W @ 1PF
120VAC
60Hz (50Hz)
INV1548-LMC
230VAC
50Hz (60Hz)
INV1548H-LMC
Output
Frequency 1
Model
Number
Notes:
1. The frequency shown in parenthesis can be obtained by reprogramming
the unit from the system controller.
Standard System Configurations
Max. Output
Power
Max. No.
Modules
Output
Voltage 1
Output
Frequency 2
Distribution
Socket Type
Manual
Bypass
Rack
Height
Model
Number
3
3KVA
2.4kW
2
120VAC or 230 VAC
60Hz / 50Hz
8 x IEC60-320
YES
4U
IX4U-1-TS50-D2E-F-LMC
3KVA
2.4kW
2
120VAC or 230 VAC
60Hz / 50Hz
8 x IEC60-320
YES
4U
IX4U-1-TS50-D2E-M-LMC
6KVA
4.8kW
4
120VAC or 230 VAC
60Hz / 50Hz
8 x IEC60-320
YES
5U
IX5U-2-TS50-D2E-F-LMC
6KVA
4.8kW
4
120VAC or 230 VAC
60Hz / 50Hz
8 x IEC60-320
YES
5U
IX5U-2-TS50-D2E-M-LMC
Notes:
1. Inverter modules must be ordered separately based on output voltage and total system capacity required. Module types may not be mixed in the same system.
2. 120VAC inverters are pre-programmed to 60Hz, 230VAC inverters are pre-programmed to 50Hz. These settings can be changed from the front panel of the controller
or remotely using the WIN-power client application.
3. “F” = Front Mounting / “M” = Mid Mounting
Standard Features
.
.
.
.
.
Hot-Swap Inverter, STS and Controller Modules
19 or 23 inch Rack Mounting
1500 to 6000 VA System Capacity
120VAC or 230VAC
40.5 to 58 VDC Input
DSP Management & Control
> 89% Efficiency
2-year Warranty
Low Distortion 50 or 60Hz Pure Sine Wave
Specifications subject to change without notice
P25-DSIX-1
ECN 18471
10/09
.
.
.
.
La Marche Mfg. (A U.S. Company)
106 Bradrock Drive, Des Plaines, IL 60018
Tel: 847.299.1188 Fax: 847.299.3061
[email protected]
www.lamarchemfg.com
SPECIFICATIONS
Typical at 48V Input, Full Load and 25°C Unless Otherwise Noted.
INVERTER MODULES
STATIC TRANSFER SWITCH (STS)
INPUT
INPUT
Voltage Range .............................................................................. 40.5-58VDC
Voltage Range
110/115/120VAC Systems .........................................................89-138VAC
208/220/230/240VAC Systems................................................176-276VAC
Undervoltage Warning Threshold ..........................................................45VDC
Undervoltage Threshold ........................................................................40VDC
Overvoltage Warning Threshold ............................................................58VDC
Overvoltage Threshold ..........................................................................60VDC
Input Current, 48VDC Input ....................................................................28.4A
Input Protection ..........................................Fused Reverse Polarity Protection
Inrush Current ...............................Less than 2x Rated Iin (IEC62040-3-1999)
Isolation
Input to Output .................................Reinforced Pri-Sec, 4242VDC / 1 min.
Input to Ground ........................... 707VDC (Varistor & filter caps removed)
Over / Undervoltage Threshold (adjustable from controller)
110VAC Systems ........................................ 117 to 127VAC / 89 to 105VAC
115VAC Systems ........................................ 122 to 132VAC / 93 to 110VAC
120VAC Systems...................................... 127 to 138VAC / 100 to 114VAC
208VAC Systems......................................220 to 240VAC / 176 to 198VAC
220VAC Systems......................................233 to 252VAC / 176 to 209VAC
230VAC Systems......................................244 to 264VAC / 185 to 218VAC
240VAC Systems......................................254 to 276VAC / 193 to 228VAC
Psophometric Noise Voltage ...................... <1mV ITU-T 0.41 (16.66-6000Hz)
Reflected Psophometrics Noise Current ..........................<1% YD/T 777-2006
OUTPUT
Reflected Relative Band Wide Current ...........<10% YD/T 777-2006 (0-2MHz)
AC Waveform ..................................................................................Sine Wave
Output Voltage ........................................... Same as utility or inverter modules
Permissible Frequency Variation to Synchronise Inverters .................... ±2.5%
Transfer Time ...................................................................... Typically 1/4 cycle
Rated Current ............................................................................................. 50A
Operation Modes (programmable) .................Inverter Priority or Utility Priority
Default Priority .................................................................................... Inverters
Wide Band Noise ......................................................<20mVrms (25Hz-20kHz)
Peak to Peak Noise ..................................................... <150mV up to 100MHz
OUTPUT
AC Waveform ......................................................................... Pure Sine Wave
Output Power ........................................1500VA @ 0.8PF OR 1200W @ 1PF
Power Factor or Load .....................................................................-0.8 to +0.8
Rated Output Voltage ...........................120VAC or 230VAC (see model table)
Output Voltage Variation ..........................................................................<±2%
Output Frequency .......................................... 50Hz or 60Hz (see model table)
Frequency Variation..............................................................................<±0.5%
Crest Factor ........................................................................................ 3:1 max.
THD of Voltage Waveform
Linear Load ..........................................................................................<3%
Non-Linear Load ......... .........................................................................<5%
Capacitive/Inductive Load ....................................................... +0.8 to +0.8 PF
without exceeding permissible distortion for resistive load
CONTROL/STATUS
LED Indicators
Fault (red) .......................................................................... Off OK, On FAIL
Warning (yellow) ............................. Off OK, Flashing for warning condition
Power On (green) ............................................ On OK, Flashing for bypass
Status/Alarm Information .......................................CAN communication failure
back-feed relay open, SCR short, output short, overload
over temperature, mains unavailable, inverter unavailable
output abnormal, fan failure, MBS position error
GENERAL
Efficiency .................................................................................................>89%
ENVIRONMENTAL
Overload Protection ......... Electronic Current Limit at Overload & Short Circuit
1.25 x Rated Current, Temperature Controlled
1.50 x Rated Current for Periods <20 Seconds
Operating Temp. Range
Without Derating ......................................................................-5°C to 50°C
With Derating .........................................................................-20°C to 70°C
Dynamic Response ...............................................................................<±10%
Isolation, Output to Chassis ..........Basic Isolation (Pri-Gnd) 2121 VDC/1 min.
Surge Protection ..........................................................................EN61000-4-5
Telcordia GR-1089 Core ANSI C62.41-IEEE, STD 587-1980
Load Sharing ..................................................................... <5% of Rated Load
Storage Temp. Range...............................................................-40°C to +85°C
Humidity..............................................................0% to 95%, Non-Condensing
Cooling ...............................Variable Speed Internal Fans (Field Replaceable)
Operating Altitude ........................................................1500m without derating
REGULATORY
CONTROL/STATUS
LED Indicators
Inverter Status ............................................................ Green OK, Red FAIL
Overload ..........................................................
..................................... Off OK, Yellow for Overload
Reverse Polarity .................................................
Off OK, Red for Reversed
.
Status/Alarm Information ((via controller) ......................Inverter Fail, Overload,
LVD A
Alarm, Fail Alarm, Thermal Derating, Power Output,
Inputt Voltage, Output Voltage, Output Current, Output
Frequency,
Low Input Voltage Shutoff, Inventory Data.
u
Runtime Info. ...............................
Through Maintenance Feature in Controller
.
Safety
Inverter/PDU/MBS/chassis ............... UL60950-1, EN60950-1, IEC60950-1
STS module .....................................................................................UL1778
EMC (individual modules) ........................................EN300 386:2001 Class B
Acoustic Noise (individual modules) ...................55dB ETS300 753, Class 3.1
Safety Standards
UL60950-1
CSA22.2, No. 60950-1
EN60950-1
3KVA SYSTEM CONFIGURATIONS
Rear views are with safety covers removed to show input and output connection details.
IX4U-1-TS50S-D2E-LMC
Bulk AC Output / 6 x IEC60320-C13 Outlets / 2x IEC60320-C20 Outlets - 120VAC or 230VAC
STS Hot-Swappable using Manual Bypass
Front View (Shown with optional SNMP Module)
Rear View
6KVA SYSTEM CONFIGURATIONS
Rear views are with safety covers removed to show input and output connection details.
IX5U-2-TS50S-D2E-LMC
Bulk AC Output / 6 x IEC60320-C13 Outlets / 2x IEC60320-C20 Outlets - 120VAC or 230VAC
STS Hot-Swappable using Manual Bypass
Front View (Shown with optional SNMP Module)
Rear View
IFC2000 Communications Interface Module
The IX Series Communications Interface Module
provides system connection to a computer via
RS232, RS485 or USB for the purposes of remote
monitoring, control or programming. Remote PC
based software provides a user friendly GUI interface.
An optional SNMP module (integral to the
STS/Controller shelf) provides alarm traps over a
TCP/IP Ethernet interface.
DSC2048 Controller Module
The IX Series Controller, allows the user to monitor real-time system status such as output voltage,
output current, alarm status, and also allows system parameters to quickly be changed with the touch
of a few keys on the front panel. With the Communications Interface Module installed remote access
can be made with a PC over a variety of interfaces.
.
.
.
.
.
.
.
.
.
.
.
Compact design (1RU height)
RS-232
RS-485
SNMP
USB
CAN bus interface embedded
Programmable dry contact
Hot swappable
Realtime clock embedded
LCD and LED indicator
Audible alarm
DPMBS2U Manual Bypass / Distribution Module
The IX Series manual bypass and power distribution module enables the user to manually switch
between inverter output or utility output and to override the STS module for maintenance purposes. A
mechanical interlock between the DPMBS2U and the STS module ensures that AC to the load cannot
be inadvertantly interrupted.
The DPMBS2U provides two means of distributing AC to the load as standard; as a single bulk output
or via eight IEC320 outlet sockets with individual Magnetic Circuit Breakers.
.
.
.
.
.
.
.
50A bypass switch
Enables hot-swap of STS module
50A bulk output on terminal block
AC utility can be isolated via MCB
100A master MCB
6 x IEC320-C13 + 2 x IEC320-C20 outlets (-E)
Individual MCBs for each circuit