Datasheet | Main System 28 Eco Technical data

Add to my manuals
56 Pages

advertisement

Datasheet | Main System 28 Eco Technical data | Manualzz
Installation & Service Instructions
System Eco Elite
Range
These instructions include the Benchmark Commissioning Checklist
and should be left with the user for safe keeping.
© Baxi Heating UK Ltd 2014
Natural Gas
Building Regulations and the Benchmark Commissioning
Checklist
Main System 24 Eco Elite
G.C.No 41 467 21
Main System 28 Eco Elite
G.C.No 41 467 22
Building Regulations (England & Wales) require notification of
the installation of a heating appliance to the relevant Local
Authority Building Control Department. From 1 April 2005 this
can be achieved via a Competent Persons Self Certification
Scheme as an option to notifying the Local Authority directly.
Similar arrangements will follow for Scotland and will apply in
Northern Ireland from 1 January 2006.
The Health & Safety Executive operates the ‘Gas Safe Register’,
a self-certification scheme for gas heating appliances.
These arrangements represent a change from the situation
whereby compliance with Building Regulations was accepted as
being demonstrated by completion of the Benchmark Logbook
(which was then left on site with the customer).
With the introduction of Self Certification Schemes, the
Benchmark Logbook is being withdrawn. However, a similar
document in the form of a commissioning checklist and service
interval record is incorporated at the back of these instructions.
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The
purpose is to ensure that customers are provided with the correct equipment for
their needs, that it is installed, commissioned and serviced in accordance with the
manufacturer’s instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The Benchmark Checklist
can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work
in accordance with the Benchmark Code of Practice which is available from the
Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
© Baxi Heating UK Ltd 2014 All rights reserved. No part of this publication may
be reproduced or transmitted in any form or by any means, or stored in any
retrieval system of any nature (including in any database), in each case whether
electronic, mechanical, recording or otherwise, without the prior written
permission of the copyright owner, except for permitted fair dealing under
Copyrights, Designs and Patents Act 1988.
This company is a member of the Benchmark initiative and fully
supports the aims of the programme. Its aim is to improve the
standards of installation and commissioning of central heating
systems in the UK and to encourage the regular servicing of all
central heating systems to ensure safety and efficiency.
Building Regulations require that installations should comply
with manufacturer's instructions. It is therefore important that
the commissioning checklist is completed by the installer. The
relevant section of Building Regulations only relates to
dwellings. Therefore the checklist only applies if the appliance is
being installed in a dwelling or some related structure.
The flowchart opposite gives guidance for installers on the
process necessary to ensure compliance with Building
Regulations.
Applications for the copyright owner’s permission to reproduce or make other
use of any part of this publication should be made, giving details of the proposed
use, to the following address:
The Company Secretary, Baxi Heating UK Limited,
Brooks House, Coventry Road, Warwick. CV34 4LL
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a
copyright work may be liable to criminal prosecution and civil claims for damages.
0086
ISO 9001
FM 00866
2
© Baxi Heating UK Ltd 2014
Installer Notification Guidelines
Choose Building
Regulations Notification
Route
Competent Person's
Self Certification Scheme
Building Control
Install and Commission this
appliance to manufacturer's
instructions
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact
a government approved
inspector
Complete the
Benchmark Checklist
If you notify via the ‘Gas Safe
Register’, the register will issue
the Building Regulations
certificate on members’ behalf
Install and Commission this
appliance to manufacturer's
instructions
Scheme Members only
Call ‘Gas Safe Register’ on:
0800 408 5577
or log onto:
www.gassaferegister.co.uk
within 10 days
Complete the
Benchmark Checklist
You must ensure that the
certificate number issued by
the ‘Gas Safe Register’ is written
onto the Benchmark Checklist
‘Gas Safe Register’ will issue a
Building Regulations Compliance
Certificate to the property owner
and inform the relevant LABC
© Baxi Heating UK Ltd 2014
LABC will record the data
and will issue a
certificate of compliance
3
Legislation
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and
the regulations in force. Read the instructions fully before installing or using the
appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety
(Installation & Use) Regulations.
Definition of competence: A person who works for a Gas Safe registered company
and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and
Use) Regulations.
Warning - Check the information on the data plate is compatible with local supply
conditions.
All Gas Safe registered engineers carry an ID card with their licence number and a
photograph. You can check your engineer is registered by telephoning
0800 408 5500 or online at www.gassaferegister.co.uk
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels:Type test for purpose of Regulation 5 certified by:
Notified Body 0087.
Product/Production certified by:
Notified Body 0086.
For GB/IE only.
This company declare that no substances harmful to health
are contained in the appliance or used during appliance
manufacture.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force, and
only used in a suitably ventilated location.
In GB, the installation must be carried out by a Gas Safe
Registered Installer. It must be carried out in accordance with
the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in
Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
Person and installed in accordance with the current edition of
I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
Codes of Practice - refer to the most recent version
In GB the following Codes of Practice apply:
Standard
Scope
BS 6891
Gas Installation.
BS 5546
Installation of hot water supplies for domestic
purposes.
BS EN 12828
Heating systems in buildings.
BS EN 14336
Installation & commissioning of water based
heating systems.
BS 6798
Installation of gas fired hot water boilers.
BS 5440 Part 1
Flues.
BS 5440 Part 2
Ventilation.
BS 7074
Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593
Treatment of water in domestic hot water
central heating systems.
In IE the following Codes of Practice apply:
Standard
Scope
I.S. 813
Domestic Gas Installations.
The following standards give valuable additional information;
BS 5546
Installation of hot water supplies for domestic
purposes.
BS EN 12828
Heating systems in buildings.
BS EN 14336
Installation & commissioning of water based
heating systems.
BS 7074
Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593
Treatment of water in domestic hot water
central heating systems.
4
© Baxi Heating UK Ltd 2014
Safe Manual Handling
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.
Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Do not handle or lift unless you feel physically able.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care
on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the
‘Installation’ section of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
© Baxi Heating UK Ltd 2014
5
CONTENTS
Section
6
© Baxi Heating UK Ltd 2014
Page
1.0
Introduction
7
2.0
General Layout
8
3.0
Appliance Operation
9
4.0
Technical Data
10
5.0
Dimensions and Fixings
11
6.0
System Details
12
7.0
Site Requirements
14
8.0
Flue Options
19
9.0
Plume Displacement
24
10.0
Installation
28
11.0
Commissioning
32
12.0
Completion
35
13.0
Servicing
36
14.0
Changing Components
38
15.0
Setting the Gas Valve
46
16.0
Electrical
47
17.0
Short Parts List
48
18.0
Fault Finding
49
Benchmark Checklist
54
1.0 Introduction
1.1
Case Front Panel
Description
1. The Main System Eco Elite is a fully automatic gas fired wall
mounted condensing system boiler. It is room sealed and fan
assisted.
2. The boiler is set to give a maximum output of :24 models 28 models -
25.94 kW
26.95 kW (Condensing)
28.63 kW
30.20 kW (Condensing)
3. It is designed for use on Natural Gas (G20).
4. The boiler incorporates a circulating pump and expansion
vessel. It is suitable for use only on fully pumped sealed systems.
5. The boiler data badge gives details of the model, serial
number and Gas Council number and is situated on the front
sloping face of the hydraulic plate. It is visible when the case
front panel is removed and the control box hinged down
(Fig. 1 & 1a).
6. The boiler model name and serial number are also shown on
the information label on the back of the facia door. This is for
user reference.
Control Box
7. The boiler is intended to be installed in residential / domestic
environments on a governed meter supply only.
Facia Door
Fig. 1
Information Label
8. The boiler must be installed with one of the purpose
designed flues such as the standard horizontal flue kit, part no.
5118489.
9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.1).
1.2
Contents of Pack
1. Boiler Unit
2. Wall Plate (inc. taps)
3. Set of Pipes (inc. nuts)
4. Template
5. Literature Pack
Data Badge
Fig. 1a
© Baxi Heating UK Ltd 2014
7
13
15
2.0 General Layout
23
2.1
1
22
14
21
16
Layout
1.
Expansion Vessel
2.
Automatic Air Vent
3.
Primary Return Temperature Sensor
4.
Circulation Pump
5.
Drain Off Point
6.
Pressure Relief Valve
7.
Selector Switch
8.
Central Heating System Pressure Gauge
9.
PCB
10.
Control Box
11.
Gas Valve
12.
Condensate Trap
13.
Heat Exchanger Air Vent
20
14.
Electrode Assembly
7
15.
Primary Heat Exchanger
16.
Fan Assembly
17.
On/Off/Reset Selector Switch
18.
Central Heating Temperature Control
19.
Calibration Control
20.
Water Pressure Sensor
21.
Gas/Air Inlet
22.
Burner Mounting Panel
23.
Igniter
24.
Burner On Light
25.
Central Heating Mode Light
26.
Calibration Mode Light
27.
Display
10
9
8
12
3
2
11
4
5
25
26
6
2
Reset
1
3
4
0
bar
17
8
© Baxi Heating UK Ltd 2014
27
24
18
19
8
3.0 Appliance Operation
Boiler Primary Circuit
1
3.1
Operating Mode (Fig. 2)
1. With a demand for heating or hot water, the pump
circulates water through the primary circuit. If the pressure is
at least 0.5 bar and the ignition sequence will start.
2. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the burner
relights automatically (anti-cycling). The pump continues to
run during this period.
2
20
18
3
4
19
5
7
6
IMPORTANT: When the selector switch is in the ‘0’
(Off) position the electrical supply to the boiler is
isolated. The boiler will not operate.
17
16
3. When the demand is satisfied the burner is extinguished
and the pump continues to run for a period of 3 minutes
(Pump Overrun).
13
3.2
15
8
14
11
Key
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Frost Protection Mode
9
10
12
Fig. 2
Heat Exchanger
Burner
Ignition Electrode
Flame Sensing Electrode
Gas Valve
Pump
Automatic Air Vent
Pressure Relief Valve
Boiler Drain Point
Gas Inlet
Boiler Flow
Boiler Return
Pressure Gauge
Automatic By-Pass
Water Pressure Sensor
Safety Thermostat
Temperature Sensor
Expansion Vessel
Return Temperature Sensor
Fan
© Baxi Heating UK Ltd 2014
1. The frost protection mode is integral to the appliance and
functions when the selector switch (see Section 2.1) is in the
ON position (
). If the system temperature falls below
5° C then the boiler will fire on its minimum setting until a
flow temperature of 30° C is reached. Further protection
can be incorporated by using a system frost thermostat.
3.3
Pump Protection
1. With the selector switch (see Section 2.1) in the ON
position (
) the pump will automatically operate for 1
minute in every 24 hours to prevent sticking.
9
4.0 Technical Data
4.1
Appliance Type
C13
Appliance Category
C33
C53
CAT I 2H
Heat Input CH (Net)
Max
Min
24 model
kW
26.06
7.82
28 model
kW
29.32
8.8
Heat Input CH (Gross)
Max
Min
24 model
kW
28.92
8.68
28 model
kW
32.54
9.77
Heat Output CH (Non-Condensing)
Max
Min
24 model
kW
25.94
7.61
28 model
kW
28.63
8.56
Min
24 model
kW
26.95
8.37
28 model
kW
30.20
9.42
Max Gas Rate
(Natural Gas - G20)
(After 10 mins)
24 model
3
m /h
2.76
28 model
m3/h
3.10
NOx Class
Inlet Pressure (Natural Gas - G20)
mbar
20
Electrical Supply
230V~ 50Hz
(Appliance must be connected to an
earthed supply)
Pump
Available Head
Power Consumption
150W
3A
Internal Fuse Rating
F2L
Condensate Drain
To accept 21.5mm (3/4 in) plastic waste pipe
Diameter
Projection
Connections
Gas Supply
Central Heating Flow
Central Heating Return
Pressure Relief Discharge
-
100mm
125mm
copper tails
22mm
22mm
22mm
15mm
Outercase Dimensions
Casing Height
Overall Height Inc Flue Elbow
Casing Width
Casing Depth
Clearances
Above Casing
Below Casing
Front
Front
L.H. Side
R.H. Side
-
Max Capacity of
CH System
(18,24)
litre
125
(27)
litre
155
Primary Water Content
of Boiler (unpressurised)
2.5
2.8
Temperatures
C.H. Flow Temp (adjustable)
25°C to 80°C max (± 5°C)
780mm
965mm
450mm
345mm
SEDBUK Declaration
SAP 2005 Seasonal Efficiency for 24 models
is 91.1%
SAP 2005 Seasonal Efficiency for 28 models
is 90.2%
200 mm Min
300 mm Min (80/125mm flue)
200 mm Min
450 mm Min (For Servicing)
5 mm Min (In Operation)
5 mm Min
5 mm Min (In Operation)
Weights
Packaged Boiler Carton
Installation Lift Weight
See graph below
Expansion Vessel
- (For Central Heating only.
Integral with appliance)
bar
Min Pre-charge Pressure 0.5
IPX0D (with timer)
IPX4D (without timer)
External Fuse Rating
bar
3
2.5
0.5
1-2
Safety Discharge
Max Operating
Min Operating
Recommended Operating Range
6.0mm (24 & 28 models)
Flue Terminal
Dimensions
5
Central Heating Primary Circuit
Pressures
Injector (Natural Gas - G20)
Electrical Protection
Heat Output CH (Condensing)
Max
System 24 & 28 Eco Elite
This value is used in the UK Government’s Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0087.
51.1 kg (24 &28)
44.5 kg (24 & 28)
Pump - Available Head (24,27)
5.5
5
4.5
NOTE: All data in this section are nominal values
and subject to normal production tolerances.
4
3.5
Metre (wg)
3
2.5
2
1.5
1
0.5
0
0
10
200
400
600
Flow Rate (l/h)
© Baxi Heating UK Ltd 2014
800
1000
1200
1400
5.0 Dimensions and Fixings
Dimensions
A 780mm
At Least 1.5°
F
B 345mm
C 450mm
D 116mm Ø Min.
A
E 145mm
F 132mm
210mm (80/125)
G 225mm
B
360° Orientation
G
D
C
G
Tube Ø 100mm
E
Tap Rail
127 mm
Condensate
Drain
130 mm
Heating
Flow
(22mm)
© Baxi Heating UK Ltd 2014
130 mm
Gas
Inlet
(22mm)
65 mm
Heating
Return
(22mm)
Pressure Relief
Valve
(15mm)
11
6.0 System Details
6.1
Central Heating Circuit
1. The appliance is suitable for fully pumped SEALED SYSTEMS
ONLY.
Treatment of Water Circulating Systems
• All recirculatory water systems will be subject to corrosion
unless an appropriate water treatment is applied. This means
that the efficiency of the system will deteriorate as corrosion
sludge accumulates within the system, risking damage to
pump and valves, boiler noise and circulation problems.
• When fitting new systems flux will be evident within the
system, which can lead to damage of system components.
• All systems must be thoroughly drained and flushed out
using, for example, Sentinel X300 or X400 or Fernox F3.
They should be used following the flushing agent
manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing
agents/descalers should comply to BS7593 requirements, e.g.
Sentinel X100 and Fernox MB-1 which should be used
following the inhibitor manufacturer’s instructions.
• Full instructions are supplied with the products, for further
information contact Sentinel (0800 389 4670) or Fernox
(0870 870 0362)
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
• It is important to check the inhibitor concentration after
installation, system modification and at every service in
accordance with the manufacturer’s instructions. (Test kits are
available from inhibitor stockists.)
• For information or advice regarding any of the above
contact Technical Enquiries.
6.2
Bypass
1. The boiler is fitted with an automatic integral bypass.
6.3
System Control
1. For optimum operating conditions, the heating system into
which the boiler is installed should include a control system.
2. Such a system will comprise of a timer control and separate
room or cylinder thermostats as appropriate.
3. The boiler should be controlled so that it operates on
demand only.
4. Operation of the system under control of the boiler
thermostat & TRV’s only does not produce the best results.
12
© Baxi Heating UK Ltd 2014
6.0 System Details
6.5
Stop
Valve
DHW
Mains
Inlet
Fig. 6
Double
Check
Valve
Temporary
Hose
System Filling and Pressurising (Fig. 6)
1. A filling point connection on the central heating return
pipework must be provided to facilitate initial filling and
pressurising and also any subsequent water loss
replacement/refilling.
Stop
Valve
CH
Return
2. The filling method adopted must be in accordance with all
relevant water supply regulations and use approved
equipment.
3. Your attention is drawn to:
for GB: Guidance G24.2 and recommendation R24.2 of the
Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
4. The sealed primary circuits may be filled or replenished by
means of a temporary connection between the circuit and a
supply pipe, provided a ‘Listed’ double check valve or some
other no less effective backflow prevention device is
permanently connected at the inlet to the circuit and the
temporary connection is removed after use.
6.6
Expansion Vessel (Central Heating only)
1. The appliance expansion vessel is pre-charged to 0.5 bar.
Therefore, the minimum cold fill pressure is 0.5 bar. The
vessel is suitable for correct operation for system capacities up
to 125 litres (18, 24) 155 litres (27). For greater system
capacities an additional expansion vessel must be fitted. For
GB refer to BS 7074 Pt 1. For IE, the current edition of I.S.
813 “Domestic Gas Installations”.
6.7
Safety Pressure Relief Valve (Fig. 7)
1. The pressure relief valve is set at 3 bar, therefore all
pipework, fittings, etc. should be suitable for pressures in
excess of 3 bar and temperature in excess of 100°C.
2. The pressure relief discharge pipe should be not less than
15mm dia, run continuously downward, and discharge outside
the building, preferably over a drain. It should be routed in
such a manner that no hazard occurs to occupants or causes
damage to wiring or electrical components. The end of the
pipe should terminate facing down and towards the wall.
3. The discharge must not be above a window, entrance or
other public access. Consideration must be given to the
possibility that boiling water/steam could discharge from the
pipe.
Fig. 7
Pressure Relief Valve
Discharge Pipe
© Baxi Heating UK Ltd 2014
13
7.0 Site Requirements
450mm
5mm Min
5mm Min
7.1
200mm Min
(300mm Min if
using 80/125mm
flueing system)
Location
1. The boiler may be fitted to any suitable wall with the flue
passing through an outside wall or roof and discharging to
atmosphere in a position permitting satisfactory removal of
combustion products and providing an adequate air supply.
The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse. (The boiler may be fitted inside a cupboard-see
Section 7.3).
2. If the boiler is sited in an unheated enclosure then it is
recommended to leave the ON/OFF Selector Switch in the
domestic hot water and central heating position to give frost
protection.
780mm
3. If the boiler is fitted in a room containing a bath or shower
reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and Building
Regulations.
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI rules.
200mm Min
Fig. 8
4. If the boiler is to be fitted into a building of timber frame
construction then reference must be made to the current
edition of Institute of Gas Engineers Publication IGE/UP/7
(Gas Installations in Timber Framed Housing).
7.2
At Least 1.5°
Clearances (Figs. 8 & 9)
1. A flat vertical area is required for the installation of the
boiler.
2. These dimensions include the necessary clearances around
the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler.
450mm Min
For Servicing
Purposes
5mm Min
In Operation
Fig. 9
14
© Baxi Heating UK Ltd 2014
7.0 Site Requirement
Gas Service Cock
7.3
Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances
installed in compartments. The appliance will run sufficiently
cool without ventilation.
7.4
Gas Supply
1. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
Fig. 10
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock (Fig. 10).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a
smaller diameter than the boiler gas connection (22mm).
Zone 2
Window
Recess
7.5
Zone 1
Electrical Supply
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference should
be made to the current edition of ETCI rules.
Zone 2
Zone 0
0.6 m
2. The mains supply is 230V ~ 50Hz fused at 3A.
Window
Recess
NOTE: The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance.
Zone 2
Fig. 11
Connection may be via a fused double-pole isolator
with a contact separation of at least 3mm in all poles
and servicing the boiler and system controls only.
In GB Only
Ceiling
Window Recess
Zone 2
Outside Zones
3. When the system includes an indirect domestic hot
water cylinder it is recommended that a cylinder
thermostat is used in conjunction with a 3 port 2 position
valve or 2 port zone valve.
7.6
Zone 1
Zone 2
2.25 m
Zone 0
0.6 m
Fig. 12
© Baxi Heating UK Ltd 2014
In GB Only
Bath & Shower Rooms
1. If the boiler is fitted in a room containing a bath or
shower and NOT FITTED with any optional integral timer
or thermostat, it can be fitted in zone 2, (Figs. 11 & 12
show zone dimensions for a bathtub. For other examples
refer to the Current I.E.E. Wiring Regulations) reference
must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI
rules.
15
Examples are shown of the following methods of termination:i) to an internal soil & vent pipe
ii) via an internal discharge branch (e.g. sink waste) downstream of the trap
iii) to a drain or gully
iv) to a purpose made soakaway
v) pumped into an internal discharge branch (e.g. sink waste) downstream of the trap
vi) pumped into an external soil & vent pipe
vii) to a drain or gully with extended external run & trace heating
It is strongly recommended to discharge internally into the household
drainage system. If connecting to a rain water drain, that drain MUST
discharge into a foul drain.
Insulation
32mm
21.5mm
i) Termination to an internal soil and
vent pipe
50mm
2.5° M
per me
tre of
inimum
n
fall
*450mm is applicable to properties
up to 3 storeys.
For multi-storey building installations
consult BS 6798.
Boiler
ii) External termination via internal discharge branch
e.g sink waste - downstream*
50mm
per me
tre of
2.5° M
inimum
pipe ru
n
fall
7.7
Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER.
CAREFUL CONSIDERATION MUST BE GIVEN TO THE
POSSIBILITY OF THE PIPEWORK BEING SUBJECT TO
FREEZING CONDITIONS AND APPROPRIATE
MEASURES TAKEN TO PREVENT BLOCKAGE.
CORRECT INSTALLATION IN ACCORDANCE WITH
THIS SECTION WILL CONSIDERABLY MINIMISE THE
LIKELIHOOD OF BLOCKAGE AND SUBSEQUENT
BOILER LOCK-OUT.
A CONDENSATE DISCHARGE PUMP AND PIPE ‘TRACE
HEATING’ ARE AVAILABLE AS ACCESSORIES - see
paragraphs 7.7.12 to 7.7.15 for further details.
The condensate discharge pipe MUST NOT RISE at any
point along its length. There MUST be a fall of AT LEAST
2.5° (50mm per metre) along the entire run EXCEPT when
employing a suitable condensate pump in basement and
cellar or similar applications.
pipe ru
450mm min*
Sink
7.0 Site Requirements
Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°
*It is NOT RECOMMENDED
to connect upstream of the
sink or other waste water
receptacle !
The boiler condensate trap incorporates a seal of 75mm,
therefore it is unnecessary to install an air break and trap in
the discharge pipework.
1. The condensate outlet will accept 21.5mm (3/4in) plastic
overflow pipe. It is strongly recommended that this discharges
internally into the household drainage system.
Where this is not possible, discharge into an outside drain is
permissible providing every possible precaution is taken to
prevent freezing.
2. Ensure the discharge of condensate complies with any
national or local regulations in force. BS 6798 & Part H1 of the
Building Regulations give further detailed guidance.
3. The discharge pipe should be run in a proprietary drain pipe
material e.g. PVC, PVC-U, ABS, PVC-C or PP.
4. Metal pipework is NOT suitable for use in condensate
discharge systems.
Boiler
iii) Termination to a drain or gully
50mm
per me
tre of
2.5° M
inimum
pipe ru
n
Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°
5. The pipe should be a minimum of 21.5mm diameter and
must be supported using suitably spaced clips of the correct
design to prevent sagging.
6. It is advisable that the full length of condensate pipe is run
internally and preferably be less than 3 metres.
fall
7. Internal runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
8. External runs MUST be a MINIMUM of 32mm and fully
insulated with material suitable for external use.
iv) Termination to a purpose made soakaway
Further specific requirements for soakaway
design are referred to in BS 6798.
Boiler
500mm min
50mm p
er metr
e of pip
2.5° Min
imum fa
e run
ll
Holes in the soak-away must
face away from the building
9. If the boiler is fitted in an unheated location the entire
condensate discharge pipe should be treated as an external run
and sized and insulated accordingly.
10. In all cases discharge pipe must be installed to aid disposal of
the condensate. To reduce the risk of condensate being
trapped, as few bends and fittings as possible should be used
and any burrs on cut pipe removed.
11. When discharging condensate into a soil stack or waste pipe
the effects of existing plumbing must be considered. If soil pipes
or waste pipes are subjected to internal pressure fluctuations
when WC's are flushed or sinks emptied then back-pressure
may force water out of the boiler trap and cause appliance
lockout.
16
© Baxi Heating UK Ltd 2014
v) pumped into an internal discharge branch
(e.g. sink waste) downstream of the trap
Sink
50mm
7.0 Site Requirement
per me
tre of p
ipe run
2.5° M
inimum
fall
Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°
7.7
Condensate Drain (cont.)
12. A boiler discharge pump is available, ‘MULTIFIT’
part no. 720648301. This pump will dispose of both
condensate & high temperature water from the relief valve.
It has a maximum head of 5 metres. Follow the instructions
supplied with the pump.
13. Condensate Drain Pipe ‘Trace Heating’ Elements are
available in various lengths. ‘MULTIFIT’ part nos.:-
Basement or similar
(heated)
1 metre 720644401
2 metre 720664101
3 metre 720664201
5 metre 720664401*
Boiler
*Where the drain is between 3 & 5 metres a 5 metre kit can
be used and “doubled back” upon itself.
14. It is possible to fit the element externally on the
condensate drain or internally as detailed in the instructions
provided.
Condensate Pump
15. The fitting of a ‘Trace Heating’ Element is NOT a
substitute for correct installation of the condensate drain.
ALL requirements in this section must still be adhered to.
vi) pumped into an external soil & vent pipe
50mm
Unheated Location
(e.g. Garage)
per me
tre of p
ipe run
2.5° M
inimum
fall
Basement or similar
(heated)
vii) to a drain or gully with extended
external run & trace heating
Boiler
The ‘Trace Heating’ element
must be installed in accordance
with the instructions supplied.
External runs & those in
unheated locations still require
insulation.
Boiler
Condensate Pump
50mm
per me
tre of
2.5° M
inimum
© Baxi Heating UK Ltd 2014
pipe ru
n
fall
Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°
17
Terminal Position with Minimum Distance (Fig. 18)
(mm)
7.0 Site Requirements
A1 Directly below an opening, air brick, opening
windows, etc.
B1 Above an opening, air brick, opening window etc.
C1 Horizontally to an opening, air brick, opening window etc.
D2 Below gutters, soil pipes or drain pipes.
E2 Below eaves.
F2 Below balconies or car port roof.
G2 From a vertical drain pipe or soil pipe.
H2 From an internal or external corner.
I
Above ground, roof or balcony level.
J
From a surface or boundary line facing a terminal.
K From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
L From an opening in carport (e.g. door, window)
into the dwelling.
M Vertically from a terminal on the same wall.
N Horizontally from a terminal on the same wall.
R From adjacent wall to flue (vertical only).
S From an adjacent opening window (vertical only).
T Adjacent to windows or openings on pitched and flat roofs
U Below windows or openings on pitched roofs
300
300
300
25 (75)
25 (200)
25 (200)
25 (150)
25 (300)
300
600
1200
600
7.8
NOTE: Due to the nature of the boiler a plume of water
vapour will be discharged from the flue. This should be
taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements
for siting balanced flue terminals. For GB recommendations
are given in BS 5440 Pt 1. For IE recommendations are given
in the current edition of I.S. 813 “Domestic Gas
Installations”.
1200
1500
300
300
1000
600
2000
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance
and that the terminal will not obstruct the passageway.
1 In addition, the terminal should be no nearer than 150 mm to an opening in the
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access,
then a suitable terminal guard must be provided.
building fabric formed for the purpose of accommodating a built-in element such as
a window frame.
2 Only ONE 25mm clearance is allowed per installation. If one of the dimensions
*4. Reduction to the boundary is possible down to 25mm
but flue deflector part no. 5111068 must be used.
D, E, F, G or H is 25mm then the remainder MUST be as shown in brackets, in
accordance with B.S.5440-1.
NOTE: The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than 300mm in
accordance with the diagram below
300 min
Terminal
Assembly
Flue (Figs. 17 & 18)
IMPORTANT:
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
*
Plume
Displacement Kit
IMPORTANT: If fitting a Plume
Displacement Flue Kit, the air inlet
must be a minimum of 150mm from
any opening windows or doors (see
Section 9.0).
Top View Rear Flue
Fig. 17
Property Boundary Line
T
J,K
Air Inlet
U
Opening Window
or Door
150mm
MIN.
N
R
I
M
C
I
I
F
D
E
A
S
I
F
J,K
B
L
A
A
G
H
H
I
Likely flue positions requiring
a flue terminal guard
18
© Baxi Heating UK Ltd 2014
Fig. 18
Fig. 18a
8.0 Flue Options
8.1
Horizontal Flue Systems
1. The standard flue is suitable only for horizontal termination
(ii) applications.
2. Maximum permissible equivalent flue lengths are:(i)
Horizontal Concentric
(60/100)
10 metres
(80/125)
20 metres
3. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:Concentric Pipes:
135° bend
0.5 metres
93° bend
1.0 metres
Horizontal
Flues
Twin Flue Pipe
135° bend
91.5° bend
0.25 metres
0.50 metres
The elbow supplied with the standard horizontal telescopic
flue kit is not included in any equivalent length calculations
Plume Displacement Kit 60 /100 Ø
1M Extensions, 45° & 93° elbows
are also available - see Section 9.0
NOTE: Flue length is measured from point (i) to (ii) as
shown.
IMPORTANT: All flue systems must be securely supported
at least once every metre. Suitable pipe supports are
available as accessories.
NOTE: Horizontal flue pipes should always be installed with at least a 1.5° fall
from the terminal to allow condensate to run back to the boiler.
This bend is equivalent to
1 metre
C
A
(ii)
B
(i)
This bend is equivalent to
1 metre
Total equivalent length =
A+B+C+2x90°Bends
© Baxi Heating UK Ltd 2014
19
Vertical
Flues
(Twin Pipe)
8.0 Flue Options
300mm Min
Apart
8.2
Twin & Vertical Flue Systems
1. Maximum permissible equivalent flue lengths are:-
Vertical Concentric
1m Min
(ii)
to
20m Max
Twin Pipe
(60/100)
10 metres
(80/80)
20 metres
(80/125)
20 metres
(i)
3. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:Concentric Pipes:
135° bend
0.5 metres
93° bend
1.0 metres
Twin Flue Pipe
Vertical
Flues
135° bend
91.5° bend
0.25 metres
0.50 metres
The elbow supplied with the standard horizontal telescopic
flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point (i) to (ii) as
shown.
(ii)
IMPORTANT: All flue systems must be securely
supported at least once every metre.
Suitable pipe supports are available as accessories.
(i)
Total Equivalent Length =
A+B+C+1x90°Bend
Roof
Terminal
All vertical and angled runs must be included,
measured from the boiler adaptor point (i) to the
joint with the flue terminal point (ii). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.
If further elbows are required the flue length must
be reduced by the following amounts:-
The total equivalent length for this example is
= 6.5 metres.
(ii)
1 metre for each 91.5° bend
0.5 metre for each 135° bend
C
Equivalent
Length Value
B
This bend is equivalent to
1 metre
1m extension
135°bend
91.5°bend
1m
0.25m
0.5m
AIR DUCT
No of
fittings/pipes
5
2
2
Sub total
5.0m
0.5m
1.0m
Equivalent Length Air Duct = 6.5m
A
(i)
Equivalent
Length Value
1m extension
135°bend
91.5°bend
1m
0.25m
0.5m
FLUE DUCT
No of
fittings/pipes
5
2
2
Sub total
5.0m
0.5m
1.0m
Equivalent Length Flue Duct = 6.5m
20
© Baxi Heating UK Ltd 2014
8.0 Flue Options
8.3
Flue Accessories
A4
A2
Key Accessory
Size
Code No
FLUE GROUP A
Concentric Flue System 100mm diameter
A3
Telescopic Internal Flue Kit
315-500mm 5119654
A2
Telescopic Flue (incl elbow)
5118069
A
Horizontal Flue Terminal (incl elbow)
5118489
B
Flue Extension
1000mm 5111074
C
Flue Bend
93°
5111075
D
Flue Bend (pair)
135°
5111085
U
Pipe Support (painted)
100mmØ 5111080
P
Wall Liner
5111067
S
Flue Terminal Deflector
5111068
A
P
E
A3
B
K,K1
R
D
C
G
F
M
H
U,W
FLUE GROUP N
Twin Flue System 80mm diameter
E
Flue Extension (pair)
1000mm
F
Flue Bend (pair)
90°
G
Flue Bend (2 pair)
135°
J
Vertical Flue Boiler Adaptor Kit
H
Vertical Flue Adaptor
Y
Flue Horizontal Terminal Kit
W
Pipe Support (pair)
80mm
5111087
5111072
5111086
720089801
5111084
5120172
5111081
FLUE GROUP G
Flue System 80/125mm diameter
A4
Horizontal Flue Kit
B
Straight Extension Kit
D
Bend Kit (pair)
C
Bend
R
Vertical Flue Adaptor
5118580
5118584
5118597
5118588
5111070
1000mm
135°
91.5°
FLUE GROUP A, N, G
Vertical Flue Kits
K
Vertical Flue Terminal (use with Group G)
K1
Vertical Flue Terminal (use with Group A)
L
Pitch Roof Flashing
M
Roof Cover Plate
N
Flat Roof Flashing
5111078
5118576
5122151
246143
246144
Y
L
N
S
J
© Baxi Heating UK Ltd 2014
21
8.0 Flue Options
8.4
Air Duct Connection
Twin Flue Duct Adaptor
1. The kit allows connection of a twin flue system to the
boiler adaptor.
Flue Duct Connection
8.5
Twin Flue Connection
1. Engage the twin flue duct adaptor in the boiler adaptor,
making sure that it is pushed down as far as possible.
2. Ensure that the air & flue ducts are connected correctly
and that they are adequately supported (at least once every
metre using the available pipe supports).
3. Ensure that all joints and elbows are fully engaged and
cannot become disconnected during operation.
22
© Baxi Heating UK Ltd 2014
8.0 Flue Options
8.6
1. In the case of a pitched roof 25 - 50 degrees, position the lead
tile to replace/flash over existing roof tiling. Make an aperture in
the roof suitable for the lower tube of the roof terminal and
ensure the integrity of the roof cover is maintained. The
adjustable plastic collar can either be positioned on the lead tile
or the lower tube of the roof terminal prior to the final
positioning of the vertical flue through the tile. Check the collar is
correctly located to suit required roof pitch (either 25° to 38° or
37° to 50°). From inside the roof adjust the flue to a vertical
position and secure to the roof structure with the clamp supplied.
Approx
1425mm
Cut the same
amount off the
Air Duct &
Flue Duct
For Roof Terminals
2. For flat roof installations the aluminium flashing must be
incorporated into the roof covering and the appropriate aperture
made in the roof decking. The vertical flue is lowered onto the
flashing making sure the collar of the flue locates securely with the
flashing. (A mastic seal may be necessary). From inside the roof,
adjust the flue to a vertical position and secure to the roof
structure with the clamp supplied.
Air Duct
Flue Duct
IMPORTANT: If the boiler is not fitted immediately after the flue
system, temporary precautions must be taken to prevent rain
entry into the room of installation. Any precautionary measures
must be removed prior to commissioning the boiler.
Flue Extension
8.7
Flue Dimensions
The standard horizontal flue kit allows for lengths between
100mm and 685mm from elbow to terminal (Fig. 19).
m
The maximum permissible equivalent flue length is:
10 metres (60/100 system)
20 metres (80/125 system)
5m
68
m
0m
10
8.8
Flue Deflector
Flue Trim
1. The rubber flue trim supplied may be fitted to either the
outside wall or on the inner wall of installation.
Fig. 19
8.9
Terminal Guard (Fig. 20)
1. When codes of practice dictate the use of terminal guards, they
can be obtained from most Plumbers’ and Builders’ Merchants.
Fig. 21
2. There must be a clearance of at least 50mm between any part
of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name
and model number.
4. The flue terminal guard should be positioned centrally over the
terminal and fixed as illustrated.
8.10
Fig. 20
© Baxi Heating UK Ltd 2014
Flue Deflector (Fig. 21)
1. Push the flue deflector over the terminal end. It may point
upwards as shown, or up to 45° either way from vertical. Secure
the deflector to the terminal with screws provided.
23
93° Elbow/Plume
Outlet Assembly
9.0 Plume Displacement
60Ø Support
Bracket
O Ring
9.1
Kit No 5118638
Content of kit
1 0.9m 60/100 Concentric Flue
1 1m 60 Dia Exhaust Flue Pipe
1 Adaptor
2 60 Dia Support Brackets
1 93° Elbow/Plume Outlet Assembly
1 Flexible Flue Trim
3 “O” Rings
1 ‘Jubilee Clip
1 Elbow
0.9 metres
60Ø Exhaust
Flue Pipe
60Ø Support
Bracket
O Ring
Fig. 22
Plume Displacement Kit (Fig. 23)
Flexible Flue
Trim
1. This kit is recommended for installations where the
condensate plume emitted from the flue may cause a nuisance
or affect the surroundings.
Adaptor
‘Jubilee’ Clip
O Ring
2. The terminal must be positioned outside the building with
the air inlet facing downward and outlet connection upwards.
Elbow
60/100Ø
Concentric Flue
45°
45°
Outlet must be at
least 45° from
wall face
3. The plume outlet must always be at least 45° to the wall,
with the ‘peak’ uppermost to prevent rain entry (Figs. 24 &
25), and be at least 2 metres above ground level. It must be
secured as shown in Fig. 18a. The plume outlet must also be
at least 500mm from the air inlet in any direction (Fig. 25).
Fig. 23
‘Peak’ Uppermost
NOTE: The outlet must be positioned so that any
condensate plume is directed away from adjacent surfaces.
There must be a constant fall along the entire length of the
flue system from the outlet back to the boiler.
4. It is possible to reduce or increase (with the addition of
extensions) the length of either or both the 60/100 concentric
and 60Ø exhaust.
5. Standard concentric flue extension kits may be added
between the boiler elbow and the terminal assembly.
6. The minimum length of the concentric flue is 100mm when
measured from the edge of the flue elbow.
500mm Min.
IMPORTANT: The maximum equivalent length of
concentric flue is:- 8 metres
Additional bends may be fitted in the concentric flue, but
the equivalent length must be reduced by 1 metre (93°
elbow) or 0.5 metres (45° elbow).
Fig. 24
Air Inlet at Bottom
Fig. 25
7. 60Ø 1 metre extensions (including support bracket), and
additional 93° & 45° elbows are available. Any additional 93°
& 45° elbows must be accounted for when calculating flue
lengths.
NOTE: Permitted positions of the plume outlet relative to
doors, windows etc. are the same as for conventional
concentric flues as detailed in the main Installation &
Servicing Instructions and BS5440 Pt. 1. It is NOT
necessary to fit a terminal guard over the air inlet or the
plume outlet.
24
© Baxi Heating UK Ltd 2014
16
16
14
14
60 Ø Exhaust (metres) X
60 Ø Exhaust (metres) X
9.0 Plume Displacement
12
10
24
8
6
4
28
9.2
12
10
In the graph the solid line diagonal represents the
relationship between the concentric flue assembly (and any
extensions) and the 60Ø exhaust (and any extensions or
additional bends).
24
8
6
4
2
28
2
0
0
0
1
2
3
4
5
6
7
8
9
0
1
Concentric 60/100 Flue (metres) Y
2
3
4
5
6
7
8
9
Concentric 60/100 Flue (metres) Y
Example 1
Flue Lengths - Not Permissible
Example 2
Flue Lengths - OK
60 Ø Exhaust (metres) X
14
12
24
8
6
4
28
2
0
0
1
2
3
4
5
6
Example 1 - Not Permissible
If, for instance, a concentric length of 5 metres was required
and the 60Ø exhaust needed to be 12 metres the graph
shows that this combination would NOT be permissible as
the intersection point would be above the solid diagonal line.
Example 2 - Flue Lengths OK
Where both lengths have been determined they can be
applied to the graph to check that the installation is
permissible. For example, if it was known that 2 metres of
concentric flue and 4 metres of 60Ø exhaust were required,
the values could be applied to the graph as shown in
Example 2. As the point of intersection of the dotted lines is
below the solid diagonal line, the combination of lengths is
shown to be acceptable.
16
10
Determining Permissible Lengths
7
8
9
Concentric 60/100 Flue (metres) Y
Example 3
Flue Lengths - OK
Support
Bracket
60Ø Exhaust
X
Example 3 - Flue Lengths OK
In the example shown, assume that the concentric part of
the flue needs to be 2.3 metres long. Find the position of
‘2.3’ on the horizontal axis of the graph and then project
upwards to the solid diagonal line. This is represented by the
vertical thick dotted line. Where this dotted line intersects
with the solid diagonal line on the graph, project across to
the vertical axis. As can be seen this corresponds with 6
metres. Therefore, the total equivalent length of the 60Ø
exhaust can be up to 6 metres. Any elbow equivalencies
must be accounted for i.e. 93° elbows are equal to 1 metre,
each 45° elbow to 0.5 metres.
45° Elbow
Y
Flue Length - Worked Example
Main System 28 Eco Elite
93° Elbow
1 metre Extension
Concentric 60/100 Flue
1 metre supplied in kit
Fig. 26
Concentric Flue
Additional Accessories
93° Elbow
45° Elbow (Pair)
1 metre 60Ø Extension
© Baxi Heating UK Ltd 2014
5121639
5121370
5121638
Fig. 27
In Fig. 27 opposite an additional 93° elbow and pair of 45°
elbows have been included in the 60Ø exhaust.
Also 3 straight extension pieces have been used.
To calculate total length:Length of 60Ø supplied in kit =
3 x 1 metre Extensions =
1 x 93° Elbow =
2 x 45° Elbow =
1 metre
3 metres
1 metre
1 metre (0.5 metres each)
Total 60Ø =
6 metres
After consulting the table in Example 3 it can be determined
that the concentric flue could be up to approximately 2.3
metres long.
25
9.0 Plume Displacement
9.3
General Fitting Notes
1. Cut a hole in the external wall which the concentric flue
assembly will pass through. The hole should allow the flue
to fall back to the boiler at an angle of at least 1.5°.
2. When completed the terminal must be at least 2 metres
above ground level (Fig. 28).
Min. 2 metres
3. Measure and cut to size the concentric assembly and any
extensions that are being used.
4. Insert the concentric assembly through the hole from
outside the building.
5. If required, the flexible flue trim should be fitted prior to
this as it cannot be fitted after. Use the large ‘Jubilee’ clip to
secure the trim to the flue (See Fig. 29, trim shown
dotted), with the screw part of the clip at the bottom.
Fig. 28
6. Connect any extensions or elbows that are being used
to the concentric assembly. Engage the extension, elbow
or concentric assembly in the boiler flue elbow. Fit the
boiler flue elbow to the boiler adaptor.
Flue Trim
7. Ensure that the concentric assembly and any extensions
fall back to the boiler at an angle of at least 1.5° and that
the external air inlet is to the bottom.
8. Use suitable brackets to support the concentric
assembly and any extensions, and make good inside and
outside.
Spigot
Position of ‘Jubilee’ Clip
screw
Fig. 29
9. The 60Ø exhaust can now be fitted. Slide the adaptor
over the plain end of the 60Ø exhaust (Fig. 31) and engage
the exhaust in the terminal. Slide the adaptor down over
the spigot. Mark and drill the adaptor, using a 2mm bit, as
shown in Fig. 30. Secure the adaptor to the spigot using
one of the screws supplied.
50mm
Adaptor
10. If it is necessary to shorten the 60Ø exhaust or any of
the extensions, the excess material must be cut from the
plain end of the pipe.
Fig. 31
30mm
Fig. 30
11. Determine the position of the 60Ø exhaust and mark
on the wall a suitable position for the support bracket. If
extensions are being used, a support bracket is supplied in
each kit.
12. Drill the wall, and fit the bracket(s) using the plug and
screw provided.
30mm
13. Mark and drill the 60Ø exhaust, using a 2mm bit, as
shown in Fig. 32. Complete the installation of the 60Ø
exhaust, securing in the brackets.
Fig. 32
Fig. 33
26
© Baxi Heating UK Ltd 2014
14. Fit the 93° elbow/plume outlet and secure with the
two remaining screws supplied. Ensure the plume outlet is
at least 45° to the wall and that the ‘peak’ is uppermost
(Fig. 33).
9.0 Plume Displacement
Plume Outlet
Elbow
9.3
General Fitting Notes (cont.)
15. For aesthetic purposes it is permissible to route the
60Ø exhaust in an enclosed box, but the air inlet and
plume outlet MUST remain in free air.
16. It is also possible to separate the plume outlet from the
93° elbow to allow the flue to be installed as shown in
Fig. 34.
50
0m
m
Mi
n.
17. To do this, first slacken the two screws retaining the
plume outlet to the elbow, and remove the outlet (Fig. 35).
The elbow can now be used to connect the vertical to
horizontal 60Ø exhaust (Fig. 34). Retighten the screws in
the elbow.
Fig. 34
18. The outlet can now be fitted into the female end of an
60Ø extension piece. It must be secured using two of the
screws supplied in the bag with the ‘Jubilee’ clip.
19. Mark the female end of the extension at 30mm as
shown in two positions, directly opposite each other
(Fig. 36).
Fig. 35
30mm
20. Using a suitable bit (e.g. 2mm), drill through the
extension and outlet. Secure using two of the screws
supplied.
21. The remaining screw must be used to secure the
adaptor to the concentric terminal.
Fig. 36
22. When the plume outlet is positioned under a balcony
or other projection (Fig. 37) it must protrude at least
200mm (it is not necessary to extend it further than this).
200mm Min.
23. When under balconies or projections it is permissible to
rotate the concentric flue length up to 70°, clockwise or
anti-clockwise (Fig. 38), if there is insufficient space to
connect vertically.
24.This will allow the connection of the exhaust to the
outlet spigot.
25. All other minimum & maximum dimensions must be
adhered to, and the air inlet positioned such that it will not
be subject to rain entry.
Fig. 37
70°
Concentric Flue Length
(shown end-on)
Outlet Spigot
© Baxi Heating UK Ltd 2014
Fig. 38
27
10.0 Installation
10.1
Unpacking & Initial Preparation
The gas supply, gas type and pressure must be checked for
suitability before connection (see Section 7.4).
1. Remove staples, open flaps and remove cardboard sheet.
Remove the polystyrene side pieces and literature. Two
people can then lift out the boiler (Fig. 39).
Fig. 39 Unpacking Procedure
2. After considering the site requirements
(see Section 7.0) position the fixing template on the wall
ensuring it is level both horizontally and vertically.
3. Mark the position of the two most suitable fixing slots for
the wall plate and boiler lower fixing holes. It is preferable to
use the vertical fixing slots.
145mm
4. Mark the position of the centre of the flue hole (rear
exit). For side flue exit, mark as shown (Fig. 40).
5. If required, mark the position of the gas and water pipes.
Remove the template.
Fig. 40
6. Cut the hole for the flue (minimum diameter 116mm).
For Side Flue Exit
7. Drill the wall as previously marked to accept the wall
plugs supplied. Secure the wall plate using the fixing screws.
Flushing Tube
8. Using a spirit level ensure that the plate is level before
finally tightening the screws.
Wall Plate
99. Connect the gas and water pipes to the valves on the
wall plate using the copper tails supplied. Ensure that the
sealing washers are fitted between the connections.
10.2
Flushing
1. Connect a tube to the central heating flow or return pipe
(Fig. 41).
Central Heating Return
2. Flush thoroughly (see System Details, Section 6.1).
Fig. 41
10.3
Wall Plate
Fitting The Boiler
1. Lift the boiler using the Lifting Points as shown by the
shaded areas (Fig. 43). The boiler should be lifted by TWO
PEOPLE. Engage the slots at the top rear of the boiler on
the wall plate (Fig. 42) (see Safe Manual Handling page 5).
2. Ease the boiler forwards and remove the sealing caps
from the boiler connections (Fig 43).
NOTE: A small amount of water may drain from the
boiler once the caps are removed.
Remove Sealing Caps
from under the Boiler
Suggested Lifting Points
shown as shaded area
28
© Baxi Heating UK Ltd 2014
Fig. 43
3. Insert the sealing washers between the valves and pipes
on the wall plate and the boiler connections.
4. Tighten all the connections.
10.0 Installation
Pressure Relief Valve
10.4
Fitting the Pressure Relief Discharge Pipe
(Fig. 44)
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the vicinity
of the boiler. Make up as much of the pipework as is
practical, including the discharge pipe supplied.
3. The pipework must be at least 15mm diameter and run
continuously downwards to a discharge point outside the
building. See section 6.7 for further details.
Fig. 44
Discharge Pipe
4. Utilising one of the sealing washers, connect the discharge
pipe to the adaptor and tighten the nut.
5. Complete the discharge pipework and route it to the
outside discharge point.
m
5m
68
Wall Thickness
Fig. 45
IMPORTANT: Make all soldered joints before connecting
to the pressure relief valve.
m
0m
10
10.5
Condensate Drain (see Section 7.7)
(X)
1. Connect the condensate drain to the trap outlet pipe.
Flue Elbow
Apply Lubricant for
ease of assembly.
Adaptor
Ensure Elbow is fully
engaged into Boiler
Adaptor
Ensure the discharge of condensate complies with any
national or local regulations in force (see British Gas
“Guidance Notes for the Installation of Domestic Gas
Condensing Boilers”.
2. The connection will accept 21.5mm (3/4in) plastic overflow
pipe which should generally discharge internally into the
household drainage system. If this is not possible, discharge
into an outside drain is acceptable.
10.6
Fitting The Flue
HORIZONTAL FLUE
1. The standard flue is suitable for lengths between 100mm
minimum and 685mm maximum, as measured from the edge
of the flue elbow outlet to the joint between the terminal
and air duct (Fig. 45).
2. Locate the flue elbow on the adaptor at the top of the
boiler. Set the elbow to the required orientation (Fig. 47).
Fig. 47
NOTE: The flue elbow is angled at 93 degrees to ensure
a fall back to the boiler.
(X)
Wall Thickness
3. Measure the distance from the outside wall face to the
elbow. This dimension will be known as ‘X’ (Fig. 48).
Fig. 48
Waste
4. To dimension ‘X’ add 50mm. This dimension to be known
as ‘Y’.
Y
IMPORTANT: Check all dimensions before cutting.
5. Mark dimension ‘Y’ on the flue as shown (Fig. 49).
Carefully cut the waste material from the flue, ensuring that
the ducts are square and free from burrs.
Flue
© Baxi Heating UK Ltd 2014
Fig. 49
29
10.0 Installation
Centralising Collar
10.6
Fitting the Flue (Cont)
6. The centralising collar may be in the waste portion of the
flue. In this case retrieve the bracket before discarding the
waste.
Fig. 50
7. Take the centralising collar (if not already fitted) and
engage it over the flue duct. This will centralise the flue and
air ducts, and ease assembly (Fig. 51).
Apply Lubricant for
ease of assembly.
Ensure Flue is fully
engaged into Flue
Elbow
8. Insert the flue through the hole in the wall. Fit the elbow
to the boiler adaptor, ensuring that it is pushed fully in.
9. Draw the flue back through the wall and engage it in the
elbow. It may be necessary to use soap solution or similar
to ease assembly of the elbow adaptor and flue (Fig. 51).
10. Ensure that the terminal is positioned with the slots to
the bottom (Fig. 52).
IMPORTANT: It is essential that the flue terminal is fitted
as shown to ensure correct boiler operation and prevent
water entering the flue.
11. Make good between the wall and air duct outside the
building.
Slots at bottom
Fig. 52
12. Fit the flue trim if required, and if necessary fit a terminal
guard (see Section 8.8 & 8.9).
CONCENTRIC VERTICAL FLUE
Fig. 51
13. Once the length of the vertical concentric extension has
been determined mark and carefully cut off the excess
material. The cut end MUST be square and free of burrs to
ensure correct insertion into the boiler adaptor.
14. Measure 25mm from the end of the flue extension and
apply a length of tape around the outer duct (Fig. 53).
25mm
15. Engage the extension into the adaptor up to this
position (Fig. 54). Once the installation of the flue is
complete and all support brackets are securely in place
remove the tape.
Extension
Fig. 53
Tape
Cut End
Adaptor
Apply Lubricant for
ease of assembly.
Ensure Extension is
fully engaged into
Boiler Adaptor
Fig. 54
30
© Baxi Heating UK Ltd 2014
10.0 Installation
10.7
Making The Electrical Connections
NOTE: Both the Live and Neutral connections are fused.
To connect an external control proceed as follows:1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of the
facia. Remove the panel.
2. Completely undo the screws securing the facia panel and
hinge it down (Fig. 55).
Cable Clamp
Fig. 56
3. Undo the terminal block cover securing screw and
remove the cover (Fig. 55).
Terminal Block Cover
4. Slacken the unused cable clamp on the LH side of the
boiler chassis (Fig. 56). Insert the external control wiring
through the clamp and route it to the terminal block.
Fig. 55
5. Refer to the instructions supplied with the control.
Facia Panel
IMPORTANT: The room thermostat MUST be suitable
for 230V switching.
6. Remove the link between terminals 1 & 2. The switched
output from the external control must be connected to
terminal 1 (Fig. 57).
Always fit fast
blow 2A fuse
Fused supply 3A
230V ~ 50Hz
230V
1
bk
2
bk
Earth (green/yellow)
g/y
Neutral (blue)
b
Live (brown)
br
7. Ensure that the external control input cable(s) have
sufficient slack to allow the control box to drop down.
Tighten the cable clamp on the boiler chassis.
8. Replace the terminal block cover, routing the external
control input cable(s) through the second cut-out.
10.8
Preliminary Electrical Checks
1. Prior to commissioning the boiler preliminary electrical
system checks should be carried out.
Terminal Block
Fig. 57
© Baxi Heating UK Ltd 2014
Fuses
2. These should be performed using a suitable meter, and
include checks for Earth Continuity,
Resistance to Earth, Short Circuit and Polarity.
31
Heat Exchanger
Automatic Air Vent
11.0 Commissioning
Fig. 58
11.1
Commissioning the Boiler
1. Reference should be made to BS:EN 12828 & 14336 when
commissioning the boiler.
2. At the time of commissioning, complete all relevant sections of
the Benchmark Checklist at the rear of this publications.
3. Open the mains water supply to the boiler.
Screw
IMPORTANT: The heat exchanger air vent on top of the
boiler (Fig. 58) MUST be opened before filling the primary
system.
4. Open all hot water taps to purge the DHW system.
Pump
Automatic Air
Vent
5. Ensure that the filling loop is connected and open, then open
the heating flow and return valves on the boiler.
6. Open the screw on the automatic air vent on the pump body
(Fig. 59).
7. The system must be flushed in accordance with BS 7593 (see
Section 6.2) and the flushing agent manufacturers instructions.
8. Pressurise the system to 1.5 bar (Fig. 60) then close and
disconnect the filling loop.
Pump
Fig. 59
9. Turn the gas supply on and purge according to in GB BS 6891
and in IE I.S. 813 “Domestic Gas Installations”.
2
1
3
10. Test for gas tightness.
4
0
bar
11. Hinge the facia panel upwards and refit the case front panel.
Tighten the securing screws.
Selector Switch
Display
Pressure Gauge
Fig. 60
2
Reset
1
3
4
0
bar
Central Heating
Temperature Control
Fig. 61
Calibration
Control
12. Having checked:
• That the boiler has been installed in accordance with these
instructions.
• The integrity of the flue system and the flue seals.
• The integrity of the boiler combustion circuit and the
relevant seals.
Proceed to put the boiler into operation as follows:
13. The Combustion Check procedure as shown by the chart in
11.2 is mandatory. The method of setting the boiler to operate
at maximum and minimum rates to comply with the procedure
is described below.
14. Ensure that all external controls are calling for heat. The actual
current boiler temperature is shown on the display.
15. Turn both control knobs fully anticlockwise, then quickly turn
the right hand knob 1/4 clockwise twice and back fully
anticlockwise.
16. The display will now alternate between ‘SF’ and the current
boiler temperature and both green LEDs will flash.
17. To set to maximum rate.
Turn the left hand knob fully clockwise. As the knob is turned the
display will change, indicating the fan speed.
18. The display will show ‘00’, indicating maximum rate, then
revert to ‘P ‘ alternating with the current boiler temperature.
19. To set to minimum rate.
Turn the left hand knob fully anti-clockwise. As the knob is turned
the display will change, indicating the fan speed. When the display
reads ‘ 0’ the boiler runs at minimum rate.
32
© Baxi Heating UK Ltd 2014
20. This function is maintained for 20 minutes unless the
maximum CH temperature is exceeded. The function can be
disabled at any time by turning the right hand knob.
Set Boiler to Maximum Rate
(see 11.1.17)
Allow the combustion to
stabilise. Do not insert probe to
avoid ‘flooding’ the analyser.
11.0 Commissioning
11.2
Checking Combustion
1. Follow the flow chart opposite.
Verify Flue Integrity
Indication that products of
combustion & inlet 

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement