AMX | Sensors and Receivers IR | 369242h QS Sensor Module Spec

369242h QS Sensor Module Spec
QS Sensor Module
QSM
Sensor Interfaces
369242i 1 03.27.15
QS Sensor Module
The QS Sensor Module (QSM) is a ceiling-mounted
device that integrates LutronR wireless and wired
sensors and controls through the QS
communication link to Energi Savr NodeTM (ESN)
units, GRAFIK EyeR QS control units, QuantumR
systems and SivoiaR QS shades / draperies.
Features
•Uses Clear ConnectR RF Technology for
communication with Radio Powr SavrTM occupancy
sensors, Radio Powr SavrT daylight sensors, and
PicoR wireless controllers.
•QSM connects to four LutronR wired sensors or
controls—occupancy sensors, daylight sensors,
EcoSystemR infrared (IR) receivers, or EcoSystemR
wallstations. Does not apply to wireless only models.
•Powered by the QS link—no line voltage connections
are required.
•Contact Lutron for compatibility details with the
QuantumR system.
•Compatible with the entire ESN product family:
—A
llows LutronR wired occupancy sensors, daylight
sensors, EcoSystemR wall stations, EcoSystemR
IR receivers, PicoR wireless controllers, Radio
Powr SavrT wireless occupancy sensors and
daylight sensors to control ESN units.
System Example
EcoSystemR
Digital Links
(up to 64 ballasts each)
Wired
Daylight
Sensors
(up to 4) 1,2
•Compatible with GRAFIK EyeR QS control units.
— GRAFIK EyeR QS control unit models starting
with QSGR.
— Allows LutronR wired or Radio Powr SavrT wireless
occupancy sensors and daylight sensors linked to a
QSM to control the GRAFIK EyeR QS control unit.
— Contact Lutron for compatibility with PicoR
wireless controllers, EcoSystemR wallstations, and
EcoSystemR infrared (IR) receivers.
•Compatible with SivoiaR QS shades / draperies.
— Allows PicoR wireless controllers to control SivoiaR
QS shades / draperies (QSM models with wireless
inputs only).
Wired
Occupancy
Sensors
(up to 4) 1
Wired EcoSystemR
Wallstation
or IR receivers
(up to 4) 1
NORTUL
OR
Control Power
120-277 V~
Wireless
Communication
QS link
seeTouchR QS Wallstation
Emergency
Contact
Closure
Input
Programmable
Contact
Closure
Input
®
Job Name:
Job Number:
Radio Powr SavrTM
Occupancy Sensor
(up to 10 per QSM)
Pico® Wireless
Controller (up to
10 per QSM)
QSM
Wired Occupancy
Sensors (up to 4)
Wired EcoSystemR
Wallstation or
IR receivers
(up to 4)
IR Transmitter
NORTUL
Wired Daylight
Sensors (up to 4) 2
OR
Radio Powr SavrT
Daylight Sensor
(up to 10 per QSM)
IR Transmitter
OR
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
OR
Notes:
1 Up to 4 wired inputs total (of any type).
2 Up to 16 wired daylight sensors total
per EcoSystemR link.
Apple, iPhone, and iPod touch are trademarks of
Apple Inc., registered in the U.S. and other countries.
Page
1
QS Sensor Module
QSM
Sensor Interfaces
369242i 2 03.27.15
Models
Frequency / Channel Code*
Number of Wired Inputs
Mounting Method
QSMX-XW-X
Frequency / Channel Code*
2—431.5 - 436.6 MHz
U.S.A., Canada and Mexico
3—868.1 - 869.8 MHz
European Union and United Arab Emirates
4—868.1 - 868.5 MHz
Singapore and China
5—865.5 - 866.5 MHz
India
7—433.0 - 434.7 MHz
Hong Kong
X—No RF
*Contact Lutron for frequency / channel code compatibility with
your particular geographic region if it is not indicated above.
Number of Wired Inputs
4—4
X—None
Mounting Method
C—Ceiling Mount
J—Junction Box Ceiling Mount
Availability/Compatibility
Refer to the chart below to determine QSM model availability and
compatibility with different sensor models.
LutronR Radio Powr SavrT
Models
Available
QSM2-4W-C
QSM2-XW-C
QSM2-4W-J
QSM2-XW-J
Occupancy / Vacancy Sensors
Daylight
Sensors
LRF2-OCRB-P, LRF2-OHLB-P,
LRF2-DCRB
LRF2-OKLB-P, LRF2-OWLB-P,
LRF2-VHLB-P, LRF2-VKLB-P,
LRF2-VWLB-P, LRF2-OCR2B-WH,
LRF2-VCR2B-WH
LutronR PicoR
Wireless Controllers
MRF2-3BRL, MRF2-3B,
MRF2-2BRL, MRF2-2B,
QSR4P-3R,
PJ-2B-Gxx-xxx,
PJ-2BRL-Gxx-xxx
PJ-3B-Gxx-xxx
PJ-3BRL-Gx-xxx
QSM3-4W-C LRF3-OCRB-P
QSM3-XW-C
LRF3-DCRB
QSRKP-2, QSRKP-2R,
QSRKP-3R
QSM4-4W-C LRF4-OCRB-P
QSM4-XW-C
LRF4-DCRB
QSRMP-2, QSRMP-2R,
QSRMP-3R
QSM5-XW-C
LRF5-DCRB
QSRNP-2, QSRNP-2R,
QSRNP-3, QSRNP-3R
QSM7-4W-C LRF7-OCR2B-P
QSM7-XW-C
LRF7-DCRB
QSRQP-2, QSRQP-2R
QSRQP-3, QSRQP-3R
QSMX-4W-C
N/A
N/A
LRF5-OCRB-P
N/A
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
2
QS Sensor Module
QSM
Sensor Interfaces
369242i 3 03.27.15
Specifications
QS Sensor Module (QSM)
Power
•24 V
•Current draw:
max 400 mA (models with wired input)
max 100 mA (models without wired input)
•Power Draw Units: (PDU)
Refer to the QS Link Power Draw Units specification
submittal (LutronR P/N 369405) for information concerning
PDUs on the QS Link. Use only LutronR approved power
sources.
•10-year power failure memory: restores settings and
programming after power interruption.
Regulatory
•LutronR Quality Systems registered to ISO 9001.2008.
Wireless Communication
(models with wireless inputs only)
•RF Range: 60 ft (18 m) line of sight, or 30 ft (9 m)
through typical construction materials.
•To ensure optimal wireless range, install the QSM in
the ceiling in a visible position from inside the space.
•LutronR Radio Powr SavrTM Occupancy sensor
(up to 10)
•LutronR Radio Powr SavrTM daylight sensor (up to 10)
•LutronR PicoR wireless controllers (up to 10)
Wired Inputs
•There are 4 universal wired inputs. Each input can
accept one of the following:
-LutronR EcoSystemR wallstations
QSM2 –
-LutronR occupancy sensors (LOS- series)
•cUL US Listed (USA and Canada).
-LutronR daylight sensors (EC-DIR- series)
-LutronR EcoSystemR infrared (IR) receivers (EC-IR,
•FCC Compliant. Complies with the limits for a Class B
EC-DIR- series)
digital device, persuant to Part 15 of the FCC Rules (USA).
-LutronR Wired PicoR Controls
•IC Certified. (Canada).
•Use of both the infrared receiver and daylight sensor
•SCT Certified (Mexico).
on the EC-DIR- series sensors is considered two
QSM3 –
wired inputs on a QSM
•CE Marked (European Union).
•Maximum wiring distance = 150 ft (46 m)
•TRA Type Approved (United Arab Emirates).
QS Link Limits
QSM5 –
•The QS link can have up to 100 devices.
•WPC Type Approved (India).
•Each QSM counts as 1 device towards the
QSM7 –
100 device limit.
•FCC Compliant. Complies with the limits for a Class B
•Each QSM draws 3 Power Draw Units (PDUs) on
digital device, persuant to Part 15 of the FCC Rules (USA). the QS link.
•Wired sensors add to the PDU draw of a QSM.
Environment
Refer to the QS Link Power Draw Units specification
•Ambient Temperature Operating Range: 32 ºF to 104 ºF
submittal (LutronR P/N 369405) for information
(0 ºC to 40 ºC).
concerning PDUs.
•Relative humidity: less than 90% non-condensing.
•QS link maximum wire run length is 2000 ft (610 m).
•For indoor use only.
Terminals
•Input wiring: 22 AWG to 12 AWG (0.5 mm2 to 4.0 mm2)
•QS link wiring: 22 AWG to 12 AWG (0.5 mm2 to 4.0 mm2)
Mounting
•QSM units should be mounted in the middle of nonmetal ceiling tile or drywall, visible from inside the space.
•Installation near metal other than a Junction Box may
reduce RF range.
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
3
QS Sensor Module
QSM
Sensor Interfaces
369242i 4 03.27.15
Mechanical Dimensions (All Models)
Side View
Front View
Back View
(QSM2-4W-C shown)
4.04 in
(102.67 mm)
1.17 in
(29.82 mm)
Mounted (-C Models)
Ceiling
Mounted (-J Models)
Ceiling
Ceiling thickness range for -C models
Min 0.30 in (7.62 mm)
to
Max1.20 in (30.48 mm)
Ceiling
Ceiling
Use appropriate Mud Ring for ceiling tile thickness
Use Mud Ring with hole
spacing shown below.
(Mud Ring not included with
any QSM models)
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
2.75 in (70 mm)
Page
4
QS Sensor Module
QSM
Sensor Interfaces
369242i 5 03.27.15
Wiring: QS Link and Wired Inputs
1
Red
+20 – 20 V COM – Common
Black
Blue or Gray
S4 – Signal
White
COM – Common
+20 – 20 V Red
QS
Link
S3 – Signal
Red
+20 – 20 V COM – Common
Black
S1 – Signal
S2 – Signal
(QSM2-4W-C shown)
Common
24 V
MUX
MUX
EcoSystemR
infrared (IR) receiver
Back View
White
COM – Common
Red
Input 21,2
+20 – 20 V 22 AWG to 14 AWG
(0.5 mm2 to 2.0 mm2)
Lutron® Cable
Standard: C-CBL-522S-WH-1
Plenum: C-PCBL-522S-CL
Max. Wired Input wire
length 150 ft (46 m)
per input
Occupancy sensor
Black
Input 11,2,3
Yellow
Black
Daylight sensor
Input 31,2
22 AWG to 14 AWG
(0.5 mm2 to 2.0 mm2)
Lutron® Cable
Standard: C-CBL-522S-WH-1
Plenum: C-PCBL-522S-CL
Max. Wired Input wire
length 150 ft (46 m)
per input
Input 41,2
EcoSystemR
wallstation or
PicoR Wired Controls
22 AWG to 14 AWG
(0.5 mm2 to 2.0 mm2)
Max. QS link wire
length 2000 ft (610 m)
1Only on QSM models with wired inputs.
2Note: For reference only. Each input is universal and can accept any of the inputs shown above.
3Only daylight sensor signal connected to QSM shown above. Use of IR signal counts as an
additional input on the QSM.
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
5
QS Sensor Module
QSM
Sensor Interfaces
369242i 6 03.27.15
Wiring: Device Power
Single QSM powered by an ESN unit
ESN unit
ESN unit
QSM
COM
+24 V
MUX
MUX
COM
+24 V
MUX
MUX
QSM
Multiple QSMs powered by an ESN unit and a QS Link Power Supply
Note: A QS Link Power Supply may be necessary if PDUs required by QSMs exceed available PDUs from the
device supplying power.
ESN unit
The ESN unit powers QSM
A; no terminal 2 connection
between QSM A and QS
Link Power Supply
The QS Link Power Supply
powers QSM B and C;
QS Link
Power Supply
QSM C
COM
+24 V
MUX
MUX
MUX
MUX
COM
COM
+24 V
MUX
MUX
QSM A
QSM B
MUX and _ occupy
terminals 2 and 3 on the
QS Link Power Supply.
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
6
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising